Statical Analisis Diagnostic Short Circuit Cables MV

download Statical Analisis Diagnostic Short Circuit Cables MV

of 6

Transcript of Statical Analisis Diagnostic Short Circuit Cables MV

  • 8/17/2019 Statical Analisis Diagnostic Short Circuit Cables MV

    1/6

      1

    Statistical analysis of the double line-to-ground

    short-circuit current in MV urban network for

    the power cable metallic screen ratingRoman Korab and Edward Siwy

     Abstract -- The construction of the metallic screen or other

    power cable elements designed for the short-circuit current

    conducting has significant influence on the cost of medium

    voltage cables in PVC (polyvinyl chloride) or XLPE (cross-linked

    polyethylene) insulation. Not only the price of the cable, but also

    the technical criteria must be taken into consideration while

    choosing the types of cables and the cross-section of the metallic

    screen or similar elements. These technical criteria can be based

    on the double line-to-ground faults statistical analysis in thenetwork. The paper presents the description of the rules of

    carrying out such analyses in urban cable MV network as well as

    the sample results of computer simulations. The method of the

    double line-to-ground fault currents calculation is consistent with

    the international standard [1].

     Index Terms-- cable metallic screen rating, double line-to-

    ground fault, medium voltage (MV) power cable, MV urban

    network, short-circuit current, unsymmetrical faults

    I. I NTRODUCTION 

    T

    HE metallic screen is the part of the medium voltage cable

    in PVC or XLPE insulation [2]. It is usually made up ofcopper tapes or wires helically stranded over the insulation

    layer (in single-core cables) or the belt insulation (in three-

    core belted cables). Fig. 1 shows the standard construction of

    the single-core MV power cable (not all shown in Fig. 1

    elements of the single-core MV power cable have to occur in

    every type of the cable). In the single-core cables individual

    metallic screens are connected to each other on both ends of

    the line. Metallic screens of every cable lines are grounded at

    least on one end of the line. In some constructions of three-

    core cables the individual thin aluminum screen for each

    conductor and the common copper centre conductor are used

    instead of the copper metallic screen.

    In normal operation conditions, the metallic screen is usedas a return path for both capacitive charging currents and

    induced currents. In the event of an electrical fault, the

    metallic screen can also conduct short-circuit currents. The

    flow of the fault current in metallic screens or other elements

    designed for short-circuit current conducting can occur in

     principle in two circumstances:

    • during the single line-to-ground fault,

    • during the double line-to-ground fault in a galvanicconnected network, however, both of ground faults can

     be situated in the same cable line as well as in two

    different lines.

    Sheath Bedding

    Cable armour 

    Metallic screen

    Insulation Conductor 

    Conductor screen

    Insulation screen(semi-conductor)

     

    Fig. 1. The standard construction of single-core MV power cable

    In the galvanic connected network double line-to-ground

    faults can occur in three various cases. All possible cases of

    double line-to-ground faults are shown in Fig. 2. In A case

     both of line-to-ground faults (in phases L2 and L3) occur in

    the same cable section. This cable section is the first section of

    the whole cable line, hence the short-circuit current flows only

    in the metallic screen of this cable section. In B case both of

    line-to-ground faults (in phases L1 and L2) occur in the same

    cable line, but in different cable section. In this case short-

    circuit currents flow in metallic screens of three cable

    sections, however, current flow in the metallic screen of the

    first section of this line is induced by the short-circuit current

    flow in conductors of phases L1 and L2. In A and B casesappropriate overcurrent protective relays are activated. In C

    case line-to-ground faults occur in two different cable lines

    and therefore the  short-circuit current flows in metallic

    screens of both lines. In this case the fault current flow path

    impedance value is probably higher than in A and B cases.

    The fault current can be interrupted by one of two circuit

     breakers installed on the beginning of each cable line,

    however, not in all situations both of overcurrent protective

    relays are activated (as a general rule in MV network two-

     phases overcurrent line protection is applied).

