TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent...

64
TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple application controller Manual version : Eng 1-07 Date : January 2011 GTM PLC Firmware version: 1_10

Transcript of TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent...

Page 1: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

TELEMETRY BEACON GTM PLC VW

With real time permanent connection Virtual Wire

PRODUCT DESCRIPTION AND PROGRAMMING MANUAL

Energize your simple application controller

Manual version : Eng 1-07 Date : January 2011 GTM PLC Firmware version: 1_10

Page 2: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.2

The GTM modules are developed to be connected to the GSM 850, GSM 900, DCS 1800 and PCS 1900 network using harmonized frequencies, therefore no particular notification is necessary. AXELPROD GSM Solutions declares its GTM products described in this manual are conform to the directive 1999/5/CE from march 9, 1999 (see conformity declaration). The information contained in this document is the proprietary information of AXELPROD GSM Solutions. The contents are confidential and any disclosure to persons other than the officers, employees, agents or subcontractors of the owner or licensee of this document, without the prior written consent of AXELPROD GSM Solutions, is strictly prohibited. Further, no portion of this publication may be reproduced, stored in a retrieval system or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, without the prior written consent of AXELPROD GSM Solutions, the copyright holder. First edition (March 2006) AXELPROD GSM Solutions publishes this manual without making any warranty as to the content contained herein. Further AXELPROD GSM Solutions reserves the right to make modifications, additions and deletions to this manual due to typographical errors, inaccurate information, or improvements to programs and/or equipment at any time and without notice. Such changes will, nevertheless be incorporated into new editions of this manual. All rights reserved. AXELPROD GSM Solutions, 2001 Trademarks

Page 3: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.3

CONTENTS 1. GTM PLC VW Introduction ...................................................................................... 5

1.1 Notes ................................................................................................................................ 5

1.2 GTM PLC VW main features ......................................................................................... 7

1.3 Vocabulary ...................................................................................................................... 8

2. GTM PLC VW programming and product description ....................................... 10

2.1 Programming principle ................................................................................................ 10

2.2 GTM PLC VW programming and function description (by PC) .............................. 13

2.2.1 Digital signal FB, CB programming ............................................................................................... 13

2.2.2 Analog signal FB, CW programming .......................................................................................... 16

2.2.3 GTM PLC VW programming by PC using the programming software .................................... 17

Tab Connection ..................................................................................................................................... 18

Tab GSM Network ................................................................................................................................. 19

Tab SMS ................................................................................................................................................. 21

Tab Status .............................................................................................................................................. 23

Tab Datalogger ...................................................................................................................................... 24

Tab Spy ................................................................................................................................................... 25

Tab Firmware ......................................................................................................................................... 26

Menu Connection .................................................................................................................................. 27

Menu Progamming ................................................................................................................................ 27

Menu Option ........................................................................................................................................... 27

Menu Help .............................................................................................................................................. 27

2.2.4 Spécial functions .............................................................................................................................. 28

GSM Signal quality on the ALPHA 2XL screen ................................................................................ 28

Update a CW value by the means of a SMS and the CW name ................................................... 29

Call function to run a process .............................................................................................................. 30

2.3 Virtual Wire .................................................................................................................... 31

2.3.1 How to start using the Virtual Wire ................................................................................................ 31

2.3.2 Once the GTM PLC VW is connected to the Virtual Wire ......................................................... 32

2.4 Turning on the GTM PLC VW ...................................................................................... 33

2.4.1 Placing the GTM PLC VW on the ALPHA 2XL controller .......................................................... 33

2.4.2 GTM PLC VW and ALPHA 2 XL controller functioning after turning ON ................................ 35

2.4.3 Two GTM PLC VW working together ............................................................................................ 37

2.5 Trouble shooting .......................................................................................................... 38

2.5.1 En utilisant les fichiers du GTM PLC VW et ceux de l’ALPHA 2 XL (Recherche basique) . 38

2.5.2 Using spy cable ................................................................................................................................ 38

2.5.3 LED behavior .................................................................................................................................... 39

3. GTM PLC VW mechanical and electrical data .................................................... 40

3.1 Mechanical data ............................................................................................................ 40

3.2 Accessories, external antenna ................................................................................... 41

3.3 data ................................................................................................................................. 41

Annexe A : Example of SMS commands ................................................................. 42

Annexe B : Table de la force du signal GSM .......................................................... 44

Page 4: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.4

ANNEXE C : Declaration of Conformity ................................................................... 45

Certifications ............................................................................................................... 46

Limitation Warranty .................................................................................................... 63

Page 5: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.5

1. GTM PLC VW Introduction

1.1 Notes The following information shown in this document is subject to change without prior notice. The GTM PLC VW is part of a new generation of wireless products using the GSM network (Global System for Mobile communication). This manual describes the GTM PLC VW and its functioning. They are intended to be used as a wireless embedded system, as an alarm system and/or as a telemetry device and can be used only with the MITSUBISHI ALPHA XL Controllers and its derivate products and will work as an extension module. The GTM PLC VW uses the SMS (Short Message System, 160 characters) to send text message on request, periodical or simple queries, as well they are able to use GPRS (General Packet Radio Service) connection to transmit data out of the EGDL (Easy Gprs Data Logger) and for its programming. In typical applications, the GTM PLC VW is a very effective solution taking into account simple and low cost mean of information transportation (SMS and GPRS). The combination between the GTM PLC VW functions and the ALPHA 2 XL controller functions will cover almost all requirements in the field of industrial automation with GSM assistance and will create then a compact and powerful solution. Besides, the GTM PLC VW can be used in many applications such as security and alarm system, telemetry, remote control, asset management, vending machines, etc…. Besides normal programming, the GTM PLC VW includes all SMS and GPRS programming and modification functionality that belong to the actual GTM family. That means programming, request, programming modification, remote control by SMS as well as GPRS programming. For any information on MITSUBISH ALPHA XL Controller and its derivate products, please refer to the corresponding Controller manual, see: http://www.mitsubishi-automation.com/products/microcontrollers.html. These manuals contain text, diagrams and explanation which will guide users in the correct programming and operation of the Controllers. Before attempting to install the GTM PLC VW in the Controller, the following manuals should be read and understood.

