THERMODYNAMIC ANALYSIS OF SUPERCRITICAL RANKINE...
-
Upload
nguyenlien -
Category
Documents
-
view
217 -
download
0
Transcript of THERMODYNAMIC ANALYSIS OF SUPERCRITICAL RANKINE...
54
CHAPTER 4
THERMODYNAMIC ANALYSIS OFSUPERCRITICAL RANKINE CYCLE
The computer program which was developed by the present investigation
as presented in Chapter 3 has been used to find different steam
properties at different operating conditions of pressure and temperature
and thermodynamic analysis of the cycle has been presented in this
chapter. In section 1.2, the basic cycle of operation of steam power plant
based on the Rankine cycle has been presented. To carryout
thermodynamic analysis of this cycle the assumptions and range of
variable parameters are given below.
4.1 ASSUMPTIONS MADE IN THE ANALYSIS
i. Capacity of the power plant = 1000 MW
ii. The isentropic efficiency of the steam turbine is 90%.
iii. The pump efficiency is assumed to be 85%.
iv. Cooling water temperature inlet to the condenser Twi=250C
v. Terminal Temperature Difference (TTD) = 50C
vi. Heat and pressure losses in the transport pipe in between the
different units of the cycle are negligible.
55
4.2 RANGE OF VARIABLE PARAMETERS
The important variables which affect significantly the performance of the
Rankine cycle (energy and exergy efficiency) have been identified and
listed below. As the literature survey revealed that significant amount of
research work has been reported as thermal power plants operating on
Rankine cycle in subcritical range of operating parameters. Hence, the
present investigation has selected the following range of operating
parameters to contribute to the analysis of Rankine cycle in
supercritical/ultra supercritical/advanced ultra supercritical ranges.
i. Steam turbine inlet temperature = 5000C to 8000C
ii. Steam turbine inlet pressure =170bar to 425bar
iii. Optimum reheat pressure ratio
iv. Condenser pressure Pc= 0.03 bar - 0.1bar
v. Temperature of flue gas at the entry of boiler = 9000C -14000C
vi. Temperature of flue gas at the exit of boiler = 800C -3000C.
The above assumptions and range of variable parameters given in
sections 4.1 and 4.2 are used for the analysis of mentioned thermodynamic
cycles in the chapter 4, chapter 5, chapter 6 and chapter 7 respectively.
56
4.3 FLOWCHART FOR THE ENERGY AND EXERGY ANALYSIS OFSUPERCRITICAL RANKINE CYCLE
Fig. 4.1 Flow diagram of finding energy and exergy analysis of SupercriticalRankine cycle
57
4.4 ENERGY EFFICIENCY OF SUPERCRITICAL RANKINE CYCLE
It may be recalled that, the energy efficiency of the cycle is defined as the
ratio of network done to the heat supplied in the boiler of the steam
power cycle,
From the figure 1.1, Energy efficiency = Wnet / H.S (4.1)
Where Wnet = Wturbine - Wpump kJ/kg (4.2)
The work done by the turbine per kg of steam supplied,
Wturbine = h1 – h2 kJ/kg (4.3)
Boiler feed pump required work per kg of steam supplied,
Wpump =h4 – h3 kJ/kg
(4.4)
Heat supplied to water/steam in the boiler per kg of steam produced is
H.S = h1– h4 kJ/kg (4.5)
4.5 EXERGY EFFICIENCY OF SUPERCRITICAL RANKINE CYCLE
The method of exergy analysis aims at the quantitative evaluation of the
exergy losses (irreversibilities) associated with a system. Hence, it is
required to calculate the irreversibility in all the components of the power
cycle for the estimation of exergy efficiency.
The irreversibility or exergy loss in each of the components is calculated
for the specified dead state (P0, T0).
58
The anthracite coal whose chemical composition has been taken from
Kotas [5], as given below, is considered for thermodynamic analysis of all
cycles of the present investigation. The heat content of this fuel is 28,940
kJ/kg.
CO2 H2O N2 O2 SO2 Total
nk[kmol/kgfuel] 6.51 1.634 35.32 9.324 0.047 57.735
xk 0.1234 0.0310 0.6679 0.1768 0.0009 1.000
Further, the equations used for the calculation of enthalpy, exergy, mean
isobaric heat capacity and mean molar isobaric exergy capacity of the
anthracite coal have been taken from Kotas [5] and are reproduced
below.
