TEST REPORT IEC 62109-1 Safety of Power Converter for use in...

133
TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter for use in Photovoltaic Power Systems Part 1: General requirements Report Number. ............................ : 64.290.18.05995.01 part 1 of 2 Date of issue .......................... : 2019-04-08 Total number of pages ................. : 103 pages Name of Testing Laboratory prepar- ing the Report ............................... : TÜV SÜD Certification and Testing (China) Co., Ltd. Guangzhou Branch 5F, Communication Building, 163 Pingyun Rd, Huangpu Ave. West, Guangzhou 510656, P. R. China .......................... : EAST Group Co., Ltd. Address ......................................... : No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Indus- try Park, 523808 DongGuan City, Guangdong Province, PEOPLE'S REPUBLIC OF CHINA Test specification: Standard........................................ : IEC/EN 62109-1:2010 Test procedure.............................. : CE_LVD Non-standard test method ........... : N/A Test Report Form No. ................... : IEC62109_1B Test Report Form(s) Originator.... : VDE Testing and Certification Institute Master TRF.................................... : Dated 2016-04 Copyright © 2016 IEC System of Conformity Assessment Schemes for Electrotechnical Equipment and Components (IECEE System). All rights reserved. This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copy- right owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the reader's interpretation of the reproduced material due to its placement and context . If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB Scheme procedure shall be removed. This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02. General disclaimer: The test results presented in this report relate only to the object tested. This report shall not be reproduced, except in full, without the written approval of the Issuing CB Testing La- boratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB, respon- sible for this Test Report.

Transcript of TEST REPORT IEC 62109-1 Safety of Power Converter for use in...

Page 1: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

TRF_IEC62109_1B

TEST REPORT

IEC 62109-1

Safety of Power Converter for use in Photovoltaic Power SystemsPart 1: General requirements

Report Number. ............................ : 64.290.18.05995.01 part 1 of 2

Date of issue .......................... : 2019-04-08

Total number of pages ................. : 103 pages

Name of Testing Laboratory prepar-ing the Report ............................... :

TÜV SÜD Certification and Testing (China) Co., Ltd. GuangzhouBranch

5F, Communication Building, 163 Pingyun Rd, Huangpu Ave.West, Guangzhou 510656, P. R. China

.......................... : EAST Group Co., Ltd.

Address ......................................... : No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Indus-try Park, 523808 DongGuan City, Guangdong Province,PEOPLE'S REPUBLIC OF CHINA

Test specification:

Standard........................................ : IEC/EN 62109-1:2010

Test procedure.............................. : CE_LVD

Non-standard test method ........... : N/A

Test Report Form No. ................... : IEC62109_1B

Test Report Form(s) Originator .... : VDE Testing and Certification Institute

Master TRF .................................... : Dated 2016-04

Copyright © 2016 IEC System of Conformity Assessment Schemes for Electrotechnical Equipmentand Components (IECEE System). All rights reserved.This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copy-right owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from thereader's interpretation of the reproduced material due to its placement and context .

If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CBScheme procedure shall be removed.

This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory andappended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.General disclaimer:The test results presented in this report relate only to the object tested.This report shall not be reproduced, except in full, without the written approval of the Issuing CB Testing La-boratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB, respon-sible for this Test Report.

Page 2: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter
Page 3: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

TRF_IEC62109_1B

List of Attachments (including a total number of pages in each attachment):This test report contains 2 parts listed in below table:

Item Description Pages

Part 1 IEC/EN 62109-1:2010 test report 103

Part 2 IEC/EN 62109-2:2011 test report 30

This test report shall be also used in conjunction with 12 pages of photo documentation.

Summary of testing:All tests were carried out according to IEC 62109-1:2010. The text of IEC 62109-1:2010 was approved by

CENELEC as a European Standard without any modification.

Tests performed (name of test and test clause):

Clause Requirement

4.3 Thermal testing

4.4 Testing in single fault condition

4.5 Humidity preconditioning

4.6 Backfeed voltage protection

4.7 Electrical ratings tests

5.1.2 Durability of markings

6.3 Ingress protection

7.3 Protection against electric shock

7.4 Protection against energy hazards

7.5 Electrical tests related to shock hazard

8.5 Wall mounting

15 Software and firmware performing safety functions.

Page 4: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

TRF_IEC62109_1B

Copy of marking plate:The artwork below may be only a draft. The use of certification marks on a product must be authorized bythe respective NCBs that own these marks.

Below electric ratings and warnings are silk-screen on label and affixed side of enclosure.

Page 5: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

TRF_IEC62109_1B

Test item particulars ..............................................:

Equipment mobility...................................................: movable hand-held stationary fixed transportable for building-in

Connection to the mains .......................................... : pluggable equipment direct plug-in permanent connection for building-in

Enviromental category ............................................. : outdoor indoor indoor unconditional conditional

Over voltage category Mains ................................... : OVC I OVC II OVC III OVC IV

Over voltage category PV ........................................: OVC I OVC II OVC III OVC IV

Mains supply tolerance (%) .....................................: +/- 10%

Tested for power systems .......................................: TN system

IT testing, phase-phase voltage (V) .........................: N/A

Class of equipment .................................................: Class I Class II Class III Not classified

Mass of equipment (kg) ...........................................: Net weight: 22.3 kg (Approx.)

Pollution degree ......................................................: PD II

IP protection class ...................................................: IP 20 (indoor use only)

TestingDate of receipt of test item(s) ................................... 2018-10-29

Dates tests performed ............................................. 2018-11-01 to 2019-03-18

Possible test case verdicts:test case does not apply to the test object ........ N/A

test object does meet the requirement ............... Pass (P)

test object was not evaluated for the require-ment ..................................................................

N/E

test object does not meet the requirement ......... Fail (F)

General remarks:"(see Attachment #)" refers to additional information appended to the report."(see appended table)" refers to a table appended to the report.The tests results presented in this report relate only to the object tested.This report shall not be reproduced except in full without the written approval of the testing laboratory.Additional test data and/or information provided in the attachments to this report.Throughout this report a comma / point is used as the decimal separator.This TRF was modified by TUV SUD Guangzhou branch by adding Cl.4 and Annex A to J.Abbreviations used in the report:Basic insulation (BI); Supplementary insulation (SI); Double insulation (DI); Reinforced insulation (RI);Functional insulation (FI); Single fault condition (SFC); Normal condition (NC); Mains overvoltage catego-ry (OVC); Pollution degree (PD), CDF (Construction Data form)

-clause 4.2.5 of IECEE 02:The application for obtaining a CB Test Certifi-cate includes more than one factory location anda declaration from the Manufacturer stating thatthe sample(s) submitted for evaluation is (are)representative of the products from each factory

Yes Not applicable

Page 6: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

TRF_IEC62109_1B

has been provided ....................................................

When differences exist; they shall be identified in the General product information section.

Name and address of factory (ies) ........................ :Factory name: EAST Group Co., Ltd.

Address: No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Industry Park, 523808 DongGuanCity, Guangdong Province, PEOPLE'S REPUBLIC OF CHINA

General product information:(1) The unit is non-isolated (transformerless) hybrid solar inverter, it is intended to be connected with

household generation systems with battery to store energy.

(2) The unit has four operating modes: grid-tied mode, anti-reflux mode, off-grid mode and bypassmode. The difference between anti-reflux mode and grid-tied mode is that energy will not be deliv-ered to the grid in anti-reflux mode.

(3) The unit has 4 connection terminals: PV input terminal, grid terminal, battery terminal and AC loadterminal. intended to use solar power, utility power and battery power to ensure continuouspower supply.

(4) The unit shall be used at specified ambient conditions. Indoor, conditioned, temperature range: 0 -40 °C. Altitude: <1000 m, Auto-derating above 1000 m; Overvoltage category: III (Grid), II(PV);Relative humidity range: 0 - 90 %.

(5) If certain functions are not permitted by local regulation, the function shall be disabled by hardwareor software setting (if applicable) by the manufacturer before putting into the market. For example,

reimbursement in some nations.

(6) Low voltage electrical installations shall comply with national and local regulation. Only qualifiedelectricians are allowed to install and maintain the converter.

(7) In order to protect the PCE, user and installer, external DC and AC circuit breaker shall beequipped at the end-use application.

(8) The unit provides four disconnection relays, two for line conductor and another two for neutralconductor.

(9) Basic insulation is provided between PV input / AC output circuit and battery circuit, additionalprotection of battery terminal is necessary in the installation.

(10) Firmware version: Inverter master: V4.09, display screen: V7.2F.

Model differences:N/A

Ratings:

Model EA5KHD

PV input rating

Max. input power 5500 W

Rated input voltage 360 Vd.c.

Max. input voltage 550 Vd.c.

MPPT voltage range 120 Vd.c. 530 Vd.c.

MPPT voltage range (full load) 250 Vd.c. 450 Vd.c.

Page 7: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

TRF_IEC62109_1B

Max. input current 2 x 12 Ad.c.

PV short circuit current 2 x 15 Ad.c.

Battery input/output rating

Battery type Lithium or Lead-acid

Rated voltage (Lithium) 51.2 Vd.c.

Battery voltage range(Lithium) 46.4 Vd.c. - 57.6 Vd.c.

Rated voltage (Lead-acid) 48 Vd.c.

Battery voltage range(Lead-acid) 40 Vd.c. 58 Vd.c.

Max. charging power 2500 W

Max. charging current 50 Ad.c.

Max. discharging power 2500 W

Max. discharging current 50 Ad.c.

Grid input rating

Rated input voltage 230 Va.c.

Rated grid frequency 50 Hz

Max. input apparent power 2000 VA

Max. input active power 2000 W

Max. input current 8.7 Aa.c

Grid output rating

Max. output apparent power 5000 VA

Max. output active power 5000 W

Rated output voltage 230 Va.c.

Max. output current 21.7 Aa.c.

Rated output frequency 50 Hz

Power factor 0.9 leading - 0.9 lagging

AC load output rating

Max. output apparent power 2000 VA

Max. output active power 2000 W

Rated output voltage 230 Va.c.

Max. output current 8.7 Aa.c.

Rated output frequency 50 Hz

General

Operating temperature range 0 - 40 °C

Protective class I

Ingress protection IP20

Page 8: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

4 General testing requirements P

4.1 General P

4.2 General conditions for testing P

4.2.1 Sequence of tests P

4.2.2 Reference test conditions P

4.2.2.1 Environmental conditions P

Unless otherwise specified, the following ambientenvironmental conditions shall exist in the test loca-tion:

a) temperature of 15 °C to 40 °C

b) a relative humidity of not more than 75 %

and not less than 5%

c) an air pressure of 75 kPa to 106 kPa.

d) no frost, dew, percolating water, rain, solar radia-tion, etc.

P

4.2.2.2 State of equipment P

4.2.2.3 Position of equipment The equipment were installedin accordance with the manu-

configuration that results in theworst-case test conditions.

P

4.2.2.4 Accessories No accessories or operator in-terchangeable parts

N/A

4.2.2.5 Covers and removable parts No such covers and remova-ble parts.

N/A

4.2.2.6 Main supply 230 Va.c. (90% to 110% toler-ance), 50Hz, TN system con-sidered.

P

4.2.2.7 Supply ports other than the mains DC input P

4.2.2.7.1 Photovoltaic supply sources PV input P

4.2.2.7.2 Battery inputs External battery pack canconnect to the unit.

P

4.2.2.8 Conditions of loading for output ports P

4.2.2.9 Earthing terminals Protective conductor terminalwas connected to earth. Nofunctional earth terminal.

P

4.2.2.10 Controls P

Controls which the operator can adjust shall be setto any position except that

Control is set to max. AC out-put power. But it is not intend-ed for user

P

Page 9: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

a) mains selection devices shall be set to the cor-rect value unless otherwise noted in this standard;

No mains selection devices. N/A

b) Combinations of settings shall not be made ifc-

tions provided with the equipment.

No combinations of settingsdevices

N/A

4.2.2.11 Available short circuit current N/A

4.3 Thermal testing P

4.3.1 General P

4.3.2 Maximum temperature Tests of equipment rated foruse in ambient temperaturesup to 40 °C

P

4.3.2.1 General P

Materials and components shall be selected so thatunder the most severe rated operating conditions,the temperatures do not exceed the temperaturelimits.

P

Conformity is verified by measuring temperaturesunder the conditions given in 4.2 for each rated op-erating condition or mode of the PCE that could af-fect the resulting temperatures.

P

The temperature limits specified below are totaltemperature limits (not temperature rise limits).

P

Tests of equipment rated for use in ambient tem-peratures up to 50°C may be conducted at anyambient temperature in the range given in 4.2.2.1,in which case the difference between the maximumrated ambient temperature and the test ambient isto be subtracted from or added to (as appropriate)the measured temperatures for comparison to thelimits specified below.

Maximum rated ambient tem-perature of the unit: 40 °C.

(see appended table)

N/A

PCE rated for use in ambient temperatures morethan 50°C shall be tested at the maximum ratedambient temperature +/- 5°C. the difference be-tween the maximum rated ambient temperatureand the test ambient is to be subtracted from oradded to the measured temperatures for compari-son to the limits specified.

N/A

PCE with different output ratings or with automaticderating for different ambient temperatures shall betested under as many conditions as are necessaryto record worst-case temperatures, including atleast the maximum ambient before derating, andthe maximum ambient with derating.

N/A

During thermal testing within NORMALCONDITIONS protective devices shall not operate.

P

Page 10: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Temperatures are to be measured by thermocou-ples, except that for coils the change of resistancemethod may be used.

Method of thermocouples isused, including transformers,inductors, and other coils. Mul-tiple embedded thermocou-ples, where the thermocouplesare attached during winding ofthe part, are more likely torecord hot-spot temperatures.

P

Limits:

- for coils and their insulation systems, the tem-perature limits in Table 1 apply.

P

- for other components the measured temperaturesshall not exceed the lower of:

(see appended table) P

- the applicable IEC component standards P

- coperating temperature

P

- if neither of the above exists, temperature limitsare given in Table 2.

P

4.3.2.2 Touch temperatures P

The maximum temperature for accessible parts ofthe PCE shall be in compliance with table 3

P

It is permitted that accessible parts that are re-quired to get hot as part of their intended function(for example heatsinks) may have temperatures upto 100 °C, if the parts are marked with the hot sur-face marking of symbol 14 of Annex C. For prod-ucts only for use in a closed electrical operating ar-ea the 100 °C limit does not apply.

P

4.3.2.3 Temperature limits for mounting surfaces P

In order to protect against long-term degradation ofbuilding materials, surfaces of the PCE that will bein contact with the mounting surface shall not ex-ceed a maximum total temperature of 90 °C.

P

4.4 Testing in single fault condition P

4.4.1 General P

Testing in single fault conditions is done to deter-mine that no hazards result from reasonably ex-pected fault conditions that may arise in normalservice or from reasonably expected misuse.

P

Fault testing shall be done unless it can be conclu-sively demonstrated that no hazards could arisefrom a particular fault condition, or unless alterna-tive methods of checking conformity are specifiedin this standard in place of fault testing.

P

4.4.2 Test conditions and duration for testing under faultconditions

P

Page 11: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

4.4.2.1 General P

The equipment shall be operated under the combi-nation of conditions in 4.2, which is least favourablefor the particular fault test being performed.

P

Fault conditions are to be applied only one at atime and shall be applied in turn in any convenientorder. Multiple simultaneous faults shall not be ap-plied, but a subsequent fault may arise as a conse-quence from an applied fault. Separate samples ofthe EUT may be used for each separate fault testapplied, or the same sample may be used for manytests if damage from previous fault tests has beenrepaired or will not affect the results of further tests.

P

4.4.2.2 Duration of tests P

The equipment shall be operated until furtherchange as a result of the applied fault is unlikely, asdetermined by (for example) opening of a devicethat removes the influence of the fault, stabilizationof temperatures, etc.

P

If a non-resettable, manual, or automatically reset-ting protective device or circuit operates in such away as to interrupt or mitigate the fault condition,the test duration is as follows:

P

- automatic reset devices or circuits: allow the pro-tection to cycle on and off until no further changeas a result of the applied fault is likely, until the ul-timate result is obtained, or until temperatures sta-bilize

P

- manual reset devices or circuits: three cycles, withthe device or circuit reset as soon as possible aftertripping

N/A

- non-resettable devices or circuits: one cycle N/A

4.4.3 Pass/fail criteria for testing under fault conditions P

4.4.3.1 Protection against shock hazard P

Compliance with requirements for protectionagainst electric shock is checked after the applica-tion of single faults as follows:

P

a) by making measurements to check that no ac-cessible DVC-A circuits have become shock-hazardous using the steady state limits for DVC-Ain Table 6 and the short-term limits of 7.3.2.3, andthat such circuits remain separated from live partsat voltages greater than DVC A with at least basicinsulation. Compliance is checked by the test of7.5.2 (without humidity preconditioning) for basicinsulation; and

P

Page 12: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

b) by performing a dielectric strength test as per7.5.2 (without humidity preconditioning) in the fol-lowing cases:

P

i) on reinforced or double Insulation, using the testlevel for Basic insulation, and

P

ii) on basic insulation in Protective Class I equip-ment, using the test level for Basic insulation, un-less it can be determined that the fault did not re-sult in any damage to the protective earthing con-ductor or terminal, or to protective bonding means;and

P

c) by inspection to ensure a fuse connected be-tween the protective earthing terminal and the pro-tective earthing conductor in the test setup has notopened; the fuse shall be rated 3A non-time-delay(for equipment rated for use on circuits protectedby overcurrent protection rated 30A or less) or 30Ato 35A non-time-delay(for equipment rated for useon circuits protected by overcurrent protection ratedmore than 30A); the enclosure is not to be contact-ing earth in any other location during the testing;and

P

d) by inspection of the enclosure to ensure that nodamage has resulted that allows access to partsthat are hazardous live.

P

4.4.3.2 Protection against the spread of fire P

Compliance with requirements for protectionagainst the spread of fire is checked by placing theequipment on white tissue-paper covering a soft-wood surface and covering the equipment withcheesecloth or surgical cotton during the fault test-ing. As an alternative, the cheesecloth or surgicalcotton may be placed only over the openings oflarge equipment.

P

There shall be no emission of molten metal, burn-ing insulation, or flaming or glowing particles fromthe fire enclosure, and there shall be no charring,glowing, or flaming of the tissue paper, cheese-cloth, or glowing or flaming of surgical cotton.

P

4.4.3.3 Protection against other hazards P

Conformity with requirements for protection againstother HAZARDS after application of the fault testsis checked as specified elsewhere in this standard.

P

4.4.3.4 Protection against parts expulsion hazards P

Page 13: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Failure of any component within the PCE shall notrelease parts outside the PCE enclosure with suffi-cient energy to lead to a hazard, for example, ex-pulsion of material into an area occupied by per-sonnel.

P

4.4.4 Single Fault conditions to be applied P

4.4.4.1 Component fault tests (see appended table) P

The following faults are simulated: P

a) Short circuit or open circuit of relevant compo-nents

P

b) Short circuit or open circuit of any componentsor insulation where failure could adversely affectsupplementary insulation or reinforced insulation.

P

c) In addition, where required by Method 2 of 9.1.1,components that could result in a fire hazard are tobe overloaded unless they comply with the re-quirements of 9.1.3

P

4.4.4.2 Equipment or parts for short-term or intermittentoperation

Not for short-term or intermit-tent operation

N/A

Components such as motors, relays, other elec-tromagnetic devices and heaters, which are nor-mally operated only intermittently, shall be operatedcontinuously if continuous operation could occur ina single fault conditions.

No components normally op-erated only intermittently

N/A

4.4.4.3 Motors P

Motors shall be stopped while fully energized orprevented from starting, whichever is less favoura-ble.

DC fans are tested. P

4.4.4.4 Transformer short circuit tests (see appended table) P

The output windings of transformers shall be short-circuited one at a time. A transformer damagedduring one test may be repaired or replaced beforethe next test.

P

4.4.4.5 Output short circuit P

Page 14: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Testing is required to be performed on all combina-tions of terminals for the port under consideration,two at a time, including neutral and earth terminals,and one test with all current-carrying terminals ofthe port shorted together at once.

(1) Grid output

(2) Battery output

(3) Load output

Above three combinations ofoutput terminals are testedone a time.

The AC output short-circuitcurrent is 319Apeak impulse(0.7ms, duration) when singlefault (1) was applied.

The battery output short-circuitcurrent is 950Apeak impulse(2.2ms, duration) when singlefault (2) was applied.

The load output short-circuitcurrent is 45.8Apeak impulse(164.5ms, duration) when sin-gle fault (3) was applied.

P

the short-circuit currents are to be recorded and ifthey exceed the maximum rated current of the cir-cuit, the maximum measured current shall be pro-vided in the installation manual for the purpose ofcoordination of overcurrent protection of the exter-nal circuit conductors.

P

4.4.4.6 Backfeed current test P

For equipment intended to be connected simulta-neously to more than one source of supply, eachinput of the PCE shall be tested one at a time, todetermine if hazardous conditions can result fromcurrent from one source of supply flowing into thewiring for another source under fault conditions.

DC (PV and battery) and ACconsider as source of supply.

P

With the PCE operating under normal conditions, ashort circuit shall be applied at the field wiring ter-minals of the circuit under consideration, with all in-tended other sources connected to the PCEthrough the over current protective devices (if any)intended to be present in the installation.

P

the short-circuit currents are to be recorded and ifthey exceed the maximum rated current for theport, the maximum measured current shall be pro-vided in the installation manual for the purpose ofcoordination of overcurrent protection of the exter-nal circuit conductors

The AC input short-circuit cur-rent is 94Apeak impulse(0.09ms).

The battery input short-circuitcurrent is 1048Apeak impulse(2.0ms).

The PV input short-circuit cur-rent is 85.8Apeak impulse(0.25ms).

P

4.4.4.7 Output overload P

Page 15: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Each output of the PCE, and each section of atapped output, shall be overloaded in turn, one at atime. The other windings are loaded or not loaded,whichever load condition of normal use is less fa-vorable. Overloading is carried out by connecting avariable resistor across the winding. The resistor isadjusted as quickly as possible and readjusted, ifnecessary, after 1 min to maintain the applicableoverload. No further readjustments are then permit-ted.

P

If over-current protection is provided by a current-sensitive device or circuit, the overload test currentis the maximum current which the over-current pro-tection device is just capable of passing for 1 h. Ifthis value cannot be derived from the specification,it is to be established by test. Before the test, thedevice is made inoperative or replaced by a linkwith negligible impedance.

N/A

For equipment in which the output voltage is de-signed to collapse when a specified overload cur-rent is reached, the overload is slowly increased tothe point of maximum output power before the pointwhich causes the output voltage to collapse.

P

In all other cases, the loading is the maximumpower output obtainable from the output.

P

4.4.4.8 Cooling system failure P

4.4.4.9 Heating devices No heating devices used N/A

In equipment incorporating heating devices, the fol-lowing faults shall be applied one at a time:

a) timers which limit the heating period shall beoverridden to energize the heating circuit continu-ously;

b) temperature control devices or circuits shall havesingle fault conditions applied such that controlover the heater is lost. Over-temperature protectiondevices meeting the requirements of 14.3 are leftoperational during the test.

N/A

4.4.4.10 Safety interlock No safety interlock N/A

4.4.4.11 Reverse d.c. connections (see appended table) P

4.4.4.12 Voltage selector mismatch No voltage selector N/A

4.4.4.13 Mis-wiring with incorrect phase sequence or polari-ty

(see appended table) P

4.4.4.14 PWB short-circuit test P

4.5 Humidity preconditioning P

4.5.1 General P

4.5.2 Conditions P

Page 16: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Relative humidity (%), temperature (°C) 92.5% RH., 40 °C, 48 h P

4.6 Voltage Backfeed protection P

4.6.1 Backfeed tests under normal conditions The PV input terminal is notaccessible to people after in-stallation. The discharge timeafter disconnection from DCand AC sources is tested in Cl.7.3.9.2.For service access, the unitwas marked with dischargetime

P

4.6.2 Backfeed tests under single-fault condtions P

4.6.3 Compliance with backfeed tests P

The PCE is compliant with the requirements if dur-ing the tests in 4.6.1 and 4.6.2 no hazardous volt-age or energy is present on the PCE terminals forthe source under test.

Measurements are taken 15 s or 1 s after thesource is de-energized or disconnected, as follows:

P

- 15 s for sources that are connected by fixed wir-ing

P

- 1 s for sources that are cord-connected or useconnectors that can be opened without the use of atool

N/A

4.7 Electrical ratings tests P

4.7.1 Input ratings (see appended table) P

4.7.1.1 Measurement requirements for DC input ports P

4.7.2 Output ratings P

5 MARKING AND DOCUMENTATION P

5.1 Marking P

5.1.1 General P

Equipment shall bear markings as specified in 5.1and 5.2

Label are marked on the PCEand graphic symbol is ex-plained in user manual

P

Graphic symbols may be used and shall be in ac-cordance with Annex C or IEC 60417 as applicable.

P

Graphic symbols shall be explained in the docu-mentation provided with the PCE.

P

5.1.2 Durability of markings P

Page 17: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Markings required by this clause to be located onthe PCE shall remain clear and legible under condi-tions of NORMAL USE and resist the effects ofcleaning agents specified by the manufacturer

P

5.1.3 Identification P

The equipment shall, as a minimum, be permanent-ly marked with:

P

a) the name or trade mark of the manufacturer orsupplier

Trade mark P

b) model number, name or other means to identifythe equipment

Model number P

c) a serial number, code or other marking allowingidentification of manufacturing location and themanufacturing batch or date within a threemonth time period.

See marking label P

5.1.4 Equipment ratings See below P

Unless otherwise specified in another part of IEC62109, the following ratings, as applicable shall bemarked on the equipment:

Special requirement as perIEC 62109-2.

P

input voltage, type of voltage (a.c. or d.c.), fre-quency, and max. continuous current for eachinput

Refer to the marking label P

output voltage, type of voltage (a.c. or d.c.),frequency, max. continuous current, and fora.c. outputs, either the power or power factorfor each output

Refer to the marking label P

the ingress protection (IP) rating as in 6.3 be-low

IP20 P

5.1.5 Fuse identification P

Marking shall be located adjacent to each fuse orfuseholder, or on the fuseholder, or in another loca-tion provided that it is obvious to which fuse themarking applies, giving the fuse current rating andwhere fuses of different voltage rating value couldbe fitted, the fuse voltage rating.

N/A

Where fuses with special fusing characteristicssuch as time delay or breaking capacity are neces-sary, the type shall also be indicated

N/A

For fuses not located in operator access areas andfor soldered-in fuses located in operator access ar-eas, it is permitted to provide an unambiguouscross-reference (for example, F1, F2, etc.) to theservicing instructions which shall contain the rele-vant information.

P

Page 18: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

5.1.6 Terminals, Connections, and Controls PV input, grid connection, loadconnection, battery connectionand communication interface

P

If necessary for safety, an indication shall be givenof the purpose of Terminals, connectors, controls,and indicators, and their various positions, includ-ing any connections for coolant fluids such as waterand drainage. The symbols in Annex C may beused, and where there is insufficient space, symbol9 of Annex C may be used.

Symbol 9 are marked on thePCE and user manual indicatethe installation and safety ofconnection of connector, con-trol and indicator.

P

Push-buttons and actuators of emergency stop de-vices, and indicator lamps used only to indicate awarning of danger or the need for urgent actionshall be coloured red.

No emergency stop N/A

A multiple-voltage unit shall be marked to indicatethe particular voltage for which it is set whenshipped from the factory. The marking is allowed tobe in the form of a paper tag or any other nonper-manent material.

No setting is accessible to us-er

N/A

A unit with d.c. terminals shall be plainly markedindicating the polarity of the connections, with:

See below P

- The PV input and battery ter-minals for each module andwhole unit are silk-screen with

- fornegative

P

a pictorial representation illustrating the properpolarity where the correct polarity can be un-ambiguously determined from the representa-tion

Not provided N/A

5.1.6.1 Protective Conductor Terminals P

The means of connection for the protective earthingconductor shall be marked with:

The PE terminal is connectedvia AC output cable

N/A

symbol 7 of Annex C; or P

N/A

the colour coding green-yellow. P

5.1.7 Switches and circuit-breakers P

The on and off-positions of switches and circuitsbreakers shall be clearly marked. If a push-buttonswitch is used as the power switch, symbols 10 and16 of Annex C may be used to indicate the on-position, or symbols 11 and 17 to indicate the off-position, with the pair of symbols (10 and 16, or 11and 17) close together.

P

5.1.8 Class Equipment Class I N/A

Page 19: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Equipment using Class protective meansthroughout shall be marked with symbol 12 of An-nex C. Equipment which is only partially protectedby DOUBLE INSULATION or REINFORCEDINSULATION shall not bear symbol 12 of TableAnnex C.

