© 2020, SatService GmbH www.satnms.com DEICE-APP-2020-02-20 1/7 System Description and Configuration of sat-nms Deice Controller The sat-nms Deice Controller is characterized by an efficient and energy-saving deicing control sequence. The module provides interfaces for up to 16 heating elements with opto-coupled in- and outputs and potential free-relay outputs. It can be mounted as outdoor unit into a cabinet next to the antenna or as indoor unit. All loop parameters and the temperature slope are software-configurable. This means, it is possible to adapt the deicing sequence to your needs and optimizing the power consumption. All heater elements are controlled separately, will be only activated if necessary and will be switched off immediately if they are not required anymore. With the SatService solution, you will get full local and remote monitoring & control capability for this controller. The sat-nms MNC module includes an integrated web-server with an Ethernet interface so that the operator can also monitor and control the deicing via its web-browser - both locally or remote whenever it is connected to the same LAN. The M&C module provides the following interfaces for monitoring & control via external equipment: Serial Remote Control Protocol via RS232 TCP/IP via the 100-Base-T Ethernet Interface SNMP (Simple Network Management Protocol) Remote Control Protocol over HTTP get request The sat-nms Deice Controller is supplied with 24VDC. The dimensions of the module are 264x165x60mm, it weighs 1.5 kg and is mounted on a DIN-Rail. Interfaces 48 digital Input 16 digital Output 8 Interfaces to control hot plates 4 analog Inputs for external PT1000 Sensors RS232, Ethernet 24V DC Power Output Web Interface - Current State The following pages explain web-based graphical interface of the sat-nms Deice Controller. The 'State' page is the main page of the sat-nms Deice-Controller that shows the current state of all in- and outputs. The page shows all information about the input / output states, temperature readings and faults. The page is read-only. Deice Operation The operation table shows the current state of the operation parameters: Mode: The mode state shows the operation state of the deicing controller. The following modes are possible: o OFF: The deice function is off; all other operation states will be reset to the start parameters Antenna Deicing Cabinet

Transcript of System Description and Configuration of sat-nms Deice ...The sat-nms Deice Controller provides an...

  • © 2020, SatService GmbH www.satnms.com DEICE-APP-2020-02-20 1/7

    System Description and Configuration of sat-nms Deice Controller

    The sat-nms Deice Controller is characterized by an efficient and energy-saving deicing control

    sequence. The module provides interfaces for up to 16 heating elements with opto-coupled in- and

    outputs and potential free-relay outputs. It can be mounted as outdoor unit into a cabinet next to the

    antenna or as indoor unit. All loop parameters and the temperature slope are software-configurable.

    This means, it is possible to adapt the deicing sequence to your needs and optimizing the power

    consumption. All heater elements are controlled separately, will be only activated if necessary and will

    be switched off immediately if they are not required anymore. With the SatService solution, you will get

    full local and remote monitoring & control capability for this controller. The sat-nms MNC module

    includes an integrated web-server with an Ethernet interface so that the operator can also monitor and

    control the deicing via its web-browser - both locally or remote

    whenever it is connected to the same LAN. The M&C module provides

    the following interfaces for monitoring & control via external

    equipment:

    • Serial Remote Control Protocol via RS232

    • TCP/IP via the 100-Base-T Ethernet Interface

    • SNMP (Simple Network Management Protocol)

    • Remote Control Protocol over HTTP get request

    The sat-nms Deice Controller is supplied with 24VDC. The

    dimensions of the module are 264x165x60mm, it weighs 1.5 kg

    and is mounted on a DIN-Rail.

    Interfaces

    • 48 digital Input

    • 16 digital Output

    • 8 Interfaces to control hot plates

    • 4 analog Inputs for external PT1000 Sensors

    • RS232, Ethernet

    • 24V DC Power Output

    Web Interface - Current State

    The following pages explain web-based graphical interface of the sat-nms Deice Controller. The 'State'

    page is the main page of the sat-nms Deice-Controller that shows the current state of all in- and

    outputs. The page shows all information about the input / output states, temperature readings and

    faults. The page is read-only.