The enthalpy values are calculated using the equations (4.6 and 4.7)
k
hpkkAA cnh ~0 kJ/kg of fuel (4.6)
k
hphkBB cnh ~0 kJ/kg of fuel (4.7)
where A is the flue gas inlet temperature(0C),
B is the flue gas outlet temperature(0C)
0 is the ambient temperature (0C)
The exergy of the flue gas entry and exit of the boiler is
k
pkkAA cnE ~0 kJ (4.8)
59
k
pkkBB cnE ~0 kJ (4.9)
Mean isobaric heat capacity for evaluating enthalpy changes is
T
Tp
hp dTc
TTTThhc
000
0 1 (4.10)
Mean molar isobaric exergy capacity for evaluating changes in
physical exergy is
T
T
T
T
pp
T
p TdTc
TdTcTTTT
c0 0
000
1 (4.11)
4.5.1 ESTIMATION OF IRREVERSIBILITY OR EXERGY LOSS INDIFFERENT COMPONENT OF THE CYCLE
4.5.1.1 Boiler:
The mass flow rate of steam (ms) required to be generated in the boiler to
produce an output of 1000MW power can be obtained from the energy
balance as given below: ms(Wnet) = 1000 MW
ms= 1000x1000 kW/ Wnet kg/s (4.12)
Using this, the mass of the flue gas (mg) required to obtain the
required mass flow rate of steam can be found by the energy balance
equation i.e., Heat gained by the steam = Heat lost by the flue gas
ms(h1 –h4)= mg (hA – hB)
mg = ms(h1 –h4)/(hA – hB) kg/s (4.13)
Exergy or Availability at state point 1
60
E1 = ms (h1-To s1) kW (4.14)
Exergy or Availability at state point 4
E4 = ms (h4-To s4) kW (4.15)
Irreversibility in the boiler is
Iboiler =(EA-EB)– (E1 – E4)
Substituting the E1, E4 from equation 4.14 and equation 4.15
Iboiler = mg(EA-EB) – ms((h1 – h4) – T0(s1 – s4)) kW (4.16)
4.5.1.2 Steam Turbine:The irreversibility in the steam turbine can be calculated by Gouy-
Stodola equation as given below
Iturbine=T0.ms (s2-s1) kW (4.17)
4.5.1.3 Condenser:Mass flow rate of cooling water circulated to condense ms, kg/s, of steam
is obtained from the energy balance is
mcw Cpw (Twi-Two )= ms (h2-h3)
mcw= ms(h2-h3)/ Cpw (Twi-Two ) (4.18)
Irreversibility in the condenser,
Icondenser= ms(s2-s3)- T0(mcwCpwln(Two/Twi) kW (4.19)
4.5.1.4 Pump:
Irreversibility in the boiler feed pump,
Ipump=ms T0(s4-s3) kW (4.20)
61
4.5.1.5 Exhaust:Irreversibility of the exhaust, Iexhaust = EB (4.21)
4.5.1.6 Total Irreversibility:
Total Irreversibility is
I =(Iboiler + Iturbine + Ipump + Icondenser + Iexhaust) kW (4.22)
4.5.1.7 Exergy Efficiency:
Exergy efficiency is defined as the ratio of exergy output to the exergy
input. Exergy output depends on the degree of Irreversibility of the cycle.
Exergy efficiency = 100*A
A
EIE (4. 23)
4.6 FRACTIONAL EXERGY LOSS
The definition of the fractional exergy loss of the component is the ratio
of irreversibility of the individual component to the total irreversibility of
the cycle. Its value is estimated for all the components of the cycle. It
gives the information regarding the loss of useful energy in all
components for different operating variables. The Fractional exergy loss
formulas of each component are as follows.
Fractional exergy loss in the boiler is,
100* IIboiler (4.24)
Fractional exergy loss in the turbine is,
100* II turbine . (4.25).
62
Fractional exergy loss in the condenser is,
100* IIcondenser (4.26)
Fractional exergy loss in the Pump is,
100* II pump (4.27)
Fractional exergy loss in the exhaust is,
100* IIexhaust (4.28)
4.7 PARAMETRIC EFFECT ON THE PERFORMANCE OFSUPERCRITICAL POWER CYCLE
In the sections of 4.1 to 4.6 the fundamental aspects related to
supercritical power cycle regarding its functioning, energy and exergy
analysis was discussed. Based on this, the effect of different variables on
the performance of the cycle is analyzed in detail in the subsequent
sections.
4.7.1 Effect of turbine inlet temperature and pressure on energyefficiency
Figure 4.2 represents the variation of energy efficiency against the
steam turbine inlet temperature at the various turbine inlet
pressures of the steam.
It may observed from the figure that, the energy efficiency increases
with an increase of turbine inlet temperature at a given turbine inlet
pressure. A similar trend in the variation of energy efficiency can be
noted at subcritical pressures of 170 bar, 200 bar and at
63
supercritical pressures of 225 bar, 250 bar etc., turbine inlet
pressures of the steam.
36
38
40
42
44
46
500 550 600 650 700 750 800Turbine inlet temperature (
0C)
En
ergy
Effi
cien
cy(%
)
170 200 225250 275 300325 350 375400 425
Fig. 4.2 Variation of energy efficiency with turbine inlet temperature of steam
At the turbine inlet pressure increases the energy efficiency increases at
a particular turbine inlet temperature. It may be noted from a figure that,
the energy efficiency increases from 37.66% to 45.66% to as the turbine
inlet pressure increases from 170bar to 425bar. Energy efficiency at
turbine inlet pressure of 425bar and at different turbine inlet
Pc=0.05bar
P1,(bar)
64
temperatures of 6000C/6500C/7000C/7500C/8000C are
41.12%/42.17%/43.37%/44.53%/ 45.66%, respectively.
Table 4.1 shows the network done by the turbine, heat supplied and
energy efficiency at different turbine inlet pressures at a given turbine
inlet temperature of 7000C. From the table, it may be inferred that, net
work output from the turbine reduces with increase in turbine inlet
pressure due to significant increase in the pump work and insignificant
variation in the turbine work.
Table 4.1 Energy efficiency at different turbine inlet pressures
P1bar
T1(0C)
Wt(kJ/kg)
Wp(kJ/kg)
Wnet(kJ/kg)
H.S.(kJ/kg)
EnergyEfficiency
(%)225 700 1563.07 26.60 1536.48 3608.455 42.58250 700 1565.65 29.55 1536.10 3594.057 42.74300 700 1567.08 35.46 1531.62 3562.736 42.99350 700 1564.82 41.38 1523.45 3528.138 43.18400 700 1559.91 47.29 1512.62 3491.736 43.32425 700 1556.68 50.24 1506.44 3473.461 43.37
Further, it may be noticed from the Table 4.1 that, the energy input
(Heat Supplied) to the boiler decreases as the turbine inlet pressure
increases. So, as the turbine inlet pressure increases both the Wnet and
heat supplied decreases. But the rate of decrease of heat supplied is
more than the rate of decrease of Wnet. Hence, the energy efficiency
increases as the pressure increases at a given turbine inlet temperature.
