The Case for R-290 in U.S. Commercial Foodservice E360 Forum • Chicago, IL • October 5, 2017 Bryan Tonn Senior Engineering Manager H&K International Allen Wicher Director, Marketing Foodservice Emerson

Transcript of The Case for R-290 in U.S. Commercial...

Page 1: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

The Case for R-290 in U.S.

Commercial Foodservice

E360 Forum • Chicago, IL • October 5, 2017

Bryan Tonn

Senior Engineering Manager

H&K International

Allen Wicher Director, Marketing — Foodservice

Emerson

Page 2: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

This presentation is intended to highlight changing developments in the law and industry topics. The law is frequently evolving and information and publications in this presentation may not reflect the latest changes in the law or legal interpretations. The statements and information provided in this presentation should not be construed as legal advice or legal opinion regarding any specific facts or circumstances, but is intended for general informational purposes only. The views and statements expressed during this presentation are the personal opinions of the presenter and do not represent those of Emerson Climate Technologies, Inc. or its affiliated companies. You should consult an attorney about your situation and specific facts and you should not act on any of the information in this presentation as the information may not be applicable to your situation. Although all statements and information contained herein are believed to be accurate and reliable, they are presented without warranty of any kind. Information provided herein does not relieve the user from the responsibility of carrying out its own tests and experiments. Statements or suggestions concerning the use of materials and processes are made without representation or warranty that any such use is free of patent infringement and are not recommendations to infringe on any patents. This presentation may not be copied or redistributed without the express written consent of Emerson Climate Technologies, Inc.

Disclaimer

2

Page 3: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Global Market Dynamics

• Smaller Retail Formats

– Deep Urban Markets

– Convenience

– Speed of Delivery

• Millennials

– e-commerce

– Clicks vs. Bricks

• Fresh

– Buy Local

– Natural and Organic

• Sustainability

• Regulations

3

Page 4: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Summary* of EPA’s Refrigerant SNAP Approval and De-listings

4

*Abbreviated – For complete listing, see EPA website.

** Includes ice machines connected to a supermarket rack refrigeration system.

*** EPA uses term “retrofit” to indicate the use of a refrigerant in an appliance that was designed or originally operated using a different refrigerant. Term does not apply to upgrades to existing equipment where the refrigerant is not changed .

Final Rule: July 20, 2015 Final Rule: September 26, 2016

Refrigerant GWP

Super-

market

(New**)

Supermarket

(Retrofit***)

Remote

condensing

unit

(New)

Remote

condensing

unit

(Retrofit***)

Stand-Alone

Refrigerated food

processing and

dispensing

equipment

(New)

Cold storage

warehouses

(New)

Ice machines

(New)

Very low-temp

refrigeration

(New)

MT < 2,200 BTU/hr.

and not contain

flooded evap.

(New)

MT ≥ 2,200

BTU/hr. with or

without flooded

evap.

(New)

LT

(New)

LT and MT

(Retrofit***)

R-404A/507A 3,943 Jan. 1, 2017 July 20, 2016 Jan. 1, 2018 July 20, 2016 Jan. 1, 2019 Jan. 1, 2020 Jan. 1, 2020 July 20, 2016 Jan. 1, 2021 ^Jan. 1, 2023 OK OK

R-452A 2,140 - - OK OK - - - - - - - -

R-410A 2,088 OK - OK - Jan. 1, 2019 Jan. 1, 2020 Jan. 1, 2020 - Jan. 1, 2021 ^Jan. 1, 2023 OK OK

R-407A

R-407C

R-407F

1,923

1,624

1,674

OK OK OK OK Jan. 1, 2019 Jan. 1, 2020 Jan. 1, 2020 OK ^Jan. 1, 2021

R-407A:

^Jan. 1, 2023

R-407C/F OK

OK R-407C only

HFC-134a 1,300 OK OK OK OK Jan. 1, 2019 Jan. 1, 2020 OK OK OK OK OK -

R-448A

R-449A1,282

1,296OK OK OK OK

Neither SNAP-

approved, nor banned

Neither SNAP-

approved, nor bannedOK

OK for

LT only- - OK -

R-513A

R-450A573

547OK OK OK OK OK OK OK OK OK OK OK -

R-290 3 - - - - OK OK OK - - - OK OK

R-744 1 OK - OK - OK OK OK - OK OK - OK

R-717 0

OK (in primary loop

of secondary

system)

