Internal Protection Transient overvoltages WASTE REDUCTION COMPLIANCE WITH INTERNATIONAL STANDARDS COST SAVINGS OVER 500 SOLUTIONS FOR SURGE PROTECTION

Transcript of SOBRETENSIONES DIGITAL PRESENTACIÓN TRANSITORIAS EN › upload › ficheros ›...

Page 1: SOBRETENSIONES DIGITAL PRESENTACIÓN TRANSITORIAS EN › upload › ficheros › TRANSIENT_OVER... · Origen. How they spread TRANSIENT OVERVOLTAGES 2 2 7 11 8 6 1 10 11 6 3 1 1 8

Internal Protection

Transient overvoltages

WASTE REDUCTIONCOMPLIANCE WITH

INTERNATIONALSTANDARDS

COST SAVINGS

OVER 500SOLUTIONS FOR

SURGEPROTECTION

Origen How they spreadTRANSIENT OVERVOLTAGES

2 2

7

8116

1

6111013

1

8

2

11

10

1

66

11

2

5

9

7

9

4

61

5

Surges due to direct lightning discharges

Discharges on building elements (corners chimneys weather vanes) that spread through the electrical installation

Discharges on antennas that spread through their cables12

Surges due to indirect lightning dischargesDischarges on overhead supply linesDischarges on overhead telephone lines

34

Direct discharges on elements close to buildings (trees metallic fences lampposts)Direct discharges to groundDischarges close to underground supply and data lines that connect equipment between different buildings

56

7

Induced surges

8

9

1011

Inductions on overhead supply and telephone linesInductions on supply and data lines inside buildings

Commutation surgesPower supply switchingCommutations in power machinery

Causes of surges and propagation mechanisms

The direct and induced surges are introduced into the building damaging electrical and electronic equipment which can even cause fires and personal injuries

For more info visit

For more info visit

Coordination

For a correct protection against overvoltages stepped and coordinated protection is required with several protection stages acting sequentially so that on one hand they are capable of supporting all the discharge current and on the other hand leave a residual voltage that is not harmful to existing equipment or that which may be installed in the future

0

12

10

8

6

4

2

0

kV600

500

400

300

200

100

V600

500

400

300

200

100

0

V600

500

400

300

200

100

0

V

0 1 2 micros 0 1 2 micros 0 1 2 micromicro ss0 20 40 60

Transient surge suppression through a stepped protection

COORDINATION IMPEDANCEDECOUPLING COIL OR LENGTH

OF 10+ METERES OF CABLE

DEVICESTYPE 1

DEVICESTYPE 2

DEVICESTYPE 2

PROTECTED EQUIPMENT

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

La soldadura exoteacutermica eficiente APLIWELDreg Secure +TRANSIENT OVERVOLTAGES

Application of 10 820 μs current impulseswith a peak current of 25 kA to obtain theircharacteristics of nominal current (In) andmaximum current (Imax)

Test according to IEC 61643 to determine In andImax up to 250 kA of current wave 820 μs

For more info visit

Protection types 1 2 amp 3 Coordinated protection

Quick selection guide

For more info visit

Domestic Domestic Domestic DomesticIndustrialIndustrial IndustrialIndustrial

ATSUB-2P 65 ATSUB-2P 65 ATSHOCK ATSOCK 25

ATSUB-4P 65 ATSUB-4P 65 ATSHOCK ATSOCK T 25

ATSUB-2P 15 ATSUB-D M 1DIN ATCOVER ATCOVERATSUB-2P 40 ATSUB-2P 40

ATSUB-4P 15 ATSUB-D ATCOVER ATCOVERATSUB 40-D ATSUB 40-D

AT-8238 AT-8238 AT-8350AT-8399 AT-8325AT-8399

AT-8287 AT-8287 3xAT-8350AT-8399 AT-8089

AT-8232 AT-8200 AT-8112 AT-8112AT-8235 AT-8235

AT-8282

ATSHOCK 30

ATSHOCK 30

ATSUB-2P 15

ATSUB-4P 15

AT-8310AT-8398

3xAT-8310AT-8398

AT-8232

AT-8282AT-8217

ATSUB 25

ATSOCK T 25

ATSUB D

ATSUB D

AT-8325AT-8399

AT-8089

AT-8216

AT-8217AT-8133 AT-8133AT-8017 AT-8017

ATSUB-2P 65AT-8238

ATSUB-2P 65AT-8238

ATSUB-4P 65AT-8287

ATSUB-4P 65AT-8287

Single phase Single phase

Single phase Single phase

Three phase Three phase

Three phase Three phase

Yes

No

No

YesYes

Main board

Central meter board

Sub-distribution

board

Residential board

No

Overhead powersupply lines

Is there any existing externallightning protection

Overhead powersupply lines

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

For more info visit

Industrial installation

2

5

4

2

3

37

7

7

6

6

6

61

1

2

3

4

5

6

7

power supply linetelephone linedata lineIT linecoaxial line

TYPE 1(direct lightning effects) ATSHOCK

Is there more than 10m of seperation cable

Decoupling coil

ATLINK

TYPE 2 (attenuated lightning effects)ATSHIELD | ATSUB | ATCOVER

TYPE 3 (attenuated electromagnetic effects)ATSOCKET | ATPLUG

TYPE 2 + 3(coordinated)

