THE STUDY OF ENERGY SAVING ON ACMV (AIR-CONDITIONING AND
MECHANICAL VENTILATION) SYSTEM FOR FKM BUILDING
ROSLI BIN CHE MAT
This report is submitted in partial fulfilment of requirement for the award of
Bachelor of Mechanical Engineering
(Design and Innovation)
Faculty of Mechanical Engineering
Universiti Teknikal Malaysia Melaka
June 2012
2
SUPERVISOR DECLARATION
‗I hereby that I read this dissertation and found its content and form to meet
acceptable presentation standards of scholarly work for the award of Bachelor of
Mechanical Engineering (Design and Innovation) with honours‘
Signature :…………………………..
Supervisor : Dr. Reduan Bin Mat Dan
Date :…………………………..
i
DECLARATION
I hereby, declare this project entitled ―the study of energy saving on acmv (air-
conditioning and mechanical ventilation) system for fkm building ‖ is the result of
my own research except as cited in the reference.
Signature:…………………
Authors name: Rosli Bin Che Mat
Date: 31 May 2012
ii
For my beloved parents, siblings and friends
iii
ACKNOWLEDGEMENT
First of all, thanks to ALLAH SWT for HIS mercy and guidance in giving
me full strength to complete the PSM (―Projek Sarjana Muda‖) project and report
about the study of energy saving on ACMV (air- conditioning and mechanical
ventilation) system for FKM building
A lot of thank to my project supervisor, Dr. Reduan Bin Mat Dan for his
support, guidance and advise me in this project and help me to complete the technical
report of PSM. This project was tested my abilities mentally and physically and also
my skill in the Mechanical Engineering.
Furthermore, I would like to thank to my PSM panels for my presentation,
En. Faizil Wasbari and En. Abdul Rafeq that willing to evaluate my PSM project.
Not forgot to second reader, En. Faizil Wasbari for PSM1 and Pn. Mahanum for
PSM2. I would like to thank to other lecturers that help me direct or indirect in this
PSM project.
Lastly, I would like to thanks to my parents, Mr Che Mat B. Che Kob and
Mrs Siah Bt Sulaiman that support me mentally and physically not even in this
project also for my study. Also to my course mate especially Mohd Azhar Ahmad,
Muhammad Azhari and others who ever never give-up in giving their support to me
in to accomplish this PSM project. Thank you very much, I will never forget all of
your kindness.
iv
ABSTRACT
This project presents the energy consumption and ACMV (air- conditioning
and mechanical ventilation) system of the FKM building. ACMV refers to the
equipment, distribution network, and terminals that provide either collectively or
individually the mechanical ventilating or air conditioning process to a building. The
main objectives of this study are to investigate the relationship between building
energy consumption and ACMV system and evaluate the building ACMV system
performance through physical measurement. Improvement methods in ACMV
system is later being proposed to reduce building energy consumption. This study is
also tend to provide a baseline estimate of current energy use which can be used for
calculation of the energy saving impact of various options for reducing energy usage.
In doing this project, physical measurement is being conducted involving air
velocity, temperature and air change rate. Window area and the building wall area
measured to obtain the OTTV (Overall Thermal Transfer Value). The lower OTTV
value is better for a building. Included proposals to reduce energy consumption and
reduce the OTTV in this report. The analysis conducted consists of building cooling
loads, energy saving estimates and costing for the building.
v
ABSTRAK
Projek ini membentangkan penggunaan tenaga dan ACMV (penghawa dingin
dan pengudaraan mekanikal) sistem bangunan di Fakulti Kejuruteraan Mekanikal
(FKM). ACMV merujuk kepada peralatan, rangkaian pengedaran dan terminal yang
menyediakan sama ada secara kolektif atau individu pengalihudaraan mekanikal atau
proses penyaman udara untuk bangunan. Objektif utama kajian ini adalah untuk
mengkaji hubungan antara penggunaan tenaga elektrik bangunan dan sistem ACMV
dan menilai prestasi sistem bangunan ACMV melalui pengukuran fizikal.