    R. Korab is with Silesian University of Technology, Faculty of Electrical

    Engineering, Institute of Power Systems Engineering and Control,

    2 Krzywoustego St, 44 - 100 Gliwice, Poland (e-mail: [email protected]).

    E. Siwy is with Silesian University of Technology, Faculty of Electrical

    Engineering, Institute of Power Systems Engineering and Control,

    2 Krzywoustego St, 44 - 100 Gliwice, Poland (e-mail: [email protected]).

    9th International Conference on Probabilistic Methods Applied to Power SystemsKTH, Stockholm, Sweden – June 11-15, 2006

    © Copyright KTH 2006

  • 8/17/2019 Statical Analisis Diagnostic Short Circuit Cables MV

    2/6

      2

    The main reasons for the double line-to-ground faults

    occurrence are disadvantageous voltage and current transients

    during the single line-to-ground fault. The frequency and the

     probability of the double line-to-ground faults occurrence

    among other  things depend on the duration of the single line-

    to-ground fault and the length of galvanic connected lines in

    the network. The network neutral point treatment has an

    essential influence on the frequency and the probability of the

    double line-to-ground faults occurrence. These faultsfrequently occur in networks operated with compensated or

    isolated neutral, less frequently in networks with resistive

    grounded neutral. Various quantitative estimation of number

    of double line-to-ground faults in the total number of faults

    can be found in the literature. It is usually assessed that no

    more than 25 % of single line-to-ground faults transform into

    double line-to-ground faults. The research into several MV

    cable urban networks performed in the 80’s of the twentieth

    century [3] showed, that the share of double line-to-ground

    faults in the total number of faults is not larger than 15 % (5 %

    on average). The mentioned research also showed, that the

     biggest possible annual frequency of the double line-to-

    ground faults occurrence in the network made of cables in

    PVC or XLPE insulation is not larger than 10 per 100 km of

    lines.

    II. THE METHOD OF THE DOUBLE LINE-TO-GROUND FAULT

    CURRENTS CALCULATION 

    For the double line-to-ground currents calculation the MV

    network model shown in Fig. 2 is used. The network is

    supplied with a bulk power transformer. The power source is

    characterized by the short-circuit power and by the transfer

    resistance and reactance ratio. In the network model single- or

    three-core cables in various insulation (PVC, XLPE, oil-

    impregnated paper) can be modeled. Modeled cables can havedifferent rated voltages and various cross-sections of metallic

    screens or the common copper centre conductors. Various

    network configurations are permissible. It is assumed that

    metallic screens or common centre conductors of every cable

    lines are grounded on both ends of the line.

    The mutual location of fault points in MV network has a

    significant impact on the double line-to-ground fault current

    flow path impedance. The mentioned factor also influences

    the fault currents flow. The resultant fault current flow path

    impedance is equal to the sum of positive and negative

    sequence power source impedance, and impedances of the

     power cables situated on the fault current flow path. The valueof the double line-to-ground short-circuit current, in kA, can

     be calculated on the basis of a symmetrical-components

    method [4], using the following formula

     Z  Z 

    U  , I 

     s

    n z 

    ∆Σ+=

    12

    2

    11  (1)

    where:

    U n  - network nominal voltage, in kV,

     Z 1 s  - positive sequence impedance (equal to the negative

    sequence impedance) of the power source, in Ω,

    Σ∆ Z   - additional impedance, equal to the sum of

    impedances of all power cables situated on thedouble line-to-ground fault current flow path, in Ω.

    After the substitution to (1) the value of additional impedance

    Σ∆ Z  = 0, the maximum possible value of double line-to-ground short-circuit current is obtained. In this case, the short-

    circuit current value is equal to a phase-to-phase short-circuit

    current value during the fault on MV busbar. It can be

    calculated by using the formula as follows

    " k 

    " k 

     s

    n" k  z    I  , I 

     Z 

    U  , I  I  33

    122 8660

    2

    3

    2

    11====   (2)

    where is a value of initial symmetrical (three-phase)

    short-circuit current, in kA, during the fault on MV busbar.

     I 3

      Formulas for calculating the single-core cable additional

    impedance and the short-circuit current flow in metallic

    screens during double line-to-ground faults are shown in

    Fig. 3. Similar formulas for the traditional three-core cables

    and the three-core cables with the common copper centre

    conductor are shown in Fig. 4. These formulas were derived

    on the basis of a ground-return circuit method [5].Fig. 2. The three possible points (A, B and C) of double line-to-ground faults

    in the medium voltage distribution cable network

    9th International Conference on Probabilistic Methods Applied to Power SystemsKTH, Stockholm, Sweden – June 11-15, 2006

    © Copyright KTH 2006

  • 8/17/2019 Statical Analisis Diagnostic Short Circuit Cables MV

    3/6

      3

     

