System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH...

41
The International Authority on Air System Components Fan Performance Mark Stevens Deputy Executive Director AMCA International

Transcript of System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH...

Page 1: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Fan Performance

Mark StevensDeputy Executive Director

AMCA International

Page 2: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Fan Testing for Air Performance

Page 3: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Test Fan

AMCA Standard 210

Auxiliary Fan

NozzlesFan Airflow

Piezometer Ring Fan Static Pressure

Page 4: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

AMCA 210 Test Results

0

100

200

300

400

500

600

700

800

0 2 4 6 8 10 12Air Flow, Q

Pres

sure

, P

0

0.5

1

1.5

2

2.5

Power, H

Page 5: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

AMCA Standards 500-D & -LTest Damper

Auxiliary Fan

NozzlesDamper Airflow

Piezometer Ring Damper Pressure Drop

Page 6: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Fan Operating Point

Operating Point

0

100

200

300

400

500

600

700

0 2 4 6 8 10 12

Air Flow, Q

Pres

sure

, PAMCA 500-D Test Results

Page 7: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Speed Change

New Operating PointNew speed

0

100

200

300

400

500

600

700

800

0 2 4 6 8 10 12 14

Air Flow, Q

Pres

sure

, P Operating Point

Page 8: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Damper Opening

New System

New Operating Point

0

100

200

300

400

500

600

700

0 2 4 6 8 10 12

Air Flow, Q

Pres

sure

, P

Operating Point

Page 9: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

System Effect1ST Definition

Installed duct configuration does not match tested duct configuration

Page 10: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Test Fan

Installation Type DDucted Inlet / Ducted Outlet

Auxiliary Fan

NozzlesFan Airflow

Piezometer Ring Fan Static Pressure

Installed Fan

PlenumPlenum

Page 11: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

AMCA Catalog Ratings

• “Performance certified is forinstallation type:

◦ A: Free inlet, Free outlet”◦ B: Free inlet, Ducted outlet”◦ C: Ducted inlet, Free outlet”◦ D: Ducted inlet, Ducted outlet”

Page 12: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

System Effect2nd Definition

Even when the tested duct configuration matches the installed duct configuration, improper duct design can introduce adverse flow conditions

Page 13: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Elbow Example

Page 14: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Page 15: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Page 16: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Page 17: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Page 18: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Page 19: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Page 20: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Page 21: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Page 22: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Page 23: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Page 24: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

AMCA Publication 201Detailed Plenum Example

Plenum

Page 25: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Detailed Plenum Example

E-F duct friction at 5000CMH (Q) 747 Pa (duct design)E contraction loss-plenum to duct 50 Pa (part of duct system)E PS energy required to create velocity at E 125 Pa (part of duct system)D PV loss (also PT loss) at D as result of air velocity decrease 0 Pa

PS does not change from duct to plenum at D C-D outlet duct on fan as tested 0 Pa

--------------------

REQUIRED Fan PS 922 Pa

Page 26: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Detailed Plenum Example

D-E duct friction at 5000CMH (Q) 747 Pa (duct design)D contraction loss-plenum to duct 50 Pa (part of duct system)D PS energy required to create velocity at D 125 Pa (part of duct system)

B-C SEF 149 PaB-C PV loss (also PT loss) at C as result of air velocity decrease 0 Pa

PS does not change from duct to plenum at C ------------------

REQUIRED Fan PS 1071 Pa

Page 27: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Fan Laws for Speed Change

QC = NC

N( ) Q Q, Fan Airflow Rate

2

PC = NC

N( ) P P, Fan Pressure

H, Fan PowerHC = NC

N( ) H

3

Page 28: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

8% Speed Change

25% More H

0

100

200

300

400

500

600

700

800

0 2 4 6 8 10 12 14Air Flow, Q

Pres

sure

,P

0

0.5

1

1.5

2

2.5

Power,H

8% More Q

Page 29: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Plenum Example from AMCA 201Assuming:

• Use of the same fan for both systems• Can attain both operating points with a

change in speed• The increased in power consumption to

overcome System Effect is about 25%◦ (1071/922)0.5 = 1.08 (Fan Law for pressure)◦ 1.083 = 1.25 (Fan Law for Power)

Page 30: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Ducted FanFan as Tested

C-D duct friction 750 Pa (duct design)A free inlet 0 Pa (no SEF)B-C outlet with straight duct attached for 2 or more diam. 0 Pa (no SEF)

--------------------

REQUIRED Fan PS 750 Pa

Page 31: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Ducted FanExhaust System

A Entrance loss-sharp edge duct 100 Pa (duct design)A-B Duct friction at 5000CMH 750 Pa (duct design)B SEF 1 (Elbow at Inlet) 150 Pa C SEF 2 (Obstruction) 50 Pa E SEF 3 (Abrupt Discharge) 150 Pa

------------------

REQUIRED Fan Ps 1200 Pa

Page 32: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Inlet System Effect

ACTUAL FAN CURVE WITH SYSTEM EFFECT

SYSTEM EFFECT

CATALOG PERFORMANCE CURVE

AIRFLOW DEFICIENCY

DE

SIG

N R

ES

ISTA

NC

E

DESIGN AIRFLOW

Page 33: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Outlet System EffectACTUAL SYSTEM WITH SYSTEM EFFECT

CALCULATED SYSTEM WITH NO ALLOWANCE FOR SYSTEM EFFECT

SYSTEM EFFECT LOSS AT DESIGN AIRFLOW

CATALOG PERFORMANCE CURVE

AIRFLOW DEFICIENCY

DE

SIG

N R

ES

ISTA

NC

E

DESIGN AIRFLOW

Page 34: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Speed Changes• Before Increasing Speed

◦ Check with the manufacturer for max safe operating speed

◦ Determine expected power increase• Motor size• Electric Service

◦ Expect more noise

Page 35: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Page 36: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Page 37: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Rules of Thumb

• Minimum 2.5 duct diameters on Outlet

• Minimum 3 to 5 duct diameters on Inlet

• Avoid inlet swirl

Page 38: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Recommendations

• Allow enough space in the building design to allow for appropriate fan connections to the system

Page 39: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Recommendations

• Use allowances in the design calculations when space or other factors dictate less than optimum arrangement of the fan outlet and inlet connections

Page 40: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Recommendations

• Include adequate allowance for the effect of all accessories and appurtenances on the performance of the system and the fan

Page 41: System Effect 2011 July compressed - AMCA · PDF fileInlet System Effect ACTUAL FAN CURVE WITH SYSTEM EFFECT ... • Allow enough space in the building design to allow for appropriate

The International Authority on Air System Components

Thank you