TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions 1 Applications The TEC2647Z-2 Zone Controller is a BACnet® Master-Slave/Token-Passing (MS/TP) device that operates with a Johnson Controls® TEC2664Z-2 Rooftop Controller to provide efficient space temperature control in constant volume zoning systems. This technologically advanced zone controller provides proportional 0 to 10 VDC control of pressure dependent Variable Air Volume (VAV) equipment with or without local reheat. The TEC2647Z-2 and TEC2664Z-2 controller combination can operate as a stand-alone zoning system, or it can operate with a Building Automation System (BAS) that enables remote monitoring and programmability in networked zoning systems. The TEC2647Z-2 Zone Controller features an intuitive user interface with backlit display that makes setup and operation quick and easy. The zone controller also employs a unique, Proportional-Integral (PI) time-proportioning algorithm that virtually eliminates temperature offset associated with traditional, differential-based zone controllers. North American Emissions Compliance United States Canada IMPORTANT: The TEC2647Z-2 Zone Controller is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the zone controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the zone controller. This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense. This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada. TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions Part No. 24-9890-676, Rev. A Issued July 18, 2008 Supersedes June 27, 2008

Transcript of TEC2647Z 2 Install[1]

Page 1: TEC2647Z 2 Install[1]

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning SystemsInstallation Instructions Part No. 24-9890-676, Rev. A

Issued July 18, 2008Supersedes June 27, 2008

ApplicationsThe TEC2647Z-2 Zone Controller is a BACnet® Master-Slave/Token-Passing (MS/TP) device that operates with a Johnson Controls® TEC2664Z-2 Rooftop Controller to provide efficient space temperature control in constant volume zoning systems. This technologically advanced zone controller provides proportional 0 to 10 VDC control of pressure dependent Variable Air Volume (VAV) equipment with or without local reheat.

The TEC2647Z-2 and TEC2664Z-2 controller combination can operate as a stand-alone zoning system, or it can operate with a Building Automation System (BAS) that enables remote monitoring and programmability in networked zoning systems.

The TEC2647Z-2 Zone Controller features an intuitive user interface with backlit display that makes setup and operation quick and easy. The zone controller also employs a unique, Proportional-Integral (PI) time-proportioning algorithm that virtually eliminates temperature offset associated with traditional, differential-based zone controllers.

North American Emissions ComplianceUnited States

Canada

IMPORTANT: The TEC2647Z-2 Zone Controller is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the zone controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the zone controller.

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.

Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked ZoningSystems Installation Instructions

1

Page 2: TEC2647Z 2 Install[1]

Mounting Figure 1 illustrates a typical zoning control system installed on a single MS/TP Bus. This installation consists of multiple TEC2647Z-2 Zone Controllers, each controlling a single zone damper; and a TEC2664Z-2 Rooftop Controller controlling a rooftop unit. The TEC2664Z-2 Rooftop Controller can be wired to an optional supervisory controller.

Location ConsiderationsLocate the TEC2647Z-2 Zone Controller:

• on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature

• away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, or stairwells; and from behind doors

• away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference

Note: Allow for vertical air circulation to the TEC2647Z-2 Zone Controller.

To install the zone controller:

1. Use a Phillips-head screwdriver to remove the security screw on the bottom of the zone controller cover.

2. Pull the bottom edge of the zone controller cover and open the zone controller as illustrated in Figure 2.

Figure 1: Typical Zoning Control System Installed on a Single MS/TP Bus

ZoneDamper

ZoneDamperZone

Damper

ZoneController

ZoneController

RS485 End-of-Line Terminator(MS-BACEOL-0)

MS/TPBus

Rooftop Unit

ReturnSupplyBypassDamper

ReturnAirflow

BypassAirflow

Mixed Airflow

FIG

:typc

l_zn

ng_s

ystm

•• •

RooftopController

ZoneController

Figure 2: Removing the Zone Controller Cover

FIG

:cvr

_rm

vl

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

2

Page 3: TEC2647Z 2 Install[1]

3. Carefully pull the locking tabs on the right side of the zone controller mounting base, and unlock the Printed Circuit Board (PCB). Open the PCB to the left as illustrated in Figure 3.

4. Pull approximately 6 in. (152 mm) of wire from the wall, and insert the wire through the hole in the zone controller mounting base.

5. Align the zone controller mounting base on the wall, and use the base as a template to mark the two mounting hole locations.

Note: Be sure to position the zone controller mounting base so that the arrow on the base points upward to indicate the top of the zone controller.

6. Drill a 3/16 in. (5 mm) hole at each of the two marked locations, and tap nylon anchors (included with the zone controller) flush to the wall surface.

7. Position the zone controller mounting base on the wall, and use the two mounting screws (included with the zone controller) to secure the base to the surface as illustrated in Figure 4.

Note: Be careful not to overtighten the mounting screws.

8. Swing the PCB back to the right and carefully snap it into the locking tabs on the zone controller mounting base.

9. Remove the screw terminal blocks as illustrated in Figure 5.

WiringWhen an existing zone controller is replaced, remove and label the wires to identify the terminal functions. When a TEC2647Z-2 Zone Controller is replaced, simply remove the old screw terminal blocks and reinsert them onto the PCB of the replacement zone controller.

To wire the zone controller:

1. Strip the ends of each wire 1/4 in. (6 mm), and connect them to the appropriate screw terminals as indicated in Table 1 and Figure 6 through Figure 9.

Figure 3: Opening the Zone Controller PCB

FIG

:prn

td_c

rct_

brd

PCBLockingTabs

Figure 4: Securing the Zone Controller Mounting Base to the Wall

FIG

:mnt

ng_b

s

!CAUTION: Risk of Electric Shock.Disconnect power supply before making electrical connections to avoid electric shock.

!CAUTION: Risk of Property Damage.Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.

IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the TEC2647Z-2 Zone Controller.

Figure 5: Removing the Screw Terminal Blocks

FIG

:trm

n l_b

lck s

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

3

Page 4: TEC2647Z 2 Install[1]

Note: For more details on wiring the MS/TP Communications Bus, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).

2. Carefully push any excess wire back into the wall.

3. Reinsert the screw terminal blocks onto the PCB.

4. Attach the MS/TP communication wires to the terminal block.

Note: If multiple wires are inserted into the terminals, be sure to properly twist the wires together prior to inserting them into the terminal connectors.

5. Reattach the zone controller cover to the mounting base (top side first).

6. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the zone controller cover.

IMPORTANT: Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings.