    1 x

     L

    12  x x ≤

    2 z  I 

    2 z  I 

    2 I 

    4 I 

    1 I 

    3 I 

    5 I 

     

    ( ) ( ) L

     x xaa Z 

     L

     xa x xa Z  21101

    21

    1210 22 −−+++=∆  ( )

    m p

    mrpmr 

     Z  Z 

     Z  Z  Z  Z  Z 

    −−−=

    2

    1    prpr    R Z  Z a +−=0  

    m p

    m p

     p

     Z  Z 

     Z  Z 

     Ra

    +−

    −=

    2

    2

    12

     

    ( )

    −+=

     L

     xbb

     L

     xb I  I    z 

    210

    1121   122   I  I  I    z  −=   ( )

    −+=

     L

     xbb

     L

     xb I  I    z 

    110

    2123   324   I  I  I    z  −=   ( )

     L

     x xbb I  I    z 

    211025

    −−=  

    m p

     p

     Z  Z 

     Rb

    −=0  

    m p

    m p

     p

     Z  Z 

     Z  Z 

     R

    +−

    =21

    2b  

    Fig. 3. The equivalent circuit scheme and formulas for calculating the single-core cables additional impedance and the short-circuit current flow in the metallic

    screens during double line-to-ground faults

    12  x x ≤

    1 x

     L

    2 z  I 

    2 z  I 

    1 I  2 I  1 I 

     

    12  x x ≤

    1 x

     L

    2 z  I 

    2 z  I 

    1 I  1 I 2 I 

     

    ( )( ) 201

    2

    21110 2   xa Z 

     L

     x xa xa Z  −+

    −+=∆   mr    Z  Z  Z  −=1    prpr    R Z  Z a +−=0  

     p

     p

     Z 

     Ra

    2

    1

    −=  

     L

     x xb I  I    z 

    21121

    −=   122   I  I  I    z  −=  

     p

     p

     Z 

     Rb =1  

    Fig. 4. The equivalent circuit scheme and formulas for calculating the additional impedance of the traditional three-core cables or the three-core cables with the

    common copper centre conductor and the short-circuit current flow in the metallic screens or the common centre conductor during double line-to-ground faults

    9th International Conference on Probabilistic Methods Applied to Power SystemsKTH, Stockholm, Sweden – June 11-15, 2006

    © Copyright KTH 2006

  • 8/17/2019 Statical Analisis Diagnostic Short Circuit Cables MV

    4/6

      4

    Individual symbols used in Fig. 3 and Fig.4 represent: The condition (3) was checked for all cable sections in

    analyzed MV network. An exceeding of the rated short time

    (one-second) thermal current was recorded when the condition

    (3) was not satisfied. Such situations are extremely rare due to

    quite unusual and unlikely location of the fault points. A

    repetition cycle (in years) of the exceeding of the rated short

    time thermal current has to be sufficiently long, longer than

    the average service life of the cable line.

     Z 1  - cable line positive sequence impedance, in Ω,

     Z r   - conductor impedance, in Ω,

     Z  p  - metallic screen impedance, in Ω,

     R p  - metallic screen resistance, inΩ,

     Z m - mutual conductors impedance, in Ω,

     Z rp - mutual conductor and metallic screen impedance, in Ω,a1, a2  - cable line per unit impedance for calculating the

    additional impedance Σ∆ Z  , in Ω/km, Computer simulations were performed for a few real 6 kVand 20 kV networks [6]. These were pure cable networks

    (6 kV networks) or cable networks with some overhead line

    sections (20 kV networks). Analyzed networks operate with

    isolated, compensated or resistive grounded neutral. The

    duration time of double line-to-ground faults was equal to a

    time delay of a delayed overcurrent protection plus 0,2 s. All

    calculations of the short-circuit current flow were performed

    for the actual value of the short-circuit power as well as for

    the increased one (after the replacement of the present bulk

     power transformer with the bigger one).

    b0, b1  - short-circuit current flow coefficients, dimensionless

    value,

     I 1,  I 2,  I 3,  I 4,  I 5  - currents flowing in individual sections of

    metallic screens, in kA.

    One of the following currents  I 1,  I 2,  I 3,  I 4 and I 5 has the biggest

    value. The biggest current value in next sections of this paper

    is marked with the I max symbol.