-

OK (In primary loop

of secondary

system)

-OK

(in primary loop of

secondary system)

OK (in primary loop of

secondary system)

OK (in primary loop of

secondary system)

OK (in primary loop of

secondary system)

OK (in primary loop of

secondary system)

OK OK -

Page 5: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Refrigerant Change Being Driven by Regulations and Voluntary Actions

5

Global Regulatory Actions to Ban High-GWP Refrigerants Place Renewed Emphasis on Natural Alternatives.

Organizations

Montreal Protocol Targets Ozone

Depletion (R-22) Signed in 1987North American Proposal

Targets CO2 Emissions

(High Global Warming)

F-Gas RegulationCarbon Tax

HFC Ban & Tax

INTERGOVERNMENTAL PANEL ON

climate change

Regulations

Page 6: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

A1 – Non-Flammable

A2L – Mildly Flammable

A3 – Flammable

B2L – Toxic, Mildly Flam.

This List Is Subject to Change. Please Contact Emerson Representatives for the Most Current Status.

Likely Refrigerant AlternativesEmerson’s Perspective and Development Path

Volumetric Capacity/

PressureNaturals

Mildly Flammable (A2L)

HFO and Blends

Lowest GWP Non-Flammable

(A1) HFC/HFO BlendsToday’s Non-Flammable (A1) HFCs

Elevated

Medium“R-404A Like”

Low“R-134a Like”

GWP 0–5 0–150 500–1,300 1,300–4,000

R-744 (CO2)1

R-290 (Propane)

3

R-717 (Ammonia)

0

R-455A (HDR-110)

146

R-454C (DR3)

146

HFO-1234yf

<1

HFO-1234ze

<1

R-449A (XP40)

1,282

R-448A (N40)

1,273

R-513A (XP10)

573

R-450A (N13)

547

R-507A

3,985R-407A

1,923

R-134a

1,300

R-407F

1,674

R-407C

1,624

R-404A

3,943

In Production Not SNAP Listed,

Next in Development

Approved or in Development In Production

6

R-452A

2,140

Page 7: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

R-404A and R-290 EER Comparison

7

R-290 Yields 20%+ Better EER Efficiency Over R-404A.

Results from Emerson’s compressor test labs, comparing the Energy Efficiency Ratio (EER) of R-404A to R-290 in medium and low back pressure (MBP), show a significant improvement when using R-290.

+10%

+21%

+13%

+23%

+22%

+22%

Page 8: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Industry Efforts Are Increasing Around Flammable Refrigerants

8

Building Codes for Mildly Flammable (A2Ls) Refrigerants Eligible for

Fast-Track Adoption in 2018–2021 ICC Building Code Cycle

AHRI Flammable Refrigerants Research Subcommittee

• Identify gaps in flammable refrigerant research

• Develop road map to complete critical research for safe use

• Focus on A2L and A3 refrigerants

• Pushing for closure on items by end of 2017

Underwriters Laboratory and ASHRAE

• Safety standards under revision to include mildly flammable refrigerant (A2L) accommodations

• Charge increase proposal for A3 and A2L

• Targeting end of CY 2017– U.S.: UL 1995, ASHRAE 15, 34

– International: ISO 5149, IEC 60335, EN378

Page 9: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

U.S. EPA SNAP-Approved End Use Applications for R-290Increasing Charge Limits and Resulting Codes/Standards, Revisions Evolving

9

ASHRAE/UL Working With Industry on Flammable Research Sub-Cmte. and Completing Charge Limit Increase and Safety Standards Proposal.

Effectivity of an R-290 Charge Limit Increase Could be 2018 for Stand-Alone Equip.

R-290: U.S. 300–500 gram charge limit in proposal

A2L: U.S. 1 kg charge limit in proposal IEC/UL/ASHRAE/ICC:

1/8HP 1/6 1/4 1/3 1/2

Domestic Refrigerators (53g)

Vending Mach.