In order to appreciate, the effect of the turbine inlet pressure on the
performance of the plant, the same data has been represented in Fig. 4.3
has been drawn with turbine inlet pressure on the abscissa and
efficiency on the ordinate. It may clearly be noted from this figure that
65
the energy efficiency increases with an increase of turbine inlet pressure
at different temperatures. The energy efficiency at turbine inlet
temperature of 8000C are 44.62% at 200bar, 44.97% at 250 bar, 45.22%
at 300 bar, 45.43% at 350 bar, 45.59% at 400 bar and 45.66% at 425
bar, respectively.
35
38
41
44
47
170
225
275
325
375
425
Turbine inlet pressure (bar)
En
ergy
Eff
icie
ncy
(%)
500550600650700750800
Fig. 4.3 Variation of energy efficiency with turbine inlet pressure of steam
Table 4.2 shows the work done by the turbine, heat supplied and energy
efficiency of different turbine inlet temperature at a given turbine inlet
pressure of 350 bar.
Table 4.2 Energy efficiency at different turbine inlet temperatures
P1bar
T1(0C)
Wt(kJ/kg)
Wp(kJ/kg)
Wnet(kJ/kg)
H.S.(kJ/kg)
EnergyEfficiency
(%)350 500 1152.79 41.38 1111.42 2904.914 38.26350 550 1273.90 41.38 1232.52 3113.997 39.58350 600 1377.18 41.38 1335.80 3274.021 40.80350 650 1472.70 41.38 1431.33 3407.117 42.01350 700 1564.82 41.38 1523.45 3528.138 43.18350 750 1655.67 41.38 1614.29 3642.351 44.32350 800 1746.26 41.38 1704.89 3752.785 45.43
Pc=0.05bar T1, (0C)
66
From the Table 4.2, it can be observed that, the turbine power output
(Wt) increases, as the turbine inlet temperature increases, however power
input to the pump (Wp) remains same. So, as a result of this, the net
work output from the turbine (Wt - Wp) increases as the turbine inlet
temperature increases. Further, it is important to note from the Table 4.2
that, the energy input to the boiler increases as the turbine inlet
temperature increases.
On careful observation of Table 4.2, it may also be noted that the energy
efficiency of the cycle increases significantly with turbine inlet
temperature due to faster rate of increase of turbine work compared to
heat supplied.
4.7.2 Effect of turbine inlet temperature and pressure on exergyefficiency
In order to arrive at the effect of variation in turbine inlet temperature on
exergy efficiency at a given turbine inlet pressure for 1000MW capacity
power plant the mass flow rates of the flue gases and steam have been
varied. At each turbine inlet temperature in range of 5000C-8000C the
values of exergy of the flue gas at the boiler entry (EA), exergy of the flue
gas at boiler exit (EB) and irreversibilities in all the components are
estimated. Thereby, the exergy efficiency at different turbine inlet
temperatures in between 5000C-8000C was calculated and variation in
exergy efficiency is presented in figure 4.4 and 4.5 respectively.
67
44
48
52
56
60
64
68
500 550 600 650 700 750 800Turbine inlet temperature (
0C)
Exe
rgy
Effi
cien
cy(%
)
170 200 225250 275 300325 350 375400 425
Fig. 4.4 Variation of exergy efficiency with turbine inlet temperature
Figure 4.4 depicts the variation of exergy efficiency with the turbine
steam inlet temperature at different turbine inlet pressures. It is
observed from the figure that the exergy efficiency increases with an
increase of temperature at a given pressure. It is found that, the exergy
efficiency at turbine inlet pressure of 425 bar and at turbine inlet
temperatures of 6000C/6500C/ 7000C /7500C /8000C are 55.3%
/58.44% /61.18% /63.66% and 65.95%, respectively.
To analyse the reason for the variation of exergy efficiency with turbine
inlet pressure at constant turbine inlet temperature the data required
has been presented in the Table 4.3.
Pc=0.05bar,TFGi =10000C,TFGo =1000C
P1,(bar)
Pc=0.05bar,TFGi =10000C,TFGo =1000C
P1,(bar)
68
Table 4.3 Exergy efficiency at different turbine inlet pressuresP1bar
T1(0C)
IboilerkW
IturbinekW
IcondenserkW
IpumpkW
IexhaustkW
IsumkW
ExergyEfficiency
(%)200 700 276887.19 109859.95 29413.55 1385.00 13075.68 430621.38 57.10225 700 268687.56 110066.75 29109.08 1223.40 13075.68 424116.91 57.75250 700 260590.73 110275.20 28857.23 2362.86 13075.68 415161.69 58.64300 700 250141.47 110699.03 28471.09 2046.92 13075.68 404434.19 59.71350 700 241452.86 111132.20 28199.74 3036.09 13075.68 396896.56 60.46400 700 234953.27 111576.18 28010.94 4036.12 13075.68 391652.19 60.98425 700 232996.12 111802.33 27940.82 3888.26 13075.68 389703.22 61.18
We know that, the exergy of the flue gas at the entry of the boiler (EA)
does not vary with turbine inlet pressure and turbine inlet temperature
of the steam. Further, on careful observation it may be noted that the
amount of irreversibility in the boiler and condenser reduces with
increase in turbine inlet pressure and the amount of irreversibility in
turbine and pump increases with increase of turbine inlet pressure. It is
also important to note that, the amount of irreversibility at exhaust does
not vary with turbine inlet pressure. As a consequence of these things;
the total irreversibility of all the components of the cycle put together is
decreasing with increase in the turbine inlet pressure. This results in the
increase of exergy efficiency with turbine inlet pressure at a constant
turbine inlet temperature.
