Test Smith Emery
Transcript of Test Smith Emery
-
8/2/2019 Test Smith Emery
1/19
SMITH-EMERY LABORATORIES
An Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626
Toro Glasswall Inc.470 Edgeley Blvd, Unit A (north side)Concord, Ontario, Canada, L4K 4G4
ATTN. Eduard Ratz
PROJECT: Series TGW1 unitized pre-glazed curtain wall system
Subject: Performance testing.
Mr. Ratz:
At your request, Smith-Emery Laboratories has provided testing at our Los Angeles facility on a series
TGW1 unitized pre-glazed curtain wall system Installed by Toro Glasswall Inc. The accompanying report
number L-10-259, presents a description of the tests performed, the results of our testing, and our
conclusions.
We appreciate this opportunity to be of service to you. If you have any questions regarding this report,
please do not hesitate to contact us at your convenience.
Respectfully Submitted,
SMITH EMERY LABORATORIES, INC.
Dana Nelson
Curtain/Window Wall Manager
Attachment: Report No. L-10-259
cc: File
-
8/2/2019 Test Smith Emery
2/19
CELEBRATING 100-YEARS
1904-2004
SMITH -EMERY LABORATORIES,INC.
781E.WASHINGTON BLVD.LOS ANGELES,CA90021
(213)749-3411PHONE (213)741-8626FAX
REPORT OF: Series TGW1 unitized pre-glazed curtain wall system.
PREPARED FOR: Toro Glasswall Inc.470 Edgeley Blvd, Unit A (north side)Concord, Ontario, Canada, L4K 4G4
PROJECT NUMBER: SE39140
REPORT NUMBER: L-10-259
REPORT DATE: FEBRUARY 19,2010
-
8/2/2019 Test Smith Emery
3/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 2 of 18
TABLE OF CONTENTS
SECTION
1.00 INTRODUCTION
1.01 Purpose
1.02 Scope of Testing
1.03 Specimen Description
1.04 Test Methods
2.00 TESTING & FINDINGS
3.00 CONCLUSIONS AND CLOSURE
3.01 Conclusions
3.02 Closure
1.00 INTRODUCTION
1.01 Purpose
The purpose of our testing was to evaluate the installed conditions of the curtain wall mockup.
1.02 Scope of Testing
The general scope of this testing program included the following:
Perform testing in accordance with the ASTM and AAMA specifications. Preparation of this report providing descriptions and results of the above testing and
our conclusions.
1.03 Specimen Description
See Toro Glass wall system drawings.
The MU was built of 9 unitized pre-glazed CW panels with over all size of 14.6 x 28.2 (4456 x 8596
mm).
-
8/2/2019 Test Smith Emery
4/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 3 of 181.04 Test Methods
The general test methods used were. E283-91(1999) Standard Test Method for Determining the Rate
of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified
Pressure Differences Across the Specimen, E330-02 Standard Test Method for Structural
Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air
Pressure Difference, E331-00 Standard Test Method for Water Penetration of Exterior Windows,
Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference, AAMA 501.1:
Standard Test Method for Exterior Windows, Curtain Walls and Doors for Water Penetration
using Dynamic Pressure AAMA 501.4 Seismic Drift.
In addition to the test standards noted above, testing was performed in general accordance with generallyaccepted engineering principles and practices. They have incorporated federal, state and local laws, codes,
ordinances and regulations, which in our professional opinion are applicable at the time of preparation of
this report.
2.00 Testing & Findings.February 2010
TESTING SEQUEANCE
1. PRELOADTEST PROCEDURE
Preload at 50% of the inward design wind pressure 37.5 PSF (1795.5 Pa).
ACCEPTANCE CRITERIA:
Visually inspect the assembly for any detrimental affects.
Results. Pass.
Observations: No visual damage observed.
