Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 1 / 45
Table of contents
1. Revisions .............................................................................................................................................. 3 2. Reference Standards and Approvals ................................................................................................ 3
2.1. Standards .............................................................................................................................................. 3
2.2. Approvals ............................................................................................................................................... 3 3. Quality assurance statement .............................................................................................................. 4 4. Identification ........................................................................................................................................ 4 5. Abbreviations & Nomenclature .......................................................................................................... 4 6. Product Description ............................................................................................................................ 6
6.1. Description of the device ....................................................................................................................... 6
6.2. layout ..................................................................................................................................................... 6
6.3. Connector and Connections .................................................................................................................. 7
6.4. Electrical & Environmental Specifications ............................................................................................ 8 7. PRODUCT FUNCTIONALITY SPECIFICATION ................................................................................ 10
7.1. USER INTERFACE ............................................................................................................................. 10
7.2. BACKLIGHT ........................................................................................................................................ 10
7.3. PUSH-BUTTON USAGE ..................................................................................................................... 10 8. High voltage Output .......................................................................................................................... 10 9. Low Voltage input (AUX 0) ............................................................................................................... 11 10. High Voltage Input ............................................................................................................................. 11 11. 0-10Vdc input ..................................................................................................................................... 11 12. Microcomm Bus Master Communication ........................................................................................ 11 13. Microcomm Bus Slave Communication ......................................................................................... 11 14. OpenTherm Communication Requirements ................................................................................... 11 15. Modbus interface ............................................................................................................................... 12 16. Outside Temperature Control ........................................................................................................... 12
16.1.1. 4 POINTS OTC CURVE ............................................................................................................................................. 12 16.1.2. HONEYWELL SIMPLIFIED OTC CURVE ................................................................................................................. 12
17. ECO working mode ........................................................................................................................... 13 18. HOLIDAY working mode ................................................................................................................... 13 19. goHAPI User interface data download ............................................................................................ 14 20. ERROR SCREENS DESCRIPTION ................................................................................................... 14 21. APPENDIX -A- .................................................................................................................................... 18
21.1. MAIN SCREENS ................................................................................................................................. 18
21.2. PUSH BUTTON ................................................................................................................................... 19
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 2 / 45
21.3. SCREENS DESCRIPTION .................................................................................................................. 20 21.3.1. MAIN MENU SCREEN ............................................................................................................................................... 20 21.3.2. TECHNICIAN MENU ACCESS CODE ...................................................................................................................... 21 21.3.3. TEXT MENU SCREEN .............................................................................................................................................. 21 21.3.4. PARAMETER/VALUE SET MENU ............................................................................................................................ 22 21.3.5. EXTENAL TEMPERATURE RELATED SCREEN SETTINGS ................................................................................. 23 21.3.6. DOMESTIC HOT WATER SETTINGS ....................................................................................................................... 24 21.3.7. PUMP POST CIRCULATION ..................................................................................................................................... 25 21.3.8. MAINTENANCE SETTINGS ...................................................................................................................................... 25 21.3.9. DEFAULT FACTORY SETTING ................................................................................................................................ 26 21.3.10. ERROR MESSAGE SCREEN ................................................................................................................................. 26 21.3.11. MENU STRUCTURE OVERVIEW ........................................................................................................................... 28
22. APPENDIX -B- .................................................................................................................................... 38
Supported Microcomm Message ID’s with functional description .................................................................... 38
Supported External microcomm Message ID’s ................................................................................................ 39 23. APPENDIX -C- IMPLEMENTED OT+ ID’S ......................................................................................... 40 24. APPENDIX –D- MODBUS IMPLEMENTATION ................................................................................. 41
24.1. Modbus configuration .......................................................................................................................... 41
24.2. Supported commands ......................................................................................................................... 41
24.3. Modbus register map ........................................................................................................................... 41
24.4. 0x11 Report Slave ID .......................................................................................................................... 44 25. APPENDIX E: EEPROM DEFAULT CONFIGURATION ................................................................... 45
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 3 / 45
1. Revisions Software
Date Description of amendments
Rev. B: Added modbus parameters settings to Technician menu under SYSTEM SETTINGS - BOILER PARAMETERS – MODBUS PARAMETERS. See paragraph 21.3.11. Added more details related to modbus setting at paragraph 24.1 Added RTC related settings/info
2. Reference Standards and Approvals
2.1. Standards
DSP49G2128 functionality fulfill the following standard:
EN 55014-1 For EMCD conformity
EN 60730 - 1
For LVD and EMCD conformity
When used together with boiler controls devices no violation of other product related to the following standards can occur:
EN298:2003
Automatic gas burner control systems for gas burners and gas burning appliances with or without fans
EN 55014-1 Electromagnetic compatibility – Emissions
EN 60730 - 1 Automatic electric controls for household and similar use
2.2. Approvals
The MMI will be used on boiler where boiler control conforms with the following EC – Directives ; system must satisfy indicated directive (self certification possible not being safety related product):
Gas Appliance Directive (90/396/EEC) Low Voltage Directive (73/23/EEC) Electro Magnetic Compatibility Directive (89/336/EEC)*
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 4 / 45
* Conformity with Electro Magnetic Compatibility Directive regarding emission for non industrial appliances can be assumed for all selected Ordering Specification (O.S.) numbers. However conformity can only be declared as part of the appliance. Regarding immunity, all controls comply with the levels for non industrial appliances.
3. Quality assurance statement Products are manufactured under an ISO 9001 (1994) based and certified Quality System. The quality system is described in the Honeywell Combustion Controls Center Quality Assurance Program and its related operational procedures and instructions. The quality system is approved by Gastec against certificate number 9.302/2. The quality organization is responsible for defining, maintaining, improving and verification of the quality systems in the field of design, production process and field quality service. Assembly processes are guided by work instructions. Patrol inspections form part of the assembly processes. Assembly inspection is performed by employees of the quality control department, using their own authorized equipment. All inspections (incoming and assembly) are performed by trained personnel and according inspection procedures.