The data of total exergy loss (total irreversibility) at a turbine inlet
temperature of 7000C and at different turbine inlet pressures is
presented in Table 4.3 and the values of total exergy loss at different
values of turbine inlet temperature and pressure are plotted in Fig. 4.5
69
340
380
420
460
500
540
500 550 600 650 700 750 800
Turbine inlet temperature (0C)
Tota
l E
xerg
y Lo
ss(M
W)
170 200225 250275 300325 350375 400425
Fig. 4.5 Variation of total exergy loss with turbine inlet temperature
A similar variation in exergy efficiency can be observed at pressures
varying from 170 to 425 bar. This can be observed from the figure 4.6
also. From this figure 4.5, it can be noted that the exergy efficiency at
turbine inlet temperature of 8000C, turbine inlet pressures at 200
bar,225 bar, 250 bar, 300 bar, 350 bar, 400 bar and 425 bar are
61.63%, 62.33%, 63.14%, 64.25%, 65.07%, 65.69% and
65.95%,respectively.
TFGi =10000C,TFGo =1000CP1=350 bar,Pc=0.05bar
P1,(bar)
70
44
48
52
56
60
64
68
170 200 225 250 275 300 325 350 375 400 425
Turbine inlet pressure ( bar)
Exe
rgy
Effi
cien
cy(%
) 500550600650700750800
Fig. 4.6 Variation of exergy efficiency with turbine inlet pressures
To analyze the reason for the variation of exergy efficiency with turbine
inlet temperature at constant turbine inlet pressure the data required
has been presented in the Table 4.4.
Table 4.4 Exergy efficiency at different turbine inlet temperaturesP1bar
T1(0C)
IboilerkW
IturbinekW
IcondenserkW
IpumpkW
IexhaustkW
IsumkW
ExergyEfficiency
(%)350 500 365197.97 112221.59 32902.32 4161.65 13075.68 527559.19 47.82350 550 324753.59 111825.82 31362.35 3752.72 13075.68 484770.16 51.71350 600 293187.34 111545.01 30162.60 3462.58 13075.68 451433.22 55.03350 650 266000.78 111321.33 29130.58 3231.49 13075.68 422759.88 57.89350 700 241452.86 111132.20 28199.74 3036.09 13075.68 396896.56 60.46350 750 218748.38 110966.84 27339.58 2865.22 13075.68 372995.72 62.84350 800 197505.66 110819.40 26535.36 2712.97 13075.68 350649.06 65.07
On careful observation it may be noted that, the amount of irreversibility
in the boiler, turbine, condenser and pump reduces with increase in
turbine inlet temperature with a given turbine inlet pressure. It is also
important to note that the amount of irreversibility at exhaust does not
vary with turbine inlet pressure. Further it is significant, to point out,
T1, (0C)
Pc=0.05bar,TFGi =10000C,TFGo =1000C
71
that the major stake of total irreversibility of the boiler is due to the
irreversibility in the boiler alone. As a consequence of these things; the
total irreversibility of all the components of the cycle put together is
decreasing with increase in the turbine inlet temperature. This results in
the increase in the exergy efficiency with turbine inlet temperature at a
constant turbine inlet pressure.
The values of the total exergy loss at different turbine inlet temperature
at a given turbine inlet pressure of 350 bar are presented in table 4.4.
However, the values of total exergy loss at different values of turbine inlet
pressures and turbine inlet temperatures are plotted in Fig.4.7.
330
370
410
450
490
530
170 200 225 250 275 300 325 350 375 400 425
Turbine inlet pressure ( bar)
Tota
l Exe
rgy
Loss
(MW
)
500550600650700750800
Fig. 4.7 Variation of total exergy loss with turbine inlet pressure at differentturbine inlet temperatures
TFGi =10000C,TFGo =1000C,T1=7000C,Pc=0.05bar
T1, (0C)
72
4.7.3 Effect of turbine inlet temperature and pressure on fractionalexergy loss (FEL)
FEL in a particular component of the cycle reflects the amount of
irreversibility in the particular component.
Figure 4.8 shows that the effect of turbine inlet temperature on fractional
exergy loss of different components of a SCRC.
0
10
20
30
40
50
60
70
500 550 600 650 700 750 800
Turbine inlet temperature (0C)
Frac
tion
al E
xerg
y Lo
ss (%
)
BoilerTurbineCondenserPumpExhaust
Fig. 4.8 Variation of fractional exergy loss of different components with turbineinlet temperature
It may be noted from the figure that, the FEL of the boiler decreases from
68.89% to 55.99%, FEL of the turbine increases from 21.27% to 31.6%
and further FEL of the condenser increases marginally from 6.24% to
7.19% with an increase of turbine inlet temperature from 5000C to
8000C. FEL of the pump is about 1% and FEL of the exhaust increases
TFGi =10000C,TFGo =1000C,P1=350 bar,Pc=0.05bar
73
marginally from 2.71% to 3.73% with increase of turbine inlet
temperature from 5000C to 8000C. In view of large magnitude of FEL in
boiler, an extensive investigation is required to study the ways of
minimizing the FEL in boiler. However, the present investigation has not
focused on this point.
Figure 4.9 represents the variation of fractional exergy loss of different
components of the cycle with turbine inlet pressure.
0
10
20
30
40
50
60
70
170 200 225 250 275 300 325 350 375 400 425
Turbine inlet pressure (bar)
Frac
tion
al E
xerg
y Lo
ss(%
)
BoilerTurbineCondenserPumpExhaust
Fig. 4.9 Variation of fractional exergy loss of different components with turbineinlet pressure
It may be noted from this figure that, FEL of the boiler decreases with
increase of pressure at a given inlet temperature. It is found that, FEL of
boiler at 200 bar is 64%, 250 bar is 62.46%, 300 bar is 61.21%, 350 bar
TFGi =10000C,TFGo =1000C,T1=7000C,Pc=0.05bar
74
is 60.51%, 400 bar is 59.66% and 425 bar is 59.12% at respectively,
where as in the turbine, the FEL increases with an increase of pressure.
