Data sheet SONOMETER™2000 Ultrasonic heat meter DH-SMT/PL VD.SH.A1.02 © Danfoss 06/2006 1 Description/Application The SONOMETER™2000 is an ultrasonic heat meter especially designed for measuring the water and energy consumption in district heating networks. The range of used dimensions from DN 25 to DN 80 enables measuring of flows from 0,06 to 80 m 3 /h. The SONOMETER™2000 is designed for and approved to counter settlements acc. to OIML R75 class 4 and EN 1434. Features - High performance accuracy. - Measurements are not affected by, the presence of contaminating particles, chemical substances or magnetite in the district heating water. - Static metering with no moving parts means no wear and tear. - Wide dynamic range. - Can be mounted horizontally or vertically. - Low pressure drop. - Compact design. - Ultrasonic signals are insensitive to layers due to direct shot. The SONOMETER™2000 is able to handle 3 types of applications: District heating/boiler application Chilled water application Combined heating/cooling application

Transcript of SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

Page 1: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

Data sheet

SONOMETER™2000Ultrasonic heat meter

DH-SMT/PL VD.SH.A1.02 © Danfoss 06/2006 1

Description/Application The SONOMETER™2000 is an ultrasonic heat meter especially designed for measuring the water and energy consumption in district heating networks.The range of used dimensions from DN 25 to DN 80 enables measuring of flows from 0,06 to 80 m3/h. The SONOMETER™2000 is designed for and approved to counter settlements acc. to OIML R75 class 4 and EN 1434.

Features- High performance accuracy.- Measurements are not affected by, the

presence of contaminating particles, chemical substances or magnetite in the district heating water.

- Static metering with no moving parts means no wear and tear.

- Wide dynamic range.- Can be mounted horizontally or vertically.- Low pressure drop.- Compact design.- Ultrasonic signals are insensitive to layers due

to direct shot.

The SONOMETER™2000 is able to handle 3 types of applications:

District heating/boiler application Chilled water application

Combined heating/cooling application

Page 2: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

SONOMETER™2000 – Ultrasonic heat meterData sheet

DH-SMT/PLVD.SH.A1.02 © Danfoss 06/20062

Ordering The SONOMETER™2000 build-up number system, in which the individual part elements are defined.

A B B B C DD EF G H K L MM NN P

- - -

Connections (sets)No tail pieces 0Tail pieces R ½” x G¾B 1Tail pieces R ¾” x G1B 2Tail pieces R 1” x G5/4B 3Tail pieces R 1½ x G2B 4Weld-on tail pieces x G1¼B AWeld-on tail pieces x G2B B

Energy calculator, type INFOCAL 5without energy calculator 00for district heating, flow meter in forward pipe 0Ffor district heating, flow meter in return pipe 0Rfor chilled water, flow meter in forward pipe (cold pipe) CF*)for chilled water, flow meter in return pipe (hot pipe) CR*)for combined cooling/heating, flow meter in forward pipe (hot pipe in winter) SF*)for combined cooling/heating, flow meter in return pipe (cold pipe in winter) SR*)*) CR/CF, SR/SF only available with country code NN = 00

Verification0 Without type approval mark1 With approval mark

2 With approval mark and verification

3 With approval mark, verification and certificate

Country codeCountry code 00, DE, SE, AT etc.Neutral country code 00 is with documentation in English

Extra functions00 Standard (no extra function)0A Accounting dateT0 Tariff functionTA Tariff and accounting date

Display units1 GJ2 KWh3 MWh4 Gcal

Optional modules0 No modules1 Data input, input A and B2 Data output, 2 pulse output CE, CV3 M-bus module and input A and B

Temp. sensor pocket sets0 No accessoriesA 40 mm brass pocketB 85 mm brass pocketC 120 mm brass pocketK 85 mm steel pocketsL 120 mm steel pocketsM 155 mm steel pocketsN 210 mm steel pocketsV ½” x 10 mm adapter for direct sensorS Ball valve DN 15T Ball valve DN 20U Ball valve DN 25