4. Identification To ensure product tracking and identification, each board shows:- Bar code label with production data Honeywell part number
Customer part number
Notes
DSP49G2128B -
5. Abbreviations & Nomenclature MMI: man Machine Interface LCD: Liquid Crystal Display
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 5 / 45
TBD: To Be Decided ID: Identifier (data) HL: Temperature High Limit TTB: Exhaust Temperature Limit ( check ) APS: Air Pressure Switch.
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 6 / 45
6. Product Description
6.1. Description of the device The Dot Matrix DSP49G2128 MMI operates in conjunction with esys/maXsys based boiler controller having a standard microcom interface. The MMI consists of an LCD Dot matrix user interface plus below indicated additional fixtures: 0-10V power input 2 General purpose relay output Open Therm protocol MODbus protocol Multipurpose input ON/OFF at low voltage (5mA) Multipurpose input 230Vac (1mA) HW basic configuration functionalities of DSP49G1053B . Support of maximum 12 rubber conductive key pushbutton position RTC with battery back-up
6.2. layout Overall dimensions Max 162mm x 93mm BOARD thickness 1,6 mm Fixing points n° 4 holes Ø 3 mm) Tolerances according to STP0015 Housing To be provided by OEM
Fig .1 Front view with optional proposed front panel
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 7 / 45
6.3. Connector and Connections
6 5 4
3 2 1 PTHCONNECTOR FRONT VIEW SMDCONNECTOR FRONT VIEW - PIN NUMBERING - - PIN NUMBERING -
Pin PTH
Pin
SMD Description Connection
ESYS 1 COMM. X01 1 1 Microfit communication – ESYS 1
X01 2 3 Microfit communication – ESYS 1 Tx
X01 3 5 Microfit communication – 7 Vcc from ESYS 1
X01 4 7 Microfit
X01 5 9 Microfit
X01 6 11 Microfit
ESYS 1 COMM. X01 7 2 Microfit communication – ESYS 1 GND
X01 8 4 Microfit communication – ESYS 1 Rx
X01 9 6 Microfit communication – 20 Vcc from ESYS 1
X01 10 8 Microfit
X01 11 10 Microfit
X01 12 12 Microfit Gnd
EXT COMM X03 1 1 Microfit Ext Communication +24v
X03 2 3 Microfit Ext Communication Rx
X03 3 5 Microfit Ext Communication +5v
X03 4 2 Microfit Ext Communication Gnd
X03 5 4 Microfit Ext Communication Tx
X03 6 6 Microfit Ext Communication Gnd
MISC
INPUT
X04 1 1 Microfit 0 – 10 Vdc input +
X04 2 3 Microfit Open Therm Gnd
X04 3 5 Microfit Open Therm Signal
X04 4 7 Microfit External sensor Gnd
X04 5 9 Microfit External sensorSignal
X04 6 2 Microfit 0 – 10 Vdc input -
X04 7 4 Microfit
X04 8 6 Microfit
X04 9 8 Microfit Room thermostat /Aux in0
X04 10 10 Microfit Room thermostat /Aux in0 Gnd
HIGH
VOLTAGE
I/O
X05 1 Minifit Rly1 Free contact – Alarm Output
X05 2 Minifit Rly1 Free contact – Alarm Output
X05 3 Minifit Rly2 Free contact – Burner on
X05 4 Minifit Rly2 Free contact – Burner on
X05 5 Minifit Generic HV input – phase input
6 4 2
5 3 1
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 8 / 45
X05 6 Minifit Generic HV input – neutral input
X07 1 1 Microfit Modbus Pup 5v
X07 2 3 Microfit Modbus Pdown Gnd
X07 3 5 Microfit Modbus Gnd
X07 4 7 Microfit
MODBUS
AUX IN
X07 5 2 Microfit Modbus B
X07 6 4 Microfit Modbus A
X07 7 6 Microfit Modbus Tb
X07 8 8 Microfit
6.4. Electrical & Environmental Specifications
Supply voltage
Powered via Microcomm , therefore ensure its specification is met (only low voltage product)
Power consumption
Max As per microcomm specification
Humidity
90% RH max at 40°C (no condensing)
Ambient temperature
-10 + 60 °C
Electrical rating
Fusing: no fuse
Relay output: free contact, Max 115/230 Vac, 0,8 A ,cosφ=0,6 (need high voltage track distances)
Multipurpose GENERIC input: 24 V DC, 5 mA
External Sensor input: 10 K B3946 NTC
0-10 Volts Input : same as DSP49G2037
Room Thermostat input : 24 V DC, 5 mA or OT+
Remote reset Input : 230 Vac, 1 mA
Modbus interface : standard RS485 non insulated (2 wires + Gnd)
RTC battery back-up: 8Hrs back-up time at nominal conditions
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 9 / 45
Communication capabilities:
Standard microcomm interface Vs main board
Standard microcomm interface for external PC connection
OT+ version 3.0
Product life
250.000 cycles at rated loads
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 10 / 45
7. PRODUCT FUNCTIONALITY SPECIFICATION
7.1. USER INTERFACE User interface can be fully defined via goHapi tool running on internet using firefox browser (https://go-hapi.honeywell.com ). For this reason product specification does not define any specific user interface functionality. Example of standard proposed user interface can be found in Appendix A
7.2. BACKLIGHT Lcd BACKLIGHT led are switched on any time a button is pressed and are switched off after 300 seconds last button has been pressed. In case of error backlight is permanently on.
7.3. PUSH-BUTTON USAGE Buttons are defined with a matrix approach of 3 rows/4 column. Specific button functionality can be determined via goHapi tool where each button is addressed with RxCy (x=1-3; y=1-4) selection. In set-up menu some specific functions like Enter, up-down, … can be assigned to some specific button The first column (C1 left column) is typically called a contextual button column since function of such a buttons is dynamically indicated on the LCD screen. Below is an example of possible keypad using all 12 buttons.