FEL in the condenser increases marginally from 6.74% to 7.17%, FEL of
the exhaust increases very marginally from 2.95% to 3.36% with an
increase of turbine inlet pressure from 170 bar to 425 bar. FEL of the
pump is very less and it is insignificant.
4.7.4 Effect of Condenser pressure on the performance
Fig.4.10 shows the variation of energy efficiency with different condenser
pressure at different turbine inlet temperature of steam.
38
40
42
44
46
48
0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1Condenser Pressure(bar)
En
ergy
effi
cien
cy(%
) 500550600650700750800
Fig. 4.10 Variation of energy efficiency of SCRC with condenser pressure atdifferent turbine inlet temperatures
It is interesting to note from Fig 4.10 that, the energy efficiency decreases
with increase of condenser pressure at a turbine inlet temperature. It
P1=350barT1,(0C)
75
may be noted that the maximum energy efficiency occurred at a
condenser pressure of 0.03bar at all turbine inlet temperatures. At a
turbine inlet pressure of 350bar, the values of energy efficiency at 5000C,
6000C, 7000C and 8000C are 40.90%, 42.47%, 44.08% and 45.72%,
respectively.
Fig.4.11 shows the variation of energy efficiency with condenser pressure
at different turbine inlet pressures at turbine inlet temperature of 7000C.
38
40
42
44
46
48
0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1Condenser Pressure(bar)
En
ergy
effi
cien
cy(%
)
225 250 300350 400 425
Fig. 4.11 Variation of energy efficiency of SCRC on condenser pressure ofdifferent turbine inlet pressure
It may be noted that the energy efficiency decreases with increase of
condenser pressure at a turbine inlet pressure. It may be interesting to
note that the maximum energy efficiency occurred at a condenser
pressure of 0.03bar at all turbine inlet pressures. At a turbine inlet
T1=7000C
P1,(bar)
76
temperature of 7000C, the values of energy efficiency at 225bar, 250bar,
300bar, 350bar, 400bar and 425 bar are 43.00%, 43.32%, 43.69%,
44.08%, 44.39% and 44.70% respectively.
To analyze the possible reason for this variation of energy efficiency of
supercritical cycle without reheat with condenser pressure at a turbine
inlet temperature and turbine inlet pressure different values of turbine
work, pump work, network done by the turbine, heat supplied and
energy efficiency have been presented in Table 4.5.
Table 4.5 Energy efficiency at different condenser pressures
As the condenser pressure increases from 0.03bar to 0.1bar, work done
by the turbine, pump work decreases, hence the net work output
decreases. The heat supplied to the boiler does not vary with increase of
condenser pressure. Hence, energy efficiency decreases with increase of
condenser pressure.
The data pertaining to variation of energy efficiency with condenser
pressure at a turbine inlet temperature of 7000C has been presented in
the table 4.5. However, a similar variation in the energy efficiency at
Pc
(bar)Wt
(kJ/kg)Wp(kJ/kg)
Wnet(kJ/kg)
H.S.(kJ/kg)
Energyefficiency(%)
0.03 1596.49 41.29 1555.20 3528.13 44.080.04 1577.66 40.11 1537.55 3528.13 43.580.05 1564.82 41.38 1523.45 3528.13 43.180.06 1550.13 38.33 1511.80 3528.13 42.850.07 1538.73 37.16 1501.57 3528.13 42.560.08 1529.20 36.45 1492.75 3528.13 42.310.09 1520.29 35.66 1484.63 3528.13 42.080.1 1513.27 35.34 1477.93 3528.13 41.89
77
different turbine inlet temperature values ranges 5000C-8000C has been
presented in Fig. 4.12.
56
57
58
59
60
61
62
63
64
65
0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1Condenser Pressure(bar)
Exe
rgy
effic
ien
cy(%
)
500 550 600650 700 750800
Fig. 4.12 Variation of exergy efficiency of SCRC on condenser pressure ofdifferent turbine inlet temperature
It may be noted from this figure that, the exergy efficiency decreases with
increase of condenser pressure at a turbine inlet temperature and the
similar variation in exergy efficiency is noticed at different turbine inlet
temperature. It may also be noted that the maximum exergy efficiency
occurred at a condenser pressure of 0.03 bar at all turbine inlet
temperatures. At a turbine inlet pressure of 350 bar, the values of exergy
efficiency at 5000C, 6000C, 7000C and 8000C are 59.68%, 60.42%,
61.37% and 62.59% respectively. The Fig.4.12 reveals the variation in
the exergy efficiency with condenser pressure at a turbine inlet pressure
TFGi =10000C,TFGo =1000CP1=350bar
T1,(0C)
78
of 350 bar and at different turbine inlet temperatures varying from
5000C-8000C. In order to observe a similar variation at different turbine
inlet pressures, Fig. 4.13 has been plotted at turbine inlet temperature of
7000C and at various turbine inlet pressures varying from 225bar –
425bar.
56
57
58
59
60
61
62
63
64
65
0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1Condenser Pressure(bar)
Exe
rgy
effic
ien
cy(%
)
225 250300 350400 425
Fig. 4.13 Variation of exergy efficiency of SCRC with condenser pressure atdifferent turbine inlet pressure
It may be noted that, the exergy efficiency decreases with increase of
condenser pressure at a turbine inlet pressure. It may be interesting to
note that the maximum exergy efficiency occurred at a condenser
pressure of 0.03 bar at all turbine inlet pressures. At a turbine inlet
temperature of 7000C, the values of energy efficiency at 225bar, 250bar,
TFGi =10000C,TFGo =1000CT1=7000C,R=0.25
P1,(bar)
79
300bar, 350bar, 400bar and 425bar are 63.67%, 63.91%, 64.14%,
64.37%, 64.60% and 65.03% respectively.
The possible reason for the decreasing trend in exergy efficiency of this
cycle with condenser pressure, Table 4.6 has been presented in the next
page.