Table 1: Terminal Identification (See Figure 6.)Terminal Number

Terminal Label

Function

4 24 V~ Hot 24 VAC from Transformer

5 24 V~ Com 24 VAC (Common) from Transformer

6 BO5 Aux Aux BO (Auxiliary Output),On/Off Reheat

7 BO5 Aux Aux BO (Auxiliary Output),On/Off Reheat

9 AO2 Analog Reheat

10 AO1 Damper (Zone)

11 Blank N/A

12 BI1 Binary Input 1

13 RS Remote Sensor

14 Scom Sensor Common

15 BI2 Binary Input 2

16 UI3 Temperature Sensor Monitoring via Supervisory Controller

Blank +, –, REF MS/TP Bus

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

4

Page 5: TEC2647Z 2 Install[1]

Figure 6: Wiring the TEC2647Z-2 Zone Controller(See Table 1.)

FIG

:wrn

g

+ REF

SupervisoryController

BI2 UI3BI1 Scom

Remote Inputs

Temperature SensorMonitoring via

Supervisory Controller

Voltage-FreeContact forMonitoring viaSupervisoryController

Voltage-FreeContact• Motion N.O.• Motion N.C.

REF

+

Same 24 VACPower Source for Auxiliary Output

(24 VAC Maximum)

Separate 24 VACPower Source for Auxiliary Output

(24 VAC Maximum)

BO5Aux

BO5Aux

24 VACZone Controller

Power

24 V~Com

24 V~Hot

BO5Aux

BO5Aux

IndependentContacts forOn/Off Reheat

Aux

Aux

24 VACZone Controller

Power

24 V~Com

24 V~Hot

9 10 11 12 13 14 15 16

ScomAO1 UI3BI1 BI2AO2 RS

Eight-Pole Bottom Connector

MS/TPConnector 24 V~

Hot24 V~Com

4 5

Two-PoleRight TopConnector

BO5Aux

BO5Aux

6 7–

Two-PoleLeft TopConnector

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

5

Page 6: TEC2647Z 2 Install[1]

Figure 7: Wiring the TEC2647Z-2 Zone Controller for Proportional 0 to 10 VDC Control

Room TemperatureZone Controller

ProportionalActuator

FIG

:tec2

647z

_prp

rtnl_

cntrl

0 to 10VDC

24 V~ Com24 V~ Hot

AO1

Figure 8: Wiring the TEC2647Z-2 Zone Controller for Proportional 0 to 10 VDC Control andOn/Off Reheat

FIG

:tec2

647z

_prp

rtnl_

cntrl

_ono

ff_rh

t

Room TemperatureZone Controller

On/OffReheat

ProportionalActuator

1C0 to 10VDC

24 V~ Com24 V~ Hot

AO1

BO5-AuxBO5-Aux

AO2

Figure 9: Wiring the TEC2647Z-2 Zone Controller for Proportional 0 to 10 VDC Control and Proportional Reheat

FIG

:tec2

647z

_prp

rtnl_

cntrl

_prp

rtnl_

rht

Room TemperatureZone Controller

ProportionalReheat

ProportionalActuator

0 to 10VDC

AO1AO2

0 to 10VDC

24 V~ Hot24 V~ Com

0 to 10 VDC

24 V~ Hot24 V~ Com

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

6

Page 7: TEC2647Z 2 Install[1]

Table 2: MS/TP Bus Objects When Networked with a Supervisory Controller (Part 1 of 3)Point Name Zone Controller Point

(Type/Address)Range

GUI Damper Position1 AI 1 0 to 100%

Cfg Zone MAC1, 2 AV 1 4 to 127

Cfg RTC MAC1, 3 AV 2 4 to 127

Cfg AO2 OA Lock Spt4 AV 3 -40.0°F/-40.0°C to122.0°F/50.0°C

Cfg BO5 OA Lock Spt4 AV 4 -40.0°F/-40.0°C to122.0°F/50.0°C

Cfg Damper Min Pos4 AV 5 0 to 100%

Cfg Damper Max Pos4 AV 6 0 to 100%

Cfg Damper Max Heat Pos4 AV 7 0 to 100%

Cfg Heating Spt Limit4 AV 8 40.0°F/4.5°C to90.0°F/32.0°C

Cfg Cooling Spt Limit4 AV 9 54.0°/12.0°C to100.0°F/37.5°C

Cfg Deadband4 AV 10 2.0F°/1.0C° to5.0F°/2.5C°

GUI Occupied Heat Spt4 AV 11 40.0°F/4.5°C to90.0°F/32.0°C

GUI Occupied Cool Spt4 AV 12 54.0°/12.0°C to100.0°F/37.5°C

GUI Unoccupied Heat Spt4 AV 13 40.0°F/4.5°C to90.0°F/32.0°C

GUI Unoccupied Cool Spt4 AV 14 54.0°/12.0°C to100.0°F/37.5°C

GUI Standby Heat Spt4 AV 15 40.0°F/4.5°C to90.0°F/32.0°C

GUI Standby Cool Spt4 AV 16 54.0°/12.0°C to100.0°F/37.5°C

GUI AO2 Status1 AV 17 0 to 100%

GUI UI3 Status1 AV 18 -40.0°F/-40.0°C to120.0°F/49.0°C

GUI PI Heat Weighted Demand1 AV 19 0 to 100%

GUI PI Cool Weighted Demand1 AV 20 0 to 100%

GUI Room Temperature5 AV 21 -40.0°F/-40.0°C to120.0°F/49.0°C

GUI Outdoor Temperature4 AV 22 -40.0°F/-40.0°C to150.0°F/65.5°C

Cfg Device Instance1 AV 23 0 to 4,194,303

GUI BI1 Status1, 6 BI 1 Inactive Text = Inactive (Contact Open)Active Text = Active (Contact Closed)

GUI BI2 Status1, 6 BI 2 Inactive Text: InactiveActive Text: Active

Cfg Temperature Scale4 BV 1 Inactive Text = °CActive Text = °F

Cfg Menu Scroll4 BV 2 Inactive Text = No ScrollActive Text = Scroll Active

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

7

Page 8: TEC2647Z 2 Install[1]

Cfg Motion Detector Function4 BV 3 Inactive Text = DisabledActive Text = Enabled

Cfg AO2 RA/DA4 BV 4 Inactive Text = Direct Acting (DA)Active Text = Reverse Acting (RA)

Cfg BO5 Time Base4 BV 5 Inactive Text = 15 MinutesActive Text = 10 Seconds

Cfg BO5 Configuration4 BV 6 Inactive Text = Normally Open (N.O.)Active Text = Normally Closed (N.C.)