8. High voltage Output Dot matrix display has 2 relay independent closing contact that can be used as high voltage output. By default they are used for:
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 11 / 45
- Rly 1: Close when esys/maxsys CH pump is running - Rly 2: CH Heat demand ON indicator
9. Low Voltage input (AUX 0) Dot matrix display has 1 low voltage input contact that can be used as general purpose input. By default it is used as CH demand signal
10. High Voltage Input Via goHapi is possible to select the usage of high voltage input between 2 different functionalities:
- CH demand - Lockout reset
11. 0-10Vdc input Dot matrix uses the analog value present on 0-10V input to generate a CH power demand proportional to this value. An analog value below 2Vdc force a CH off status (removal of heat demand) while any other value from 2 till 10Vdc generate a CH request with power demand linearly proportional to analog value. Activation of CH heat demand via 0-10V is done via user interface.
12. Microcomm Bus Master Communication
The MMI is a master in the esys/maxsys communication. This is the highest priority communication interface for the MMI. The supported ID’s (application layer) are listed in Appendix B. There will be three levels of communication priority for this. The Highest-level is communication loop that is continuously communicated. A Normal-level message is communicated once every Highest-level communication loop was finished. A Low-level message is communicated once every Normal-level communication loop was finished. A special level will also be included. Messages at this level will only be communicated once at startup.
The MMI uses the Microprocessor’s hardware USART at a speed of 19200 Baud, 8-bit Data, 1 start-bit en 1 stop-bit for Transmit (Tx) and Receive (Rx) of serial data. Further specification for the protocol is done in the document “External Communication Class 1..6” [ERE2038.doc
13. Microcomm Bus Slave Communication
The goHapi dot matrix provide a slave microcomm communication for external control . This will normally be used to connect master devices like a Personal Computer through a PC CVBC Communication cable to the MMI. It is also used to access the connected Esys/Maxsys family product, therefore functioning in such a case as a “Bridge”. The supported ID’s (application layer) are listed in appendix B. Microcomm communication is 19.2 baud UART , 8-bit Data, 1 start-bit, 1 stop-bit for Receive (Rx) and Transmit (Tx) of serial data. Further specification for the protocol is done in the document “External Communication Class 1..6” [ERE2038.doc.
14. OpenTherm Communication Requirements
The MMI is a slave in the OpenTherm Communication. This is used to connect OpenTherm Master devices for Remote control of the MMI and connected esys/maxsys family products. The supported ID’s (application layer) are listed in Appendix C.
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 12 / 45
15. Modbus interface Details of Modbus functionality and content of ID are contained in appendix D of this document
16. Outside Temperature Control
The MMI will convert the Analog/Digital conversion result to the corresponding temperature.
Via specific goHapi selection OTC algorithm can be choosen between 2 possible options:
16.1.1. 4 POINTS OTC CURVE Via user interface Is possible to set the following values that determine the OTC curve and therefore the actual boiler setpoint during CH request:
A - Otc_offset: this is the minimum CH setpoint value
B - Otc setpoint maximum: this is the maximum CH setpoint value
C - Otc weather cold: this is the external temperature value at which the maximum CH setpoint will be used
D - Otc weather warm: this is the external temperature value at which the mminimum CH setpoint will be used
E - OTC warm weather shutdown: this is the external temperature value at which the CH heat demand will be removed/ignoired
Combining the above points CH actual setpoint will follow a line as indicated in the following figure:
16.1.2. HONEYWELL SIMPLIFIED OTC CURVE This is done trough a special lookup table between the limits of –30 to + 70 degrees Celsius. This is the standard used 8-bit lookup table.
The MMI calculate and use a Control Temperature Setpoint for Central Heating when an Outside Temperature Sensor is connected, The value of Control Setpoint is limited to the value of CH Setpoint set by User.
For calculating this Control Temperature Setpoint, the following calculation is done:
Control Temp. Setpoint = OTC Offset + C1 *(20 – Outside Temperature) / 4
Where:
C1 = derived from the OTC Curve number:
If OTC Curve number = 1..7 then C1 = OTC Curve number
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 13 / 45
If OTC Curve number = 8, then C1 = 9
If OTC Curve number = 9, then C1 = 12
If OTC Curve number = 10, then C1 = 18
The Control Temp. Setpoint is limited by Maximum value of CH user setpoint . The Esys CH User Setpoint is aligned with the maximum of the DSP temperature range.
For Outside Temperatures above 20 degrees Celsius, Control Temp. Setpoint =10`C.
OTC CURVES
20
30
40
50
60
70
80
90
20 16 12 8 4 0 -4 -8 -12
-16
-20
OUTDOOR TEMPERATURE
WA
TE
R T
EM
PE
RA
TU
RE
. Control Temperature Setpoint (Water Temperature) in relation to the Outside Temperature
17. ECO working mode ECO working mode can be selected via pushbutton. Whenever ECO mode is selected the following functions are implemented:
- CH mode. Boiler continue to run as per actual settings but CH temperature setpoint is reduced by a value equal to ECO setpoint. In case of OTC usage or modulating setpoint received from external the actual setpoint is reduced by the value equal to ECO setpoint. In case resulting setpoint is lower than minimum, actual setpoint will be limited to minimum
- DHW mode. Same as per CH but with DHW ECO setpoint acting on DHW value ECO mode is exited automatically via time switcher or if forced manually via pushbutton, after push of same ECO button. Eco mode is indicated by ECO icon on screen when manually activated or with a text ECO below Tap/Radiator when activated by scheduler otherwise defined via goHapi
18. HOLIDAY working mode Holiday mode is entered pressing holiday button on user interface. When button is pressed a request to indicate holiday start date and holiday end date is shown . When start date is reached (00:00 of that day) boiler adjust current CH and DHW setpoint accordly to Holiday setpoint value set in menus. When end date day expire
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 14 / 45
(24:00) boiler return to normal operation. This has to be consider to anticipate return of holiday in case home heating is required to start in advance.