Bev. Dispensers

UC/Prep

Bottle Coolers

3/4 1

1DS 1DG 2DS 3DS 3DG

X = Applications Not Approved by EPA SNAP Final Rule

X

Ice

Walk-Ins (Remote)

Commercial Reach-Ins

X2DG

150g Charge Limit Current

Larger Units Achievable With Multiple Systems

300+ g Charge Limit in ProposalIn Proposal

(stand-alone, OK)

Page 10: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

R-290 U.S. Stand-Alone End Use Applications Did You Know?...

10

EPA

UL 427 Charge

Limits

DOE

Waivers

End Use SNAP-Approved

Can use multiple 150g. refrig.

systems in a single appliance

End Use SNAP-Approved

Can use multiple 150g refrig. systems in

a single appliance.

Must mitigate 150g to 300g charge:

a. WICF volume min. per SA3.3.1 OR

b. Refrigerant detection per SA4.3 AND

c. Class 1, Div. 2 components

Test Procedure Exists

Waiver not needed

Test Procedure Does Not Exist

Yes, OEM needs DOE waiver approval

to sell.

Be Sure to Consult Authority Having Jurisdiction (AHJ) for Additional Code/Standard Requirements Before Installing.

Page 11: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Store Type and

Surface Area (ft²)Trend Architecture and Refrigerant Toward 2020

Warehouses and

Large Supermarkets

>40k ft²

Medium-Size Supermarkets

10k to 40k ft²

Small Supermarkets and

Hard Discounts

6k to 10k ft²

C-Stores

1.2k to 6k ft²

Restaurants

<1.2k ft²

Refrigerant and Architecture Decisions in Context of Store Format

Centralized Architecture: NH3, Cascade and Booster CO2

Centralized: HFO/CO2 or Booster CO2

Centralized: HFO or CO2 Distributed HFO or CO2 Integrated Display Cases R-290

Integrated Display Cases R-290/Plug-Ins

Integrated Display Cases R-290

Semi-Centralized/Distributed HFO or CO2

Distributed HFC/HFO/CO2

Distributed HFC/HFO Multiple Units

11

Page 12: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

The Recent Evolution of R-290

• AHT began exploring natural refrigerants for

self-contained in the 1990s

• Began serial production with R-290 in early

2000s

• More than 500,000 installations globally

• Thousands of installs all over North America

• Many other manufacturers online in recent years,

with others to follow

12

Page 13: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Flammable Refrigerants Create Challenges

Refrigerants Approved by the EPA Under Significant New Alternatives

Policy (SNAP)

Limitations

• No retrofitting of equipment to R-290 allowed, only new equipment

• Stand-Alone Equipment Only

• Charge Limit of 150 Grams (5.3 Ounces)

• Currently No Formalized Certification of Service Technicians Required

• No Channel Developed for Service Replacements for Compressors

• AHJ (Authority Having Jurisdiction)

– Local Authorities Such as State, Local, as Well as Fire Marshals May Have Other

Restrictions

R-290 (Propane)

R-600a (Isobutane)

R-441A (a blend)

Guideline for technicians

with info on best practices

Servicing Infrastructure Needs Development;

Be Sure to Check AHJ Before Installing Equipment. 13

Page 14: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

R-290 Servicing

• Specialized Training for R-290 Is Not Required, but Highly Recommended

– Refrigeration Service Engineers Society, RSES.org

• Flammable Refrigerant Leak Detector Required

– Leave on While Servicing

• Place Safety Placard Advising No Smoking or Open Flames

• R-290 May Be Recovered, But Is Not Required. It Can Be Vented to the Atmosphere.

• Adhere to Proper Brazing Recommendations

• Charging Procedures Are Same for R-290 as HFC Refrigerants

• Copeland Has Published Service Bulletins for Use

• Wholesaler R-290 Stocking Plan Templates for Compressor and Units Can Be

Established Upon Request

Adherence to Servicing Procedures a Must.

Wholesaler R-290 Stocking Plans Can Be Accommodated. 14

Page 15: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

The Case for R-290 in U.S.

15

Charge Limit Increase in U.S. Will Bring a Revision Iteration of All Regulations Impacted.