Kemudiannya, kaedah penambahbaikkan dalam sistem ACMV yang dicadangkan
untuk mengurangkan penggunaan tenaga bangunan. Kajian ini juga cenderung untuk
menyediakan suatu anggaran asas penggunaan tenaga semasa yang boleh digunakan
untuk pengiraan kesan penjimatan tenaga pelbagai pilihan untuk mengurangkan
penggunaan tenaga. Dalam melakukan projek ini, ukuran fizikal dijalankan yang
melibatkan halaju udara, suhu dan kadar perubahan udara. Luas tingkap serta luas
dinding bangunan diukur untuk mendapatkan nilai OTTV( nilai keseluruhan
pemindahan haba). Semakin rendah nilai OTTV semakin bagus untuk sesuatu
bangunan. Disertakan cadangan untuk mengurangkan penggunaan tenaga serta
mengurangkan nilai OTTV. Analisis yang dijalankan terdiri daripada membina
beban penyejukan, anggaran penjimatan tenaga dan kos penggunaan ACMV untuk
bangunan.
vi
TABLE OF CONTENTS
DECLARATION. ......................................................................................................... i
ABSTRACT ................................................................................................................ iv
ABSTRAK ................................................................................................................... v
TABLE OF CONTENTS ............................................................................................ vi
List of tables ................................................................................................................. x
List of figures .............................................................................................................. xi
List of symbols and abbreviation .............................................................................. xiii
List of appendixs ........................................................................................................ xv
CHAPTER 1
INTRODUCTION ....................................................................................................... 1
1.0 BACKGROUND ........................................................................................... 1
1.1 OBJECTIVES ............................................................................................... 2
1.2 SCOPES OF PROJECT ................................................................................ 2
1.3 PROBLEMS STATEMENT AND SOLUTIONS ........................................ 3
CHAPTER 2
LITERATURE REVIEW............................................................................................. 4
2.0 INTRODUCTION ......................................................................................... 4
2.1 AIR- CONDITIONING AND MECHANICAL VENTILATION (ACMV)
SYSTEM .................................................................................................................. 5
2.1.1 Air- Conditioning ................................................................................... 6
2.1.2 Mechanical Ventilation .......................................................................... 7
2.2 GREEN BUILDING ..................................................................................... 7
2.2.1 Green Building Index (GBI) .................................................................. 9
2.2.2 How Does GBI Work ........................................................................... 10
vii
2.3 THERMAL CONDUCTIVITY .................................................................. 11
2.4 RADIATION ............................................................................................... 13
2.5 OVERALL THERMAL TRANSFER VALUE (OTTV) ............................ 15
2.5.1 Concept 0f OTTV ................................................................................ 16
2.6 GUIDELINES FOR ENERGY EFFICIENCY IN DESIGN OF AIR
CONDITIONING INSTALLATIONS .................................................................. 18
2.6.1 Design Considerations ......................................................................... 18
2.6.2 Load Calculation and Sizing for AC System ....................................... 18
2.6.3 Air Side System Design Criteria .......................................................... 19
2.6.4 Water Side Distribution System ........................................................... 20
2.6.5 Off Hours Control ................................................................................ 20
2.6.6 Energy Saving Systems ........................................................................ 21
2.7 ENERGY MANAGEMENT SYSTEM (EMS) .......................................... 23
2.7.1 Energy Consuming Areas .................................................................... 23
2.7.2 Application of EMS to ACMV system ................................................ 23
2.8 BENEFITS OF LOW ENERGY BUILDINGS .......................................... 24
CHAPTER 3:
METHODOLOGY ..................................................................................................... 25
3.0 INTRODUCTION ....................................................................................... 25
3.1 FLOW CHART OF THE PROJECT .......................................................... 26
3.2 STRATEGY TO REDUCE ENERGY CONSUMPTION OF ACMV ....... 29
3.3 DETERMINE OTTV( OVERALL THERMAL TRANSFER VALUE) .... 31
3.3.1 Building Specifications ........................................................................ 31
3.3.2 OTTV Formula .................................................................................... 34
3.3.3 Malaysian Standard MS 1525:2007 ..................................................... 34
3.4 determine cooling load ................................................................................ 35
3.4.1 External Load ....................................................................................... 35
3.4.2 Internal Load ........................................................................................ 37
CHAPTER 4 ..................................................................................................................