19. goHAPI User interface data download Dot matrix display support goHapi functionality, used to download custom made user interface into product flash. Download is done via any serial communication package (ie hyperterminal) and standard cable connected to slave microcomm interface. To enable download press and hold for approx. 3 seconds simultaneously buttons C1-R2 (Column-Row) and C3-R2. This causes reset of the display and entering the “goHapi mode” - just at this moment buttons can be released. LCD is cleared and backlight starts blinking; at this point is possible to transfer .BIN file containing user interface description and setting. At the end of transfer display is reset and program start execute normally. Any blackout interrupts this mode leaving goHAPI part of flash data corrupted. After such unsuccessfull loading of data, the uplload mode has to be repeated with correct data file. If an inappropriate .BIN file is loaded into device, error E94 is show at the screen with comment: "HAPI mismatch, can't continue". Device is then resetted after 30 seconds waiting for correct file to be uploaded. Serial connection setting must be as follow:
- 19200 bps - Data bit 8 - Parity none - Stop bit 1 - Flow control None - Protocol XModem
20. ERROR SCREENS DESCRIPTION Error screen is splitted in different parts:
- Lower part: contain description as per following table column “description” - Upper part: contain error code number as per following table column “hard/soft lockout code”
Hard
Lockout Code
Description
E1 Failed Ignition
E2 False Flame
E3 High Boiler Temperature
E4 Air flow/damper
E5 Blower Speed
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 15 / 45
E6 Air flow/damper
E8 Flame Circuit Error
E9 Gas Valve Circuit Error
E15 Sensor Drift
E16 Supply Sensor Stuck
E17 Return Sensor Stuck
E18 Sensor Failure
E21 Internal Control Fault
E30 Supply Sensor Shorted
E31 Supply Sensor Open
E43 Return Sensor Shorted
E44 Return Sensor Open
E80 Return > Supply
E87 External Limit Open
Soft Lockout Code
Description
E7 High Flue Temperature
E12 Internal Control Fault
E13 Reset Limit Reached
E25 Internal Control Fault
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 16 / 45
E32 DHW Sensor Shorted
E33 DHW Sensor Open
E34 Low Voltage
E37 Low Water
E45 Flue Sensor Shorted
E46 Flue Sensor Open
E47 Water Pressure Error
E76 External Limit Open
E77 Siphon error
E81 Sensor Drift
E82
E83
E84
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 17 / 45
E87 Overtemp lockout
E89 Incorrect Setting
E90 Firmware Mismatch
E91
E92
E93 Outdoor Sensor Shorted
E94 Internal Display Fault
E95 Supply Sensor Error
E96 Outdoor Sensor Open
E97
E98
E99 Controller Bus Error
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 18 / 45
21. APPENDIX -A-
USER INTERFACE DESCRIPTION OF DEFAULT HONEYWELL DSP49G2128 IMPLEMENTATION
21.1. MAIN SCREENS Following pictures show the icons displayed on main screen. First 3 screens are related to normal working condition while forth is the error screen main display where date & time indication is replaced by main error number and description.
n icon Note
1 Logo On different main screens (here Honeywell logo shown but can be custome
2 snowflake Shown when winter mode (CH)
3 sun Shown when Summer mode (DHW only)
4 outside_temp Shown When OTC detected
5 house_outline Always shown
6 radiator Shown when CH enabled or striped when disabled
7 tap Shown when DHW enabled or striped when disabled
10 ON radiator Ch allowed
11 ON(tap) DHW allowed
12 ECO (radiator) CH allowed in ECO mode
13 ECO (tap) DHW allowed in ECO mode
14 OFF (radiator) CH off by timer
15 OFF (tap) DHW off by timer
16 pump_circ Pump is running or CH demand active
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 19 / 45
18 pump_sanit DHW Pump is running or DHW demand active
19 flame1 Size of flame icon indicate flame presence & power level (0‐25%)
20 flame2 Size of flame icon indicate flame presence & power level (26‐50%)
21 flame3 Size of flame icon indicate flame presence & power level (51‐75%)
22 flame4 Size of flame icon indicate flame presence & power level (76‐100%)
23 Flow temperature Indicate supply Temperature
24 Water pressure Water pressure indicator and value
25 eco_mode Shown when ECO mode activated manually
27 holiday Shown when holiday mode activated
28 warning Shown when error present
29 i_button When indicated button is pressed additional error info are displayed
30 line Separator line always shown
21.2. PUSH BUTTON Description of standard default button implementation:
R1-C1: follow corresponding LCD meaning (contextual button) R2-C1: follow corresponding LCD meaning (contextual button) R3-C1: follow corresponding LCD meaning (contextual button) R1-C2: up button used to scroll through menus R3-C2: down button used to scroll through menus R2-C2: OK button, used to confirm highlighted selection or as confirmation of what is required by LCD R1-C3: Escape button. Used to return to main screen (always active) R1-C4: On-Off button. Used to put boiler in Off mode (Only main Logo and date/time displayed (always active) R2-C3: Menu button used to enable access to both User and Installer menu (always active) R2-C4: Summer-Winter button. Used to enable-Disable CH and DHW (active in main screens) R3-C3: Holiday button. Used to enable Holiday function (active in main screens)
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 20 / 45
R3-C4: Eco button. Used to enable Eco function (active in main screens)
21.3. SCREENS DESCRIPTION DSP user interface is build using different screen type and structures. Main screen structures are defined below:
21.3.1. MAIN MENU SCREEN
n icon x
1 user User Menu Indicator
2 tech Technician menu indicator
3 user‐access‐button When associated button pressed User menu is accessed
4 tech‐access‐locked‐button When associated button is pressed Technician menu is accessed
5 BACK‐button General indication of Back function button (valid through all screens)
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 21 / 45
21.3.2. TECHNICIAN MENU ACCESS CODE When technician menu has to be accessed an access code is required. Access code is entered in following screen; value is 231
+- button are used to increment/decrement selected value Up-down arrow are used to select character to be modified Ok butotn will confirm value
21.3.3. TEXT MENU SCREEN Text menu screen is used to propose a list of possible selection . Via up/down arrow is possible to move through text menu, OK will confirm selection. Active selection is highlighted using reversed text approach. (only 1 line highlighted at the time) Back button will return to previous screen When menu is used for direct actions (ie enable-disable, language selection, …) on entry actual selection is highlighted. With up-down arrow is possible to move through selection, entering OK will activate highlighted selection and return to previous screen. Main User/Technician menu list is written in capital letter while all other text are in normal letter. Hereunder an example of text menu screen. A facing down arrow indicate text line did not fit into one screen and there are additional lines below A right arrow at the end of a line means hitting enter on that line there are additional info (valid for status display menu list)
