Test Smith Emery

download Test Smith Emery

of 19

Transcript of Test Smith Emery

  • 8/2/2019 Test Smith Emery

    1/19

    SMITH-EMERY LABORATORIES

    An Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626

    Toro Glasswall Inc.470 Edgeley Blvd, Unit A (north side)Concord, Ontario, Canada, L4K 4G4

    ATTN. Eduard Ratz

    PROJECT: Series TGW1 unitized pre-glazed curtain wall system

    Subject: Performance testing.

    Mr. Ratz:

    At your request, Smith-Emery Laboratories has provided testing at our Los Angeles facility on a series

    TGW1 unitized pre-glazed curtain wall system Installed by Toro Glasswall Inc. The accompanying report

    number L-10-259, presents a description of the tests performed, the results of our testing, and our

    conclusions.

    We appreciate this opportunity to be of service to you. If you have any questions regarding this report,

    please do not hesitate to contact us at your convenience.

    Respectfully Submitted,

    SMITH EMERY LABORATORIES, INC.

    Dana Nelson

    Curtain/Window Wall Manager

    Attachment: Report No. L-10-259

    cc: File

  • 8/2/2019 Test Smith Emery

    2/19

    CELEBRATING 100-YEARS

    1904-2004

    SMITH -EMERY LABORATORIES,INC.

    781E.WASHINGTON BLVD.LOS ANGELES,CA90021

    (213)749-3411PHONE (213)741-8626FAX

    REPORT OF: Series TGW1 unitized pre-glazed curtain wall system.

    PREPARED FOR: Toro Glasswall Inc.470 Edgeley Blvd, Unit A (north side)Concord, Ontario, Canada, L4K 4G4

    PROJECT NUMBER: SE39140

    REPORT NUMBER: L-10-259

    REPORT DATE: FEBRUARY 19,2010

  • 8/2/2019 Test Smith Emery

    3/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 2 of 18

    TABLE OF CONTENTS

    SECTION

    1.00 INTRODUCTION

    1.01 Purpose

    1.02 Scope of Testing

    1.03 Specimen Description

    1.04 Test Methods

    2.00 TESTING & FINDINGS

    3.00 CONCLUSIONS AND CLOSURE

    3.01 Conclusions

    3.02 Closure

    1.00 INTRODUCTION

    1.01 Purpose

    The purpose of our testing was to evaluate the installed conditions of the curtain wall mockup.

    1.02 Scope of Testing

    The general scope of this testing program included the following:

    Perform testing in accordance with the ASTM and AAMA specifications. Preparation of this report providing descriptions and results of the above testing and

    our conclusions.

    1.03 Specimen Description

    See Toro Glass wall system drawings.

    The MU was built of 9 unitized pre-glazed CW panels with over all size of 14.6 x 28.2 (4456 x 8596

    mm).

  • 8/2/2019 Test Smith Emery

    4/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 3 of 181.04 Test Methods

    The general test methods used were. E283-91(1999) Standard Test Method for Determining the Rate

    of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified

    Pressure Differences Across the Specimen, E330-02 Standard Test Method for Structural

    Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air

    Pressure Difference, E331-00 Standard Test Method for Water Penetration of Exterior Windows,

    Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference, AAMA 501.1:

    Standard Test Method for Exterior Windows, Curtain Walls and Doors for Water Penetration

    using Dynamic Pressure AAMA 501.4 Seismic Drift.

    In addition to the test standards noted above, testing was performed in general accordance with generallyaccepted engineering principles and practices. They have incorporated federal, state and local laws, codes,

    ordinances and regulations, which in our professional opinion are applicable at the time of preparation of

    this report.

    2.00 Testing & Findings.February 2010

    TESTING SEQUEANCE

    1. PRELOADTEST PROCEDURE

    Preload at 50% of the inward design wind pressure 37.5 PSF (1795.5 Pa).

    ACCEPTANCE CRITERIA:

    Visually inspect the assembly for any detrimental affects.

    Results. Pass.

    Observations: No visual damage observed.