2. AIR INFILTRATION TEST(Ref: ASTM E 283)
TEST PROCEDURE
Cover and seal the mockup completely with polyethylene sheeting while leaving the chamber
uncovered. Develop a positive differential pressure of 6.24 PSF (298.8 Pa) on the chamber. Record
the airflow required to maintain this pressure. This number represents the airflow through the
chamber. Remove the sheeting and reestablish the positive pressure of 6.24 PSF (298.8 Pa). Record
the airflow required to maintain this pressure. This number is the airflow through the mockup and
chamber. The difference between the two-recorded airflows is the airflow through the mockup.
-
8/2/2019 Test Smith Emery
5/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 4 of 18
ACCEPTANCE CRITERIA:
0.06 CFM per square foot of exterior surface, exclusive of any operating window and door areas.
Mockup area x.06 = S.F. .
Fixed area =25 CFM maximum allowable
Total 3.2 CFM
Results:Pass.
Pretest Results
3. WATER PENETRATION UNDER STATIC PRESSURE
(Ref. ASTM E 331)
TEST PROCEDURE
Establish a positive test pressure of 15 PSF (718.2 Pa) on the mockup. Apply water to the exterior of
the mockup at a rate of 5 gallons per hour per square foot for a period of fifteen minutes while
maintaining the differential pressure of 15 PSF (718.2 Pa). During this period, visually inspect the
interior of the mockup for water penetration.
ACCEPTANCE CRITERIA:There shall be no unacceptable water leakage, defined as follows:
The occurrence of condensation during water infiltration tests is acceptable. Other water leakage is
acceptable only if all of the following conditions are satisfied: (a) the water is contained and drained
to the exterior; (b) there would be no staining or other damage to any part of the completed building
or its furnishings (c) No appearance of water on any visible interior surfaces.
Results:Fail.
Observations: Water was observed at the jambs of the mockup at the stack joint at the end dams
interface with the chamber closure a non job condition.
A Toro Glass wall representative performed remedial repairs.
4. WATER PENETRATION UNDER STATIC PRESSURE
(Ref. ASTM E 331)
TEST PROCEDURE
Establish a positive test pressure of 15 PSF (718.2 Pa) on the mockup. Apply water to the exterior of
the mockup at a rate of 5 gallons per hour per square foot for a period of fifteen minutes while
maintaining the differential pressure of 15 PSF (718.2 Pa). During this period, visually inspect the
-
8/2/2019 Test Smith Emery
6/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 5 of 18interior of the mockup for water penetration.
ACCEPTANCE CRITERIA:
There shall be no unacceptable water leakage, defined as follows:
The occurrence of condensation during water infiltration tests is acceptable. Other water leakage is
acceptable only if all of the following conditions are satisfied: (a) the water is contained and drained
to the exterior; (b) there would be no staining or other damage to any part of the completed building
or its furnishings (c) No appearance of water on any visible interior surfaces.
Results:Pass.
Observations: No water penetration was observed.
5. WATER PENETRATION UNDER DYNAMIC PRESSURE
(Ref.: AAMA 501.1)
TEST PROCEDURE
Apply an air stream equivalent to a static differential air pressure of 15 PSF (718.2 Pa) to the mockup.
Apply water to the mockup at a rate of five gallons per hour per square foot for a period of fifteen
minutes. During this period visually inspect the interior of the mockup for water penetration.
ACCEPTANCE CRITERIA:
There shall be no unacceptable water leakage, defined as follows:The occurrence of condensation during water infiltration tests is acceptable. Other water leakage is
acceptable only if all of the following conditions are satisfied: (a) the water is contained and drained
to the exterior: (b) there would be no staining or other damage to any part of the completed building
or its furnishings: (c) No appearance of water on any visible interior surfaces.
Results:Pass.
Observations: No water penetration was observed.
6. STRUCTURAL TEST AT 50% & 100% OF INWARD DESIGN PRESSURE
TEST PROCEDUREApply positive pressure to the mockup of listed below PSF and hold for 10 seconds. Release the
pressure difference across the mockup. After a recovery period of not less than 1 minute nor more
than 5 minutes at zero load, record initial readings. Increase positive pressure to listed below PSF and
hold for 10 seconds. Record deflection readings.