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 22 / 45
21.3.4. PARAMETER/VALUE SET MENU Parameter or value set menu are typically used to change value of a parameter, a variable, … For single value parameters screen structure is as indicated below. Title of the screen will point to parameter under modification, with contextual pushbutton parameter is changed, Ok button will confirm change while back button will return to previous screen leaving parameter unchanged. On entry display shows actual parameter value
LABEL NUMBER
MEANING
Parameter name: Screen Title Lower case 1 Icon shows effect of push button R1-C1 to parameter 2 Icon shows effect of push button R2-C1 to parameter 3 Back button 4 Parameter value area 5 Up-down indicator/button, used to move across parameters when there is more than 1 6 OK button to confirm parameter set
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 23 / 45
21.3.5. CLOCK SCREEN SETTING Following picture shows an example of clock setting screen; real one for SW optimization has AM/PM indicator in the time space and time indicator uses a smaller font (16 Bold) . +- button are used to change the selected value , OK to confirm actual selection and move to next field (ie from Hrs to minutes). When 24 Hr or 60 Minutes are reached count is restarted from the beginning. Hour format (12 or 24 Hours is defined into setting menu) When 12 Hours format AM or PM are highlighted indicated period to whom hour is referred
21.3.6. DATE SCREEN SETTING Following picture shows date setting screen . +- button are used to change the selected value , OK to confirm actual selection and move to next field (ie from day to month to year)
21.3.7. EXTENAL TEMPERATURE RELATED SCREEN SETTINGS Below the list of screens related to variable adjustments linked to external temperature. Adjustment is done via indicated +- buttons and it is confirmed via OK button
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 24 / 45
Outside temperature for max setpoint is the external temperature at which the CH setpoint will be put at maximum (see OTC description chapter, point C). Outside temperature for min setpoint is the external temperature at which the CH setpoint will be put at minimum (see OTC description chapter, point D) Outside temperature for switch off is the external temperature at which the CH demand is switched OFF (see 17.1.1.4, point E).
21.3.8. DOMESTIC HOT WATER SETTINGS Below the screens related to DHW setpoint adjustment Adjustment is done via indicated +- buttons and it is confirmed via OK button
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 25 / 45
Boiler temp for heating cylinder is the temperature at which primary water is heated-up during a DHW call when boiler does not have DHW temperature sensor Domestic temperature is the DHW setpoint used in case boiler has specific DHW sensor
21.3.9. PUMP POST CIRCULATION Typically at the end of an heat demand pump is kept running for a determined time. This time is settable via the pump post circulation screen. This screen shows how post circulation time is set ; the pump affected by this setting depends on the menu the setting has been activated (CH or DHW setting) Adjustment is done via indicated +- buttons and it is confirmed via OK button
21.3.10. MAINTENANCE SETTINGS Below screens shows service company info setting and expected maintenance date. These 2 fields are supposed to be inserted by service person Data entry is done in the same way as per the others screens: +- button to change value, up-down arrow to select value to be changed, OK to save setting
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 26 / 45
21.3.11. DEFAULT FACTORY SETTING Depending from where this screen is invoked, it will restore user of installer default factory settings. OK will start restore of data while any other key will go back to previous screen. to confirm. From user menu at the end of restore screen will go back to main while from technician menu will go back one screen
21.3.12. HOLIDAY PERIOD SETTING To program and eneable holiday functionality (CH and DHW with limited setpoint determined by settings done in CH and DHW menus) suitcase (holiday) button must be pressed. When pressed below screens asking for holiday start/end will be displayed. When holiday enabled boiler will work in the selected period with holiday setpoints set..
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 27 / 45
21.3.13. ERROR MESSAGE SCREEN Error message is entered from main screen when an error is present and Information button is pressed. Strucutre of screen is as indicated below:
- error message contain the text indicated in chapter ERROR SCREEN DESCRIPTION under description column . Lower line of error message text area contain error number. Optionally is possible to ad dadditional text below ethe frame to provide info to user
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 28 / 45
21.3.14. SCHEDULER SETTING SCREEN Scheduler allow possibility to define working condition ranges during the day choosing between 3 status: ON, ECO, Off. Implementation allows to set 6 different ranges/status; the “empty” time between ranges is considered to be OFF, allowing therefore to extend the real number of ranges. Via up-down key Is possible to move between ranges while +-key will increase/decries the time of specific range (when in time area) or toggle working condition when in third column . Working condition toggling allow to select On mode: boiler is enabled; ECO mode: boiler will use reduced setpoint. To facilitate changes two additional possibilities are added to working mode selection: the first one is OFF mode that cancel also the time, in case user want to delete completely a scheduler line; second is off mode to disable the boiler but maintaining the indication of range selection (this to facilitate ie a temporary disable of boiler maintaining the scheduler set). Scheduler functionality is acting independently on CH and DHW, means each of them has is own scheduler. The status of scheduler is shown on main screen with then indication ON- ECO-OFF under tap/radiator. Scheduler set can be done for each day, for group of week days, for week-end days or for the entire week. When group of day is programmed and later a single day of that group is changed, opening the group of day screen will be cleared meaning that days are not anymore equals