    Deice Operation

    The operation table shows the current state of the operation parameters:

    • Mode: The mode state shows the operation state of the deicing controller. The following modes are possible:

    o OFF: The deice function is off; all other operation states will be reset to the start parameters

    Antenna Deicing Cabinet

  • © 2020, SatService GmbH www.satnms.com DEICE-APP-2020-02-20 2/7

    o MANUAL: The deicing will start manually by overwriting the deice sensor state. The Heater/Blowers will only start if the ambient sensor states ON, the ambient

    temperature is below the threshold, the internal reflector temperature is below the

    threshold minus the hysteresis and no alarm exists of the Heater/Blower.

    o AUTO: The system operates in auto mode that is the normal operation mode. Snow on the deice sensor will trigger the deice procedure.

    • Request Deice: This state shows that a deice cycle is requested and the loop control of the Heater/Blowers is active.

    • Active Stages: This state shows, which stage of the Heater/Blowers is active.

    o 0 = no stage is active

    o 1 = all Heater/Blowers selected are active

    o 2 = stage 1 and 2 are active

    o 3 = all stages are active

    • Temperature slop: During the heating phase, this value shows the temperature slope in the main reflector in °C per min. This value compared with the corresponding threshold is used to select the

    number of used stages.

    • Summary alarm: This state shows the summary alarm of the deice section.

    Deice Sensor State

    The Sensor State shows the current state of each sensor involved in the deice procedure:

    • Deice Sensor / Remaining Time: The State ON means the sensor is triggered by snow. The remaining time counter

    will be started after the sensor falls back to OFF and will

    display the time how long the deice cycle will be kept on

    after loss of the input trigger.

    • Optic Sensor / Panel Temp.: This state will be displayed if snow is inside the reflector and shows the temperature of the panel in the main reflector.

    • Ambient Temp. Sensor: This state is ON if the temperature is below the configured temperature sensor value and below the real measured value. Attention! Only if the state is ON and the value is

    below the adjusted threshold deicing is possible.

    • Reflector Temp. bottom / top: This value is used to control the temperature inside the reflector for the adjusted threshold.

    • Sub-Reflector Control Temp.: This state controls the ON/OFF State of the sub-reflector heating.

    Deice Heater/Blower State

    The Heater/Blower State shows the current state of each Heater/Blower:

    • The second column shows the name of the specific Heater/Blower unit to identify the device.

    • The third column displays the state ON/OFF

    • The fourth column gives information in which stages the Heater/Blower operates. Outputs configured as 'UNUSED' show neither a circuit name

    nor an ON/OFF state.

  • © 2020, SatService GmbH www.satnms.com DEICE-APP-2020-02-20 3/7

    • The fifth and sixth columns show the alarm state of each Heater/Blower unit. Two separate Alarm Inputs are foreseen for each Heater/Blower Unit. Inputs configured as 'UNUSED' show neither an

    OK/FLT state.

    Rain-blower Operation

    The operation table shows the current state of the operation parameters:

    • Mode: The mode state shows the operation state of the rain- blower controller. The following modes are possible:

    o OFF: The rain-blower function is off; all other operation states will be reset to the start

    parameters.

    o MANUAL: The rain-blower will start manually by overwriting the rain sensor state. The Heater/Blower will only start if there is no alarm of the Heater/Blower.

    o AUTO: The system operates in auto mode that is the normal operation mode. Rain or snow on the deice sensor will trigger the rain-blower procedure.

    • Request Rain-Blower: This state shows that a rain-blower cycle is requested and the control of the Heater/Blower is active.

    • Summary Alarm: This state shows the summary alarm of the rain-blower section.

    Rain Blower Sensor State

    The sensor state shows the current state of each sensor which is involved in the rain-blower procedure:

    • Rain or Deice Sensor / Remaining Time: The State ON means, the sensor is triggered by snow or rain. The

    remaining time counter will start after the sensor falls

    back to OFF and will display the time how long the rain-blower cycle will be kept on after loss of the

    input trigger.

    Rain-blower Heater/Blower State

    The Heater/Blower state shows the current state of the feedhorn

    blower.

