    Copyright Siemens AG 2004 1

    Ergnzungsblatt/Supplementary Note Bestell-Nr./Order-No.: C53000X5674C1091

    Ein-/Ausgabebaugruppe C-I/O-2 ab Ausgabestand 7

    deutsch: Seite 2

    Hinweis:

    Dieses Gert enthlt eine neue Ein-/Ausgabebaugruppe C-I/O-2 mit Ausgabestand 7. Bittebeachten Sie, dass die Bezeichnungen einiger Steckbrcken sowie die Konfigurationsmg-lichkeit der Binrausgaben gegenber der Darstellung in lteren Gertehandbchern gen-dert wurden. Die Details sind in diesem Ergnzungsblatt beschrieben.

    Input/Output Board C-I/O-2 from Production State 7

    English: page 6

    Note:This device features a new input/output board C-I/O-2 from production state 7. Please notethat the designations of several jumpers and the configuration of binary outputs has changedcompared to older device manuals. The details are described in this supplementary note.

  • 7/25/2019 Supplementary Note C IO 2

    2/10

    2 C53000X5674C1091

    Allgemeines

    Es gibt von der Ein-/Ausgabebaugruppe C-I/O-2 ab Ausgabestand 7 zwei Bestckungsvarianten:

    Ausfhrung mit normaler ErdstromerfassungBaugruppennummer C53207-A324-B50-*

    Ausfhrung mit empfindlicher Erdstromerfassung

    Baugruppennummer C53207-A324-B60-*

    In einer auf der Leiterplatte aufgedruckten Tabelle (siehe Bild 1) ist die entsprechende Baugruppennummergekennzeichnet.

    Leiterplatte der Baugruppe

    In dem folgenden Bild ist die rumliche Lage der fr alle Einstellungen der Baugruppe bentigten Brcken dar-gestellt.

    Bild 1 Ein-/Ausgabebaugruppe C-I/O-2 ab Ausgabestand 7 mit Darstellung der fr die Kontrolle der Einstellungennotwendigen Brcken

  • 7/25/2019 Supplementary Note C IO 2

    3/10

  • 7/25/2019 Supplementary Note C IO 2

    4/10

    4 C53000X5674C1091

    Hinweis:

    Die Relais fr die Binrausgaben sind auf der Leiterplatte der Baugruppe mit K1 bis K8 bezeichnet.

    In den bersichtsplnen im Anhang der Gertehandbcher sind die zugehrigen Binrausgaben mit BA undeiner Ziffer bezeichnet, z.B. BA1. Die Ziffern knnen je nach Gertetyp unterschiedlich sein, d.h. dem RelaisK1 kann z.B. bei einem Gertetyp die Binrausgabe BA1 und bei einem anderen Gertetyp die Binrausgabe

    BA8 zugeordnet sein.Es gibt folgende Zuordnungen:

    K1: BA1 BA8 BA12K2: BA2 BA9 BA13K3: BA3 BA10 BA14K4: BA4 BA11 BA15K5: BA5 BA12 BA16K6: BA6 BA13 BA17K7: BA7 BA14 BA18K8: BA8 BA15 BA19

    Zuordnung der Binrausgaben zu den Gertetypen:

    BA1 bis BA8: 7SA6, 7UM62, 7UT613, 7UT63, 7VK61BA8 bis BA15: 7SA522, 7SD5, 7SD52BA12 bis BA19: 7UM61

    Das folgende Bild zeigt den Ausschnitt eines bersichtsplanes aus einem Gertehandbuch. In diesem Beispielsind den Relais K1 bis K8 die Binrausgaben BA8 bis BA15 zugeordnet.

    Bild 3 Ausschnitt eines bersichtsplanes (Beispiel)

    Strom-versorgung

    Q1Q2

    IL1

    Q7Q8

    I4

    Q3Q4

    IL2

    Q5

    Q6

    IL3

    R13R14

    U4

    R15R17

    UL1

    J11J12

    BE8

    UL2

    J3J4J6J5

    BE3BE4BE5

    K9

    K10

    BA4

    K6K7

    BA1BA2

    K1

    K2( )~

    +

    -

    R1R2

    BA8

    R3BA9

    BA10

    R11R12

    BA15

    R9R10

    BA14

    R7

    R8

    1 2

    3 2

    R18R16

    UL3

    K17K18

    BE1

    J1J2

    BE2

    J7J8

    BE6

    J9J10

    BE7

    K8K5

    BA3

    K11K12

    BA5

    K13K14

    BA6

    K15K16

    BA7

    R4R6

    BA11

    R5BA12

    Life-K3

    K4kontakt

    1 2

    3 2

    BA13

    R9

    R10

    1 2

    3 2

    BA14

    R11

    R12

    1 2

    3 2

    BA15

    R1R2

    BA8

    R3R4

    BA11

    R6R5

    BA12

    BA9BA10

    Zustzliche Einstellmglichkeiten

    R7

    R8

    1 2

    3 2

    BA13

    X43

    X42

    X41

    Auftrennung der gemeinsamenWurzel von BA8 bis BA12 mit

    den Brcken X80, X81, X82.

