THE ESSENTIAL CREDENTIAL SMART BUILDINGS CENTER 2019 ... · 5/15/2019 · THE ESSENTIAL CREDENTIAL...
Transcript of THE ESSENTIAL CREDENTIAL SMART BUILDINGS CENTER 2019 ... · 5/15/2019 · THE ESSENTIAL CREDENTIAL...
2019 TECHNICAL WEBINAR SERIES
THE ESSENTIAL CREDENTIAL
SMART BUILDINGS CENTER
SPEAKER:Jeremy Richmond, Smart Buildings Solutions Manager, MacDonald Miller
MODERATOR:Cynthia Putnam, Principle, Putnam Price Group www.TheBOC.info
Energy Management Information Systems: How Do You Track and Communicate Savings Over Time
May 15, 2019 11:00am Pacific Time
LEARN. LEAD. SUSTAIN
Thank You to our Sponsors
LEARN. LEAD. SUSTAIN
https://www.theboc.info/boc1905/
Webinar Quiz
This presentation is intended for use by the Building Operator Certification program. No copy or use of this presentation should occur without the permission of NEEC and speakers.
LEARN. LEAD. SUSTAIN
▪ Understand the different types of EMIS platforms
▪ Understand the consumers of EMIS data
▪ Understand the necessity of the M&V Plan
▪ Understand the different reporting formats
Learning Objectives
LEARN. LEAD. SUSTAIN
Today’s Speaker and Moderator
Jeremy Richmond Cynthia Putnam
LEARN. LEAD. SUSTAIN
EMIS – Why Care??
• Greater performance requires more in-depth granularity of the data.
• Utility bill analysis is only beneficial monthly and can miss many underlying items.
• Code compliance from the City, State and Federal levels are increasing in necessity.
LEARN. LEAD. SUSTAIN
EMIS – What is it
Source – Department of Energy Better Buildings Report 2013
LEARN. LEAD. SUSTAIN
Who consumes EMIS data
Source – NEEA Inventory of Commercial Energy Management and Information Systems for M&V Applications 2013
LEARN. LEAD. SUSTAIN
IPMVP – M&V Plan
International Performance Measurement and Verification Protocol
• Establish Baseline Period
• Option A – Retrofit Isolation with KEY parameters• Example – Lighting Retrofit
• Option B – Retrofit Isolation with ALL parameters• Example – Controls replacement on single AHU
• Option C – Whole Facility Measurement• Example – Boiler and Chiller Replacements
• Option D – Calibrated Simulation• Example – New construction modeling
LEARN. LEAD. SUSTAIN
IPMVP – Adjustments
International Performance Measurement and Verification Protocol
• Degree Day Adjustments• Balance Point for CDD/HDD• TMY2/3 – Typical Meteorological Year 2 or 3 year average
• Occupancy Adjustments
• Major Projects
LEARN. LEAD. SUSTAIN
Fault Detection Loss Opportunity
How do you qualify how much the problem has already cost you?
• Use Trend Data• Use Equipment Metadata – HP, CFM, Coil size• Calculate the BTU/hr or kWh of the issue• Apply $$ per BTU/hr or $$ per kWh• Apply $$ per kW if you are only affecting peak demand
• Example Fault Calculation:Utility Rate * (( Fan HP * 0.746 * 0.7/0.85) * Fan Duty Cycle)
LEARN. LEAD. SUSTAIN
Reporting Statistics
• A single issue may not represent the need to correct or report on the problem. However when the data is grouped in statistical format the needs can filter to the top.
LEARN. LEAD. SUSTAIN
Energy Star Portfolio Manger
• Space Type and Utilization• Meters• Reporting
• Statement of Energy Performance
• Progress and Goals Report
LEARN. LEAD. SUSTAIN
Financial Reporting
LEARN. LEAD. SUSTAIN
Campus Reporting
LEARN. LEAD. SUSTAIN
Campus Reporting
LEARN. LEAD. SUSTAIN
Case Study
• Incumbent Maintenance Provider
• Sensors and Calibration Top Savers
King County Library System
LEARN. LEAD. SUSTAIN
Case Study
Dual Duct AHU Building• Simultaneous heating & cooling fault identified due to improper VAV damper positions. • Facility staff corrected BAS programming.
• Electric demand rate is $21.98 per hour which results in $106,420 a year in savings!
DoD Federal Contractor Building A
LEARN. LEAD. SUSTAIN
▪ Lawrence Berkeley National Labs
▪ www.lbl.gov
▪ Pacific Northwest National Labs
▪ www.pnnl.gov
▪ Northwest Energy Efficiency Alliance
▪ www.neea.org
▪ Better Buildings
▪ www.energy.gov/eere/better-buildings
Resources
LEARN. LEAD. SUSTAIN
▪ Energy Trust of Oregon – Commercial SEM▪ www.energytrust.org/commercialsem
▪ Snohomish County PUD - Retro-Commissioning and SEM▪ https://www.snopud.com/Site/Content/Documents/ci/CI_han
dout_RetroCx_418.pdf
▪ Avista – Commercial Performance Based Incentives▪ https://www.myavista.com/energy-savings/tools-for-your-
business/rebates-washington
▪ San Diego Gas & Electric – Commercial Incentives▪ https://www.sdge.com/businesses/savings-center/rebates-
incentives/incentives
Utility Incentives
time for … Q&A
LEARN. LEAD. SUSTAIN
Washington & Oregon
• Smart Buildings Center - http://www.smartbuildingscenter.org/tool-library/
Idaho
• University of Idaho – Integrated Design Lab - http://www.idlboise.com/content/tool-loan-library-free-
resource-idaho-power-company-customers
California
• Pacific Gas & Electric - http://www.pge.com/pec/tll/
• Sonoma County - http://sonomacounty.ca.gov/General-Services/Energy-and-Sustainability/Tool-Lending-Library/
• Southern California Edison - https://www.sce.com/business/consulting-services/energy-education-centers
• San Diego Gas & Electric - https://www.sdge.com/energy-innovation-center/tool-and-book-lending-library
New York
• CUNY Building Performance Lab - http://www.cunybpl.org
Tool Lending Library Locations
| THE ESSENTIAL CREDENTIAL
IMPROVE YOUR FACILITY & CAREER
• DEMAND REDUCTION• LIGHTING• ENERGY MANAGEMENT
• BUILDING SCOPING• O&M STRATEGIES• INDOOR AIR QUALITY
www.theboc.info877-850-4793 (toll free)
BOC National Partner Network
LEARN. LEAD. SUSTAIN
Take the Webinar Quiz: https://www.theboc.info/boc1905/
➢ Earn 1.5 points today towards the maintenance of your BOC certification *
Maintain Your BOC Credential
Maintenance Application Deadline: March 31
* Make sure to keep a record of your webinar attendance and quiz completion for next year’s maintenance application
LEARN. LEAD. SUSTAIN
➢September 18: Safety Practices in Building Operations
➢October TBD: Going Beyond Benchmarking your Building
2019 BOC Webinars