Strength and Deformability of High Strength R.C Columns Subjected to Eccentric Loading · 2017. 11....
Transcript of Strength and Deformability of High Strength R.C Columns Subjected to Eccentric Loading · 2017. 11....
-
1
Strength and Deformability of High Strength R.C Columns Subjected to
Eccentric Loading
Yasser Mahmuod Mohammad 1, Zainab E. Abd El-Shafy
2,
Kamal A. Assaf3 and Yehia A. Hassanean
4
Abstract:
The use of high-strength concrete (HSC) has been widely accepted by designers and contractors in
reinforced concrete structures, especially heavily loaded column of high-rise building and bridges.
To study the strength and deformability of HSC columns subjected to eccentric loading, nine
columns were tested under eccentric loading and one column only was tested under axial loading.
The investigated parameters were concrete compressive strength, slenderness and rectangularity
ratios, and load eccentricity. The concrete compressive strength ranged from 36.0 to 75.0 MPa
and the slenderness ratio was ranged from 6.67 to 10.0 while the considered eccentricities ratios
ranged from 0.0 to 0.80. Also, comparison between experimental and analytical study was carried.
The results indicated that increasing concrete compressive strength resulted in increasing the
column strength capacity. While increasing the eccentricity are resulted in decreasing the column
strength capacity. Also the comparison between experimental and analytical study indicated that
both ACI 318R-14 and ECP 203-07 codes are acceptable and valid to determine both the load and
the moment capacity of such columns subjected to eccentric loading if take into consideration the
additional moment induced due to column deformations.
Keywords: High Strength Concrete HSC; R.C Columns; Eccentric Loading; Strength; Deformability; Stress-Strain Curves.
Introduction
One of the advantages of using HSC in columns is that it allows smaller size columns cross-
section; thus, providing more floor space and reducing cost of formwork. ACI committee 363R-92
[2], defined high strength concrete as a concrete strength of 41 MPa or greater. Now more recently,
compressive strengths approaching 138 MPa have been used [2]. Many experimental and
analytical researches have been carried out to study the effect of different parameters on the
behavior and deformability of HSC columns under eccentric loading. Previous studies [9], [10],
[11], [12] and [16] reported that:
a. Mode of failure of HSC columns was typically flexure with concrete spalling in the compression zone.
b. Increasing the concrete compressive strength could increase the capacity of the reinforced HSC columns; however, it could significantly decrease the ductility and deformability of the
columns.
c. As the eccentricity increases, the columns give more ductile behavior while columns capacity decreases.
d. Increasing transverse volumetric ratio, decreasing both tie spacing and tie yield strength and tie configuration are very effective in increasing capacity and ductility of HSC columns.
1Civil Engineering Dept, Al.Azhar University, Qena branch. E-mail: [email protected]
2Lectturer of Structural Engineering Civil Eng. Department Faculty of Engineering Assiut University. Assiut 71516,
Egypt. E-mail: [email protected] 3 Associated Prof. of Structural Eng, Civil Eng. Dept., Faculty of Eng. Assiut University,.
4Prof. of Reinforced Concrete, Civil Eng. Dept., Faculty of Eng. Assiut University, E-mail: [email protected].
-
2
e. Increasing longitudinal reinforcement ratio and yield strength of main steel had a little effect on capacity and ductility of confined HSC columns.
f. Concrete cover spalling zone tended to be larger as concrete compressive strength and steel ratio increased, also as slenderness ratio and initial eccentricity decreased.
Abo Eleineen et al, [1], carried out an experimental and analytical program to study the general
deformational behavior of eccentrically loaded high performance concrete columns and concluded
that the ductility and the failure strain of high performance concrete are lower than those of normal
strength concrete. Canbay et al, [6] and Husem et al, [12] reported that the ultimate strength
calculated by using ACI equivalent rectangular stress block over estimates the capacity of high
strength concrete columns but the capacities calculated using CSA A23.3 stress block agree better
with the experimental results. Nadaf and Biradar [7], also reported that HSC columns tended
towards brittleness leading less deflection at mid height. Also, decreasing the spacing of lateral ties
at both the ends up to certain distance influenced the resistance to the shear generated by uniaxial
loading. Foster [14], studied the spalling of the concrete cover of HSC columns with high-axial
loads applied at small eccentricity and concluded that only one way to prevent early spalling of the
cover and to improve the ductility is to add steel fibers to concrete mixture. Antonius [4], tested
twelve HSC columns to study the effect of confinement on high-strength columns subjected to
eccentric loading and to develop stress-strain analytical model and concluded that the ductility of
reinforced concrete columns depended on the confinement provided by the lateral reinforcement
and the strength enhancement of concrete tended to associated with less ductility and more
brittleness for the failure.