N/A

Where such equipment has provision for the con-nection of an earthing conductor for functional rea-sons (see 7.3.6.4) it shall be marked with symbol 6of Annex C

N/A

5.1.9 Terminal boxes for External Connections No such terminal boxes. N/A

Where required by note 1 of Table 2 as a result ofhigh temperatures of terminals or parts in the wiringcompartment, there shall be a marking, visible be-side the terminal before connection, of either:

N/A

a) the minimum temperature Rating and size ofthe cable to be connected to the TERMINALS;or

N/A

b) a marking to warn the installer to consult the in-stallation instruction. Symbol 9 of Table D-1 isan acceptable marking

N/A

5.2 Warning markings P

5.2.1 Visibility and legibility requirements for warningmarkings

P

Warning markings shall be legible, and shall haveminimum dimensions as follows:

P

Printed symbols shall be at least 2.75 mm high P

Printed text characters shall be at least 1.5 mmhigh and shall contrast in colour with the back-ground

P

Symbols or text that are moulded, stamped orengraved in a material shall have a characterheight of at least 2,0 mm, and if not contrastingin colour from the background, shall have adepht or raised height of at least 0,5 mm.

N/A

If it is necessary to refer to the instruction manualto preserve the protection afforded by the equip-ment, the equipment shall be marked with symbol 9of Annex C

The manual provide necessaryinformation for the warningmarking.

P

Symbol 9 of Annex C is not required to be used ad-jacent to symbols that are explained in the manual

P

5.2.2 Content for warning markings P

5.2.2.1 Ungrounded heatsinks and similar parts Ungrounded heatsink P

Page 20: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

An ungrounded heat sink or other part that may bemistaken for a grounded part and involves a risk ofelectric shock in accordance with 7.3 shall bemarked with symbol 13 of Annex C, or equivalent.The marking may be on or adjacent to the heatsinkand shall be clearly visible when the PCE is disas-sembled to the extent that a risk of contact with theheatsink exists.

Symbol 13 marked onheatsink

P

5.2.2.2 Hot Surfaces N/A

A part of the PCE that exceeds the temperaturelimits specified in 4.3.2 shall be marked with sym-bol 14 of Annex C or equivalent.

N/A

5.2.2.3 Coolant Coolant is not used N/A

A unit containing coolant that exceeds 70 °C shallbe legibly marked externally where readily visibleafter installation with symbol 15 of Annex C. Thedocumentation shall provide a warning regardingthe risk of burns from hot coolant, and either:

N/A

a) statement that coolant system servicing is to bedone only by SERVICE PERSONNEL, or

N/A

b) instructions for safe venting, draining, or other-wise working on the cooling system, if theseoperations can be performed withoutOPERATOR access to HAZARDS internal tothe equipment

N/A

5.2.2.4 Stored energy P

Where required by 7.3.9.2 or 7.4.2 the PCE shallbe marked with Symbol 21 of Annex C and the timeto discharge capacitors to safe voltage and energylevels shall accompany the symbol.

Symbol 21 is marked on PCE P

5.2.2.5 Motor guarding P

Where required by 8.2 a marking shall be providedwhere it is visible to service personnel before re-moval of a guard, warning of the hazard and givinginstructions for safe servicing (for example discon-nection of the source before removing the guard).

It is not accessible by finger. P

5.2.3 Sonic hazard markings and instructions No sonic hazard N/A

If required by 10.2.1 a PCE shall: N/A

a) be marked to warn the operator of the sonicpressure hazard; or

N/A

Page 21: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

b) be provided with installation instructions thatspecify how the installer can ensure that thesound pressure level from equipment at itspoint of use after installation, will not reach avalue, which could cause a hazard. These in-structions shall include the measured soundpressure level, and shall identify readily availa-ble and practicable protective materials ormeasures which may be used.

N/A

5.2.4 Equipment with multiple sources of supply PV array, battery and ACmains.

P

A PCE with connections for multiple energysources shall be marked with symbol 13 of AnnexC and the manual shall contain the information re-quired in 5.3.4.

Symbol 13 provided on PCE P

The symbol shall be located on the outside of theunit or shall be prominently visible behind any cov-er giving access to hazardous parts.

P

5.2.5 Excessive touch current N/A

Where required by 7.3.6.3.7 the PCE shall bemarked with symbol 15 of Annex C. See also 5.3.2for information to be provided in the installationmanual.

N/A

5.3 Documentation P

5.3.1 General P

The documentation provided with the PCE shallprovide the information needed for the safe opera-tion, installation, and (where applicable) mainte-nance of the equipment. The documentation shallinclude the items required in 5.3.2 through 5.3.4,and the following:

P

a) explanations of equipment makings, includingsymbols used

P

b) location and function of terminals and controls P

c) all ratings or specifications that are necessaryto safely install and operate the PCE, includingthe following environmental ratings along withan explanation of their meaning and any result-ing installation requirements:

P

ENVIRONMENTAL CATEGORY as per 6.1 Indoor P

WET LOCATIONS classification fort he in-tended external environment as per 6.1

Suitable for dry location P

POLLUTION DEGREE classification for theintended external environment as per 6.2

2 P

INGRESS PROTECTION rating as per 6.3 IP20 P

Page 22: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Ambient temperature and relative humidityratings

Max. 40 °C and 90%RH P

MAXIMUM altitude rating Up to 2000 m P

OVERVOLTAGE CATEGORY assigned toeach input and output port as per7.3.7.1.2, accompanied by guidance re-garding how to ensure that the installationcomplies with the required overvoltage cat-egories;

OVC II (PV), OVC III (Mains) P

d) a warning that when the photovoltaic array isexposed to light, it supplies a d.c. voltage to thePCE

P

5.3.1.1 Language English provide P

Instructions related to safety shall be in a languagethat is acceptable in the country where the equip-ment is to be installed.

For other country language,further evaluation is needed.

N/A

5.3.1.2 Format P

In general, the documentation must be provided inprinted form and is to be delivered with the equip-ment.

Printed form provided and is tobe delivered with equipment

P

For equipment which requires the use of a comput-er for both installation and operation, documenta-tion may be provided in electronic format withoutaccompanying printed format.

P

5.3.2 Information related to installation P

The documentation shall include installation andwhere applicable, specific commissioning instruc-tions and, if necessary for safety, warnings againsthazards which could arise during installation orcommissioning of the equipment. The informationprovided shall include:

P

a) assembly, location, and mounting require-ments:

P

b) ratings and means of connection to eachsource of supply and any requirements relatedto wiring and external controls, colour coding ofleads, disconnection means, or overcurrentprotection needed, including instructions thatthe installation position shall not prevent accessto the disconnection means;

P

c) ratings and means of connection of any outputsfrom the PCE, and any requirements related towiring and externals controls, colour coding ofleads, or overcurrent protection needed;

P

d) explanation of the pin-out of connectors for ex-ternal connections, unless the connector isused for a standard purpose (e.g. RS 232)

P

Page 23: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

e) ventilation requirements; P

f) requirements for special services, for examplecooling liquid;

No cooling liquid or other spe-cial service

N/A

g) instructions and information relating to soundpressure level if required by 10.2.1;

N/A

h) where required by 14.8.1.3, instructions for theadequate ventilation of the room or location inwhich PCE containing vented or valve-regulated batteries is located, to prevent theaccumulation of hazardous gases;

No such battery N/A

i) tightening torque to be applied to wiring termi-nals;

P

j) values of backfeed short-circuit currents availa-ble from the PCE on input and output conduc-tors under fault conditions, if those currents ex-ceeds the max. rated current of the circuit, asper 4.4.4.6;

P

k) for each input to the PCE, the max value ofshort-circuit current available from the source,for which the PCE is designed; and

P

l) compatibility with RCD and RCM; N/A

m) instructions for protective earthing, includingthe information required by 7.3.6.3.7 if a sec-ond protective earthing conductor is to be in-stalled:

Provided in the installationmanual.

P

n) where required by 7.3.8, the installation instruc-tions shall include the following or equivalentwording:

N/A

external protective earthing conductor. Where aresidual current-operated protective (RCD) ormonitoring (RCM) device is used for protectionin a case of direct or indirect contact, only anRCD or RCM of Type B is allowed on the sup-ply side of this prod

N/A

o) for PCE intended to charge batteries, the bat-tery nominal voltage rating, size, and type

P

p) PV array configuration information, such as rat-ings, whether the array is to be grounded orfloating, any external protection devices need-ed, etc.

P

5.3.3 Information related to operation P

Instructions for use shall include any operating in-structions necessary to ensure safe operation, in-cluding the following, as applicable:

P

Page 24: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Instructions for adjustment of controls includingthe effects of adjustment;

P

Instructions for interconnection to accessoriesand other equipment, including indication ofsuitable accessories, detachable parts and anyspecial materials;

P

Warnings regarding the risk of burns from sur-faces permitted to exceed the temperature lim-its of 4.3.2 and required operator actions to re-duce the risk; and

P

Instructions, that if the equipment is used in amanner not specified by the manufacturer, theprotection provided by the equipment may beimpaired.

P

5.3.4 Information related to maintenance P

Maintenance instructions shall include the follow-ing:

P

Intervals and instructions for any preventivemaintenance that is required to maintain safety(for example air filter replacement or periodicre-tightening of terminals);

P

Instructions for accessing operator access are-as, if any are present, including a warning notto enter other areas of the equipment;

P

Part numbers and instructions for obtaining anyrequired operator replaceable parts;

No replaceable parts N/A

Instructions for safe cleaning (if recommended) P

Where there is more than one source of supplyenergizing the PCE, information shall be pro-vided in the manual to indicate which discon-nect device or devices are required to be oper-ated in order to completely isolate the equip-ment.

P

5.3.4.1 Battery maintenance No energy storage battery in-side

N/A

Where required by 14.8.5, the documentation shallinclude the applicable items from the following listof instructions regarding maintenance of batteries:

N/A

Servicing of batteries should be performed orsupervised by personnel knowledgeable aboutbatteries and the required precautions

N/A

When replacing batteries, replace with thesame type and number of batteries or batterypacks

N/A

Page 25: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

General instructions regarding removal and in-stallation of batteries

N/A

CAUTION: Do not dispose of batteries in a fire.The batteries may explode.

N/A

CAUTION: Do not open or damage batteries.Released electrolyte is harmful to the skin andeyes. It may be toxic.

N/A

CAUTION: A battery can present a risk of elec-trical shock and high short-circuit current. Thefollowing precautions should be observed whenworking on batteries:

N/A

a) Remove watches, rings, or other metal objects. N/A

b) Use tools with insulated handles. N/A

c) Wear rubber gloves and boots. N/A

d) Do not lay tools or metal parts on top of batter-ies

N/A

e) Disconnect charging source prior to connectingor disconnecting battery terminals

N/A

f) Determine if battery is inadvertently grounded.If inadvertently grounded, remove source fromground. Contact with any part of a groundedbattery can result in electrical shock. The likeli-hood of such shock can be reduced if suchgrounds are removed during installation andmaintenance (applicable to equipment and re-mote battery supplies not having a groundedsupply circuit).

N/A

6 ENVIRONMENTAL REQUIREMENTS AND CONDITIONS P

The manufacturer shall rate the PCE for the follow-ing environmental conditions:

P

ENVIRONMENTAL CATEGORY, as in 6.1 be-low

Indoor use P

Suitability for WET LOCATIONS or not Suitability for dry locations P

POLLUTION DEGREE rating in 6.2 below PD2 P

INGRESS PROTECTION (IP) rating, as in 6.3below

IP20 P

Ultraviolet (UV) exposure rating, as in 6.4 be-low

Indoor use N/A

Ambient temperature and relative humidity rat-ings, as in 6.5 below

P

6.1 Environmental categories and minimum environmental conditions P

6.1.1 Outdoor N/A

Page 26: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

6.1.2 Indoor, unconditioned N/A

6.1.3 Indoor, conditioned P

6.2 Pollution degree PD2 P

6.3 Ingress Protection IP20 P

6.4 UV exposure N/A

6.5 Temperature and humidity Max. 40 °C and 90%RH P

7 PROTECTION AGAINST ELECTRIC SHOCK AND ENERGY HAZARDS P

7.1 General P

7.2 Fault conditions Normal and single fault condi-tion are considered

P

7.3 Protection against electric shock P

7.3.1 General In the PCE the earthed metalenclosure is evaluated bymeans of basic insulation fromDVC C circuit.

DVC A circuit and unearthedaccessible parts are evaluatedby means of double insulationor reinforce insulation fromDVC C.

DVC C: The PV input andmains output.

DVC A: the communication in-terface.

P

7.3.2 Decisive voltage classification P

7.3.2.1 Use of decisive voltage class (DVC) Working voltage and protec-tive measures are considered.

P

7.3.2.2 Limits of DVC (according table 6) P

7.3.2.3 Short-terms limits of accessible voltages under faultconditions

P

7.3.2.4 Requirements for protection (according table 7) Single fault condition is con-sidered. Accessible earthedconductive parts are separat-ed from DVC-C circuits bybasic insulation. Accessibleunearthed conductive partsseparated from DVC C circuitby double insulation.

P

7.3.2.5 Connection to PELV and SELV circuits The external signal communi-cation interface are consideredas SELV

P

7.3.2.6 Working voltage and DVC P

Page 27: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

7.3.2.6.1 General Transients and voltagefluctuations are disregarded.And worst case normaloperating condition isconsidered

P

7.3.2.6.2 AC working voltage (see Figure 2) 230 Vr.m.s considered P

7.3.2.6.3 DC working voltage (see Figure 3) Max. DC open voltage: 550 V P

7.3.2.6.4 Pulsating working voltage (see Figure 4) N/A

7.3.3 protective separation See description in Cl. 7.3.1 P

Protective separation shall be achieved by: P

double or reinforced insulation, or P

protective screening, i.e. by a conductivescreen connected to earth by protective bond-ing in the PCE, or connected to the protectiveearth conductor itself, whereby the screen isseparated from live parts by at least basic insu-lation, or

P

protective impedance comprising limitation ofcurrent per 7.3.5.3 and of discharged energyper 7.3.5.4, or

P

limitation of voltage according to 7.3.5.4. N/A

The protective separation shall be fully and effec-tively maintained under all conditions of intendeduse of the PCE

P

7.3.4 Protection against direct contact P

7.3.4.1 General P

Protection against direct contact is employed toprevent persons from touching live parts that do notmeet the requirements of 7.3.5 and shall be provid-ed by one or more of the measure given in 7.3.4.2(enclosures and barriers) and 7.3.4.3 (insulation).

Enclosure provided P

Open type sub-assemblies and devices do not re-quire protective measures against direct contactbut the instruction provided with the equipmentmust indicate that such measures must be providedin the end equipment or in the installation.

End use product N/A

Product intended for installation in CLOSEDELECTRICAL OPERATING AREAS, (see 3.9)need not have protective measures against directcontact, except as required by 7.3.4.2.4.

No use under this condition N/A

7.3.4.2 Protection by means of enclosures and barriers P

The following requirements apply where protectionagainst contact with live parts is provided by enclo-sures or barriers, not by insulation in accordancewith 7.3.4.3.

Enclosure provided to preventaccess to inside live parts

P

Page 28: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

7.3.4.2.1 General P

Parts of enclosures and barriers that provide pro-tection in accordance with these requirements shallnot be removable without the use of a tool (see7.3.4.2.3).

Secured by screws P

Polymeric materials used to meet these require-ments shall also meet the requirements of 13.6

P

7.3.4.2.2 Access probe criteria P

Protection is considered to be achieved when theseparation between the test probes and live parts,when tested as described below, is as follows:

P

a) decisive voltage classification A, (DVC A) - theprobe may touch the live parts

The communication interfaceis considered as DVC A

P

b) decisive voltage classification B, (DVC B) - theprobe must not touch bare live parts

The DVC B circuit is not ac-cessible by probe

P

c) decisive voltage classification C, (DVC C) theprobe must have adequate clearance to liveparts, based on the clearance for Basic insula-tion using the recurring peak working voltageinvolved,

The DVC C circuit is not ac-cessible by probe

P

7.3.4.2.3 Access probe tests P

Compliance with 7.3.4.2.1 is checked by all of thefollowing:

P

a) Inspection; and P

b) Tests with the test finger (Figure D.1) and testpin (Figure D.2) of 0E, the results of which shallcomply with the requirements of 7.3.4.2.1 a),b), and c) as applicable. Probe tests are per-formed on openings in the enclosures after re-moval of parts that can be detached or openedby an operator without the use of a tool, includ-ing fuseholders, and with operator accessdoors and covers open. It is permitted to leavelamps in place for this test. Connectors that canbe separated by an operator without use of atool, shall also be tested during and after dis-connection. Any movable parts are to be put inthe most unfavorable position.

P

The test finger and the test pin are applied asabove, without appreciable force, in every pos-sible position, except that floor-standing equip-ment having a mass exceeding 40 kg is not tilt-ed.

P

Page 29: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Equipment intended for building-in or rackmounting, or for incorporation in larger equip-ment, is tested with access to the equipmentlimited according to the method of mounting de-tailed in the installation instructions.

N/A

c) Openings preventing the entry of the jointedtest finger ( Figure E-1 of 0E) during test b)above, are further tested by means of straightunjointed test finger (Figure E-3 of 0E), appliedwith a force of 30 N. If the unjointed finger en-ters, the test with the jointed finger is repeatedexcept that the finger is applied using any nec-essary force up to 30 N.

air-intakes for cooling fans. P

d) In addition to a) c) above, top surfaces of en-closure shall be tested with the IP3X probe ofIEC 60529. The test probe shall not penetratethe top surface of the enclosure when probedfrom the vertical direction ±5 ° only.

N/A

7.3.4.2.4 Service access areas 16.1 s@60 V bus after dis-connecting DC side.Inside PCE are not intentional-ly touched with energizedparts when installation andmaintenance. Symbol 21 ofAnnex C are marked on PCEand explained in user manual.

P

7.3.4.3 Protection by means of insulation of live parts The earthed enclosure is withbasic insulation from the liveparts inside

P

Where the requirements of 7.3.4.2 are not met, liveparts shall be provided with insulation if:

P

their working voltage is greater than the maxi-mum limit of decisive voltage class A, or

P

for a DVC A or B circuit, protective separationfrom adjacent circuit of DVC C is not provided

P

7.3.5 Protection in case of direct contact The communication interfaceare direct contact and evaluat-ed with double insulation fromlive parts

P

7.3.5.1 General P

Protection in case of direct contact is required toensure that contact with live parts does not producea shock hazard.

P

The protection against direct contact according to7.3.4 is not required if the circuit contacted is sepa-rated from other circuits according to 7.3.2.3, and:

Considered P

Page 30: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

is of decisive voltage class A and complies with7.3.5.2, or

The communication interfaceis DVC A and double insula-tion from the live parts bymeans of isolation transformerwith isolation power supplyand opto-coupler

P

is provided with protective impedance accord-ing to 7.3.5.3, or

At least four resistors (total re-sistance >2.4voltage sampling.

P

is limited in voltage according to 7.3.5.4 N/A

In addition to the measures as given in 7.3.5.2 to7.3.5.4, it shall be ensured that in the event of erroror polarity reversal of connectors no voltages thatexceed DVC A can be connected into a circuit withprotective separation. This applies for example toplug-in-sub-assemblies or other plug-in deviceswhich can be plugged-in without the use of a tool(key) or which are accessible without the use of atool.

Considered P

Conformity is checked by visual inspection and trialinsertion.

P

7.3.5.2 Protection using decisive voltage class A The communication interfaceis DVC A and double insula-tion from the live parts bymeans of isolation transformerwith isolation power supplyand opto-coupler

P

7.3.5.3 Protection by means of protective impedance At least five resistors (total re-sistance > 5

P

Circuits and conductive parts do not require protec-tion against direct contact if any connection to cir-cuits of DVC-B or DVC-C is through protective im-pedance, and the accessible circuit or part is oth-erwise provided with protective separation from cir-cuits of DVC-B or DVC-C according 7.3.3.

P

7.3.5.3.1 Limitation of current through protective impedance P

The current available through protective impedanceto earth and between simultaneously accessibleparts, measured at the accessible live parts, shallnot exceed a value of 3,5 mA a.c. or 10 mA d.c.under normal and single-fault conditions.

P

7.3.5.3.2 Limitation of discharging energy through protectiveimpedance

P

Page 31: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

The discharging energy available between simulta-neously accessible parts protected by protectiveimpedance shall not exceed the charging voltageand capacitance limits given in Table 9, which ap-plies to both wet and dry locations, under normaland single fault conditions. Refer to figure 8.

P

7.3.5.4 Protection by means of limited voltages No such design N/A

That portion of a circuit that has its voltage reducedto DVC-A by a voltage divider that complies withthe following requirements, and that is otherwiseprovided with protective separation from circuits ofDVC-B or DVC-C according to 7.3.3, does not re-quire protection against direct contact.

N/A

The voltage divider shall be designed so that undernormal and single fault conditions, including faultsin the voltage division circuit, the voltage across theoutput of the voltage divider does not exceed thelimit for DVC-A.

N/A

This type of protection shall not be used in case ofprotective class II or unearthed circuits, because itrelies on protective earth being connected.

N/A

7.3.6 Protection against indirect contact P

7.3.6.1 General P

Protection against indirect contact is required toprevent shock- hazardous current being accessiblefrom conductive parts during an insulation failure.This protection shall comply with the requirementsfor protective class I (basic insulation plus protec-tive earthing), class II (double or reinforced insula-tion) or class III (limitation of voltages)

P

That part of a PCE meets the requirements of7.3.6.2 and 7.3.6.3 is defined as protective class I

The earthed metal enclosuremeet this requirement

P

That part of a PCE meets the requirements of7.3.6.4 is defined as protective class II.

The communication interfaceis double insulated from liveparts inside.

P

That part of PCE which meets the requirements ofdecisive voltage class A and in which no hazardousvoltages are derived, is defined as protective classIII. No shock hazard is present in such circuits.

N/A

Where protection against indirect contact is de-pendent on means provided during installation, theinstallation instructions shall provide details of therequired means and shall indicate the associatedhazards.

The manual require the PCEmust be securely earthed

P

7.3.6.2 Insulation between live parts and accessible con-ductive parts

See Cl. 7.3.7.4 and Cl. 7.3.7.5 P

Page 32: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Accessible conductive parts of equipment shall beseparated from live parts by insulation meeting therequirements of Table 7 or by clearances as speci-fied in 7.3.7.4 and creepages as specified in 7.3.7.5

P

7.3.6.3 Protective class I Protective bonding and earthing P

7.3.6.3.1 General P

Equipment of protective class I shall be providedwith protective earthing, and with protective bond-ing to ensure electrical contact between accessibleconductive parts and the means of connection forthe external protective earthing conductor, exceptbonding is not required for:

P

a) accessible conductive parts that are protectedby one of the measures in 7.3.5.2 to 7.3.5.4, or

N/A

b) accessible conductive parts are separated fromlive parts of DVC-B or -C using double or rein-forced insulation.

P

7.3.6.3.2 Requirements for protective bonding P

Electrical contact with the means of connection ofthe external protective earthing conductor shall beachieved by one or more of the following means:

The PCE provide internal andexternal optional earthingscrews for protective earthing.

P

a) through direct metallic contact; P

b) through other conductive parts which are notremoved when the PCE or sub-units are usedas intended ;

N/A

c) through a dedicated protective bonding conduc-tor;

P

d) through other metallic components of the PCE N/A

Where direct metallic contact is used and one orboth of the parts involved is painted or coated, thepaint or coating shall be removed in the area ofcontact, or reliably penetrated, to ensure metal tometal contact.

P

For moving or removable parts, hinges or slidingcontacts designed and maintained to have a lowresistance are examples of acceptable means ifthey comply with the requirements of 7.3.6.3.3.

No such design N/A

Metal ducts of flexible or rigid construction and me-tallic sheaths shall not be used as protective bond-ing conductors, unless the device or material hasbeen investigated as suitable for protective bondingpurposes.

No such design N/A

7.3.6.3.3 Rating of protective bonding P

Page 33: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Protective bonding shall withstand the highestthermal and dynamic stresses that can occur to thePCE item(s) concerned when they are subjected toa fault connecting live parts to accessible conduc-tive parts.

The protective bonding shall remain effective for aslong as a fault to the accessible conductive partspersists or until an upstream protective device re-moves power from the part.

P

Protective bonding shall meet following require-ments:

P

a) For PCE with an overcurrent protective devicerating of 16 A or less, the impedance of theprotective bonding means shall not exceed 0,1

elow.

N/A

b) For PCE with an overcurrent protective devicerating of more than 16 A, the voltage drop inthe protective bonding test shall not exceed2,5 V during or at the end of the test below.

P

As alternative to a) and b) the protective bondingmay designed according to the requirements for theexternal protective earthing conductor in 7.3.6.3.5,in which case no testing is required.

P

The impedance of protective bonding means shallbe checked by passing a test current through thebond for a period of time as specified below. Thetest current is based on the rating of the overcur-rent protection for the equipment or part of theequipment under consideration, as follows:

P

a) For pluggable equipment type A, the overcur-rent protective device is that provided externalto the equipment (for example, in the buildingwiring, in the mains plug or in an equipmentrack);

N/A

b) For pluggable equipment type B and fixedequipment, the maximum rating of the overcur-rent protective device specified in the equip-ment installation instructions to be provided ex-ternal to the equipment;

Fixed equipment P

c) For a circuit or part of the equipment for whichan overcurrent protective device is provided aspart of the equipment, the rating of the provid-ed overcurrent device.

N/A

Page 34: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Voltages are measured from the protective earthingterminal to all parts whose protective bondingmeans are being considered. The impedance of theprotective earthing conductor is not included in themeasurement. However, if the protective earthingconductor is supplied with the equipment, it is per-mitted to include the conductor in the test circuit butthe measurement of the voltage drop is made onlyfrom the main protective earthing terminal to theaccessible part required to be earthed.

Measured from the farthestpart of earthed metal enclo-sure to the input earth terminal

P

On equipment where the protective earthconncection to a subassembly or to a separate unitis part of a cable that also supplies power to thatsubassembly or unit, the resistance of the protec-tive bonding conductor in that cable is not includedin the protective bond impedance measurementsfor the subassembly or separate unit, as shown inFigure 11. However, this option is only permitted ifthe cab le is protected by a suitably rated protectivedevice that takes into account the size of the con-ductor. Otherwise the impedance of the protectivebonding conductor between the separate units is tobe included, by measuring to the protective earth-ing terminal where the power source enters the firstunit in the system, as shown in Figure 12.

Figure 11 used P

7.3.6.3.3.1 Test current, duration, and acceptance criteria P

The test current, duration of the test and ac-ceptance criteria are as follows:

P

a) For PCE with an overcurrent protective devicerating of 16 A or less, the test current is 200%of the overcurrent protective device rating, butnot less than 32 A, applied for 120s. The im-pedance of the protective bonding means dur-ing and at the end of the test shall not exceed

N/A

b) For PCE with an overcurrent protective devicerating of more than 16 A, the test current is200% of the overcurrent protective device rat-ing and the duration of the test is as shown inTable 10 below. The voltage drop in the protec-tive bonding means, during and at the end ofthe test, shall not exceed 2,5 V.

0.25 V P

c) During and after the test, there shall be nomelting, loosening, or other damage that wouldimpair the effectiveness of the protective bond-ing means.

P

The test current is derived from an a.c or d.c supplysource, the output of which is not earthed.

DC supply P

Page 35: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

As an alternative to Table 10, where the time-current characteristic of the overcurrent protectivedevice that limits the fault current in the protectivebonding means is known because the device is ei-ther provided in the equipment or fully specified inthe installation instructions, the test duration may

s time-currentcharacteristic. The tests are conducted for a dura-tion corresponding to the 200% current value onthe time-current characteristic.

P

7.3.6.3.4 Protective bonding impedance (routine test) N/A

If the continuity of the protective bonding isachieved at any point by a single means only (forexample a single conductor or single fastener), or ifthe PCE is assembled at the installation location,then the impedance of the protective bonding shallalso be tested as a routine test.

The test shall be as in 7.3.6.3.3, except for the fol-lowing:

Declared by Manufacturer andworking instruction checkedduring factory inspection

N/A

the test current may be reduced to any conven-ient value greater than 10 A sufficient to allowmeasurement or calculation of the impedanceof the protective bonding means:

N/A

the test duration may be reduced to no lessthan 2 s

N/A

For equipment subject to the type test in7.3.6.3.3.1a), the impedance during the routine test

N/A

For equipment subject to the type test in7.3.6.3.3.1b) the impedance during the routine testshall not exceed 2,5 V divided by the test currentrequired by 7.3.6.3.3.1b).

N/A

7.3.6.3.5 External protective earthing conductor N/A

A protective earthing conductor shall be connectedat all times when power is supplied to PCE of pro-tective class I. Unless local wiring regulations stateotherwise, the protective earthing conductor cross-sectional area shall be determined from Table 11 orby calculation according to IEC 60364-5-54.

N/A

If the external protective earthing conductor is rout-ed through a plug and socket or similar means ofdisconnection, it shall not be possible to disconnectit unless power is simultaneously removed from thepart to be protected.

