STANDARD ONE-STOREY SCHOOL BUILDING

16
STANDARD ONE-STOREY VARIOUS DPWH PROPOSED PROJECTS (DETAILED ENGINEERING DESIGN AND/OR SPECIAL STUDIES) SCHOOL BUILDING (2 - CLASSROOMS) JOINT VENTURE OF PDF Compressor Pro

Transcript of STANDARD ONE-STOREY SCHOOL BUILDING

Page 1: STANDARD ONE-STOREY SCHOOL BUILDING

STANDARD ONE-STOREY

VARIOUS DPWH PROPOSED PROJECTS(DETAILED ENGINEERING DESIGN AND/OR SPECIAL STUDIES)

SCHOOL BUILDING(2 - CLASSROOMS)

JOINT VENTURE OF

PDF Compressor Pro

Page 2: STANDARD ONE-STOREY SCHOOL BUILDING

SECRETARYDIRECTOR IV, BOD

GILBERTO S. REYES ROGELIO L. SINGSON

UNDERSECRETARY

RAUL C. ASISG-1

BOD 1

15

(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)

STANDARD ONE-STOREYSCHOOL BUILDING( 2-CLASSROOM )

VARIOUS DPWH

PROPOSED PROJECTS

BILL OF QUANTITIES

OIC, BUILDING DIVISION

I.

BILL OF QUANTITIES WITH-OUT SHEAR WALL

TWO-CLASSROOM

Mobilization / Demobilization

A.

II. Temporary Facilities and Billboard

III. Safety and Health

IV. Earthworks

V. Termite Control Works

VI. Concrete Works

VII. Masonry Works

VIII. Fabricated Materials and Hardwares

IX. Finishing Works

X. Carpentry Works

XI. Roof and Framing Works

XII. Painting Works

XIII. Electrical Works

PDF Compressor Pro

Page 3: STANDARD ONE-STOREY SCHOOL BUILDING

SECRETARYDIRECTOR IV, BOD

GILBERTO S. REYES ROGELIO L. SINGSON

UNDERSECRETARY

RAUL C. ASISA-1

BOD 2

15

(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)

STANDARD ONE-STOREYSCHOOL BUILDING( 2-CLASSROOM )

VARIOUS DPWH

PROPOSED PROJECTS

T A B L E O F C O N T E N T S

STRUCTURAL PLUMBING ELECTRICAL MECHANICAL

PERSPECTIVE

PERSPECTIVE,

TABLE OF CONTENTS

OIC, BUILDING DIVISION

ARCHITECTURAL

GENERAL

G - 1 BILL OF QUANTITIES

A - 1 PERSPECTIVE VIEW, TABLE OF CONTENTS

A - 2 GROUND FLOOR PLAN, FRONT AND REAR ELEVATION,

LONGITUDINAL SECTION AND SCHEDULE OF FLOOR FINISHES

A - 3 ROOF PLAN, REFLECTED CEILING PLAN, TYPICAL SIDE

ELEVATION, CROSS SECTION, SCHEDULE OF DOORS AND

WINDOWS

A - 4 CEILING PLAN, SECTION, PERSPECTIVE, TYPICAL CEILING VENT

PLAN AND VENT SECTION DETAIL

A - 5 DETAILED CROSS SECTION, DETAIL SECTION OF EAVES FRONT,

DETAIL SECTION OF RAMP & CORRIDOR, DETAIL SECTION OF

CORRIDOR & SPOT DETAIL OF RAMP FLOORING

A - 6 BLACKBOARD DETAIL, CONNECTION SECTION DETAIL, SECTION,

SPOT DETAIL SECTION EDGE FRAMING, CHALK DUST BOX DETAIL

& SPECIFICATION

S - 1 GENERAL NOTES, BEAM CONSTRUCTION JOINT

TYPE REINFORCEMENT DETAIL CONTROL

JOINTS FOR SLAB-ON-FILL

S - 2 STANDARD DETAILS

S - 3 STANDARD DETAILS

S - 4 FOUNDATION PLAN, DETAIL OF F-1/C-1,COLUMN

ELEVATION, DETAIL OF STIFFENER, DETAIL OF

FOOTING TIE BEAM, DETAIL SECTION OF RAMP &

CORRIDOR, DETAIL SECTION OF CORRIDOR

S - 5 ROOF FRAMING PLAN, DETAIL OF ROOF BEAM

RB-1 & RB-2, DETAIL SECTION OF LRB-1 & PC-1,

ELEVATION OF END WALL FRAME, CONNECTION

OF PURLINS TO LRB-1

S - 6 TRUSS DETAILS

S - 7 DETAIL SECTION AT EAVES, CONNECTION OF G.I.