1. Experimental program
Experimental program of this work was consisted of ten HSC columns with cross section of
150×150 mm, 150×200 mm and 150×250 mm and overall height of 1000 mm, 1250 mm and 1500
mm with two end cantilevers to apply eccentricity and prevent boundary effects. Columns
longitudinal reinforcement was 6Ф10 mm and lateral reinforcement of 1 Ø 8/150 mm. Three
different strengths of concrete with target compressive strength of 36, 60 and 75 MPa were used.
All tested columns have concrete cover of 25 mm. Columns were tested under eccentric loading
with eccentricity ratio, e/t = 0, 0.2, 0.5 and 0.8. The tested reference column R and Nine columns
were arranged in four groups B, C, D and E as presented in table No. 1. Also complete details of
specimens were shown in Figure (1).
2. Material Properties Concrete mixes were designed to produce concrete target cubic concrete compressive strength of
36, 60 and 75 MPa. The properties of the material used in the mixes were as follows:
Cement: Ordinary Portland cement with chemical, physical and mechanical properties complied with Egyptian Standard Specifications E.S.S.
Coarse aggregate: The coarse aggregate used in normal-strength concrete was local gravel of 20 mm maximum nominal size, 2.65 specific gravity and 1.67 t/m
3 volume weight. The coarse
aggregate used in high-strength concrete was crushed basalt of 20 mm maximum nominal size, 2.7
specific gravity and 2.35 t/m3 volume weight.
Fine aggregate: The fine aggregate used was local natural siliceous sand with 2.60, 1.58 and 2.58 specific gravity, volume weight and fineness modules respectively.
Water: Drinking water was used for mixing and curing.
-
3
Silica fume: Silica fume was used in producing high-strength concrete specimens with average particle size of 0.1µm, the specific surface area is (12 – 15m
2/g) and the specific gravity is 2.2.
Superplasticizer: High-range-water-reducing admixture (HRWRA) was added to concrete composites to improve workability without increasing water content. Product density is 1.21t/m
3
and for doses about 3% by weight of cement content.
Steel reinforcement: Longitudinal reinforcement steel was deformed bars of high tensile steel with diameter of 10 mm, while lateral reinforcement steel were plain bars of normal mild steel
with diameter of 8 mm.
Tables (2) and (3) are summarized the concrete mix proportions and mechanical properties of the
used steel.
Table (1): Details of the tested columns
Group Column
No. As
b
mm
t
mm e/t
fcu (MPa)
t/b h/b Ties / Spacing
(mm)
R R 6Ф10 150 250 0.0 75 1.66 10.0 1 Ø 8/150
B
A2 6Ф10 150 250 0.5 75 1.66 10.0 1 Ø 8/150
B1 6Ф10 150 150 0.5 75 1.00 10.0 1 Ø 8/150
B2 6Ф10 150 200 0.5 75 1.33 10.0 1 Ø 8/150
C C1 6Ф10 150 250 0.2 75 1.66 10.0 1 Ø 8/150
C2 6Ф10 150 250 0.8 75 1.66 10.0 1 Ø 8/150
D D1 6Ф10 150 250 0.5 36 1.66 10.0 1 Ø 8/150
D2 6Ф10 150 250 0.5 60 1.66 10.0 1 Ø 8/150
E E1 6Ф10 150 250 0.5 75 1.66 6.67 1 Ø 8/150
E2 6Ф10 150 250 0.5 75 1.66 8.33 1 Ø 8/150
fcu Target cubic concrete compressive strength.
As Longitudinal reinforcement.
b Breadth of column cross-section.
t Depth of column cross-section.
h Column height
e Load eccentricity.
Table (2): Mix by weight for the different mixes.
Mix
No.
Amount of constituent materials/m3
fcu
MPa Cement
(kg)
Aggregate (kg) Water
(Liter)
Silica fume
(kg)
HRWRA
(kg) Sand Gravel Basalt
1 450 610 1220 ------- 175 --- -- 36
2 500 600 ----- 1200 155 75 12 60
3 550 570 ----- 1140 145 90 16 75
Table (3): Mechanical properties of the used steel
Commercial diameter in mm 6 8 10 12
Yield strength in MPa 299.4 242.0 617.5 512.1
Ultimate strength in MPa 445.9 398.0 719.4 673.9
Elongation % 30.00 26.0 11.0 12.0
Grade according to ECP203 280/450 240/350 400/600 400/600
-
4
Figure (1): Details of the tested Columns.