GUI BO5 Status1 BV 7 Inactive Text = OffActive Text = On

Sta AO2 Lock Status1 BV 8 Inactive Text = InactiveActive Text = Active

Sta BO5 Lock Status1 BV 9 Inactive Text = InactiveActive Text = Active

GUI Room Temp Override4 BV 10 Inactive Text = NormalActive Text = Override

Sta RTC Smart Recovery7 BV 11 Inactive Text = OffActive Text = On

Cfg Zone Baud1 MV 1 1 = 96002 = 192003 = 384004 = 768005 = Auto

Cfg Reheat Configuration4 MV 2 1 = None2 = Analog Duct Reheat Only3 = On/Off Duct Reheat Only4 = On/Off Peripheral Reheat Only5 = Analog Duct Reheat andOn/Off Peripheral Reheat

Cfg BI1 Configuration4 MV 3 1 = None2 = Motion N.O.3 = Motion N.C.

Cfg PI Heat Weight4 MV 4 1 = 0%2 = 25%3 = 50%4 = 75%5 = 100%

Cfg PI Cool Weight4 MV 5 1 = 0%2 = 25%3 = 50%4 = 75%5 = 100%

Cfg Temporary Occupancy Time1 MV 6 1 = 0 Hours2 = 1 Hour3 = 2 Hours4 = 3 Hours5 = 4 Hours6 = 5 Hours7 = 6 Hours8 = 7 Hours9 = 8 Hours10 = 9 Hours11 = 10 Hours12 = 11 Hours13 = 12 Hours

Table 2: MS/TP Bus Objects When Networked with a Supervisory Controller (Part 2 of 3)Point Name Zone Controller Point

(Type/Address)Range

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

8

Page 9: TEC2647Z 2 Install[1]

Connecting the MS/TP BusTo connect the MS/TP Bus:

1. Set the device address of the TEC2647Z-2 Zone Controller per the engineering drawings; and test for bus voltage, polarity, and isolation prior to wiring the MS/TP Bus. (See the Zone MAC parameter in Table 3 to set the device address for the zone controller.)

Note: Pressing and holding the UP/DOWN arrow keys simultaneously displays the device address that is assigned.

Note: The wiring rules for the MS/TP Bus differ from the wiring rules for the N2 Bus. For more details on wiring the MS/TP Communications Bus, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).

2. Observe the polarity when connecting the bus wires to the zone controller.

3. After the bus wires are connected to the first zone controller, continue in a daisy-chained fashion to the next device on the MS/TP Bus.

Note: The bus wiring must be twisted-pair lines. Do not run the bus wiring in the same conduit as line voltage wiring (30 VAC or above) or other wiring that switches power to highly inductive loads (such as contactors, coils, motors, or generators).

Cfg Network Handle4 MV 7 1 = Default Zone Handle (Supervisory Controller Monitors the Zoning System)2 = Default Minus Occupancy (Allows Each Zone to be Scheduled Independently)3 = Full Release (Supervisory Controller Assumes Complete Control of the Zoning System)

GUI Zone Keypad Lockout4 MV 8 1 = No Lockout2 = Level 13 = Level 24 = Level 3

GUI Occupancy8 MV 9 1 = Released2 = Occupied3 = Unoccupied4 = Temporary Occupied

Sta RTC Zone Sequencing7 MV 10 1 = Cool2 = Heat

GUI Effective Occupancy1 MV 11 1 = Occupied2 = Unoccupied3 = Temporary Occupied4 = Standby

TEC2647Z-72aaa9, 10 Device 72aaa N/A

1. This MS/TP Bus object is readable only.2. Cfg Zone MAC is the unique device address of the zone controller (from 004 to 127) on the MS/TP network.3. Cfg RTC MAC is the unique device address of the rooftop controller (from 004 to 127) on the MS/TP network.4. This MS/TP Bus object is readable and writable.5. This MS/TP Bus object is readable only unless GUI Room Temp Override is set to Active Text = Override, then it is

readable and writable.6. The polarity property of this MS/TP Bus object is readable and writable.7. This MS/TP Bus object is readable only unless Cfg Network Handle is set to 3 = Full Release, then it is readable

and writable. This MS/TP Bus object enables the occupancy setpoint at the occupied time.8. This MS/TP Bus object is readable only unless Cfg Network Handle is set to 2 = Default Minus Occupancy or

3 = Full Release, then it is readable and writable.9. The designation aaa is the address of the device (from 004 to 127) on the MS/TP network.10. Max_Master and Object_Name are writable.

Table 2: MS/TP Bus Objects When Networked with a Supervisory Controller (Part 3 of 3)Point Name Zone Controller Point

(Type/Address)Range

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

9

Page 10: TEC2647Z 2 Install[1]

The MS/TP Bus requires proper termination and biasing at each end of a segment (a segment is a physically continuous length of wire). The zone controller is not equipped with the ability to provide this termination; therefore, it is not recommended that it be located at the physical ends of a bus segment. An end-of-line terminator is required if a supervisory controller is not at the end of the segment. If a supervisory controller is at the end of the segment, then the end-of-line terminator switch on the supervisory controller must be set in the ON position.

Note: See Table 4 for end-of-line terminator ordering information.

For applications with a supervisory controller on the MS/TP Bus, set the supervisory controller to establish the baud rate, and set the rooftop controller for automatic baud rate detection.

For stand-alone applications where a supervisory controller is not present, at least one device on the MS/TP Bus must be set to establish the baud rate. It is recommended that the baud rate be set at only one rooftop controller, and all other devices be set for automatic baud rate detection. Doing so prevents duplicate devices from having mismatched baud rates. After the baud rate is set, recycle the power to the device that was used to set the baud rate.

Do not exceed the maximum number of devices allowed on a Field Bus. Be sure that the wiring terminations are set correctly, and that all communication wiring is daisy-chained with no taps.

A small green light under the zone controller cover (on the left edge, when facing the zone controller) indicates the communications mode when the zone controller is operating. The following blink codes may be seen:

• Short-Short-Long: Indicates that the baud rate is known and communication is active.

• Short-Short: Indicates that the zone controller is scanning for the correct baud rate and there is no communication.

• Off: Indicates that there is no power to the zone controller or the MS/TP wiring polarity is reversed.

• Long: Indicates that the MS/TP communication daughter board is the wrong type for the main board.

MS/TP Device Mapping into a Network Automation Engine (NAE)PreparationBefore mapping a TEC2647Z-2 Zone Controller into an NAE:

1. Decide which point objects within the zone controller need to be mapped. Only map the point objects that need to be viewed on a regular basis, since excessive mapping lowers system performance. Suggested Graphical User Interface (GUI), Configuration (Cfg), and Status (Sta) point objects for mapping are included in Table 2. In addition, monitoring points may be mapped if they are used. Use the Engineering view to examine infrequently used point objects.

Note: We recommend that all zone controller configuration parameters be set as desired prior to mapping the objects into the controller. If any zone controller configuration parameters are altered after the objects are mapped into the controller, we recommend that all objects be remapped. We also recommend caution when mapping configuration parameters, as they should only be mapped if the operator is fully familiar with their use.