21.3.15. MENU STRUCTURE OVERVIEW Following is the content of User menu and submenus with associated actions/functions.
USER MENU SUBMENU 1 SUBMENU 2 NOTES
1. HEATING Heating user settings
1. CH temperature/OTC set
Set the CH temperatures and OTC curve parameters
1 CH temperature set Adjust setpoint of CH circuit
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 29 / 45
2 Outside temperature for CH off
Set the external temperature at which Heat demand is removed. If Off heat demand is never removed by controller (only by ext RT). If OTC is not present a screen asking to hit OK will be sown
2. Eco setpoint reduction Set the temperature that will be subtracted from actual setpoint when ECO mode is activated
3 Scheduler set Invoke scheduler menu
1 Enable/disable on board scheduler
Based on selection is possible to enable/disable CH on board scheduler (in this case scheduler could be controlled externally)
2 Scheduler set Used to program on board scheduler
2. DOMESTIC HOT WATER
Domestic hot water user settings
1. DHW setpoint Set the DHW temperature (in case of DHW with sensor this is the actual DHW temperature, in case of DHW with Switch this is the base boiler Flow temperature )
2 Eco setpoint reduction
Set the temperature that will be subtracted from actual setpoint when ECO mode is activated
3 Scheduler set Invoke scheduler menu
1 Enable/disable on board scheduler
Based on selection is possible to enable/disable DHW on board scheduler (in this case scheduler could be controlled externally)
2 Scheduler set Used to program on board scheduler
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 30 / 45
3. HOLIDAY 1 CH holiday setpoint Set CH temperature used when Holiday mode active
2 DHW holiday setpoint Set DHW temperature used during holiday mode
4 MAINTENANCE Set maintenance related info
1 Service information Used to display service company phone number or entered info
2 Service due date Shows next service due date When date expire a MSG is shown on lower part of main screen asking for service
5 SETTINGS Boiler option settings
1 Select language English Italian
Allow selection of different languages (actual language is highlighted on enter)
2 Select units Fahrenheit Celsius
Allow selection of different unit (actual unit set is highlighted on enter) Selecting Fahrenheit will force to show all units (so not only temperatures) in Imperial, selecting Celsius in European style. If Fahrenheit selected degrees value will show only even numbers (due to conversion sometimes 2 button actions are required to change value).
3Set date Allow RTC date setting.
4 Set time Allow RTC time set. When selected a screen asking for time format 24/12 Hours is opened. When selected appropriate format screens jump to time entering screen
5 Restore factory data Pressing OK all the user settings will be restored to the original factory default settings
6 DIAGNOSTICS Will display boiler usage information and errors
1 Boiler Information Display the following information: CH request
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 31 / 45
DHW demand Firing rate (in %) * Flame ionization current (uA) * Boiler setpoint * Boiler Supply temperature * Return temperature * Flue temperature * Outdoor temperature * DHW storage temperature * Boiler fan speed (rpm*50) CH ignition (number) CH runtime (in Hours) DHW ignitions (number) DHW Runtime (in Hours) System Pressure (water pressure in bar/psi) When a line has an * at the end means that hitting Ok when line is highlighted will open a graph that shows the latest 120 variable values stored every 12 minutes (24 hours history). Sample will not be averaged over the 12 minutes period
2 Error History Show a list of recent errors. Hitting OK on highlighted error will open a new screens that contain details on boiler status when error occurred
TECHNICIAN MENU SUBMENU 1 SUBMENU 2 NOTES
1 ADVANCED CH SETTINGS
Heating installer advanced settings
1 CH power set 1. Maximum power
Set % of boiler maximum power in CH mode
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 32 / 45
2. Minimum power
Set % of boiler minimum power in CH mode
2 CH temperatures Set (selecting OK) and show boiler temperatures
1. Absolute max temperature
Set CH absolute max temperature (CH temperature boiler setting will never exceed)
2. CH maximum setpoint
Determine higher boundary of CH setpoint
3. CH minimum setpoint
Determine lower boundary of CH setpoint
3. CH setpoint histeresys
Set CH setpoint histeresys (temperature above setpoint at which boiler will be switched off)
3. OTC Parameters Set the OTC parameters
1. Outside temp for max CH
Define external temperature at which OTC will set maximum CH setpoint
2. Outside temp for min CH
Define external temperature at which OTC will set minimum CH setpoint
3. Outside temp for CH OFF
Define external temperature at which OTC will disable central heating (even if RT request is on)
4.OTC setpoint table Show in a table the link between external temperature and actual setpoint determined by OTC parameter selection
4. CH pump settings Set pump usage related parameters
1. Post pump time Set the CH pump overrun time
5. CH anticycling timer Set the anticycling timer (minimum time between boiler goes off till next ignition)
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 33 / 45
6. CH request type Allow selection of different CH requests based on installation type:
- Only OTC - Room Tstat - 0-10V Signal
2 ADVANCED DHW SETTINGS
Domestic hot water advanced settings
1 DHW power 1. Maximum power Set % of boiler maximum power in DHW mode
2. Minimum power Set % of boiler minimum power in DHW mode
2 DHW Temperatures Set (selecting OK) and show DHW temperatures
1. Storage temperature setpoint
Set Flow temperature during DHW mode when DHW done via thermostat (Switch)
2. Boiler temperature setpoint
Set DHW temperature setpoint when DHW done with temperature sensor
3. DHW setpoint histeresys
Set DHW setpoint histeresys (temperature above setpoint at which boiler will be switched off)
3 DHW pump settings Define pump usage in DHW mode
1. DHW post pump time
Set DHW pump overrun time
4 DHW priority Define DHW priority over CH
1. DHW priority status
Enable/disable DHW priority over CH
2. DHW priority timeout
Define after how much time DHW priority is ended (CH can be served if present for the same amount of time)
5 DHW request type Define DHW request type: - Switch - Sensor
Switch DHW start when DHW flow close
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 34 / 45
Sensor DHW start based on required vs actual DHW temperature
3 SYSTEM SETTINGS
Boiler and system settings
1 Boiler parameters
1 Ignition power Set power % used when igniting burner
2 Delay siphon check
Delay time to validate a siphon error
3 Antilegionella Enable/disable antilegionella function
4 Modbus address Allow assignement of modbus address. In modbus address screen hitting OK address is saved and screen is moved to Modbus baudrate screen. Here is possible to select Modbus baudrate. Hitting OK baudrate is saved and screen is moved to Modbus frame screen wher ei spossible to select modbus frame characteristics. Hitting ok will go back to boiler parameter screen. In any of the above mentioned screen hitting back will return to boiler parameter screen
2 User interface settings
1 Select language English Italian Allow selection of different languages (actual language is highlighted on enter)
2 Select units Fahrenheit Celsius Allow selection of different unit (actual unit set is highlighted on enter) Selecting Fahrenheit will force to show all units (so not only temperatures) in
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 35 / 45
Imperial, selecting Celsius in European style. If Fahrenheit selected degrees value will show only even numbers (due to conversion sometimes 2 button actions are required to change value).