-
5
3. Fabrication of the tested columns
This program was carried out in the R.C. laboratory at Assiut University. The mixing of
constituent materials was achieved by means of horizontal pan mixer of 0.1 m3 capacity. For
normal-strength concrete, the dry aggregates and cement were first mixed for one minute, then; the
water was added and mixing was continued for two minutes. The same steps were followed for
HSC, where the dry aggregates, cement and silica fume were mixed for one minute, then the
HRWRA was added to the water and poured it gradually and mixing was continued for two
minutes. All columns were cast vertically in steel forms. Before casting, the interior faces of the
form were greased to facilitate the extraction of concrete columns. Casting of concrete was done in
layers, where each layer was compacted with an electrical internal rod vibrator. For all columns,
the time of mixing and the method of compaction were held constant. Concrete samples of three
cubes 15cm side length were cast with each column at the same time. The measured slump for mix
no. 1 was 65 mm, while mixes no.2 and 3 were wet and sloppy due to its content of HRWRA. The
columns and cubes were sprayed with fresh water two times per day until 28 days from casting.
Electrical resistance strain gauges were mounted on the reinforcing bars at the proposed position
before casting. The gauges were covered with a water-tight material to protect strain gauges
against moisture.
4. Test set up and procedure
All columns were white painted one day before testing to facilitate cracks observations during
loading test. Deformations of the longitudinal reinforcement steel were measured by electrical-
resistance strain gauges. Two adjacent longitudinal steel bars were instrumented at the middle
height by two electrical strain gauges which glued and isolated to protect it before casting .To
measure concrete deformations; one electrical strain gauge was instrumented on expected
compression side at the mid-height of specimens to predict strains in compression zone. All strain
gauges were connected to a digital strain indicator to collect readings at different loading stages.
Longitudinal displacement was measured using a dial gauge with an accuracy of 0.01mm fixed on
bottom head of the testing machine. Also lateral deformations were measured by two dial gauges
fixed on two adjacent sides of specimens at the mid-height region. To apply eccentricity, load was
applied with two special roller bearing systems to ensure eccentricity on specimens. Column was
placed between heads of compression machine and adjusted the assembly roller bearing system on
the top and bottom of tested column to control eccentricities. Load was applied with a constant
increment of 5 ton for each load level up to failure and was kept constant for about three minutes.
During this period, reading of electrical strain gauges of steel and concrete strains, dial gauges.
Also cracks width and the cracks propagation were recorded at the beginning and end of each
increment of loading.
5. General Behavior and Mode of Failure of Tested Columns
Due to big eccentricity applied on the tested columns, first crack initiated prematurely. For all
tested column under eccentric loading the first crack initiated horizontally at mid height of the
tension side. By increasing load, the width of first crack increased and other horizontally cracks
initiated parallel to first crack along the tension side of the tested columns. Subsequently, by
increasing load, all these cracks had trended towards compression side in horizontal direction till it
reached to the neutral axis of cross-section then it moved in inclined direction. Before failure
occurred; vertical cracks appeared suddenly at mid third or close to mid third of compression side
for columns A2, B1, C1, D1 and E1. The vertical cracks are appeared at upper third of
compression side for column B2, D2, E2 and, R while these cracks were appeared at lower third of
-
6
compression side for column C2 till failure took place. Failure was associated with separated of
concrete cover in compression zone for. Figures (2 and 3) showed Failure mode and pattern of
cracks of tested column. Table (4) summarized test results for tested columns.
Column (A2) Column (B1) Column (B2) Column (C1) Column (C2)
Column (D1) Column (D2) Column (E1) Column (E2) Column (R)
Figure (2): Failure Mode and Pattern of Cracks for Tested Columns.
Figure (3): Crack zones of the tested columns.
-
7
Table (4): Test Results
Group
No.
Column
No. 𝑓𝑐ˋ
(Mpa)
ei
(mm)
△fail efail (mm)
Pcr
(KN)
Pult
(KN)
Mult
(KN.m) △1
(mm)
△2 (mm)
R R 63.2 0 17.1 13.6 0 1600 1950 0
B
A2 64.3 125 25.5 6.55 143.95 50 500 71.975
B1 63.5 75 27.4 5.00 97.40 50 300 29.22
B2 64.8 100 26.6 5.60 121.00 50 450 54.45
C C1 64.40 50 21.2 10.70 60.50 600 1050 63.525
C2 64.7 200 41.8 3.55 238.25 40 260 61.945
D D1 28.92 125 27.3 7.70 144.60 50 250 36.15
D2 52.7 125 26.5 6.80 144.70 50 450 65.11
E E1 64.6 125 20.7 8.10 137.6 200 600 82.56
E2 64.5 125 24.8 7.40 142.4 100 550 78.32
Where:
𝑓𝑐ˋ : Cylinder concrete compressive strength (MPa).
ei : Initial load eccentricity (mm).