SHEET ROOFING TO PURLIN, TRUSS SUPPORT

CONNECTION DETAIL, SPOT DETAIL, DETAIL

CONNECTION OF CROSS BRACING, PURLIN

SPLICE, DETAIL PLAN CONNECTION OF PURLIN &

SAG ROD

EE - 1 POWER AND LIGHTNING LAYOUT, ELECTRICAL

SYMBOLS, GENERAL NOTES, ELECTRICAL

RISER DIAGRAM, SCHEDULE OF LIGHTNING

FIXTURES AND LAMPS, SCHEDULE OF LOADS

AND COMPUTATION

NOTE :

PDF Compressor Pro

Page 4: STANDARD ONE-STOREY SCHOOL BUILDING

SECRETARYDIRECTOR IV, BOD

GILBERTO S. REYES ROGELIO L. SINGSON

UNDERSECRETARY

RAUL C. ASISA-2

BOD 3

15

(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)

STANDARD ONE-STOREYSCHOOL BUILDING( 2-CLASSROOM )

VARIOUS DPWH

PROPOSED PROJECTS

GROUND FLOOR PLAN

FRONT ELEVATION

REAR ELEVATION

GROUND FLOOR PLAN,

FRONT ELEVATION,

REAR ELEVATION,

LONGITUDINAL SECTION AND

SCHEDULE OF FLOOR FINISHES

LONGITUDINAL SECTION

OIC, BUILDING DIVISION

NOTE :

SCHEDULE OF FLOOR FINISHES :

PDF Compressor Pro

Page 5: STANDARD ONE-STOREY SCHOOL BUILDING

SECRETARYDIRECTOR IV, BOD

GILBERTO S. REYES ROGELIO L. SINGSON

UNDERSECRETARY

RAUL C. ASISA-3

BOD 4

15

(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)

STANDARD ONE-STOREYSCHOOL BUILDING( 2-CLASSROOM )

VARIOUS DPWH

PROPOSED PROJECTS

ROOF PLAN

REFLECTED CEILING PLAN

SCHEDULE OF

DOOR AND WINDOWS

TYPICAL SIDE ELEVATION

CROSS SECTION

ROOF PLAN,

REFLECTED CEILING PLAN,

TYPICAL SIDE ELEVATION,

CROSS SECTION AND

SCHEDULE OF DOOR AND WINDOWS

SECTION A

OIC, BUILDING DIVISION

NOTE :

PDF Compressor Pro

Page 6: STANDARD ONE-STOREY SCHOOL BUILDING

SECRETARYDIRECTOR IV, BOD

GILBERTO S. REYES ROGELIO L. SINGSON

UNDERSECRETARY

RAUL C. ASISA-4

BOD 5

15

(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)

STANDARD ONE-STOREYSCHOOL BUILDING( 2-CLASSROOM )

VARIOUS DPWH

PROPOSED PROJECTSCEILING PLAN,

PERSPECTIVE,

SECTION,

TYPICAL CEILING VENT PLAN AND

VENT SECTION DETAIL

PERSPECTIVECEILING PLAN

S E C T I O N

D E T A I L

OIC, BUILDING DIVISION

TYP. CLG. VENT SECTION DETAIL

TYP. CLG. VENT PLAN DETAIL

NOTE :

PDF Compressor Pro

Page 7: STANDARD ONE-STOREY SCHOOL BUILDING

SECRETARYDIRECTOR IV, BOD

GILBERTO S. REYES ROGELIO L. SINGSON

UNDERSECRETARY

RAUL C. ASISA-5

BOD 6

15

(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)

STANDARD ONE-STOREYSCHOOL BUILDING( 2-CLASSROOM )

