Statical Analisis Diagnostic Short Circuit Cables MV
-
Upload
10rodriguez -
Category
Documents
-
view
216 -
download
0
Transcript of Statical Analisis Diagnostic Short Circuit Cables MV
-
8/17/2019 Statical Analisis Diagnostic Short Circuit Cables MV
1/6
1
Statistical analysis of the double line-to-ground
short-circuit current in MV urban network for
the power cable metallic screen ratingRoman Korab and Edward Siwy
Abstract -- The construction of the metallic screen or other
power cable elements designed for the short-circuit current
conducting has significant influence on the cost of medium
voltage cables in PVC (polyvinyl chloride) or XLPE (cross-linked
polyethylene) insulation. Not only the price of the cable, but also
the technical criteria must be taken into consideration while
choosing the types of cables and the cross-section of the metallic
screen or similar elements. These technical criteria can be based
on the double line-to-ground faults statistical analysis in thenetwork. The paper presents the description of the rules of
carrying out such analyses in urban cable MV network as well as
the sample results of computer simulations. The method of the
double line-to-ground fault currents calculation is consistent with
the international standard [1].
Index Terms-- cable metallic screen rating, double line-to-
ground fault, medium voltage (MV) power cable, MV urban
network, short-circuit current, unsymmetrical faults
I. I NTRODUCTION
T
HE metallic screen is the part of the medium voltage cable
in PVC or XLPE insulation [2]. It is usually made up ofcopper tapes or wires helically stranded over the insulation
layer (in single-core cables) or the belt insulation (in three-
core belted cables). Fig. 1 shows the standard construction of
the single-core MV power cable (not all shown in Fig. 1
elements of the single-core MV power cable have to occur in
every type of the cable). In the single-core cables individual
metallic screens are connected to each other on both ends of
the line. Metallic screens of every cable lines are grounded at
least on one end of the line. In some constructions of three-
core cables the individual thin aluminum screen for each
conductor and the common copper centre conductor are used
instead of the copper metallic screen.
In normal operation conditions, the metallic screen is usedas a return path for both capacitive charging currents and
induced currents. In the event of an electrical fault, the
metallic screen can also conduct short-circuit currents. The
flow of the fault current in metallic screens or other elements
designed for short-circuit current conducting can occur in
principle in two circumstances:
• during the single line-to-ground fault,
• during the double line-to-ground fault in a galvanicconnected network, however, both of ground faults can
be situated in the same cable line as well as in two
different lines.
Sheath Bedding
Cable armour
Metallic screen
Insulation Conductor
Conductor screen
Insulation screen(semi-conductor)
Fig. 1. The standard construction of single-core MV power cable
In the galvanic connected network double line-to-ground
faults can occur in three various cases. All possible cases of
double line-to-ground faults are shown in Fig. 2. In A case
both of line-to-ground faults (in phases L2 and L3) occur in
the same cable section. This cable section is the first section of
the whole cable line, hence the short-circuit current flows only
in the metallic screen of this cable section. In B case both of
line-to-ground faults (in phases L1 and L2) occur in the same
cable line, but in different cable section. In this case short-
circuit currents flow in metallic screens of three cable
sections, however, current flow in the metallic screen of the
first section of this line is induced by the short-circuit current
flow in conductors of phases L1 and L2. In A and B casesappropriate overcurrent protective relays are activated. In C
case line-to-ground faults occur in two different cable lines
and therefore the short-circuit current flows in metallic
screens of both lines. In this case the fault current flow path
impedance value is probably higher than in A and B cases.
The fault current can be interrupted by one of two circuit
breakers installed on the beginning of each cable line,
however, not in all situations both of overcurrent protective
relays are activated (as a general rule in MV network two-
phases overcurrent line protection is applied).