2. Verify that a Field Bus is defined in the NAE. BACnet MS/TP devices attach to a Field Bus. Refer to the BACnet® MS/TP Integration with NAE Technical Bulletin (LIT-12011013) for instructions on how to define a Field Bus.

3. Verify that a BACnet Integration is defined for the Field Bus. The zone controller is mapped as a BACnet device under a Field Bus BACnet Integration. Refer to the BACnet Controller Integration with NAE/NCE Technical Bulletin (LIT-1201531) for instructions on how to define a BACnet Integration.

Note: For Metasys® system Release 4.0 or later software, this step is not required.

At this point, the zone controller and the required point objects inside the zone controller can be mapped.

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

10

Page 11: TEC2647Z 2 Install[1]

Adding a Zone ControllerThe zone controller must be added before its points can be mapped. To do this, select the BACnet Integration under the Field Bus (refresh the tree view if required to see a newly added BACnet Integration) and choose Field Device from the Insert menu.

Note: For Metasys system Release 4.0 or later software, select the Field Bus or a folder under it.

Assisted Definition using Auto Discovery is the easiest way to add a new zone controller online; however, this requires that the zone controller to be added is connected and ready to communicate.

Device object names used with BACnet communication must be unique to fully satisfy the requirements of BACnet MS/TP network guidelines. The zone controller automatically selects a device object name for itself using the format TEC2647Z-72aaa, where aaa designates the device address selected (from 004 to 127) on the MS/TP network. If this name needs to be changed by writing a new one into the zone controller device object, that should be done before any point objects are mapped. Be sure that the name of the new zone controller being added to the NAE matches that of the zone controller itself.

Device object IDs used with BACnet communication must be unique to fully satisfy the requirements of BACnet MS/TP network guidelines. The zone controller automatically selects a device object ID for itself using the format 72aaa, where aaa designates the device address selected (from 004 to 127) on the MS/TP network (for example, 72004, 72005). If this ID needs to be changed by writing a new one into the zone controller device object, that should be done before any point objects are mapped. Be sure that the ID of the new zone controller being added to the NAE matches that of the zone controller itself. This number goes into the Instance Number field, Network section, Hardware tab of the Configure step in the Insert Field Device Wizard.

Adding Point ObjectsThe required point objects must be mapped under the zone controller device. To accomplish this, select the zone controller device under the BACnet Integration (refresh the tree view if required to see a newly added zone controller device), and choose Field Point from the Insert menu.

Note: For Metasys system Release 4.0 or later software, select a Field Bus or a folder under it.

Assisted Definition using Auto Discovery is the easiest way to add new point objects online; however, this requires that the zone controller to be mapped is connected and ready to communicate.

When mapping point objects, the point type must match the BACnet object type (for example, AV, MV, or BI), and the point instance number must match the point BACnet instance number.

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

11

Page 12: TEC2647Z 2 Install[1]

Setup and AdjustmentsZone Controller Operation Overview

Zone Controller User Interface KeysThe TEC2647Z-2 Zone Controller user interface consists of three keys on the front cover (as illustrated in Figure 10). The function of each key is as follows:

• OVERRIDE key overrides the unoccupied mode to occupied at the local user interface for the specified TOccTime. (TOccTime is defined by selecting the appropriate time period in the Installer Configuration Menu.) The OVERRIDE key also allows access to the Installer Configuration Menu. See Configuring the TEC2647Z-2 Zone Controller on page 13.

Note: If the Lockout parameter is set to (2): Level 3 or (3): Level 4, then this OVERRIDE key is disabled.

• UP/DOWN arrow keys change the configuration parameters and activate a setpoint adjustment.

Backlit Liquid Crystal Display (LCD)The TEC2647Z-2 Zone Controller includes a two-line, eight-character backlit display. Low-level backlighting is present during normal operation and brightens when any user interface key is pressed. The backlight returns to low level when the zone controller is left unattended for 45 seconds.

Light-Emitting Diodes (LEDs)Two LEDs are included to show a call for heating or a call for cooling:

• The HEAT LED is on when heating or reheat is on.

• The COOL LED is on when cooling is on.

Status Display MenuThe Status Display Menu is displayed during normal zone controller operation. This menu continuously scrolls through the following parameters:

• Room Temperature

• Occupancy Status (Occupied/Unoccupied/Standby/Override)

• Outside Temperature (An outside air temperature sensor is recommended to allow the H lock and C lock parameters of the rooftop controller to discontinue heating or cooling operation in response to the outside air temperature. If an outside air temperature sensor is not installed, an ambiguous outside air temperature displays on the zone controller unless its MenuScro parameter is set to off.)

Note: An option is available within the Installer Configuration Menu to lock out the scrolling display and show only the Room Temperature parameter.

Figure 10: Front Cover of Zone Controller

70.0ºFRoom TempBacklit, plain text

LCD is easy to readin any condition.

Three keys on the zone controllermake operation easy and intuitive.

LEDs indicatesystem activity.

FIG

:frnt

_vw

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

12

Page 13: TEC2647Z 2 Install[1]

Configuring the TEC2647Z-2 Zone ControllerThe TEC2647Z-2 Zone Controller comes from the factory with default settings for all configurable parameters. The default settings are shown in Table 3. To reconfigure the parameters via the zone controller, follow the steps in this section.

To access the Installer Configuration Menu, press and hold the OVERRIDE key for approximately 8 seconds. Once the Installer Configuration Menu begins, release and press the OVERRIDE key to scroll through the parameters listed in Table 3. When the desired parameter is displayed, use the UP/DOWN arrow keys to choose the desired selection option. Then press and release the OVERRIDE key to continue scrolling through the parameters.

When the zone controller is in the Installer Configuration Menu and left unattended for approximately 8 seconds, the zone controller reverts to the Status Display Menu.

Monitoring Inputs BI2 and UI3BI2 provides voltage-free contact status via the supervisory controller only. Examples of monitoring include airflow proving and filter status.

The UI3 input provides temperature sensor monitoring via the supervisory controller.

Table 3: Installer Configuration Menu (Part 1 of 5)Parameter Appearing on Display

Description and Default Selection Options

Zone MAC1 Sets a unique device address for the zone controller on the MS/TP network.Default: 255

Range: 004 to 127Note: When setting the device address, press the UP/DOWN arrow keys to change the device address in increments of 1; press and hold the UP/DOWN arrow keys to change the device address in increments of 10.

ZoneBaud Sets the baud rate of the zone controller on the MS/TP network.Default: Auto

(9600): 9600 bps(19200): 19200 bps(38400): 38400 bps(76800): 76800 bps(Auto): Auto Baud

Get From Gets all of the installer configuration menu parameter values except Zone MAC, ZoneBaud, RTC MAC, BO5 cont, Set Type, and Cal RS of another zone controller. Also copies the GUI Occupied Heat Spt, GUI Occupied Cool Spt, and Cfg Network Handle MS/TP Bus objects.Default: 255Note: This parameter requires that communication on the MS/TP Bus be functioning. If communication is not functioning, the installer configuration menu does not scroll past this parameter.