Page 6: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.6

MITSUBISHI Manuals for further information if need ed. Programming manual. Hardware manual. Software programming manual. Communication manual. Technical manual. AXELPROD manual Programming and description manual GTM PLC VW complete kit includes : - A GSM unit extension module. - A MITSUBISHI APLHA 2 XL 14 MR-D. - A IR-PCB linking board to be placed in the ALPHA 2 XL controller - External magnet antenna with 2.5 meter cable or small SMA antenna. - Special programming and spy cable.

Page 7: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.7

1.2 GTM PLC VW main features � 80 digital alarm criterions with unlimited SMS destination numbers � 60 analog criterions controllable by SMS � SMS remote control on any FB and ALPHA 2 XL controller outputs � Periodical control SMS, including any digital or analog values � Virtual Wire, GPRS real time and permanent bidirectional connection. See chapter 2.3 � Input / Outputs event file � SMS to EMAIL � SMS connection between ALPHA 2 XL controllers � Endless combination between ALPHA 2 XL controller and GSM unit functions � Firmware update, see http://www.axelprod.net/

Page 8: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.8

1.3 Vocabulary The purpose of this section is to describe the vocabulary used in this documentation. Keyword (Further called). Description GSM (GSM). Global System for Mobile Communications. SMS (SMS). Short Message System. A SMS is a bidirectional service for short alphanumeric (up to 160 bytes) messages. Messages are transported in a store-and-forward fashion. For point- to-point SMS, a message can be sent to another subscriber to the service, and an acknowledgement of receipt could be provided to the sender. SIM (SIM). Subscriber Identity Module. Smart card providing personal mobility, so that the user can have access to subscribed services. GPRS (GPRS). General Packet Radio Service. The data is divided into packets and is then transferred via the radio and core GPRS network. In GTM applications, it is used to repatriate the data from the GSM unit data logger to the AXELPROD EGDL server. PS: Data can not be repatriated directly to cell phones. GTM PLC VW (GTM PLC VW). GSM Transmitter Module for Programmable Logic ALPHA 2 XL Controller with Virtual Wire. IR-PCB (IR-PCB). Infra Red Printed Circuit Board. Small PCB delivered with the GTM PLC VW to link the ALPHA 2 XL controller and the GSM unit for the serial communication. FB (FB). User-friendly method combining special purpose dedicated Function Blocks used to program MITSUBISH ALPHA XL Controllers and derivate products. FBs could have a analog or digital input and a analog or digital output. FBD (FBD). Function Block Diagram. Diagram regrouping all necessary function blocks to program the ALPHA 2 XL controllers. CB (CB). Digital signal Communication Function Block Bit Device. CBs are created through the AL-PCS/WIN-E2 menu: Option/Dedicated communication…from the preprogrammed FBs. Possible values: ON or OFF

Page 9: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.9

CW (CW). Communication Word. Analog signal Communication Function Block Word Device. CWs are created through the AL- PCS/WIN-E2 menu: Option/Dedicated communication…from the preprogrammed FBs. Possible values: -32768 to -32767 AL232-CAB (AL232-CAB). Cable used to program the ALPHA 2 XL controller. AL-PCS/WIN-E2 (AL-PCS/WIN-E2). MITSUBISHI ALPHA-XL programming software and derivate product programming software. PC (PC). Personal Computer. Ordinateur personnel. Outgoing SMSSMS messages sent by the GTM PLC Incoming SMS SMS messages sent by the user to the GTM PLC VW Outgoing SMS SMS messages sent by the GTM PLC VW to the user. CBXX (CBXX). Communication Bit, any CB between CB01 to CB80. Digital signal. Possible values: ON or OFF CWXX (CWXX). Communication Word, any CW between CW01 to CW60. Analog signal. Possible values: -32768 to -32767

Symbol :

Remark

Important notice

Example

Page 10: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.10

2. GTM PLC VW programming and product description The purpose of this section is to describe the programming principle, the GTM PLC VW programming software and the product functions. The programming software can be only used with the GTM PLC VW. The following document will describe how to program the GTM PLC VW by the means of the programming software and give a description off all functions of the products. For any hardware information, please refer to the chapter 3.

2.1 Programming principle This section reference ALPHA 2 XL controller manual: Controller programming manual. Controller software manual. In this section, only the programming principle is explained. Programming details are described in chapter. 2.2 As the GSM unit has a built in intelligence that needs to be programmed as well as the ALPHA 2 XL controller does. Therefore, the user will need to program the GSM unit with its programming software and its cable or by Virtual Wire, as well as the Controller with the AL-PCS/WIN-E2 with its cable. The user will have to purchase an extra programming cable.