Table 4.6 Exergy efficiency at different condenser pressures
Further, on careful observation from the Table 4.6, the irreversibility in
the boiler, turbine and pump are decreasing with an increase of
condenser pressure from 0.03bar to 0.1bar. Irreversibility of exhaust
does not change and irreversibility of the condenser increases
significantly with an increase of condenser pressure and thereby
increasing the total irreversibility and the value of EA does not vary with
condenser pressure. Hence, exergy efficiency decreases with increase of
condenser pressure.
The data of total exergy loss at a turbine inlet temperature of 7000C and
at a turbine inlet pressure of 350 bar and are presented in the Table 4.6.
However, the values of total exergy loss at different values of turbine inlet
temperatures are presented in Fig.4.14.
Pc
(bar)Iboiler
kWIturbine
kWIcondenser
kWIpump
kWIexhaust
kWIsum
kWExergyEfficiency
(%)0.03 247548.81 114318.27 9540.51 3250.07 13075.68 387733.34 61.370.04 243944.27 112522.45 19935.10 3130.35 13075.68 392607.84 60.890.05 241508.44 111132.20 28199.74 2980.51 13075.68 396896.56 60.460.06 239346.72 109979.57 35286.86 2753.20 13075.68 400442.03 60.110.07 237572.67 109023.23 41160.47 2580.02 13075.68 403412.06 59.810.08 235842.13 108177.49 46554.42 2461.02 13075.68 406110.75 59.540.09 234700.53 107440.02 51282.58 2239.71 13075.68 408738.53 59.280.1 233292.05 106773.67 55617.84 2208.01 13075.68 410967.25 59.06
80
350
370
390
410
430
450
0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1Condenser Pressure(bar)
Tota
l exe
rgy
loss
, MW
500550600650700750800
Fig 4.14 Variation of total exergy loss of condenser pressure of thecycle
The variation of fractional exergy loss at a condenser pressure of 0.05
bar was already discussed. Further, it may be observed from the Fig.4.15
that FEL in case of condenser pressure increases with an increase of
condenser pressure with a minimum of exergy loss of 2.22% at 0.03 bar
condenser pressure and a maximum of 12.21% at a condenser pressure
of 0.1 bar. FEL increases with decrease in condenser pressure. However,
FEL of the boiler and turbine decreases with increase in condenser
pressure. In the boiler, at 0.1 bar is 60.39%, 0.05 bar is 64.38% and at
0.03 bar is 67.01% respectively. FEL of the steam turbine is decreases
with decrease in condenser pressure. FEL of the turbine at 0.1 bar is
23.45%, at 0.05 bar is 25.26% and at 0.03 bar is 26.59% respectively.
FEL of the pump is nearly 1% and FEL of the exhaust decreases very
P1=350bar,T1=7000C,TFGi =10000C,TFGo =1000C
T1,(0C)
81
marginally from 3.04% to 2.87% with increase of condenser pressure
from 0.03 bar to 0.01 bar.
0
10
20
30
40
50
60
70
0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1Condenser Pressure(bar)
Frac
tion
al E
xerg
y Lo
ss
BoilerTurbineCondenserPumpExhaust
Fig 4.15 Variation of fractional exergy loss with condenser pressure
4.7.5 Effect of boiler inlet flue gas temperature on exergy efficiencyFor the generation of 1000 MW power from steam power plant at
different turbine inlet pressure and turbine inlet temperatures the values
of exergy efficiency, irreversibilities in all the components at different flue
gas inlet temperatures from 9000C to 14000C have been formed in Table
4.7a and 4.7b and presented in Fig.4.16, 4.17 and 4.18.
Fig 4.16 shows the variation of exergy efficiency on different temperature
of boiler flue gas inlet temperature with different turbine inlet
temperature, at a given turbine inlet pressure and at boiler flue gas
outlet temperature of 1000C.
TFGi =10000C,TFGo =1000CT1=7000C,P1=350bar
82
54
58
62
66
70
900 1000 1100 1200 1300 1400Boiler flue gas inlet Temperature(
0C)
Exe
rgy
effic
ien
cy(%
)500550600650700750800
Fig. 4.16 Variation of exergy efficiency of SCRC on boiler flue gas inlettemperature of different turbine inlet temperature
It may be noted that exergy efficiency increases with increase of boiler
flue gas inlet temperatures at a boiler flue gas exit temperature at all
turbine inlet temperatures at a turbine inlet pressure. It may be noted
that the minimum and maximum exergy efficiency occurred at a boiler
flue gas inlet and outlet temperatures of boiler are 9000C and 14000C. At
turbine inlet pressure of 350 bar and at boiler flue gas exit temperature
of 1000C, it is interesting to note that the maximum exergy efficiency at
5000C, 6000C, 7000C and 8000C are 64.11%, 66.42%, 68.34% and
71.56% respectively at boiler flue gas inlet temperature of 14000C.
Figure 4.17 shows the variation of exergy efficiency on different flue gas
inlet temperature of the boiler at a boiler flue gas outlet temperature at
different turbine inlet pressures at a turbine inlet temperature.
TFGo =1000C,P1=350bar
T1,(0C)
83
56
60
64
68
72
900 1000 1100 1200 1300 1400Boiler flue gas inlet Temperature(
0C)
Exe
rgy
effic
ien
cy(%
)
225 250300 350400 425
Fig. 4.17 Variation of exergy efficiency of SCRC on boiler flue gas inlettemperature of different turbine inlet pressure
A similar trend in variation of exergy efficiency is observed in Fig.4.16. At
turbine inlet temperature of 7000C bar and at boiler flue gas exit
temperature of 1000C, it is interesting to note that the maximum exergy
efficiency at 225 bar, 250 bar, 300bar, 350bar, 400bar and 425bar are
64.71%, 68.60%, 69.67%, 70.42%, 70.94% and 71.14% respectively at
boiler flue gas inlet temperature of 14000C.