Sensor type10 No sensors included1A Pt 500, direct sensor 1.5 m cable1B Pt 500, direct sensor 3 m cable1C Pt 500 pocket sensor 6 mm, 1.5 m cable1D Pt 500 pocket sensor 6 mm, 3 m cable1E Pt 500 pocket sensor 6 mm, 5 m cable1F Pt 500 pocket sensor 6 mm, 10 m cable1G Pt 500 pocket sensor 6 mm, 20 m cable

Voltage supply0 No power supply1 3,6 V battery supply2 230 V a.c. supply3 24 V a.c. supply

Flow meter

Size Qn

(m3/h) Cal.PN

16 25 40Without flow meter 0 BBB 0 BBB 0 BBB260 mm x G1¼B 3,5 EN G202DN 25 3,5 EN D203260 mm x G1¼B 6 EN G204DN 25 6 EN D206DN 32 6 EN D207300 mm x G2B 10 EN G205DN 40 10 EN D208DN 50 15 EN D209DN 65 25 EN D210DN 80 40 EN D211DN 50 36 Std 0300 0300 0300DN 65 60 Std 0301 0301 0301DN 100 60 EN 0302 0302 0302DN 80 100 Std 0303 0303 0303DN 100 180 Std 0306 0306 0306DN 125 100 EN 0304 0304 0304DN 125 250 Std 0307 0307 0307DN 150 150 EN 0305 0305 0305DN 150 360 Std 0309 0309 0309DN 200 250 EN 0308 0308 0308DN 200 600 Std 0311 0311 0311DN 250 400 EN 0310 0310 0310DN 250 1000 Std 0312 0312 0312DN 300 1500 Std 0313 0313 0313DN 350 2000 Std 0314 0314 0314DN 400 2500 Std 0315 0315 0315DN 500 3000 Std 0316 0316 0316DN 600 3500 Std 0317 0317DN 700 4000 Std 0318 0318DN 800 4500 Std 0319 0319DN 1000 5000 Std 0320 0320DN 1200 6000 Std 0321

Number system for the flow meter, type SONO 2500 CT, flow part for SONOMETER™2000

Number system for the flow meter pulse code for INFOCAL 5 intended for SONOMETER™3000

Page 3: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

Data sheet

DH-SMT/PL VD.SH.A1.02 © Danfoss 06/2006 3

SONOMETER™2000 – Ultrasonic heat meter

Ordering examples Complete heat meter SONOMETER™2000

A B B B C DD EF G H K L MM NN P

G 2 0 5 4 - 0R 1D B - 1 2 1 00 - PL 1

The complete heat meter SONOMETER™2000 consisting of flow meter type SONO 2500 CT, Q

n=10 m3/h, PN 25, size 300 mm x G2B; tail pieces

R 1½ x G2B; energy calculator type INFOCAL 5 for district heating and flow meter in return pipe;

set of pocket sensors 6 mm, type Pt 500 with 3 m cable; set of 85 mm brass pocket; 3,6 V battery supply; module with data output, 2 pulse output CE, CV; display with GJ units; standard function; documentation in Polish; with approval mark.

Flow meter, type SONO 2500 CT only

A B B B C DD EF G H K L MM NN P

G 2 0 5 4 - 00 00 0 - 0 0 0 00 - PL 1

The flow meter, type SONO 2500 CT consisting of flow meter type SONO 2500 CT, Q

n=10 m3/h,

PN 25, 300 mm x G2B;

tail pieces R 1½ x G2B; documentation in Polish; with approval mark.

Energy calculator, type INFOCAL 5 with temperature sensors only

A B B B C DD EF G H K L MM NN P

0 2 0 5 0 - 0R 1D B - 1 2 1 00 - PL 1

The energy calculator, type INFOCAL 5 with temperature sensors dedicated for flow meter type SONO 2500 CT, Q

n=10 m3/h, PN 25, 300

mm x G2B; tail pieces R 1½ x G2B and consisting of energy calculator, type INFOCAL 5 without defined application;

set of pocket sensors 6 mm type Pt 500 with 3 m cable; set of 85 mm brass pocket; 3,6 V battery supply; module with data output, 2 pulse output CE, CV; display with GJ units; standard function; documentation in Polish; with approval mark.