Mult : Failure moment (KN.m)
△fail : Deflection at Pult (mm). Pcr : Cracking load (KN).
Pult : Failure load (KN).
efail = ei + △fail (mm). △1 : Mid-height axial displacement (mm). △2 : Mid-height lateral displacement (mm).
6. Discussion of test results 6.1 : Cracking and Ultimate loads:
The relation between both the cracking and ultimate loads, and the studied parameters are plotted
in Figure (4.a) to Figure (4.d). The cracking load is not affected by both rectangularity of the
column cross-section and concrete compressive strengths but pronounced effect is observed due to
increase of the load eccentricity. Increasing of load eccentricity ratio from 0.0 to 0.80 is leads to
decrease the cracking load by 97.5 %. The decreasing of cracking load this is may be due to the
higher tensile stresses induced due to higher induced bending moment. Also, the higher
slenderness ratio meets low cracking load this is may be due to the higher values of added bending
moment. Increasing the slenderness ratio from 6.33 to 10.0 is decreasing the cracking load by
75%.
The same behavior is almost observed for the affects of the studied parameters on the ultimate
loads. Increasing rectangularity ratio from 1 to 1.67 resulted in increasing column load capacity
with 67% as shown in Figure (4.a). Also, increasing load eccentricity ratio from zero to 0.8 of
column thickness led to decrease load capacity by 87%, as shown in figure (4.b). This is due to the
higher tensile stresses induced due to higher induced bending moment. Figure (4.c) indicated that
increasing concrete compressive strength (𝑓𝑐ˋ) from 30 MPa to 64.0 MPa resulted in increasing
column capacity by 100%. Also increasing slenderness ratio from 6.67 to 10.0 is leads to decrease
the load capacity 16.67% as shown in Figure (4.d).
-
8
Figure (4-a): Effect of rectangularity ratio on ultimate and cracking
load.
Figure (4-b): Effect of load eccentricity on ultimate and cracking load.
Figure (4-c): Effect of concrete compressive strength on ultimate and
cracking load. Figure (4-d): Effect of slenderness ratio on ultimate and cracking load.
6.2 Maximum Mid-height Deformations:
Both rectangularity ratio and concrete compressive strength have slightly affected on the
maximum axial mid-height displacements of the tested columns. Increasing rectangularity ratio
from 1.0 to 1.67 resulted in decreasing mid-height displacement by 7%. This reduction is due to
increase column dimension in the direction of load eccentricity. Likewise increasing concrete
compressive strength from 29.0 MPa to 64.0 MPa resulted in decreasing maximum axial mid-
height displacement 6.6%. On the other hand load eccentricity has pronounced affect on the
maximum axial mid-height displacement. As the load eccentricity increased from zero to 0.8 of
column thickness leads to increase in maximum axial mid-height displacement by 144% this could
be attributed to the increase in moment acting on tested columns. Furthermore, increasing
slenderness ratio from 6.67 to 10 led to increase maximum axial mid-height displacement by
23.19%. Figure (5.a) to Figure (5.d) show the effect of the investigated parameters on the
maximum axial mid-height displacements.
B1
B2A2
B1 B2 A2
0
100
200
300
400
500
600
0.5 1 1.5 2
Load
(K
N)
Rectangularity ratio (t/b)%
Ultimate Load
Cracking Load
C2
A2
C1
R
C2A2C1
R
0
500
1000
1500
2000
2500
0 0.2 0.4 0.6 0.8 1
Load
(K
N)
Load Eccentricity ratio (e/t)%
Ultimate Load
Cracking Load
D1
D2A2
D1 D2 A2
0
100
200
300
400
500
600
20 30 40 50 60 70
Load
(K
N)
Concrete Compressive Strength (fcˋ)
Ultimate Load
Cracking Load
E2 E2A2
E2
E1A2
0
100
200
300
400
500
600
700
5 6 7 8 9 10 11L
oad
(K
N)
Slenderness ratio (h/b)%
Ultimate Load
Cracking Load
-
9
Figure (5-a): Effect of rectangularity ratio on mid-height displacement. Figure (5-b): Effect of load eccentricity on axial mid-height
displacement.
Figure (5-c): Effect of concrete compressive strength on axial mid-height
displacement. Figure (5-d): Effect of slenderness ratio on axial mid-height
displacement.