N/A

The cross-sectional area of every external protec-tive earthing conductor which does not form part ofthe supply cable or cable enclosure shall, in anycase, be not less than:

External protective earthingconductor is integrated withoutput cable

N/A

Page 36: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

2,5 mm² if mechanical protection is provided; N/A

4 mm² if mechanical protection is not provided. N/A

For cord-connected equipment, provisions shall bemade so that the external protective earthing con-ductor in the cord shall, in the case of failure of thestrain-relief mechanism, be the last conductor to beinterrupted.

N/A

7.3.6.3.6 Means of connection for the external protectiveearthing conductor

P

7.3.6.3.6.1 General P

The means of connection for the external protectiveearthing conductor shall be located near the termi-nals for the respective live conductors. The meansof connections shall be corrosion-resistant andshall be suitable for the connection of cables ac-cording to 7.3.6.3.5.The means of connection for the protective earthingconductor shall not be used as a part of the me-chanical assembly of the equipment or for otherconnections.A separate means of connection shall be providedfor each external protective earthing conductor.Connection and bonding points shall be so de-signed that their current-carrying capacity is notimpaired by mechanical, chemical, or electrochem-ical influences. Where enclosures and/or conduc-tors of aluminium or aluminium alloys are used,particular attention should be given to the problemsof electrolytic corrosion.

Integrated within output cable P

The means of connection for the protective earthingconductor shall be permanently marked with:

P

symbol 7 of Annex C; or P

the colour coding green-yellow P

Marking shall not be done on easily changeableparts such as screws.

N/A

7.3.6.3.7 Touch current in case of failure of the protectiveearthing conductor

P

The requirements of this sub-clause shall be satis-fied to maintain safety in case of damage to or dis-connection of the protective earthing conductor.

The measured touch current is1.5 mA.

P

For pluggable equipment type A, the touch currentmeasured in accordance with 7.5.4 shall not ex-ceed 3,5 mA a.c. or mA d.c.

N/A

Page 37: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

For all other PCE, one or more of the followingmeasure shall be applied, unless the touch currentmeasured in accordance with 7.5.4 using the testnetwork of IEC 60990 test figure 4 shall not exceed3,5 mA a.c. or 10 mA d.c.

N/A

a) Permanently connected wiring, and: N/A

a cross-section of the protective earthingconductor of at least 10 mm² Cu or 16 mm²Al; or

N/A

automatic disconnection of the supply incase of discontinuity of the protectiveearthing conductor; or

N/A

provision of an additional terminal for asecond protective earthing conductor of thesame cross-sectional area as the originalprotective earthing conductor and installa-tion instruction requiring a second protec-tive earthing conductor to be installed or

N/A

b) Connection with an industrial connector accord-ing to IEC 60309 and a minimum protectiveearthing conductor cross-section of 2,5 mm² aspart of a multi-conductor power cable. Ade-quate strain relief shall be provided.

N/A

In addition, the caution symbol 15 of Annex Cshall be fixed to the product and the installationmanual shall provide details of the protectiveearthing measures required in the installationas required in 5.3.2.

N/A

When it is intended and allowed to connect twoor more PCEs in parallel using one commonPE conductor, the above touch current re-quirements apply to the maximum number ofthe PCEs to be connected in parallel, unlessone of the measures in a)

N/A

or b) above is used. The maximum number ofparallel PCEs is used in the testing and has tobe stated in the installation manual.

N/A

7.3.6.4 Protective Class II Double or Reinforced Insula-tion

Communication interface isevaluated with double insula-tion from live part inside.Comply with clause 7.3.4.3

P

Equipment or parts of equipment designed for pro-tective class II shall have insulation between liveparts and accessible surfaces in accordance with7.3.4.3. The following requirements also apply:

N/A

Page 38: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

equipment designed to protective class II shallnot have means of connection for the externalprotective earthing conductor. However thisdoes not apply if the external protective earth-ing conductor is passed through the equipmentto equipment series-connected beyond it. In thelatter event, the external protective earthingconductor and its means for connection shallbe insulated with basic insulation from the ac-cessible surface of the equipment and from cir-cuits that employ protective separation, extra-low voltage, protective impedance and limiteddischarging energy, according to 7.3.5. Thisbasic insulation shall correspond to the ratedvoltage of the series-connected equipment;

N/A

metal-encased equipment of protective class IImay have provision on its enclosure for theconnection of an equipotential bonding conduc-tor;

N/A

equipment of protective class II may have pro-vision for the connection of an earthing conduc-tor for functional reasons or for damping ofovervoltages; it shall, however, be insulated asthough it is a live part;

N/A

equipment employing protective class II shallbe marked according to 5.1.8.

N/A

7.3.7 Insulation Including Clearance and Creepage Dis-tance

P

7.3.7.1 General P

This subclause gives minimum requirements for in-sulation, based on the principles of IEC 60664.

P

Manufacturing tolerances shall be taken into ac-count during measurement of creepage, clearance,and insulation distance in the PCE.

P

Insulation shall be selected after consideration ofthe following influences:

P

pollution degree PD2 P

overvoltage category PV (OVC II), Mains (OVC III) P

supply earthing system TN considered. P

insulation voltage PV input: max. 550 Vd.c. andMains: 230 Va.c.

P

location of insulation See table 7.3.7.4 and 7.3.7.5for detail

P

type of insulation See table 7.3.7.4 and 7.3.7.5for detail

P

Page 39: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Compliance of insulation, creepage distances, andclearance distances, shall be verified by measure-ment or visual inspection, and the tests of 7.5.

P

7.3.7.1.3 Supply earthing systems P

Three basic types of earthing system are describedin IEC 60364-1. They are:

Inverter is intended to installedin TN system.

P

TN system: has one point directly earthed, theaccessible conductive parts of the installationbeing connected to that point by protectiveconductors. Three types of TN systems, TN-C,TN-S and TN-C-S, are defined according to thearrangement of the neutral and protective con-ductor.

P

TT system: has one point directly earthed, theaccessible conductive parts of the installationbeing connected to earth electrodes electricallyindependent of the earth electrodes of thepower system;

N/A

IT sytem: has all live parts isolated from earthor one point connected to earth through an im-pedance, the accessible conductive parts of theinstallation being earthed independently or col-lectively to the earthing system.

N/A

7.3.7.1.4 Insulation voltages See table 7.3.7.4 and 7.3.7.5for detail

P

Table 12 makes use of the circuit system voltageand overvoltage category to define the impulsewithstand voltage and the temporary overvoltage.

P

7.3.7.2 Insulation between a circuit and its surroundings P

7.3.7.2.1 General

Basic, supplementary and reinforced insulation be-tween a circuit and its surroundings shall be de-signed according to:

Impulse voltage;

temporary overvoltage;

working voltage of the circuit;

230Va.c., OVC III (4000 V im-pulse voltage, 1500 Vrms tem-porary overvoltage) for the ACmains output;

550 Vd.c. system voltage, OVCII (4000 V impulse voltage, notemporary overvoltage for thePV input;

No insulation between PV andAC mains output.

Basic insulation between PV/AC mains and battery terminal.

P

7.3.7.2.2 Circuit connected directly to the mains

Clearance and solid insulation between circuit con-nected directly to the mains and their surroundingsshall be designed according to the impulse voltage,temporary overvoltage, or working voltage, whichev-er gives the most severe requirement

System voltage for mains is300 Vrms according to table12. 4000 V impulse voltagegives the most severe re-quirement

P

Page 40: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

7.3.7.2.3 Circuit other than mains circuit

Clearance and solid insulation between circuit otherthan the mains and their surroundings shall be de-signed according to impulse voltage and recurringpeak voltage

System voltage for PV is 550Vd.c.

P

7.3.7.2.4 Insulation between circuits

a) For clearances and insulation, the require-ments are determined by the circuit havingthe higher impulse voltage;

b) For creepages, r.m.s. working voltageacross the insulation determines the re-quirements.

Impulse voltage (4000 V) iscalculated from table 12 forclearance before basic isola-tion transformer for PV and ACmains side.

Impulse voltage (2500 V) iscalculated from table 12 forclearance after basic isolationtransformer for battery side.

Working voltage (550 Vd.c.)across insulation is used forcreepage.

P

7.3.7.3 Functional insulation

For parts or circuit in OVC I, functional insulationshall be designed according to the working voltageacross the insulation

For parts or circuit in OVC II, functional insulationshall be designed according to the applicable im-pulse voltage as determined by 7.3.7.1.4

P

7.3.7.4 Clearance distances P

7.3.7.4.1 Determination

Table 13 defines the minimum clearance distancesrequired to provide functional, basic , or supplemen-tary insulation

P

Clearance for use in altitudes above 2000 m shall becalculated with correction factor according to TableA.2 of IEC 60664-1

Not intended to use in altitudesabove 2000 m.

N/A

For reinforced insulation, the value corresponding tothe next higher impulse voltage, or 1.6 times thetemporary overvoltage, or 1.6 times the workingvoltage shall be used, whichever results in the mostsevere requirement

P

7.3.7.4.2 Electric field homogeneity

For homogeneous electric field and impulse voltageis equal to or greater than 6000V for a circuit con-nected directly to the mains or 4000V within a circuit,the clearance may be reduced to the requirement byTable F.2 Case B of IEC 60664-1. In this case, im-pulse voltage test shall be performed on the clear-ance

Inhomogeneous electric field isconsidered for PCE

N/A

Page 41: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

7.3.7.4.3 Clearance to conductive enclosures

Clearance shall be measured following the defor-mation test of 13.7 for conductive enclosures

P

7.3.7.5 Creeage distances P

7.3.7.5.1 General

Creepage distances shall be large enough to pre-vent long-term degradation of the surface of solid in-sulators.

For reinforced insulation, the value is doubled.

If less than clearance, it shall be increased to thatclearance

PV Maximum 550 Vd.c. systemvoltage is used for the RMSvoltage across insulation

P

7.3.7.5.2 Voltage r.m.s. value of working voltage is used. In-terpolation is permitted

P

7.3.7.5.3 Materials P

7.3.7.6 Coating N/A

7.3.7.7 PWB spacings for functional insulation PWB rated V-0 and has a min-imum CTI of 175, short-circuittest are considered

P

7.3.7.8 Solid insulation P

7.3.7.8.1 General

Material for solid insulation shall be able to withstandmechanical, electrical, thermal and climatic stressesin normal use and ageing during the expected life-time. Compliance is evaluated by test and inspec-tion.

Insulation tape, sheet, opticalIsolator, isolation power supplyand transformer.

P

7.3.7.8.2 Requirements for electrical withstand capability ofsolid insulation

P

7.3.7.8.2.1 Basic and supplementary, reinforced, and double in-sulation. Solid insulation shall withstand the impulsevoltage test 7.5.1 and voltage test 7.5.2.

P

In addition, if recurring peak working voltage acrossthe insulation is greater than 700 V and voltagestress on insulation is greater than 1kV/mm, doubleand reinforced insulation shall withstand the partialdischarge test according to 7.5.3

N/A

7.3.7.8.2.2 Functional insulation N/A

7.3.7.8.3 Thin sheet or tape material P

7.3.7.8.3.1 General

Insulation of thin sheet or tape less than 0,7 mm issubject to this requirement

P

7.3.7.8.3.2 Material thickness not less than 0,2 mm P

Page 42: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Basic or supplementary insulation shall consist ofat least one layer of material, and shall meet theimpulse and a.c. or d.c. voltage test requirementsof 7.3.7.8.2.1 for basic or supplementary insulation.

Communication transformerwith isolation power supplyconsider as double insulation.

P

Double insulation shall consist of at least two layersof material. Each layer shall meet the impulse anda.c. or d.c. voltage test requirements of 7.3.7.8.2.1for basic insulation, and the partial discharge re-quirements of 7.3.7.8.2.1. The two or more layerstogether shall meet the impulse and a.c. or d.c.voltage test requirements of 7.3.7.8.2.1 for doubleinsulation.

P

Reinforced insulation shall consist of a single layerof material, which will meet the impulse, a.c. or d.c.voltage, and partial discharge test requirements7.3.7.8.2.1 for reinforced insulation.

Insulation sheet cover on dis-play consider as reinforced in-sulation.

P

7.3.7.8.3.3 Material thickness less than 0,2 mm P

Basic or supplementary insulation shall consist ofat least one layer of material, and shall meet theimpulse and a.c. or d.c. voltage test requirementsof 7.3.7.8.2.1 for basic or supplementary insulation.

P

Double insulation shall consist of at least three lay-ers of material. Each layer shall meet the impulseand a.c. or d.c. voltage test requirements of7.3.7.8.2.1 for basic insulation any two layers to-gether shall meet the impulse, a.c. or d.c. voltage,and partial discharge test requirements of7.3.7.8.2.1 for double insulation.

P

Reinforced insulation consisting of a single layer ofmaterial less than 0,2 mm thick is not permitted.

N/A

7.3.7.8.3.4 Compliance

Component, sub-assembly, or material is checkedby applicable tests 7.5.1 to 7.5.3 according to7.3.7.8.

P

7.3.7.8.4 Printed wiring boards (PWBs) P

7.3.7.8.4.1 General

Insulation between conductor layers in double-sided single-layer PWBs, multi-layer PWBs andmetal core PWBs, shall meet the requirements forsolid insulation in 7.3.7.8.

P

For the inner layers of multi-layer PWBs, the insula-tion between adjacent tracks on the same layershall be treated as either:

P

a creepage distance for pollution degree 1 and aclearance as in air (see Annex A, figure A.13); or

P

as solid insulation, in which case it shall meet therequirements of 7.3.7.8.

N/A

Page 43: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

7.3.7.8.4.2 Use of coating materials N/A

A coating material used to provide a microenviron-ment or to provide functional, basic, supplementaryand reinforced insulation shall meet the requirementas specified below.

N/A

Type 1 protection (as defined in IEC 60664-3) im-proves the microenvironment (Pollution Degree) ofthe parts under protection. The clearance andcreepage distance of Table 13 and Table 14 for pol-lution degree 1 apply under the protection. Betweentwo conductive parts, it is a requirement that one orboth conductive parts, together with all the spacingbetween them, are covered by the protection.

N/A

Type 2 protection is considered to be similar to solidinsulation. Under the protection, the requirements forsolid insulation specified in 7.3.7.8 are applicableand spacings shall not be less than those specifiedin Table 1 of IEC 60664-3. The requirements forclearance and creepage in Table 13 and Table 14do not apply. Between two conductive parts, it is arequirement that both conductive parts, together withthe spacing between them, are covered by the pro-tection so that no airgap exists between the protec-tive material, the conductive parts and the printedwiring boards.

N/A

The coating material used to provide Type 1 andType 2 protection shall be designed to withstand thestresses anticipated to occur during the expectedlifetime of the PCE.

N/A

Compliance is checked by a type test on representa-tive conducted according to IEC 60664-3Clause 5.

N/A

For the Cold test (5.7.1), a temperature of 25 °Cshall be used, and for the rapid change of tempera-ture test (5.7.3): 25 °C to +125 °C, except that if thetemperature rating of the PCE is lower than 25 °C,the low temperature limit for the test is reduced tothe rating of the PCE.

N/A

7.3.7.8.5 Wound components P

Varnish or enamel insulation of wires shall not beused for basic, supplementary, double or reinforcedinsulation.

Varnish are not considered asinsulation and voltage test per-formed as routine test. See al-so Cl.7.3.7.8.1 to Cl.7.3.7.8.2

P

Wound components shall meet the requirements of7.3.7.8.1 and 7.3.7.8.2.

N/A

The component itself shall pass the requirementsgiven in 7.3.7.8.1 and 7.3.7.8.2. If the componenthas reinforced or double insulation, the voltage testin 7.5.2 shall be performed as a routine test.

P

Page 44: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

7.3.7.8.6 Potting materials N/A

A potting material may be used to provide solid in-sulation or to act as a coating to protect againstpollution. If used as solid insulation, it shall complywith the requirements of 7.3.7.8.1 and 7.3.7.8.2. Ifused to protect against pollution, the requirementsfor Type 1 protection in 7.3.7.8.4.2 apply.

Potting materials used in boostinductor and inverting inductorare not intended to provide sol-id insulation or to act a coatingto protect against pollution.

N/A

7.3.7.9 Insulation requirements above 30 kHz P

Where voltages across insulation have fundamen-tal frequencies greater than 30 kHz, further consid-erations apply. Requirements for this are providedin IEC 60664-4, and the more severe of these andthe requirements of 7.3.7.1 to 7.3.7.8 shall be ap-plied.

P

Annex G contains flow-charts for the determinationof clearance and creepage distances under thesecircumstances. For convenience, Tables 1 and 2 ofIEC 60664-4 are also included in Annex G.

P

7.3.8 Residual Current-operated protective (RCD) ormonitoring (RCM) device compatibility.

Internal RCM is used accord-ing to IEC 62109-2 test.

P

RCD and RCM are used to provide protectionagainst insulation faults in some domestic and in-dustrial installations, additional to that provided bythe installed equipment.

N/A

7.3.9 Protection against shock hazard due to stored en-ergy

P

7.3.9.1 Operator access area Accessible communication in-terface is DVC A

P

In the case of plugs, connectors, or similar devicesthat can be disconnected without the use of a tool,the withdrawal of which results in the exposure ofconductors (e.g. pins), the discharge time to reducethe voltage to DVC A (see 7.3.2.2) or, for capaci-tors, to a stored charge level below the limits speci-fied in 7.3.5.3.2, shall not exceed 1 s.

P

7.3.9.2 Service access areas P

Capacitors and other energy storage devices locat-ed behind panels that are removable for servicing,installation, or disconnection shall present no risk ofelectric shock or energy hazard from stored chargeafter disconnection of the PCE.

P

Page 45: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Capacitors within a PCE shall be discharged to avoltage less than DVC A (see 7.3.2.2), or an ener-gy level below the limits specified in 7.3.5.3.2, with-in 10 s after the removal of power from the PCE. Ifthis requirement is not achievable for functional orother reasons, the warning symbol 21 of Annex Cand an indication of the discharge time shall beplaced in a clearly visible position on the enclosure,the capacitor protective barrier, or at a point closeto the capacitor(s) concerned (depending on theconstruction) (see 5.2.2.4).

16.1s@60 V bus after discon-necting DC side.

Inside capacitor discharge toDVC A and no energy hazardlevel within 60 seconds.

P

For energy storage devices (such as batteries or ul-tra capacitors) the intended function of which is tomaintain charge even with the PCE off and discon-nected from external sources, a barrier or insulationshall be provided so that unintentional contact withhazardous live parts is prevented. The warningsymbol 21 of Annex C shall be placed in a clearlyvisible position on or adjacent to the barrier or insu-lation, where it will be seen before removal of thebarrier or insulation.

Warning symbol 21 of AnnexC is marked on PCE

P

7.4 Protection against energy hazards P

7.4.1 Determination of hazardous energy level P

A hazardous energy level is considered to exist if Condition b is considered P

a) The voltage is 2 V or more, and power availa-ble after 60 s exceeds 240 VA.

N/A

b) The stored energy in a capacitor is at a voltage.U of 2 V or more, and the stored energy. E,calculated from the following equation, exceeds20J:E = 0,5 CU²

See below Cl.7.4.3

C=470 µF x 5=2350 µF

U=130.5 Vpeak@20 J

P

7.4.2 Operator Access Areas No energized parts accessibleby user

P

Equipment shall be so designed that there is norisk of energy hazard in operator access areas fromaccessible circuits.

P

7.4.3 Services Access Areas P

Energy storage devices located behind panels thatare removable for servicing, installation or discon-nection shall present no risk of electric energy haz-ard from charge stored after disconnection of thePCE.

P

Energy storage devices within a PCE shall be dis-charged to an energy level less than 20 J, as in7.4.1, within 10 s after the removal

Warning symbol 21 of AnnexC is marked

P

7.5 Electrical tests related to shock hazard P

7.5.1 Impulse voltage test (type test) P

Page 46: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

7.5.2 Voltage test (dielectric strength test) (type test) P

7.5.3 Partial discharge test (type test or sample test) N/A

7.5.4 Touch current measurement (type test) P

The touch current shall be measured if required by7.3.6.3.7 and shall not be greater than 3.5 mA a.c.or 10 mA d.c. or special measures of protection asgiven in 7.3.6.3.7 are required.

Measured touch current is 1.5mA. See clause 7.3.6.3.7

P

For type tests on PCE for which wet locations re-quirements apply according to 6.1, the humiditypre-conditioning of 4.5 shall be performed immedi-ately prior to the touch current test.

P

7.5.5 Equipment with multiple sources of supply N/A

8 PROTECTION AGAINST MECHANICAL HAZARDS P

8.1 General POperation shall not lead to a mechanical HAZARDin NORMAL CONDITION or SINGLE FAULTCONDITION.Edges, projections, corners, openings, guards,handles and the like, that are accessible to the op-erator shall be smooth and rounded so as not tocause injury during normal use of the equipment.

P

Conformity is checked as specified in 8.2 to 8.6. P

8.2 Moving parts P

Moving parts shall not be able to crush, cut orpierce parts of the body of an OPERATOR likely tocontact them, nor severely pinch the OPERATOR'sskin. Hazardous moving parts of equipment, that ismoving parts which have the potential to cause in-jury, shall be so arranged, enclosed or guarded asto provide adequate protection against the risk ofpersonal injury.

is protected bybarriers.

P

8.2.1 Protection of service persons P

Protection shall be provided such that unintentionalcontact with hazardous moving parts is unlikelyduring servicing operations. If a guard over a haz-ardous moving part may need to be removed forservicing, the marking of symbol 15 of Table D-1shall be applied on or near the guard.

The fans stopped operatingduring servicing.

P

8.3 Stability N/AEquipment and assemblies of equipment not se-cured to the building structure before operationshall be physically stable in NORMAL USE.

Wall mounted N/A

8.4 Provisions for lifting and carrying P

Page 47: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

If carrying handles or grips are fitted to, or suppliedwith, the equipment, they shall be capable of with-standing a force of four times the weight of theequipment.

P

Equipment or parts having a mass of 18 kg or moreshall be provided with a means for lifting and carry-ing or directions shall be given in the manufactur-er s documentation.

About 22.3 kg(net weight) P

8.5 Wall mounting P

Mounting brackets on equipment intended to bemounted on a wall or ceiling shall withstand a forceof four times the weight of the equipment.

It is intended to be mountedon concrete wall

P

8.6 Expelled parts N/A

Equipment shall contain or limit the energy of partsthat could cause a HAZARD if expelled in the eventof a fault.

N/A

9 PROTECTION AGAINST FIRE HAZARDS P

9.1 Resistance to fire P

This subclause specifies requirements intended toreduce the risk of ignition and the spread of flame,both within the equipment and to the outside, bythe appropriate use of materials and componentsand by suitable construction.

Components are witnessed atnormal condition and abnor-mal tests are verified

P

9.1.1 Reducing the risk of ignition and spread of flame P

For equipment or a portion of equipment, there aretwo alternative methods of providing protectionagainst ignition and spread of flame that could af-fect materials, wiring, wound components and elec-tronic components such as integrated circuits, tran-sistors, thyristors, diodes, resistors and capacitors.

Method 1 used P

9.1.2 Conditions for a fire enclosure P

A FIRE ENCLOSURE is required for equipment orparts of equipment for which Method 2 is not fullyapplied and complied with.

P

9.1.2.1 Parts requiring a fire enclosure P

Except where Method 2 is used, or as permitted in9.1.2.2, the following are considered to have a riskof ignition and, therefore, require a FIREENCLOSURE:

P

components in PRIMARY CIRCUITS P

components in SECONDARY CIRCUITS sup-plied by power sources which exceed the limitsfor a LIMITED POWER SOURCE as specifiedin 9.2;

P

Page 48: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

components in SECONDARY CIRCUITS sup-plied by a LIMITED POWER SOURCE asspecified in 9.2, but not mounted on a materialof FLAMMABILITY CLASS V-1;

N/A

components within a power supply unit or as-sembly having a limited power output comply-ing with the criteria for a LIMITED POWERSOURCE as specified in 9.2, including overcur-rent protective devices, limiting impedances,regulating networks and wiring, up to the pointwhere the LIMITED POWER SOURCE outputcriteria are met;

P

components having unenclosed arcing parts,such as open switch and relay contacts andcommutators, in a circuit at HAZARDOUSVOLTAGE or at a HAZARDOUS ENERGYLEVEL; and

Certified relay with fire enclo-sure

N/A

insulated wiring, except as permitte in 9.1.2.2. PVC wire N/A

9.1.2.2 Parts not requiring a fire enclosure Fire enclosure used N/A

9.1.3 Materials requirements for protection against firehazard

P

9.1.3.1 General P

ENCLOSURES, components and other parts shallbe so constructed, or shall make use of such mate-rials, that the propagation of fire is limited.

P

9.1.3.2 Materials for fire enclosures PIf an enclosure material is not classified as speci-fied below, a test may be performed on the finalenclosure or part of the enclosure, in which casethe material shall additionally be subjected to peri-odic SAMPLE testing.

1. V-0 PCB as part of fireenclosure.

2. V-0 barrier used.3. LPS for display circuit.

P

9.1.3.3 Materials for components and other parts inside fireenclosures

At least V-1 material used in-side fire enclosure, PCB ratedV-0 and internal wire ratedVW-1

P

9.1.3.4 Materials for air filter assemblies N/A

9.1.4 Openings in fire enclosures P

9.1.4.1 General N/A

For equipment that is intended to be used or in-stalled in more than one orientation as specified inthe product documentation, the following require-ments apply in each orientation.

The equipment is intended tobe used one orientation

N/A

These requirements are in addition to those in thefollowing sections:

N/A

7.3.4, Protection against direct contact; N/A

Page 49: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

7.4, Protection against energy hazards; N/A

13.5, Openings in enclosures N/A

9.1.4.2 Side openings treated as bottom openings N/A

9.1.4.3 Openings in the bottom of a fire enclosure P

The bottom of a FIRE ENCLOSURE or individualbarriers, shall provide protection against emissionof flaming or molten material under all internalparts, including partially enclosed components orassemblies, for which Method 2 of 9.1.1 has notbeen fully applied and complied with.

Metal bottom screens withmesh opening less than 2mm.

P

9.1.4.4 Equipment for use in a CLOSED ELECTRICALOPERATING AREA

Not intend use at this area N/A

The requirements of 9.1.4.3 do not apply to FIXEDEQUIPMENT intended only for use in a CLOSEDELECTRICAL OPERATING AREA and to bemounted on a concrete floor or other non-combustible surface. Such equipment shall bemarked as follows:

N/A

WARNING: FIRE HAZARD SUITABLE FORMOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY

N/A

9.1.4.5 Doors or covers in fire enclosures No door or cover operated byuser.

N/A

9.1.4.6 Additional requirements for openings in transporta-ble equipment

N/A

9.2 LIMITED POWER SOURCES N/A

9.2.1 General N/A

9.2.2 Limited power source tests N/A

9.3 Short-circuit and overcurrent protection P

9.3.1 General P

The PCE shall not present a hazard, under short-circuit or overcurrent conditions at any port, includ-ing phase-to-phase, phase-to-earth and phase-to-neutral, and adequate information shall be providedto allow proper selection of external wiring and ex-ternal protective devices.

P

9.3.2 Protection against short-circuits and overcurrentsshall be provided for all input circuits, and for outputcircuits that do not comply with the requirements forlimited power sources in 9.2, except for circuits inwhich no overcurrent hazard is presented by short-circuits and overloads.

P

Page 50: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

9.3.3 Protective devices provided or specified shall haveadequate breaking capacity to interrupt the maxi-mum short circuit current specified for the port towhich they are connected. If protection that is pro-vided integral to the PCE for an input port is notrated for the short-circuit current of the circuit inwhich it is used, the installation instructions shallspecify that an upstream protective device, ratedfor the prospective short-circuit current of that port,shall be used to provide backup protection.

External circuit breaker shallbe used for AC side.

P

10 PROTECTION AGAINST SONIC PRESSURE HAZARDS N/A

10.1 General N/A

The equipment shall provide protection against theeffect of sonic pressure. Conformity tests are car-ried out if the equipment is likely to cause suchHAZARDS.

N/A

10.2 Sonic pressure and Sound level N/A

10.2.1 Hazardous Noise Levels N/A

11 PROTECTION AGAINST LIQUID HAZARDS N/A

11.1 Liquid Containment, Pressure and Leakage No liquid containment system N/A

The liquid containment system components shallbe compatible with the liquid to be used.

N/A

There shall be no leakage of liquid onto live partsas a result of:

N/A

a) Normal operation, including condensation; N/A

b) Servicing of the equipment; or N/A

c) Inadvertent loosening or detachment of hosesor other cooling system parts over time.

N/A

11.2 Fluid pressure and leakage N/A

11.2.1 Maximum pressure N/A

11.2.2 Leakage from parts N/A

11.2.3 Overpressure safety device N/A

11.3 Oil and grease N/A

12 CHEMICAL HAZARDS N/A

12.1 General N/A

13 PHYSICAL REQUIREMENTS P

Page 51: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

13.1 Handles and manual controls P

Handles, knobs, grips, levers and the like shall bereliably fixed so that they will not work loose innormal use, if this might result in a hazard. Sealingcompounds and the like, other than selfhardeningresins, shall not be used to prevent loosening. Ifhandles, knobs and the like are used to indicate theposition of switches or similar components, it shallnot be possible to fix them in a wrong position if thismight result in hazard.