Set of temperature sensors only

A B B B C DD EF G H K L MM NN P

J - 0 0 0 0 0 - 00 1D B - 0 0 0 00 - PL 1

The set of temperature sensors consisting of set of pocket sensors 6 mm type Pt 500 with 3 m cable; set of 85 mm brass pocket; documentation in Polish; with approval mark.

Accessories BUS communicationThe energy calculator needs a special adapter cable to communicate with a PC for signal compatibility with the RS 232 level. To access the terminals, it is necessary to use one of the supplementary modules – pulse output or input module, which, in addition to specific terminals - both have 3 terminals for connection to a PC.

Pulse output moduleModule contains 3 terminals for DATA, REQUEST and GND. There are also 2 x 2 terminals for CE, CV/Alarm. Both outputs are galvanically separate.Pulse sequence CE: 1 pulse per change in the least significant digit in the energy unit and resolution selected.Pulse sequence CV: 1 pulse per change in the least significant digit in the volume unit and resolution selected.Alarm: 1 pulse per hour for as long as the unit has detected a fault.The function is not activated in the standard configuration.

M-bus moduleThe M-bus protocol is in accordance with EN 1434-3 and EN 60870-5.For communication with an M-bus, it is necessary to fit energy calculator with an add-on module.The M-bus module contains, in addition to terminals for BUS connection, terminals for counter inputs A and B.

Page 4: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

SONOMETER™2000 – Ultrasonic heat meterData sheet

DH-SMT/PLVD.SH.A1.02 © Danfoss 06/20064

Technical data

Energy calculator, type INFOCAL 5

Heat meter EN 1434 Chilled water EN 1434 pr. A1

Approved in accordance with

Temperature range Θ: 0 ... 170 °C Θ: 2 ... 30 °C

Differential temperature ΔΘ: 3 ... 150 K ΔΘ: 2 ... 20 K

Accuracy (EN 1434 demand) Max. ± (0.5 + 3K/ΔΘ) [%] (Danfoss) Max. ± (0.1 + 2K/ΔΘ) [%]

Flow range Qn (q

p) £ 25000 m3/h

Environment class A

Temperature input

Measuring range 0 ... 170 °C

Differential temperature 1 ... 170 K

Sensor type Pt 500

Sensor connection 2 wire

Measurement resolution 0.01 °C

Flow input 1

Pulse/frequency ≤ 400 Hz 1)

Pulse ON time ≥ 0.5 ms

Pulse OFF time ≥ 1.5 ms

Pulse input A and B

Pulse/frequency ≤ 400 Hz 1)

Pulse ON time ≥ 0.5 ms

Pulse OFF time ≥ 1.5 ms

Bus outputProtocol EN 60870-5

Connection Open collector, 2400/300 baud, 3.6 V

Optical connectionProtocol EN 60870-5

Connection Optical eye, 600 baud, EN 61107

Pulse output CE and CV/Alarm

ON time > 30 ms

ON current ≤ 10 mA

External supply ≤ 24 V d.c.

OFF time with alarm Approx. 1 hour

Frequency 10 Hz

Supply data

Internal voltage 3.6 +0.1/-0.4 V d.c.

Current consumption Typically 45 mA

Battery 3.6 V lithium D cell

Battery lifetime Typically 8 years with Danfoss flow meter, 10 years with independently powered flow meter

Power supply 230 V a.c. +15/-30% 50/60 Hz or 24 V a.c.

Back-up 3.0 V CR 2032 cell (only in calculators with MM = OA, TO, TA)

Environment/safety

Generally EN 1434

Ambient temperature +5...+55 °C

Storage temperature -25...+70 °C

Enclosure IP 54 in accordance with IEC 529

Vibrations 1G, 1 & 1000 Hz in accordance with IEC 68-2-34

Free fall IEC 68-2-32

EMC EN 1434 (EN 50081-1 / 50082-1)

Personal safety EN 60730

Materials

Top PC Lexan 141R Transparent 111

Pipe/wall fitting PA 6,6 GF25

Other plastic parts ABS Cycolac GPM500

Gaskets Neoprene

Rubber bushing EPDM 50

Packaging Biodegradable cardboard1) The combined pulse frequency at flow 1, in A and B may not exceed 400 Hz, whether they are used one at a time or simultaneously.