On other hand maximum mid-height lateral displacement is increased by 31% when the
rectangularity ratio increased from 1.0 to 1.67. Also, decreasing in maximum lateral displacement
by 73.9% is observed when the load eccentricity increased from zero to 0.8 of column thickness.
Also, the maximum mid-height lateral displacement is decreasing by 15% , when concrete
compressive strength increase from 29.0 MPa to 64.0 MPa because of HSC columns are behave
more brittle than those of NSC. On the other hand, increasing slenderness ratio from 6.67 to 10
resulted in decreasing in maximum mid-height lateral displacement by 19.1%; this is because of
column with small slenderness ratio failed in brittle manner with compression failure mode
causing large lateral displacement. Figures from (6-a) to (6-d) illustrated the effect of investigated
parameters on lateral mid-height displacement.
Figure (6-a): Effect of rectangularity ratio on lateral mid-height
displacement.
Figure (6-b): Effect of load eccentricity on lateral mid-height
displacement.
0
100
200
300
400
500
600
0 5 10 15 20 25 30
Lo
ad
(K
N)
Axial Mid-hieght Displacement (mm).
B1, t/b=1
B2, t/b=1.33
A2, t/b=1.67 0
500
1000
1500
2000
2500
0 10 20 30 40 50
Lo
ad
(K
N)
Axial Mid-hieght Displacement (mm).
C1, e/t = 0.2
C2, e/t = 0.8
A2, e/t = 0.5
R, e/t = 0
0
100
200
300
400
500
600
0 5 10 15 20 25 30
Lo
ad
(K
N)
Axial Mid-hieght Displacement (mm).
D1, fc' = 31.09 MPaD2, fc' =52.68 MPaA2, fc' = 64.28 MPa
0
200
400
600
800
0 5 10 15 20 25 30L
oa
d (
KN
)
Axial Mid-hieght Displacement (mm).
E1, h/b = 6.67
E2, h/b = 8.33
A2, h/b = 10
0
100
200
300
400
500
600
0 2 4 6 8
Lo
ad
(K
N)
Lateral Mid-hieght Displacement (mm).
B1, t/b=1
B2, t/b=1.33
A2, t/b=1.670
500
1000
1500
2000
2500
0 5 10 15
Lo
ad
(K
N)
Lateral Mid-hieght Displacement (mm).
C1, e/t = 0.2
C2, e/t = 0.8
A2, e/t = 0.5
R, e/t = 0
-
10
Figure (6-c): Effect of concrete compressive strength on lateral mid-
height displacement.
Figure (6-d): Effect of slenderness ratio on lateral mid-height
displacement.
6.3 Ultimate Induced Strains
Figures from (7-a) to (9-d) illustrated relation between ultimate mid-height induced strains in both
concrete and steel and investigated parameters. Both concrete compressive strain and steel
compression strain are almost having the same observed behavior of mid-height displacements.
Where increase rectangularity ratio or load eccentricity led to increase both concrete compressive
strain and steel compression strain. On other hand increase concrete compressive strength or
slenderness ratio decrease both concrete compressive strain and steel compression strain.
Likewise; increasing rectangularity and slenderness ratio, concrete compressive strength and load
eccentricity resulted in increasing tension steel strain. Table (5) summarized results of ultimate
induced strain for tested columns.
Figure (7-a): Effect of rectangularity ratio on concrete compressive
strain.
Figure (7-b): Effect of load eccentricity on concrete compressive
strain.
Figure (7-c): Effect of concrete compressive strength on concrete
compressive strain.
Figure (7-d): Effect of slenderness ratio on concrete compressive
strain.
0
100
200
300
400
500
600
0 2 4 6 8 10
Lo
ad
(K
N)
Lateral Mid-hieght Displacement (mm).
D1, fc' = 31.09 MPaD2, fc' = 52.68 MPaA2, fc' = 64.28 MPa
0
200
400
600
800
0 2 4 6 8 10
Lo
ad
(K
N)
Lateral Mid-hieght Displacement (mm).
E1, h/b = 6.67
E2, h/b = 8.33
A2, h/b = 10
0
100
200
300
400
500
600
-0.003-0.0025-0.002-0.0015-0.001-0.00050
Lo
ad
(K
N)
Concrete Compressive Strain
B1, t/b=1
B2, t/b=1.33
A2, t/b=1.670
500
1000
1500
2000
2500
-0.004-0.003-0.002-0.0010
Lo
ad
(K
N)
Concrete Compressive Strain
C1, e/t = 0.2
C2, e/t = 0.8
A2, e/t = 0.5
R, e/t = 0
0
100
200
300
400
500
600
-0.0035-0.003-0.0025-0.002-0.0015-0.001-0.00050
Lo
ad
(K
N)
Concrete compressive Strain
D1, fc' = 31.09 MPa
D2, fc' = 52.68 MPa
A2, fc' = 64.28 MPa
0
200
400
600
800
-0.004-0.003-0.002-0.0010
Lo
ad
(K
N)
Concrete Compressive Strain
E1, h/b = 6.67
E2, h/b = 8.33
A2, h/b = 10
-
11
Figure (8-a): Effect of rectangularity ratio on steel compression
strain.