P

13.1.1 Adjustable controls N/A

13.2 Securing of parts P

13.3 Provisions for external connections P

13.3.1 General P

13.3.2 Connection to an a.c. Mains supply AC connector P

13.3.2.1 General P

For safe and reliable connection to a MAINS sup-ply, equipment shall be provided with one of the fol-lowing:

P

terminals or leads or a non-detachable powersupply cord for permanent connection to thesupply; or

permanent connection to thesupply.

P

a non-detachable power supply cord for con-nection to the supply by means of a plug

N/A

an appliance inlet for connection of a detacha-ble power supply cord; or

N/A

a mains plug that is part of direct plug-inequipment as in 13.3.8

N/A

13.3.2.2 Permanently connected equipment P

13.3.2.3 Appliance inlets N/A

13.3.2.4 Power supply cord N/A

13.3.2.5 Cord anchorages and strain relief N/A

For equipment with a non-detachable power supplycord, a cord anchorage shall be supplied such that:

N/A

the connecting points of the cord conductorsare relieved from strain; and

N/A

the outer covering of the cord is protected fromabrasion.

N/A

13.3.2.6 Protection against mechanical damage P

13.3.3 Wiring terminals for connection of external conduc-tors

P

13.3.3.1 Wiring terminals P

Page 52: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

13.3.3.2 Screw terminals P

13.3.3.3 Wiring terminal sizes P

13.3.3.4 Wiring terminal design P

13.3.3.5 Grouping of wiring terminals P

13.3.3.6 Stranded wire N/A

13.3.4 Supply wiring space N/A

13.3.5 Wire bending space for wires 10 mm² and greater N/A

13.3.6 Disconnection from supply sources Installation manual instruct thedisconnect device shall beprovided before connectingAC mains, PV array and bat-tery.

P

13.3.7 Connectors, plugs and sockets No such connectors, plugsand sockets employed

N/A

13.3.8 Direct plug-in equipment N/A

13.4 Internal wiring and connections P

13.4.1 General P

13.4.2 Routing Internal wire is routed to avoidsharp edge and overheat

P

13.4.3 Colour coding Green-yellow wire used asprotective bonding only

P

13.4.4 Splices and connections P

13.4.5 Interconnections between parts of the PCE No such interconnections N/A

13.5 Openings in enclosures P

13.5.1 Top and side openings P

Openings in the top and sides of ENCLOSURESshall be so located or constructed that it is unlikelythat objects will enter the openings and create haz-ards by contacting bare conductive parts.

P

13.6 Polymeric Materials P

13.6.1 General P

13.6.1.1 Thermal index or capability P

13.6.2 Polymers serving as enclosures or barriers pre-venting access to hazards

Polymers serving as barrierspreventing access to hazards

P

13.6.2.1 Stress relief test P

13.6.3 Polymers serving as solid insulation N/A

13.6.3.1 Resistance to arcing Arcing parts are enclosed in-side certified relay

N/A

13.6.4 UV resistance N/A

Page 53: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Polymeric parts of an OUTDOOR ENCLOSURErequired for compliance with this standard shall besufficiently resistance to degradation by ultra-violet(UV) radiation

N/A

13.7 Mechanical resistance to deflection, impact, or drop P

13.7.1 General P

13.7.2 250-N deflection test for metal enclosures P

13.7.3 7-J impact test for polymeric enclosures P

13.7.4 Drop test N/A

13.8 Thickness requirements for metal enclosures P

13.8.1 General P

13.8.2 Cast metal N/A

13.8.3 Sheet metal P

14 COMPONENTS P

14.1 General P

Where safety is involved, components shall beused in accordance with their specified RATINGSunless a specific exception is made. They shallconform to one of the following:

P

1. applicable safety requirements of a relevantIEC standard. Conformity with other require-ments of the component standard is not re-quired. If necessary for the application, compo-nents shall be subjected to the test of thisstandard, except that it is not necessary to car-ry out identical or equivalent tests already per-formed to check conformity with the componentstandard;

P

2. the requirements of this standard and, wherenecessary for the application, any additionalapplicable safety requirements of the relevantIEC component standard;

P

3. if there is no relevant IEC standard, the re-quirements of this standard;

P

4. applicable safety requirements of a non-IECstandard which are at least as high as those ofthe applicable IEC standard, provided that thecomponent has been approved to the non-IECstandard by a recognized testing authority.

P

Page 54: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Components such as optocouplers, capacitors,transformers, and relays connected across basic,supplemental, reinforced, or double insulation shallcomply with the requirements applicable for thegrade of insulation being bridged, and if not previ-ously certified to the applicable component safetystandard shall be subjected to the voltage test of7.5.2 as routine test.

P

14.2 Motor Over temperature Protection N/A

Motors which, when stopped or prevented fromstarting (see 4.4.4.3), would present an electricshock HAZARD, a temperature HAZARD, or a fireHAZARD, shall be protected by an over-temperature or thermal protection device meetingthe requirements of 14.3.

N/A

14.3 Overtemperature protection devices N/A

14.4 Fuse holders N/A

14.5 MAINS voltage selecting devices N/A

14.6 Printed circuit boards P

Printed circuit boards shall be made of materialwith a flammability classification of V-1 of IEC60707 or better.

V-0 P

This requirement does not apply to thin-film flexibleprinted circuit boards that contain only circuitspowered from limited power sources meeting therequirements of 9.2.

N/A

Conformity of the flammability RATING is checkedby inspection of data on the materials. Alternatively,conformity is checked by performing the V-1 testsspecified in IEC 60707 on three samples of the rel-evant parts.

N/A

14.7 Circuits or components used as transient overvoltage limiting devices N/A

If control of transient overvoltage is employed in theequipment, any overvoltage limiting component orcircuit shall be tested with the applicable impulsewithstand voltage of Table 7-10 using the testmethod from 7.5.1 except 10 positive and 10 nega-tive impulses are to be applied and may be spacedup to 1 min apart.

N/A

14.8 Batteries N/A

Equipment containing batteries shall be designedto reduce the risk of fire, explosion and chemicalleaks under normal conditions and after a singlefault in the equipment including a fault in circuitrywithin the equipment battery pack.

No battery used. N/A

14.8.1 Battery Enclosure Ventilation N/A

Page 55: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

14.8.1.1 Ventilation requirements N/A

14.8.1.2 Ventilation testing N/A

14.8.1.3 Ventilation instructions N/A

14.8.2 Battery Mounting N/A

Compliance is verified by the application of theforce to the battery s mounting surface. The testforce is to be increased gradually so as to reachthe required value in 5 to 10 s, and is to be main-tained at that value for 1 min. A nonmetallic rack ortray shall be tested at the highest normal conditionoperating temperature.

N/A

14.8.3 Electrolyte spillage N/A

Battery trays and cabinets shall have an electro-lyte-resistant coating.

N/A

The ENCLOSURE or compartment housing aVENTED BATTERY shall be constructed so thatspillage or leakage of the electrolyte from one bat-tery will be contained within the ENCLOSURE andbe prevented from:

N/A

a) reaching the PCE outer surfaces that can becontacted by the USER

N/A

b) contaminating adjacent electrical componentsor materials; and

N/A

c) bridging required electrical distances N/A

14.8.4 Battery Connections N/A

Reverse battery connection of the terminals shallbe prevented if reverse connection could result in ahazard within the meaning of this Standard

N/A

14.8.5 Battery maintenance instructions N/A

The information and instructions listed in 5.3.4.1shall be included in the operator manual for equip-ment in which battery maintenance is performed bythe operator, or in the service manual if batterymaintenance is to be performed by service person-nel only.

N/A

14.8.6 Battery accessibility and maintainability N/A

Battery terminals and connectors shall be accessi-ble for maintenance with the correct TOOLS. Bat-teries with liquid electrolyte, requiring maintainedshall be so located that the battery cell caps areaccessible for electrolyte tests and readjusting ofelectrolyte levels.

N/A

15 Software and firmware performing safety functions P

Page 56: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Annex A Measurement of clearances and creepage distanc-es (see 7.3.7.4 and 7.3.7.5)

P

Annex B Programmable Equipment P

B.1 Software or firmware that perform safety criticalfunctions

P

B.1.1 Firmware or software that performs a critical safetyfunction/s, the failure of which can result in a risk offire, electric shock or other hazard as specified bythis standard, shall be evaluated by one of the fol-lowing means.

P

a) All software or firmware limits or controls shall bedisabled before the test to evaluate the hardwarecircuitry during the abnormal test condition relatedto the safety function.

P

b) Protective controls employing software or firm-ware to perform their function(s), shall be so con-structed that they comply with IEC 60730-1 AnnexH to address the risks identified in B.2.1.

N/A

B.2 Evaluation of controls employing software P

Annex C Symbols to be used in equipment markings P

Annex D Test Probes for Determining Access P

Annex E RCDs N/A

Annex F Altitude correction for clearances N/A

Annex G Clearance and creepage distance determination forfrequencies greater than 30 kHz

P

Annex H Measuring Instrument for Touch Current Measure-ments

P

H.1 Measuring instrument P

H.2 Alternative measuring instrument N/A

Annex I Examples of Protection, Insulation, and Overvolt-age Category Requirements for PCE

P

Annex J Ultraviolet light conditioning test N/A

Page 57: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

4.7 #1 TABLE: mains supply electrical data in normal condition P

Model PV Grid

U (V) d.c. I (A)d.c. P (kW) d.c. U (V) a.c. I (A) a.c. P (kW) a.c.

EA5KHD 120.4 25.02 3.012 208.1 13.49 2.798

249.9 19.00 4.749 208.8 21.49 4.480

359.1 13.16 4.725 208.8 21.49 4.480

449.6 10.48 4.711 208.8 21.51 4.481

529.0 8.92 4.718 208.8 21.53 4.487

120.7 24.94 3.010 231.2 11.69 2.699

249.8 20.96 5.235 231.3 21.46 4.958

359.0 14.51 5.208 231.3 21.46 4.959

450.0 11.54 5.192 231.3 21.47 4.959

530.0 9.81 5.198 231.3 21.49 4.961

120.8 24.91 3.010 254.1 10.73 2.724

249.8 20.88 5.216 254.2 19.51 4.954

360.0 14.41 5.188 254.2 19.52 4.955

449.0 11.52 5.171 254.0 19.50 4.957

530.0 9.78 5.181 254.2 19.56 4.961

Remark: Grid-Tied mode, PV to grid, no load.

4.7 #2 TABLE: mains supply electrical data in normal condition P

Model PV Grid Load

U (V)d.c.

I (A)d.c. P (kW)d.c.

U (V)a.c.

I (A) a.c. P (kW)a.c.

U (V)a.c.

I (A) a.c. P (kW)a.c.

EA5KHD 120.1 25.09 3.013 207.5 3.91 0.792 207.4 9.68 2.008

250.0 18.97 4.742 208.0 11.82 2.448 208.1 9.70 2.018

360.2 13.10 4.718 208.0 11.82 2.449 208.1 9.70 2.018

449.8 10.45 4.699 208.0 11.82 2.448 208.1 9.70 2.018

529.6 8.88 4.703 208.0 11.83 2.449 208.1 9.69 2.017

120.4 25.02 3.011 230.7 3.05 0.696 230.6 8.78 2.025

249.9 20.95 5.234 231.1 12.65 2.913 231.3 8.81 2.037

360.1 14.46 5.208 231.1 12.65 2.915 231.3 8.81 2.037

449.1 11.56 5.190 231.1 12.66 2.915 231.3 8.80 2.036

530.0 9.76 5.170 231.1 12.67 2.916 231.3 8.80 2.036

Page 58: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

120.6 25.02 3.017 253.7 2.80 0.704 253.7 7.95 2.016

249.9 20.87 5.214 254.1 11.57 2.931 254.3 7.95 2.021

360.1 14.40 5.187 254.1 11.58 2.932 254.3 7.95 2.021

449.1 11.50 5.167 254.1 11.58 2.931 254.3 7.95 2.020

530.0 9.75 5.166 254.1 11.59 2.933 254.3 7.95 2.020

Remark: Grid-Tied mode, PV to grid and load.

4.7 #3 TABLE: mains supply electrical data in normal condition P

Model PV Load

U (V) d.c. I (A)d.c. P (kW) d.c. U (V) a.c. I (A) a.c. P (kW) a.c.

EA5KHD 119.5 18.10 2.162 230.2 8.79 2.024

249.7 8.41 2.101 230.2 8.66 1.994

359.6 5.88 2.113 230.2 8.76 2.016

449.6 4.68 2.106 230.3 8.76 2.017

529.6 3.99 2.112 230.4 8.76 2.018

Remark: Off-Grid mode, PV to load.

4.7 #4 TABLE: mains supply electrical data in normal condition P

Model PV Battery

U (V) d.c. I (A)d.c. P (kW) d.c. U (V) d.c. I (A)d.c. P (kW) d.c.

EA5KHD 119.9 23.52 2.819 56.3 45.53 2.561

251.1 11.21 2.815 56.3 45.60 2.566

360.0 7.79 2.805 56.3 45.61 2.566

448.6 6.25 2.803 56.2 45.65 2.568

528.5 5.22 2.757 56.2 45.71 2.569

Remark: Off-Grid mode, PV to Battery.

4.7 #5 TABLE: mains supply electrical data in normal condition P

Model Battery Load

U (V) d.c. I (A)d.c. P (kW) d.c. U (V) a.c. I (A) a.c. P (kW) a.c.

EA5KHD 49.8 43.71 2.176 230.2 8.78 2.021

Remark: Off-Grid mode, Battery to load.

Page 59: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

4.7 #6 TABLE: mains supply electrical data in normal condition P

Model Battery Grid

U (V) d.c. I (A)d.c. P (kW) d.c. U (V) a.c. I (A) a.c. P (kW) a.c.

EA5KHD 50.2 53.24 2.672 230.7 10.72 2.473

Remark: Battery to Grid(House load).

4.7 #7 TABLE: mains supply electrical data in normal condition P

Model PV Load Battery

U (V)d.c.

I (A)d.c. P (kW)d.c.

U (V)a.c.

I (A) a.c. P (kW)a.c.

U (V)d.c.

I (A)d.c. P (kW)d.c.

EA5KHD 119.6 25.54 3.054 230.3 8.76 2.016 56.4 15.16 0.855

250.9 19.47 4.885 230.2 8.75 2.015 56.3 45.75 2.574

360.2 14.02 4.794 230.2 8.75 2.015 56.3 45.68 2.560

451.0 10.77 4.859 230.3 8.76 2.018 56.2 45.35 2.550

528.4 9.17 4.844 230.3 8.76 2.017 56.3 45.37 2.554

Remark: PV to load and battery.

4.7 #8 TABLE: mains supply electrical data in normal condition P

Model PV Grid Battery

U (V)d.c.

I (A)d.c. P (kW)d.c.

U (V)a.c.

I (A) a.c. P (kW)a.c.

U (V)d.c.

I (A)d.c. P (kW)d.c.

EA5KHD 120.9 24.99 3.020 207.4 0.98 0.203 56.2 45.45 2.556

249.7 21.84 5.456 207.6 12.95 2.682 56.2 45.55 2.562

360.0 15.22 5.480 207.7 13.21 2.737 56.3 45.53 2.561

451.4 12.13 5.476 207.7 13.25 2.745 56.2 45.56 2.562

529.3 10.37 5.486 207.7 13.35 2.766 56.2 45.56 2.562

121.3 24.95 3.025 230.4 1.04 0.239 56.2 45.56 2.563

249.7 21.93 5.477 230.6 11.36 2.612 56.2 45.55 2.562

359.9 15.18 5.464 230.6 11.44 2.630 56.2 45.57 2.563

451.3 12.13 5.473 230.6 11.40 2.621 56.2 45.57 2.563

528.9 10.34 5.468 230.6 11.54 2.651 56.2 45.58 2.563

120.8 24.95 3.013 253.0 0.87 0.205 56.2 45.57 2.563

248.7 22.01 5.475 253.6 10.31 2.607 56.2 45.59 2.563

360.0 15.22 5.477 253.6 10.35 2.617 56.2 45.58 2.563

450.3 12.21 5.497 253.6 10.47 2.625 56.2 45.59 2.562

Page 60: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

530.4 10.36 5.496 253.6 10.48 2.649 56.2 45.61 2.564

Remark: PV to grid and battery.

4.7 #9 TABLE: mains supply electrical data in normal condition P

Model Grid Load

U (V) a.c. I (A) a.c. P (kW) a.c. U (V) a.c. I (A) a.c. P (kW) a.c.

EA5KHD 229.7 8.96 2.056 229.1 8.84 2.025

Remark: Grid to load.

4.7 #10 TABLE: mains supply electrical data in normal condition P

Model PV Battery Load

U (V)d.c.

I (A)d.c. P (kW)d.c.

U (V)d.c.

I (A)d.c. P (kW)d.c.

U (V)a.c.

I (A) a.c. P (kW)a.c.

EA5KHD 122.2 8.07 0.986 50.9 23.41 1.192 230.2 8.77 2.019

249.7 3.98 0.995 48.5 23.68 1.148 230.2 8.76 2.016

360.8 2.76 0.997 48.5 23.47 1.138 230.2 8.76 2.016

399.2 2.33 0.929 51.9 23.53 1.221 230.2 8.75 2.015

444.5 2.46 1.096 57.1 18.14 1.036 230.3 8.76 2.018

Remark: PV and battery to load.

4.3 Thermal testing (by thermocouples) PModel EA5KHD

No. Ambient

(°C)Humidity

(RH)Test

time

PV Grid Load Battery

V

d.c.

A

d.c.W

V

a.c.

A

a.c.W

V

a.c.

A

a.c.W

V

d.c.

A

d.c.W

(1) 40 50% 2h59min 250 22.0 5494 207 21.6 4481 -- -- -- 55.8 11.6 649

(2) 40 50% 3h4min 249 22.0 5493 253 19.7 4990 -- -- -- 56.0 3.9 220

(3) 40 50% 2h16min 450 12.2 5484 207 21.6 4482 -- -- -- 55.9 12.5 698

(4) 40 50% 3h38min 450 12.2 5489 254 19.6 4970 -- -- -- 56.1 4.3 242

(5) 40 50% 2h31min 250 19.9 4982 -- -- -- 230 8.9 2046 55.9 44.6 2497

(6) 40 50% 3h7min 450 10.9 4903 -- -- -- 230 8.9 2044 55.9 44.7 2496

Page 61: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

(7) 40 50% 2h5min -- -- -- 230 10.8 2489 -- -- -- 51.2 54.0 2768

Remark:

(1) - (4) : Grid-Tied mode, PV to grid and battery;

(5) - (6) : Off-Grid mode, PV to load and battery;

(7) : Off-Grid mode, Battery to grid (house load).

No.

Temperature (°C) ofpart at:

Measured temperature (°C) Permit-ted(°C)(1) (2) (3) (4) (5) (6) (7)

1 PV1 input terminalblock (internal) 44.0 44.3 41.9 41.9 42.8 41.2 40.2 105

2 PV1 input internalwire 46.3 46.4 43.2 42.9 44.3 42.9 40.3 105

3 DC switch discon-nector 46.1 45.8 44.0 43.6 42.9 42.8 40.7 70

4 Varistor R31 on PV-inverter board 44.8 44.8 41.9 41.8 42.7 43.6 40.2 105

5 C21 on PV-inverterboard 45.7 45.7 42.8 42.7 43.5 44.8 40.5 105

6 L3 on PV-inverterboard 61.5 61.1 47.3 46.9 55.2 51.1 40.7 90

7 C35 on PV-inverterboard 52.6 52.2 47.6 47.2 47.9 46.3 41.2 125

8 CT1 on PV-inverterboard 50.1 49.7 46.8 46.9 46.1 46.2 41.8 85

9 Boost1 inductive coil 81.1 79.5 57.4 55.8 69.5 66.9 42.4 110

10 Boost1 inductive core 81.8 80.4 56.9 55.4 70.5 65.4 42.1 --

11 Boost1 IGBT Q7 onPV-inverter board 64.7 64.5 50.3 50.5 58.8 54.1 42.3 130

12 D1 on PV-inverterboard 65.9 65.5 54.4 54.0 59.2 53.8 42.2 130

13 Insulation paper be-tween Q7 and heatsink on PV-inverterboard

60.2 59.8 49.0 48.8 54.6 53.4 41.9 150

14 C15 on PV-inverterboard 47.3 47.1 44.7 44.1 44.1 47.1 41.1 105

15 Q1 on PV-inverterboard 75.0 73.5 73.7 71.8 53.7 52.5 54.9 130

16 Q5 on PV-inverterboard 75.2 72.4 74.1 71.0 53.3 52.2 54.4 130

17 D3 on PV-inverterboard 72.9 70.1 72.1 68.9 52.9 51.9 53.3 130

Page 62: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

18 C86 on PV-inverterboard 53.6 52.7 53.3 52.0 45.6 47.5 45.9 85

19 Fan1 (Under the pow-er wire of Fan1) 45.1 44.9 44.5 44.1 42.7 44.3 42.3 70

20 Inverter inductive coil 90.0 81.2 90.0 80.4 50.3 49.6 51.9 110

21 Inverter inductive core 86.5 78.2 86.9 77.8 49.6 49.0 51.0 --

22 C118 on PV-inverterboard 45.9 45.4 46.3 46.7 41.6 43.3 42.0 105

23 CT4 on PV-inverterboard 51.2 50.4 51.1 49.9 45.0 45.5 45.8 105

24 L16 on PV-inverterboard 52.0 50.6 52.1 50.3 43.8 45.4 44.5 110

25 Relay RLY6 on PV-inverter board 56.8 55.3 56.6 55.1 41.9 43.7 48.5 60

26 CT3 on PV-inverterboard 47.0 46.4 46.9 47.2 40.3 41.2 42.4 105

27 C79 on PV-inverterboard 42.9 42.9 42.9 42.4 39.7 39.8 40.8 110

28 Varistor R109 on PV-inverter board 44.4 44.1 44.3 43.5 39.7 40.1 41.0 125

29 Fuse F1 on PV-inverter board 52.0 50.2 52.2 50.0 39.7 39.7 42.6 130

30 Grid input internalwire 46.3 45.7 46.5 45.2 39.8 39.8 41.3 105

31 Grid input terminalblock (internal) 43.9 43.6 43.9 43.2 39.8 39.6 40.6 105

32 CT5 on PV-inverterboard 43.5 43.6 43.4 43.4 47.7 47.8 42.1 110

33 L17 on PV-inverterboard 43.0 43.2 43.1 43.0 47.7 47.8 42.0 90

34 Grid Auxiliary Powerwire 40.2 40.8 40.5 40.4 40.4 40.4 40.0 105

35 L1 on DC-DC board 44.9 44.8 44.4 44.2 44.4 45.6 46.1 110

36 C291 on DC-DCboard 46.6 46.5 46.1 45.8 46.6 51.6 44.0 85

37 Q54 on DC-DC board 50.6 49.3 50.0 48.7 60.3 60.0 47.0 130

38 L29 on DC-DC board 49.7 48.3 49.4 48.9 64.6 66.9 52.0 110

39 C306 on DC-DCboard 54.0 51.7 53.3 51.0 70.8 70.0 54.3 105

40 T12 transformer coilon DC-DC board 60.9 57.9 59.3 56.6 86.9 85.5 53.8 110

Page 63: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

41 T12 transformer coreon DC-DC board 52.5 51.3 52.1 51.9 61.4 69.9 51.0 --

42 L26 on DC-DC board 53.7 51.2 52.6 50.3 75.5 74.4 55.4 110

43 L28 on DC-DC board 45.6 43.8 45.4 45.2 66.3 66.0 64.5 110

44 C296 on DC-DCboard 46.8 44.1 46.3 45.8 73.4 72.5 67.9 105

45 T3 transformer coil onDC-DC board 43.2 42.6 45.9 44.9 49.0 49.0 88.3 110

46 T3 transformer coreon DC-DC board 43.1 42.5 47.5 46.5 49.1 49.1 87.6 --

47 D16 on DC-DC board 42.1 41.8 41.5 41.3 44.1 45.3 65.1 130

48 C33 on DC-DC board 43.6 43.0 43.5 43.3 49.8 50.5 66.1 85

49 C31 on DC-DC board 41.9 41.6 41.5 41.2 44.4 46.7 59.2 105

50 Fuse F2 on DC-DCboard 45.0 43.6 44.4 43.3 65.0 66.3 79.6 130

51 Relay RLY1 on DC-DC board 44.4 44.2 44.4 43.9 46.4 49.7 49.4 70

52 BAT internal wire 43.0 41.4 42.6 41.0 64.9 65.3 83.1 90

53 BAT terminal block(internal) 42.2 40.8 41.4 40.5 54.8 56.3 66.8 120

54 Q8 on DC-DC board 42.5 41.6 42.2 42.1 47.8 51.2 54.3 130

55 D94 on DC-DC board 48.3 44.2 47.8 44.2 69.9 69.3 52.9 130

56 Q49 on DC-DC board 52.8 52.7 52.5 52.4 51.9 51.9 51.0 130

57 T9 transformer coil onDC-DC board 50.1 50.0 49.6 49.5 49.3 51.8 48.7 110

58 T9 transformer coreon DC-DC board 51.3 51.2 51.0 50.9 50.7 52.6 49.9 --

59 Grid Auxiliary Powerterminal block 42.3 42.4 42.1 42.0 42.1 42.7 41.8 75

60 T10 on DC-DC board 41.3 41.5 41.1 41.2 40.7 41.0 41.1 110

61 T11 on DC-DC board 43.2 43.3 43.1 43.1 42.9 43.3 43.8 110

62 D88 on DC-DC board 44.2 45.7 43.8 45.2 40.5 40.5 44.4 130

63 U25 on DC-DC board 43.1 43.6 42.8 43.1 41.9 42.1 43.3 110

64 U26 on DC-DC board 46.0 46.1 46.6 46.7 46.7 46.7 48.3 110

65 U27 on DC-DC board 48.0 47.9 47.9 48.1 47.3 47.5 47.0 110

66 PCB near BAT 41.1 40.7 40.8 40.3 46.1 47.6 52.3 130

67 PCB near Bus circuit 48.9 48.4 48.3 47.6 45.6 45.4 43.9 130

68 The front of unit 41.6 41.7 41.6 41.1 40.1 39.7 40.0 70

69 The flank of unit 45.6 45.1 45.0 44.4 40.9 40.3 40.3 70

Page 64: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

70 The top of unit 43.5 43.7 43.4 43.0 41.3 41.0 40.9 70

71 The mounting surfac-es of unit 46.8 46.6 45.6 46.1 42.4 43.3 41.3 90

72 LCD 39.3 40.0 41.1 39.8 39.7 39.3 39.5 70

73 Test ambient temper-ature 1 39.3 39.6 41.0 39.2 39.7 39.4 39.5 Ref.

Supplementary information:

4.4 TABLE: fault condition tests P

Ambient temperature( C) : 25

40%

No. componentNo. fault

Input

(V)Output

(V, kW)Testtime

Observation

Clause 4.4.4.1 Component fault tests

Below component single fault applied on PV_inverter board

1 Q7 (pin 2 toPin 3) S-C 360 Vd.c. 230 Va.c.,

5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCD

age. No hazard. Recoverable.

2 Q1 (pin C tppin E) S-C 360 Vd.c. 230 Va.c.,

5kW 5minThe fault applied during the unit op-eration. After applied the fault, theunit operated as normal. No dam-age. No hazard. Recoverable.

3 R93 S-C 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCDdisplay alaNo damage. No hazard. Recovera-ble.

4 R201 O-C 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit operated as normal. No dam-age. No hazard. Recoverable.

5 C114 S-C 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCD

cuit breaker overcurrent protection.No hazard. Unrecoverable.

Page 65: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

6 R22 O-C 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit operated as normal. No dam-age. No hazard. Recoverable.

7 R126 O-C 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration. After applied the fault, thegrid disconnected immediately and

age. No hazard. Recoverable.

8 RLY7 S-C 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould not restart and LCD display

damage. No hazard. Recoverable.

9 RLY9 S-C 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould not restart and LCD display

damage. No hazard. Recoverable.

10 CT5(pin 1 topin 4) S-C 360 Vd.c. 230 Va.c.,

5kW 5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. But the gridoutput power which displayed onLCD was wrong. No damage. Nohazard. Recoverable.

11 CT5(pin 2 topin 3) S-C 360 Vd.c. 230Va.c.,

5kW 5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. But the gridoutput power which displayed onLCD was wrong. No damage. Nohazard. Recoverable.

12 C79 S-C 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration. After applied the fault, thegrid disconnected immediately and

F1 was damaged. No hazard. Unre-coverable.

13 RLY3 (pin 4to pin 5) S-C 360 Vd.c. 230 Va.c.,

5kW 5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould not restart and LCD display

coverable.

Page 66: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

14 RLY11 (pin4 to pin 5) S-C 360 Vd.c. 230 Va.c.,

5kW 5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould not restart and LCD display

coverable.