AL-PCS/WIN-E2 SOFTWARE Standard programming

GTM PLC VW Programming SOFTWARE or Virtual Wire SMS,period, Destinations, Periodical i/o status, etc…

Page 11: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.11

ALPHA 2 XL programming: Picture 2.1a, creating a CB list

CB, digital signal Each FB should be programmed properly and all FBs needed for SMS transmission must be wired with an OFF-DELAY. (B194, B196, B199). This section reference ALPHA 2 XL controller manual: Communication manual Ch. 6. Then, all OFF-DELAY FB will be added automatically in the FB list. The user will choose among the FB list the right OFF-DELAY FBs to create a CB list. This CB list will be scanned by the GSM unit of the GTM PLC VW for SMS generation. A maximum of 99 CBs can then be created for SMS transmission (99 alarm criterions). (See picture 2.1a). CW, analog signal FBs can contain also analog values (from -32768 to 32767). In order to reach them by SMS or by Virtual Wire, as well as for the FBs for the CBs list, all needed FBs must be selected to create the CW list. The user will choose among the FB list the right FBs to create this CW list. A list of maximum of 99 CWs can be created for consulting or modification by SMS or used for the Virtual Wire. See picture 2.1b.

Page 12: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.12

Picture 2.1b, creating a CW list.

Once the Controller is programmed, the user will run the GTM PLC VW programming software and, among other functions, associates the CBs and CW list with CB name and CW name, the corresponding SMS text and the destinations. Picture 2.1c, associating CB name, corresponding SMS text and destinations.

Page 13: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.13

2.2 GTM PLC VW programming and function description (by PC) This section presents the GTM PLC VW programming software. It will guide the user through the ALPHA 2 XL controller and the GSM unit programming and will describe its functions through clear examples: 1 Digital signal FB, CB. 2 Analog signal FB, CW. 3 Program the GSM unit using the GTM PLC VW programming software. The whole programming is saved in a non volatile memory, therefore between turning on and turning off the GSM unit, the programming remains. Before programming and choosing the “Connection” menu, the GSM unit must be ready to be properly powered.

2.2.1 Digital signal FB, CB programming After a new FBD .vls file is created using the Mitsubishi ALPHA 2XL programming software, the user must set, under the menu “Option/GSM and serial communication…”, the serial communication to “Other”.

This phase is mandatory , without it, the GTM PLC VW GSM unit is unable to communicate with the ALPHA 2 XL. At least one power turning off and on process must be done on the ALPHA 2 XL in order to take the “Other” programming into account. This process can be done later.

Page 14: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.14

Example: The user places for Input 1 (I 01) a counter with a “number of counts” of 5 (threshold at 5). Wires to the counter a OFF-DELAY FB programmed with a 300 seconds off delay.. Picture 2.2a, creating the FB05 for alarm SMS.

Then, the Option/Dedicated communication menu must be opened. Picture 2.2b, associating the FB05 with CB01 for alarm SMS creating a CB list.

Station number must be always let to 0 and communication memory always to 50 or 100

Page 15: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.15

The user will associate the FB No B5 to CBNo 1 in order to create the first alarm criterion. This Communication Bit (CB01) will be scanned by the GSM unit of the GTM PLC VW as the first criterion to generate a SMS. The same procedure will be used for further FB until a maximum of CB99. The CB list must not contain any “holes” meaning all CBs must follow each other.

The Station number must always be 0 and the communi cation memory of 50 or 100 Each FB should be programmed properly and all FBs needed for SMS transmission must be wired to an OFF-DELAY programmed with the minimum time of 180 seconds.

Page 16: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.16

2.2.2 Analog signal FB, CW programming The “Analog” FBs value can have a value from -32768 to 32767. If the user wishes to get or modify these values by SMS or use them for the VW monitoring system, these values must be declared. This declaration will be done through the CW list: Picture 2.2c, associating the FB06 with CW01 (Count) or/and CW02 (Current Count) to create a CW list.

Proceeding this way, Count and Current Count of FB06 can be used as described above. Once all FBs have been programmed along with their CB list and CW list, the user can write the programming to the ALPHA 2 XL controller.

Page 17: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.17

2.2.3 GTM PLC VW programming by PC using the progra mming software Download previously the free GTM PLC VW PROGRAMMER software from www.axelprod.net. The installation has to be done following the instructions included in the software installation. Insert the SIM card first on the module, the GTM must not be powered .

Connect the Spy/Programming jack cable to the GTM PLC VW. Connect the serial cable connector to the right PC com port.

Page 18: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.18

Tab Connection Run the software, the first window will appear: Go to the menu Connection and click on Connect. At this time, it will be asked to turn off the power supply (if it is on) a few seconds and turn it back on. Choose the right com port and click on OPEN. If the right com port is chosen, a few tens of seconds later the software and the GTM PLC VW will be connected together.

If the PIN code of the SIM card is enabled, PIN code will be ask and if the user wishes to disable it, it can be done by clicking on Disable PIN. The PIN code being disabled, it can not be enabled back by this software.

Page 19: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.19

Tab GSM Network

GSM Status: Click on GSM Status in order to get all of available GSM operators. Once the GSM operator list has been automatically filled, the user will choose the GSM band and the GSM operator among the list presented in the pull down menus. The user might choose from all automatic choice, GSM band and operators, to fully lock on one specific operator. If Automatic is chosen in the pull down menu GSM Band, the GTM PLC VW will need maximum 90 seconds to find the right GSM band automatically. (AXELPROD advises not to use this choice) If Automatic is chosen in the pull down menu GSM operator, the GTM PLC VW will choose always the best operator giving the best signal. If a specific GSM operator is chosen and the check box lock manual choice is checked , the GTM PLC VW will be locked on the chosen GSM operator. If this operator is no longer available, the GTM PLC VW will not be reachable anymore. If a specific GSM operator is chosen and the check box lock manual choice is not checked , the GTM PLC VW will be locked on the chosen GSM operator. If this operator is no longer available, the GTM PLC VW will choose automatically another available and authorized operator, but it will get back to the chosen GSM operator if it is again available.