R. Korab is with Silesian University of Technology, Faculty of Electrical
Engineering, Institute of Power Systems Engineering and Control,
2 Krzywoustego St, 44 - 100 Gliwice, Poland (e-mail: [email protected]).
E. Siwy is with Silesian University of Technology, Faculty of Electrical
Engineering, Institute of Power Systems Engineering and Control,
2 Krzywoustego St, 44 - 100 Gliwice, Poland (e-mail: [email protected]).
9th International Conference on Probabilistic Methods Applied to Power SystemsKTH, Stockholm, Sweden – June 11-15, 2006
© Copyright KTH 2006
-
8/17/2019 Statical Analisis Diagnostic Short Circuit Cables MV
2/6
2
The main reasons for the double line-to-ground faults
occurrence are disadvantageous voltage and current transients
during the single line-to-ground fault. The frequency and the
probability of the double line-to-ground faults occurrence
among other things depend on the duration of the single line-
to-ground fault and the length of galvanic connected lines in
the network. The network neutral point treatment has an
essential influence on the frequency and the probability of the
double line-to-ground faults occurrence. These faultsfrequently occur in networks operated with compensated or
isolated neutral, less frequently in networks with resistive
grounded neutral. Various quantitative estimation of number
of double line-to-ground faults in the total number of faults
can be found in the literature. It is usually assessed that no
more than 25 % of single line-to-ground faults transform into
double line-to-ground faults. The research into several MV
cable urban networks performed in the 80’s of the twentieth
century [3] showed, that the share of double line-to-ground
faults in the total number of faults is not larger than 15 % (5 %
on average). The mentioned research also showed, that the
biggest possible annual frequency of the double line-to-
ground faults occurrence in the network made of cables in
PVC or XLPE insulation is not larger than 10 per 100 km of
lines.
II. THE METHOD OF THE DOUBLE LINE-TO-GROUND FAULT
CURRENTS CALCULATION
For the double line-to-ground currents calculation the MV
network model shown in Fig. 2 is used. The network is
supplied with a bulk power transformer. The power source is
characterized by the short-circuit power and by the transfer
resistance and reactance ratio. In the network model single- or
three-core cables in various insulation (PVC, XLPE, oil-
impregnated paper) can be modeled. Modeled cables can havedifferent rated voltages and various cross-sections of metallic
screens or the common copper centre conductors. Various
network configurations are permissible. It is assumed that
metallic screens or common centre conductors of every cable
lines are grounded on both ends of the line.
The mutual location of fault points in MV network has a
significant impact on the double line-to-ground fault current
flow path impedance. The mentioned factor also influences
the fault currents flow. The resultant fault current flow path
impedance is equal to the sum of positive and negative
sequence power source impedance, and impedances of the
power cables situated on the fault current flow path. The valueof the double line-to-ground short-circuit current, in kA, can
be calculated on the basis of a symmetrical-components
method [4], using the following formula
Z Z
U , I
s
n z
∆Σ+=
12
2
11 (1)
where:
U n - network nominal voltage, in kV,
Z 1 s - positive sequence impedance (equal to the negative
sequence impedance) of the power source, in Ω,
Σ∆ Z - additional impedance, equal to the sum of
impedances of all power cables situated on thedouble line-to-ground fault current flow path, in Ω.
After the substitution to (1) the value of additional impedance
Σ∆ Z = 0, the maximum possible value of double line-to-ground short-circuit current is obtained. In this case, the short-
circuit current value is equal to a phase-to-phase short-circuit
current value during the fault on MV busbar. It can be
calculated by using the formula as follows
" k
" k
s
n" k z I , I
Z
U , I I 33
122 8660
2
3
2
11==== (2)
where is a value of initial symmetrical (three-phase)
short-circuit current, in kA, during the fault on MV busbar.