Below component single fault applied on DC-DC board

15 R346 S-C 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately. ZD15,C205, C246 and U15 were dam-aged. No hazard. Unrecoverable.

16 Q49 (pin Dto pin S) S-C 360 Vd.c. 230 Va.c.,

5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately. R301and R300 were damaged. No haz-ard. Unrecoverable.

17 R300 S-C 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately. Nodamage. No hazard. Recoverable.

18 U28 (pin 1to pin 3) S-C 360 Vd.c. 230 Va.c.,

5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCD

Recoverable.

19 U27 (pin 1to pin 2) S-C 360 Vd.c. 230 Va.c.,

5kW 5minThe fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately. Nodamage. No hazard. Recoverable.

20 U27 (pin 3to pin 4) S-C 360 Vd.c. 230 Va.c.,

5kW 5minThe fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately. Nodamage. No hazard. Recoverable.

21 U27 (pin 1) O-C 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately. Nodamage. No hazard. Recoverable.

22 D88 (pin 1to pin 3) S-C

PV:

360 Vd.c.

Grid:

230 Va.c.

230 Va.c.,5kW / 2kW 5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould restart. When the unit was atbypass mode, the LCD blacked.R366 was damaged. No hazard.Unrecoverable.

Page 67: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

23 C258 S-C

PV:

360 Vd.c.

Grid:

230 Va.c.

230 Va.c.,5kW / 2kW 5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould restart. When the unit was atbypass mode, the LCD blacked.R366 was damaged. No hazard.Unrecoverable.

24 R368 S-C 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit operated as normal. No dam-age. No hazard. Recoverable.

25 U25 (pin 1to pin 2) S-C

PV:

360 Vd.c.

Grid:

230 Va.c.

230 Va.c.,5kW / 2kW 5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould restart. When the unit was atbypass mode, the LCD blacked. Nodamage. No hazard. Recoverable.

26 U25 (pin 3to pin 4) S-C

PV:

360 Vd.c.

Grid:

230 Va.c.

230 Va.c.,5kW / 2kW 5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould restart. When the unit was atbypass mode, the LCD blacked. Nodamage. No hazard. Recoverable.

27 U25 pin 1 O-C

PV:

360 Vd.c.

Grid:

230 Va.c.

230 Va.c.,5kW / 2kW 5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould restart. When the unit was atbypass mode, the LCD blacked. Nodamage. No hazard. Recoverable.

28 U16 (pin 2to pin 3) S-C

PV:

360 Vd.c.

Grid:

230 Va.c.

230 Va.c.,5kW / 2kW 5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould restart. When the unit was atbypass mode, the LCD blacked. Nodamage. No hazard. Recoverable.

29 D67 S-C

PV:

360 Vd.c.

Grid:

230 Va.c.

230 Va.c.,5kW / 2kW 5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould restart. When the unit was atbypass mode, the LCD blacked.C263 and C267 were damaged. Nohazard. Unrecoverable.

Page 68: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

30 Q51 (pin Dto pin S) S-C

PV:

360 Vd.c.

BAT:

51.2 Vd.c.

230 Va.c.,5kW /2.5kW

5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould restart. When the unit wassupplied by the battery, the LCDblacked. R379 and R378 were

31 R379 S-C

PV:

360 Vd.c.

BAT:

51.2 Vd.c.

230 Va.c.,5kW /2.5kW

5minThe fault applied during the unit op-eration. After applied the fault, theunit operated as normal. No dam-age. No hazard. Recoverable.

32 R377 S-C

PV:

360 Vd.c.

BAT:

51.2 Vd.c.

230 Va.c.,5kW /2.5kW

5min

The fault applied during the unit op-eration, the unit operated with ab-normal noise after applied the fault.When the unit shutdown and re-started, the unit could restart. Whenthe unit was supplied by the battery,the LCD blacked. U14 and ZD17were damaged. No hazard. Unre-coverable.

33 C270 S-C

PV:

360 Vd.c.

BAT:

51.2 Vd.c.

230 Va.c.,5kW /2.5kW

5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCD

was damaged. The fuse on the bat-tery circuit was damaged. No haz-ard. Unrecoverable.

34 D68 S-C

PV:

360 Vd.c.

BAT:

51.2 Vd.c..

230 Va.c.,5kW /2.5kW

5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould restart. When the unit wassupplied by the battery, the LCDblacked. C264 was damaged. Nohazard. Unrecoverable.

35 U26 (pin 1to pin 2) S-C

PV:

360 Vd.c.

BAT:

51.2 Vd.c.

230 Va.c.,5kW /2.5kW

5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould restart. When the unit was on-ly supplied by the battery, the LCDblacked. No damage. No hazard.Recoverable.

Page 69: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

36 U26 (pin 3to pin 4) S-C

PV:

360 Vd.c.

BAT:

51.2 Vd.c.

230 Va.c.,5kW /2.5kW

5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould restart. When the unit was on-ly supplied by the battery, the LCDblacked. No damage. No hazard.Recoverable.

37 U26 pin 1 S-C

PV:

360 Vd.c.

BAT:

51.2 Vd.c.

230 Va.c.,5kW /2.5kW

5min

The fault applied during the unit op-eration, the unit operated as normalafter applied the fault. When the unitshutdown and restarted, the unitcould restart. When the unit was on-ly supplied by the battery, the LCDblacked. No damage. No hazard.Recoverable.

38 D14 S-C 51.2 Vd.c. 230 Va.c.,2.5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCD

DC BUS LOWVOLTard. Unrecoverable.

39 R231 S-C 51.2 Vd.c. 230 Va.c.,2.5kW 5min

The fault applied during the unit op-eration. After applied the fault, the

The fuses (F1, F2, F3) on the bat-tery circuit were damaged. No haz-ard. Unrecoverable.

40 RLY1 (pin 1to pin 2) S-C 51.2 Vd.c. 230 Va.c.,

2.5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit operated as normal. When theunit shutdown and restarted, theunit could restart. No damage. Nohazard. Recoverable.

41 Q5 (pin D topin S) S-C 51.2 Vd.c. 230 Va.c.,

2.5kW 5min

The fault applied during the unit op-eration. After applied the fault, the

The fuses (F1, F2, F3) on the bat-tery circuit were damaged. No haz-ard. Unrecoverable.

42 Q54 (pin Dto pin S) S-C 360 Vd.c. 51.2 Vd.c.

2.5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCDdisp

Recoverable.

Page 70: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

43 D94 (pin 1to pin 2) S-C 360 Vd.c. 51.2 Vd.c.

2.5kW 5min

The fault applied during the unit op-eration. After applied the fault, the

The fuses (F1, F2, F3) on the bat-tery circuit were damaged. No haz-ard. Unrecoverable.

44 R415 S-C 360 Vd.c. 51.2 Vd.c.2.5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCD

Battery ChargingOver Current Hardhazard. Recoverable.

Below component single fault applied on control board

45 U29 (pin 2to pin 3) S-C 360 Vd.c. 230 Va.c.,

5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit operated as normal and LCD

No damage. No hazard. Recovera-ble.

46 U7 (pin 12to pin 13) S-C 360 Vd.c. 230 Va.c.,

5kW 5min

The fault applied during the unit op-eration. After applied the fault, the

7 was damaged.No hazard. Unrecoverable.

47 U20 (pin 2to pin 3) S-C 360 Vd.c. 230 Va.c.,

5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCD

shutdownand restarted, the unit could not re-start and LCD display alarmed

age. No hazard. Recoverable.

Clause 4.4.4.4 Transformer short circuit tests

48 T9 (pin 8 topin 9) S-C 360 Vd.c. 230 Va.c.,

5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit operated as normal. When theunit shutdown and restarted, theunit could restart but the LCDblacked. No damage. No hazard.Recoverable.

49 T9 (pin 11 topin 12) S-C 360 Vd.c. 230 Va.c.,

5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit operated as normal. When theunit shutdown and restarted, theunit could not restart and the LCDblacked. No damage. No hazard.Recoverable.

Page 71: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

50 T9 (pin 13 topin 14) S-C 360 Vd.c. 230 Va.c.,

5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit operated as normal. When theunit shutdown and restarted, theunit could not restart but the LCDblacked. No damage. No hazard.Recoverable.

51 T10 (pin 6 topin 9) S-C

PV:

360 Vd.c.

Grid

230 Va.c.,

230 Va.c.,5kW / 2kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit operated as normal. When thePV input was removed, the LCDblacked after a few seconds. Nodamage. No hazard. Recoverable.

52 T10 (pin 6 topin 7) S-C

PV:

360 Vd.c.

Grid

230 Va.c.,

230 Va.c.,5kW / 2kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit operated as normal. When thePV input was removed, the LCDblacked after a few seconds. Nodamage. No hazard. Recoverable.

53 T11 (pin 6 topin 9) S-C 51.2 Vd.c. 230 Va.c.,

2.5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit operated as normal. When thegrid was disconnected, the LCDblacked after a few seconds. Nodamage. No hazard. Recoverable.

54 T11 (pin 6 topin 7) S-C 51.2 Vd.c. 230 Va.c.,

2.5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit operated as normal. When thegrid was disconnected, the LCDblacked after a few seconds. Nodamage. No hazard. Recoverable.

55 T2 (pin 11 topin 19) S-C 51.2 Vd.c. 230 Va.c.,

2.5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCDdisplay alar

Recoverable.

56 T3 (pin 11 topin 19) S-C 51.2 Vd.c. 230 Va.c.,

2.5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCD

OW

Recoverable.

57 T12 (pin 3 topin 4) S-C 360 Vd.c.

Grid:

230 Va.c.,5kW

BAT:

51.2 Vd.c.

2.5kW

5minThe fault applied during the unit op-eration. After applied the fault, theunit could not charge the battery. Nodamage. No hazard. Recoverable.

Page 72: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

58 T12 (pin 4 topin 5) S-C 360 Vd.c.

Grid:

230 Va.c.,5kW

BAT:

51.2 Vd.c.

2.5kW

5minThe fault applied during the unit op-eration. After applied the fault, theunit could not charge the battery. Nodamage. No hazard. Recoverable.

59 T8 (pin N1to pin N2) S-C 360 Vd.c.

Grid:

230 Va.c.,5kW

BAT:

51.2 Vd.c.

2.5kW

5minThe fault applied during the unit op-eration. After applied the fault, theunit could not charge the battery. Nodamage. No hazard. Recoverable.

60 T8 (pin N4to pin N5) S-C 360 Vd.c.

Grid:

230 Va.c.,5kW

BAT:

51.2 Vd.c.

2.5kW

5minThe fault applied during the unit op-eration. After applied the fault, theunit could not charge the battery. Nodamage. No hazard. Recoverable.

Clause 4.4.4.7 Output overload

61 AC output O-L 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration, After applied the fault, theunit operated as normal. The ACoutput without overload function. Nodamage. No hazard. Recoverable.

62 Load output O-L 360 Vd.c. 230 Va.c.,2kW --

The fault applied during the unit op-eration.(1) When the unit overload 110%

lasted 10 mins, the LCD display

(2) When the unit overload 125%lasted 1 min, the LCD display

(3) When the unit overload 150%lasted 10 s, the LCD display

(4) When the unit overload 175%lasted 200 ms, the LCD display

Then the unit shutdown. No dam-age. No hazard. Recoverable.

Page 73: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

63 BAT output O-L 360 Vd.c. 51.2 Vd.c.,2.5kW 5min

The fault applied during the unit op-eration, After applied the fault, theunit operated as normal. The batteryoutput without overload function. Nodamage. No hazard. Recoverable.

Clause 4.4.4.8 Cooling system failure

64Fan 1 onPV_inverterboard

Blocked 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCD

damage. No hazard. Recoverable.

65Fan 2 onPV_inverterboard

Blocked 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCD

damage. No hazard. Recoverable.

66Fan 1 onDC-DCboard

Blocked 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCD

damage. No hazard. Recoverable.

67Fan 2 onDC-DCboard

Blocked 360 Vd.c. 230 Va.c.,5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCD

damage. No hazard. Recoverable.

68 Q15 (pin 1to pin 5) S-C 360 Vd.c. 230 Va.c.,

5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCD

hazard. Recoverable.

69 Q39 (pin 1to pin 5) S-C 360 Vd.c. 230 Va.c.,

5kW 5min

The fault applied during the unit op-eration. After applied the fault, theunit shutdown immediately and LCD

hazard. Recoverable.

Clause 4.4.4.11 Reverse d.c. connections

70 - R 360 Vd.c. 230Va.c.,5kW 5min

The fault applied before the unit op-eration. After applied the fault, theunit could not start and LCD display

age. No hazard. Recoverable.

71 - R 51.2 Vd.c. 230Va.c.,2.5kW 5min

The fault applied before the unit op-eration. After applied the fault, theunit could not start and LCD display

damage. No hazard. Recoverable.

Page 74: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Clause 4.4.4.13 Mis-wiring with incorrect phase sequence or polarity

72 AC output Land N Mis-wiring 360 Vd.c. 230 Va.c.,

5kW 5minThe fault applied before the unit op-eration. After applied the fault, theunit operated as normal. No dam-age. No hazard. Recoverable.

73 AC output Land PE Mis-wiring 360 Vd.c. 230 Va.c.,

5kW 5minThe fault applied before the unit op-eration. After applied the fault, theunit could not connect to grid. Nodamage. No hazard. Recoverable.

74 AC outputPE

Not conne-cted 360 Vd.c. 230 Va.c.,

5kW 5minThe fault applied before the unit op-eration. After applied the fault, theunit operating as normal. No haz-ard. No damage. Recoverable.

supplementary information:(1) S-C: short circuit, O-C: open circuit, O-L: overload, R: reversed.(2) PV simulator used for apply these fault condition test.

7.3.7 TABLE: Creepage distances and clearances for appliances P

clearance cl and creepage dis-tance dcr at/of:

Systemvoltage

(V)

OVC required cl(mm)

cl (mm) requiredcr (mm)

dcr(mm)

PV to PE(BI) DC: 550AC: 230

II (PV)III (AC)

3.0 3.4 3.0 3.4

PV1 input circuit to signal collec-tion circuit (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 4.0 3.0 4.0

PV2 input circuit to signal collec-tion circuit (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.3 3.0 3.3

Between PV input circuit andsignal collection circuit throughhigh impedance resistance (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 1.07*5=5.4 3.0 1.07*5=5.4

Between PV input circuit and PEthrough high impedance re-sistance (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 1.07*5=5.4 3.0 1.07*5=5.4

Between Bus circuit to PEthrough high impedance re-sistance (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 1.07*5=5.4 3.0 1.07*5=5.4

Between grid/load circuit to signalcollection circuit through high im-pedance resistance (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 1.07*4=4.3 3.0 1.07*4=4.3

DVC C circuit to signal collectioncircuit (CT3 to R118) (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.1 3.0 3.1

DVC C circuit to signal collectioncircuit (CT1) (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.5 3.0 3.5

DVC C circuit to signal collectioncircuit (CT2) (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.5 3.0 3.5

Page 75: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

DVC C circuit to signal collectioncircuit (CT3) (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.7 3.0 3.7

DVC C circuit to signal collectioncircuit (CT4) (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.2 3.0 3.2

DVC C circuit to signal collectioncircuit CT5) (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.0 3.0 3.0

DVC C circuit to signal collectioncircuit (PCB under RLY6) (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.3 3.0 3.3

DVC C circuit to signal collectioncircuit (RLY7) (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.2 3.0 3.2

DVC C circuit to signal collectioncircuit (RLY8) (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.6 3.0 3.6

DVC C circuit to signal collectioncircuit (RLY9) (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.5 3.0 3.5

DVC C circuit to signal collectioncircuit (RLY10) (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 5.4 3.0 5.4

Between primary and secondaryof T2 on the DC-DC board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 4.8(3.5 Innerlayer)

3.0 4.8(3.5 Innerlayer)

Between primary and secondaryof T3 on the DC-DC board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 4.8(3.5 Innerlayer)

3.0 4.8(3.5 Innerlayer)

Between primary and secondaryof T12 on the DC-DC board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 5.2(3.5 Innerlayer)

3.0 5.2(3.5 Innerlayer)

Between primary and secondaryof T11 on the DC-DC board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 6.0 3.0 6.0

Between core and secondary ofT11 on the DC-DC board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.6 3.0 3.6

Hazardous parts (R370\C249) tosignal collection circuit track (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.4 3.0 3.4

J33(DVC A circuit) to AC inputconnector on the DC-DC board(J31) (RI)

DC: 550AC: 230

II (PV)III (AC)

5.5 5.9 5.5 5.9

Between primary and secondary(Pin 11-14) of T9 on the DC-DCboard (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 6.0 3.0 6.0

Between secondary (Pin 11-14)and secondary (Pin 8-9) of T9on the DC-DC board (SI)

DC: 550AC: 230

II (PV)III (AC)

3.0 6.0 3.0 6.0

Between primary and secondary(Pin 8-9) of T9 on the DC-DCboard (RI)

DC: 550AC: 230

II (PV)III (AC)

5.5 8.0 5.5 8.0

Between core and secondary(Pin 11-14) of T9 on the DC-DCboard (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 4.2 3.0 4.2

Page 76: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Between core and secondary(Pin 8-9) of T9 on the DC-DCboard (RI)

DC: 550AC: 230

II (PV)III (AC)

5.5 8.3 5.5 8.3

Between primary and secondaryof T8 on the DC-DC board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 7.4 3.0 7.4

Between primary and secondaryof U25 on the DC-DC board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 6.2 3.0 6.2

Between primary and secondaryof U26 on the DC-DC board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 6.2 3.0 6.2

Between primary and secondaryof U27 on the DC-DC board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 6.2 3.0 6.2

SELV parts(TP4) to hazardousparts(C284) (RI)

DC: 550AC: 230

II (PV)III (AC)

5.5 6.2 5.5 6.2

PCB track of SELV parts to haz-ardous parts (RI)

DC: 550AC: 230

II (PV)III (AC)

5.5 6.0 5.5 6.0

PCB track of SELV parts to con-trol circuit parts (SI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.5 3.0 3.5

Ground screw H2 to Hazardousparts on DC-DC board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 6.6 3.0 6.6

Ground screw H5 to Hazardousparts on DC-DC board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.6 3.0 4.9

Ground screw H7 to Hazardousparts on DC-DC board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 6.3 3.0 6.3

Ground screw H6 to Hazardousparts on DC-DC board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 5.7 3.0 5.7

Ground screw H14 to Hazardousparts on DC-DC board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 6.8 3.0 6.8

Ground screw H8 to Hazardousparts on DC-DC board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 6.7 3.0 6.7

Ground screw H6 to Hazardousparts on PV board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 5.3 3.0 5.3

Ground screw H9 to Hazardousparts on PV board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.1 3.0 3.1

Ground screw H10 to Hazardousparts on PV board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.6 3.0 3.6

Ground screw H7 to Hazardousparts on PV board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.1 3.0 3.1

Ground screw H2 to Hazardousparts on PV board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.1 3.0 3.1

Ground screw H1 to Hazardousparts on PV board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.4 3.0 3.4

Ground screw H8 to Hazardousparts on PV board (BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.2 3.0 3.2

Page 77: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Between primary and secondaryof T2 on the display board (RI)

DC: 550AC: 230

II (PV)III (AC)

5.5 5.9 5.5 5.9

Between primary and secondaryof U21 on the display board (RI)

DC: 550AC: 230

II (PV)III (AC)

5.5 6.3 5.5 6.3

Between primary and secondaryof T1 on the IGBT driver board(BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 3.1 3.0 3.1

Between primary and secondaryof U1 on the IGBT driver board(BI)

DC: 550AC: 230

II (PV)III (AC)

3.0 4.0 3.0 6.0

Supplementary information:

(1) For AC mains circuit, nominal voltage is 230 V and overvoltage category is OVC III, impulse voltagecorrespond to mains circuit is 4000 V;

(2) For PV circuit, system voltage is 550 V and overvoltage category is OVC II, impulse voltage corre-spond to PV circuit is 2945 V;

(3) For battery circuit, is evaluated with basic insulation from AC mains and PV circuit, impulse voltage is2500 V;

7.3.7.8.3.2 to 7.3.7.8.3.3 TABLE: distance through insulation measurement P

distance through insulation di at/of:U r.m.s.

(V) test voltage (V)required di

(mm)di

(mm)

Plastic isolation sheet between upper enclosureand PCBA (BI)

550Vd.c.

230Va.c.

1500Vr.m.s. -- 0.25

Plastic isolation sheet between PCBA and lowerenclosure (BI)

550Vd.c.

230Va.c.

1500Vr.m.s. -- 0.25

Insulation cover sheet on display (RI) 550Vd.c.

230Va.c.

3000Vr.m.s. -- 0.50

Two layers Insulation tape (RI) 550Vd.c.

230Va.c.

3000Vr.m.s. -- Certified

Supplementary information:

7.5 TABLE: electric strength measurements, impulse voltage test and partial dis-charge test

P

test voltage applied between: test voltage(V)

impulse with-stand voltage

(V)

partial dischargeextinction voltage

(V)result

PV terminal and BAT terminal, relaycontact short-circuit (BI) 2120Vd.c. 4000Vpeak N/A Pass

PV terminal and metal enclosure (BI) 2120Vd.c. 4000Vpeak N/A Pass

Page 78: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

Grid/AC load terminal and BAT termi-nal, relay contact short-circuit (BI) 2120Vd.c. 4000Vpeak N/A Pass

Grid/AC load terminal and metal en-closure, relay contact short-circuit (BI) 2120Vd.c. 4000Vpeak N/A Pass

BAT terminal and metal enclosure, re-lay contact short-circuit (BI) 2120Vd.c. 4000Vpeak N/A Pass

PV terminal and all communicationport (RI) 4240Vd.c 6000Vpeak N/A Pass

PV terminal and accessible plastic en-closure of the display (RI) 4240Vd.c 6000Vpeak N/A Pass

Grid/AC load terminal and all commu-nication port, relay contact short-circuit(RI)

4240Vd.c 6000Vpeak N/A Pass

Grid/AC load terminal and accessibleplastic enclosure of the display, relaycontact short-circuit (RI)

4240Vd.c 6000Vpeak N/A Pass

BAT terminal and all communicationport, relay contact short-circuit (RI) 4240Vd.c 6000Vpeak N/A Pass

BAT terminal and accessible plasticenclosure of the display, relay contactshort-circuit (RI)

4240Vd.c 6000Vpeak N/A Pass

Supplementary information: Circuit breakers, contactors are closed before apply these tests.

Page 79: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

Metal enclosureEAST Group Co.,Ltd. Sheet metal

611mm*547mm*150mm, thickness:1.65mm.

IEC 62109-1IEC 62109-2IEC 62477-1

Tested withappliance

Plastic enclo-sure -- --

86 mm * 211 mm,thickness: 2 mm.

IEC 62109-1

IEC 62109-2

Tested with

appliance

Material of plas-tic enclosure

CHI MEICORPORATION PA-765A(+) ABS, V-0, 130 °C

UL 746B

UL 94UL E56070

PCB

HUIZHOUTRUSTWINELECTRONICSDEVELOPMENTCO LTD

TW-8 V-0, 130 °C,CTI>175

UL 746BUL 94UL 746C

E340729

PV1 inputterminal block

SHENZHENCONECTIONELECTRONICSCO., LTD.

DRTB10 -NR1

600 Vd.c., 65 Ad.c.,20 AWG - 6 AWG,105 °C, V-0

UL 1059UL 486EUL 60947-1

UL E304128

Grid inputterminal block

SHENZHENCONECTIONELECTRONICSCO. LTD.

DRTB10 -NR1

600 Vd.c., 65 Ad.c.,20 AWG - 6 AWG,105 °C, V-0

UL 1059UL 486EUL 60947-1

UL E304128

Load inputterminal block

SHENZHENCONECTIONELECTRONICSCO. LTD.

DRTB10 -NR1

600 Vd.c., 65 Ad.c.,20 AWG - 6 AWG,105 °C, V-0

UL 1059UL 486EUL 60947-1

UL E304128

BAT terminalblock

SHENZHENCONNECTIONELECTRONIC COLTD

DRTB35-RST

600 Vd.c., 100Ad.c., 16 AWG - 2AWG, -40 °C to120 °C, V-0

UL 1059UL 486EUL 60947-1

UL E304128

Material of allterminal block

TORAYINDUSTRIES INC

3004-V0(rr),CM3004-V0(rr)

Polyamide 66, V-0,105 °C

UL 746BUL 94

UL E41797

PV1/GRIDinput internalwire

ZHONGLI SCIENCE& TECHNOLOGYGROUP CO LTD

1015 11 AWG, VW-1,105 °C, 600 Va.c. UL 758 UL E156525

Load inputinternal wire

ZHONGLI SCIENCE& TECHNOLOGYGROUP CO LTD

1015 11 AWG, VW-1,105 °C, 600 Va.c. UL 758 UL E156525

BAT internalwire

GUANGDONGHICHAINELECTRICITY COLTD

10326 AWG, VW-1,90 °C, 1000Va.c./1200 Vd.c.

UL 758 UL E304337

Internal earthingwire

ZHONGLI SCIENCE& TECHNOLOGYGROUP CO LTD

1015 10 AWG, VW-1,105 °C, 600 Va.c. UL 758 UL E156525

Page 80: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

DC switchdisconnector

IMO PRECISIONCONTROLS LTD SI25-PM64-4

1500V, 1000VDC,25A, -50 °C to70 °C

IEC 60947-3VDE0660UL508i

UL E362605TUV

Boost inductorSHENZHEN CLICKELECTRONICSCO.,LTD.

LC184-747 67Ts, 1.2mH, ClassB

IEC 62109-1IEC 62109-2

Tested withappliance

- PCB KINGBOARDLAMINATES LTD FR-4

V-0, 130 °C,CTI>175

UL 746BUL 94UL 746C

E123995

- Core Various Various Iron silicon --Tested withappliance

- WireTAI-I ELECTRICWIRE & CABLE COLTD

-- 155 °C, MW 5-C UL 1446 UL E85640

- Alternative

GUANGDONGJINGDA REASPECIALENAMLED WIRECO.,LTD.

-- 155 °C, MW 5-C UL 1446 UL E223994

- EpoxyDONGGUANEATTOELECTRONICMATERIAL CO LTD

E-500 (XX) V-0, 130 °C UL 746C UL E218090

- TubeCHANGYUANELECTRONICSGROUP CO LTD

CB-HFT*, CB-HFT(XY)*,CYG-MT*

300Vrms, 125 °C,VW-1 UL 224 UL E180908

- VarnishHANG CHEUNGCOATINGS(HUIYANG) LTD

8562* 155 °C UL 1446 UL E200154

- Alternative KYOCERACORPORATION TVB2180T*(a) 155 °C UL 1446 UL E83702

- Margin tape

3M COMPANYELECTRICALMARKETS DIV(EMD)

44 D (a) 130 °C UL 510A UL E17385

Inverter inductorSHENZHEN CLICKTECHNOLOGYCO.LTD

LC250-2931.6 x 2P x

82Ts, 800µHClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- WireTAI-I ELECTRICWIRE & CABLE COLTD

-- 155 °C, MW 5-C UL 1446 UL E85640

- Alternative

GUANGDONGJINGDA REASPECIALENAMELED WIRECO LTD

-- 155 °C, MW 5-C UL 1446 UL E223994

Page 81: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- EpoxyDONGGUANEATTOELECTRONICMATERIAL CO LTD

E-500 (XX) V-0, 130 °C UL 746C UL E218090

- TubeCHANGYUANELECTRONICSGROUP CO LTD

CB-HFT*, CB-HFT(XY)*,CYG-MT*

300Vrms, 125 °C,VW-1 UL 224 UL E180908

- VarnishHANG CHEUNGCOATINGS(HUIYANG) LTD

8562* 155 °C UL 1446 UL E200154

- Alternative KYOCERACORPORATION TVB2180T*(a) 155 °C UL 1446 UL E83702

- Tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

PF* (d)(g) 180 °C UL 510A UL E165111

- Margin tape

3M COMPANYELECTRICALMARKETS DIV(EMD)

44 D (a) 130 °C UL 510A UL E17385

- Core Various VariousIEC 62109-1IEC 62109-2

Tested withappliance

FanDONGGUANPROTECHNICELECTRIC CO LTD

MGT8012UB-R25

12Vd.c., 0.66A, -10 °C to 70 °C

UL 507 UL E187236TUV

Plastic isolationsheet betweenupper and lowerenclosure

EAST Group Co.,Ltd. Various 500 mm * 600 mm,

thickness: 0.25mmIEC 62109-1IEC 62109-2

Tested withAppliance

Material ofplastic isolationsheet betweenupper and lowerenclosure

SICHUANDONGFANGINSULATINGMATERIAL CO LTD

DF6025 V-0, 105 °CUL 746CUL 94UL 746B

UL E199019

Plastic isolationsheet betweenPCBA and low-er enclosure

Various Various 415mm * 482mm,thickness: 0.25mm

IEC 62109-1IEC 62109-2

Tested withAppliance

Material of plas-tic isolationsheet betweenPCBA and low-er enclosure

FORMEX, DIV OFILLINOIS TOOLWORKS INC

FORMEX GK-(a)(b)(f1) V-0, 115 °C

UL 746CUL 94UL 746B

UL E121855

LCD display

SHENZHENTOPWAYTECHNOLOGYCO., LTD.