VARIOUS DPWH

PROPOSED PROJECTSDETAILED CROSS SECTION,

TYPICAL DET. SECTION OF EAVES FRONT,

DETAIL SECTION OF RAMP & CORRIDOR,

DETAIL SECTION OF CORRIDOR AND

SPOT DETAIL OF RAMP FLOORINGOIC, BUILDING DIVISION

DETAILED CROSS SECTION

DETAIL SECTION OF RAMP AND CORRIDOR

TYPICAL DETAIL SECTION OF EAVE (FRONT)

DETAIL SECTION OF CORRIDOR

SPOT DETAIL OF RAMP FLOORING

NOTE :

PDF Compressor Pro

Page 8: STANDARD ONE-STOREY SCHOOL BUILDING

SECRETARYDIRECTOR IV, BOD

GILBERTO S. REYES ROGELIO L. SINGSON

UNDERSECRETARY

RAUL C. ASISA-6

BOD 7

15

(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)

STANDARD ONE-STOREYSCHOOL BUILDING( 2-CLASSROOM )

VARIOUS DPWH

PROPOSED PROJECTSBLACKBOARD DETAIL,

CONNECTION SECTION DETAIL,

SECTION,

SPOT DETAIL SECTION EDGE FRAMING,

CHALK DUST BOX DETAILOIC, BUILDING DIVISION

BLACKBOARD DETAIL CONNECTION SECTION DETAIL

S E C T I O N

CHALK DUST BOX DETAIL

SPOT DETAIL SECTION

EDGE FRAMING

NOTE :

PDF Compressor Pro

Page 9: STANDARD ONE-STOREY SCHOOL BUILDING

SECRETARYDIRECTOR IV, BOD

GILBERTO S. REYES ROGELIO L. SINGSON

UNDERSECRETARY

RAUL C. ASISS-1

BOD 8

15

(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)

STANDARD ONE-STOREYSCHOOL BUILDING( 2-CLASSROOM )

VARIOUS DPWH

PROPOSED PROJECTS GENERAL NOTES,

BEAM CONSTRUCTION JOINT,

TYPICAL REINFORCEMENT DETAIL,

CONTROL JOINTS FOR SLAB-ON-FILL

1S-1

GENERAL NOTES & STANDARD DETAILSNOT TO SCALE

1C CONTROL JOINTS FOR SLAB-ON-FILL

NOT TO SCALE

BEAM CONSTRUCTION JOINT1AS-1

TYP. REINFORCEMENT DETAIL1BNOT TO SCALE

NOT TO SCALE

S-1

S-1

OIC, BUILDING DIVISION

DOMICIANO B. LUSICA

PROJECT MANAGER

NELSON S. ANTONIO

PRC No.: 14234 TIN No.: 178-384-258

NAPOLEON B. TORIBIO

PRC No.: 32516 TIN No.: 107-915-002

STRUCTURAL DESIGN

POSITION: STRUCTURAL ENGINEER

STRUCTURAL DESIGN

POSITION: STRUCTURAL ENGINEER

GENERAL NOTES:

PDF Compressor Pro

Page 10: STANDARD ONE-STOREY SCHOOL BUILDING

SECRETARYDIRECTOR IV, BOD

GILBERTO S. REYES ROGELIO L. SINGSON

UNDERSECRETARY

RAUL C. ASISS-2

BOD 9

15

(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)

STANDARD ONE-STOREYSCHOOL BUILDING( 2-CLASSROOM )

VARIOUS DPWH

PROPOSED PROJECTS

STANDARD DETAILS

OIC, BUILDING DIVISION

DOMICIANO B. LUSICA

PROJECT MANAGER

NELSON S. ANTONIO

PRC No.: 14234 TIN No.: 178-384-258

NAPOLEON B. TORIBIO

PRC No.: 32516 TIN No.: 107-915-002

STRUCTURAL DESIGN

POSITION: STRUCTURAL ENGINEER

STRUCTURAL DESIGN

POSITION: STRUCTURAL ENGINEER

NOTE :NOTE :

NOTE :BEAMS COLUMNS FLOOR SLABS

SPLICING REQUIREMENT OF REINFORCING BARS "Ls" or "Ld"

REMOVAL OF FORMS & SHORINGS CAMBER REQUIREMENT

STRUCTURAL ELEMENTSCLEAR SPAN

BETWEEN SUPPORTS

MINIMUM TIME PERIOD

(DAYS) ELEMENT MINIMUM CAMBER

BEAM RE-BAR

TERMINATION BEND TYPICAL BEAM & GIRDER RE-BAR LAYOUT

CORNER / EXTERIOR COL.

