VACON STEP-DOWN STEP-UP SOLUTION
15.11.2005 2
Heikki Salo
15.11.2005 3
Heikki Salo
~ M~
M~
Pump or fan
~
How to control medium voltage motor
1. Step down transformer 6/0.4 kV or 6/0.69 kV2. Frequency converter Vacon CXC / NX3. Vacon sinus filter4. Step up transformer 0.4/6 kV or 0.69/6 kV5. 6 kV motor
15.11.2005 4
Heikki Salo
• Pump motor• 630 kW• 6 kV• 72 A
Water treatment plant
15.11.2005 5
Heikki Salo
15.11.2005 6
Heikki Salo
800 kW frequency converter for motor test bay
15.11.2005 7
Heikki Salo
• Frequency converter for motors- 55...500 kW, 400 V- 250..800 kW, 690 V- 250..800 kW, 6 kV and 10 kV via step up trafo- squared torque applications
• No load net voltage 764 V +10%,-15%- UkNettrafo = 4%, UkStep up = 4%, UkFilter = 2%
• Maximum losses at full load- Vacon: 24 kW (=3%)- Filter : 2.2 kW
• Fundamental wave content of output voltage 95%THD < 10%
• Low net voltage distortions by net harmonics
Main customer requirements
15.11.2005 8
Heikki Salo
15.11.2005 9
Heikki Salo
800 kW, 690/400 V, 880 Afrequency converter
Block diagram
15.11.2005 10
Heikki Salo
Net current, transformer primary side, full load 800 kw
15.11.2005 11
Heikki Salo
Phase to earth voltage Uu1 before the sinus filter
Phase to earth voltage Uu2 after the filter
15.11.2005 12
Heikki Salo
Output after the sinus filter at full load,800 kW, 690 V
Output voltage after the filter: 500 V, 2 ms per div
Output current after the filter: 500 A, 2 ms per div
15.11.2005 13
Heikki Salo
Output voltage and current at different frequencies
50 Hz 30 Hz
20 Hz 10 Hz
15.11.2005 14
Heikki Salo
What is the maximum peakvoltage after the filter fromphase to earth
Phase to phase voltage U31and current after the filter
15.11.2005 15
Heikki Salo
Is there a phase shift between filter in and output
Phase to earth voltage after the filter
Voltage before and afterthe filter together
==> no phase shift
15.11.2005 16
Heikki Salo
15.11.2005 17
Heikki Salo
• Vodokanal of St. Petersburg
Four units with step-down transformers, 630 kW FC and motor 690 V.
• Pskov
Two units of step-down/step-up transformers and 630 kW frequency converters for main feeder pumps at a district heating plant.
• Tatarstan
Pumps for 16 units step-down/up -solution 315 kW up to 900 kW. District heating pumps.
• Yakutia
2 units 1000 kW step-down / step-up for 6 kV pump motors.
References • BelarusPower plant pump, 630 kW, 6 kV with step-down / up transformers.
• LithuaniaDistrict heating plants one unit for 630 kW, 6 kV motor; a step-down / step-up transformer and frequency converter and same solution for 315 kW, 6 kV motor.
• PolandPower plant 800 and 1100 kW main feeding pumps 6 kV Step down / step up –solution.
• EstoniaTarto district heating plant 500 kW 6 kV motorStep down / step up solution with existing oil-immersed transformers.
Both 12-pulse and 6-pulse applications are used in the
above mentioned cases