ACCEPTANCE CRITERIA:
Net deflection of any metal-framing members shall not exceed L/175 of the clear span or 3/4
whichever is less for spans less than 13-6 For spans over 13-6 Net deflection of any metal-framing
-
8/2/2019 Test Smith Emery
7/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 6 of 18members shall not exceed L240 = center of glass shall not exceed
Results. Pass.
Transducer locations and deflections.
Transducers 1, 2, 3 typical horizontal mullion.
Transducers 4, 5, 6 typical vertical mullion.
Maximum Allowable deflections at design.
Transducer locations and deflections.
Transducers 1, 2, 3 = 0.324 (8.2 mm) max
Transducers 4, 5, 6 = 0.625 (15.8 mm) max.
30 PSF (1436.4 Pa)
Net deflections 1, 2, 3 = 0.001 (0.03 mm)
Net deflection 4, 5, 6 = 0.132 (3.4 mm)
45 PSF (2154.6 Pa)
Net deflections 1, 2, 3 = 0.007 (0.2 mm)
Net deflection 4, 5, 6 = 0.232 (5.9 mm)
55 PSF (2633.4 Pa)
Net deflections 1, 2, 3 = 0.004 (0.1 mm)
Net deflection 4, 5, 6 = 0.298 (7.6 mm)
7. STRUCTURAL TEST AT 50% & 100% OF OUTWARD DESIGN PRESSURE
TEST PROCEDURE
Apply negative pressure to the mockup of listed below PSF and hold for 10 seconds. Release the
pressure Difference across the mockup. After a recovery period of not less than 1 minute nor more
than 5 minutes at zero load, record initial readings. Increase negative pressure to listed below PSF and
hold for 10 seconds. Record deflection readings. Reduce pressure to zero.
ACCEPTANCE CRITERIA:
Same as procedure (6)
Results. Pass.
Transducer locations and deflections.
Transducers 1, 2, 3 typical horizontal mullion.
Transducers 4, 5, 6 typical vertical mullion.
-
8/2/2019 Test Smith Emery
8/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 7 of 18
Maximum Allowable deflections at design.
Transducer locations and deflections.
Transducers 1, 2, 3 = 0.324 (8.2 mm) max
Transducers 4, 5, 6 = 0.625 (15.8 mm) max.
30 PSF (1436.4 Pa)
Net deflection 1, 2, 3 = 0.013 (0.3 mm)
Net deflection 4, 5, 6 = 0.008 (0.2 mm)
45 PSF (2154.6 Pa)
Net deflection 1, 2, 3 = 0.013 (0.3 mm)
Net deflection 4, 5, 6 = 0.120 (3.1 mm)
55 PSF (2633.4 Pa)
Net deflection 1, 2, 3 = 0.017 (0.4 mm)
Net deflection 4, 5, 6 = 0.148 (5.0 mm)
8. WATER PENETRATION UNDER STATIC PRESSURE
(Ref. ASTM E 331)
TEST PROCEDUREEstablish a positive test pressure of 15 PSF (718.2 Pa) on the mockup. Apply water to the exterior of
the mockup at a rate of 5 gallons per hour per square foot for a period of fifteen minutes while
maintaining the differential pressure of 15 PSF (718.2 Pa). During this period, visually inspect the
interior of the mockup for water penetration.
ACCEPTANCE CRITERIA:
There shall be no unacceptable water leakage, defined as follows:
The occurrence of condensation during water infiltration tests is acceptable. Other water leakage is
acceptable only if all of the following conditions are satisfied: (a) the water is contained and drained
to the exterior; (b) there would be no staining or other damage to any part of the completed building
or its furnishings (c) No appearance of water on any visible interior surfaces.
Results:Pass.
Observations: No water penetration was observed.
