Supplementary Note C IO 2
Transcript of Supplementary Note C IO 2
-
7/25/2019 Supplementary Note C IO 2
1/10
Copyright Siemens AG 2004 1
Ergnzungsblatt/Supplementary Note Bestell-Nr./Order-No.: C53000X5674C1091
Ein-/Ausgabebaugruppe C-I/O-2 ab Ausgabestand 7
deutsch: Seite 2
Hinweis:
Dieses Gert enthlt eine neue Ein-/Ausgabebaugruppe C-I/O-2 mit Ausgabestand 7. Bittebeachten Sie, dass die Bezeichnungen einiger Steckbrcken sowie die Konfigurationsmg-lichkeit der Binrausgaben gegenber der Darstellung in lteren Gertehandbchern gen-dert wurden. Die Details sind in diesem Ergnzungsblatt beschrieben.
Input/Output Board C-I/O-2 from Production State 7
English: page 6
Note:This device features a new input/output board C-I/O-2 from production state 7. Please notethat the designations of several jumpers and the configuration of binary outputs has changedcompared to older device manuals. The details are described in this supplementary note.
-
7/25/2019 Supplementary Note C IO 2
2/10
2 C53000X5674C1091
Allgemeines
Es gibt von der Ein-/Ausgabebaugruppe C-I/O-2 ab Ausgabestand 7 zwei Bestckungsvarianten:
Ausfhrung mit normaler ErdstromerfassungBaugruppennummer C53207-A324-B50-*
Ausfhrung mit empfindlicher Erdstromerfassung
Baugruppennummer C53207-A324-B60-*
In einer auf der Leiterplatte aufgedruckten Tabelle (siehe Bild 1) ist die entsprechende Baugruppennummergekennzeichnet.
Leiterplatte der Baugruppe
In dem folgenden Bild ist die rumliche Lage der fr alle Einstellungen der Baugruppe bentigten Brcken dar-gestellt.
Bild 1 Ein-/Ausgabebaugruppe C-I/O-2 ab Ausgabestand 7 mit Darstellung der fr die Kontrolle der Einstellungennotwendigen Brcken
-
7/25/2019 Supplementary Note C IO 2
3/10
-
7/25/2019 Supplementary Note C IO 2
4/10
4 C53000X5674C1091
Hinweis:
Die Relais fr die Binrausgaben sind auf der Leiterplatte der Baugruppe mit K1 bis K8 bezeichnet.
In den bersichtsplnen im Anhang der Gertehandbcher sind die zugehrigen Binrausgaben mit BA undeiner Ziffer bezeichnet, z.B. BA1. Die Ziffern knnen je nach Gertetyp unterschiedlich sein, d.h. dem RelaisK1 kann z.B. bei einem Gertetyp die Binrausgabe BA1 und bei einem anderen Gertetyp die Binrausgabe
BA8 zugeordnet sein.Es gibt folgende Zuordnungen:
K1: BA1 BA8 BA12K2: BA2 BA9 BA13K3: BA3 BA10 BA14K4: BA4 BA11 BA15K5: BA5 BA12 BA16K6: BA6 BA13 BA17K7: BA7 BA14 BA18K8: BA8 BA15 BA19
Zuordnung der Binrausgaben zu den Gertetypen:
BA1 bis BA8: 7SA6, 7UM62, 7UT613, 7UT63, 7VK61BA8 bis BA15: 7SA522, 7SD5, 7SD52BA12 bis BA19: 7UM61
Das folgende Bild zeigt den Ausschnitt eines bersichtsplanes aus einem Gertehandbuch. In diesem Beispielsind den Relais K1 bis K8 die Binrausgaben BA8 bis BA15 zugeordnet.
