System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH...
Transcript of System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH...
![Page 1: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/1.jpg)
The International Authority on Air System Components
Fan Performance
Mark StevensDeputy Executive Director
AMCA International
![Page 2: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/2.jpg)
The International Authority on Air System Components
Fan Testing for Air Performance
![Page 3: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/3.jpg)
The International Authority on Air System Components
Test Fan
AMCA Standard 210
Auxiliary Fan
NozzlesFan Airflow
Piezometer Ring Fan Static Pressure
![Page 4: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/4.jpg)
The International Authority on Air System Components
AMCA 210 Test Results
0
100
200
300
400
500
600
700
800
0 2 4 6 8 10 12Air Flow, Q
Pres
sure
, P
0
0.5
1
1.5
2
2.5
Power, H
![Page 5: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/5.jpg)
The International Authority on Air System Components
AMCA Standards 500-D & -LTest Damper
Auxiliary Fan
NozzlesDamper Airflow
Piezometer Ring Damper Pressure Drop
![Page 6: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/6.jpg)
The International Authority on Air System Components
Fan Operating Point
Operating Point
0
100
200
300
400
500
600
700
0 2 4 6 8 10 12
Air Flow, Q
Pres
sure
, PAMCA 500-D Test Results
![Page 7: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/7.jpg)
The International Authority on Air System Components
Speed Change
New Operating PointNew speed
0
100
200
300
400
500
600
700
800
0 2 4 6 8 10 12 14
Air Flow, Q
Pres
sure
, P Operating Point
![Page 8: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/8.jpg)
The International Authority on Air System Components
Damper Opening
New System
New Operating Point
0
100
200
300
400
500
600
700
0 2 4 6 8 10 12
Air Flow, Q
Pres
sure
, P
Operating Point
![Page 9: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/9.jpg)
The International Authority on Air System Components
System Effect1ST Definition
Installed duct configuration does not match tested duct configuration
![Page 10: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/10.jpg)
The International Authority on Air System Components
Test Fan
Installation Type DDucted Inlet / Ducted Outlet
Auxiliary Fan
NozzlesFan Airflow
Piezometer Ring Fan Static Pressure
Installed Fan
PlenumPlenum
![Page 11: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/11.jpg)
The International Authority on Air System Components
AMCA Catalog Ratings
• “Performance certified is forinstallation type:
◦ A: Free inlet, Free outlet”◦ B: Free inlet, Ducted outlet”◦ C: Ducted inlet, Free outlet”◦ D: Ducted inlet, Ducted outlet”
![Page 12: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/12.jpg)
The International Authority on Air System Components
System Effect2nd Definition
Even when the tested duct configuration matches the installed duct configuration, improper duct design can introduce adverse flow conditions
![Page 13: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/13.jpg)
The International Authority on Air System Components
Elbow Example
![Page 14: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/14.jpg)
The International Authority on Air System Components
![Page 15: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/15.jpg)
The International Authority on Air System Components
![Page 16: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/16.jpg)
The International Authority on Air System Components
![Page 17: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/17.jpg)
The International Authority on Air System Components
![Page 18: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/18.jpg)
The International Authority on Air System Components
![Page 19: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/19.jpg)
The International Authority on Air System Components
![Page 20: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/20.jpg)
The International Authority on Air System Components
![Page 21: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/21.jpg)
The International Authority on Air System Components
![Page 22: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/22.jpg)
The International Authority on Air System Components
![Page 23: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/23.jpg)
The International Authority on Air System Components
![Page 24: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/24.jpg)
The International Authority on Air System Components
AMCA Publication 201Detailed Plenum Example
Plenum
![Page 25: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/25.jpg)
The International Authority on Air System Components
Detailed Plenum Example