Page 20: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.20

Activate Virtual Wire: The Virtual Wire is a powerful and simple function enabling real time GPRS permanent bi directional and real time connection between your GTM modules and your PC. It will enable the following actions: - Programming, programming modification - Real time value monitoring on www-unwired-monitoring.com - Analog/Digital Input/Output, parameter status - Firmware update* - Parameter modifications - and more... * Done under special conditions. If the user wishes to use the Virtual Wire, check the Virtual Wire check box. If it is not done, the user must fill the fields for APN, IP, USER and PASS settings. This setting information is available by the GSM operator chosen for the SIM card used in the GTM PLC VW. In most cases, the IP is 0.0.0.0, the USER and PASS are blank (leave it empty), but in any case, these settings must be checked with your GSM operator. Once the fields are filled up, the user must apply this setting to the GTM PLC VW by clicking the APPLY button, then test the Virtual Wire by clicking on the TEST button. A message box will come saying if the test is successful or not. If not, please check the settings again. A check box “Enable to send a copy of each SMS to the server” can be check in order to send a copy of every SMS, previously sent to the destination, on your account on www.unwired-monitoring.com. Test Virtual Wire: After filling up APN, IP, USER and PASS push on Test Virtual Wire in order to check if all the GSM operator GPRS setting are correct, if not please by sure to have the right settings. IMEI, copy and past the IMEI number during the registration of your module on www.unwired-monitoring.com.

Page 21: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.21

Tab SMS

Add signal quality: By checking the check box, on every SMS a signal quality message will be added representing the signal quality in %. Add credit: By checking the check box, on every SMS a credit status message will be added showing the remaining amount of credit on the prepaid SIM card. (Only valid for prepaid SIM card and if this service is available). A field is reserve for the credit string and it is specific for every GSM operator, please ask you operator for this information. Example: Swisscom. The string is *130#, therefore the field must be filled with *130#

Page 22: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.22

Enter numbers: This field is reserved to enter a destination number. Then clicking on the ADD button of the corresponding CB to add this number to the list of destination for this CB. The list is unlimited but must stay inside reasonable numbers. Each time the ADD button is clicked the menu list Add dest. number and destination menu list of the corresponding input is filled with this number. Anytime the user can delete the number by clicking the DEL button. A destination can be any email. Just program, as destination in the destination number field, the email where the SMS will be sent. Example: [email protected] PS: This email destination function can only work i f the Virtual Wire is activated. A destination can be the SMS server on www.unwired-monitoring.com. The user will choose in the menu Destination “SMS SERVER” and click on ADD button to add the SMS server as destination for the corresponding input. CBname: Name of the CB Message: Text message when the alarm appears. Destination: Destination phone number where the SMS will be sent. SMS SERVER as destination. The SMS Message will be sent to AXELPROD SMS server. Register to www.unwired-monitoring.com and enter the SIM card number working with the GTM in the right field under menu “MODULES”. Then, under the menu “SMS” will appear the SMS. (free service) SAVE and DELETE: save or delete any CB. CW name: Enter here the name of the CW used.

Page 23: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.23

Tab Status

This tab enables the user to TEST the ALPHA 2 XL CB and CW.

Page 24: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.24

Tab Datalogger

The user can choose which CB or CW will be part of the Data sent to www.unwired-monitoring.com through the Virtual Wire. Any chosen CB or CW must be previously specified as explained ch. 2.1 (create a CB list, create a CW list). These data will be sent every period of time with a specified duration, if this duration is let at 0, the sending will never stop.

Page 25: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.25

Tab Spy

This tab is used to spy the module during programming and functioning. For troubleshooting the user will have to save this window using the Save to file button and send it to AXELPROD technical support. Clear button will clear everything inside the spy window. Pause button allows to have a look inside the spy window. Once everything is programmed, click on Restart module. At this moment, the user can spy the module functioning if it works correctly according to its programming.

Page 26: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.26

Tab Firmware

This tab will tell the user if the GTM PLC VW is up-to-date or not. If not, the user will be able to upgrade the firmware by clicking on Update now.

Page 27: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.27

Menu Connection Through this menu, the user can Connect to or Disconnect from the GTM PLC VW once the cable connection procedure is done, see ch. 2.2.4. Quit will kill the GTM PLC VW GTM PROGRAMMER window and disable the com port.

Menu Progamming Read programming from file: Through this menu, the user can load previously saved programming file. Save programming to file: Through this menu, the user can save a programming file. Read programming from GTM: Through this menu, the user can load programming from the GTM PLC VW. Save programming to GTM: Through this menu, the user can save the programming in the GTM PLC VW. Clear programming form: Through this menu, the user can erase all programming fields.

Menu Option Language: Choice for the language. Simulation mode: By enabling the simulation menu, the user will be able to test the module using the spy/programming cable and the spy window, the SMS will be displayed and simulated (not sent). PS: We strongly recommend making at least one alarm SMS test at the end of the SMS simulation testing procedure with this option disabled in order to be sure that the GTM PLC VW is not in simulation mode anymore.

Menu Help About: This menu will give the software version. New spy window: Clicking this menu will create an additional spy window.

Page 28: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.28

2.2.4 Spécial functions The goal of this section is to describe special functions of the GTM PLC VW :

GSM Signal quality on the ALPHA 2XL screen It is possible to get on the ALPHA 2XL screen the GSM signal quality. See on http://www.axelprod.net/prod_gtmplc_vw.php to dowload the example. By the means of a Counter FB and its « CurrentCount » value, it is possible to display the Signal quality, see the example underneath:

The « CurrentCount » of B03 must set set to CW99 and the « Count » must be programmed at 100. The GTM PLC VW will automatically update the « Current Count » level to the signal quality in %.