"
k
I 3
Formulas for calculating the single-core cable additional
impedance and the short-circuit current flow in metallic
screens during double line-to-ground faults are shown in
Fig. 3. Similar formulas for the traditional three-core cables
and the three-core cables with the common copper centre
conductor are shown in Fig. 4. These formulas were derived
on the basis of a ground-return circuit method [5].Fig. 2. The three possible points (A, B and C) of double line-to-ground faults
in the medium voltage distribution cable network
9th International Conference on Probabilistic Methods Applied to Power SystemsKTH, Stockholm, Sweden – June 11-15, 2006
© Copyright KTH 2006
-
8/17/2019 Statical Analisis Diagnostic Short Circuit Cables MV
3/6
3
1 x
L
12 x x ≤
2 z I
2 z I
2 I
4 I
1 I
3 I
5 I
( ) ( ) L
x xaa Z
L
xa x xa Z 21101
21
1210 22 −−+++=∆ ( )
m p
mrpmr
Z Z
Z Z Z Z Z
−
−−−=
2
1 prpr R Z Z a +−=0
m p
m p
p
Z Z
Z Z
Ra
+−
−=
2
2
12
( )
−+=
L
xbb
L
xb I I z
210
1121 122 I I I z −= ( )
−+=
L
xbb
L
xb I I z
110
2123 324 I I I z −= ( )
L
x xbb I I z
211025
−−=
m p
p
Z Z
Rb
−=0
m p
m p
p
Z Z
Z Z
R
+−
=21
2b
Fig. 3. The equivalent circuit scheme and formulas for calculating the single-core cables additional impedance and the short-circuit current flow in the metallic
screens during double line-to-ground faults
12 x x ≤
1 x
L
2 z I
2 z I
1 I 2 I 1 I
12 x x ≤
1 x
L
2 z I
2 z I
1 I 1 I 2 I
( )( ) 201
2
21110 2 xa Z
L
x xa xa Z −+
−+=∆ mr Z Z Z −=1 prpr R Z Z a +−=0
p
p
Z
Ra
2
1
−=
L
x xb I I z
21121
−= 122 I I I z −=
p
p
Z
Rb =1
Fig. 4. The equivalent circuit scheme and formulas for calculating the additional impedance of the traditional three-core cables or the three-core cables with the
common copper centre conductor and the short-circuit current flow in the metallic screens or the common centre conductor during double line-to-ground faults
9th International Conference on Probabilistic Methods Applied to Power SystemsKTH, Stockholm, Sweden – June 11-15, 2006
© Copyright KTH 2006
-
8/17/2019 Statical Analisis Diagnostic Short Circuit Cables MV
4/6
4
Individual symbols used in Fig. 3 and Fig.4 represent: The condition (3) was checked for all cable sections in
analyzed MV network. An exceeding of the rated short time
(one-second) thermal current was recorded when the condition
(3) was not satisfied. Such situations are extremely rare due to
quite unusual and unlikely location of the fault points. A
repetition cycle (in years) of the exceeding of the rated short
time thermal current has to be sufficiently long, longer than
the average service life of the cable line.
Z 1 - cable line positive sequence impedance, in Ω,
Z r - conductor impedance, in Ω,
Z p - metallic screen impedance, in Ω,
R p - metallic screen resistance, inΩ,
Z m - mutual conductors impedance, in Ω,
Z rp - mutual conductor and metallic screen impedance, in Ω,a1, a2 - cable line per unit impedance for calculating the
additional impedance Σ∆ Z , in Ω/km, Computer simulations were performed for a few real 6 kVand 20 kV networks [6]. These were pure cable networks
(6 kV networks) or cable networks with some overhead line
sections (20 kV networks). Analyzed networks operate with
isolated, compensated or resistive grounded neutral. The
duration time of double line-to-ground faults was equal to a
time delay of a delayed overcurrent protection plus 0,2 s. All
calculations of the short-circuit current flow were performed
for the actual value of the short-circuit power as well as for
the increased one (after the replacement of the present bulk
power transformer with the bigger one).
b0, b1 - short-circuit current flow coefficients, dimensionless
value,
I 1, I 2, I 3, I 4, I 5 - currents flowing in individual sections of
metallic screens, in kA.
One of the following currents I 1, I 2, I 3, I 4 and I 5 has the biggest
value. The biggest current value in next sections of this paper
is marked with the I max symbol.