E-F duct friction at 5000CMH (Q) 747 Pa (duct design)E contraction loss-plenum to duct 50 Pa (part of duct system)E PS energy required to create velocity at E 125 Pa (part of duct system)D PV loss (also PT loss) at D as result of air velocity decrease 0 Pa
PS does not change from duct to plenum at D C-D outlet duct on fan as tested 0 Pa
--------------------
REQUIRED Fan PS 922 Pa
![Page 26: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/26.jpg)
The International Authority on Air System Components
Detailed Plenum Example
D-E duct friction at 5000CMH (Q) 747 Pa (duct design)D contraction loss-plenum to duct 50 Pa (part of duct system)D PS energy required to create velocity at D 125 Pa (part of duct system)
B-C SEF 149 PaB-C PV loss (also PT loss) at C as result of air velocity decrease 0 Pa
PS does not change from duct to plenum at C ------------------
REQUIRED Fan PS 1071 Pa
![Page 27: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/27.jpg)
The International Authority on Air System Components
Fan Laws for Speed Change
QC = NC
N( ) Q Q, Fan Airflow Rate
2
PC = NC
N( ) P P, Fan Pressure
H, Fan PowerHC = NC
N( ) H
3
![Page 28: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/28.jpg)
The International Authority on Air System Components
8% Speed Change
25% More H
0
100
200
300
400
500
600
700
800
0 2 4 6 8 10 12 14Air Flow, Q
Pres
sure
,P
0
0.5
1
1.5
2
2.5
Power,H
8% More Q
![Page 29: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/29.jpg)
The International Authority on Air System Components
Plenum Example from AMCA 201Assuming:
• Use of the same fan for both systems• Can attain both operating points with a
change in speed• The increased in power consumption to
overcome System Effect is about 25%◦ (1071/922)0.5 = 1.08 (Fan Law for pressure)◦ 1.083 = 1.25 (Fan Law for Power)
![Page 30: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/30.jpg)
The International Authority on Air System Components
Ducted FanFan as Tested
C-D duct friction 750 Pa (duct design)A free inlet 0 Pa (no SEF)B-C outlet with straight duct attached for 2 or more diam. 0 Pa (no SEF)
--------------------
REQUIRED Fan PS 750 Pa
![Page 31: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/31.jpg)
The International Authority on Air System Components
Ducted FanExhaust System
A Entrance loss-sharp edge duct 100 Pa (duct design)A-B Duct friction at 5000CMH 750 Pa (duct design)B SEF 1 (Elbow at Inlet) 150 Pa C SEF 2 (Obstruction) 50 Pa E SEF 3 (Abrupt Discharge) 150 Pa
------------------
REQUIRED Fan Ps 1200 Pa
![Page 32: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/32.jpg)
The International Authority on Air System Components
Inlet System Effect
ACTUAL FAN CURVE WITH SYSTEM EFFECT
SYSTEM EFFECT
CATALOG PERFORMANCE CURVE
AIRFLOW DEFICIENCY
DE
SIG
N R
ES
ISTA
NC
E
DESIGN AIRFLOW
![Page 33: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/33.jpg)
The International Authority on Air System Components
Outlet System EffectACTUAL SYSTEM WITH SYSTEM EFFECT
CALCULATED SYSTEM WITH NO ALLOWANCE FOR SYSTEM EFFECT
SYSTEM EFFECT LOSS AT DESIGN AIRFLOW
CATALOG PERFORMANCE CURVE
AIRFLOW DEFICIENCY
DE
SIG
N R
ES
ISTA
NC
E
DESIGN AIRFLOW
![Page 34: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/34.jpg)
The International Authority on Air System Components
Speed Changes• Before Increasing Speed
◦ Check with the manufacturer for max safe operating speed
◦ Determine expected power increase• Motor size• Electric Service
◦ Expect more noise
![Page 35: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/35.jpg)
The International Authority on Air System Components
![Page 36: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/36.jpg)
The International Authority on Air System Components
![Page 37: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/37.jpg)
The International Authority on Air System Components
Rules of Thumb
• Minimum 2.5 duct diameters on Outlet
• Minimum 3 to 5 duct diameters on Inlet
• Avoid inlet swirl
![Page 38: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/38.jpg)
The International Authority on Air System Components
Recommendations
• Allow enough space in the building design to allow for appropriate fan connections to the system
![Page 39: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/39.jpg)
The International Authority on Air System Components
Recommendations
• Use allowances in the design calculations when space or other factors dictate less than optimum arrangement of the fan outlet and inlet connections
![Page 40: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/40.jpg)
The International Authority on Air System Components
Recommendations
• Include adequate allowance for the effect of all accessories and appurtenances on the performance of the system and the fan
![Page 41: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate](https://reader035.fdocuments.in/reader035/viewer/2022062600/5ab459057f8b9a0f058bb61e/html5/thumbnails/41.jpg)
The International Authority on Air System Components
Thank you