Bild 3 Ausschnitt eines bersichtsplanes (Beispiel)
Strom-versorgung
Q1Q2
IL1
Q7Q8
I4
Q3Q4
IL2
Q5
Q6
IL3
R13R14
U4
R15R17
UL1
J11J12
BE8
UL2
J3J4J6J5
BE3BE4BE5
K9
K10
BA4
K6K7
BA1BA2
K1
K2( )~
+
-
R1R2
BA8
R3BA9
BA10
R11R12
BA15
R9R10
BA14
R7
R8
1 2
3 2
R18R16
UL3
K17K18
BE1
J1J2
BE2
J7J8
BE6
J9J10
BE7
K8K5
BA3
K11K12
BA5
K13K14
BA6
K15K16
BA7
R4R6
BA11
R5BA12
Life-K3
K4kontakt
1 2
3 2
BA13
R9
R10
1 2
3 2
BA14
R11
R12
1 2
3 2
BA15
R1R2
BA8
R3R4
BA11
R6R5
BA12
BA9BA10
Zustzliche Einstellmglichkeiten
R7
R8
1 2
3 2
BA13
X43
X42
X41
Auftrennung der gemeinsamenWurzel von BA8 bis BA12 mit
den Brcken X80, X81, X82.
1)
Konfiguration der Binrausgaben1)
der Baugruppe C-I/O-2 bis einschlielichAusgabestand 6 und Lieferstellung mit
Umschalten von BA14, BA15als Schlieer oder ffner mitden Brcken X42, X43.
C-I/O-2 ab Ausgabestand 7
fr C-I/O-2 ab Ausgabestand 7:
-
7/25/2019 Supplementary Note C IO 2
5/10
C53000X5674C1091 5
Brckeneinstellungen
Die Brcke X64 entfllt bei Ausfhrung mit empfindlicher Erdstromerfassung.
*) Lieferzustand
*) Lieferzustand
Tabelle 1 Brckenstellung von Nennstrom bzw. Messbereich
Brcke 7SA522, 7SA6, 7SD5, 7SD52, 7UT613, 7UT63, 7VK61 7UM61, 7UM62
Nennstrom 1 AMessbereich 100 A
Nennstrom 5 AMessbereich 500 A
Nennstrom 1 AMessbereich 20 A
Nennstrom 5 AMessbereich 100 A
X51 12 12 12 12
X60 12 23 12 23
X61 35 45 25 35
X62 35 45 25 35
X63 35 45 25 35
X64 35 45 25 35
Tabelle 2 Brckenstellung fr die Konfiguration der Wurzelungvon K1 bis K5 (Lieferzustand) bzw. fr die Einstellungvon K1, K4 und K5 als Einzelrelais
Brcke K1 bis K5 gewurzelt *) K1, K4, K5 als Einzelrelais(K2, K3 ohne Funktion)
X80 12, 34 23, 45
X81 12, 34 23, 45
X82 23 12
Tabelle 3 Brckenstellung fr die Kontaktartder Relais K6 bis K8
fr Brcke Ruhestellung offen(Schlieer) *)
Ruhestellung geschlossen(ffner)
K6 X41 12 23
K7 X42 12 23
K8 X43 12 23
Tabelle 4 Brckenstellung der Baugruppenadressen
Brcke Lieferzustand
X71 12 (H)
X72 12 (H)
X73 23 (L)
-
7/25/2019 Supplementary Note C IO 2
6/10
6 C53000X5674C1091
General
From production state 7, the input/output board C-I/O-2 is available in two configuration variants:
With normal earth current detectionPCB number C53207-A324-B50-*
With sensitive earth current detection
PCB number C53207-A324-B60-*
A table imprinted on the printed-circuit board (see figure 4) indicates the respective PCB number.
Printed Circuit Board
The following figure shows the arrangement of the jumpers required for all PCB settings.
Figure 4 Input-/output board C-I/O-2 from production state 7 with representation of the jumpers settings required forthe module configuration
Pin-assignment for thejumpers X61 to X64
-
7/25/2019 Supplementary Note C IO 2
7/10
-
7/25/2019 Supplementary Note C IO 2
8/10
8 C53000X5674C1091
Note:
The relays for the binary outputs are marked K1 to K8 on the printed-circuit board.
The general diagrams in the Appendix of the device manuals indicate the associated binary outputs with BOand a number, e.g. BO1. The numbers may vary with device type, i.e. relay K1 may be assigned to binaryoutput BO1 in one device and to BO8 in another.