TERMINATION BEND

INTERIOR COLUMN

TERMINATION BEND

TYP. PLAN OF BEAM /

GIRDER COL. JOINTTYP. BEAM PENETRATION DETAIL

STANDARD DETAILS

PDF Compressor Pro

Page 11: STANDARD ONE-STOREY SCHOOL BUILDING

SECRETARYDIRECTOR IV, BOD

GILBERTO S. REYES ROGELIO L. SINGSON

UNDERSECRETARY

RAUL C. ASISS-3

BOD 10

15

(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)

STANDARD ONE-STOREYSCHOOL BUILDING( 2-CLASSROOM )

VARIOUS DPWH

PROPOSED PROJECTS

STANDARD DETAILS

OIC, BUILDING DIVISION

DOMICIANO B. LUSICA

PROJECT MANAGER

NELSON S. ANTONIO

PRC No.: 14234 TIN No.: 178-384-258

NAPOLEON B. TORIBIO

PRC No.: 32516 TIN No.: 107-915-002

STRUCTURAL DESIGN

POSITION: STRUCTURAL ENGINEER

STRUCTURAL DESIGN

POSITION: STRUCTURAL ENGINEER

NOTE :

LINTEL BEAMS MASONRY

SCHEDULE OF MASONRY WORKS

TYP. CHB WALL OPENING ELEV.TYPICAL MASONRY ELEVATION

STANDARD DETAILS

TYPICAL LINTEL BEAM DETAIL

R.C. & CHB EXTERIOR WALL

SIDE ANCHORAGE DET.

PDF Compressor Pro

Page 12: STANDARD ONE-STOREY SCHOOL BUILDING

SECRETARYDIRECTOR IV, BOD

GILBERTO S. REYES ROGELIO L. SINGSON

UNDERSECRETARY

RAUL C. ASISS-4

BOD 11

15

(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)

VARIOUS DPWH

PROPOSED PROJECTS

STANDARD ONE-STOREYSCHOOL BUILDING( 2-CLASSROOM )

FOUNDATION PLAN

DETAIL OF FOOTING TIE BEAM

DETAIL OF F-1 / C-1

DETAIL SECT. OF RAMP & CORRIDOR

DETAIL SECT. OF CORRIDOR

DETAIL OF STIFFENER

COLUMN ELEVATION

OIC, BUILDING DIVISION

DOMICIANO B. LUSICA

PROJECT MANAGER

NELSON S. ANTONIO

PRC No.: 14234 TIN No.: 178-384-258

NAPOLEON B. TORIBIO

PRC No.: 32516 TIN No.: 107-915-002

STRUCTURAL DESIGN

POSITION: STRUCTURAL ENGINEER

STRUCTURAL DESIGN

POSITION: STRUCTURAL ENGINEER

FOUNDATION PLAN, DETAIL OF F-1 / C-1,

COLUMN ELEVATION,

DETAIL OF STIFFENER,

DETAIL OF FOOTING TIE BEAM,

DETAIL SECTION OF RAMP & CORRIDOR,

NOTE :

PDF Compressor Pro

Page 13: STANDARD ONE-STOREY SCHOOL BUILDING

ROOF FRAMING PLAN,

SECRETARYDIRECTOR IV, BOD

GILBERTO S. REYES ROGELIO L. SINGSON

UNDERSECRETARY

RAUL C. ASISS-5

BOD 12

15

(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)

STANDARD ONE-STOREYSCHOOL BUILDING( 2-CLASSROOM )

VARIOUS DPWH

PROPOSED PROJECTSDETAIL OF ROOF BEAM RB-1 & RB-2,

DETAIL SECTION OF LRB-1 & PC-1ELEVATION OF END WALL FRAMECONNECTION OF PURLINS TO LRB-1

ROOF FRAMING PLAN

DETAIL OF ROOF BEAM (RB-1)

DETAIL OF ROOF BEAM (RB-2)