viii
RESULT ..................................................................................................................... 40
4.0 INTRODUCTION ....................................................................................... 40
4.1 Result for OTTV calculation ....................................................................... 40
4.1.1 Sample calculation OTTV.................................................................... 43
4.2 Result of cooling load calculation ............................................................... 46
4.2.1 Sample calculation of cooling load ...................................................... 48
4.3 Electricity costing for FKM building .......................................................... 54
4.4 Guidelines for maintenance an air conditioning systems ............................ 55
4.4.1 Schedule of maintenance...................................................................... 56
4.4.2 Monthly Routine Service and Repair ................................................... 57
CHAPTER 5 (DISCUSSION) ................................................................................... 63
5.1 Current OTTV ............................................................................................. 63
5.2 Proposed OTTV .......................................................................................... 64
5.3 Background To MS ( Malaysia Standard ) 1525 : 2007 .............................. 65
5.4 Building Envelope, Window Design And OTTV ....................................... 65
5.5 Ways To Improve OTTV (Reduce OTTV) ................................................. 66
5.6 Building cooling load estimation ................................................................ 66
5.6.1 How to keep cooling loads low ............................................................ 67
5.7 Electricity costing for FKM building .......................................................... 68
5.8 Services and maintenance............................................................................ 68
CHAPTER 6
CONCLUSION AND RECOMMENDATION ......................................................... 69
6.1 Achievement of objective one ..................................................................... 69
6.2 Achievement of objective two ..................................................................... 69
6.3 Achievement of objective three ................................................................... 70
6.4 Recommendations for future work .............................................................. 71
6.4.1 To optimize the design of ACMV system in term of sizing. It should be
balance between cost of optimization and saving. ............................... 71
6.4.2 To study individual component energy saving .................................... 71
ix
REFERENCES ........................................................................................................... 72
APPENDIX A ............................................................................................................ 77
APPENDIX B ............................................................................................................ 79
APPENDIX C ............................................................................................................ 82
x
LIST OF TABLES
TABLE TITLE PAGE
2.1 Thermal conductivities of some materials at room temperature
(Source: Cengel, Y.A, 2003)
13
2.2 Emissivity‘s of some materials at 300K (Source: Cengel, Y.A,
2003)
14
3.1 Properties of green glazed wall 33
3.2 Properties of pre-cast concrete wall 33
4.1 Summary of current OTTV 41
4.2 Summary of proposed OTTV 42
4.3 Summary of current cooling load 46
4.4 Summary of proposed cooling load 47
4.5 Solar Cooling Load (SCL) at 12 pm 49
4.6
5.1
Schedule Of Maintenance
Total OTTV for each facade elevation
56
63
xi
LIST OF FIGURES
FIGURE TITLE PAGE
2.1 PusatTenaga Malaysia 8
2.2 Diamond Building Putrajaya 8
2.3 A simple experiment setup to determine the thermal
conductivity of a material (Source: Cengel, Y.A, 2003)
12
2.4 Radiation heat transfer between a surface and the surfaces
surrounding it (Source: Cengel, Y.A, 2002)
14
2.5 Radiation heat transfer between a surface and the surfaces
surrounding it (Source: Cengel, Y.A, 2003)
15
3.1 Final Year Project Flow Chart 28
3.2 Strategy To Reduce Energy Consumption Of ACMV 29
3.3 Top View With Actual Orientation 31
3.4 West Wall 31
3.5 South Wall 32
3.6 East Wall 32
3.7 North Wall 32
4.1 Refrigerant Compressors 57
4.2 Water Chillers 58
4.3 Cooling Towers 59
xii
4.4 Cooling Chiller Pump 60
4.5 Water Pumpset 60
4.6 Air Filter At Air Handling Unit 64
4.7 Air Handling Unit 64
4.8 Ducting System 64
4.9 Piping System 64
xiii
LIST OF SYMBOLS AND ABBREVIATION
A area
U heat transfer coefficient
TD temperature difference
CLTD cooling load temperature difference
CLTDc corrected cooling load temperature difference
Q cooling load
SHGF solar heat gain factor
SC shading coefficient
CLF cooling load vactor
RT refrigerant ton
LM correction for latitude and month
K Thermal Conductivity
α Thermal absorptivity
ω Specific Humidity
m Specific mass flow rate
Relative humidity
T Absolute Temperature
xiv
h Enthalpy
'fgh Enthalpy of vaporization
QL Latent heat transfer
QS Sensible heat transfer
Q Heat transfer rate
W Work
COP Coefficient of Performance
OTTV overall thermal transfer value
ACMV air conditioning mechanical ventilation
PSM ―projek sarjana muda‖
xv
LIST OF APPENDIXS
APPENDIX TITLE
A Gantt chart
B Table which used for calculation
C Plan floor of FKM building( MARS)
CHAPTER 1
INTRODUCTION
1.0 BACKGROUND
The project tries to find ways on reducing the energy consumption of the
ACMV (air- conditioning and mechanical ventilation) system of the FKM building.