Figure (8-b): Effect of load eccentricity on steel compression
strain.
Figure (8-c): Effect of concrete compressive strength on steel
compression strain.
Figure (8-d): Effect of slenderness ratio on steel compression
strain.
Figure (9-a): Effect of rectangularity ratio on steel compression
strain.
Figure (9-b): Effect of load eccentricity on steel compression
strain.
Figure (9-c): Effect of concrete compressive strength on steel compression
strain.
Figure (9-d): Effect of slenderness ratio on steel compression strain.
0
100
200
300
400
500
600
-0.002-0.0015-0.001-0.00050
Lo
ad
(K
N)
Steel Compression Strain
B1, t/b=1
B2, t/b=1.33
A2, t/b=1.670
500
1000
1500
2000
2500
-0.002-0.0015-0.001-0.00050
Lo
ad
(K
N)
Steel Compression Strain
C1, e/t = 0.2
A2, e/t = 0.5
R, e/t = 0
0
100
200
300
400
500
600
-0.002-0.0015-0.001-0.00050
Lo
ad
(K
N)
Steel Compression Strain
D1, fc' = 31.09 MPa
D2, fc' = 52.68 MPa
A2, fc' = 64.28 MPa0
200
400
600
800
-0.003-0.002-0.0010L
oa
d (
KN
)
Steel Compression Strain
E1, h/b = 6.67
E2, h/b = 8.33
A2, h/b = 10
0
100
200
300
400
500
600
0 0.002 0.004 0.006 0.008 0.01
Lo
ad
(K
N)
Steel Tension Strain
B1, t/b=1
B2, t/b=1.33
A2, t/b=1.670
200
400
600
800
1000
1200
0 0.005 0.01 0.015
Lo
ad
(K
N)
Steel Tension Strain
C1, e/t = 0.2
C2, e/t = 0.8
A2, e/t = 0.5
0
100
200
300
400
500
600
0 0.002 0.004 0.006 0.008 0.01
Lo
ad
(K
N)
Steel Tension Strain
D1, fc' = 31.09 MPa
D2, fc' = 52.68 MPa
A2, fc' = 64.28 MPa0
200
400
600
800
0 0.002 0.004 0.006 0.008 0.01
Lo
ad
(K
N)
Steel Tension Strain
E1, h/b = 6.67
E2, h/b = 8.33
A2, h/b = 10
-
12
Table (5): Induced strains for tested columns
Group
No.
Column
No. 𝑓𝑐ˋ
(Mpa)
Pcr
(KN)
Pult
(KN) cu s Mode of
failure sc st R R 63.19 1600 1950 0.00192 0.00182 ------ Compression
B
A2 64.28 50 500 0.00269 0.00169 0.00823 Tension
B1 63.51 50 300 0.00156 0.00105 0.00147 Compression
B2 64.79 50 450 0.00186 0.00124 0.00442 Tension
C C1 64.40 600 1050 0.00222 0.00188 0.00292 Compression
C2 64.66 40 260 0.00334 ------ 0.01170 Tension
D D1 28.92 50 250 0.00298 0.00118 0.00272 Compression
D2 52.68 50 450 0.00281 0.00126 0.00344 Tension
E E1 64.60 200 600 0.00333 0.00256 0.00210 Compression
E2 64.47 100 550 0.00289 0.00225 0.00252 Compression
Where:
cu : Mid-height concrete strain
s : Mid-height steel strain
st : Mid-height steel compression strain
st : Mid-height steel tension strain
7. Interaction diagram of the tested columns
In order to determine capacity (maximum load and moment) of high strength concrete column
sections, interaction diagram should be drawn. To get applicable interaction diagrams for high
strength concrete sections, equivalent rectangular stress blocks of both ECP 203-07 [5] and ACI
318R-14 [3] were used. Then, strain compatibility and equilibrium of forces were applied to
determine ultimate load and moment capacities of the section .By using Excel sheet, interaction
diagrams for tested columns were drawn. Figures from (10) to (14) show these interaction
diagrams and experimental results (axial load and bending moments) attached to it, in order to
check applicability of these diagrams. Figures indicated that all tested columns are safe and valid
except column (D1), this may be attributed to normal concrete compressive strength.