The following assignments exist:K1: BO1 BO8 BO12K2: BO2 BO9 BO13K3: BO3 BO10 BO14K4: BO4 BO11 BO15K5: BO5 BO12 BO16K6: BO6 BO13 BO17K7: BO7 BO14 BO18K8: BO8 BO15 BO19
Assignment of binary outputs to the device types:
BA1 to BA8: 7SA6, 7UM62, 7UT613, 7UT63, 7VK61
BA8 to BA15: 7SA522, 7SD5, 7SD52BA12 to BA19: 7UM61
The following figure shows a section of a general diagram from a device manual. In the example, binary outputsBO8 to BO15 are assigned to the relays K1 to K8.
Figure 6 Section of a general diagram (example)
Powersupply
Q1Q2
IL1
Q7Q8 I4
Q3Q4
IL2
Q5Q6
IL3
R13R14
U4
R15R17
UL1
J11J12
BI8
UL2
J3J4J6
J5
BI3BI4BI5
K9K10
BO4
K6K7
BO1BO2
K1
K2( )~
+
-
R1R2
BO8
R3BO9
BO10
R11R12
BO15
R9R10BO14
R7
R8
1 2
3 2
R18R16
UL3
K17K18
BI1
J1J2
BI2
J7J8
BI6
J9J10
BI7
K8K5
BO3
K11K12BO5
K13K14
BO6
K15K16
BO7
R4R6
BO11
R5BO12
LifeK3
K4contact
1 2
3 2
BO13
R9R10
1 2
3 2BO14
R11
R12
1 2
3 2
BO15
R1R2
BO8
R3R4
BO11
R6R5
BO12
BO9BO10
R7
R8
1 2
3 2
BO13
X43
X42
X41
Splitting the common rootof BO8 to BO12 using jumpersX80, X81, X82.
1)
Configuration of binary outputs1)
of board C-I/O-2 up to includingproduction state 6 and delivery position
Switchover of BO14, BO15as NO contact or NC contactwith the jumpers X42, X43.
with C-I/O-2 from production state 7
Additional settings for C-I/O-2from production state 7:
-
7/25/2019 Supplementary Note C IO 2
9/10
C53000X5674C1091 9
Jumper Settings
There is no jumper X64 for the version with sensitive earth current input.
*) Presetting
*) Presetting
Table 5 Jumper setting for nominal current and measuring range
Jumper 7SA522, 7SA6, 7SD5, 7SD52, 7UT613, 7UT63, 7VK61 7UM61, 7UM62
Nominal current 1 AMeasuring range 100 A
Nominal current 5 AMeasuring range 500 A
Nominal current 1 AMeasuring range 20 A
Nominal current 5 AMeasuring range 100 A
X51 12 12 12 12
X60 12 23 12 23
X61 35 45 25 35
X62 35 45 25 35
X63 35 45 25 35
X64 35 45 25 35
Table 6 Jumper setting for the configuration of K1 to K5 with common connection(presetting) and of K1, K4, K5isolated
Jumper K1 to K5with common connection *)
K1, K4, K5 isolated(K2, K3 without function)
X80 12, 34 23, 45
X81 12, 34 23, 45
X82 23 12
Table 7 Jumper setting for the contact mode of K6 to K8
for Jumper Quiescent state open(NO contact) *)
Quiescent state closed(NC contact)
K6 X41 12 23
K7 X42 12 23
K8 X43 12 23
Table 8 Jumper setting of printing circuit board addresses
Jumper Presetting
X71 12 (H)
X72 12 (H)
X73 23 (L)
-
7/25/2019 Supplementary Note C IO 2
10/10
SIEMENS AKTIENGESELLSCHAFT Bestell-Nr./Order-No.: C53000X5674C1091Bestellort/Available from: PTD PA Bln W5Printed in Germany/Imprim en Allemagne
AG 0404 0.1 -- 10 De-En
Weitergabe sowie Vervielfltigung dieser Unterlage, Ver-wertung und Mitteilung ihres Inhalts nicht gestattet, soweitnicht ausdrcklich zugestanden. Zuwiderhandlungen ver-pflichten zu Schadenersatz. Alle Rechte fr den Fall derPatenterteilung oder GM-Eintragung vorbehalten.
Copying this document and giving it to others and the useor communication of the contents thereof, are forbiddenwithout express authority. Offenders are liable to the pay-ment of damages. All Rights are reserved in the event ofthe grant of a patent or registration of a utility model ordesign.
nderungen vorbehalten
Subject to technical alteration