Page 5: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

Data sheet

DH-SMT/PL VD.SH.A1.02 © Danfoss 06/2006 5

SONOMETER™2000 – Ultrasonic heat meter

Ultrasonic flow meter, type SONO 2500 CT

Nominal diameter DN 25 25 25 25 32 40 40 50 65 80

Thread connection - G1¼B G1¼ B - - G2B - - - -

Nominal flow, qp(Q

n) (m3/h) 3.5 3.5 6 6 6 10 10 15 25 40

Min. flow qi (l/h)* 35 35 60 60 60 100 100 150 250 400

Min. flow cut off (l/h) 7 7 12 12 12 20 20 30 50 80

Max. flow cut off at qs (m3/h) 7 7 9 9 9 20 20 30 50 80

Pressure loss at qp(Qn) (bar)** 0.04 0.04 0.07 0.07 0.05 0.05 0.05 0.06 0.07 0.10

Nominal heat power, kW*** 140 140 240 240 240 400 400 600 1000 1600

Water temperature +20 °C to + 150 °C (horizontal) (3.5 m3/h only 130 °C)+20 °C to + 120 °C (vertical)

Output signal, pulse/l 25 25 25 25 25 10 10 7.5 4.5 2.5

Pulse duration 3.9 msec.

Max. frequency 64 Hz

Power consumption Pmax.

< 360 µW

Iavg

100 µA

Ipeak

10 mA

Power supply From integrator, 3.65 V ± 0.1 V d.c. (Lithium battery)

Istart

(average) < 15 mA

tstart

0.15 - 2.0 sec.

Ambient temperature 0 °C to +55 °C

Storage temperature - 20 °C to +70 °C

Humidity < 80 %

Water temperature +20 °C to +150 °C (3.5 m3/h only 130 °C)

Enclosure IP 65

Electrical connection between heat calculator/flowmeter Max. 2.5 m cable (which is incl.)

Connection max. pressure 25 bar

Accuracy Better than EN 1434-1, class 2

Straight inlet pipe Min. 5 x DN

Environmental classification EN 1434-1 enviromental class C(Industrial Installations)

Installation Horizontal/vertical (no influence on accuracy)

Pipe materials W 2.1096.01 (G-CuSn5ZnPb) (3.5 m3/h also polymer comp. liner)

Transducer materials Stainless steel W 1.4435

Flange gaskets Fibre gasket (non-asbestos)

O-ring EPDM

* Min. flow, when the accuracy is better than 3 %** Pressure loss acc. to EN 1434 6.17*** Calculated at ΔT = 40 °C and q

P

Pressure drop curves

Page 6: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

SONOMETER™2000 – Ultrasonic heat meterData sheet

DH-SMT/PLVD.SH.A1.02 © Danfoss 06/20066

Temperature sensor

Type Direct mountedType DS (EN 1434)

Pocket sensorType PS (EN 1434)

Element Pt 100/500, 2-wire (EN 60751) Pt 500, 2-wire (EN 60751)

Pairing 10 °C, 80 °C, 130 °C

Media temperature 0...180 °C 0...150 °C

Response time t 0,5 Typically 0.8 sec./0.4 m/sec. See spec. sensor pocket

Medium Circulation water

Pressure rating PN 16 See spec. sensor pocket

Protection IP 67 IP 65

Pipe material W-No. 2.4816 (uns -n06600) W-No. 1.4303 (AISI 304 Ti)

Sensor pockets

Type Brass Stainless steel

Media temperature 0 - 180 °C

Medium Circulation water

Response time t 0.5Typically 9 sec./0.4 m/sec.Typically 5 sec./0.4 m/sec.

with pasta

Typically 13 sec./0.4 m/sec.Typically 5 sec./0.4 m/sec.

with pasta

Pressure rating PN 25

Material CUZN 40 Pb2 (Ms 58) W-no. 1.4571

Adapter CUZN 40 Pb2 (Ms 58)

Design and function The SONOMETER™2000 consists of set, as follows:- Ultrasonic flow meter, type SONO 2500 CT- Thermal energy calculator, type INFOCAL

5 with integral hardware and software for measuring flow rate, temperature and energy consumption

- Temperature sensors

Ultrasonic flow meter, type SONO 2500 CTThe ultrasonic flow meter measures with the assistance of directly transferring pulses between sounders, without necessity of pulse reflecting from mirror’s surfaces. Thanks to application of this innovative principle of operation the measures are characterized by accuracy and reliability, and in connection with wide range of dynamic measures those flow meters have assurance of more than 20 years operation stability.