Air Conditioning is the control of the humidity of air by either increasing or
decreasing its moisture content. Added to the control of the humidity is the control
of temperature by either heating or cooling the air, the purification of the air by
washing or filtering the air and the control of the air motion and ventilation.
Ventilation refers to the process of supplying and removing air by natural or
mechanical means to and from any space, Such air may or may not be conditioned.
Building energy standards or codes are becoming more and more important in
energy efficiency policies [1]. These standards can help raise concern and awareness
of building energy conservation, promote energy efficient designs in buildings,
encourage the development of energy efficient building products, and form a basis
for assessing building energy performance and developing energy efficiency
programmers [2]. Many countries in the world are now developing or upgrading their
building energy standards in order to achieve the energy efficiency goals.
In response to broad concerns regarding the environment and climate change,
Green Buildings are becoming much more common and are increasingly in demand
by building owners and occupiers [3]. As a result, they are featuring more
prominently in the portfolios of most building developers, architects and engineering
consultants. The current green trends are quickly becoming the new standard.
2
1.1 OBJECTIVES
The objectives of this study are:
i. To reduce OTTV (Overall Thermal Transfer Value) of FKM building and
complying requirement of MS (Malaysia Standard) 1525.
ii. To propose methods on ACMV system maintenance and operation that
can reduce building energy consumption.
iii. To estimate saving energy consumption for FKM building by calculate
cooling load.
1.2 SCOPES OF PROJECT
The scopes of this study are:
i. Building load calculation including OTTV (overall thermal transfer
value).
ii. Practical measurements involving temperature, humidity and air change
rate.
iii. Standard guidelines of procedures for building maintenance based on the
study.
3
1.3 PROBLEMS STATEMENT AND SOLUTIONS
One of the biggest energy consumption for a non-residential building is the
AMCV system. Any saving made on the energy consumption at this system will
give significant impact to the cost of running and maintaining the
building. Critical analysis and study need to be conducted on which component
of the total ACMV system uses the highest energy and innovation and critical
thinking is required on how to reduce these consumptions. Present OTTV value
need to be determined and new expected OTTV value need to be projected in
order to bring about the saving into the system. These are the solution for this
problem:
i. Redesign the building properties especially the window and the walls.
ii. Research and find types of air conditioner and the systems of ACMV.
iii. Determine cooling load.
iv. Conduct the measurements including the OTTV, present energy
consumption by the ACMV and temperature mapping.
v. Propose Energy estimates, costing and saving.
CHAPTER 2
LITERATURE REVIEW
2.0 INTRODUCTION
This literature review is based on term on related topic that was study and has
been discussed by a professional and has given a complete explanation on how the
things of study work out. The stated review below is important hint in study of
saving energy consumption of ACMV (air-conditioning and mechanical ventilation)
system relates on GBI (green building index).
ACMV represent Air-conditioning and mechanical ventilation systems. It
fills the fundamental principles and systems in a manner that is technically accurate,
yet of practical use in the real working world [4]. Today‘s really, which mandates
time and cost effectiveness in ACMV work, dictates this principles approach. By
doing this project, some research and observation needed to know energy
consumption saving and ACMV systems report [21].
i. Research the energy consumption of air- conditioning and mechanical
ventilation, ACMV by the journal by previous study, journal, article, etc.
ii. Research the system of ACMV and their equipment.
iii. Research the green building index Malaysia, MS1525:2007 about energy
management system of ACMV.
iv. Research the concept OTTV (overall thermal transfer value) review.