Advantages• Hydrocarbon-based, non-synthetic

substance

• EPA-approved in commercial refrigeration applications

• Very low environmental impacts: GWP = 3; ODP = 0

• High-efficiency, high-performance, reliable

• LT and MT applications that address EPA and DOE compliance challenges

• Safe when proper protocols and procedures are followed

• Hydrocarbons can be used in multiple applications such as secondary systems, self-contained cases and condensing units

Challenges• Classified A3 flammable refrigerant

• Not a “drop-in” refrigerant; equipment and components designed for R-290

• Globally mandated low-charge limits of 150g restrict application range

• Difficulty getting approved in fire and building codes

• Lack of trained and certified technicians

• Market is currently missing a complete product and safety training course

• Charge limit, safety and related legislations/regulations are the key areas to address for hydrocarbons

Page 16: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

The Case for R-290 in U.S.

Commercial Foodservice —

An H&K Story

E360 Forum • Chicago, IL • October 5, 2017

Bryan TonnSenior Engineering Manager H&K International

Page 17: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

H&K International

• Kitchen equipment supplier for commercial food service industry

• Started in 1975

• Turnkey operation

• Corporately based in Ireland, with engineering and manufacturing in:

– Mesquite, TX

– Rugby, UK

– Jakarta, Indonesia

– San Luis Potosi, Mexico

• 1,500 employees worldwide with 12 distribution centers globally, and sales support on six continents

• Servicing McDonalds, Braum’s, Burger King, Chipotle, IHOP, KFC, Whataburger, Costco, Popeye’s, Subway, and others

• Ships to more than 102 countries annually

17

Page 18: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

The Case for R-290 — An H&K Story

• What challenges did H&K face relating to refrigerants?

• What factors did H&K consider when making a refrigerant change?

• What influenced H&K’s decision to use R-290?

• What challenges did H&K have with R-290?

• What were H&K’s end results with R-290?

17

Page 19: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

What Were the Challenges?

• Customer requirements for lower-GWP refrigerants

• 2017 DOE regulations and efficiency limits of existing refrigerants

• EPA/SNAP and de-listing of existing refrigerants

• Manufacturing with multiple refrigerants

• International and domestic marketplaces

• Competition in the marketplace

19

Page 20: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

• Regulatory

• Energy

• Customer requirements

• Engineering resources

• Manufacturing

• Cost

• Safety

• Availability

• Global market consideration

• Long-term plan

What Were the Factors?

20

Page 21: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Major Influences

21

Experience in Europe

Environmental Impact

Impacts of Future Rulings

Energy Savings

Industry Trends

Customer Requests

Page 22: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Major Influences (cont’d.)

22

Experience in Europe

Environmental Impact

Impacts of Future Rulings

Energy Savings

Industry Trends

Customer Requests

R-290

Page 23: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

R-290 Challenges

• Design

• Supply chain and manufacturing

• Service

• Customers

22

Page 24: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

R-290 Design Challenges

• Design

– Component selection and layout

• Separate electrical and refrigerant-carrying components

• Minimize copper tubing runs

– Very sensitive charge

• 5g can be critical

– Limits with 150g charge

• Limited to ½-HP low-temp application

• Multiple refrigerant circuits challenging

– Safety certifications

• Additional requirements to meet UL471, SB1

24

Page 25: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

R-290 Supply Chain and Manufacturing Challenges

• Supply Chain

– Component lead time and availability

– Inventory control/change-over

• Manufacturing

– Improved leak detection

– Dedicated charging system

– Multiple refrigerant product lines

25

http://www.galileotp.com/products

Page 26: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

R-290 Service Challenges

• Service

– Certified technicians

• Shortages already

• Process changes specific for propane

– Design for service

• Mobile units

• Cartridge design

26

Page 27: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

R-290 Customer Challenges

• Customers

– Education/direction

• New for most customers

• Leadership required

– Communication

• Why are we doing this?

• When will they start seeing these?

• How will they know it is R-290?

27

Page 28: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

• Performance Impact of R-290

– 36% (avg.) energy savings with R-290

change only

– Additional savings from other changes possible

• Cost Savings Impact of R-290

– $168K in utility costs in Europe since 2013

• Additional $151K in Europe over the

next three years

• $50K each year units stay in operation

– Projected $769K savings for U.S. over

next three years

R-290 Results

28

Page 29: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Questions?