    2. AIR INFILTRATION TEST(Ref: ASTM E 283)

    TEST PROCEDURE

    Cover and seal the mockup completely with polyethylene sheeting while leaving the chamber

    uncovered. Develop a positive differential pressure of 6.24 PSF (298.8 Pa) on the chamber. Record

    the airflow required to maintain this pressure. This number represents the airflow through the

    chamber. Remove the sheeting and reestablish the positive pressure of 6.24 PSF (298.8 Pa). Record

    the airflow required to maintain this pressure. This number is the airflow through the mockup and

    chamber. The difference between the two-recorded airflows is the airflow through the mockup.

  • 8/2/2019 Test Smith Emery

    5/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 4 of 18

    ACCEPTANCE CRITERIA:

    0.06 CFM per square foot of exterior surface, exclusive of any operating window and door areas.

    Mockup area x.06 = S.F. .

    Fixed area =25 CFM maximum allowable

    Total 3.2 CFM

    Results:Pass.

    Pretest Results

    3. WATER PENETRATION UNDER STATIC PRESSURE

    (Ref. ASTM E 331)

    TEST PROCEDURE

    Establish a positive test pressure of 15 PSF (718.2 Pa) on the mockup. Apply water to the exterior of

    the mockup at a rate of 5 gallons per hour per square foot for a period of fifteen minutes while

    maintaining the differential pressure of 15 PSF (718.2 Pa). During this period, visually inspect the

    interior of the mockup for water penetration.

    ACCEPTANCE CRITERIA:There shall be no unacceptable water leakage, defined as follows:

    The occurrence of condensation during water infiltration tests is acceptable. Other water leakage is

    acceptable only if all of the following conditions are satisfied: (a) the water is contained and drained

    to the exterior; (b) there would be no staining or other damage to any part of the completed building

    or its furnishings (c) No appearance of water on any visible interior surfaces.

    Results:Fail.

    Observations: Water was observed at the jambs of the mockup at the stack joint at the end dams

    interface with the chamber closure a non job condition.

    A Toro Glass wall representative performed remedial repairs.

    4. WATER PENETRATION UNDER STATIC PRESSURE

    (Ref. ASTM E 331)

    TEST PROCEDURE

    Establish a positive test pressure of 15 PSF (718.2 Pa) on the mockup. Apply water to the exterior of

    the mockup at a rate of 5 gallons per hour per square foot for a period of fifteen minutes while

    maintaining the differential pressure of 15 PSF (718.2 Pa). During this period, visually inspect the

  • 8/2/2019 Test Smith Emery

    6/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 5 of 18interior of the mockup for water penetration.

    ACCEPTANCE CRITERIA:

    There shall be no unacceptable water leakage, defined as follows:

    The occurrence of condensation during water infiltration tests is acceptable. Other water leakage is

    acceptable only if all of the following conditions are satisfied: (a) the water is contained and drained

    to the exterior; (b) there would be no staining or other damage to any part of the completed building

    or its furnishings (c) No appearance of water on any visible interior surfaces.

    Results:Pass.

    Observations: No water penetration was observed.

    5. WATER PENETRATION UNDER DYNAMIC PRESSURE

    (Ref.: AAMA 501.1)

    TEST PROCEDURE

    Apply an air stream equivalent to a static differential air pressure of 15 PSF (718.2 Pa) to the mockup.

    Apply water to the mockup at a rate of five gallons per hour per square foot for a period of fifteen

    minutes. During this period visually inspect the interior of the mockup for water penetration.

    ACCEPTANCE CRITERIA:

    There shall be no unacceptable water leakage, defined as follows:The occurrence of condensation during water infiltration tests is acceptable. Other water leakage is

    acceptable only if all of the following conditions are satisfied: (a) the water is contained and drained

    to the exterior: (b) there would be no staining or other damage to any part of the completed building

    or its furnishings: (c) No appearance of water on any visible interior surfaces.

    Results:Pass.

    Observations: No water penetration was observed.

    6. STRUCTURAL TEST AT 50% & 100% OF INWARD DESIGN PRESSURE

    TEST PROCEDUREApply positive pressure to the mockup of listed below PSF and hold for 10 seconds. Release the

    pressure difference across the mockup. After a recovery period of not less than 1 minute nor more

    than 5 minutes at zero load, record initial readings. Increase positive pressure to listed below PSF and

    hold for 10 seconds. Record deflection readings.