Range: 001 to 255Note: Entering a zone controller address begins a routine to get the parameter values of that zone controller, and imports those values to the zone controller from which the Get From parameter is being set. After getting the parameters, this value reverts back to 255. When getting the parameter value, press the UP/DOWN arrow keys to change the device address in increments of 1; press and hold the UP/DOWN arrow keys to change the device address in increments of 10.

RTC MAC2 Sets a unique device address for the rooftop controller to which the zone controller communicates.Default: 4Note: All zone controllers associated with the same rooftop controller must have the same RTC MAC parameter setting as the rooftop controller.

Range: 004 to 127Note: When setting the device address, press the UP/DOWN arrow keys to change the device address in increments of 1; press and hold the UP/DOWN arrow keys to change the device address in increments of 10.

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

13

Page 14: TEC2647Z 2 Install[1]

MenuScro Gives the option of having the display continuously scroll the parameters.Note: If an outside air temperature sensor is not installed at the rooftop controller, set the MenuScro parameter of the zone controller to off to prevent an ambiguous outside air temperature from displaying.Default: on

(off): The scroll is inactive.(on): The scroll is active.

C or F Provides temperature scale options for display.Default: °F

(°C): Celsius Scale(°F): Fahrenheit Scale

PIR Func3 Enables the standby setpoints.Default: offNote: Integrated Passive Infrared (PIR) is a future option for occupancy detection. Set the PIR Func parameter to off unless this PIR is installed.

(on): PIR is installed. The BI1 parameter should be set to None.(off): PIR is not installed. The BI1 parameter can be set to MotionNO or MotionNC.

Lockout Selectable Lockout Levels for limiting end user keypad interaction.Default: 0

Lockout Level

FunctionOccupied Temperature Setpoints

LocalOverride

Rooftop Controller Demand Override

(0): Level 1 Access Access Access

(1): Level 2 Access Access No Access

(2): Level 3 Access No Access No Access

(3): Level 4 No Access No Access No Access

BI13 Configuration of Binary Input 1.Default: NoneNote: BI1 can be used for remote mounted occupancy sensing.

(None): No function is associated with an input.(MotionNO): Used in the occupied mode only to toggle from the occupied setpoint to the standby setpoint when no motion is detected in the zone for 30 minutes. As soon as motion is detected in the zone, the occupied setpoint resumes. Contact open = no motion detected; contact closed = motion detected.(MotionNC): Used in the occupied mode only to toggle from the occupied setpoint to the standby setpoint when no motion is detected in the zone for 30 minutes. As soon as motion is detected in the zone, the occupied setpoint resumes. Contact open = motion detected; contact closed = no motion detected.

RehtConf Sets the number and type of reheat stages controlled by the zone controller.Default: 1

(0): None(1): Analog Duct Reheat Only(2): On/Off Duct Reheat Only(3): On/Off Peripheral Reheat Only(4): Analog Duct Reheat and On/Off Peripheral Reheat

AO2RA/DA4 Choice of reverse or direct acting analog reheat output signal.Default: DA

(RA): Reverse Acting, 0 to 100% = 10 to 0 VDC(DA): Direct Acting, 0 to 100% = 0 to 10 VDC

Table 3: Installer Configuration Menu (Part 2 of 5)Parameter Appearing on Display

Description and Default Selection Options

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

14

Page 15: TEC2647Z 2 Install[1]

AO2 OALK5 Sets the maximum outside air sensor temperature at which the first stage of zone reheat (analog reheat stage) can be used.Default: 55.0°F/13.0°C

Range: -40.0°F/-40.0°C to 122.0°F/50.0°CNote: When setting the maximum outside air sensor temperature, press the UP/DOWN arrow keys to change the temperature in 5.0F°/2.5C° increments; press and hold the UP/DOWN arrow keys to change the temperature in 50.0F°/25C° increments.

BO5 OALK5 Sets the maximum outside air sensor temperature at which the second stage of zone reheat (on/off reheat stage) can be used.Default: 32.0°/0.0°C

Range: -40.0°F/-40.0°C to 122.0°F/50.0°CNote: When setting the maximum outside air sensor temperature, press the UP/DOWN arrow keys to change the temperature in 5.0F°/2.5C° increments; press and hold the UP/DOWN arrow keys to change the temperature in 50.0F°/25C° increments.

BO5 Time4 Sets the time base for the reheat output (if used).Default: 0

(1): 10 seconds (six cycles per minute), for various equipment with solid-state relays that withstand short duty cycles such as electric heat.(0): 15 minutes (four cycles per hour), for various equipment with mechanical relays or contactors controlling mechanical reheat systems.

BO5 cont Sets the BO5 contact function.Default: N.O.

(N.C.): Energized = Contact Opened; De-Energized = Contact Closed(N.O): Energized = Contact Closed; De-Energized = Contact Opened

Unocc HT Sets the Unoccupied Heating setpoint value.Default: 62.0°F/16.5°C

Range: 40.0°F/4.5°C to 90.0°/32.0°C

Note: When adjusting the temperature, press the UP/DOWN arrow keys to change the temperature in 0.5F°/0.5C° increments; press and hold the UP/DOWN arrow keys to change the temperature in 5.0F°/5.0C° increments.

Unocc CL Sets the Unoccupied Cooling setpoint value.Default: 80.0°F/26.5°C

Range: 54.0°F/12.0°C to 100.0°C/37.5°C

St-By HT3 Sets the Standby Heating setpoint value.Default: 65.0°F/18.5°C

Range: 40.0°F/4.5°C to 90.0°/32.0°C

St-By CL3 Sets the Standby Cooling setpoint value.Default: 75.0°/24.0°C

Range: 54.0°F/12.0°C to 100.0°C/37.5°C

Set Type Provides the option of temporarily changing the heating or cooling setpoint by pressing the UP/DOWN arrow keys.Default: permnent

(temporar): Local changes to the heating or cooling setpoints are temporary and remain effective for the specified TOccTime.(permnent): Local changes to the heating or cooling setpoints are permanently stored in the zone controller memory.

TOccTime Sets the duration of the Temporary Occupancy Time when the heating or cooling setpoints in the Occupied mode are established by:• an Override Function enabled in

the Main User Menu (when the zone controller is in the Unoccupied mode)

• a temporary heating or cooling setpoint

Default: 2.0 hrs

Range: 0.0 to 12.0 hrsNote: When adjusting the TOccTime, press the UP/DOWN arrow keys to change the time in 1-hour increments; press and hold the UP/DOWN arrow keys to change the time in 10-hour increments.