    Formulas shown in Fig. 3 and Fig. 4 have a general nature,

    i.e. they can be applied when one of fault points is located in

    the given cable section and the second fault point is located in

    a different one. When the second fault point is located in the

    cable section situated closer to the power source, in certainformulas x2 = 0. In other situations, when second fault point is

    located in the cable section situated farther to the power

    source, in certain formulas  x1 =  L. When both fault points are

    located outside the considered cable section, then  x1 =  x2 =  L.

    In such cases the additional impedance is equal to 2 Z 1. This

    result is consistent with the symmetrical-components method.

    Fig. 5 to Fig. 10 show the frequency histograms of double

    line-to-ground fault currents flowing in conductors or in

    metallic screens of power cables for two chosen urban MV (6

    and 20 kV) networks. In all mentioned figures an average

    value of appropriate current is represented by a thick line.

    0 0.2 0.4 0.6 0.8 1

    0

    0.2

    0.4

    0.6

           f     r     e     q     u     e     n     c     y

    ''

    22   k  z    I  I 

    kA49102   , I  ' ' 

    k  =

     

    III. THE SAMPLE R ESULTS OF COMPUTER SIMULATIONS 

    The statistical modeling method is used for calculations of

    the short-circuit current flow in the metallic screens during

    double line-to-ground faults. It was assumed that a probability

    of the fault points location is equal in the whole cablenetwork. For each combination of the fault point location the

    following quantities are calculated:

    • the impedance of individual power cable sectionssituated on the fault current flow path,

    • the whole impedance of the fault current flow path,Fig. 5. The frequency histogram of double line-to-ground fault current in 6 kV

    cable conductor for the actual (126 MVA) value of the short-circuit power• the value of the double line-to-ground short-circuit

    current I  z 2,

    • the value of currents flowing in metallic screens of allcable sections situated on the fault current flow path.

    During computer simulations of double line-to-ground

    faults the following condition was checked each time

    thr k k th   I T nm I T  I  ≤+= )(max   (3)      n

    0 0.2 0.4 0.6 0.8 1

    0

    0.1

    0.2

    0.3

    0.4

    ''

    22   k  z    I  I 

           f     r     e     q     u     e

         c     y

    kA3452   , I  ' ' k  =

     

    where:

     I th  - thermal equivalent short-circuit current, in kA,

    T k   - duration of double line-to-ground short-circuit

    current, in s,

     I max  - the biggest current flowing in individual sections of

    metallic screens, in kA

    m, n  - factors for the calculation of the thermal equivalent

    short-circuit current, dimensionless values, Fig. 6. The frequency histogram of double line-to-ground fault current in 20 kV

    cable conductor for the actual (214 MVA) value of the short-circuit power I thr   - rated short time (one-second) thermal current, in k Α.

    9th International Conference on Probabilistic Methods Applied to Power SystemsKTH, Stockholm, Sweden – June 11-15, 2006

    © Copyright KTH 2006

  • 8/17/2019 Statical Analisis Diagnostic Short Circuit Cables MV

    5/6

      5

    In Fig. 5 through 10 the fault currents are related to the

     phase-to-phase short-circuit current value during the fault on

    MV busbar. The value of the phase-to-phase short-circuit

    current is shown in each figure. Usually in 6 kV networks the

    value of the bulk power transformer impedance (calculated at

    the lower voltage side of this transformer) is very small.

    Hence, as a general rule, the value of the phase-to-phase

    short-circuit current is large, larger than in 20 kV networks,

     but it quickly decreases as the distance between the fault pointlocation and the MV busbar increase. In 20 kV networks the

     phase-to-phase short-circuit current decrease is slower. The

    main reason for the quick 6 kV phase-to-phase short-circuit

    decrease is a power cable reactance. The value of 6 kV power

    cable reactance is not much smaller than the reactance of

    20 kV power cable, whereas a voltage in 6 kV network is

    more than 3 times smaller than in 20 kV network. 