LM256160BFW -20 °C to 70 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Page 82: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformityMaterial ofplastic isolationcover sheetonLCD display

SICHUANLONGHUA FILM COLTD

PC-1860A-ECO V-0, 80 °C

UL 746CUL 94UL 746B

UL E254551

Grid AuxiliaryPower wire

GUANGDONGHICHAINELECTRICITY COLTD

1015 28AWG 4/0AWG,105 °C, 600Va.c. UL 758 UL E304337

--Below list is the critical components on the PV_INVERTER board

Varistor (R31,R3, R21, R49,R50, R53)

THINKINGELECTRONICINDUSTRIAL COLTD

TVR20821 820Vdc, 6500A, -40 °C to 105 °C

UL 1449IEC/EN61051-1

UL E314979VDE: 005944

X capacitor(C21, C42)

FUTUNGELECTRONICSCO., LTD.

PMK1K0PS22J4K0

1000Vdc, 0.22uF, -40 °C to 105 °C

IEC 60384-1,IEC 60384-16

Tested withappliance

X capacitor (C9,C41)

SHENZHENSURONGCAPACITORSCO ,.LTD

CBB21 630V, 680nF, -40 °C to 85 °C

IEC 60384-1,IEC 60384-16

Tested withappliance

Inductor (L3,L17,L6)

SHENZHEN CLICKELECTRONICSCO.,LTD.

LC31-06020Ts, 2.0mH

20Ts, 2.0mH

IEC 62109-1IEC 62109-2

Tested withappliance

- Wire

PACIFIC ELECTRICWIRE & CABLE(SHENZHEN) COLTD

PEW/U 130 °C UL1446 UL E201757

- Varnish JOHN C DOLPHCO.,LTD BC-359 130 °C UL1446 UL E317429

- EpoxySHAW HUOWENTERPRISE COLTD

9001A/9001B V-0, 90 °C UL 746C UL E105888

AlternativeSHENZHENYUYUAN POWERCO.,LTD

CHOKE 208XN1: 2.0 mHN2: 2.0 mHClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- Wire FENG CHINGMETAL CORP xPEW 155 °C UL 1446 UL E172395

- AlternativePACIFIC ELECTRICWIRE & CABLE(SHENZHEN) COLTD

UEW/U@ 130 °C UL 1446 UL E201757

- EpoxyDONGGUANEATTOELECTRONICMATERIAL CO LTD

3300A-1/3300B-1

V-0, 130 °C UL 746C UL E218090

Page 83: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- Core KAWATESU MA070 T31*19*13mmIEC 62109-1IEC 62109-2

Tested withappliance

Y capacitor(C35, C2, C5,C54, C55, C43,C40, C14,C126, C127)

Nanjing Yuyue Elec-tronics Co., Ltd. CT7

400 Va.c., 470 pF, -25 °C to 125 °C, Y1

IEC/EN60384-14

VDE40008010

Current sensor(CT1, CT2)

Nanjing ChiefulScience &TECHNOLOGYCO.,LTD.

CSM015NPT5 Vd.c., 15 A, -25 °C to 85 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Boost IGBT(Q7, Q8)

InfineonTechnologies AG SPW47N60C3

600V, 47A, -55 °Cto 150 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Boost diode(D1, D2) Cree Inc C3D16060D

600V, 22A, -55 °Cto 175 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Insulation paperbetween IGBTand heat sink

KUNSHANZHONGDIMATERIALSTECHNOLOGY COLTD

TSP-10 &V-0, 150 °C, thick-ness: 0.15mm,26mmx20mm

UL 1694UL 94UL 746A

UL E343369

Bus capacitor(C15, C116,C115, C114,C39)

HUNAN AIHUAGROUP CO.,LTD

ELH2JM471R60TT

550V, 470µF,-25 °C to 105 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Inverter IGBT (Q1, Q2, Q3, Q4,Q5, Q6)

FairchildSemiconductor

FGA60N65SMD

650 V, 60 A, -55 °Cto 175 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Diode(D3, D4) IXYS Corporation DSEC 30-06A 600 V, 2x 15 A, -55 °C to 175 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Capacitor(C86,C87, C84, C85,C16, C17)

SHENZHENSURONGCAPACITORSCO.,LTD

MPP474J6240815P0

630 Vd.c, 0.47 µF, -40 °C to 85 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Currentsensor(CT4)

LEMSWITZERLAND S A

CKSR 25-NP 5 Vd.c., 25 A, -40 °C to 105 °C UL 508 UL E189713

X capacitor(C118)

XIAMENFARATRONIC CO.,LTD.

C6A475Vd.c.,6.5 uF,-40 °C to 105 °C

UL 810EN 61071,EN 61881-1

UL E256238TUV R50266136

Y capacitor(C121, C117,C122, C123,C62, C64, C61,C63, C124,C132, C119,C125)

Nanjing Yuyue Elec-tronics Co., Ltd. CT7 400V, 4700pF, -

25 °C to 125 °C, Y1IEC/EN60384-14

VDE40008010

Page 84: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformityRelay (RLY6,RLY5, RLY8,RLY10, RLY7,RLY9)

PANASONICCORPORATION ALFG2PF12

Contact 250 Va.c.,31 Aa.c., coil 12Vd.c.-40 °C to 60 °C

UL 60947-1IEC/EN61810-1

UL E43028VDE40023067

Current sensor(CT3)

LEMSWITZERLAND S A

CTSR 0.3-TP/SP17

0.3A, 5V, -40 °C to105 °C

EN 50178IEC 61010-1UL 508

UL E189713

X capacitor(C79, C120)

XIAMENFARATRONIC CO.,LTD.

MKP62 275 Va.c., 2.2 uF, -40 °C to 110 °C, X2

IEC/EN60384-14UL 60384-14

VDE40000358UL E186600

Varistor(R109,R108,R86)

Shantou High-NewTechnologyDev. Zone SongtianEnterprise Co., Ltd.

20D681K680V, 6500A,-40 °C to 125 °C

UL1449IEC 61051

UL E330837VDE40023049

Fuse (F1)CONQUERELECTRONICSCO.,LTD.

ABE 250 Va.c., 40 Aa.c.,175 °C

UL 248-1UL 248-14

UL E82636

Currentsensor(CT5)

SHENZHENFERROCOILELECTRONICSTECHNOLOGYCO.,LTD

EI-28

N1(4-x 1000.5TsN2(3-1TsN2(6-1TsClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- Bobbin CHANG CHUNPLASTICS CO LTD T375J V-0, 150 °C

UL 746UL 94

UL E59481

- Copper wire

PACIFIC ELECTRICWIRE & CABLE(SHENZHEN) COLTD

UEW/U 130 °C, MW 75-C UL 1446 UL E201757

- Tape

XINYUSHENGDAFENGELECTRICMATERIAL CO LTD

SDF-312 130 °C UL 510A UL E317896

- Teflon tubeCHANGYUANELECTRONICSGROUP CO LTD

CB-TT-L 200 °C, VW-1 UL 224 UL E180908

- VarnishHANG CHEUNGCOATINGS(HUIYANG) LTD

8562* 155 °C UL 1446 UL E200154

Page 85: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

Alternative

JEPULSTECHNOLOGY(SHENZHEN)CO.,LTD

LC28-045

N1(4-x 1000.5TsN2(3-1TsN2(6-1TsClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- Bobbin CHANG CHUNPLASTICS CO LTD T375J V-0, 150 °C

UL 746UL 94

UL E59481

- AlternativeE I DUPONT DENEMOURS & COINC

101L V-0, 130 °CUL 746UL 94

UL E41938(M)

- Copper wireSHENZHENCHENGWEIINDUSTRY CO LTD

UEW-E 130 °C, MW 75-C UL 1446 UL E227475

- Mylar tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

CT(c)(g) 130 °C UL 510A UL E165111

- Margin tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

WF* (c)(h) 130 °C UL 510A UL E165111

- Teflon tubeCHANGYUANELECTRONICSGROUP CO LTD

CB-TT-L 200 °C, VW-1 UL 224 UL E180908

- VarnishHANG CHEUNGCOATINGS(HUIYANG) LTD

8562* 155 °C UL 1446 UL E200154

AlternativeSHENZHEN CLICKTECHNOLOGYCO.LTD

DB2801-123

N1(4-x 1000.5TsN2(3-1TsN2(6-1TsClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- Bobbin CHANG CHUNPLASTICS CO LTD T373J V-0, 150 °C

UL 746UL 94

UL E59481

- Copper wire

PACIFIC ELECTRICWIRE & CABLE(SHENZHEN) COLTD

UEW/U@ 130 °C UL 1446 UL E201757

- TapeJINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

PZ* (b) 130 °C UL 510A UL E165111

Page 86: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- TubeFLUO TECHINDUSTRIES COLTD

TFL 200 °C, VW-1 UL 224 UL E175982

- Varnish

ELANTASELECTRICALINSULATIONELANTAS PDG INC

V1630FS 180 °C UL 1446 UL E75225

Inductor (L16,L7)

Shenzhen SpitzerElectronic Co., Ltd

SPT-42H6284-L

10Ts;N210Ts;Class B

IEC 62109-1IEC 62109-2

Tested withappliance

- WIRE

WUXI JUFENGCOMPOUND LINECOLTD

MW 30-C 180 °C UL 1446 E206882

- AlternativeTAI-I COPPER(GUANZHOU) COLTD

SMEIW MW77-C 180 °C UL 1446 E85640

- InsulationFILM

DUPONT TEIJINFILM U S L P

Melinex238PV(a)

0.075×8mm, VTM-2130 °C

UL 746UL 94

E93687

- MARGINTAPE

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

WF* (c)(h) 4mm*0.3 ,130 °C UL 510A E165111

- GLUE

GUANGZHOUPOCHELYELECTRONICMATERIAL CO LTD

5225A/B EPOXY, V-0,130 °C

UL 746UL 94

E204979

- BOBBINKINGBOARDLAMINATESHOLDINGS LTD

KB-6165 V-0, 130 °CUL 746UL 94

E123995

- Core DMEGC R10KIEC 62109-1IEC 62109-2

Tested withappliance

Relay (RLY3,RLY11)

XIAMEN HONGFAELECTROACOUSTIC CO LTD

HFD32A/30VDC0.5A/125VAC

UL 60947-1IEC/EN61810-1

VDE40018867UL E133481

High FrequencyTransformer(T1)

ShenZhen JiaMeiRuiELECTRONICSCO.,LTD

JBK-13E-259

21Ts

20Ts

21TsClass B

IEC 62109-1IEC 62109-2

Tested withappliance

Page 87: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- BobbinCHANG CHUNPLASTICS CO LTD T375J V-0, 150 °C

UL 1694UL 94UL 746A

UL E59481

- WireTAI-I ELECTRICWIRE & CABLE COLTD

UEWB 130 °C UL 1446 UL E85640

- Mylar tape

JINGJIANG YAHUAPRESSURESENSITIVEGLUE CO LTD

CT-280B No flame retard-ant+, 130 °C UL 510A UL E165111

- Tripleinsulated wire

FURUKAWAELECTRIC CO LTD TEX-E 130 °C

UL 1446IEC/EN62368-1

UL E206440VDE 006735

- Varnish

ZHUHAICHANGXIAN NEWMATERIALSTECHNOLOGY COLTD

E962 130 °C UL 1446 UL E335405

- Core TDG EP13 TP4 10*10*10mmIEC 62109-1IEC 62109-2

Tested withappliance

Heat sinkEAST Group Co.,Ltd.

Sheet metal,AL6063

220×39×70mm IEC 62109-1IEC 62109-2

Tested withappliance

--Below list is the critical components on the DC-DC board

Inductor (L1)

SHENZHENFERROCOILELECTRONICSTECHNOLOGYCO.,LTD

T184-8 65Ts, 304 uH,Class B

IEC 62109-1IEC 62109-2

Tested withappliance

- WirePACIFIC ELECTRICWIRE & CABLE(SHENZHEN) COLTD

UEW/U@ 130 °C UL 1446 UL E201757

- VarnishSHENZHENHUAJINGMEICHEMICAL CO LTD

8562/a 155 °C UL 1446 UL E322508

- Baffle HON TAIMATERIAL CO LTD HT-E3502 V-0, 130 °C

UL 746EUL 94UL 746A

UL E122230

- EpoxyDONGGUANEATTOELECTRONICMATERIAL CO LTD

3300A-1/3300B-1

V-0, 130 °C UL 746C UL E218090

- Tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

PZ* (b) 130 °C UL 510A UL E165111

Page 88: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- Core

SHENZHEN CITYMAHANMAGNETOELECTRIC CO. LTD.

T184-8IEC 62109-1IEC 62109-2

Tested withappliance

X capacitor(C291, C290)

SHENZHENSURONGCAPACITORSCO., LTD..

MPP105J6311120P0

630V, 1.0UF, V-0, -40 °C to 85 °C, X2

IEC 62109-1IEC 62109-2

Tested withappliance

MOSFETS(Q54, Q55)

Infineon Technolo-gies AG

IPW65R041CFD

650V, 68.5A, -55 °C to 150 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Inductor (L29,L30)

JEPULSTECHNOLOGY(SHENZHEN)CO.,LTD

BCK3001-096 400P x 2C x 12Ts,22.6 uH, Class B

IEC 62109-1IEC 62109-2

Tested withappliance

- Insulation pa-per

E I DUPONT DENEMOURS & COINC

Nomex 410 220 °CUL 1694UL 94UL 746A

UL E34739

-Tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

PF* (d)(g) 180 °C UL 510A UL E165111

- AlternativeSHENZHEN MEIXINELECTRONIC COLTD

MXPI-310F 180 °C UL 510A UL E304309

- Margin tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

WF* (c)(h) 130 °C UL 510A UL E165111

- EpoxyDONGGUANEATTOELECTRONICMATERIAL CO LTD

E-500 (XX) V-0, 130 °C UL 746C UL E218090

- BobbinKINGBOARDLAMINATESHOLDINGS LTD

KB-6160C V-0, 130 °CUL 1694UL 94UL 746A

UL E123995

- Varnish

SUZHOU TAIHUELECTRICADVANCEDMATERIAL CO LTD

T-4260(a) 155 °C UL 1446 UL E228349

- PCBKINGBOARDLAMINATESHOLDINGS LTD

FR-4 130 °C, V-0 UL 94 UL E123995

- Core TDG HOLDING CO.,LTD

PQ32/30TP4W 30*25*28mm

IEC 62109-1IEC 62109-2

Tested withappliance

AlternativeSHENZHEN CLICKTECHNOLOGY CO.LTD

PQ32-1060N1:LI400P x 2C x 12Ts,22.6 uH, Class B

IEC 62109-1IEC 62109-2

Tested withappliance

Page 89: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- Wire

PACIFIC ELECTRICWIRE & CABLE(SHENZHEN) COLTD

MW79-C 155 °C UL 1446 UL E201757

- AlternativeTAI-I ELECTRICWIRE & CABLE COLTD

MW79-C 155 °C UL 1446 UL E85640

- Tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

PF-301 180 °C UL 510A UL E165111

- Alternative SYMBIO INC KA180 200 °C UL510AULE50292

- Margin tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO.LTD

WF* (c)(h) 130 °C UL 510A UL E165111

- EpoxyDONGGUANEATTOELECTRONICMATERIAL CO LTD

E-500 (XX) V-0, 130 °C UL 746C UL E218090

- BobbinE I DUPONT DENEMOURS & COINC

Nomex 410 220 °CUL 1694UL 94UL 746A

UL E34739

- AlternativeZHUZHOU TIMESELECTRICINSULATION COLTD

TJ6640NMN 180 °CUL 1694UL 94UL 746A

UL E355960

- Varnish KYOCERACHEMICAL CORP TVB2180T*(a) 155 °C UL 1446 UL E83702

- Alternative

ELANTASELECTRICALINSULATIONELANTAS PDG INC

V1630FS 130 °C UL 1446 UL E75225

- PCBSHENGYITECHNOLOGY COLTD

FR-4 130 °C, V-0 UL 94 UL E109769

- AlternativeKINGBOARDLAMINATESHOLDINGS LTD

FR-4 130 °C, V-0 UL 94 UL E123995

- Core DMEGC PQ32/30DMR95 34*30*30mm

IEC 62109-1IEC 62109-2

Tested withappliance

X capacitor(C305, C306,C307, C308)

XIAMENFARATRONIC COLTD

MMKP82 630V, 47nF, -40 °Cto 105 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Page 90: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

Transformer(T12)

SHENZHEN CLICKTECHNOLOGYCO,.LTD

BCK5501-1069

200x 4P x 4TsN2: COPPER FOIL,

2TsN3: COPPER FOIL,

2Ts

200x 4P x 4TsClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- BobbinE I DUPONT DENEMOURS & COINC

410 220 °C, V-0UL 1694UL 94UL 746A

E34739

- Core ANCI EE55/55/21ACP95 58*42*9mm

IEC 62109-1IEC 62109-2

Tested withappliance

- WireTAI-I ELECTRICWIRE & CABLE COLTD

UEWF 155 °C UL 1446 UL E85640

- Alternative

PACIFIC ELECTRICWIRE & CABLE(SHENZHEN) COLTD

UEF1/U@ 155 °C UL 1446 UL E201757

- Mylar tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

PF-301 180 °C UL 510A UL E165111

- Margin tape 3M COMPANY 44D(a) 130 °C UL 510A UL E17385

- Varnish KYOCERACORPORATION TVB2180T*(a) 155 °C UL 1446 UL E83702

- EpoxyDONGGUANEATTOELECTRONICMATERIAL CO LTD

E-500 (XX) V-0, 130 °C UL 746C UL E218090

- TubeGREAT HOLDINGINDUSTRIAL COLTD

TFL 200 °C, VW-1 UL 224 UL E156256

Inductor (L13L26)

JEPULSTECHNOLOGY(SHENZHEN)CO.,LTD

LC12-028100Ts

1TsClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- BobbinE I DUPONT DENEMOURS & COINC

FR530(l)(+)(f1),FR530L(l)(+)(f1)

V-0, 155 °CUL 94UL 746A

UL E41938

Page 91: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- WireSHENZHENCHENGWEIINDUSTRY CO LTD

(x)UEW-E-(&)-(*) 130 °C UL 1446 UL E227475

- Alternative FENG CHINGMETAL CORP xUEW-2 130 °C UL 1446 UL E172395

- AlternativeSHENZHENCHENGWEIINDUSTRY CO LTD

(x)PEW(EI)-F 155 °C UL 1446 UL E227475

- Alternative FENG CHINGMETAL CORP xPEW 155 °C UL 1446 UL E172395

- EpoxyDONGGUANEATTOELECTRONICMATERIAL CO LTD

3300A-1/3300B-1

V-0, 130 °C UL 746C UL E218090

- Mylar tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

WF* (c)(h) 130 °C UL 510A UL E165111

- Epoxy baffleKINGBOARDLAMINATESHOLDINGS LTD

KB-6160C V-0, 130 °CUL 746BUL 94UL 746A

UL E123995

- Core JING YUAN CH7 T12.7*7.92*6.35IEC 62109-1IEC 62109-2

Tested withappliance

AlternativeSHENZHEN CLICKTECHNOLOGYCO.LTD

LC12-177

N1:100Ts

1TsClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- Margin tapeJINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

WF* (c)(h) 130 °C UL 510A UL E165111

- Wire

PACIFIC ELECTRICWIRE & CABLE(SHENZHEN) COLTD

UEW/U@ 130 °C UL 1446 UL E201757

- AlternativeTAI-I ELECTRICWIRE & CABLE COLTD

UEWB 130 °C UL 1446 UL E85640

- BobbinE I DUPONT DENEMOURS & COINC

FR530(l)(+)(f1),FR530L(l)(+)(f1)

V-0, 155 °CUL 1694UL 94UL 746A

E41938

- EpoxyDONGGUANEATTOELECTRONICMATERIAL CO LTD

3300A-1/3300B-1

V-0, 130 °C UL 746C UL E218090

Page 92: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- PCBKINGBOARDLAMINATESHOLDINGS LTD

FR-4 V-0, 130 °CUL 1694UL 94UL 746A

UL E123995

- Core KINGBOARD R7K T12.7*7.92*6.35CIEC 62109-1IEC 62109-2

Tested withappliance

Inductor (L28)SHENZHEN CLICKTECHNOLOGYCO.LTD

LC28-181

3P x3Ts, 60uH

3P x3Ts, 60uHClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- Wire

PACIFIC ELECTRICWIRE & CABLE(SHENZHEN) COLTD

MW5-C 155 °C UL 1446 UL E201757

- AlternativeTAI-I ELECTRICWIRE & CABLE COLTD

MW5-C 155 °C UL 1446 UL E85640

- AlternativeTA YA ELECTRICWIRE & CABLECO LTD

MW5-C 155 °C UL 1446 UL E84201

- EpoxyDONGGUANEATTOELECTRONICMATERIAL CO LTD

3300A-1/3300B-1

V-0, 130 °C UL 746C UL E218090

- VarnishHANG CHEUNGCOATINGS(HUIYANG) LTD

8562* 155 °C UL 1446 UL E200154

- Core DMEGC R7K T28*16*13CIEC 62109-1IEC 62109-2

Tested withappliance

Electrolyticcapacitor(C296, C297)

DONGGUAN WINSHINEELECTRONIC CO.,LTD.

063SH332M2240C40J

63Vd.c, 3300µF, -55°C to 105 °C

IEC 62109-1IEC 62109-2

Tested withappliance

X capacitor(C292, C293,C294, C295)

Xiamen FaratronicCo. Ltd. C23 63V, 3.3µF, -55 °C

to 105 °CIEC 62109-1IEC 62109-2

Tested withappliance

Diode (D94,D95)

IXYS Corporation DSSK 60-02A 200V, 2×30A, -55°C to 175 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Transformer(T8)

Shenzhen SpitzerElectronic Co., Ltd GR24020T5 N1:N2:N3=20:24:2

4, 0.64mH, Class BIEC 62109-1IEC 62109-2

Tested withappliance

- Tripleinsulated wire

COSMOLINK CO.LTD. TIW-M 130 °C

UL 2352UL 60950-1IEC/EN62368-1

UL E213764VDE 138053

Page 93: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- Tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

PZ-280 130 °C UL 510A UL E165111

- Alternative

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

PF*(d)(g) 155 °C UL 510A UL E165111

- TubeCHANGYUANELECTRONICSGROUP CO LTD

CB-TT-L -1,200 °C UL 224 UL E180908

- Varnish

SUZHOU TAIHUELECTRICADVANCEDMATERIAL CO LTD

T-4260(a) 155 °C UL 1446 UL E228349

- Glue

GUANGZHOUPOCHELY NEWMATERIALTECHNOLOGY COLTD

5225A/B 130 °C, V-0UL 94UL 746B

UL E204979

- BobbinCHANG CHUNPLASTICS CO LTD T375J 150 °C, V-0

UL 94UL 746B

UL E59481

- Core NCD LP3 14*14*14mmIEC 62109-1IEC 62109-2

Tested withappliance

Transformer(T3, T2)

JEPULSTECHNOLOGY(SHENZHEN)CO.,LTD

BCK5501-204

20P x 2P x 8TsN2: COPPER FOIL,

25 x 30mm x4TsN3: COPPER FOIL,

4Ts

20P x 2P x 8TsClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- BobbinE I DUPONT DENEMOURS & COINC

FR530(l)(+)(f1),FR530L(l)(+)(f1)

V-0, 155 °CUL 1694UL 94UL 746A

E41938

- Core TDG HOLDING CO.,LTD TP4

Ferrite,55mm*55mm*21mm

IEC 62109-1IEC 62109-2

Tested withappliance

- Wire FENG CHINGMETAL CORP xUEW-2 130 °C UL 1446 UL E172395

Page 94: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- Alternative

PACIFIC ELECTRICWIRE & CABLE(SHENZHEN) COLTD

UEW/U@ 130 °C UL 1446 UL E201757

- AlternativeTAI-I ELECTRICWIRE & CABLE COLTD

UEWB 130 °C UL 1446 UL E85640

- Mylar tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

CT-280B 130 °C UL 510A UL E165111

- Alternative3M COMPANYELECTRICALMARKETS DIV(EMD)

1350F-1 (b) 130 °C UL 510A UL E17385

- Margin tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

WF* (c)(h) 130 °C UL 510A UL E165111

- Alternative

3M COMPANYELECTRICALMARKETS DIV(EMD)

44 (a) 130 °C UL 510A UL E17385

- Teflon TubeGREAT HOLDINGINDUSTRIAL COLTD

TFL 200 °C, VW-1 UL 224 UL E156256

- AlternativeCHANGYUANELECTRONICSGROUP CO LTD

CB-TT-L 200 °C, VW-1 UL 224 UL E180908

- Varnish

SUZHOU TAIHUELECTRICADVANCEDMATERIAL CO LTD

T-4260(a) 155 °C UL 1446 UL E228349

- EpoxyDONGGUANEATTOELECTRONICMATERIAL CO LTD

E-500 (XX) V-0, 130 °C UL 746C UL E218090

AlternativeSHENZHEN CLICKTECHNOLOGYCO,.LTD

BCK5501-1063

20P x 2P x 8TsN2: COPPER FOIL,

4TsN3: COPPER FOIL,

4Ts

20P x 2P x 8TsClass B

IEC 62109-1IEC 62109-2

Tested withappliance

Page 95: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- BobbinE I DUPONT DENEMOURS & COINC

FR530(l)(+)(f1),FR530L(l)(+)(f1)

V-0, 155 °CUL 1694UL 94UL 746A

E41938

- Core Various VariousFerrite,55mm*55mm*21mm

IEC 62109-1IEC 62109-2

Tested withappliance

- WireTAI-I ELECTRICWIRE & CABLE COLTD

UEWB 130 °C UL 1446 UL E85640

- AlternativePACIFIC ELECTRICWIRE & CABLE(SHENZHEN) COLTD

UEF1/U@ 155 °C UL 1446 UL E201757

- Alternative FENG CHINGMETAL CORP xUEW 130 °C UL 1446 UL E172395

- Mylar tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

CT(b)(g) 130 °C UL 510A UL E165111

- Margin tapeJINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

WF* (c)(h) 130 °C UL 510A UL E165111

- Varnish KYOCERACORPORATION TVB2180T*(a) 155 °C UL 1446 UL E83702

- EpoxyDONGGUANEATTOELECTRONICMATERIAL CO LTD

E-500 (XX) V-0, 130 °C UL 746C UL E218090

- TubeGREAT HOLDINGINDUSTRIAL COLTD

TFL 200 °C , VW-1 UL 224 UL E156256

Diode (D16,D14, D15, D17)

Advanced PowerTechnology Inc

APT30DQ120BG*

1200V, 30A, -55 °Cto 175 °C

IEC 62109-1IEC 62109-2

Tested withappliance

X capacitor(C33)

EACO Capacitor Inc STH-250-20-44#

250 Va.c., 20 uF, -40 °C to 85 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Electrolyticcapacitor (C31,C30)

HUNAN AIHUAGROUP CO.,LTD

ELH1JM472P50KC

63 Vd.c, 4700 uF, -40 °C to 105 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Fuse (F1, F2,F3)

CONQUERELECTRONICS COLTD

ABE(VI) 250 Va.c., 40 Aa.c.,175 °C

UL 248-1UL 248-14

UL E82636

Relay (RLY1)SONG CHUANPRECISION CO.,LTD

MV011P1-1AH-C

60VDC, 100A, -40 °C to 70 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Page 96: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

Y capacitor(C26, C27, C28,C29, C135,C136)

Shantou High-NewTechnologyDev. Zone SongtianEnterprise Co., Ltd.