    1)

    Konfiguration der Binrausgaben1)

    der Baugruppe C-I/O-2 bis einschlielichAusgabestand 6 und Lieferstellung mit

    Umschalten von BA14, BA15als Schlieer oder ffner mitden Brcken X42, X43.

    C-I/O-2 ab Ausgabestand 7

    fr C-I/O-2 ab Ausgabestand 7:

  • 7/25/2019 Supplementary Note C IO 2

    5/10

    C53000X5674C1091 5

    Brckeneinstellungen

    Die Brcke X64 entfllt bei Ausfhrung mit empfindlicher Erdstromerfassung.

    *) Lieferzustand

    *) Lieferzustand

    Tabelle 1 Brckenstellung von Nennstrom bzw. Messbereich

    Brcke 7SA522, 7SA6, 7SD5, 7SD52, 7UT613, 7UT63, 7VK61 7UM61, 7UM62

    Nennstrom 1 AMessbereich 100 A

    Nennstrom 5 AMessbereich 500 A

    Nennstrom 1 AMessbereich 20 A

    Nennstrom 5 AMessbereich 100 A

    X51 12 12 12 12

    X60 12 23 12 23

    X61 35 45 25 35

    X62 35 45 25 35

    X63 35 45 25 35

    X64 35 45 25 35

    Tabelle 2 Brckenstellung fr die Konfiguration der Wurzelungvon K1 bis K5 (Lieferzustand) bzw. fr die Einstellungvon K1, K4 und K5 als Einzelrelais

    Brcke K1 bis K5 gewurzelt *) K1, K4, K5 als Einzelrelais(K2, K3 ohne Funktion)

    X80 12, 34 23, 45

    X81 12, 34 23, 45

    X82 23 12

    Tabelle 3 Brckenstellung fr die Kontaktartder Relais K6 bis K8

    fr Brcke Ruhestellung offen(Schlieer) *)

    Ruhestellung geschlossen(ffner)

    K6 X41 12 23

    K7 X42 12 23

    K8 X43 12 23

    Tabelle 4 Brckenstellung der Baugruppenadressen

    Brcke Lieferzustand

    X71 12 (H)

    X72 12 (H)

    X73 23 (L)

  • 7/25/2019 Supplementary Note C IO 2

    6/10

    6 C53000X5674C1091

    General

    From production state 7, the input/output board C-I/O-2 is available in two configuration variants:

    With normal earth current detectionPCB number C53207-A324-B50-*

    With sensitive earth current detection

    PCB number C53207-A324-B60-*

    A table imprinted on the printed-circuit board (see figure 4) indicates the respective PCB number.

    Printed Circuit Board

    The following figure shows the arrangement of the jumpers required for all PCB settings.

    Figure 4 Input-/output board C-I/O-2 from production state 7 with representation of the jumpers settings required forthe module configuration

    Pin-assignment for thejumpers X61 to X64

  • 7/25/2019 Supplementary Note C IO 2

    7/10

  • 7/25/2019 Supplementary Note C IO 2

    8/10

    8 C53000X5674C1091

    Note:

    The relays for the binary outputs are marked K1 to K8 on the printed-circuit board.

    The general diagrams in the Appendix of the device manuals indicate the associated binary outputs with BOand a number, e.g. BO1. The numbers may vary with device type, i.e. relay K1 may be assigned to binaryoutput BO1 in one device and to BO8 in another.

    The following assignments exist:K1: BO1 BO8 BO12K2: BO2 BO9 BO13K3: BO3 BO10 BO14K4: BO4 BO11 BO15K5: BO5 BO12 BO16K6: BO6 BO13 BO17K7: BO7 BO14 BO18K8: BO8 BO15 BO19

    Assignment of binary outputs to the device types:

    BA1 to BA8: 7SA6, 7UM62, 7UT613, 7UT63, 7VK61

    BA8 to BA15: 7SA522, 7SD5, 7SD52BA12 to BA19: 7UM61

    The following figure shows a section of a general diagram from a device manual. In the example, binary outputsBO8 to BO15 are assigned to the relays K1 to K8.