Table 3: Installer Configuration Menu (Part 3 of 5)Parameter Appearing on Display

Description and Default Selection Options

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

15

Page 16: TEC2647Z 2 Install[1]

Cal RS Sets the desired room air temperature sensor calibration (offset). The offset can be added to or subtracted from the actual displayed room temperature.Default: 0.0F°/0.0C°

Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C° increments

Deadband Sets the minimum deadband between heating and cooling setpoints.Default: 2.0F°/1.0C°

Range: 2.0F°/1.0C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C° increments

Heat max Sets the Occupied, Standby, and Unoccupied maximum Heating setpoint values.Default: 90.0°F/32.0°C

Range: 40.0°F/4.5°C to 90.0°/32.0°C

Note: When adjusting the temperature, press the UP/DOWN arrow keys to change the temperature in 0.5F°/0.5C° increments; press and hold the UP/DOWN arrow keys to change the temperature in 5.0F°/5.0C° increments.

Cool min Sets the Occupied, Standby, and Unoccupied minimum Cooling setpoint values.Default: 54.0°F/12.0°C

Range: 54.0°F/12.0°C to 100.0°C/37.5°C

Min Pos Sets the minimum position of the zone damper.Default: 10%

Range: 0 to 100% Note: When adjusting the damper position, press the UP/DOWN arrow keys to change the position in 1% increments; press and hold the UP/DOWN arrow keys to change the position in 10% increments.

Max Pos Sets the maximum position of the zone damper.Default: 100%

Range: 0 to 100%

MaxHTPos6 Sets the minimum heating position of the zone damper to maximize hot airflow on a call for reheat with cold supply air.Default: 30%

Range: 0 to 100%

PIHT Wei7 Sets the weight of the Proportional-Intergral (PI) heating demand of a zone, used in the PI heating calculation of the zone controller.Default: 100%

(0%): PI Heating Weight of 0%(25%): PI Heating Weight of 25%(50%): PI Heating Weight of 50%(75%): PI Heating Weight of 75%(100%): PI Heating Weight of 100%Note: A zone that includes a special application (such as a server room, mechanical room, or cafeteria) may affect the average heating demand at the rooftop controller level, resulting in discomfort in other zones. Setting the PI heating weight to 0% eliminates this problem.

Table 3: Installer Configuration Menu (Part 4 of 5)Parameter Appearing on Display

Description and Default Selection Options

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

16

Page 17: TEC2647Z 2 Install[1]

PICL Wei7 Sets the weight of the PI cooling demand of a zone, used in the PI cooling calculation of the zone controller.Default: 100%

(0%): PI Cooling Weight of 0%(25%): PI Cooling Weight of 25%(50%): PI Cooling Weight of 50%(75%): PI Cooling Weight of 75%(100%): PI Cooling Weight of 100%Note: A zone that includes a special application (such as a server room, mechanical room, or cafeteria) may affect the average cooling demand at the rooftop controller level, resulting in discomfort in other zones. Setting the PI cooling weight to 0% eliminates this problem.

1. Zone MAC is the unique device address of the zone controller (from 004 to 127) on the MS/TP network.2. RTC MAC is the unique device address of the rooftop controller (from 004 to 127) on the MS/TP network.3. The standby setpoints are used in the standby mode. The PIR Func parameter must be set to on, or the BI1 parameter

must be set to either MotionNO or MotionNC to enable the standby mode.4. The settings for this parameter are valid only if the analog reheat sequences are enabled.5. The settings for this parameter can only be enabled if an outside air temperature sensor is connected and ready for

operation.6. The MaxHTPos value should never be lower than the Min Pos value; likewise, the MaxHTPos value should never be

higher than the Max Pos value.7. The setting for this parameter does not change the PI demand used locally at the zone controller to maintain the setpoint;

instead, it only adjusts the PI demand transferred to the rooftop controller for its highest/average demand calculations.

Table 3: Installer Configuration Menu (Part 5 of 5)Parameter Appearing on Display

Description and Default Selection Options

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

17

Page 18: TEC2647Z 2 Install[1]

Sequence of OperationThe sequence of operation is determined by the Johnson Controls TEC2664Z-2 Rooftop Controller mode and the configuration parameters preselected for the zone controller; refer to the TEC2664Z-2 BACnet MS/TP Rooftop Controller for Stand-Alone and Networked Zoning Systems Installation Instructions (Part No. 24-9890-684) for more information. See Figure 11 through Figure 20 for sequence of operation examples.

Figure 11: Zone Controller Set for No Reheat, AO2 = 0 VDC and BO5 = Off(Rooftop Controller in Cooling Mode)

CoolingSetpoint

HeatingSetpoint

AO1

FIG

:cnt

rl_cr

v_1

Figure 12: Zone Controller Set for No Reheat, AO2 = 0 VDC and BO5 = Off(Rooftop Controller in Heating Mode)

CoolingSetpoint

HeatingSetpoint

AO1

FIG

:cnt

rl_cr

v_2

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

18

Page 19: TEC2647Z 2 Install[1]

Figure 13: Zone Controller Set for Analog Duct Reheat Only, BO5 = Off(Rooftop Controller in Cooling Mode)

CoolingSetpoint

* If AO2 stage is locked, then AO1 = minimum position.

HeatingSetpoint

AO1

AO2

FIG

:cnt

rl_cr

v_3

Figure 14: Zone Controller Set for Analog Duct Reheat Only, BO5 = Off(Rooftop Controller in Heating Mode)

CoolingSetpoint

HeatingSetpoint

AO1

AO2

FIG

:cnt

rl_cr

v_4

Figure 15: Zone Controller Set for On/Off Duct Reheat Only,AO2 = 0% and On/Off Reheat Time Base = 10 Seconds

(Rooftop Controller in Cooling Mode)

CoolingSetpoint

HeatingSetpoint

A01

B05

FIG

:cnt

rl_cr

v_5

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

19

Page 20: TEC2647Z 2 Install[1]

Figure 16: Zone Controller Set for On/Off Duct Reheat Only,AO2 = 0% and On/Off Reheat Time Base = 15 Minutes

(Rooftop Controller in Cooling Mode)

CoolingSetpoint

HeatingSetpoint

AO1

B05

FIG

:cnt

rl_cr

v_6

Figure 17: Zone Controller Set for On/Off Duct Reheat Only, AO2 = Off(Rooftop Controller in Heating Mode)

CoolingSetpoint

HeatingSetpoint

AO1

B05

FIG

:cnt

rl_cr

v_7

Figure 18: Zone Controller Set for On/Off Peripheral Reheat Only, AO2 = 0%(Rooftop Controller in Cooling Mode)

CoolingSetpoint

HeatingSetpoint

AO1

B05

AO1

FIG

:cnt

rl_cr

v_8

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

20

Page 21: TEC2647Z 2 Install[1]

Figure 19: Zone Controller Set for Terminal Reheat on AO2 and Peripheral Heating on BO5(Rooftop Controller in Cooling Mode)

CoolingSetpoint

HeatingSetpoint

AO1AO2

B05

FIG

:cnt

rl_cr

v_9

Figure 20: Zone Controller Set for Terminal Reheat on AO2 and Peripheral Heating on BO5(Rooftop Controller in Heating Mode)

CoolingSetpoint

HeatingSetpoint

AO1

AO2

B05

FIG

:cnt

rl_cr

v_10

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

21

Page 22: TEC2647Z 2 Install[1]

AccessoriesAll the accessories in Table 4 include mounting hardware; contact the nearest Johnson Controls representative to order any of these parts.