5
2.1 AIR- CONDITIONING AND MECHANICAL VENTILATION
(ACMV) SYSTEM
ACMV stands for air conditioning and mechanical ventilation and refers to
the equipment, distribution network and terminals used either collectively or
individually to provide fresh filtered air, heating, cooling and humidity control in a
building.
A facility can have any combination of heat operated (absorption) and
cooling mode to supply the ACMV system. For heating a facility, a gas-or oil-fired
boiler or furnace, heat pump, rooftop unit, new technology such as infrared radiation,
or electric heat could be employed. Common cooling sources include rooftop units,
chillers, heat pumps, air conditioner or some sort of off-peak cooling system.
For the purpose of this part, ‗ACMV system‘ is considered to be of three
basic types:
a. Central air- distribution systems
In this type, either ACMV system equipment or an engineered and
field-assembled combination of ACMV system components, receives
recirculated room air (plus outside air as required) from a central duct
system, performs the required ventilating or air-conditioning functions, and
delivers the conditioned air to the central duct system, for final delivery to the
conditioned space of the building.
b. Central circulating water systems
In this type, a centrifugal, rotary, screw, scroll or reciprocating,
compression refrigeration or absorption refrigeration type water-chilling
package provides chilled water to a central piping system; and the piping
system supplies cooled water, as required, to water-air heat exchangers
(terminal units) serving the conditioned space of the building. The water
chilling package, including its heat-rejecting element and the terminal unit
are considered to be ACMV system components.
6
c. Multiple units systems
In this type, a number of units of ACMV Equipment, each receiving a
supply of electric energy, perform the functions of cooling air for distribution
to a space or zone of the building.
2.1.1 Air- Conditioning
Air conditioning is treating air for temperature, cleanliness and humidity, and
directing its distribution to meet requirements of a conditioned space. Comfort air
conditioning is when the primary function of the system is to provide comfort to
occupants of the conditioned space. The term industrial air conditioning is used
when the primary function is other than comfort.
There are three basic types of air conditioners:
a. Direct expansion coolers include window air conditioners, heat pumps and
packaged or rooftop units. Air is cooled and dehumidified as it moves past a
cold, refrigerant-filled coil.
b. Chilled water systems use water cooled by a refrigeration machine instead of
air. This cool water supplies a coil, which cools and dehumidifies the air.
c. Evaporative (or ―swamp‖) coolers are usually only appropriate in hot, dry
climates and bring hot air in contact with a water spray or damp surface. The
result is evaporation of moisture, which lowers the temperature of the air.
7
2.1.2 Mechanical Ventilation
Ventilation is a process that either supplies or removes air from a space by
natural or mechanical means. All air that is exhausted from a building must be
replaced by outside air. Outside air must be brought to a certain temperature by
makeup air units used throughout the building. Negative building pressure can be a
problem during winter heating season and could lead to a number of other problems
such as difficulty in opening doors and equipment operation. Air seeps through gaps
around windows, doors and ducts. Equations are available to estimate makeup air
heating costs in the Guide to Industrial Assessments for Pollution Prevention and
Energy Efficiency, referenced at the end of this document
Air is distributed through ducts. Units such as a window air conditioner,
distribute air directly from the unit. Other units using baseboards or radiators may
deliver heat through water, steam or electric resistance systems. Blowers and
registers deliver air in forced air systems.
2.2 GREEN BUILDING
A Green building focuses on increasing the efficiency of resource use –
energy, water, and materials – while reducing building impact on human health and
the environment during the building‘s lifecycle, through better sitting, design,
construction, operation, maintenance, and removal. Green Buildings should be
designed and operated to reduce the overall impact of the built environment on its
surroundings. These are the important about green building:
a. Green buildings are designed to save energy and resources, recycle materials
and minimise the emission of toxic substances throughout its life cycle.
b. Green buildings harmonise with the local climate, traditions, culture and the
surrounding environment.
c. Green buildings are able to sustain and improve the quality of human life
whilst maintaining the capacity of the ecosystem at local and global levels.