DETAIL SECTION OF LRB-1 & PC-1

ELEV. OF END WALL FRAME

D E T A I L

CONNECTION OF PURLINS TO LRB-1

D E T A I L

OIC, BUILDING DIVISION

DOMICIANO B. LUSICA

PROJECT MANAGER

NELSON S. ANTONIO

PRC No.: 14234 TIN No.: 178-384-258

NAPOLEON B. TORIBIO

PRC No.: 32516 TIN No.: 107-915-002

STRUCTURAL DESIGN

POSITION: STRUCTURAL ENGINEER

STRUCTURAL DESIGN

POSITION: STRUCTURAL ENGINEER

D E T A I L

PDF Compressor Pro

Page 14: STANDARD ONE-STOREY SCHOOL BUILDING

TRUSS DETAILS

SECRETARYDIRECTOR IV, BOD

GILBERTO S. REYES ROGELIO L. SINGSON

UNDERSECRETARY

RAUL C. ASISS-6

BOD 13

15

(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)

STANDARD ONE-STOREYSCHOOL BUILDING( 2-CLASSROOM )

VARIOUS DPWH

PROPOSED PROJECTS

DETAIL ELEVATION OF TRUSS

DETAIL-1 DETAIL-2

CONNECTION OF G.I.

SHEET ROOFING TO PURLIN DETAIL-3

DETAIL-4

D E T A I L

OIC, BUILDING DIVISION

DOMICIANO B. LUSICA

PROJECT MANAGER

NELSON S. ANTONIO

PRC No.: 14234 TIN No.: 178-384-258

NAPOLEON B. TORIBIO

PRC No.: 32516 TIN No.: 107-915-002

STRUCTURAL DESIGN

POSITION: STRUCTURAL ENGINEER

STRUCTURAL DESIGN

POSITION: STRUCTURAL ENGINEER

NOTES ON ROOF CONSTRUCTION :

PDF Compressor Pro

Page 15: STANDARD ONE-STOREY SCHOOL BUILDING

DETAIL SECTION @ EAVES,

SECRETARYDIRECTOR IV, BOD

GILBERTO S. REYES ROGELIO L. SINGSON

UNDERSECRETARY

RAUL C. ASISS-7

BOD 14

15

(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)

STANDARD ONE-STOREYSCHOOL BUILDING( 2-CLASSROOM )

VARIOUS DPWH

PROPOSED PROJECTSTRUSS SUPPORTCONNECTION DETAIL,SPOT DETAILDETAIL CONN. OF CROSS BRACINGPURLIN SPLICE, ROOFING FIXER

DETAIL SECTION AT EAVES

ISOMETRIC VIEW OF CONNECTION

OF G.I. SHEET TO PURLIN

TRUSS SUPPORT CONN. DETAIL PURLIN SPLICE

SPOT DETAIL

DETAIL PLAN CONN. OF

PURLINS AND SAG ROD

DETAIL CONN. OF CROSS BRACING

DETAIL OF EAVE @

END WALL OF BUILDING

ROOFING FIXER

OIC, BUILDING DIVISION

DOMICIANO B. LUSICA

PROJECT MANAGER

NELSON S. ANTONIO

PRC No.: 14234 TIN No.: 178-384-258

NAPOLEON B. TORIBIO

PRC No.: 32516 TIN No.: 107-915-002

STRUCTURAL DESIGN

POSITION: STRUCTURAL ENGINEER

STRUCTURAL DESIGN

POSITION: STRUCTURAL ENGINEER

NOTE :

PDF Compressor Pro

Page 16: STANDARD ONE-STOREY SCHOOL BUILDING

SECRETARYDIRECTOR IV, BOD

GILBERTO S. REYES ROGELIO L. SINGSON

UNDERSECRETARY

RAUL C. ASISEE-1

BOD 15

15

(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)

STANDARD ONE-STOREYSCHOOL BUILDING( 2-CLASSROOM )

VARIOUS DPWH

PROPOSED PROJECTS POWER AND LIGHTING LAYOUT,

ELECTRICAL SYMBOLS, GENERAL NOTES,ELECTRICAL RISER DIAGRAM,

SCHEDULE OF LIGHTING FIXTURES AND LAMPS,

SCHEDULE OF LOADS AND COMPUTATION

POWER LAYOUT

LIGHTING LAYOUT ELECTRICAL RISER DIAGRAM

OIC, BUILDING DIVISION

NOTE :

GENERAL NOTES :

1

2

CKT.