Formulas shown in Fig. 3 and Fig. 4 have a general nature,
i.e. they can be applied when one of fault points is located in
the given cable section and the second fault point is located in
a different one. When the second fault point is located in the
cable section situated closer to the power source, in certainformulas x2 = 0. In other situations, when second fault point is
located in the cable section situated farther to the power
source, in certain formulas x1 = L. When both fault points are
located outside the considered cable section, then x1 = x2 = L.
In such cases the additional impedance is equal to 2 Z 1. This
result is consistent with the symmetrical-components method.
Fig. 5 to Fig. 10 show the frequency histograms of double
line-to-ground fault currents flowing in conductors or in
metallic screens of power cables for two chosen urban MV (6
and 20 kV) networks. In all mentioned figures an average
value of appropriate current is represented by a thick line.
0 0.2 0.4 0.6 0.8 1
0
0.2
0.4
0.6
f r e q u e n c y
''
22 k z I I
kA49102 , I ' '
k =
III. THE SAMPLE R ESULTS OF COMPUTER SIMULATIONS
The statistical modeling method is used for calculations of
the short-circuit current flow in the metallic screens during
double line-to-ground faults. It was assumed that a probability
of the fault points location is equal in the whole cablenetwork. For each combination of the fault point location the
following quantities are calculated:
• the impedance of individual power cable sectionssituated on the fault current flow path,
• the whole impedance of the fault current flow path,Fig. 5. The frequency histogram of double line-to-ground fault current in 6 kV
cable conductor for the actual (126 MVA) value of the short-circuit power• the value of the double line-to-ground short-circuit
current I z 2,
• the value of currents flowing in metallic screens of allcable sections situated on the fault current flow path.
During computer simulations of double line-to-ground
faults the following condition was checked each time
thr k k th I T nm I T I ≤+= )(max (3) n
0 0.2 0.4 0.6 0.8 1
0
0.1
0.2
0.3
0.4
''
22 k z I I
f r e q u e
c y
kA3452 , I ' ' k =
where:
I th - thermal equivalent short-circuit current, in kA,
T k - duration of double line-to-ground short-circuit
current, in s,
I max - the biggest current flowing in individual sections of
metallic screens, in kA
m, n - factors for the calculation of the thermal equivalent
short-circuit current, dimensionless values, Fig. 6. The frequency histogram of double line-to-ground fault current in 20 kV
cable conductor for the actual (214 MVA) value of the short-circuit power I thr - rated short time (one-second) thermal current, in k Α.
9th International Conference on Probabilistic Methods Applied to Power SystemsKTH, Stockholm, Sweden – June 11-15, 2006
© Copyright KTH 2006
-
8/17/2019 Statical Analisis Diagnostic Short Circuit Cables MV
5/6
5
In Fig. 5 through 10 the fault currents are related to the
phase-to-phase short-circuit current value during the fault on
MV busbar. The value of the phase-to-phase short-circuit
current is shown in each figure. Usually in 6 kV networks the
value of the bulk power transformer impedance (calculated at
the lower voltage side of this transformer) is very small.
Hence, as a general rule, the value of the phase-to-phase
short-circuit current is large, larger than in 20 kV networks,
but it quickly decreases as the distance between the fault pointlocation and the MV busbar increase. In 20 kV networks the
phase-to-phase short-circuit current decrease is slower. The
main reason for the quick 6 kV phase-to-phase short-circuit
decrease is a power cable reactance. The value of 6 kV power
cable reactance is not much smaller than the reactance of
20 kV power cable, whereas a voltage in 6 kV network is
more than 3 times smaller than in 20 kV network.