    0 0.2 0.4 0.6 0.8 1

    0

    0.2

    0.4

    0.6

    ''

    2max   k  I  I 

           f     r     e     q     u     e     n     c     y

    kA49102   , I  ' ' 

    k  =

     Fig. 7. The frequency histogram of the biggest value of current flowing in 6 kV

    cable metallic screens for the actual (126 MVA) value of the short-circuit power

    0 0.2 0.4 0.6 0.8 1

    0

    0.1

    0.2

    0.3

    0.4

    ''2max   k  I  I 

           f     r     e     q     u     e     n     c     y

    kA3452   , I  ' ' 

    k  =

     Fig. 8. The frequency histogram of the biggest value of current flowing in 20 kV

    cable metallic screens for the actual (214 MVA) value of the short-circuit power

    The value of double line-to-ground currents in the given

    network mainly depends on the bulk power transformer rated

     power. The level of the short-circuit power on 110 kV busbar

    as well as the neutral point treatment in MV network have

    much smaller influence on the value of these currents. The

    value of double line-to-ground currents quickly decreases as

    the distance between fault points increases. The longer

    individual power cable sections and the smaller the cross-

    section of the metallic screens are, the bigger decrease in fault

    current is. The influence of these factors is growing when the

     bulk power transformer rated power is increasing. As a result

    double line-to-ground fault currents in 6 kV networks are

    much smaller than in 20 kV networks. 

    For the actual value of the short-circuit power, the average

    value of fault currents flowing in cable metallic screens in

    analyzed real 20 kV networks ranges from 3.0 to 3.7 kA. Forthe maximum possible value of the 20 kV short-circuit power,

    the average value of these fault currents increases and ranges

    from 4.0 to 4.9 kA (which gives about 45 ÷ 60 % of the

     phase-to-phase short-circuit current value during the fault on

    20 kV busbar). In analyzed 6 kV networks, for the actual

    value of the short-circuit power, the average value of fault

    currents flowing in cable metallic screens ranges from 1.8 to

    2.4 kA. For the maximum possible value of the 6 kV short-

    circuit power the average value of these fault currents ranges

    from 2.0 to 2.7 kA (which gives about 12 ÷ 15 % of the

     phase-to-phase short-circuit current value during the fault on

    MV busbar).

    0 0.2 0.4 0.6 0.8 1

    0

    0.2

    0.4

    0.6

           f     r     e     q     u     e     n     c     y

    ''

    2max   k  I  I 

    kA65162   , I   ' ' 

    k  =

     Fig. 9. The frequency histogram of the biggest value of current flowing in 6

    kV cable metallic screens for the increased (200 MVA) value of the short-

    circuit power

    0 0.2 0.4 0.6 0.8 1

    0

    0.1

    0.2

    0.3

    0.4

    ''

    2max   k  I  I 

           f     r     e     q     u     e     n     c     y

    kA2482   , I  ' ' k  =

     Fig. 10. The frequency histogram of the biggest value of current flowing in

    20 kV cable metallic screens for the increased (330 MVA) value of the short-

    circuit power

    9th International Conference on Probabilistic Methods Applied to Power SystemsKTH, Stockholm, Sweden – June 11-15, 2006

    © Copyright KTH 2006

  • 8/17/2019 Statical Analisis Diagnostic Short Circuit Cables MV

    6/6

      6

    V. CONCLUSIONS IV. THE POWER CABLE METALLIC SCREEN R ATING 

    The rated metallic screen cross-section should be

    determined on the basis of computer simulations in a way

    which makes the repetition cycle (in years) of the exceeding

    of the rated short time thermal current sufficiently long. It

    means that the probability of the exceeding of the rated short

    time thermal current should be sufficiently small. The

    repetition cycle of several score years guarantees that the

    exceeding of the rated short time thermal current of cable

    metallic screens will not occur in all service life of the

    considered cable network. Table 1 presents detailed results of

    the repetition cycle for analyzed 6 kV and 20 kV networks for

    different power cables types and different values of the short-

    circuit power on MV busbar. It was assumed in simulations

    that the annual frequency of the double line-to-ground faults

    occurrence is equal to 2 per 100 km of lines.

    Rational criterions for the power cable metallic screen

    rating was formulated on the basis of computer simulations

    results. These criterions depend on the network rated voltage,

    the neutral point treatment and the double line-to-ground

    duration time. Very often power cables with the minimal (6,

    10 or 16 mm2) cross-section of metallic screen can be installed

    in networks, especially with the resistive grounded neutral.

    But in some cases the recommended in standard [2] metallic

    screen cross-section can be insufficient.