-
8/2/2019 Test Smith Emery
9/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 8 of 18
9. STORY DRIFT INPLANE OF CONSTRUCTION DELTA S DISPLACEMENT
2.25 (57.2 mm) each way from zero
(Ref AAMA 501.4)
TEST PROCEDURE
Using a hydraulic system the intermediate floor level will be moved to the left of center and then to the
right of center this shall be repeated for three cycles.
ACCEPTANCE CRITERIA
No damage or disengagement of trim or snap on members glazing gaskets or sealant, no breakage ofglass shall occur.
Results:Pass.
Observations: No damage or disengagement was observed.
10. WATER PENETRATION UNDER STATIC PRESSURE
(Ref. ASTM E 331)
TEST PROCEDURE
Establish a positive test pressure of 15 PSF (718.2 Pa) on the mockup. Apply water to the exterior of
the mockup at a rate of 5 gallons per hour per square foot for a period of fifteen minutes whilemaintaining the differential pressure of 15 PSF (718.2 Pa). During this period, visually inspect the
interior of the mockup for water penetration.
ACCEPTANCE CRITERIA:
There shall be no unacceptable water leakage, defined as follows:
The occurrence of condensation during water infiltration tests is acceptable. Other water leakage is
acceptable only if all of the following conditions are satisfied: (a) the water is contained and drained
to the exterior; (b) there would be no staining or other damage to any part of the completed building
or its furnishings (c) No appearance of water on any visible interior surfaces.
Results:Pass.
Observations: No water penetration was observed.
11. WATER PENETRATION UNDER STATIC PRESSURE
(Ref. ASTM E 331)
TEST PROCEDURE
Establish a positive test pressure of 20 PSF (957.6 Pa) on the mockup. Apply water to the exterior of
the mockup at a rate of 5 gallons per hour per square foot for a period of fifteen minutes while
-
8/2/2019 Test Smith Emery
10/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 9 of 18
maintaining the differential pressure of 20 PSF (957.6 Pa). During this period, visually inspect the
interior of the mockup for water penetration.
ACCEPTANCE CRITERIA:
There shall be no unacceptable water leakage, defined as follows:
The occurrence of condensation during water infiltration tests is acceptable. Other water leakage is
acceptable only if all of the following conditions are satisfied: (a) the water is contained and drained
to the exterior; (b) there would be no staining or other damage to any part of the completed building
or its furnishings (c) No appearance of water on any visible interior surfaces.
Results:Pass.
Observations: No water penetration was observed.
12. STRUCTURAL TEST AT 75%, & 150% OF INWARD DESIGN PRESSURE
(Ref. ASTM E 330)
TEST PROCEDURE
Apply positive pressure to the mockup of listed below PSF and hold for 10 seconds. Release the
pressure difference across the mockup. After a recovery period of not less than 1 minute nor more
than 5 minutes at zero load, record initial readings. Increase positive pressure to listed below PSF.Hold for 10 seconds Reduce pressure to zero.
ACCEPTANCE CRITERIA:
There shall be no glass breakage, permanent damage to panels, fasteners or anchors shall occur, No
permanent deformation to wall or framing members.
Results. Pass. Readings recorded were taken at load not at zero.
Transducer locations and deflections.
Transducers 1, 2, 3 typical horizontal mullion.
Transducers 4, 5, 6 typical vertical mullion.
Maximum Allowable deflections at 1.5 x design.
Transducer locations and deflections.
Transducers 1, 2, 3 = 0.062 (1.6 mm) max
Transducers 4, 5, 6 = 0.125 (3.6 mm ) max
-
8/2/2019 Test Smith Emery
11/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 10 of 18
65 PSF (3112.2 Pa)
Net deflection 1, 2, 3 = 0.008 (0.2 mm)
Net deflection 4, 5, 6 = 0.140 (3.6 mm)
75 PSF (3591 Pa)
Net deflection 1, 2, 3 = 0.010 (0.3 mm)
Net deflection 4, 5, 6 = 0.210 (5.3 mm)
85 PSF (4069.8 Pa)
Net deflection 1, 2, 3 = 0.010 (0.3 mm)Net deflection 4, 5, 6 = 0.258 (6.6 mm )
13. STRUCTURAL TEST AT 75% & 150% OF OUTWARD DESIGN PRESSURE
(Ref. ASTM E 330)
TEST PROCEDURE
Apply negative pressure to the mockup of listed below listed below PSF and hold for ten seconds.