    ACCEPTANCE CRITERIA:

    Net deflection of any metal-framing members shall not exceed L/175 of the clear span or 3/4

    whichever is less for spans less than 13-6 For spans over 13-6 Net deflection of any metal-framing

  • 8/2/2019 Test Smith Emery

    7/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 6 of 18members shall not exceed L240 = center of glass shall not exceed

    Results. Pass.

    Transducer locations and deflections.

    Transducers 1, 2, 3 typical horizontal mullion.

    Transducers 4, 5, 6 typical vertical mullion.

    Maximum Allowable deflections at design.

    Transducer locations and deflections.

    Transducers 1, 2, 3 = 0.324 (8.2 mm) max

    Transducers 4, 5, 6 = 0.625 (15.8 mm) max.

    30 PSF (1436.4 Pa)

    Net deflections 1, 2, 3 = 0.001 (0.03 mm)

    Net deflection 4, 5, 6 = 0.132 (3.4 mm)

    45 PSF (2154.6 Pa)

    Net deflections 1, 2, 3 = 0.007 (0.2 mm)

    Net deflection 4, 5, 6 = 0.232 (5.9 mm)

    55 PSF (2633.4 Pa)

    Net deflections 1, 2, 3 = 0.004 (0.1 mm)

    Net deflection 4, 5, 6 = 0.298 (7.6 mm)

    7. STRUCTURAL TEST AT 50% & 100% OF OUTWARD DESIGN PRESSURE

    TEST PROCEDURE

    Apply negative pressure to the mockup of listed below PSF and hold for 10 seconds. Release the

    pressure Difference across the mockup. After a recovery period of not less than 1 minute nor more

    than 5 minutes at zero load, record initial readings. Increase negative pressure to listed below PSF and

    hold for 10 seconds. Record deflection readings. Reduce pressure to zero.

    ACCEPTANCE CRITERIA:

    Same as procedure (6)

    Results. Pass.

    Transducer locations and deflections.

    Transducers 1, 2, 3 typical horizontal mullion.

    Transducers 4, 5, 6 typical vertical mullion.

  • 8/2/2019 Test Smith Emery

    8/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 7 of 18

    Maximum Allowable deflections at design.

    Transducer locations and deflections.

    Transducers 1, 2, 3 = 0.324 (8.2 mm) max

    Transducers 4, 5, 6 = 0.625 (15.8 mm) max.

    30 PSF (1436.4 Pa)

    Net deflection 1, 2, 3 = 0.013 (0.3 mm)

    Net deflection 4, 5, 6 = 0.008 (0.2 mm)

    45 PSF (2154.6 Pa)

    Net deflection 1, 2, 3 = 0.013 (0.3 mm)

    Net deflection 4, 5, 6 = 0.120 (3.1 mm)

    55 PSF (2633.4 Pa)

    Net deflection 1, 2, 3 = 0.017 (0.4 mm)

    Net deflection 4, 5, 6 = 0.148 (5.0 mm)

    8. WATER PENETRATION UNDER STATIC PRESSURE

    (Ref. ASTM E 331)

    TEST PROCEDUREEstablish a positive test pressure of 15 PSF (718.2 Pa) on the mockup. Apply water to the exterior of

    the mockup at a rate of 5 gallons per hour per square foot for a period of fifteen minutes while

    maintaining the differential pressure of 15 PSF (718.2 Pa). During this period, visually inspect the

    interior of the mockup for water penetration.

    ACCEPTANCE CRITERIA:

    There shall be no unacceptable water leakage, defined as follows:

    The occurrence of condensation during water infiltration tests is acceptable. Other water leakage is

    acceptable only if all of the following conditions are satisfied: (a) the water is contained and drained

    to the exterior; (b) there would be no staining or other damage to any part of the completed building

    or its furnishings (c) No appearance of water on any visible interior surfaces.

    Results:Pass.

    Observations: No water penetration was observed.