CE Series 250Va.c., 10000pF,-25 °C to 125°C, Y2

UL 60384-14IEC/EN60384-14

UL E208107VDE::40025748

X capacitor (C38, C39,C169, C170)

SONG CHUANPRECISION CO.,LTD

CBB21 630Vd.c., 0.1uF, -40°C to 105°C

IEC 62109-1IEC 62109-2

Tested withappliance

MOSFETS (Q5,Q6, Q7,Q8, Q9,Q10, Q11, Q12)

Infineon Technolo-gies AG IRFP4668PBF 200V, 130A, -55 °C

to 175 °CIEC 62109-1IEC 62109-2

Tested withappliance

MOSFETS(Q49)

Fairchild Semicon-ductor FQP6N90C 900V, 6A, -55 °C to

150 °CIEC 62109-1IEC 62109-2

Tested withappliance

Transformer(T9)

SHENZHEN CLICKTECHNOLOGYCO., LTD

ETD29

27Ts

8Ts

6Ts

2Ts

4Ts

27TsClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- Core DMEGC EC29 DMR40 30*35*25mmIEC 62109-1IEC 62109-2

Tested withappliance

- Bobbin CHANG CHUNPLASTICS CO LTD T375HF V-0, 150 °C

UL 1694UL 94UL 746A

UL E59481

- Teflon TubeGREAT HOLDINGINDUSTRIAL COLTD

TFL VW-1, 200 °C UL 224 UL E156256

- WireTA YA ELECTRICWIRE & CABLE COLTD

LZ-UEWB 130 °C, MW 75-C UL 1446 UL E84201

- Alternative FENG CHINGMETAL CORP

xUEW 130 °C, MW 75-C UL 1446 UL E172395

- AlternativeROSHOWTECHNOLOGY COLTD

xUEW@/130,QA@-x/130 130 °C, MW 75-C UL 1446 UL E215691

- AlternativeTAI-I ELECTRICWIRE & CABLE COLTD

UEW130 °C, MW 75-C UL 1446 UL E85640

Page 97: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- Tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

CT (b)(g) 130 °C UL 510A UL E165111

- Varnish KYOCERACORPORATION TVB2180T*(a) 155 °C UL 1446 UL E83702

- Margin tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

WF* (c)(h) 130 °C UL 510A UL E165111

Grid AuxiliaryPower terminalblock(J21, J31)

YUEQING HENGJIUINDUSTRIALCO.,LTD

HA396 250V, 10A, -25 °Cto 75 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Material of J21,J31

DONGGUAN CITYFENG TONGPLASTIC CO LTD

ST-PBT 301 V-0, 75 °CUL 746CUL 94UL 746B

UL E352852

Inductor (L20)SHENZHENYUYUAN POWERCO.,LTD

T16*12*8C10Ts, 580 uH

10Ts, 580 uHClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- Wire

PACIFIC ELECTRICWIRE & CABLE(SHENZHEN) COLTD

PEWH/U 180 °C UL 1446 UL E201757

- BobbinKINGBOARDLAMINATESHOLDINGS LTD

KB-6150 V-0, 130 °CUL 1694UL 94UL 746A

UL E123995

- TubeGREAT HOLDINGINDUSTRIAL COLTD

TFL VW-1, 200 °C UL 224 UL E156256

- EpoxyDONGGUANEATTOELECTRONICMATERIAL CO LTD

3300A-1/3300B-1

V-0, 130 °C UL 746C UL E218090

- Varnish

SHEN ZHENNOBLE FLOWERTECHNOLOGYINDUSTRIAL COLTD

RT9669 V-0, 260 °CUL 746EUL 94

UL E480212

- Core T001 R10K T16*12*8C, 130IEC 62109-1IEC 62109-2

Tested withappliance

Page 98: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformityY capacitor(C217, C221,C313, C321,C322, C218,C222, C219,C220)

NAN JING YUYUEELECTRONICS COLTD

UL: CT7, 2EVDE: CT7

400V,1000pF-25 °C to 125 °C,Y1

UL 60384-14IEC/EN60384-14

UL E237728VDE40008010

X capacitor(C285)

Xiamen FaratronicCo. Ltd. C37

630Vd.c., 2.2uF, -40 °C to 105 °CV-0

IEC 62109-1IEC 62109-2

Tested withappliance

Optocoupler(U27, U25, U26)

LITE-ONTECHNOLOGYCORP

LTV-816Isolation 5000Vr.m.s, -30 °C to110 °C

UL 1577IEC/EN60747-5-5

UL E113898VDE:40015248

Transformer(T10)

SHENZHEN CLICKTECHNOLOGYCO,.LTD

EE25

48Ts

72Ts

8Ts

7Ts

48TsClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- Bobbin CHANG CHUNPLASTICS CO LTD T375HF V-0, 150 °C

UL 1694UL 94UL 746A

UL E59481

- Core DMEGC EI25C DMR40 28*20*25mm,130 °C

IEC 62109-1IEC 62109-2

Tested withappliance

- TubeGREAT HOLDINGINDUSTRIAL COLTD

TFL VW-1, 200 °C UL 224 UL E156256

- Wire

PACIFIC ELECTRICWIRE & CABLE(SHENZHEN) COLTD

UEW/U@ 130 °C, MW 75-C UL 1446 UL E201757

- AlternativeTA YA ELECTRICWIRE & CABLE COLTD

LZ-UEWB 130 °C, MW 75-C UL 1446 UL E84201

- AlternativeTAI-I ELECTRICWIRE & CABLE COLTD

UEW130 °C, MW 75-C UL 1446 UL E85640

- AlternativeROSHOWTECHNOLOGY COLTD

xUEW@/130,QA@-x/130 130 °C, MW 75-C UL 1446 UL E215691

- Alternative FENG CHINGMETAL CORP

xUEW 130 °C, MW 75-C UL 1446 UL E172395

Page 99: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- Tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

CT (b)(g) 130 °C UL 510A UL E165111

- Varnish KYOCERACORPORATION TVB2180T*(a) 155 °C UL 1446 UL E83702

- Margin tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

WF* (c)(h) 130 °C UL 510A UL E165111

X capacitor(C259, C260)

SHANTOU HIGH-NEWTECHNOLOGYDEVELOPMNTZONE SONGTIANENTERPRISE COLTD

MPX 275V, 0.33uF, -40 °C to 110 °C, X2

UL 60384-14IEC/EN60384-14

UL E208107VDE40034679

- Alternative

SHENZHENSURONGCAPACITORS COLTD

MPX/MKP 280V, 0.33uF, -40 °C to 110 °C, X2

UL 60384-14IEC/EN60384-14

UL E314875VDE40008924

D88

SHEN ZHEN XINGHONG YANGELECTRONICCO.,LTD

DB106 800V, 1A, -55 °C to150 °C

IEC 62109-1IEC 62109-2

Tested withappliance

MOSFETS(Q50)

FAIRCHILDSEMICONDUCTORCORP

FQPF4N90C 900V, 4A, -55 °C to150 °C

IEC 62109-1IEC 62109-2

Tested withappliance

Inductor (L21,L22)

SHENZHENYUYUAN POWERCO., LTD

PPI184040*2pcs

N1: 2.0 mHN2: 2.0 mHClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- Core POCO PPI184040 T9*5*3CIEC 62109-1IEC 62109-2

Tested withappliance

- Wire

PACIFIC ELECTRICWIRE & CABLE(SHENZHEN) COLTD

PEWH/U 180 °C, MW 30-C UL 1446 UL E201757

- Varnish

SHEN ZHENNOBLE FLOWERTECHNOLOGYINDUSTRIAL COLTD

RT9669 V-0, 260 °CUL 746EUL 94

UL E480212

- PCBKINGBOARDLAMINATESHOLDINGS LTD

KB-6160C V-0, 130 °CUL 746EUL 94

UL E123995

Page 100: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- TapeJINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

CT-280B 130 °C UL 510A UL E165111

- EpoxyDONGGUANEATTOELECTRONICMATERIAL CO LTD

3300A-1/3300B-1

V-0, 130 °C UL 746C UL E218090

Transformer(T11)

SHENZHEN CLICKTECHNOLOGYCO,.LTD

EI25

15Ts

90Ts

10Ts

10Ts

15TsClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- Bobbin CHANG CHUNPLASTICS CO LTD T375HF V-0, 150 °C

UL 1694UL 94UL 746A

UL E59481

- Core Various Various 28.0x 6.5x23.5mmIEC 62109-1IEC 62109-2

Tested withappliance

- TubeGREAT HOLDINGINDUSTRIAL COLTD

TFL VW-1, 200 °C UL 224 UL E156256

- Wire

PACIFIC ELECTRICWIRE & CABLE(SHENZHEN) COLTD

UEW/U@ 130 °C, MW 75-C UL 1446 UL E201757

- Alternative TA YA ELECTRICWIRE & CABLE COLTD

LZ-UEWB 130 °C, MW 75-C UL 1446 UL E84201

- Alternative TAI-I ELECTRICWIRE & CABLE COLTD

UEW130 °C MW 75-C UL 1446 UL E85640

- Alternative ROSHOWTECHNOLOGY COLTD

xUEW@/130,QA@-x/130 130 °C, MW 75-C UL 1446 UL E215691

- Alternative FENG CHINGMETAL CORP

xUEW 130 °C, MW 75-C UL 1446 UL E172395

- TapeJINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

CT (b)(g) 130 °C UL 510A UL E165111

Page 101: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- Varnish KYOCERACORPORATION TVB2180T*(a) 155 °C UL 1446 UL E83702

- Margin tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUECO LTD

WF* (c)(h) Flame retardant+,130 °C UL 510A UL E165111

X capacitor(C269)

XIAMENFARATRONIC COLTD

C24 63V, 470nF, -55 °Cto 125 °C

IEC 62109-1IEC 62109-2

Tested withappliance

MOSFETS(Q51)

Vishay Intertechnol-ogy, Inc., IRF740PBF 400V, 10A, - 55 to

150 °CIEC 62109-1IEC 62109-2

Tested withappliance

Heat sinkEAST Group Co.,Ltd. AL6063 279×72×40mm

IEC 62109-1IEC 62109-2

Tested withappliance

--Below list is the critical components on the IGBT Driver board

Transformer(T1)

SHENZHEN CLICKTECHNOLOGYCO,.LTD

EE-10

N1: 2UEWØ0.13×1P 240TSN2: 2UEWØ0.14×1P 113TSClass B

IEC 62109-1IEC 62109-2

Tested withappliance

- BobbinCHANG CHUNPLASTLCS CO.,LTD

T375HF V-0, 150 °C UL94 UL E59481

- CoreDMEGCMAGNETICS CO.,LTD

EE10 R10K 12×13×5mmIEC 62109-1IEC 62109-2

Tested withappliance

- Alternative GUANDA EE10 GH10 12×13×5mmIEC 62109-1IEC 62109-2

Tested withappliance

- Tape

JINGJIANG YAHUAPRESSURESENSITIVE GLUEFTY

CT (b)(g) 130 °C UL 510A E165111

- WirePACIFIC ELECTRICWIRE & CABLECO., LTD

UEF1/U@ MW-79C, 155 °C UL 1446 E201757

- AlternativeTA YA ELECTRICWIRE & CABLECO., LTD

LZ-UEWB MW-79C, 130 °C UL 1446 E84201

- AlternativeTAI-I ELECTRICWIRE & CABLECO., LTD

UEWFMW-79C, 155 °C UL 1446 E85640

- AlternativeROSHOWTECHNOLOGYCO ., LTD

xUEW@/155,QA@-x/155 MW-79C, 155 °C UL 1446 E215691

- AlternativeFENG CHINGMETAL CORP xFSW MW-79C, 155 °C UL 1446 E172395

Page 102: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

- VarnishKYOCERACORPORATION TVB2180T*(a) MW 28-C, 155 °C UL 1446 E83702

-TubeGREAT HOLDINGINDUSTRIAL CO.,LTD

TFL VW-1, 200 °C UL 224 E156256

-EPOXY

DONGGUANEATTOELECTRONICMATERIAL CO.,LTD

E-500(XX) V-0, 130 °CUL 94UL 746C

E218090

Optocoupler(U1)

FAIRCHILDSEMICONDUCTORCORP

FOD3150 Isolation 5000Vrms-40 °C to 100 °C UL1577 UL E90700

--Below list is the critical components on the control board

MCU (U3) Texas Instruments TMS320F28377SZWTT -40 °C to 125 °C

IEC 62109-1IEC 62109-2

Tested withappliance

--Below list is the critical components on the LCD board

Transformer(T2)

SHENZHEN CLICKTECHNOGY CO.,LTD

TB1301-005 50mA:5mA, -20 °Cto 70 °C

IEC 62109-1IEC 62109-2

Tested withappliance

-MAGNETWIRE

TAI-I ELECTRICWIRE & CABLE COLTD

UEWF-E MW 80-C,155 °C UL 1446 E85640

-AlternativeFENG CHINGMETAL CORP xFSW-NY MW 80-C,155 °C UL 1446 E172395

-CaseCHANG CHUNPLASTICS CO LTD 4115(f1) 120 °C, V-0, thick-

ness:0.75mm

UL 746AUL 94UL 746B

E59481

- AlternativeCHANG CHUNPLASTICS CO LTD 4130 140 °C, V-0, thick-

ness:0.74mm

UL 746AUL 94UL 746B

E59481

- BaseCHANG CHUNPLASTICS CO LTD 4115(f1) 120 °C, V-0, thick-

ness: 0.75mm

UL 746AUL 94UL 746B

E59481

- AlternativeCHANG CHUNPLASTICS CO LTD 4130 140 °C, V-0, thick-

ness: 0.74mm

UL 746AUL 94UL 746B

E59481

- EPOXY

GUANGZHOUWELLSELECTRONICMATERIAL CO LTD

9002GA/B-SY V-0, 90 °CUL 94UL 746C

E229633

- Alternative

DONGGUANEATTOELECTRONICMATERIAL CO LTD

3300A-1/3300B-1 V-0, 130 °C

UL 94UL 746C

E218090

Page 103: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-1

Clause Requirement Test Result Remark Verdict

TRF_IEC62109_1B

list of critical components

Object / part No. Manufacturer/trademark Type / model Technical data Standard Mark(s) of

conformity

U21

UL: TEXASINSTRUMENTSTUCSON CORPVDE: TEXASINSTRUMENTSDEUTSCHLANDGMBH

ISO1050DUBR

-40 °C to 125 °C,isolation 2500Va.c.

UL 1577DIN V VDE V0884-10

VDE40016131UL E181974

Note:(1) If no special indicate, list of critical components are applied for all models.(2) Throughout this file (CDF) a commais used as the decimal separator.

........ End of test report

Page 104: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

TRF_IEC62109_2B

TEST REPORTIEC 62109-2:2011

Safety of power converters for use in photovoltaic power systemsPart 2: Particular requirements for inverters

Report Number. ............................ : 64.290.18.05995.01 part 2 of 2

Date of issue ................................. : 2019-04-08

Total number of pages ................. : 30 pages

.......................... : EAST Group Co., Ltd.

Address ......................................... : No.6 Northern Industry Road, Songshan Lake Sci. & Tech.Industry Park, 523808 DongGuan City, Guangdong Province,PEOPLE'S REPUBLIC OF CHINA

Test specification:

Standard ....................................... : IEC/EN 62109-2:2011

Test procedure ............................. : CE_LVD

Non- N/A

Test Report Form No.................... : IEC62109_2B

Test Report Form(s) Originator ... : LCIE - Laboratoire Central des Industries Electriques

Master TRF ................................... : Dated 2016-08

Copyright © 2010 Worldwide System for Conformity Testing and Certification of ElectrotechnicalEquipment and Components (IECEE), Geneva, Switzerland. All rights reserved.This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copyrightowner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the reader'sinterpretation of the reproduced material due to its placement and context.

If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to theCB Scheme procedure shall be removed.

This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratoryand appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.

General disclaimer:

The test results presented in this report relate only to the object tested.This report shall not be reproduced, except in full, without the written approval of the Issuing CB TestingLaboratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB,responsible for this Test Report.

Page 105: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter
Page 106: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

List of Attachments (including a total number of pages in each attachment):

This test report contains 2 parts listed in below table:

Item Description Pages

Part 1 IEC/EN 62109-1:2010 test report 103

Part 2 IEC/EN 62109-2:2011 test report 30

This test report shall be also used in conjunction with 12 pages of photo documentation.

Summary of testing:

All tests were carried out according to IEC 62109-2(ed.1). The text of IEC 62109-2(ed.1) was approvedby

CENELEC as a European Standard without any modification.

Tests performed (name of test and test clause):

Clause Requirement

4.4.4.15 Fault-tolerance of protection for grid-interactive inverters

4.4.4.17 Cooling system failure Blanketing test

4.7.4.2 Steady state output voltage at nominal DC input

4.7.4.3 Steady state output voltage across the DC input range

4.7.4.4 Load step response of the output voltage at nominal DC input

4.7.4.5 Steady state output frequency

4.7.5.2 Sinusoidal output voltage waveform requirements

4.8.2.1 Array insulation resistance detection for inverters for ungrounded arrays

4.8.3.5 Protection by residual current monitoring

Summary of compliance with National Differences (List of countries addressed):

The product fulfils the requirements of _________ (insert standard number and edition and delete thetext in parenthesis, leave it blank or delete the whole sentence, if not applicable)

Copy of marking plate:The artwork below may be only a draft. The use of certification marks on a product must be authorizedby the respective NCBs that own these marks.

See Report No.: 64.290.18.05995.01 part 1 of 2.

Page 107: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

Test item particulars................................................ :

Equipment mobility ................................................. : movable hand-held stationary fixed transportable for building-in

Connection to the mains ......................................... : pluggable equipment direct plug-in permanent connection for building-in

Environmental category .......................................... : outdoor indoor indoor Unconditional conditional

Over voltage category Mains .................................. : OVC I OVC II OVC III OVC IV

Over voltage category PV ....................................... : OVC I OVC II OVC III OVC IV

Mains supply tolerance (%) ..................................... : +/- 10%

Tested for power systems ....................................... : TN system

IT testing, phase-phase voltage (V) ......................... : N/A

Class of equipment ................................................. : Class I Class II Class III Not classified

Mass of equipment (kg) ........................................... : Net weight: 22.3 kg (Approx.)

611*547*150

Pollution degree ...................................................... : PD II

IP protection class ................................................... : IP 20 (indoor use only)

Testing .................................................................... :

Date of receipt of test item ...................................... : 2018-10-29

Date (s) of performance of tests .............................. : 2018-11-01 to 2019-03-18

Possible test case verdicts:- test case does not apply to the test object ............. : N/A- test object does meet the requirement .................. : P (Pass)- test object was not evaluated for the requirement . : N/E- test object does not meet the requirement ............ : F (Fail)General remarks:"(See Enclosure #)" refers to additional information appended to the report."(See appended table)" refers to a table appended to the report.The tests result presented in this report relate only to the object tested.

This report shall not be reproduced except in full without the written approval of the testing laboratory.List of test equipment must be kept on file and available for review.Additional test data and/or information provided in the attachments to this report.Throughout this report a comma / point is used as the decimal separator.Abbreviations used in the report:Basic insulation (BI); Supplementary insulation (SI); Double insulation (DI); Reinforced insulation (RI);Functional insulation (FI); Single fault condition (SFC); Normal condition (NC); Supply overvoltage category(OVC); Pollution degree (PD), CDF (Data form for electrical equipment and machinery)

-clause 4.2.5 of IECEE 02:

Page 108: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

The application for obtaining a CB Test Certificateincludes more than one factory location and adeclaration from the Manufacturer stating that thesample(s) submitted for evaluation is (are)representative of the products from each factory hasbeen provided .......................................................... :

Yes

Not applicable

When differences exist; they shall be identified in the General product information section.

Name and address of factory (ies) ........................ :Factory name: EAST Group Co., Ltd.

Address: No.6 Northern Industry Road, Songshan Lake Sci. & Tech. Industry Park, 523808 DongGuan City,Guangdong Province, PEOPLE'S REPUBLIC OF CHINA

General product information:See Report No.: 64.290.18.05995.01 part 1 of 2

Model different:N/A

Electrical Ratings:See Report No.: 64.290.18.05995.01 part 1 of 2

Page 109: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

4 General testing requirements P

4.4.4 Single fault conditions to be applied P

4.4.4.15 Fault-tolerance of protection for grid-interactiveinverters

P

4.4.4.15.1 Fault-tolerance of residual current monitoringaccording to 4.8.3.5: the residual currentmonitoring system operates properly

P

a) ..- The inverter ceases to operate (see appended table)4.4.4.15.1

P

- Indicates a fault in accordance with §13.9 P

- Disconnect from the mains P

- not re-connect after any sequence ofremoving and reconnecting PV power

P

- not re-connect after any sequence ofremoving and reconnecting AC power

P

- not re-connect after any sequence ofremoving and reconnecting both PV andAC power

P

b) ..- The inverter continues to operate P

- the residual current monitoring systemoperates properly under single faultcondition

P

- Indicates a fault in accordance with §13.9 P

c) ..- The inverter continues to operate regardlessof loss of residual current monitoring functionality

N/A

- not re-connect after any sequence ofremoving and reconnecting PV power

N/A

- not re-connect after any sequence ofremoving and reconnecting AC power

N/A

- not re-connect after any sequence ofremoving and reconnecting both PV andAC power

N/A

- Indicates a fault in accordance with §13.9 N/A

4.4.4.15.2 Fault-tolerance of automatic disconnecting means P

4.4.4.15.2.1

The means provided for automatic disconnectionof a grid-interactive inverter from the mains shall:

P

- disconnect all grounded current-carrying P

Page 110: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

conductors from the mains

- disconnect all ungrounded current-carryingconductors from the mains

P

- be such that with a single fault applied to thedisconnection means or to any other locationin the inverter, at least basic insulation orsimple separation is maintained between thePV array and the mains when thedisconnecting means is intended to be in theopen state.

See appended table4.4.4.15.2 Fault-tolerance ofautomatic disconnecting

P

4.4.4.15.2.2

Design of insulation or separation complies withrequirements of 7.3.7 of Part 1: report here Part 1comment and verdict.

P

4.4.4.15.2.3

For non-isolated inverter, automatic checking ofthe isolation provided by a disconnect means aftersingle fault.

(see appended table) P

If the check fail:

- any still-functional disconnection means shallbe left in the open position

P

- at least basic or simple separation shall bemaintained between the PV input and themains

P

- the inverter shall not start operation P

- the inverter shall indicate a fault inaccordance with 13.9

P

4.4.4.16 A stand-alone inverter with a transfer switch totransfer AC loads from the mains or other ACbypass source to the inverter output:

Stand-alone mode waschecked by the testsaccordingly for model:EA5KHD

P

- shall continue to operate normally P

- shall not present a risk of fire as the result ofan out-of-phase transfer

P

- shall not present a risk of shock as the resultof an out-of-phase transfer

P

- And having control preventing switching:components

P

4.4.4.17 Cooling system failure Blanketing test

No hazards according to the criteria of sub-clause4.4.3 of Part 1 shall result from blanketing theinverter.

This test is not required for inverters restricted to

See appended test tableCooling system failureBlanketing test.

P

Page 111: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

use only in closed electrical operating areas.

Test stop condition: time duration value or P

4.7 Electrical ratings tests P

4.7.4 Stand-alone Inverter AC output voltage and frequency P

4.7.4.1 General P

4.7.4.2 Steady state output voltage at nominal DC input

The steady-state AC output voltage shall not beless than 90 % or more than 110 % of the ratednominal voltage with the inverter supplied with itsnominal value of DC input voltage.

(See attached table) P

4.7.4.3 Steady state output voltage across the DC inputrange

The steady-state AC output voltage shall not beless than 85 % or more than 110 % of the ratednominal voltage with the inverter supplied withany value within the rated range of DC inputvoltage.

(See attached table) P

4.7.4.4 Load step response of the output voltage atnominal DC input

The AC output voltage shall not be less than 85 %or more than 110 % of the rated nominal voltagefor more than 1,5 s after application or removal ofa resistive load.

(See attached table) P

4.7.4.5 Steady state output frequency

The steady-state AC output frequency shall notvary from the nominal value by more than +4 %or 6 %.

(See attached table) P

4.7.5 Stand-alone inverter output voltage waveform P

4.7.5.1 General P

4.7.5.2 The AC output voltage waveform of a sinusoidaloutput stand-alone inverter shall have a totalharmonic distortion (THD) not exceeding of 10 %and no individual harmonic at a level exceeding6 %.

(See attached table) P

4.7.5.3 Non-sinusoidal output waveform requirements N/A

4.7.5.3.1 General N/A

4.7.5.3.2 The total harmonic distortion (THD) of the voltagewaveform shall not exceed 40 %.

N/A

4.7.5.3.3 The slope of the rising and falling edges of the N/A

Page 112: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

positive and negative half-cycles of the voltagewaveform shall not exceed 10 V/µs measuredbetween the points at which the waveform has avoltage of 10 % and 90 % of the peak voltage forthat half-cycle.

4.7.5.3.4 The absolute value of the peak voltage of thepositive and negative half-cycles of the waveformshall not exceed 1,414 times 110 % of the RMSvalue of the rated nominal AC output voltage.

N/A

4.7.5.4 Information requirements for non-sinusoidalwaveforms

The instructions provided with a stand-aloneinverter not complying with 4.7.5.2 shall includethe information in 5.3.2.6.

N/A

4.7.5.5 Output voltage waveform requirements for inverters for dedicated loads.

For an inverter that is intended only for use with a known dedicated load, thefollowing requirements may be used as an alternative to the waveformrequirements in 4.7.5.2 to 4.7.5.3.

N/A

The combination of the inverter and dedicatedload shall be evaluated to ensure that the outputwaveform does not cause any hazards in the loadequipment and inverter, or cause the loadequipment to fail to comply with the applicableproduct safety standards.

N/A

The inverter shall be marked with symbols 9 and15 of Table C.1 of Part 1.

N/A

The installation instructions provided with theinverter shall include the information in 5.3.2.13.

N/A

4.8 Additional tests for grid-interactive inverters P

4.8.1 General requirements regarding inverter isolationand array grounding

P

- Ungrounded. P

- Transformer-less type. P

4.8.2 Array insulation resistance detection for invertersfor ungrounded and functionally grounded arrays

Ungrounded. P

4.8.2.1 Array insulation resistance detection for invertersfor ungrounded arrays

P

Inverter shall have means to measure DCinsulation resistance from PV input (array) toground before starting operation

P

Or Inverter shall be provided with instruction in N/A

Page 113: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

accordance with 5.3.2.11.

Measured DC insula P

Inverter measurement circuit shall be capable ofdetecting insulation resistance below the limitvalue R= Vmax/30mA under normal conditions

The limit of the PV arrayinsulation resistance:Vmax PV =550 Vd.c.(see appended table)

P

Inverter measurement circuit shall be capable ofdetecting insulation resistance below the limitvalue R= Vmax/30mA with ground fault in the PVarray

Isolated inverters shall indicate a fault if theinsulation resistance is less than the limit value

P

Isolated inverter fault indication maintained untilinsulation resistance has recovered to a valuehigher than the limit value

P

Non-isolated inverters, or inverters with isolation not complying with the leakagecurrent limits in the minimum inverter isolation requirements in Table 30:

P

- shall indicate a fault in accordance with 13.9 P

- shall not connect to the mains P

4.8.2.2 Array insulation resistance detection for invertersfor functionally grounded arrays

N/A

a-1)The value of the total resistance, includingthe intentional resistance for array functionalgrounding, the expected insulation resistance ofthe array to ground, and the resistance of anyother networks connected to ground (for examplemeasurement networks) must not be lower than R= (VMAX PV/30 mA) ohms.

N/A

a-2) The installation instructions shall include theinformation required in 5.3.2.12.

N/A

b-1) As an alternative to a), or if a resistor valuelower than in a) is used, the inverter shallincorporate means to detect, during operation, ifthe total current through the resistor and anynetworks (for example measurement networks) inparallel with it, exceeds the residual currentvalues and times in Table 31

N/A

b-2) Inverter shall either disconnect the resistor or N/A

b-3) If the inverter is a non-isolated inverter, orhas isolation not complying with the leakagecurrent limits in the minimum inverter isolationrequirements in Table 30, it shall also disconnect

N/A

Page 114: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

from the mains.

c) The inverter shall have means to measure theDC insulation resistance from the PV input toground before starting operation, in accordancewith 4.8.2.1.

N/A

4.8.3 Array residual current detection P

4.8.3.1 General P

4.8.3.2 30 mA touch current type test for isolatedinverters

Transformer- less type N/A

4.8.3.3 Fire hazard residual current type test for isolatedinverters

Transformer- less type N/A

4.8.3.4 N/A

- The requirement for additional protection in4.8.3.1 can be met by provision of an RCDwith a residual current setting of 30 mA,located between the inverter and the mains.

N/A

- The selection of the RCD type to ensurecompatibility with the inverter must be madeaccording to rules for RCD selection in Part 1.

N/A

- The RCD provided integral to the inverter, or N/A

- The RDC provided by the installer if details ofthe rating, type, and location for the RCD aregiven in the installation instructions per5.3.2.9.

N/A

4.8.3.5 Protection by residual current monitoring P

4.8.3.5.1 General P

Where required by Table 30, the inverter shallprovide residual current monitoring that functionswhenever the inverter is connected to the mainswith the automatic disconnection means closed.

P

The residual current monitoring means shallmeasure the total (both a.c. and d.c. components)RMS current.

P

As indicated in Table 30 for different invertertypes, array types, and inverter isolation levels,detection may be required for excessivecontinuous residual current, excessive suddenchanges in residual current, or both, according tothe following limits:

P

a) Continuous residual current: The inverter shall disconnect within 0,3 s andindicate a fault in accordance with 13.9 if the continuous residual current exceeds:

P

Page 115: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

- maximum 300 mA for inverters with P

- maximum 10 mA per kVA of rated continuousoutput power for inverters with continuousoutput power rating > 30 kVA.

N/A

The inverter may attempt to re-connect if thearray insulation resistance meets the limit in 4.8.2.

b) Sudden changes in residual current: Theinverter shall disconnect from the mains within thetime specified in Table 31

P

The inverter indicates a fault in accordance with13.9, if a sudden increase in the RMS residualcurrent is detected exceeding the value in thetable.

