Stock Room Heater - TSR
Transcript of Stock Room Heater - TSR
Unit Ref Output A B C D E F G H J K
kW mm mm mm mm mm mm mm mm mm mm
TSR A Ambient 435 425 310 100 167.5 200 45 90 117.5 100
TSR 3 3.0 435 425 310 100 167.5 200 45 90 117.5 100
TSR 4 4.0 435 425 310 100 167.5 200 45 90 117.5 100
TSR 5 5.0 435 425 310 100 167.5 200 45 90 117.5 100
TSR 7 7.0 435 425 310 100 167.5 200 45 90 117.5 100
For further details, please refer to GA5028
DA
F
J K
E
GH
DA
Side View
B
C
Inlet View
Top View
M12 mounting
points
M12 mounting
points
Isolator
280 CTR
255124.5 15
B
C
Outlet View
Aerofoil outlet blades
Access Cover
Dimensions
Mounting Height:Std sizes:Mounting:Standard Outputs:Spec options:
up to 3.0 metres435 x 425 x 310mm (L x W x H)Threaded fixing holes provided to accommodate M12 threaded rod (rod by others)Ambient, Electric (1 Phase) 3kW, (3 phase) 4; 5 & 7kW Colour
Stock Room Heater - TSRThe TSR electric Stock Room Heater is designed to be mounted up to 3 metres. The unit provides up to 7kW of thermostatically controlled heating with adjustable aerofoil discharge blades enabling the heated air to be directed.The TSR is provided with an installation kit to accommodate drop rod, wall or ceiling mounting.
TSR, Issue B - 2016© Envirotec Ltd. Due to a policy of continuous development and improvement, the right is reserved to supply products which may differ from those described in this publication.
TSR - detail of thermostat control and Isolator.
Heater Output - Electric
Note - all Electric heater selections are based on a return temperature of 15oC.
Unit Ref Width Air Vol
mm m3/s
TSR A 425 0.30
TSR 3 425 0.30
TSR 4 425 0.30
TSR 5 425 0.30
TSR 7 425 0.30
Output Air Off Phase
kW oC
n/a n/a n/a
3.00 23.3 1
3.99 26.0 3
4.98 28.7 3
7.00 35.7 3
Wall Mounting
286
120
Hanging Brackets
Hanging Brackets
120120
Single bracket for ceiling mounting
Twin bracket for ceiling mounting
Drop Rod Hanging
150Minimum
TSR - Mounting OptionsThe TSR can be installed vertically or horizontally.
Vertical - Threaded Drop Rod Hanging.4off M12 sockets are included, adjacent to the inlet grille. Threaded rod by others.
Horizontal - Ceiling Mounting / Hanging Brackets4 off M12 bolts are included on the top of the TSR to accommodate either a single or pair of hanging brackets.
Horizontal - Wall MountingA single M12 stud is included in the centre of the top plate to match the cantilever bracket supplied with the TSR.
All dimensions in mm
General Data
Unit Ref
TSR A
TSR 3
TSR 4
TSR 5
TSR 7
MotorPower FLC SC
kW Amps Amps
0.025 0.86 1.72
0.025 0.86 1.72
0.025 0.86 1.72
0.025 0.86 1.72
0.025 0.86 1.72
Weight
Ambient Electric
kg kg
13 14
13 15
13 15
13 15
13 15Unit weights
are approximate
WiringAmbient units wired to:GSS 618
1 Phase units wired to:GSS 1028/1PH/Isolator
3 Phase units wired to:GSS 1028/3PH/Isolator