    Web Interface - Settings

    The page 'Settings' is used

    to configure the sat-nms

    Deice Controller. It is

    possible to change any

    parameters in this page.

    • 'Operation Mode Deice' and 'Operation Mode

    Rainblower' are

    'Operation Parameter'.

    For each Operation the

    following parameters

    are possible to change:

    OFF, MANUAL, AUTO.

  • © 2020, SatService GmbH www.satnms.com DEICE-APP-2020-02-20 4/7

    • The 'Loop Parameters' are adjustable values for the heating control.

    Web Interface - Setup

    The pages accessible through the 'Setup' menu items contain the sat-nms Deice Controller's installation

    parameters. Installation parameters are protected by an administrator password, without a successful

    login as administrator you may view the configuration settings but you may not change them.

    • General Setup: Contains general configuration parameters like communication interface settings, passwords etc.

    • Output Circuits: The usage of the output circuits of the sat-nms Deice Controller will be configured on this page like Blower/Heater, Sub Reflector, Feed Horn Blower

    • Input Circuits: The usage of the input circuits is configured on this page like alarm contacts of the heater, digital temperature sensors, etc.

    • Temperature Sensors: The temperature sensors connected to the sat-nms Deice Controller are configured on this page.

    • State All: State of all Inputs and Outputs in the basic format

    • Set Outputs: Setting of all Outputs, which are set as normal outputs.

    Event Log

    The sat-nms Deice Controller provides an internal event log recording all changes at input circuits,

    output circuit actuations and temperature limit alarms. Each event is stored with a time stamp read

    from the sat-nms Deice Controller's real time clock. The event log is limited to a size of 500 events, the

    log works as a circular buffer and recent entries automatically overwrite the elder ones. The event log

  • © 2020, SatService GmbH www.satnms.com DEICE-APP-2020-02-20 5/7

    resides in the sat-nms Deice Controller's volatile memory; the log always starts empty when the sat-nms

    Deice Controller is powered on.

    Auto Mode Sequence

    When the AUTO mode is selected, the system is controlled by an ambient temperature sensor, a

    reflector temperature sensor, optic sensor for snow, 4x PT1000 sensors to measure the real value and

    the Rain/Snow Sensor Controller. Is the temperature below the ambient temperature and water is

    detected, the sat-nms Deice Controller will trigger the deice procedure.

    For example, snow is detected by the snow sensor, sub reflector heater and stage 1 with all

    Heater/Blowers selected turning on in 1-second intervals. The temperature slope shows the user during

    the heating phase the temperature slope in the main reflector in °C per min. This value compared with

    the corresponding threshold is used to select the number of used stages.

    The delay time will start after the snow sensor goes back to OFF. If the optic sensor detects no snow

    during the delay time the heaters are switched off prematurely.

  • © 2020, SatService GmbH www.satnms.com DEICE-APP-2020-02-20 6/7

    The next figure shows the control sequence of the air chamber temperature in the reflector.

    Output Circuits Connectors

    CON 4 and CON 5 refer to

    the photo-MOS outputs.

    CON 10, 11, 12, 13, 22, 23,

    24 and CON 25 are the 24V

    DC power relay outputs of

    the sat-nms Deice

    Controller.

    This figure shows how you

    connect the

    Blower/Heaters to the sat-

    nms Deice Controller. You

    have the possibility to

    control one Blower/Heater

    (blue line) or more than

    one (green line) with one

    output. K1, K2, and K3 are

    solid states with 24V DC

    input and 230V AC output.

    In parallel to the SNMP and HTTP interface the sat-nms Deice

    Controller provides at CON 16, for example, status and alarm contacts

  • © 2020, SatService GmbH www.satnms.com DEICE-APP-2020-02-20 7/7

    via general purpose relay outputs. This can be used for additional monitoring purposes.

    Input Circuits Connectors

    The sat-nms Deice Controller has 48 inputs (CON6, 7, 8,

    9, 18, 19, 20, 21, 10, 11, 12, 13, 22, 23, 24 and CON 25).

    Each input may be configured as a simple state

    monitor, signaling its state as ON/OFF, or as alarm

    input signaling its state as OK/FLT. The following figure

    gives an overview of the various ports.