3 Set date Set system date
4 Set time Set system time
3 Service settings 1 Service information
Used to insert service company phone number (selection done as per technician password enter)
2 Service due date Next service due date (input done as per date entering)
4 DIAGNOSTICS
1 Boiler Information Display the following information: CH request DHW demand Firing rate (in %) Flame ionization current (uA) Boiler setpoint Boiler Supply temperature Return temperature Flue temperature Outdoor temperature DHW storage temperature Boiler fan speed (rpm*50) CH ignition (number, stored every 20 counts so it will be 20-40-…) CH runtime (in Hours stored every hour) DHW ignitions (number , stored every 20 counts so it will be 20-40-…) DHW Runtime (in Hours stored every hour) System Pressure (water pressure in bar/psi) When a line has an * at the end means that hitting Ok
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 36 / 45
when line is highlighted will open a graph that shows the latest 120 variable values stored every 12 minutes (24 hours history). Sample will not be averaged over the 12 minutes period
2 Lockout history Show a list of recent errors. Hitting OK on highlighted error will open a new screens that contain details on boiler status when error occurred. List maximum length is 8
3 Manual test Used to force a CH test request that will ignite the boiler (if no error conditions) at the indicated power. Manual test mode is enabled/disabled via OK button or ended when technician password timeout (default 15 minutes) expire. Exiting the manual test screen while test is in progress allow technician to navigate through other menus to check boiler status and functionality
5 USER SETTINGS Access to user settings from advanced menu. Will allow user setting of heating, domestic hot water and holiday
1 Heating Enter user menu Heating area
2 Domestic hot water Enter user menu DHW area
3 Holiday Enter user menu holiday area
6 RESTORE FACTORY SETTINGS
Pressing OK all the advanced settings will be restored to the original factory default settings
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 37 / 45
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 38 / 45
22. APPENDIX -B- Supported Microcomm Message ID’s with functional description
To be added
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 39 / 45
Supported External microcomm Message ID’s To be added
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 40 / 45
23. APPENDIX -C- IMPLEMENTED OT+ ID’S Hereunder the list of implemented OT+ ID’s Class ID R/W
* Description
1 0 R Status 1 W Control setpoint (limited by CH setpoint) 5 R Fault flags/ faultcode
2 2 W Master configuration (dummy write) 3 R Slave configuration 124 W OpenTherm version master (dummy write) 125 R OpenTherm version slave 126 W Master product version (dummy write)
3 4 W Lockout reset 4 17 R Relative modulation level
18 R CH water pressure (not for WP switch configured) 25 R CH water temperature 26 R DHW water temperature (not for BT switch configured) 27 R Outside temperature 28 R CH return water temperature
5 6 R Remote parameters transfer-enable read/write flags 48 R DHW setpoint bounds (not for BT switch configured) 49 R CH setpoint bounds 56 R/W DHW setpoint (not for BT switch configured) 57 R/W Max CH setpoint
6 10 R Number of TSP’s 11 R/W TSP
7 12 R Size of fault history buffer 13 R History fault
8 14 W Maximum relative modulation level
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 41 / 45
24. APPENDIX –D- MODBUS IMPLEMENTATION This appendix describes Modbus registers for DSP49G2128.
24.1. Modbus configuration The Modbus communication line is set to 38400b/s by default but via technician menu is possible to change it to any value between 1200 and 38400, Default modbus communication frame is 8bit, 1stop, parity none (8N1) but via technician menu can be change to 8bit, 2 stop, parity none (8N2) or 8 bit, even parity, 1 stop (8E1) Default modbus address is 1.
24.2. Supported commands The Dot-Matrix display has implemented basic Modbus commands.
0x03 Read Holding Registers 0x04 Read Input Registers 0x06 Write Single Register 0x10 Write Multiple Registers 0x11 Report Slave ID
24.3. Modbus register map The next table shows the register map for Dot-Matrix display.
ID R/W Accessible by command
Name Format Range Notes
0 R/- 0x04 (Input registers)
MB: Esys flags
Flag8 0-255 Bit: description 0: CH mode 1: DHW mode 2: Test mode 3: flame
LB: Esys flags
Flag8 0-255
Bit: description 0: fault 1: valve1 2: valve2 3: aps 4: fan 5: pump
1 R/- 0x04 (Input registers)
MB: Error flags
Flag8 0-255 Bit: description 1: lockout
LB: Error code
U8 0-99 OEM specific error number.