Page 29: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.29

Update a CW value by the means of a SMS and the CW name It is possible to update a CW value by the means of a SMS and its name programmed during the CW name programming (see Tab SMS, CW Name ) Example: The name given for CW01 is THRESHOLD. With the following SMS, the CW01 value will be 14566 : THRESHOLD =14566 Example of reading the CW01 value: With the following SMS, a returned SMS will be: THRESHOLD? Sms returned : THRESHOLD =14566

Page 30: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.30

Call function to run a process It is possible to run a process on the ALPHA 2 XL by through a call. The user simply call the SIM card number of the GTM PLC VW (wait until the GTM hang up your call by itself) and the GSM unit will write 1 on CW98 (Current Count of the a Counter FB). An example of the Calling function is available on http://www.axelprod.net/prod_gtmplc_vw.php

- Create a counter FB and add the “Current Count” of this Counter FB at CW98. - Program on this FB for “Number of count”: 1. - Connect the Counter output to the CL (Clear input). After each call the result would be a pulse generated on the Counter output. Important notice: For security reasons, the calling number must be programmed on the SIM card number of the GTM PLC VW, otherwise no process can be generated.

Page 31: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.31

2.3 Virtual Wire The Virtual Wire is a powerful and simple function enabling real time GPRS permanent bi directional connection between your GTM modules (or your application) and your PC. The Virtual Wire is a tunnel where all information can be send to your application or send from your application to your PC. After turning on the GTM modules equipped with the new feature Virtual Wire, a permanent link is established between your application and your PC enabling all kind of actions, such as: - Programming, programming modification - Real time following, surveillance and value monitoring on http://www.unwired-monitoring.com - Analog/Digital Input/Output direct access. - Firmware update - Parameter modifications - and more... Thanks to the Virtual Wire, the GSM-GPRS cost will be strongly reduced due to its permanent connection. In fact, the connection is kept alive by the GTM modules saving disconnection and connection costs allowing the users to make actions on their applications at very low cost and in real time.

2.3.1 How to start using the Virtual Wire By the GTM PLC VW PROGRAMMING SOFTWARE . The user can enable the Virtual Wire by normally programming the GTM PLC VW and all GSM operator settings using the software. When the GTM PLC VW is turned on and after the booting time, the GTM will automatically be connected to the Virtual Wire.

Page 32: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.32

By sending an SMS . This way, the user can install the GTM PLC VW on site as it is, without any programming, then he will send the SMS from his office. The SIM card must be previously inserted and the PIN code disabled. The SMS syntax can be obtained as follow: Example using Swisscom GPRS settings: (ask your GSM operator for the settings) APN: gprs.swisscom.ch IP: 0.0.0.0 (usually 0.0.0.0) USER: “” (usually blank) PASS: “” (usually blank) SMS syntax: GPRS=gprs.swisscom.ch/0.0.0.0/no/no If USER and PASS are blank, “no” must be written in the SMS (case sensitive). If the settings are correct, the user will receive a SMS to confirm that the GTM PLC VW is connected to the Virtual Wire.

2.3.2 Once the GTM PLC VW is connected to the Virtu al Wire Once the GTM PLC VW is connected to Virtual Wire, the user is invited to register his PLC VW on the Virtual Wire dedicated monitoring and programming web site: www.unwired-monitoring.com Now the GTM PLC VW is virtually connected to your PC and the user will be able to: - Programming, programming modification - Real time monitoring on www-unwired-monitoring.com - Analog/Digital Input/Output, parameter status - Firmware update (under condition) - Parameter modifications - and more... On www.unwired-monitoring.com, a free section is reserved for the module management and the programming. A ten by ten PLC VW licensed section is reserved for real time monitoring including alarm front panel, dash board and historical graphic. Please ask for pricing to your nearest PLC VW dealer or directly to www.axelprod.net. www.unwired-monitoring.com is intuitive and all explanations are online.

Page 33: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.33

2.4 Turning on the GTM PLC VW

2.4.1 Placing the GTM PLC VW on the ALPHA 2XL contr oller

Any manipulations on the GTM PLC VW, IR-PCB or the ALPHA 2 XL controller must be done properly protected against Electrical Surge Discharges (ESD). This section reference ALPHA 2 XL controller manual: Technical manual. First the user must insert the SIM card in its holder following the drawing on the GTM PLC VW PCB.

The SIM card can be inserted before or after the programming, but must not be in any case inserted or removed when the GTM PLC VW is powered ON. The SIM card should not have any SMS in its memory. If it is the case, the user will have to erase them using a standard cell phone or they will be erase automatically by the GTM PLC.

SIM PIN CODE The user has the choice between two PIN code situations: 1) The user inserts a SIM card with PIN code disabl ed In this case it is not necessary to program the PIN code in the programmer software. The GTM PLC VW will operate with a SIM card with PIN code disabled all time. 2) The user insert a SIM card with PIN code enabled In this case the user must program the PIN code through the GTM PLC VW programmer in order to use the GTM PLC VW. During operation the GTM will enter the PIN code but will not disable it.

Page 34: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.34

Insert the IR-PCB inside the ALPHA 2 XL controller matching the male connector with the ALPHA 2 XL female connector:

Be sure to properly insert the IR-PCB in a horizontal position Slide the GTM PLC VW extension module with its housing as it is explained in the ALPHA 2 XL controller manual. The user might have to lift slightly the back of the GTM PLC VW while sliding it in order to prevent any damage on the SIM card and the circuitry. As it is almost in, just give a final push to plug the housing on the ALPHA 2 XL controller. Connect the power cable to the GTM PLC VW right terminal (+ on T1 and the GND on T2) and turn power on. If the Spy cable is connected, the user might see the task process done by the GTM PLC VW, (see ch. 2.5.2)

Page 35: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.35

Turning ON

Internal booting time

PCconnected? PROGRAMMING

Clear Controller displayGTM PLC usedas MODEM?