DISCLAIMER

Although all statements and information contained herein are believed to be accurate and reliable, they are presented without guarantee or warranty of any kind, expressed or

implied. Information provided herein does not relieve the user from the responsibility of carrying out its own tests and experiments, and the user assumes all risks and liability for

use of the information and results obtained. Statements or suggestions concerning the use of materials and processes are made without representation or warranty that any such

use is free of patent infringement and are not recommendations to infringe on any patents. The user should not assume that all toxicity data and safety measures are indicated

herein or that other measures may not be required.

Thank You!

29

Allen Wicher

Emerson

Director, Marketing — Foodservice

[email protected]

937-493-2496

Bryan Tonn

H&K International

Senior Manager — Engineering

[email protected]

214-818-3580

Page 30: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

BACKUP

30

Page 31: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

• Court Ruling

• Mexichem and Arkema challenged the EPA’s SNAP refrigerant delisting in the D.C. Circuit Court of Appeals arguingi. the EPA had no authority under

the Clean Air Act Section 612 to require the replacement of HFCs

• Court ruled in favor 2:1 against the EPA and found that Section 612 only had congressional authority to phase out ozone-depleting substances and not HFCs, which are non-ozone depleting substances and deciding that– the July 2015 SNAP rule 20 is

vacated or eliminated altogether

– 45-day appeals window is open

• Response and Next Steps

• There will likely be appeals by chemical companies in the next 45 days for various reasons at the Circuit Court of Appeals and/or Supreme Court.

– The court could possibly grant a “stay” of the rule while the appeals process proceeds that would continue the refrigerant delisting’s as it stands.

– Successful appeals could take up to a year.

• States like California may act to fill the void and potentially create regulations on HFCs.

• AHRI and other industry bodies have yet to officially respond to this.

July 15, 2015 — EPA SNAP Rule Delisting Refrigerants for Commercial

Refrigerants Vacated per Court Order Decided August 8, 2017

30

Page 32: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Emerson Position

Message

• Emerson maintains neutrality on this court ruling.

• Emerson serves globally, and lower-GWP refrigerants are required investments.

• Emerson serves as an HVACR industry leader and will continue to provide compression technologies qualified for lower-GWP refrigerants, including:

– R-448A, R-449A, R-450A, R-513A and R-290

– R-452A is actively being planned for.

Customer FAQ

• Am I (remote CDU) going to be affected starting 1.1.18?

–Unclear at the moment, given there will likely be an appeal within the 45-day window.

–The court may or may not grant a “stay” of the rule that can affect the date of impact.

• What should I plan for now?

–Continue qualifying for alternative refrigerants, given uncertainty on the appeals process.

31

Page 33: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Other Refrigerant Regulation Activity

Current Regulatory Proposals Target 150 GWP for Multiple Applications,

Creating Demand for Refrigerants With GWPs of Less Than 150. 33

Environmental Canada (EC)**:

proposal November 26, 2016

Commercial application GWP limit Date

Refrigeration – centralized

systems (MT/LT racks)1,500 2020

Refrigeration – condensing units 2200 2020

Refrigeration – LT stand-alone 1,500 2020

Refrigeration – MT stand-alone 700 2020

Foams 150 2021

Mobile refrigeration 2,200 2025

AC – chillers 700 2025

Domestic refrigeration 150 2025

F-Gas (EU): effective May 20, 2014

Commercial application GWP limit Date

Self-contained refrigeration 2,500 2020

Stationary refrigeration 2,500 2020

Self-contained refrigeration 150 2022

Centralized refrigeration 150 2022

– Except top side of cascade 1,500 2022

CARB: Short-lived climate pollutant reduction strategy

— proposal Nov. 28, 2016 (comments Jan. 17, 2017)

Commercial application GWP limit Date

All refrigerant sales 2,500 ?

Non-residential refrigeration 150 ?

AC (non-residential and

residential)

750 ?

** http://www.gazette.gc.ca/rp-pr/p1/2016/2016-11-26/html/reg1-eng.php

Comment period ended Feb. 8, 2017.