P

The inverter may attempt to re-connect if thearray insulation resistance meets the limit in 4.8.2.

4.8.3.5.2 Test for detection of excessive continuousresidual current: test repeated 5 times and time todisconnect shall not exceed 0,3 s.

P

4.8.3.5.3 Test for detection of sudden changes in residualcurrent repeated 5 times and each of the 5 resultsshall not exceed the time limit indicated in foreach row (30mA, 60mA and150mA) of Table 31.

P

4.8.3.6 Systems located in closed electrical operatingareas

N/A

The protection against shock hazard is notrequired if the installation information providedwith the inverter indicates the restriction for use ina closed electrical operating area, and

N/A

Installation information indicates what forms ofshock hazard protection are and are not providedintegral to the inverter, in accordance with 5.3.2.7.

N/A

The inverter shall be marked as in 5.2.2.6. N/A

5 MARKING AND DOCUMENTATION P

5.1 Marking P

5.1.4 Equipment ratings P

PV input ratings: See marking label. P

- Vmax PV (absolute maximum) (d.c. V) P

- Isc PV (absolute maximum) (d.c. A) P

a.c. output ratings: See marking label. P

Page 116: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

- Voltage (nominal or range) (a.c. V) P

- Current (maximum continuous) (a.c. A) P

- Frequency (nominal or range) (Hz) P

- Power (maximum continuous) (W or VA) P

- Power factor range P

a.c input ratings: See marking label. P

- Voltage (nominal or range) (a.c. V) P

- Current (maximum continuous) (a.c. A) P

- Frequency (nominal or range) (Hz) P

d.c. output ratings: P

- Voltage (nominal or range) (d.c. V) P

- Current (maximum continuous) (d.c. A) P

Protective class (I or II or III) I P

Ingress protection (IP) rating per part 1 IP 20 P

An inverter that is adjustable for more than onenominal output voltage shall be marked to indicatethe particular voltage for which it is set whenshipped from the factory.

N/A

5.2 Warning markings P

5.2.2 Content for warning markings P

5.2.2.6 Inverters for closed electrical operating areas N/A

Where required by 4.8.3.6, an inverter notprovided with full protection against shock hazardon the PV array shall be marked with a warningthat the inverter is only for use in a closedelectrical operating area, and referring to theinstallation instructions.

N/A

5.3 Documentation P

5.3.2 Information related to installation P

5.3.2.1 Ratings. Subclause 5.3.2 of Part 1 requires the documentation to include ratingsinformation for each input and output. For inverters this information shall be as inTable 33 below. Only those ratings that are applicable based on the type ofinverter are required.

P

PV input quantities : See user manual P

- Vmax PV (absolute maximum) (d.c. V) P

- PV input operating voltage range (d.c. V) P

- Maximum operating PV input current (d.c. A) P

Page 117: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

- Isc PV (absolute maximum) (d.c. A) P

- Max. inverter backfeed current to the array(a.c. or d.c. A)

P

a.c. output quantities: P

- Voltage (nominal or range) (a.c. V) P

- Current (maximum continuous) (a.c. A) P

- Current (inrush) (a.c. A, peak and duration) P

- Frequency (nominal or range) (Hz) P

- Power (maximum continuous) (W or VA) P

- Power factor range P

- Maximum output fault current (a.c. A, peakand duration or RMS)

P

- Maximum output overcurrent protection (a.c.A)

P

a.c. input quantities: P

- Voltage (nominal or range) (a.c. V) P

- Current (maximum continuous) (a.c. A) P

- Current (inrush) (a.c. A, peak and duration) P

- Frequency (nominal or range) (Hz) P

d.c input (other than PV) quantities: P

- Voltage (nominal or range) (d.c. V) P

- Nominal battery voltage (d.c. V) P

- Current (maximum continuous) (d.c. A) P

d.c. output quantities: P

- Voltage (nominal or range) (d.c. V) P

- Nominal battery voltage (d.c. V) P

- Current (maximum continuous) (d.c. A) P

Protective class (I or II or III) I P

Ingress protection (IP) rating per part 1 IP20 P

5.3.2.2 Grid-interactive inverter setpoints Non-adjustable to operator,setted by manufacture beforeshipment

N/A

Page 118: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

For a grid-interactive unit with field adjustable trippoints, trip times, or reconnect times, thepresence of such controls, the means foradjustment, the factory default values, and thelimits of the ranges of adjustability shall beprovided in the documentation for the PCE or inother format such as on a website. Provided

.

N/A

The setting of field adjustable setpoints shall beaccessible rom the PCE

N/A

5.3.2.3 Transformers and isolation Transformer-less N/A

whether an internal isolation transformer isprovided, and if so, what level of insulation(functional, basic, reinforced, or double) isprovided by that transformer. The instructionsshall also indicate what the resulting installationrequirements are regarding such things asearthing or not earthing the array, providingexternal residual current detection devices, etc.

N/A

An inverter shall be provided with information to the installer regarding: N/A

- providing of internal isolation transformer N/A

- the level of insulation (functional, basic,reinforced, or double)

N/A

The instructions shall also indicate what the resulting installation requirements areregarding:

N/A

- earthing or not earthing the array Not earthing N/A

- providing external residual current detectiondevices

N/A

- requiring an external isolation transformer, N/A

5.3.2.4 Transformers required but not provided N/A

An inverter that requires an external isolation transformer not provided with theunit, shall be provided with instructions that specify, and for the external isolationtransformer with which it is intended to be used:

N/A

- the configuration type N/A

- electrical ratings N/A

- environmental ratings N/A

5.3.2.5 PV modules for non-isolated inverters P

Non-isolated inverters shall be provided withinstallation instructions that require PV modulesthat have an IEC 61730 Class A rating

P

Page 119: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

If the maximum AC mains operating voltage ishigher than the PV array maximum systemvoltage then the instructions shall require PVmodules that have a maximum system voltagerating based upon the AC mains voltage.

N/A

5.3.2.6 Non-sinusoidal output waveform information N/A

The instruction manual for a stand-alone inverter not complying with 4.7.5.2 shallinclude a warning that:

N/A

- the waveform is not sinusoidal, N/A

- some loads may experience increasedheating,

N/A

- the user should consult the manufacturers ofthe intended load equipment before operatingthat load with the inverter

N/A

The inverter manufacturer shall provide information regarding: N/A

- what types of loads may experience increasedheating

N/A

- recommendations for maximum operatingtimes with such loads

N/A

The inverter manufacturer shall specify for the waveforms as determined by thetesting in 4.7.5.3.2 through 4.7.5.3.4.:

N/A

- THD N/A

- slope N/A

- peak voltage N/A

5.3.2.7 Systems located in closed electrical operatingareas

N/A

Where required by 4.8.3.6, an inverter not provided with full protection againstshock hazard on the PV array shall be provided with installation instructions:

N/A

- requiring that the inverter and the array mustbe installed in closed electrical operatingareas

N/A

- indicating which forms of shock hazardprotection are and are not provided integral tothe inverter (for example the RCD, isolationtransformer complying with the 30 mA touchcurrent limit, or residual current monitoring forsudden changes)

N/A

5.3.2.8 Stand-alone inverter output circuit bonding P

Where required by 7.3.10, the documentation for an inverter shall include thefollowing:

P

Page 120: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

- if output circuit bonding is required but is notprovided integral to the inverter, the requiredmeans shall be described in the installationinstructions, including which conductor is to bebonded and the required current carryingcapability or cross-section of the bondingmeans;

N/A

- if the output circuit is intended to be floating,the documentation for the inverter shallindicate that the output is floating.

P

5.3.2.9 N/A

Where the requirement for additional protection in4.8.3.1 is met by requiring an RCD that is notprovided integral to the inverter, as allowed by4.8.3.4, the installation instructions shall state theneed for the RCD,.

N/A

and shall specify its rating, type, and requiredcircuit location

N/A

5.3.2.10 Remote indication of faults P

The installation instructions shall include anexplanation of how to properly make connectionsto (where applicable), and use, the electrical orelectronic fault indication required by 13.9.

P

5.3.2.11 External array insulation resistance measurementand response

N/A

The installation instructions for an inverter for use with ungrounded arrays thatdoes not incorporate all the aspects of the insulation resistance measurement andresponse requirements in 4.8.2.1, must include:

N/A

- for isolated inverters: an explanation of whataspects of array insulation resistancemeasurement and response are not provided, and

N/A

- an instruction to consult local regulations todetermine if any additional functions arerequired or not;

N/A

- for non-isolated inverters: an explanation ofwhat external equipment must be provided inthe system, and

N/A

- what the setpoints and response implementedby that equipment must be, and:

N/A

- how that equipment is to be interfaced withthe rest of the system.

N/A

5.3.2.12 Array functional grounding information N/A

Page 121: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

Where approach a) of 4.8.2.2 is used, the installation instructions for the invertershall include all of the following:

N/A

a) the value of the total resistance between thePV circuit and ground integral to the

N/A

b) the minimum array insulation resistance toground that system designer or installer mustmeet when selecting the PV panel and systemdesign, based on the minimum value that thedesign of the PV functional grounding in the

N/A

c) the minimum value of the total resistance R =VMAX PV/30 mA that the system must meet,with an explanation of how to calculate the

N/A

d) a warning that there is a risk of shock hazardif the total minimum resistance requirement isnot met.

N/A

5.3.2.13 Stand-alone inverters for dedicated loads N/A

Where the approach of 4.7.5.5 is used, theinstallation instructions for the inverter shallinclude a warning that the inverter is only to beused with the dedicated load for which it wasevaluated, and

N/A

shall specify the dedicated load. N/A

5.3.2.14 Identification of firmware version(s) P

An inverter utilizing firmware for any protectivefunctions shall provide means to identify thefirmware version.

P

This can be a marking, but the information canalso be provided by a display panel,communications port or any other type of user

The firmware version can beidentified on the displaypanel.

P

7 Protection against electric shock and energy hazards P

7.3 Protection against electric shock P

7.3.10 Additional requirements for stand-alone inverters P

One circuit conductor bonded to earth to create agrounded conductor and an earthed system.

IT system, neutral wasfloating.

N/A

The means used to bond the grounded conductorto protective earth provided within the inverter or

N/A

Page 122: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

as part of the installation P

If not provided integral to the inverter, the requiredmeans shall be described in the installationinstructions as per 5.3.2.8.

P

The means used to bond the grounded conductorto protective earth shall comply with therequirements for protective bonding in Part 1,

P

If the bond can only ever carry fault currents instand-alone mode, the maximum current for thebond is determined by the inverter maximumoutput fault current.

P

Output circuit bonding arrangements shall ensurethat in any mode of operation, the system onlyhas the grounded circuit conductor bonded toearth in one place at a time..

P

Switching arrangements may be used, in whichcase the switching device used is to be subjectedto the bond impedance test along with the rest ofthe bonding path

N/A

Inverters intended to have a circuit conductorbonded to earth shall not impose any normalcurrent on the bond except for leakage current.

P

Outputs that are intentionally floating with nocircuit conductor bonded to ground, must not haveany voltages with respect to ground that are ashock hazard in accordance with Clause 7 ofParts 1 and 2.

P

The documentation for the inverter shall indicatethat the output is floating as per 5.3.2.8.

P

7.3.11 Functionally grounded arrays N/A

All PV conductors in a functionally grounded arrayshall be treated as being live parts with respect toprotection against electric shock.

N/A

9 Protection against fire hazards P

9.3 Short-circuit and overcurrent protection P

9.3.4 Inverter backfeed current onto the array P

The backfeed current testing and documentation requirements in Part 1 apply,including but not limited to the following.

P

Inverter backfeed current onto the PV array P

Page 123: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

This inverter backfeed current value shall beprovided in the installation instructions regardlessof the value of the current, in accordance withTable 33.

P

13 Physical requirements P

13.9 Fault indication P

Where this Part 2 requires the inverter to indicate a fault, both of the followingshall be provided:

P

a) a visible or audible indication, integral to theinverter, and detectable from outside theinverter, and

P

b) an electrical or electronic indication that canbe remotely accessed and used.

P

The installation instructions shall includeinformation regarding how to properly makeconnections (where applicable) and use theelectrical or electronic means in b) above, inaccordance with 5.3.2.10.

P

Page 124: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

4.4.4 TABLE: Single fault condition to be applied P

Ambient temperature ( C) ................................. : 25 C

Power source for EUT: Manufacturer, model/type,output rating ...................................................... : --

4.4.4.15.1 Fault-tolerance of residual current monitoring

ComponentNo.

Fault Supply voltage (V)

Test time Fuse # Fusecurrent

(A)

Observation

CT1 (pin 8 topin 9) on PV

board

Shortcircuit

PV: 360Vd.c.AC: 230Va.c. 5min -- --

The fault applied during theunit operation. After appliedthe fault, the PV inputshutdown and LCD display

damage. No hazard.Recoverable.

CT2 (pin 8 topin 9) on PV

board

Shortcircuit

PV: 360Vd.c.AC: 230Va.c. 5min -- --

The fault applied during theunit operation. After appliedthe fault, the PV inputshutdown and LCD display

damage. No hazard.Recoverable.

R22 Opencircuit

PV: 360Vd.c.AC: 230Va.c. 5min -- --

The fault applied during theunit operation. After appliedthe fault, the unit operatedas normal. No damage. Nohazard. Recoverable.

R213 on PVboard

Opencircuit

PV: 360Vd.c.AC: 230Va.c. 5min -- --

The fault applied during theunit operation. After appliedthe fault, the PV inputshutdown and LCD display

turn into bypass mode. Nodamage. No hazard.Recoverable.

RLY3 (pin 4 topin 5)

Shortcircuit

PV: 360Vd.c.AC: 230Va.c. 5min -- --

The fault applied during theunit operation, the unitoperated as normal afterapplied the fault. When theunit shutdown and restarted,the unit could not restart andLCD display alarmed

No damage. No hazard.Recoverable.

Page 125: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

RLY11 (pin 4 topin 5)

Shortcircuit

PV: 360Vd.c.AC: 230Va.c. 5min -- --

The fault applied during theunit operation, the unitoperated as normal afterapplied the fault. When theunit shutdown and restarted,the unit could not restart andLCD display alarmed

No damage. No hazard.Recoverable.

U9 (VCC toGEN) on control

board

Shortcircuit

PV: 360Vd.c.AC: 230Va.c. 5min -- --

The fault applied during theunit operation. After appliedthe fault, the unit shutdownimmediately and LCDdisplay alarmed " SYS CAN

. Q3 was damaged. Nohazard. Unrecoverable.

T9 (pin14 afterD87 to pin 11)

on DC-DCboard

Shortcircuit

PV: 360Vd.c.AC: 230Va.c. 5min -- --

The fault applied during theunit operation. After appliedthe fault, the unit shutdownimmediately and LCDblacked. No damage. Nohazard. Recoverable.

U15 (pin 3 to pin5) on DC-DC

board

Shortcircuit

PV: 360Vd.c.AC: 230Va.c. 5min -- --

The fault applied during theunit operation. After appliedthe fault, the unit shutdownimmediately and LCDblacked. No damage. Nohazard. Recoverable.

U25 (pin 7 topin 8) on control

board

Shortcircuit

PV: 360Vd.c.AC: 230Va.c. 5min -- --

The fault applied during theunit operation. After appliedthe fault, the unit operatedas normal. When the PVinput was removed, the LCDblacked after a few seconds.No damage. No hazard.Recoverable.

Supplementary information:

Page 126: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

4.4.4 TABLE: Single fault condition to be applied P

Ambient temperature ( C) .................................. : 25 C

Power source for EUT: Manufacturer, model/type,output rating ...................................................... : --

4.4.4.15.2 Fault-tolerance of automatic disconnecting means

ComponentNo.

Fault Grid voltage (V)

Test time Fuse # Fusecurrent

(A)

Observation

RLY5 Shortcircuit

PV: 360Vd.c.AC: 230Va.c. 5min -- --

The fault applied during the unitoperation, the unit operated asnormal after applied the fault.When the unit shutdown andrestarted, the unit could notrestart and LCD display alarmed

damage. No hazard.Recoverable.

RLY6 Shortcircuit

PV: 360Vd.c.AC: 230Va.c. 5min -- --

The fault applied during the unitoperation, the unit operated asnormal after applied the fault.When the unit shutdown andrestarted, the unit could notrestart and LCD display alarmed

damage. No hazard.Recoverable.

RLY8 Shortcircuit

PV: 360Vd.c.AC: 230Va.c. 5min -- --

The fault applied during the unitoperation, the unit operated asnormal after applied the fault.When the unit shutdown andrestarted, the unit could notrestart and LCD display alarmed

damage. No hazard.Recoverable.

RLY10 Shortcircuit

PV: 360Vd.c.AC: 230Va.c. 5min -- --

The fault applied during the unitoperation, the unit operated asnormal after applied the fault.When the unit shutdown andrestarted, the unit could notrestart and LCD display alarmed

damage. No hazard.Recoverable.

Check that the relays fulfil the basic insulation or simple separationbased on the PV circuit working voltage. Yes

Each active phase can be switched. (L and N) Yes

Supplementary information: The investor can disconnect from grid during a relay occurred a single failure.

Page 127: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

4.4.4.17 Cooling system failure Blanketing test P

Test voltage (Vd.c.) ........................ 360Vd.c.

Test current (Id.c.) 12Ad.c., 12Ad.c.

Test voltage (Va.c.) ........................ 230Va.c.

Test current (Ia.c.) 21.7Aa.c.

tamb1 ( C) ........................................ 26.0 C

tamb2 ( C) ........................................ 26.0 C

Test 7 hours

maximum temperature T of part/at:: T ( C) Tmax ( C)

Enclosure outer surface, rear 53.6 90

Enclosure outer surface, front 57.5 90

Enclosure outer surface, left side 51.0 90

Mounting surfaces 56.9 90

Supplementary information:Operation mode: PV supply to grid and battery (5.5kW), during the test, no hazard.

4.7.4.2 &4.7.4.3 &4.7.4.4 &4.7.4.5

Steady state output voltage at nominal DC input &Steady state output voltage across the DC input range &Load step response of the output voltage at nominal DC input &Steady state output frequency

P

AC output U (V) Frequency (Hz) Condition/status CommentsL1 L2 L1 L2 L1 L2

232.0 -- -- 50.00 -- -- Without load PV supply the AC load,at PV voltage: 250 Vd.c.

231.7 -- -- 50.01 -- -- Resistive loadapplication

231.8 -- -- 49.98 -- -- Resistive load removal

232.0 -- -- 49.99 -- -- Without load PV supply the AC load,at PV voltage: 360 Vd.c.

231.8 -- -- 50.01 -- -- Resistive loadapplication

231.8 -- -- 50.01 -- -- Resistive load removal

232.3 -- -- 49.99 -- -- Without loadPV supply the AC load,at PV voltage: 450 Vd.c.231.7 -- -- 49.99 -- -- Resistive load

application232.3 50.01 Resistive load removal

Page 128: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

AC output U (V) Frequency (Hz) Condition/status CommentsL1 L2 L3 L1 L2 L3

232.1 -- -- 49.98 -- -- Without load Battery supply the ACload, and battery supplyat 46.4 Vd.c..

Battery type: Lithium.232.4 -- -- 49.99 -- -- Resistive load

application

231.8 -- -- 50.00 -- -- Resistive load removal

232.2 -- -- 50.00 -- -- Without load Battery supply the ACload, and battery supplyat 51.2 Vd.c..

Battery type: Lithium.232.1 -- -- 50.00 -- -- Resistive load

application

231.8 -- -- 50.01 -- -- Resistive load removal

232.0 -- -- 50.01 -- -- Without load Battery supply the ACload, and battery supplyat 57.6 Vd.c.

Battery type: Lithium.231.7 -- -- 50.00 -- -- Resistive load

application

231.9 -- -- 49.99 -- -- Resistive load removal

232.3 -- -- 49.99 -- -- Without load Battery supply the ACload, and battery supplyat 40 Vd.c..

Battery type: Lead-acid.232.1 -- -- 49.99 -- -- Resistive load

application

232.0 -- -- 50.01 -- -- Resistive load removal

232.3 -- -- 50.00 -- -- Without load Battery supply the ACload, and battery supplyat 48 Vd.c..

Battery type: Lead-acid.232.4 -- -- 50.00 -- -- Resistive load

application

232.0 -- -- 50.00 -- -- Resistive load removal

232.4 -- -- 50.00 -- -- Without load Battery supply the ACload, and battery supplyat 58 Vd.c.

Battery type: Lead-acid.231.9 -- -- 49.99 -- -- Resistive load

application

232.6 -- -- 50.00 -- -- Resistive load removal

Supplementary information:

Page 129: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

4.7.5.2 Sinusoidal output voltage waveform requirements P

Model EA5KHD

Harmonic.Nr.(U)

P/ Prated : % of rated output power Limits (% ofFundamental)5% 50% 100%

2 0.116% 0.018% 0.005% 6%

3 0.148% 0.931% 0.991% 6%

4 0.054% 0.011% 0.007% 6%

5 0.199% 0.490% 0.570% 6%

6 0.025% 0.014% 0.002% 6%

7 0.083% 0.296% 0.396% 6%

8 0.031% 0.010% 0.003% 6%

9 0.049% 0.192% 0.278% 6%

10 0.015% 0.009% 0.005% 6%

11 0.045% 0.122% 0.203% 6%

12 0.014% 0.001% 0.005% 6%

13 0.053% 0.081% 0.171% 6%

14 0.013% 0.021% 0.007% 6%

15 0.051% 0.055% 0.126% 6%

16 0.016% 0.015% 0.002% 6%

17 0.042% 0.022% 0.103% 6%

18 0.009% 0.007% 0.007% 6%

19 0.059% 0.018% 0.086% 6%

20 0.026% 0.012% 0.006% 6%

21 0.052% 0.012% 0.087% 6%

22 0.019% 0.003% 0.010% 6%

23 0.080% 0.014% 0.078% 6%

24 0.042% 0.010% 0.012% 6%

25 0.093% 0.012% 0.041% 6%

26 0.011% 0.025% 0.011% 6%

27 0.089% 0.016% 0.028% 6%

28 0.024% 0.042% 0.015% 6%

29 0.078% 0.016% 0.017% 6%

30 0.014% 0.007% 0.006% 6%

31 0.044% 0.008% 0.017% 6%

Page 130: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

32 0.015% 0.007% 0.007% 6%

33 0.030% 0.022% 0.014% 6%

34 0.018% 0.003% 0.006% 6%

35 0.025% 0.014% 0.011% 6%

36 0.005% 0.006% 0.005% 6%

37 0.017% 0.014% 0.007% 6%

38 0.004% 0.004% 0.005% 6%

39 0.012% 0.007% 0.004% 6%

40 0.008% 0.011% 0.003% 6%

THD (2-40) 0.379% 1.125% 1.291% 10%

Supplementary information: PV supply to AC load output

4.7.5.2 Sinusoidal output voltage waveform requirements P

Model EA5KHD

Harmonic.Nr.(U)

P/ Prated : % of rated output power Limits (% ofFundamental)5% 50% 100%

2 0.129% 0.009% 0.011% 6%

3 0.164% 0.952% 0.992% 6%

4 0.049% 0.019% 0.004% 6%

5 0.229% 0.508% 0.576% 6%

6 0.024% 0.009% 0.003% 6%

7 0.046% 0.303% 0.377% 6%

8 0.022% 0.012% 0.010% 6%

9 0.042% 0.197% 0.272% 6%

10 0.022% 0.016% 0.005% 6%

11 0.051% 0.136% 0.210% 6%

12 0.016% 0.004% 0.006% 6%

13 0.054% 0.088% 0.159% 6%

14 0.020% 0.015% 0.017% 6%

15 0.049% 0.061% 0.131% 6%

16 0.009% 0.006% 0.012% 6%

17 0.046% 0.048% 0.102% 6%

18 0.018% 0.011% 0.011% 6%

19 0.061% 0.027% 0.078% 6%

Page 131: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

20 0.012% 0.011% 0.003% 6%

21 0.064% 0.024% 0.068% 6%

22 0.039% 0.008% 0.017% 6%

23 0.071% 0.013% 0.048% 6%

24 0.033% 0.044% 0.015% 6%

25 0.088% 0.013% 0.041% 6%

26 0.010% 0.017% 0.030% 6%

27 0.082% 0.013% 0.020% 6%

28 0.018% 0.024% 0.010% 6%

29 0.067% 0.016% 0.018% 6%

30 0.012% 0.021% 0.011% 6%

31 0.049% 0.022% 0.006% 6%

32 0.025% 0.018% 0.008% 6%

33 0.036% 0.021% 0.006% 6%

34 0.011% 0.009% 0.007% 6%

35 0.022% 0.015% 0.008% 6%

36 0.002% 0.007% 0.004% 6%

37 0.015% 0.020% 0.003% 6%

38 0.004% 0.004% 0.003% 6%

39 0.008% 0.015% 0.002% 6%

40 0.011% 0.007% 0.004% 6%

THD (2-40) 0.396% 1.157% 1.284% 10%

Supplementary information: Battery supply to AC load output

4.8.2 TABLE: Array insulation resistance detection for inverters for ungrounded andfunctionally grounded arrays

P

4.8.2.1 Array insulation resistance detection for inverters for ungrounded arrays P

DC Voltagebelow minimum

operating voltage(V)

DC Voltage forinverter begin

operation(V)

Resistance betweenground and PV input

terminal

Required Insulationresistance

R = (VMAX PV / 30mA)

Result

PV+, (tracker 1)

115 150 16500 18333

The unit could notoperate and LCD display

INSU.TOGROUND IMPE.OCCUR

Page 132: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

PV+, (tracker 2)

115 150 16500 18333

The unit could notoperate and LCD display

INSU.TOGROUND IMPE.OCCUR

PV-, (tracker 1)

115 150 16500 18333

The unit could notoperate and LCD display

INSU.TOGROUND IMPE.OCCUR

PV-, (tracker 2)

115 150 16500 18333

The unit could notoperate and LCD display

INSU.TOGROUND IMPE.OCCUR

Note:

For isolated inverters, shall indicate a fault in accordance with 13.9 (operation is allowed); the fault indicationshall be maintained until the array insulation resistance has recovered to a value higher than the limit above

For non-isolated inverters, or inverters with isolation not complying with the leakage current limits in theminimum inverter isolation requirements in Table 30, shall indicate a fault in accordance with 13.9, and shallnot connect to the mains; the inverter may continue to make the measurement, may stop indicating a faultand may connect to the mains if the array insulation resistance has recovered to a value higher than the limitabove.

It is not required to test all PV input terminals if analysis of the design indicates that one or more terminalscan be expected to have the same result, for example where multiple PV string inputs are in parallel.

Supplementary information:

1. The setting isolation resistor value is 20 k .

2. All above tests indicate a fault in accordance with clause 13.9

4.8.3.5 TABLE: Protection by residual current monitoring P

Test conditions: See below

4.8.3.5.2 Test for detection of excessive continuous residual current P

TrackerNo.

PV

(+ or -)Input

(Vd.c.)Output

(Va.c., kW)

Baselinetrigger

current (mA)

Measured trigger time (ms), shall < 300 ms

(repeat 5 times)

1 + 360 230, 5 220 60 56 69 57 961 - 360 230, 5 225 67 44 57 76 67

Note:

maximum 300mA for inverters with continuous output po maximum 10mA per kVA of rated continuous output power for inverters with continuous output power

Page 133: TEST REPORT IEC 62109-1 Safety of Power Converter for use in ...en.eastups.com/u/cms/en/202006/03165629v091.pdf · TRF_IEC62109_1B TEST REPORT IEC 62109-1 Safety of Power Converter

IEC 62109-2Clause Requirement Test Result Remark Verdict

rating > 30 kVA.

This test shall be repeated 5 times, and for all 5 tests the time to disconnect shall not exceed 300 ms.The test is repeated for each PV input terminal. It is not required to test all PV input terminals if analysis ofthe design indicates that one or more terminals can be expected to have the same result, for examplewhere multiple PV string inputs are in parallel.

Supplementary information:All above tests indicate a fault in accordance with clause 13.9.

4.8.3.5 TABLE: Protection by residual current monitoring P

Test conditions: See below

4.8.3.5.3 TABLE: Test for detection of sudden changes in residual current P

TrackerNo.

PV

(+ or -)Input

(Vd.c.)Output

(Va.c., kW)

Baselinetrigger

current (mA)

Measured trigger time (ms), shall < 300 msfor (30 mA); <150 ms for (60 mA); <40 ms for

(150 mA) (repeat 5 times)

30 mA sudden changes in residual current1 + 360 230, 5 220 246 243 246 250 2511 - 360 230, 5 225 260 248 265 261 249

60 mA sudden changes in residual current1 + 360 230, 5 220 121 142 115 136 1241 - 360 230, 5 225 135 144 138 146 142

150 mA sudden changes in residual current1 + 360 230, 5 220 30 35 40 30 301 - 360 230, 5 225 32 26 35 35 36

Note:

The capacitive current is risen until disconnection.

Test condition: Ic + 30/60/150mA <= Icmax. R1 is set that 30/60/150mA Flow and switch S is closed.

Supplementary information:

t