At given each turbine inlet temperatures/pressure the values of exergy of
the flue gas at the boiler entry (EA), exergy of the flue gas at boiler exit
(EB) and irreversibilities in all the components are estimated and are
shown in Table 4.7a and 4.7b, this may be the possible reason to
increasing the exergy efficiency.
TFGi =10000C,TFGo =1000C,T1=7000C
P1,(bar)
84
Table 4.7a Energy efficiency, enthalpy, exergy, different boiler flue gas inlettemperature
FGi EnergyEfficiency
(%)
ms
(kg/sec]mg
(kg/sec] hA
kJ/kghB
kJ/kgEA
kJEB
kJ
900 43.18 656.40 1.591423 1575629.88 120400.21 856472.94 13075.681000 43.18 656.40 1.403148 1770892.63 120400.21 1003827.38 13075.681100 43.18 656.40 1.253402 1968080.25 120400.21 1156579.63 13075.681200 43.18 656.40 1.132592 2165165.25 120400.21 1313820.25 13075.681300 43.18 651.00 1.043991 2368081.75 120400.21 1475446.88 13075.681400 43.18 656.40 0.909170 2667652.00 120400.21 1640968.00 13075.68
It may be noted from the Table enthalpy and exergy of flue gases at the
exit from the boiler does not vary. Enthalpy and exergy of flue gases at
the entrance of the boiler increases with an increase of boiler flue gas
inlet temperature from 9000C to 14000C at a given steam turbine inlet
temperature of 7000C and a given steam turbine inlet pressure.
Table 4.7b Exergy efficiency different boiler flue gas inlet temperature
FGi Iboiler
kW
Iturbine
kW
Icondenser
kW
Ipump
kW
Iexhaust
kW
ISUM,
kW
ExergyEfficiency(%)
900 192184.9 111132.20 28199.74 4334.51 13075.68 348927.1 59.261000 240171.2 111132.20 28199.74 4334.51 13075.68 396913.3 60.461100 283220.8 111132.20 28199.74 4334.51 13075.68 439962.9 61.961200 323327.8 111132.20 28199.74 4334.51 13075.68 480069.9 63.471300 379198.1 111132.20 28199.74 4334.51 13075.68 535940.1 65.201400 414314.7 111132.20 28199.74 4334.51 13075.68 571056.9 67.34
As the boiler flue gas inlet temperature increases from 9000C to 14000C,
the energy efficiency does not change due to increase of flue gas
temperature, exergy value of the boiler entrance EA, enthalpy of the flue
gas entry hA are increases and exergy value at the boiler exit, EB,
enthalpy of the flue gas exit hB, mass of the steam, enthalpy of the flue
gas exit hB are does not vary and mass of the flue gas decreases of the
given boiler flue gas inlet temperature exit for the given 1000 MW
85
capacity. Further, irreversibility of the boiler increases; irreversibility of
the turbine, condenser, pump and exhaust does not change as the
increase of boiler flue gas inlet temperature and there by total
irreversibility of the boiler increases. Hence, exergy efficiency increases
with an increase of flue gas temperature and are shown in the Table 4.7a
and 4.7b.
On further careful observation, the total exergy loss at boiler flue gas
temperature at different turbine inlet temperature at a turbine inlet
pressure presented in the Table 4.7b. However, the values of total exergy
loss are plotted in Fig.4.18.
300
350
400
450
500
550
600
900 1000 1100 1200 1300 1400Boiler flue gas inlet Temperature(
0C)
Tota
l exe
rgy
loss
(MW
)
500550600650700750800
Fig. 4.18 Variation of total exergy loss of SCRC on boiler flue gas inlettemperature of different turbine inlet temperature
T1,(0C)
P1=350bar,Pc=0.05bar,TFGo =1000C
86
For 1000 MW capacity power plant the effect of varying the inlet flue gas
temperature of the boiler on FEL of all the components has been
presented in Figure 4.19.
0
10
20
30
40
50
60
70
900 1000 1100 1200 1300 1400
Boiler flue gas inlet temperature(0C)
Frac
tion
al E
xerg
y Lo
ss(%
)
Boiler TurbineCondenser PumpExhaust
Fig 4.19 Variation of fractional exergy loss with boiler flue gas inlettemperature
It may be noted from the figure 4.19 that, FEL of the boiler was found
vary 59.45% to 57.82% as flue gas inlet temperature from 9000C to
14000C. However, FEL of the turbine decreases from 29.86% to 16.74%
with an increase of boiler flue gas inlet temperature. FEL of exhaust
rapidly increases from 1.94% to 20.53% with an increase of flue gas inlet
temperature. FEL of the condenser decreases from 7.58% to 4.25% and
FEL of the pump is negligible.
T1=7000C,P1=350barPc=0.05bar,TFGo =1000C
87
4.7.6 Effect of boiler flue gas outlet temperature on exergyefficiency
For 1000 MW power generation from steam power plant at steam turbine
inlet pressure of 350 bar and steam turbine inlet temperature of 7000C
the values of energy efficiency, exergy efficiency, irreversibilities in all the
components, mass flow rates of steam and flue gas at different flue gas
exit temperatures from 800C to 3000C have been formed and presented
in the Table 4.8a and 4.8b.
Figure 4.20 represents the variation of exergy efficiency of boiler flue gas
outlet temperature of different turbine inlet temperature, at a turbine
inlet pressure of 350 bar and at boiler flue gas inlet temperature of
10000C.