Results indicated that both ACI 318R-14 and ECP 203-07 are valid and safe for all tested columns
except columns C1 and D1, this could attributed to small eccentricity for column C1 and lower
compressive strength for column D1. All columns except columns C1 and D1 revealed
experimental values higher than interaction diagram this could attributed to additional moment
according to mid-height deformations.
Table (6) summarizes a comparison between loads obtained from experimental program and loads
calculated by interaction diagrams according to both ACI 318R-14 and ECP 203-07. It was
observed that ACI 318R-14 interaction diagram was more conservative than ECP 203-07.
-
13
Figure (10) Interaction diagram for column (B1) according to ACI 318 R-14 and ECP203-07 with experimental results attached to it.
Figure (11) Interaction diagram for column (B2) according to ACI 318 R-14 and ECP203-07 with experimental results attached to it.
Figure (12) Interaction diagram for column (A2), (C1), (C2), (E1) and (E2) according to ACI 318 R-14 and ECP203-07 with
experimental results attached to it.
Figure (13) Interaction diagram for column (D1) according to ACI 318 R-14 and ECP203-07 with experimental results attached to it.
B10
200
400
600
800
1000
1200
1400
1600
0 5 10 15 20 25 30 35
Lo
ad
(K
N)
Moment (KN.m)
ECP 203-07
B1
0
200
400
600
800
1000
1200
1400
1600
0 5 10 15 20 25 30 35
Lo
ad
(K
N)
Moment (KN.m)
ACI318R-14
B2 0
500
1000
1500
2000
2500
0 10 20 30 40 50 60
Lo
ad
(K
N)
Moment (KN.m)
ECP 203-07
B2 0
500
1000
1500
2000
2500
0 10 20 30 40 50 60
Lo
ad
(K
N)
Moment (KN.m)
ACI318R-14
E2 A2C2
C1
E1
0
500
1000
1500
2000
2500
0 20 40 60 80 100
Lo
ad
(K
N)
Moment (KN.m)
ECP 203-07
E2 A2 C2
C1
E1
0
500
1000
1500
2000
2500
0 20 40 60 80 100
Lo
ad
(K
N)
Moment (KN.m)
ACI318R-14
D1
0
200
400
600
800
1000
1200
1400
0 10 20 30 40 50
Lo
ad
(K
N)
Moment (KN.m)
ECP 203-07
D1
0
200
400
600
800
1000
1200
1400
0 10 20 30 40 50
Lo
ad
(K
N)
Moment (KN.m)
ACI318R-14
-
14
Figure (14) Interaction diagram for column (D2) according to ACI 318 R-14 and ECP203-07 with experimental results attached to it.
Table (6) Comparison between experimental and analytical loads
Group No. Colum No. PExp (KN) PACI (KN) PECP (KN) (PExp
PACI) (
PExp
PECP)
R R 1950 2279.86 2137.72 0.86 0.91
B
A2 500 550.00 552.48 0.91 0.90
B1 300 340.93 365.20 0.88 0.82
B2 450 453.50 476.25 0.99 0.94
C C1 1050 1356.68 1330.4 0.77 0.79
C2 260 255.00 261.50 1.02 0.99
D D1 250 344.65 339.52 0.72 0.73
D2 450 483.92 494.88 0.93 0.91
E E1 600 551.68 553.68 1.09 1.08
E2 550 551.12 553.20 0.99 0.99
10. Conclusions
This research program was conducted to investigate an experimental study on strength and
deformability of high strength reinforced concrete columns subjected to eccentric loading. From
tests carried out, herein, the following main conclusions can be drawn:
1. The concrete cover spalling zone of the tested columns was tended to be larger for higher concrete strengths. On the other hand, such zone tended to be smaller for higher slenderness
ratios or load eccentricities.
2. Increasing rectangularity ratio for columns leads to increase the column capacity as well as decrease the column ductility. Increasing rectangularity ratio by 67% increasing in column
capacity by 67% but decreasing mid-height displacement by 7%.
3. Increasing concrete compressive strength increasing the column load capacity and decreasing the ductility and deformability of reinforced high-strength concrete columns. Increasing
concrete compressive strength by 106% increasing column load capacity by 100%, on the
contrary; decreasing both of mid-height axial displacement by 3.0 and 6.6% and mid-height
lateral displacement by 15%.