The ultrasonic principle is used in measuring the flow. Two ultrasonic transducers functioning as both transmitter and receiver are positioned opposite each other at the inlet and outlet of the flow meter.Ultrasonic signals are transmitted between both transducers. One signal travels in the same direction as the water flow, the other travels against the flow.

District heating systems with ultrasonic flow meterMeasurement is performed by determining the time the ultrasonic signal takes to travel with and against the flow. The principle can be expressed as follows: t

up – t

down Δt

v = K = K t

up x t

down t2

tdown

= Time in the flow directiont

up = Time against the flow direction

v = Average flow velocityt = Transit timeK = Proportional factorThis measuring principle offers the advantage that it is independent of variations in the actual sound velocity of the liquid.Proportional factor K is determined by wet calibration.

Page 7: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

Data sheet

DH-SMT/PL VD.SH.A1.02 © Danfoss 06/2006 7

SONOMETER™2000 – Ultrasonic heat meter

Pulse output

BlueYellowRed

BlueYellowRed

Typical calculatorSONO 2500 CT

Energy calculator, type INFOCAL 5The energy calculator made in microprocessor’s technology is a device designed for counting energy consumption in district heating systems. Adulteration of reading by user is not possible. Reading of signals from the flow meter and from a pair of sensors the calculator in constant method counts and stores in read-only memory a data concerning energy consumption as well as other values connected with energy transfer control and necessary to settlements.

Basic functions- High accuracy thermal energy metering- Optical data reading in accordance

with EN 1434- Choice of battery, 230 V a.c. or 24 V a.c.- Instantaneous values for energy/volume flow- 24 months’ memory- Error logging with date and time

Additional functions- Battery back-up of real time clock in the event

of power failure- Tariff functions- Read-out of account date- Client-specific display format

Add-on modules- Plug-in module with data output, pulse output

for accumulated energy and water or output signal for failure

- Plug-in module with data output and 2 extra pulse inputs

- Plug-in module for M-bus communication and 2 extra pulse inputs

Advanced functions for cooling/heating applications- Separate totalizer registers for cooling/heating

applications- Zero point calibration of ΔΘ for cooling systems

Display descriptionThe energy calculator has an easily-read 8-digit LCD display with associated pictograms for the various functions. As the display has been made for several applications, there will be figures/symbols which are not used for normal district heating applications.The energy calculator has only one operating button.The display will always be configured for the application chosen, and for the selected display settings.In normal operation, the display will show cumulative energy values.

Primary itemsA short press on the operating button changes from one main menu to the next main menu.

Secondary itemsA long press changes the display to the associated sub-menu.

Serial number/client number

Maximum power/flow

Instantaneous power

Main menu

Sub-menu

Tariff record 1 and 2, tariff limits 1 and 2Temperature sensor error

Other error

Pulse indicator

Rest symbol

Page 8: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

SONOMETER™2000 – Ultrasonic heat meterData sheet

DH-SMT/PLVD.SH.A1.02 © Danfoss 06/20068

Display viewsDepending on the choice of extra modules and functions under the build-up number, the related display views are automatically opened. It is thus not necessary to define display views as these are automatically generated when ordering.

It is possible to “blank” or add display views. Changes can be made using special reprogramming software or ordered directly from Danfoss.

Maximum display views

In views of values that include the date, the display will “swap” between value and date

Page 9: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

Data sheet

DH-SMT/PL VD.SH.A1.02 © Danfoss 06/2006 9

SONOMETER™2000 – Ultrasonic heat meter

Standard display views, district heating and chilled water applications (DD=OF/OR and DD=CF/CR)1)

(K= 0, MM= 00)1)

Display menu for combined cooling/heating systems (DD=SF/SR)1)

1) please refer to Ordering paragraf on page 2

Page 10: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

SONOMETER™2000 – Ultrasonic heat meterData sheet

DH-SMT/PLVD.SH.A1.02 © Danfoss 06/200610

CalculationCalculation of energy is based on the following formula:

Energy = Volume x (THot

- TCold

) x Kfactor

(Ti)

Volume: Volume [m3] of a given amount of water

THot

: Measured temperature in the flowT

Cold: Measured temperature in the

returnK

factor (T

i): Thermal coefficient of water based

on the polynomial associated with Dr. Stuck’s tables of enthalpy and heat content

The energy calculation is made by a counter that depends on the size of the flow meter, pulse frequency and legal requirements.The calculator always carries out at least one energy calculation every 10 minutes if the flow meter has not sent enough pulses to prompt an energy calculation.