30
35
40
45
50
55
60
65
70
80 100 150 200 250 300Boiler flue gas outlet Temperature(
0C)
Exe
rgy
effic
ien
cy(%
) 500550600650700750800
TFGi =10000C,P1=350bar
T1,(0C)
88
Fig. 4.20 Variation of exergy efficiency of SCRC on boiler flue gas outlettemperature of different turbine inlet temperature
It may be observed from the figure 4.20 that, the exergy efficiency
decreases with an increase in flue gas inlet temperature and may be
noted that the maximum exergy efficiency occurs at a boiler flue gas
outlet temperature of 800C. The values of exergy efficiency of boiler flue
gas outlet temperature of 800C at turbine inlet temperatures of 5000C,
6000C, 7000C and 8000C are 60.58%, 62.86%, 65.22% and 67.66%
respectively.
Figure 4.21 shows the variation of exergy efficiency of boiler flue gas
outlet temperature of different turbine inlet pressure, at a turbine inlet
temperature of 7000C and at boiler flue gas inlet temperature of 10000C.
35
40
45
50
55
60
65
70
80 100 150 200 250 300Boiler flue gas outlet temperature(
0C)
Exe
rgy
effic
ien
cy(%
)
225
300
400
425
TFGi =10000C,T1=7000C
P1,(bar)
89
Fig. 4.21 Variation of exergy efficiency of SCRC on boiler flue gas outlettemperature of different turbine inlet pressure
It may be noted from the figure 4.21 that, the exergy efficiency decreases
with an increase in flue gas inlet temperature. It may be noted that the
maximum exergy efficiency occurs at a boiler flue gas outlet temperature
of 800C. The values of exergy efficiency of boiler flue gas outlet
temperature of 800C at turbine inlet pressures of 225bar, 250bar,
300bar, 350 bar, 400 bar and 425bar are 61.69%, 62.01%, 62.32%,
62.64%, 62.95% and 63.27% respectively.
At given each turbine inlet temperatures/pressure the values of exergy of
the flue gas at the boiler entry (EA), exergy of the flue gas at boiler exit
(EB) and irreversibilities in all the components are estimated and are
shown in Table 4.8a and 4.8b, this may be the possible reason to
increasing the exergy efficiency with an increase of boiler flue gas outlet
temperature from 800C to 3000C at a given turbine inlet temperature of
7000C and a given steam turbine inlet pressure.
Table 4.8a Energy efficiency, enthalpy, exergy, different boiler flue gas inlettemperature
FGo EnergyEfficiency
(%)
ms
(kg/secmg
(kg/sec) HA
kJHB
kJEA
kJEB
kJ
80 43.18 656.406 1.375947 1770892.63 87771.67 1003827.38 7231.65100 43.18 656.406 1.403148 1770892.63 120400.21 1003827.38 13075.68150 43.18 656.406 1.477369 1770892.63 203318.22 1003827.38 33823.10200 43.18 656.406 1.561598 1770892.63 287869.78 1003827.38 62097.98250 43.18 656.406 1.657758 1770892.63 373893.91 1003827.38 96560.63300 43.18 656.406 1.768100 1770892.63 461076.66 1003827.38 136312.89
90
As the boiler flue gas outlet temperature increases from 800C to 3000C,
the energy efficiency does not change due to increase of boiler flue gas
outlet temperature, exergy value of the boiler entrance EA, enthalpy of the
flue gas entry hA are does not vary and exergy value at the boiler exit, EB,
enthalpy of the flue gas exit hB, are increasing with increase of boiler flue
gas temperature exit for the given 1000 MW capacity.
Table 4.8b Exergy efficiency different boiler flue gas inlet temperature
FGo Iboiler
kW
Iturbine
kW
Icondenser
kW
Ipump
kW
Iexhaust
kW
ISUM,
kW
ExergyEfficiency(%)
80 233066 111132 28199.7 4334.51 7231.65 383964 61.75100 240171 111132 28199.7 4334.51 13075.70 396913 60.46150 271623 111132 28199.7 4334.51 33823.10 449112 55.26200 295145 111132 28199.7 4334.51 62098.00 500910 50.10250 315994 111132 28199.7 4334.51 96560.60 556221 44.59300 334664 111132 28199.7 4334.51 136313.0 614644 38.77
Further, irreversibility of the boiler increases; irreversibility of the
turbine, condenser and pump does not change and irreversibility of
exhaust increases rapidly with an increase of boiler flue gas inlet
temperature, and there by total irreversibility of the boiler increases.
Hence, exergy efficiency increases with an increase of flue gas
temperature and are shown in the Table 4.8a and 4.8b.
On further careful observation, the total exergy loss at boiler flue gas
temperature at different turbine inlet temperature at a turbine inlet
pressure presented in the Table 4.8b. However, the values of total exergy
loss are plotted in Fig.4.22.
91
300
350
400
450
500
550
600
650
700
80 100 150 200 250 300Boiler flue gas outlet temperature(
0C)
Tota
l Exe
rgy
loss
, MW
500 550 600650 700 750800
Fig. 4.22 Variation of exergy efficiency of SCRC on boiler flue gas outlettemperature of different turbine inlet temperature
Figure 4.23 represents variation of fractional exergy loss as function of
flue gas outlet temperature.
It may be noted fractional exergy loss of the boiler was found to be vary
59.45% to 57.82%. FEL of the turbine decreases from 29.86% to 16.74%.
FEL of exhaust has significant effect on the boiler flue gas outlet
temperature, which increases from 1.94% to 20.53% with increase of
boiler flue gas outlet temperature from 800C to 3000C. FEL of the
condenser decreases from 7.58% to 4.25% and FEL of the pump is nearly
1%.
TFGi =10000C,TFGo =1000CP1=350bar
T1,(0C)
92
0
10
20
30
40
50
60
70
80 100 150 200 250 300Boiler flue gas outlet temperature(
0C)
Frac
tion
al E
xerg
y Lo
ss BoilerTurbineCondenserPumpExhaust
Fig 4.23 Variation of fractional exergy loss with flue gas outlet temperature
T1=7000C,P1=350barPc=0.05bar,TFGi =10000C