4. Increasing load eccentricity decreasing the column load capacity and increasing ductility of tested column. Increasing load eccentricity ratio from zero to 80% decreasing column load
capacity by 87%. On the contrary; such an increasing of load eccentricity increasing of both
mid-height axial displacement 144%, and mid-height lateral displacement 73.9%.
D2
0
500
1000
1500
2000
2500
0 10 20 30 40 50 60 70
Lo
ad
(K
N)
Moment (KN.m)
ECP 203-07
D2
0
500
1000
1500
2000
2500
0 10 20 30 40 50 60 70
Lo
ad
(K
N)
Moment (KN.m)
ACI318R-14
-
15
5. Increasing load eccentricity increasing concrete compressive strain and exceeding maximum concrete compressive strain.
6. Increasing the slenderness ratio of column decreasing column load capacity but increasing ductility of tested column. Increasing ratio by 50% decreasing the column capacity by
16.67%, on the contrary; increase mid-height lateral displacement by 23.19%.
References
1- Abd-Elwahab Abo Eleineen; Ali Shereif Abd-Elfaiad; Amr H. Abd-Elazim and Weal
Mohamed Montaser “Behavior of High Performance Concrete Columns under Eccentric
Loading” Second International Conference on Civil Engineering, 1-3 April 2000, pp. 98-109.
2- ACI committee 363R-92 “State-of-the-Art Report on High-Strength Concrete” ACI Structural
Journal, July-August 1997.
3- ACI committee 318 “Building Code Requirement for Reinforced Concrete (ACI 318-14) and
Commentary (318R-14)” American Concrete Institute.
4- Antonius “Confinement Effects on High-Strength Concrete Columns Subjected eccentric
loading” Proceedings of the 4th
ASEAN Civil Engineering Conference, Yogyakarta, 22-23
November 2011.
5- CSA (Canadian Standards Association) (1994): “Design of Concrete Structures” CSA A23.3-
94, Dec., 1994, 200pp.
6- Egyptian Code of Practice for design and construction of R.C. Structures, ECP 203-2007
7- Erdem Canbay, Guney Ozcebe and Ugur Ersoy “High-Strength Concrete Columns under
Eccentric Load” Journal of Structural Engineering, Vol. 132, No.7, July 2006. pp. 1052-1060.
8- Firoz Nadaf and Praveen Biradar “Behavior of Slender Column Subjected to Eccentric
Loading” International Journal of Innovations in Engineering Research and Technology, Vol.
2, Issue 4, April 2015.
9- Halit Cenan Mertol, Sami Rizkalla, Pual Zia and Amir Mirmiran “Characteristics of
Compressive Stress Distribution in High-Strength Concrete” ACI Structural Journal, Vol. 105,
No. 5, September-October 2008, pp.626-633.
10- Hisham H. H. Ibrahim, and James G. MacGregor “Test of Eccentrically Loaded High-Strength
Concrete Columns” ACI Structural Journal, Vol. 93, No. 5, September-October 1996. pp. 585-
594.
11- Hisham H. H. Ibrahim, and James G. MacGregor “Flexural Behavior of Laterally Reinforced
High-Strength Concrete Columns” ACI Structural Journal, Vol. 93, No. 6, November-
December 1996. pp. 674-684.
12- Jae-Hoon Lee and Hyeok-Soo Son “Failure and Strength of High-Strength Concrete Columns
Subjected to Eccentric Loads” ACI Structural Journal, Vol. 97, No. 1, January-February 2000,
pp. 75-85.
13- Metin Husem, Selim Pul, Selcuk E. Gorkem and Serhat Demir “The Behavior of High-
Strength Reinforced Concrete Columns under Low Eccentric Loading” European Journal of
Environmental
14- and Civil Engineering, April 2015.
15- Natalie Anne Lloyd and B. Vijaya Rangan “Studies on High-Strength Concrete Columns under
Eccentric compression” ACI Structural Journal Vol. 93, No.6, November-December 1996,
631-638.
16- Stephen J. Foster “On Behavior of High-Strength Concrete Columns: Cover Spalling, Steel
Fibers, and Ductility” ACI Structural Journal Vol. 98, No.4, July-August 2001, pp. 583-589.
-
16
17- S. Kim, H. C. Mertol, S. Rizkalla and P. Zia “Behavior of High-Strength Concrete Rectangular
Columns” Seventh international Congress on Advances in Civil Engineering, October11-13,
2006, Yildiz Technical University, Istanbul, Turkey, pp.1-10.
18- Teng-Hooi Tan and Ngoc-Ba Nguyen “Flexural Behavior of Confined High-Strength Concrete
Columns” ACI Structural Journal Vol. 102, No.2, March-April 2005, pp. 198-205.