BENTLY NEVADA SYSTEM 1® TIPS & TRICKS
November 2011, Volume 2, Issue 11
Dear System 1 User, In the November issue of System 1® Tips and Tricks we’ll show you how to set up spectral bands in System 1. Spectral bands are used to configure software alarms to help you detect specific problems or malfunctions. We hope you enjoy this issue. Sincerely, Your North America FAE team This month’s tip by: Michael Thevanh, Field Application Engineer, Sugar Land, TX
Versions: All Applies to: System 1 Tools
User Level: Power User Diagnostic User IT Group Mid Level User Occasional User New User
How to set up spectral bands in System 1
1 1. Open the System 1 configuration software and connect to the Enterprise. 2. Select the point you want to set the spectral bands for. You can select the point from the Enterprise view or from the Hierarchy. 3. Right click on the point and select “Properties”.
2 1. Select the “Variables” tab. 2. Select “Spectral Bands ” at the bottom of the page
3 Enable the band you want to configure (1-16), give it a name, select the type, set the bandwidth, center frequency, units, enable alarming, set the setpoint and finally the severity for the alarm. Click “OK” and save the Enterprise.
4 If you want to adjust the band frequencies or display scales (plot scales), you can select one of the buttons highlighted in green to make these changes.
1 - 16
5 Viewing the bands on a spectrum Plot: 1. Open System 1 Display
and connect to the enterprise.
2. Open the spectrum plot for the point you configured (right click on the point → Plots → Spectrum).
3. Right click on the plot and select “Configure”.
6 Select the “View” tab and Check the “Show Spectral Band Setpoints”. Click “OK” or “Apply”.
7 The two spectral bands we created are now shown on the spectrum plot (Sorry second one is a bit hard to see)
8 The spectral bands can be adjusted by right clicking on the plot and selecting the “Adjust Spectral Bands” option
9 Select the Band you want to reconfigure (in this case Pump Cavitation or Bearing Frequency), using the pulld down box. Enter the new Bandwidth, Center Frequency and Setpoint and click “Apply”
10
The next window pops up, showing the changes you made and the associated point in the hierarchy. Click “Save” to save the changes.
11
The adjusted Spectral band is now shown on the spectrum plot.
DID YOU KNOW? Orbit Magazine is now available as an iPad app. It’s an easy way for you to stay connected to the latest and greatest Bently Nevada technical content. You can download it from this link: http://www.ge-mcs.com/orbitipad
Bently Nevada Technical Support: [email protected] 775-215-1818
Bently Nevada website: http://www.ge-mcs.com/en/bently-nevada.html System 1 Blog (You’ll need to join the forum): http://supportcentral.ge.com/blog/blogs_frame.asp?prod_id=20858