2 R/- 0x04 (Input MB:
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 42 / 45
ID R/W Accessible by command
Name Format Range Notes
registers) LB: Error source
U8 0-F 0 : Esys burner controller in cascade F : Dot-Matrix display
3 R/- 0x04 (Input registers)
MB:
LB: Comfort state
U8 0-255 Comfort state Esys burner states – correct values depends on OS number V2042 states: 0: Stanby 1: Test mode init 2: Test mode run 5: DHW mode init 6: DHW mode run 7: DHW mode cool 9: CH init 10: CH run 11: CH cool
256 -/W 0x06 (Write single register)
MB: 0xAA U8 Dot-Matrix display provides a reset command on device which is filled in Error source. The reseting is done when previous command return non zero value.
LB: 0x55 U8
512 R/W 0x03 (Read Holding
Registers) 0x06 (Write
single register) 0x10 (Write
multiple registers)
MB: Heat demand flags
U8 0-255 Bit: description 0: DHW enable
LB: Heat demand
U8 0-255 Reading: 0 = No heat demand detected 0x55 = Heat demand present 0xFF = Test mode demand present Write: 0 = no heat demand 0x55 = CH demand 0xFF = Test demand Value is valid for 30s from the last successful write. When this register is written, the modbus control logic is activated and registers 513, 514 are used for control.
513 R/W 0x03 (Read Holding
Registers) 0x06 (Write
single register) 0x10 (Write
multiple registers)
MB:
LB: Max percentage
U8 0-100 0-100% maximal percentage power Used for Modbus control
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 43 / 45
ID R/W Accessible by command
Name Format Range Notes
514 R/W 0x03 (Read Holding
Registers) 0x06 (Write
single register) 0x10 (Write
multiple registers)
MB:
LB: Control Set point
U8 Limited to OTC offset,
CH set point and Abs max set point
Control set point in degrees of Celsia. This value is used as a target temperature for supply sensor, when Modbus heat demand is generated.
768 R/- 0x04 (Input registers)
CH supply temperature
S16 Value *0,1 [ºC] example : 278 = 27,8ºC 0x8000 invalid value
769 R/- 0x04 (Input registers)
MB:
LB: CH return
temperature
S8 Value in degrees of Celsia
770 R/- 0x04 (Input registers)
MB:
LB: DHW temperature
S8 Value in degrees of Celsia
771 R/- 0x04 (Input registers)
MB: Sensor : Value in degrees of Celsia 0x8000 – invalid value Switch: ad value > 250 0x7FFF – Flue sensor open ad value < 5 0x0000 – Flue sensor closed If switch input is outside limits 0x8000 – invalid value
LB: Flue temperature
S8
772 R/- 0x04 (Input registers)
MB:
LB: OTC temperature
S8 Outside temperature sensor Value in degrees of Celsia 0x8000 – invalid value
773 R/- 0x04 (Input registers)
MB:
LB: Water pressure [bar]
U8 value from water pressure sensor/switch value * 0.1 [bar]
774 R/- 0x04 (Input MB:
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 44 / 45
ID R/W Accessible by command
Name Format Range Notes
registers) LB: Flame current
U8 Flame current in uA
775 R/- 0x04 (Input registers)
MB:
LB: Modulation
U8 Actual modulation level
776 R/- 0x04 (Input registers)
MB:
LB: Calculated set point
U8 Actual set point for supply sensor. Value in degrees of Celsia. 0x8000 invalid value in case no set point is set.
1280 R/W 0x03 (Read Holding
Registers) 0x06 (Write
single register) 0x10 (Write
multiple registers)
MB:
LB: CH set point max
U8 User maximal CH set point.
MB:
1281 R/W 0x03 (Read Holding
Registers) 0x06 (Write
single register) 0x10 (Write
multiple registers)
LB: DHW set point
U8 DHW user set point.
61440 R/W 0x03 (Read Holding
Registers) 0x06 (Write
single register) 0x10 (Write
multiple registers)
MB:
LB: Modbus address
U8 1-247 Modbus device address.
24.4. 0x11 Report Slave ID This command returns string with Dot-Matrix display identification. The identification contains information about product name and software version. Example: “DSP2128 v.00.04” – DSP2128 – product name – v.00.04 – version number
Technical specification Honeywell Combustion Controls srl
Title: DSP49G2128– Dot Matrix MMI for boiler applications
Doc: DSP49G2128E20
Description Ope. App. Date Rev.First Issue GiaCri 0090013 120910 A Added modbus settings GiaCri 0097693 31-Jan-2013 B
Page. 45 / 45
25. APPENDIX E: EEPROM DEFAULT CONFIGURATION This appendix contain eeprom parameters description and their default value and ranges
parameter default min max unit/meaning otc_weather_warm 20 15 25 °C otc_weather_cold -15 -34 10 °C storage_setpoint 60 0 255 °C dhw_setpoint 60 10 65 °C warm_weather_temperature 6 6 25 6=OFF, otherwise °C enable 3 0 3 CH on, DHW on suspend 0 0 255 SUSPEND off language 1 1 3 enum, 1=ENGLISH relay0_cfg 0x0014 0x0000 0xFFFF special relay1_cfg 0x0010 0x0000 0xFFFF special storage_setpoint_holiday 59 0 255 °C ch_setpoint_holiday 62 0 255 °C dhw_setpoint_holiday 45 0 255 °C ch_setpoint_delta_eco 9 0 255 dif °C dhw_setpoint_delta_eco 11 0 255 dif °C scheduler_ch_enable 1 0 255 on scheduler_dhw_enable 1 0 255 on Modbus device.address 1 0 247
Modbus device.baudrate 5 0 55=MODBUS_BAUDRATE_38400
holiday start 126230400
0 epoch epoch Fri, 01 Jan 2010 00:00:00 GMT
holiday end 126230400
0 epoch epoch Fri, 01 Jan 2010 00:00:00 GMT
service due 315576000
0 epoch epoch Wed, 01 Jan 2070 00:00:00 GMT