0 0.2 0.4 0.6 0.8 1
0
0.2
0.4
0.6
''
2max k I I
f r e q u e n c y
kA49102 , I ' '
k =
Fig. 7. The frequency histogram of the biggest value of current flowing in 6 kV
cable metallic screens for the actual (126 MVA) value of the short-circuit power
0 0.2 0.4 0.6 0.8 1
0
0.1
0.2
0.3
0.4
''2max k I I
f r e q u e n c y
kA3452 , I ' '
k =
Fig. 8. The frequency histogram of the biggest value of current flowing in 20 kV
cable metallic screens for the actual (214 MVA) value of the short-circuit power
The value of double line-to-ground currents in the given
network mainly depends on the bulk power transformer rated
power. The level of the short-circuit power on 110 kV busbar
as well as the neutral point treatment in MV network have
much smaller influence on the value of these currents. The
value of double line-to-ground currents quickly decreases as
the distance between fault points increases. The longer
individual power cable sections and the smaller the cross-
section of the metallic screens are, the bigger decrease in fault
current is. The influence of these factors is growing when the
bulk power transformer rated power is increasing. As a result
double line-to-ground fault currents in 6 kV networks are
much smaller than in 20 kV networks.
For the actual value of the short-circuit power, the average
value of fault currents flowing in cable metallic screens in
analyzed real 20 kV networks ranges from 3.0 to 3.7 kA. Forthe maximum possible value of the 20 kV short-circuit power,
the average value of these fault currents increases and ranges
from 4.0 to 4.9 kA (which gives about 45 ÷ 60 % of the
phase-to-phase short-circuit current value during the fault on
20 kV busbar). In analyzed 6 kV networks, for the actual
value of the short-circuit power, the average value of fault
currents flowing in cable metallic screens ranges from 1.8 to
2.4 kA. For the maximum possible value of the 6 kV short-
circuit power the average value of these fault currents ranges
from 2.0 to 2.7 kA (which gives about 12 ÷ 15 % of the
phase-to-phase short-circuit current value during the fault on
MV busbar).
0 0.2 0.4 0.6 0.8 1
0
0.2
0.4
0.6
f r e q u e n c y
''
2max k I I
kA65162 , I ' '
k =
Fig. 9. The frequency histogram of the biggest value of current flowing in 6
kV cable metallic screens for the increased (200 MVA) value of the short-
circuit power
0 0.2 0.4 0.6 0.8 1
0
0.1
0.2
0.3
0.4
''
2max k I I
f r e q u e n c y
kA2482 , I ' ' k =
Fig. 10. The frequency histogram of the biggest value of current flowing in
20 kV cable metallic screens for the increased (330 MVA) value of the short-
circuit power
9th International Conference on Probabilistic Methods Applied to Power SystemsKTH, Stockholm, Sweden – June 11-15, 2006
© Copyright KTH 2006
-
8/17/2019 Statical Analisis Diagnostic Short Circuit Cables MV
6/6
6
V. CONCLUSIONS IV. THE POWER CABLE METALLIC SCREEN R ATING
The rated metallic screen cross-section should be
determined on the basis of computer simulations in a way
which makes the repetition cycle (in years) of the exceeding
of the rated short time thermal current sufficiently long. It
means that the probability of the exceeding of the rated short
time thermal current should be sufficiently small. The
repetition cycle of several score years guarantees that the
exceeding of the rated short time thermal current of cable
metallic screens will not occur in all service life of the
considered cable network. Table 1 presents detailed results of
the repetition cycle for analyzed 6 kV and 20 kV networks for
different power cables types and different values of the short-
circuit power on MV busbar. It was assumed in simulations
that the annual frequency of the double line-to-ground faults
occurrence is equal to 2 per 100 km of lines.
Rational criterions for the power cable metallic screen
rating was formulated on the basis of computer simulations
results. These criterions depend on the network rated voltage,
the neutral point treatment and the double line-to-ground
duration time. Very often power cables with the minimal (6,
10 or 16 mm2) cross-section of metallic screen can be installed
in networks, especially with the resistive grounded neutral.
But in some cases the recommended in standard [2] metallic
screen cross-section can be insufficient.