    Until now in Polish MV cables networks three-core and

    single-core cables with 50 mm2 metallic screens cross-section

    were commonly used. The application of proposed rules in

     practice makes the use of power cable with the smaller

    metallic screens cross-section possible. The installation of

     power cables with the smaller metallic screens cross-section

    cause significant savings of network investment costs.TABLE I

    THE R EPETITION CYCLE (IN YEARS) OF THE EXCEEDING OF THE R ATED

    SHORT TIME THERMAL CURRENT FOR POWER CABLE METALLIC SCREENS VI. R EFERENCES 

    Short-circuit

     power

    Power cables installed in analyzed network:Type / Conductor cross-section [mm2] /

    Metallic screen cross-section [mm2]

    Analyzed

    network

    MVA Real *) 5C/120/16 5C/240/25 5F/120/35

    155 171 32 48 82

    175 141 30 41 73U n = 6 kV

    lenght = 42,5 km200 111 29 36 66

    222 577 16 125 90

    260 215 9 59 46U n = 20 kV

    lenght = 25 km330 74 6 21 22

    [1] “Short-circuit currents in three-phase a.c. systems – Part 3: Currents

    during two separate simultaneous line-to-earth short-circuits and partialshort-circuit currents flowing through earth,” International Standard IEC

    60909-3, 2nd ed., 2003.

    [2] “Distribution cables with extruded insulation for rated voltages from

    3,6/6 (7,2) kV to 20,8/36 (42) kV,” Polish Standard PN–HD 620 S1:

    2002(U).

    [3] G. Bartodziej, J. Popczyk, K. Żmuda, “Verification of the short–circuit

    withstand of wires of 6–20 kV cables in industrial networks,” IV

    International Symposium on Short–Circuit Currents in Power Systems,

    Universite de Liege, Technical University of Lodz, Liege, 6–8.10.1990.

    [4] J.D. Glover, M.S. Sarma, "Power system analysis and design," 3rd  ed.

    Pacific Grove: Brooks/Cole, 2002.*) – different types of power cables with the different conductor cross-section;

    mostly the metallic screen cross-section is equal to 50 mm2  [5] M. Krakowski, ”The ground-return circuit”, Warsaw: WNT 1979 (in

    Polish).

    Until now in Polish MV cable network three-core and

    single-core cables with 50 mm2 metallic screens cross-section

    were commonly used. For such metallic screen cross-sectionthe exceeding of the rated short time thermal current in

    analyzed networks is extremely rare. The results presented in

    Table 1 show that in most cases the metallic screen cross-

    section can be much smaller than 50 mm2. But it should be

    emphasized that the recommended in standard [2] metallic

    screen cross-section equal to 16 mm2  can be insufficient,

    especially in 20 kV networks.

    [6] K. Żmuda, R. Korab, E. Siwy, ” The analysis of possibility of the cross-

    section of the metallic screen reduction in the MV power cables in the

    urban networks,” Silesian University of Technology, Gliwice, Tech.

    Rep. MZE 04-073JK, February 2004, (in Polish).

    VII. BIOGRAPHIES 

    Roman Korab  was born in Zawiercie, Poland, on

    October 6, 1973. He obtained his M.Sc. and Ph.D.

    degree from the Silesian University of Technology

    in 1998 and 2003, respectively.

    He is presently working at Faculty of Electrical

    Engineering, Institute of Power Systems

    Engineering and Control. His research interests

    mainly include power system operation and

    development economics, optimization and control.

    The presented method of calculation of double line-to-

    ground short-circuit currents include some safety factors.

    These factors result from following assumptions:

    • the permissible short-circuit temperature is valuated with

    some margin of safety,• the infinite value of 110 kV busbar short-circuit power is

    assumed,

    Edward Siwy was born in Piekary Sl., Poland, on

    January 17, 1963. He obtained his M.Sc. and Ph.D.

    degree from the Silesian University of Technology

    in 87 and 1997, respectively.• non-resistive double line-to-ground faults, power cableconnections and groundelectrodes are assumed, He is presently working at Faculty of Electrical

    Engineering, Institute of Power Systems

    Engineering and Control. His research interests

    mainly include transmission and distribution

    networks optimization.

    • the possibility of faster short-circuit interruption by cut-off or ground-fault protections is omitted.

    Mentioned assumptions make the possibility of the exceeding

    of the rated short time thermal current smaller.

    9th International Conference on Probabilistic Methods Applied to Power SystemsKTH, Stockholm, Sweden – June 11-15, 2006

    © Copyright KTH 2006