• Phase-down (NAP) option also proposed

(2019 — 90%; 2024 — 65%; 2030 — 30%;

2036 — 15%; baseline 2011–2013)

Page 34: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Alternatives for Refrigerant Applications

34

Watch: EPA SNAP, AHRI’s A2L Research, Standards and Code Committees, Equipment Manufacturers’ New Product Launches, CARB Proposal (<150 GWP)

Environment

R-410A

like

capacity

R-404A &

R-407/22

like

R-134a

like

GWP level

400–675

< 1,500

~600

~300

HFO 1234yf

HFO 1234ze

ARM-42

R410A

R-22

R-407A

R-407C

R-407F, R-452A

0 500 1,000 1,500 2,000

Pressure

or

R32/HFC/HFO

Blends

R-32/HFO

blends

HFC/HFO

BlendsR-134a

CO2

R-404A

R-507A

DR2, N12, ARC 1

R290

NH3

A1 – Non-flammable

A2L – Mildly flammable

A3 – Flammable

R-123 like

(v. low pr.)

(3,922)

R-32

R-32/HFO

blends

R-448A

R-449A

R-450A

R-513A

R-444B = L20

L40, DR7

ARM-20b

HDR110

DR3

ARM-20a

R-446A, R-447A, ARM-71a

<150

B2L – Toxic, mildly flam. Qualitative; not to scale

EstablishedAvailable nowOEMs testing

Page 35: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Foodservice Channel and Business Dynamics

35

Customers Balancing Four Basic Variables for Their Businesses.

0

50

100

150

200

250

HFC CO₂

Component electronics are a larger spend

% of top 50 retailers testing

refrigerant alternatives

$K

6%

83%

0%

20%

40%

60%

80%

100%

2010 2015

Optional

Mechanical

Electronics

0%

20%

40%

60%

80%

100%

Sales % Margin %

Fuel andtobacco

Food and bev.

Other

C-stores targeting foodservice for growth

DOE regulations require

new system designs

Now '17 Now '18 Now '20

% E

ne

rgy -37%-35%

-17%

Reach-In Ice Walk-In

Page 36: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Where We Are: Energy Regulations and Refrigerants

36

Redesigns Are Widespread. Results Require System-Wide Optimization.

Today 2019

EPA refrigerants

Low-GWP blend

CO2

Low GWP Blend

R-290

R-404A

R-290

Low-GWP blend

% M

ark

et

100%

40%

100%

50%

Today 2017 Today 2018 Today 2017

0

20

40

-37%-35%

-17%-25%

Today 2017

SupermarketCA Title 24

Walk-inIceReach-in

DOE energy

% E

ne

rgy

2012 2013Today 2018 Today 2020

Page 37: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Compliance Will Not Be Easy

CARB: All Commercial Refrigeration <150 GWP, Effective Date TBD.

Natural Refrigerant Options Can Be Applied to All Commercial Applications Listed Here.

EPA Refrig. DOE Energy

2017 2018 2019 2020 2021

Supermarket (Rack)

Walk-In (Remote CDU)

Cooler

Freezer

Reach-In (Stand-Alone)

Cooler <2,200 BTU

>2,200 BTU

Freezer

Ice Machine

Dispensing

<2,500 GWP

<2,500 GWP

20–40%

<600 GWP

<600 GWP

<1,500 GWP

30–50%

5–15%

1/1/17

1/1/18

3/27/17

1/1/18

R-290 approved

1/1/20

1/1/19

1/1/20

20–30%

<1,500 GWP

36

Page 38: The Case for R-290 in U.S. Commercial Foodserviceclimate.emerson.com/documents/presentations-chicago-–-case-for-r... · OK OK OK OK Jan. 1, 2019 Jan. 1, ... •Wholesaler R-290

Refrigerant and Minimum Energy Efficiency Regulations

Require Industry to Balance the Equation in U.S.

38

Seek Best Solution for End Users

• Reduce energy consumption with optimized refrigeration equipment system performance.

• Ensure EPA compliance and reduce GWP with refrigerant choices that minimize impact to equipment performance.

• Preserve reliability, serviceability and safety. Understand the toxicity, flammability and pressure implications.

• Estimate the total cost of ownership and viability of technology changes.