    Figure 6 Section of a general diagram (example)

    Powersupply

    Q1Q2

    IL1

    Q7Q8 I4

    Q3Q4

    IL2

    Q5Q6

    IL3

    R13R14

    U4

    R15R17

    UL1

    J11J12

    BI8

    UL2

    J3J4J6

    J5

    BI3BI4BI5

    K9K10

    BO4

    K6K7

    BO1BO2

    K1

    K2( )~

    +

    -

    R1R2

    BO8

    R3BO9

    BO10

    R11R12

    BO15

    R9R10BO14

    R7

    R8

    1 2

    3 2

    R18R16

    UL3

    K17K18

    BI1

    J1J2

    BI2

    J7J8

    BI6

    J9J10

    BI7

    K8K5

    BO3

    K11K12BO5

    K13K14

    BO6

    K15K16

    BO7

    R4R6

    BO11

    R5BO12

    LifeK3

    K4contact

    1 2

    3 2

    BO13

    R9R10

    1 2

    3 2BO14

    R11

    R12

    1 2

    3 2

    BO15

    R1R2

    BO8

    R3R4

    BO11

    R6R5

    BO12

    BO9BO10

    R7

    R8

    1 2

    3 2

    BO13

    X43

    X42

    X41

    Splitting the common rootof BO8 to BO12 using jumpersX80, X81, X82.

    1)

    Configuration of binary outputs1)

    of board C-I/O-2 up to includingproduction state 6 and delivery position

    Switchover of BO14, BO15as NO contact or NC contactwith the jumpers X42, X43.

    with C-I/O-2 from production state 7

    Additional settings for C-I/O-2from production state 7:

  • 7/25/2019 Supplementary Note C IO 2

    9/10

    C53000X5674C1091 9

    Jumper Settings

    There is no jumper X64 for the version with sensitive earth current input.

    *) Presetting

    *) Presetting

    Table 5 Jumper setting for nominal current and measuring range

    Jumper 7SA522, 7SA6, 7SD5, 7SD52, 7UT613, 7UT63, 7VK61 7UM61, 7UM62

    Nominal current 1 AMeasuring range 100 A

    Nominal current 5 AMeasuring range 500 A

    Nominal current 1 AMeasuring range 20 A

    Nominal current 5 AMeasuring range 100 A

    X51 12 12 12 12

    X60 12 23 12 23

    X61 35 45 25 35

    X62 35 45 25 35

    X63 35 45 25 35

    X64 35 45 25 35

    Table 6 Jumper setting for the configuration of K1 to K5 with common connection(presetting) and of K1, K4, K5isolated

    Jumper K1 to K5with common connection *)

    K1, K4, K5 isolated(K2, K3 without function)

    X80 12, 34 23, 45

    X81 12, 34 23, 45

    X82 23 12

    Table 7 Jumper setting for the contact mode of K6 to K8

    for Jumper Quiescent state open(NO contact) *)

    Quiescent state closed(NC contact)

    K6 X41 12 23

    K7 X42 12 23

    K8 X43 12 23

    Table 8 Jumper setting of printing circuit board addresses

    Jumper Presetting

    X71 12 (H)

    X72 12 (H)

    X73 23 (L)

  • 7/25/2019 Supplementary Note C IO 2

    10/10

    SIEMENS AKTIENGESELLSCHAFT Bestell-Nr./Order-No.: C53000X5674C1091Bestellort/Available from: PTD PA Bln W5Printed in Germany/Imprim en Allemagne

    AG 0404 0.1 -- 10 De-En

    Weitergabe sowie Vervielfltigung dieser Unterlage, Ver-wertung und Mitteilung ihres Inhalts nicht gestattet, soweitnicht ausdrcklich zugestanden. Zuwiderhandlungen ver-pflichten zu Schadenersatz. Alle Rechte fr den Fall derPatenterteilung oder GM-Eintragung vorbehalten.

    Copying this document and giving it to others and the useor communication of the contents thereof, are forbiddenwithout express authority. Offenders are liable to the pay-ment of damages. All Rights are reserved in the event ofthe grant of a patent or registration of a utility model ordesign.

    nderungen vorbehalten

    Subject to technical alteration