Note: Review the technical specifications of the accessories prior to their use in an application.

Repair InformationIf the TEC2647Z-2 Zone Controller fails to operate within its specifications, see Table 5 for troubleshooting details. For a replacement zone controller, contact the nearest Johnson Controls representative.

Table 4: Accessories (Order Separately)Code Number DescriptionSEN-600-1 Remote Inside Air Temperature Sensor

TE-6361M-11 Duct Mount Air Temperature Sensor (Metal Enclosure)

TE-6363P-11, 2 Outside Air Temperature Sensor (Plastic Enclosure)

SEN-600-4 Remote Inside Air Temperature Sensor with Occupancy Override and LED

MS-BACEOL-0 RS485 End-of-Line Terminator

ZOVSD-wwwXhhh Rectangular damper with a factory-installed Johnson Controls M9104-GGA-3 Electric Actuator for proportional zoning applications. Widths (www) are available from 8 in./20.3 cm (008) to 30 in./76.2 cm (030) in 1 in./2.5 cm increments. Heights (hhh) are available from 6 in./15.2 cm (006) to 30 in./76.2 cm (030) in 1 in./2.5 cm increments.Example: To order a rectangular damper assembly measuring 8 in./20.3 cm wide by 6 in./15.2 cm high, use code number ZOVSD-008X006.

RZGddPNNO Round damper with a factory-installed Johnson Controls M9104-GGA-3 Electric Actuator for proportional zoning applications. Diameters (dd) are available from 6 in./15.2 cm (06) to 18 in./45.7 cm (18) in 1 in./2.5 cm increments.Example: To order a round damper assembly measuring 6 in./15.2 cm in diameter, use code number RZG06PNNO.

1. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.

2. An outside air temperature sensor is recommended to allow the H lock and C lock parameters of the rooftop controller to discontinue heating or cooling operation in response to the outside air temperature. If an outside air temperature sensor is not installed, an ambiguous outside air temperature displays on the zone controller unless its MenuScro parameter is set to off.

Table 5: Troubleshooting Details1 (Part 1 of 5)Symptom Probable Cause SolutionLoss of Control or Poor Control at Multiple Zones

Duplicate Media Access Control (MAC) Addresses Are Interrupting Communications

Check all devices on the network for unique MAC addresses.

Wiring Errors Are Interrupting Communications

Check connections and continuity.

Zone Controllers Are Disconnected or Offline

Cycle the power on the zone controllers (in case the MAC address was changed without a reset).

Remove the cover of the zone controllers and observe that the green LED on the communication module is flashing repeatedly (short-short-long). If the communication module appears to be out of service:• check that it is properly attached to the main thermostat circuit board• check that the communication cable is properly installed

Rooftop Controllers Are Disconnected or Offline

Cycle the power on the rooftop controllers (in case the MAC address was changed without a reset).

Check for the Comm Lost alarm at the rooftop controller.

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

22

Page 23: TEC2647Z 2 Install[1]

Loss of Control or Poor Control at Multiple Zones

All Units on the Network Are Set to Auto Baud

Select one MS/TP master unit on the network (preferably the rooftop controller or a supervisory controller) to operate at a specific baud rate.

One or More Units on the Network Are Set to Specific but Conflicting Baud Rates

Check that all of the units not set to Auto Baud have the same baud rate selected.

Improper Rooftop Controller Parameters

Review all parameters against the system design.

Insufficient Airflow from the Rooftop Unit

Check the installation and configuration of the bypass damper.

Check the static pressure setpoint and transducer.

Check the fan control wiring.

Check for the proper fan delay configuration at the rooftop controller.

Check for a fan malfunction.

Rooftop Unit Heating/Cooling Stage Malfunction

Check for proper operation of all rooftop heating/cooling stages.

Check for proper number and sizing of the stages.

Check all wiring.

Check the discharge air lockout temperature.

Check the discharge air sensor.

Check for the proper anti-cycle configuration at the rooftop controller and other equipment.

Inappropriate Modification of the Rooftop Controller or Zone Controller Configuration by the Supervisory Controller

Set the password access at the supervisory controller to restrict access to authorized personnel.

Do not map sensitive configuration parameters into the supervisory controller.

Inappropriate Modification of the Rooftop Controller or Zone Controller by an Unauthorized User

Review the configuration parameters against the system design.

Alternate Control Scheme is Active with Faulty or Missing Input (Active when the Rooftop Controller Loses All Communications)

Replace or repair the missing, inaccurate, or wrong return air sensor.

Fix and/or relocate the inaccurate or poorly placed rooftop controller integral temperature sensor.

Alternate Control Scheme is Active with Inappropriate Setpoints

Check and reenter the setpoints if needed.

Inappropriate Discharge Air Sensor Configuration

If heating/cooling lockout based on the discharge air is desired, properly install a rooftop controller discharge air sensor and properly set the discharge air low limit and discharge air high limit parameters.

Inappropriate Outside Air Sensor Configuration

It heating/cooling lockout based on the outside air is desired, properly install an outside air temperature discharge air sensor, and properly set the cooling lockout and heating lockout parameters.

Table 5: Troubleshooting Details1 (Part 2 of 5)Symptom Probable Cause Solution

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

23

Page 24: TEC2647Z 2 Install[1]

Loss of Control or Poor Control at a Single Zone

Zone Controller MAC Address (Associated with the Rooftop Controller) Is not Changed from Its Default

Confirm that each zone controller is associated with the desired rooftop controller.

Zone Controller MAC Address (Associated with the Rooftop Controller) Is Set to No Device or Non-Rooftop Controller Device

Confirm that each zone controller is associated with the desired rooftop controller.

Zone Controller MAC Address (Associated with the Rooftop Controller) Is Set to the Incorrect Rooftop Controller

Confirm that each zone controller is associated with the desired rooftop controller.

Zone Controller MAC Address Is Set in the Range of 128 through 254

Confirm that each zone controller has a unique MAC address in the range of 4 through 127.