Temperature measurementThe energy calculator has been developed for paired Pt 500.For each energy calculation, a temperature measurement is taken according to a dual-slope measuring principle, and a measurement of two reference resistances. This compensates for temperature and long-term drift, and any effect of supply frequency (hum) on the temperature measurements is compensated for.Contact resistance between the top and bottom parts is compensated for by a three-conductor measurement.

Permanent memory/account date readingThe LOG of the calculator is updated every 10 minutes with all the cumulative values: - Date, - S energy, - S water, - S records 1 and 2, - peak values of energy or flow, - counter records A and B, - date/time and info code.The energy calculator allows for two possible account date outputs.If the use of account date output has been selected during configuration, the above data are stored to enable output to a selected date in the year. All data are stored for a further 24 months in a record for possible subsequent study of operating conditions in the system.

Accounting date output The accounting date is set as standard to June 1. Secondary accounting date is inactive.This function with associated display menu settings is activated in the build-up number under identification key “MM”.

Tariff record In addition to the main record, 2 extra records can be used: tariff records 1 and 2.There are two tariff limit values associated with each of the two records, which can be reprogrammed using Danfoss energy calculator reprogramming software.

The following tariff types are available:- Power-based tariff, flow-based tariff, cooling

tariff, return temperature tariff, flow-controlled tariff with summation of time.

- The tariff record is set to “flow-controlled tariff” as standard, and qs is set as limit (depending of flow type).

- Tariff records are not available whenever choosing an energy calculator for combined cooling/heating.

Energy/volume maximumEnergy and volume can be outputted for the previous three months with associated dates when the maximum power occurred. Integration time can be set to 15, 30 or 60 minutes.Standard factory setting: peak volume: 15 minutes; peak energy: 60 minutes. Views are NOT active in the standard display configuration.

Error handling If energy calculator records an error, this will be indicated by a ” ” and a ”!” in the display for a sensor error or for another error. The error will similarly be recorded on the LOG. The LOG can contain up to 10 failures with a statement of date/time of occurrence of the error and eventually occurrence of the error.Using the function key, it is possible to read the error code, which is indicated by an ”F”.Resetting the error code is undertaken either using a hand terminal or by briefly separating the calculator top from the lower part and re-connecting it with the lower part, while the operating button is held down. The energy calculator is now in a reset mode, and error codes can be deleted from the display.

The following errors can be detected:F1 Forward temperature sensor is interrupted

or short-circuited.F2 Return temperature sensor is interrupted or

short-circuited.F3 Internal equipment error.F4 Differential temperature high and no flow

for 48 hours.F5 Water flow exceeds preset Qs.

Page 11: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

Data sheet

DH-SMT/PL VD.SH.A1.02 © Danfoss 06/2006 11

SONOMETER™2000 – Ultrasonic heat meter

Zero point calibration of differential temperature (only types CF/CR)Cooling systems always operate with a small Δt and a relatively high flow rate. For technical reasons no sensor pair provides completely accurate temperature difference measurements when the sensor temperature difference between forward and return flow is close to zero.The energy calculator type CF/CR contains a special zero point calibration routine that can be activated in order to minimize the temperature difference measuring failure.Normally the zero point calibration is not needed, but can be activated out in order to obtain maximum accuracy in the energy calculation.The zero point calibration function requires a short circuit between forward and return sensor in the cooling system – e.g. by installing a valve V1. (See application drawing).

Optical output The energy calculator is fitted with an optical infra-red send/receive port in accordance with IEC 61107.Protocol standard, EN 60870-3 (M-bus protocol).A reader head with a permanent magnet in accordance with EN 1434 can be used for programming/altering programming of readout data, configuration data, etc. The reader head can also be used for amendment of measuring data.