Release the pressure difference across the mockup. After a recovery period of not less than 1 minute
nor more than 5 minutes at zero load, record initial readings. Increase negative pressure to listed below
listed below PSF hold for 10 seconds. Reduce pressure to zero.
ACCEPTANCE CRITERIA:Same as procedure (12).
Results. Pass. Readings recorded were taken at load not at zero.
Transducer locations and deflections.
Transducers 1, 2, 3 typical horizontal mullion.
Transducers 4, 5, 6 typical vertical mullion.
Maximum Allowable deflections at 1.5 x design.
Transducer locations and deflections.
Transducers 1, 2, 3 = 0.062 (1.6 mm) max
Transducers 4, 5, 6 = 0.125 ( 3.6 mm ) max
65 PSF (3112.2 Pa)
Net deflection 1, 2, 3 = 0.015 (0.4 mm)
Net deflection 4, 5, 6 = 0.184 (4.7 mm)
75 PSF (3591 Pa)
-
8/2/2019 Test Smith Emery
12/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 11 of 18
Net deflection 1, 2, 3 = 0.016 (0.4 mm)
Net deflection 4, 5, 6 = 0.218 (5.5 mm)
14. STORY DRIFT INPLANE OF CONSTRUCTION DELTA M DISPLACEMENT
3.5 (88.9 mm) each way from zero
(Ref AAMA 501.4)
TEST PROCEDURE
Using a hydraulic system the intermediate floor level will be moved to the left of center and then to the
right of center this shall be repeated for three cycles.
ACCEPTANCE CRITERIA
No damage or disengagement of trim or snap on members glazing gaskets or sealant, no breakage of
glass shall occur.
Results:Pass.
Observations: No damage or disengagement was observed.
A maximum load of 100 PSF (4788 Pa) outward was placed on the test assembly with no failure
observed.
3.00 CONCLUSIONS AND CLOSURE
3.01 CONCLUSIONS
We make no statement of compliance other than a pass fail result of the material tested or analyzed to any
specification. Based on specific data and information contained in this report, our general understanding of
the test methods and principals involved, and general experience in the materials testing field, it is our
professional judgment that all portions of this mockup meet the requirements set forth in the testing
specifications and documents.
3.02 CLOSURE
The findings in this report were prepared in accordance with generally accepted material engineering and
testing principles and practices. No other warranty, either expressed or implied, is made. This report has
been prepared for the above named client for the above named project. The use of this report for any other
purpose shall be at the users own discretion based on their own interpretation of the results contained
within.
ENDOFREPORT
-
8/2/2019 Test Smith Emery
13/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 12 of 18
Respectfully Submitted,
SMITH EMERY LABORATORIES, INC.
Dana Nelson
SSmmiitthh--EEmmeerryy LLaabboorraattoorriieess
781 E Washington Blvd
Los Angeles, Ca 90021
213-749-3411 x 348
213-494-3636 cell
213-746-7228 fax
Email: [email protected]
-
8/2/2019 Test Smith Emery
14/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 13 of 18
-
8/2/2019 Test Smith Emery
15/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 14 of 18
-
8/2/2019 Test Smith Emery
16/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 15 of 18
-
8/2/2019 Test Smith Emery
17/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 16 of 18
-
8/2/2019 Test Smith Emery
18/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 17 of 18
-
8/2/2019 Test Smith Emery
19/19
SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904
781 East Washington Boulevard Phone (213) 749-3411
Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010
Laboratory No: L-10-259
Page 18 of 18