  • 8/2/2019 Test Smith Emery

    9/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 8 of 18

    9. STORY DRIFT INPLANE OF CONSTRUCTION DELTA S DISPLACEMENT

    2.25 (57.2 mm) each way from zero

    (Ref AAMA 501.4)

    TEST PROCEDURE

    Using a hydraulic system the intermediate floor level will be moved to the left of center and then to the

    right of center this shall be repeated for three cycles.

    ACCEPTANCE CRITERIA

    No damage or disengagement of trim or snap on members glazing gaskets or sealant, no breakage ofglass shall occur.

    Results:Pass.

    Observations: No damage or disengagement was observed.

    10. WATER PENETRATION UNDER STATIC PRESSURE

    (Ref. ASTM E 331)

    TEST PROCEDURE

    Establish a positive test pressure of 15 PSF (718.2 Pa) on the mockup. Apply water to the exterior of

    the mockup at a rate of 5 gallons per hour per square foot for a period of fifteen minutes whilemaintaining the differential pressure of 15 PSF (718.2 Pa). During this period, visually inspect the

    interior of the mockup for water penetration.

    ACCEPTANCE CRITERIA:

    There shall be no unacceptable water leakage, defined as follows:

    The occurrence of condensation during water infiltration tests is acceptable. Other water leakage is

    acceptable only if all of the following conditions are satisfied: (a) the water is contained and drained

    to the exterior; (b) there would be no staining or other damage to any part of the completed building

    or its furnishings (c) No appearance of water on any visible interior surfaces.

    Results:Pass.

    Observations: No water penetration was observed.

    11. WATER PENETRATION UNDER STATIC PRESSURE

    (Ref. ASTM E 331)

    TEST PROCEDURE

    Establish a positive test pressure of 20 PSF (957.6 Pa) on the mockup. Apply water to the exterior of

    the mockup at a rate of 5 gallons per hour per square foot for a period of fifteen minutes while

  • 8/2/2019 Test Smith Emery

    10/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 9 of 18

    maintaining the differential pressure of 20 PSF (957.6 Pa). During this period, visually inspect the

    interior of the mockup for water penetration.

    ACCEPTANCE CRITERIA:

    There shall be no unacceptable water leakage, defined as follows:

    The occurrence of condensation during water infiltration tests is acceptable. Other water leakage is

    acceptable only if all of the following conditions are satisfied: (a) the water is contained and drained

    to the exterior; (b) there would be no staining or other damage to any part of the completed building

    or its furnishings (c) No appearance of water on any visible interior surfaces.

    Results:Pass.

    Observations: No water penetration was observed.

    12. STRUCTURAL TEST AT 75%, & 150% OF INWARD DESIGN PRESSURE

    (Ref. ASTM E 330)

    TEST PROCEDURE

    Apply positive pressure to the mockup of listed below PSF and hold for 10 seconds. Release the

    pressure difference across the mockup. After a recovery period of not less than 1 minute nor more

    than 5 minutes at zero load, record initial readings. Increase positive pressure to listed below PSF.Hold for 10 seconds Reduce pressure to zero.

    ACCEPTANCE CRITERIA:

    There shall be no glass breakage, permanent damage to panels, fasteners or anchors shall occur, No

    permanent deformation to wall or framing members.

    Results. Pass. Readings recorded were taken at load not at zero.

    Transducer locations and deflections.

    Transducers 1, 2, 3 typical horizontal mullion.

    Transducers 4, 5, 6 typical vertical mullion.

    Maximum Allowable deflections at 1.5 x design.

    Transducer locations and deflections.

    Transducers 1, 2, 3 = 0.062 (1.6 mm) max

    Transducers 4, 5, 6 = 0.125 (3.6 mm ) max

  • 8/2/2019 Test Smith Emery

    11/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 10 of 18

    65 PSF (3112.2 Pa)

    Net deflection 1, 2, 3 = 0.008 (0.2 mm)

    Net deflection 4, 5, 6 = 0.140 (3.6 mm)

    75 PSF (3591 Pa)

    Net deflection 1, 2, 3 = 0.010 (0.3 mm)

    Net deflection 4, 5, 6 = 0.210 (5.3 mm)

    85 PSF (4069.8 Pa)

    Net deflection 1, 2, 3 = 0.010 (0.3 mm)Net deflection 4, 5, 6 = 0.258 (6.6 mm )

    13. STRUCTURAL TEST AT 75% & 150% OF OUTWARD DESIGN PRESSURE

    (Ref. ASTM E 330)

    TEST PROCEDURE

    Apply negative pressure to the mockup of listed below listed below PSF and hold for ten seconds.