Temperature sensorsThe temperature sensor set is designed for use with the energy calculator for measurement of the energy consumption in a district heating net. To ensure an accurate measurement of the temperature difference according to EN 1434, the sensors are delivered as matched pairs. The sensor set can be supplied with type approval marking according to local demands.

Mounting Flow meter, type SONO 2500 CTThe flow meter can be mounted in either forward or return pipes. The correct direction is indicated with an arrow on the flange or on the body.When horizontally mounted, the max. liquid temperature is 150 °C .

For 3.5 m3/h max. 130 °C. The max. liquid temperature must be reduced to 120 °C when the electronics (black enclosure) is turned upwards.When vertically mounted, the max. liquid temperature is also 120 °C.

The electronics (black enclosure) must not be insulated.The length before the flow meter must at least be 5 x DN.

The flow meter must be filled completely with water during measurements.It is not necessary to use filters when using the flow meter.

Page 12: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

SONOMETER™2000 – Ultrasonic heat meterData sheet

DH-SMT/PLVD.SH.A1.02 © Danfoss 06/200612

WiringThe flow meter must be connected to the following terminals of energy calculator.- 9 red (+)- 10 yellow (signal)- 11 blue (-)

Energy calculator, type INFOCAL 5The energy calculator can be mounted in a panel, on a wall or as a compact fitting on flow meter (DN 25 - DN 50) using fittings included.It is not possible to fit energy calculator compactly on the other series. Instructions are enclosed with the product with a statement of the standard display configuration.

Wall mounting Mounting on SONO 2500 CT

Panel mounting Mounting on SONO 2500 CT

Page 13: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

Data sheet

DH-SMT/PL VD.SH.A1.02 © Danfoss 06/2006 13

SONOMETER™2000 – Ultrasonic heat meter

Dimensions Energy calculator, type INFOCAL 5

Flow meter, type SONO 2500 CT

Nominal diameter 25 25 25 25 32 40 40 50 65 80

Nominal flow, qp(Q

n) m3/h 3.5 3.5 6 6 6 10 10 15 25 40

Flange diameter D, mm 114 - - 114 139 - 148 163 184 198

Bolt circle diameter d, mm 85 - - 85 100 - 110 125 145 160

Build in length L, mm 260 260 260 260 260 300 300 270 300 300

High A, mm 78 78 78 78 78 78 78 91 91 91

Weight, kg 5.2 3.4 3.6 5.4 6.1 3.6 7.9 8.5 10.8 12.6

Flange1) dimension F, mm 100 - - 100 125 - 138 147 170 188

Internal diameter di, mm 30 30 30 30 37.2 43.4 43.4 54.5 70.3 82.5

Thread2) connection G - G1¼B G1¼ B - - G2B - - - -1) Flanges PN 25 acc. to ISO 7005-32) Thread acc. to ISO 228

Page 14: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

SONOMETER™2000 – Ultrasonic heat meterData sheet

DH-SMT/PLVD.SH.A1.02 © Danfoss 06/200614

Temperature sensor

Type Direct mountedType DS (EN 1434)

Pocket sensorType PS (EN 1434)

Diameter D (mm) ø 5,4/3,3 ø 6

Sensor length L2 (mm) 27,5 50

Cable lenght C (m) ? ?

Sensor pockets

Type Brass Stainless steel

Length L

1 (mm) 47 82 117 98 133 168 223

L (mm) 40 85 120 85 120 155 210

Diameter D1 (mm) ø 8

Dimension G G ½

Adapter nipple Ball valve

DN h H L Rp

15 29 77 64 ½”

20 29 77 73 ¾”

25 34 84 85,5 1”

Page 15: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

Data sheet

DH-SMT/PL VD.SH.A1.02 © Danfoss 06/2006 15

SONOMETER™2000 – Ultrasonic heat meter

Page 16: SONOMETER™2000 Ultrasonic heat meterData sheet SONOMETER 2000 – Ultrasonic heat meter meter ...

16

SONOMETER™2000 – Ultrasonic heat meterData sheet

VD.SH.A1.02 © Danfoss 06/2006 DH-SMT/PL