MODEM

Controller Display:MODEM USE

SYSTEM READYGSM Setting up

Clear Controller displayController Display:GSM BOOTING

Loading programmingController Display:LOADING PROGRAMMING

GSM setting upController Display:GSM SETTING UP

GTM PLC hardwareset up

Start Main loopController Display:SYSTEM READY

Scanning CB

CB ON orOFF?

Adding SMS anddestination to the buffer

SMS bufferempty? SMS sending

30 seconds?Check SIM card

for incoming SMS

SMS onSIM? Back to Main loop

SMS treatmentCommand

programmingrequest

Adding SMS anddestination to the buffer

SMS bufferempty?SMS sending

Scanning CB forperiodical SMS

Adding SMS anddestination to the buffer

Execute periodicalcommand or request

Scanning CB forsaving EGDL

dataEGDL data saving

24 Hours?

Scanning CB forsending data?

GPRS upload

Back to Main loop

GSM signal check

Checking:File size

Even file upload

Controller Display:INCOMING SMS

Controller Display:OUTGOING SMS

YES

YES

YES

YES

YES

YESYES

NO

NO

Boo

ting

tim

e

MAIN LOOP

YES

YES

Sca

nnin

g ti

me

2.4.2 GTM PLC VW and ALPHA 2 XL controller functioning after turning ON After turning on the GTM PLC VW and the ALPHA 2 XL controller, the following scheme explains the functioning of the whole system.

Page 36: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.36

The GTM PLC VW needs a booting time in order to execute tasks such as loading the user programming, setting up the GSM, etc… Once the system is ready, the GTM PLC VW start by scanning the CBXX for any change in order to send alarm SMS. It will also place SMS to be sent in the buffer, checking the SIM card for any incoming SMS, scanning data logging for the Virtual Wire.

Page 37: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.37

2.4.3 Two GTM PLC VW working together It is possible to make two (or more) GTM PLC VW working together through the GSM network. GTM PLC VW 1 could send SMS command to the GTM PLC VW 2 (or inversely) in order to react to this command or to run a process. The only requirement to respect in order to do so, is to program the SMS message that will be sent from GTM PLC VW 1 to GTM PLC VW 2 with a “*” at the end of the SMS. When the SMS with the “*” at its end is received by the GTM PLC VW 2, it will not send a “OK” back by SMS to GTM PLC VW 1, this will avoid SMS jam between the two GTM PLC VW.

After an event on GTM PLC VW 1, a SMS command is generated from GTM PLC VW 1 to GTM PLC VW 2 in order to turn GTM PLC VW 2 output 6 to ON: CB01 is used on GTM PLC VW 1. CB01 message from OFF to ON: CW06=220* CB01 destination: GTM PLC VW 2 SIM card number

AXELPROD strongly recommend a human intervention or control in that process when two GTM PLC VW must work together. For example a second destination, or an other CBXX, can be programmed on GTM PLC VW 1 and a digital FB (CBXX) can be connected to GTM PLC VW 2 DOUT6 in order to send a SMS to a destination when DOUT6 is turn on or off on GTM PLC VW 2. Do not add command at the end of the SMS if you use “*”

GTM PLC +

GTM

GTM PLC I GTM PLC II

GSM NETWORK

SMS : CW06=220*

Page 38: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.38

2.5 Trouble shooting

2.5.1 En utilisant les fichiers du GTM PLC VW et ce ux de l’ALPHA 2 XL (Recherche basique)

For trouble shooting report the user can reach the GTM PLC VW support of AXELPROD using the email address [email protected]. The user must joint the following files and information with the email:

− The programming file. The programming file can be obtained by exporting the programming to a text file using the extension file .txt. To get this file, use the GTM PLC VW programming software following the description ch. Menu/Save PROG to file.

− The VLS file. The VLS is the ALPHA 2XL programming file issued from the AL-PCS/WIN-E2 programming software from MITUSUBISHI.

− Serial number, IMEI, GTM PLC VW firmware version issued from the the GTM PLC VW programming software after having made the connection to the GTM PLC VW, File/Connection to GTM and tab start.

These file have to be jointed to the user email in order to help AXELPROD support to solve the problem.

2.5.2 Using spy cable In order to spy the GTM PLC VW, just plug the programming/spy cable on the GTM PLC VW and run the AXELPROD GTM SPY SOFTWARE. GTM SPY SOFTWARE at http://www.axelprod.net/

Once the trouble is appearing, the user might save the window and send it to the technical support of AXELPROD ([email protected]) or your nearest dealer. PS: Never let the spy cable on the GTM PLC VW without the SPY SOFTWARE activated.

Page 39: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.39

2.5.3 LED behavior There is two led on GTM PLC VW, one green and one red: The green led represent the GSM unit signal status as follow:

GREEN LED Status Device Status

Permanently off Device is off.

Fast blinking (period 1s)

GSM Net search / Not registered

Slow blinking (period 3s) Registered full service.

The red led represent the GTM PLC VW status, as follow:

RED LED Status Device Status

Permanently off Device is off.

Blinking (period 30s)

GTM PLC VW is ready and in idle mode, waiting for external event.