Until now in Polish MV cables networks three-core and
single-core cables with 50 mm2 metallic screens cross-section
were commonly used. The application of proposed rules in
practice makes the use of power cable with the smaller
metallic screens cross-section possible. The installation of
power cables with the smaller metallic screens cross-section
cause significant savings of network investment costs.TABLE I
THE R EPETITION CYCLE (IN YEARS) OF THE EXCEEDING OF THE R ATED
SHORT TIME THERMAL CURRENT FOR POWER CABLE METALLIC SCREENS VI. R EFERENCES
Short-circuit
power
Power cables installed in analyzed network:Type / Conductor cross-section [mm2] /
Metallic screen cross-section [mm2]
Analyzed
network
MVA Real *) 5C/120/16 5C/240/25 5F/120/35
155 171 32 48 82
175 141 30 41 73U n = 6 kV
lenght = 42,5 km200 111 29 36 66
222 577 16 125 90
260 215 9 59 46U n = 20 kV
lenght = 25 km330 74 6 21 22
[1] “Short-circuit currents in three-phase a.c. systems – Part 3: Currents
during two separate simultaneous line-to-earth short-circuits and partialshort-circuit currents flowing through earth,” International Standard IEC
60909-3, 2nd ed., 2003.
[2] “Distribution cables with extruded insulation for rated voltages from
3,6/6 (7,2) kV to 20,8/36 (42) kV,” Polish Standard PN–HD 620 S1:
2002(U).
[3] G. Bartodziej, J. Popczyk, K. Żmuda, “Verification of the short–circuit
withstand of wires of 6–20 kV cables in industrial networks,” IV
International Symposium on Short–Circuit Currents in Power Systems,
Universite de Liege, Technical University of Lodz, Liege, 6–8.10.1990.
[4] J.D. Glover, M.S. Sarma, "Power system analysis and design," 3rd ed.
Pacific Grove: Brooks/Cole, 2002.*) – different types of power cables with the different conductor cross-section;
mostly the metallic screen cross-section is equal to 50 mm2 [5] M. Krakowski, ”The ground-return circuit”, Warsaw: WNT 1979 (in
Polish).
Until now in Polish MV cable network three-core and
single-core cables with 50 mm2 metallic screens cross-section
were commonly used. For such metallic screen cross-sectionthe exceeding of the rated short time thermal current in
analyzed networks is extremely rare. The results presented in
Table 1 show that in most cases the metallic screen cross-
section can be much smaller than 50 mm2. But it should be
emphasized that the recommended in standard [2] metallic
screen cross-section equal to 16 mm2 can be insufficient,
especially in 20 kV networks.
[6] K. Żmuda, R. Korab, E. Siwy, ” The analysis of possibility of the cross-
section of the metallic screen reduction in the MV power cables in the
urban networks,” Silesian University of Technology, Gliwice, Tech.
Rep. MZE 04-073JK, February 2004, (in Polish).
VII. BIOGRAPHIES
Roman Korab was born in Zawiercie, Poland, on
October 6, 1973. He obtained his M.Sc. and Ph.D.
degree from the Silesian University of Technology
in 1998 and 2003, respectively.
He is presently working at Faculty of Electrical
Engineering, Institute of Power Systems
Engineering and Control. His research interests
mainly include power system operation and
development economics, optimization and control.
The presented method of calculation of double line-to-
ground short-circuit currents include some safety factors.
These factors result from following assumptions:
• the permissible short-circuit temperature is valuated with
some margin of safety,• the infinite value of 110 kV busbar short-circuit power is
assumed,
Edward Siwy was born in Piekary Sl., Poland, on
January 17, 1963. He obtained his M.Sc. and Ph.D.
degree from the Silesian University of Technology
in 87 and 1997, respectively.• non-resistive double line-to-ground faults, power cableconnections and groundelectrodes are assumed, He is presently working at Faculty of Electrical
Engineering, Institute of Power Systems
Engineering and Control. His research interests
mainly include transmission and distribution
networks optimization.
• the possibility of faster short-circuit interruption by cut-off or ground-fault protections is omitted.
Mentioned assumptions make the possibility of the exceeding
of the rated short time thermal current smaller.
9th International Conference on Probabilistic Methods Applied to Power SystemsKTH, Stockholm, Sweden – June 11-15, 2006
© Copyright KTH 2006