Zone Controllers Are Disconnected or Offline

Cycle the power on the zone controllers (in case the MAC address was changed without a reset).

Remove the cover of the zone controllers and observe that the green LED on the communication module is flashing repeatedly (short-short-long). If the communication module appears to be out of service:• check that it is properly attached to the main thermostat circuit board• check that the communication cable is properly installed

Zone Controller Damper Malfunction

Check the damper installation.

Check the damper minimum position and the damper maximum position parameters.

Incorrect Zone Sequence for the Zone Demand

Check if the zone is paired with a drastically different zone (for example, one zone mostly paired with another zone mostly in shade).

Check the PI weighting of the zone.

Check for a faulty zone sensor or poor placement of the sensor.

Check for proper placement of the zone controller (for example, no holes in the wall or not placed in the air stream).

Insufficient (or Missing) Reheat

Check that the specified reheat is sufficient for the zone.

Incorrectly Installed or Configured Reheat

Check the configuration for installed reheat.

Check the AO2 OALK and BO5 OALK parameters on the zone controller.

Check the wiring.

Check the MaxHTPos parameter on the zone controller.

Improper Zone Controller Configuration Parameters

Review the configuration parameters against the system design.

If Get From service was used to configure the zone controller, confirm that configuration parameters of the source zone controller are correct.

PI Weighting Is Incorrect Evaluate the heating and cooling weighting parameters for the zone.

Table 5: Troubleshooting Details1 (Part 3 of 5)Symptom Probable Cause Solution

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

24

Page 25: TEC2647Z 2 Install[1]

Cannot Modify the Occupied Setpoints at the Zone Controller Keypad

Lockout Is Set to 3 Change the lockout level to either 0, 1, or 2.

No Response (or Inadequate Response) to the Zone Controller Occupancy Override

Wrong Override Strategy Is Configured

Check that the zone controller lockout level is set to 1 if local override is desired.Note: Local override attempts to reach the occupied setpoints without requesting any additional cooling or heating from the rooftop controller.

Check that the zone controller lockout level is set to 0 if global override is desired.Note: Global override causes the rooftop controller to consider the demand of the zone when determining the zone sequence.

Zone Standby Setpoints Are Not Used When Expected

The PIR Func Parameter Is Not Configured Properly or the PIR Device Is Not Installed Properly

Configure the PIR Func parameter properly.

Install the PIR device properly.

The BI1 Parameter Is Not Configured Properly or the Motion Detector Is Not Installed Properly

Check that the PIR Func parameter is set to off.

Check that the BI1 parameter is configured properly.

Install the motion detector properly.

Zone Continues to Use Standby Setpoints When the Zone Is Occupied

The PIR Device or the Motion Detector Is Not Installed or Functioning Properly

Check the installation and function of the PIR device and the motion detector.

Cannot Access the Occupancy Schedule at the Rooftop Controller Keypad

Lockout Is Set to 2 Change the lockout level to 0.

Verify that the BI1 parameter is not set to remote night setback.

Cannot Change the System Mode at the Rooftop Controller Keypad

Lockout Is Set to 1 or 2 Change the lockout level to 0.

Zones Are Not Following the Rooftop Controller Occupancy Schedule

Wrong Network Handle Is Written to the Zone Controller

Write the correct network handle to the zone controller.Note: The network handle is only written via the supervisory controller; not the zone controller installer configuration menu.

Confirm that each zone controller is associated with the desired rooftop controller.

Cannot Start or Cancel the System Occupancy at the Rooftop Controller Keypad

Lockout Is Set to 2 Change the lockout level to 0 or 1.

Zones Are Not Following the Supervisory Controller Occupancy Schedule

Wrong Network Handle Is Written to the Zone Controller

Write the correct network handle to the zone controller.The network handle is only written via the supervisory controller, not the zone controller installer configuration menu.

Table 5: Troubleshooting Details1 (Part 4 of 5)Symptom Probable Cause Solution

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

25

Page 26: TEC2647Z 2 Install[1]

Technical Specifications

No Progressive Recovery

Progressive Recovery Is Not Functioning

Check that the Prog rec parameter is set to on.

Check if the gap between schedule events is less than 90 minutes.Note: If progressive recovery is desired, the system must be in the unoccupied mode for more than 90 minutes.

Check that the occupied heating setpoint is less than the unoccupied heating setpoint, and that the occupied cooling setpoint is greater than the unoccupied cooling setpoint.

Check if the rooftop controller is offline and is attempting progressive recovery using return air control. If network communication is lost, the return air sensor controls the rooftop controller to maintain the heating and cooling setpoints. Check that the occupied heating setpoint is less than the unoccupied heating setpoint, and that the occupied cooling setpoint is greater than the unoccupied cooling setpoint.

Supervisory Controller Cannot Control

--- Check the wiring.

Check for failure of auto discovery or manual definition of the rooftop controllers and zone controllers.

Check for incorrect network handle.

Not All Configuration Parameters Are Visible at the Zone Controller

The Get From Parameter Is Set to a Value Other Than 255

Change the Get From parameter to 255, until a baud rate is established on the network.

1. For common MS/TP troubleshooting information, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).

Table 5: Troubleshooting Details1 (Part 5 of 5)Symptom Probable Cause Solution

TEC2647Z-2 BACnet MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems (Part 1 of 2)Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or

Safety Extra-Low Voltage (SELV)

Analog Output Rating 0 to 10 VDC into 2k ohm Resistance (Minimum)

Auxiliary Output Rating

Triac Output 19 to 30 VAC, 15 mA to 1 A Continuous Current, 3 A Peak In-Rush Current

Binary Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1 and BI2

Analog Inputs Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative Temperature Coefficient (NTC) Thermistor Sensors

Temperature Sensor Type Local 10k ohm NTC Thermistor

Wire Size 18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended

MS/TP Network Guidelines 32 Devices Maximum; 4,000 ft (1,219 m) Maximum Cable Length

Temperature Range

Backlit Display

-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments

Heating Control

40.0°F/4.5°C to 90.0°F/32.0°C

Cooling Control

54.0°F/12.0°C to 100.0°F/37.5°C

Accuracy ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated

Minimum Deadband 2F°/1C° between Heating and Cooling

TEC2647Z-2 BACnet® MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems Installation Instructions

26

Page 27: TEC2647Z 2 Install[1]

Ambient Conditions

Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing

Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing

Compliance United States UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment

FCC Compliant to CFR 47, Part 15, Subpart B, Class A

Canada UL Listed, File E27734, CCN XAPX7, Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment

Industry Canada, ICES-003

Shipping Weight 0.75 lb (0.34 kg)

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

TEC2647Z-2 BACnet MS/TP Zone Controller for Stand-Alone and Networked Zoning Systems (Part 2 of 2)