Permanently on Booting

Page 40: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.40

3. GTM PLC VW mechanical and electrical data

3.1 Mechanical data As the GTM PLC VW is an extension board all the mechanical data can be found in the Mitsubishi automation web site: http://www.mitsubishi-automation.com

Contact

1 +8 to 24 Volts

2 GND

3 NA

4 NA

5 NA

6 NA

7 NA

8 NA

9 NA

10 HB

Contact 10, Heard Beat. Open collector output activated with a maximum interval of 300 seconds. Minimum activation time : 200ms. This contact could be used as Heard Beat for the ALPHA 2XL. If the power for the GSM unit is coming from one of the ALPHA 2XL output relay. See www.axelprod.net for Hear Beat example.

Page 41: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.41

3.2 Accessories, external antenna

The GTM PLC VW needs an external in antenna.

GSM ANT-MAG2 Antenna

3.3 data Power supply 8 to 30 Volts, 500mA, better 1 A. Current consumption 30 mA, stand by < 300 mA, during a call. Temperature range -10 to 80°C, storage. -10 to 55°C, functioning. See www.axelprod.ch for more accessories.

Page 42: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.42

Annexe A : Example of SMS commands

SMS to enable the Virtual Wire: Example using Swisscom GPRS settings: (ask your GSM operator for the settings) APN: gprs.swisscom.ch IP: 0.0.0.0 (usually 0.0.0.0) USER: “” (usually blank) PASS: “” (usually blank) SMS syntax: GPRS=gprs.swisscom.ch/0.0.0.0/no/no If USER and PASS are blank, “no” must be written in the SMS (case sensitive). If the settings are correct, the user will receive a SMS to confirm that the GTM PLC VW is connected to the Virtual Wire. Programming SMS: It is possible to program manually SMS programming command: All programming position modification can be made by SMS. Only one position at a time can be modified. The SMS must start with “#” and must not contain more that 160 characters. The user might have a look on the .txt file exported from the GTM UMODULE programming software for the exact syntax, just put a “#” as first SMS character and the file text line.

Page 43: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.43

- Example: Replacing all destinations for CB01. #CB01T=+41795896562,+41795478512,+41785478752 CB01T is the “KEY” for destination for CB01. +41795896562,+41795478512,+41785478752 is the VALUE EXAMPLE - Example: Erasing destination of CB01. #CB01T= - Example: request for destination of CB01. #CB01T? List of key:

CLÉS EXEMPLE DES VALEURS DESCRIPTIONS

GTMNAME PENDERGAST Module Name

CB01N FIRE Name for CB01

CB02N LEVEL DETECTION Name for CB02

CB03N INTRUSION Name for CB03

Etc…

CB01T +41752366598,+458965698 Destination for alarm on CB01

CB02T +89562363598 Destination for alarm on CB01

CB03T +3365896587 Destination for alarm on CB01

VIRTUAL YES Virtual Wire activated

VIRTUAL NO Virtual Wire deactivated

CREDIT *130# Remaining credit at the end of the SMS

SIGNAL YES Niveau du signal à la fin du SMS

Consult the exported text file from the GTM PLC VW programming software for the rest of the keys.

Page 44: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.44

Annexe B : Table de la force du signal GSM

Value Value on SMS Signal strenght Indication according to std GSM phone

0 0% -113 dBm or less Signal very low. 1 3% -111 dBm May indicate only 1 antenna bar 2 6% -109 dBm May indicate only 1 antenna bar 3 9% -107 dBm May indicate only 1 antenna bar 4 12% -105 dBm May indicate only 1 antenna bar 5 16% -103 dBm May indicate only 1 antenna bar 6 19% -101 dBm May indicate only 2 antenna bar 7 22% -99 dBm May indicate only 2 antenna bar 8 25% -97 dBm May indicate only 2 antenna bar 9 29% -95 dBm May indicate only 2 antenna bar 10 32% -93 dBm May indicate only 3 antenna bar 11 35% -91 dBm May indicate only 3 antenna bar 12 38% -89 dBm May indicate only 3 antenna bar 13 41% -87 dBm May indicate only 3 antenna bar 14 45% -85 dBm May indicate only 3 antenna bar 15 48% -83 dBm May indicate only 4 antenna bar 16 51% -81 dBm May indicate only 4 antenna bar 17 54% -79 dBm May indicate only 4 antenna bar 18 57% -77 dBm May indicate only 4 antenna bar 19 61% -75 dBm May indicate only 4 antenna bar 20 64% -73 dBm May indicate only 4 antenna bar 21 67% -71 dBm May indicate only 4 antenna bar 22 70% -69 dBm May indicate only 4 antenna bar 23 74% -67 dBm May indicate only 4 antenna bar 24 77% -65 dBm May indicate only 4 antenna bar 25 80% -63 dBm May indicate only 4 antenna bar 26 83% -61 dBm May indicate only 4 antenna bar 27 87% -59 dBm May indicate only 4 antenna bar 28 90% -57 dBm May indicate only 4 antenna bar 29 93% -55 dBm May indicate only 4 antenna bar 30 96% -53 dBm May indicate only 4 antenna bar 31 100% -51 dBm or more May indicate only 4 antenna bar 99 0% Not detected No bar

Page 45: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.45

ANNEXE C : Declaration of Conformity Declaration of Conformity Us AXELPROD GSM TRANSMISSION 10, ch. Du Champ-des-Bois 1234 Vessy Geneva SWITZERLAND Declare under our own responsibility that the product family: GTM, standing for Gsm Transmitter Module Which this declaration refers is conform to the following standards ETS 300 342-1 : Radio Equipment and Systems (RES) Ed2:1997 Electromagnetic compatibility (EMC) for European digital cellular telecommunications system (GSM 850-900 et GSM 1800-1900 MHz) Part 1: Mobile and portable radio and ancillary equipment EN 61000-3-2:1995 : Electromagnetic compatibility (EMC) - Part 3: Limits Section 2: Limits for harmonic current emissions (equipment input current up to and including 16 A per phase) EN 61000-3-3:1995 : Electromagnetic compatibility (EMC) - Part 3: Limits Section 3: Limitation of voltage fluctuations and flicker in low- voltage supply systems for equipment with rated current < 16 A The GTM modules are developed to be connected to the GSM 900 et GSM 1800 using harmonized frequency. Therefore no particular notification has to be done.