NO.

LIGHT OUTLETS

LOAD DESCRIPTIONBRANCH CKT. BREAKER

501203 230

1440

VA PER

CKT.AF

VOLTS

2 15

P AT

SIZE OF HOMERUN

( WIRES IN CONDUIT )

3003 MACB : 50AF, 2P, 240V, 40AT, 18kAIC

CONVENIENCE OUTLETS 20 2 - 3.5mm² TW + 1 - 3.5mm² TW (G) in 15mmØ C

2 - 3.5mm² TW + 1 - 3.5mm² TW (G) in 15mmØ C

1.00 = 13.06 AMPERESL 230

3003I @ 100% D.F. =

USE : 2 - 8.0mm² THWN + 1 - 5.5mm² TW (G) in 20mmØ RSC

50230 2

3 CEILING FANS 360 2050230 2 2 - 3.5mm² TW + 1 - 3.5mm² TW (G) in 15mmØ C

NOTE:

ONE (1)-18W, 230V, 60Hz AC,COMPACT FLUORESCENT LIGHTING FIXTURE WITH MEDIUM

BASE KEYLESS TYPE PORCELAIN RECEPTACLE

TWO (2)-36W, 230V, 60Hz AC, FLUORESCENT LIGHTING FIXTURE , BOX TYPE2

SYMBOLS

SURFACED CEILING

MOUNTED

DESCRIPTION

1

SCHEDULE OF LIGHTING FIXTURES AND LAMPS :

ALL FLUORESCENT LIGHTING FIXTURES SHALL BE EQUIPPED WITH A HIGH POWER FACTOR, PRE-HEAT

WITH STARTER AND THERMALLY PROTECTED BALLAST, COMPLETE WITH ALL NECESSARY ACCESSORIES,

WIRED AND READY FOR USE.

INSTALLATION/

MOUNTING

SCHEDULE OF LOADS AND COMPUTATIONS :

DISTRIBUTION PANELBOARD " DP "

T O T A L

ELECTRIC SERVICE METER

ELECTRIC SERVICE ENTRANCE

M

UNDERGROUND OR UNDERFLOOR CONDUIT RUN

DISTRIBUTION PANELBOARD

CIRCUIT HOMERUN

CONCEALED OR EMBEDDED CONDUIT RUN

2 SINGLE POLE WALL SWITCHES IN ONE SWITCH PLATE

SINGLE POLE WALL SWITCH

S

ELECTRICAL RISER

PULL BOX / JUNCTION BOX WITH COVER PLATE

ELECTRICAL SYMBOLS :

WALL FAN CONTROL SWITCHFC

2-36 WATTS, 230 VOLTS, 60Hz, FLUORESCENT LIGHTING FIXTURE,

WALL FAN, 65 WATTS, 230V, 60Hz WF

S

GROUNDING SYSTEM

2

1 18 WATTS COMPACT FLUORESCENT LAMP WITH MEDIUM BASE, KEYLESS TYPE PORCELAIN RECEPTACLE OUTLET

DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE, 20A, 250VOLTS "WP" DENOTES WEATHERPROOF OUTLET

180

0 m

m

310

0 m

m (M

IN.)

OVERHEAD SERVICE ENTRANCE: 230

V, 1Ø, 2W, 60Hz., A.C. WITH 20mmØ

TYPE "F" CONDULET, WEATHERHEAD

2 - 5.5mm² THWN + 1-5.5mm²

TW (G) in 20mmØ RSC

M

"DP"

GROUNDING SYSTEM

16mmØ X 2400mm LENGTH

COPPERCLAD GROUNDING

ROD

5.5mm² TW GROUND WIRE

in 15mmØ C - CLAMPED TO

COPPER-CLAD GROUNDING

ROD

180

0 m

m

GROUND FLOOR LEVEL

FINISHED GRADE LEVEL

BU

ILD

ING

LIN

E

M

WF WF

WF WF

SURFACED CEILING

MOUNTED

BOX TYPE

PDF Compressor Pro