    Release the pressure difference across the mockup. After a recovery period of not less than 1 minute

    nor more than 5 minutes at zero load, record initial readings. Increase negative pressure to listed below

    listed below PSF hold for 10 seconds. Reduce pressure to zero.

    ACCEPTANCE CRITERIA:Same as procedure (12).

    Results. Pass. Readings recorded were taken at load not at zero.

    Transducer locations and deflections.

    Transducers 1, 2, 3 typical horizontal mullion.

    Transducers 4, 5, 6 typical vertical mullion.

    Maximum Allowable deflections at 1.5 x design.

    Transducer locations and deflections.

    Transducers 1, 2, 3 = 0.062 (1.6 mm) max

    Transducers 4, 5, 6 = 0.125 ( 3.6 mm ) max

    65 PSF (3112.2 Pa)

    Net deflection 1, 2, 3 = 0.015 (0.4 mm)

    Net deflection 4, 5, 6 = 0.184 (4.7 mm)

    75 PSF (3591 Pa)

  • 8/2/2019 Test Smith Emery

    12/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 11 of 18

    Net deflection 1, 2, 3 = 0.016 (0.4 mm)

    Net deflection 4, 5, 6 = 0.218 (5.5 mm)

    14. STORY DRIFT INPLANE OF CONSTRUCTION DELTA M DISPLACEMENT

    3.5 (88.9 mm) each way from zero

    (Ref AAMA 501.4)

    TEST PROCEDURE

    Using a hydraulic system the intermediate floor level will be moved to the left of center and then to the

    right of center this shall be repeated for three cycles.

    ACCEPTANCE CRITERIA

    No damage or disengagement of trim or snap on members glazing gaskets or sealant, no breakage of

    glass shall occur.

    Results:Pass.

    Observations: No damage or disengagement was observed.

    A maximum load of 100 PSF (4788 Pa) outward was placed on the test assembly with no failure

    observed.

    3.00 CONCLUSIONS AND CLOSURE

    3.01 CONCLUSIONS

    We make no statement of compliance other than a pass fail result of the material tested or analyzed to any

    specification. Based on specific data and information contained in this report, our general understanding of

    the test methods and principals involved, and general experience in the materials testing field, it is our

    professional judgment that all portions of this mockup meet the requirements set forth in the testing

    specifications and documents.

    3.02 CLOSURE

    The findings in this report were prepared in accordance with generally accepted material engineering and

    testing principles and practices. No other warranty, either expressed or implied, is made. This report has

    been prepared for the above named client for the above named project. The use of this report for any other

    purpose shall be at the users own discretion based on their own interpretation of the results contained

    within.

    ENDOFREPORT

  • 8/2/2019 Test Smith Emery

    13/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 12 of 18

    Respectfully Submitted,

    SMITH EMERY LABORATORIES, INC.

    Dana Nelson

    SSmmiitthh--EEmmeerryy LLaabboorraattoorriieess

    781 E Washington Blvd

    Los Angeles, Ca 90021

    213-749-3411 x 348

    213-494-3636 cell

    213-746-7228 fax

    Email: [email protected]

  • 8/2/2019 Test Smith Emery

    14/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 13 of 18

  • 8/2/2019 Test Smith Emery

    15/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 14 of 18

  • 8/2/2019 Test Smith Emery

    16/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 15 of 18

  • 8/2/2019 Test Smith Emery

    17/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 16 of 18

  • 8/2/2019 Test Smith Emery

    18/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 17 of 18

  • 8/2/2019 Test Smith Emery

    19/19

    SMITH-EMERY LABORATORIESAn Independent Commercial Testing Laboratory, Established 1904

    781 East Washington Boulevard Phone (213) 749-3411

    Los Angeles, California 90021 Fax (213) 741-8626File No: 39140 February 19, 2010

    Laboratory No: L-10-259

    Page 18 of 18