Page 46: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.46

Certifications

Page 47: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.47

The Telit TRIZIUM Family modules is assessed to be conform to the R&TTE Directive as stand-alone product, so If the module is installed in conformance with Dai Telecom installation instructions require no further evaluation under Article 3.2 of the R&TTE Directive and do not require further involvement of a R&TTE Directive Notified Body for the final product. In all other cases, or if the manufacturer of the final product is in doubt then the equipment integrating the radio module must be assessed against Article 3.2 of the R&TTE Directive. In all cases assessment of the final product must be made against the Essential requirements of the R&TTE Directive Articles 3.1(a) and (b), safety and EMC respectively, and any relevant Article 3.3 requirements. The Telit TRIZIUM Family modules are conforming to the following European Union Directives: R&TTE Directive 1999/5/EC (Radio Equipment & Telecommunications Terminal Equipments) Low Voltage Directive 73/23/EEC and product safety Directive 89/336/EEC for conformity for EMC. In order to satisfy the essential requisite of the R&TTE 99/5/EC directive, the TRIZIUM module is compliant with the following standards: GSM (Radio Spectrum). Standard: EN 301 511 and 3GPP 51.010-1 EMC (Electromagnetic Compatibility). Standards: EN 301 489-1 and EN 301 489-7 LVD (Low Voltage Directive) Standards: EN 60 950 Furthermore the Telit TRIZIUM Family modules are FCC Approved as module to be installed in other devices. These devices have to be used only for fixed and mobile applications. If the final product after integration is intended for portable use, a new application and FCC ID is required. The Telit TRIZIUM Family modules are conforming to the following US Directives: Use of RF Spectrum. Standards: FCC 47 Part 24 (GSM 1900) EMC (Electromagnetic Compatibility). Standards: FCC47 Part 15

Page 48: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.48

Page 49: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.49

Page 50: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.50

Page 51: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.51

Page 52: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.52

Page 53: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.53

Page 54: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.54

Page 55: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.55

Page 56: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.56

Page 57: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.57

Page 58: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.58

Page 59: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.59

Page 60: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.60

Page 61: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.61

Page 62: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.62

Page 63: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.63

Limitation Warranty Each GTM product is warranted to be free from detects in material and workmanship under normal us. The warranty period is one year and begins on the date code marked underneath the module or by the SMS command <#V>. Parts, product repairs and services are warranted for 90 days. This warranty extends only to the original buyer or end-user customer or a GTM authorized seller and does not apply, in AXELProd’s opinion, if the module has been misused, altered, neglected or damaged by accident or abnormal conditions of operation or handling. AXELprod warrants that software will operate substantially in accordance with its functional specifications for one year. GTM authorized sellers shall extend this warranty on new and unused products to end-user customers only but have no authority to extend a greater or different warranty on behalf of AXELprod. Warranty support is available if product is purchased directly from AXELProd or through a AXELProd authorized sellers outlet or Buyer has paid the applicable international price. AXELProd reserves the right to invoice Buyer for importation costs or repair/replacement parts when product purchased in one country is submitted for repair in another country. AXELProd,s warranty obligation is limited, at AXELProd option, to refund of the purchase price, free of charge repair, or replacement on a defective product which is returned to a AXELProd authorized service center within the warranty period. To obtain warranty service, contact AXELProd or your nearest GTM authorised service center or send the product, with a description of the difficulty, postage and insurance prepaid (FOB Destination), to the nearest AXELProd authorized service center. AXELprod assumes no risk for damage in transit. Following warranty repair, the product will be returned to Buyer, transportation prepaid (FOB Destination). If AXELProd determines that the failure was caused by misuse, alteration, accident or abnormal condition of operation or handling, AXELProd will provide an estimate of repair costs and obtain authorization before commencing the work. Following repair, the product will be returned to the Buyer transportation prepaid and the Buyer will be billed for the repair and return transportation charges (FQB Shipping Point). This document contains information proprietary to AXELProd. The contents are confidential and any disclosure to persons other than the officers, employees, agents or subcontractors of the owner or licensee of this document, without the prior written consent of the AXELProd, is strictly prohibited. No part of this publication may be reproduced, stored in retrieval system, or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, without the prior written consent of the copyright holder. First edition (January 2001) This manual is published by AXELProd without any warranty. Improvements and changes in this manual necessitated by typographical errors, inaccuracies, or modifications in programs and/or equipment, may be made by AXELProd at any time and without notice. Such changes will, however, be incorporated into new editions of this manual. All rights reserved. AXELProd, 2000 Document version 1.0X, english version Printed in SWITZERLAND. Trademarks Company stamp/Signature

Page 64: TELEMETRY BEACON GTM PLC VW - AxelProd · TELEMETRY BEACON GTM PLC VW With real time permanent connection Virtual Wire PRODUCT DESCRIPTION AND PROGRAMMING MANUAL Energize your simple

p.64

A complete manual of each GTM product is available for more details. Any contact should be done to your nearest GTM dealer or to :

AXELProd 10, chemin du Champ-des-bois 1234 VESSY/SWITZERLAND

phone : +41 22 784 42 04 fax : +41 22 784 43 05

http ://www.axelprod.net [email protected]