ATFONO

ATLINE

ATFREQ

ATLAN

ATSOCKET ATSUB ATCOVER

Power supply

YES NO

Telecomunication amp data

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Residential installation

ATFONO ATPLUG ATSUB ATCOVER 1

2

2

3

3

4

2

1

4

3

power supply linetelephone linecoaxial line

TYPE 1 + 2(attenuated lightning effects)

ATSHIELD ATSUB ATCOVER

TYPE 3(attenuated electromagnetic effects)

ATSOCKET ATPLUG

TYPE 2 + 3(coordinated)

ATFONO

ATFREQ

Telecomunication amp dataPower supply

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Office installation

ATSUB ATLAN

12

3

3

3

3

3

3

5

5

5

5

5

5

5

6

4

4

4

4

4

4

1

2

3

5

4

6

power supply linetelephone lineIT linecoaxial line

TYPE 1(direct lightning effects) ATSHIELD

Is there more than 10m of seperation cable

Decoupling coil

ATLINK

TYPE 2 (attenuated lightning effects)ATSUB | ATCOVER

TYPE 3 (attenuated electromagnetic effects)ATSOCKET | ATPLUG

TYPE 2 + 3(coordinarted)

ATFONO

ATLAN

ATFREQ

Power supply

YES NO

Telecomunication amp data

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Photovoltaic installations

TYPE 1 + 2(direct or attenuated lightning effects)

ATSHIELDATSUB

TYPE 2(attenuated lightning effects ) ATPV

power supply lineDC power line

Direct current Power supply

1 2

ATPV ATSHIELD

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

Follow us

APLICACIONES TECNOLOacuteGICAS SAParque Tecnoloacutegico of Valencia

CNicolaacutes Copeacuternico St4 - 46980 Paterna (Valencia) SPAIN

(+34)961 318 250 atsaat3wcom at3wcom

EXOTHERMICWELDING

EARTHING

PERMANENTOVERVOLTAGES

TRANSIENTOVERVOLTAGES

AIR TERMINALSAND ACCESSORIES

LOCAL STORMDETECTION

Page 2: SOBRETENSIONES DIGITAL PRESENTACIÓN TRANSITORIAS EN › upload › ficheros › TRANSIENT_OVER... · Origen. How they spread TRANSIENT OVERVOLTAGES 2 2 7 11 8 6 1 10 11 6 3 1 1 8

Origen How they spreadTRANSIENT OVERVOLTAGES

2 2

7

8116

1

6111013

1

8

2

11

10

1

66

11

2

5

9

7

9

4

61

5

Surges due to direct lightning discharges

Discharges on building elements (corners chimneys weather vanes) that spread through the electrical installation

Discharges on antennas that spread through their cables12

Surges due to indirect lightning dischargesDischarges on overhead supply linesDischarges on overhead telephone lines

34

Direct discharges on elements close to buildings (trees metallic fences lampposts)Direct discharges to groundDischarges close to underground supply and data lines that connect equipment between different buildings

56

7

Induced surges

8

9

1011

Inductions on overhead supply and telephone linesInductions on supply and data lines inside buildings

Commutation surgesPower supply switchingCommutations in power machinery

Causes of surges and propagation mechanisms

The direct and induced surges are introduced into the building damaging electrical and electronic equipment which can even cause fires and personal injuries

For more info visit

For more info visit

Coordination

For a correct protection against overvoltages stepped and coordinated protection is required with several protection stages acting sequentially so that on one hand they are capable of supporting all the discharge current and on the other hand leave a residual voltage that is not harmful to existing equipment or that which may be installed in the future

0

12

10

8

6

4

2

0

kV600

500

400

300

200

100

V600

500

400

300

200

100

0

V600

500

400

300

200

100

0

V

0 1 2 micros 0 1 2 micros 0 1 2 micromicro ss0 20 40 60

Transient surge suppression through a stepped protection

COORDINATION IMPEDANCEDECOUPLING COIL OR LENGTH

OF 10+ METERES OF CABLE

DEVICESTYPE 1

DEVICESTYPE 2

DEVICESTYPE 2

PROTECTED EQUIPMENT

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

La soldadura exoteacutermica eficiente APLIWELDreg Secure +TRANSIENT OVERVOLTAGES

Application of 10 820 μs current impulseswith a peak current of 25 kA to obtain theircharacteristics of nominal current (In) andmaximum current (Imax)

Test according to IEC 61643 to determine In andImax up to 250 kA of current wave 820 μs

For more info visit

Protection types 1 2 amp 3 Coordinated protection

Quick selection guide

For more info visit

Domestic Domestic Domestic DomesticIndustrialIndustrial IndustrialIndustrial

ATSUB-2P 65 ATSUB-2P 65 ATSHOCK ATSOCK 25

ATSUB-4P 65 ATSUB-4P 65 ATSHOCK ATSOCK T 25

ATSUB-2P 15 ATSUB-D M 1DIN ATCOVER ATCOVERATSUB-2P 40 ATSUB-2P 40

ATSUB-4P 15 ATSUB-D ATCOVER ATCOVERATSUB 40-D ATSUB 40-D

AT-8238 AT-8238 AT-8350AT-8399 AT-8325AT-8399

AT-8287 AT-8287 3xAT-8350AT-8399 AT-8089

AT-8232 AT-8200 AT-8112 AT-8112AT-8235 AT-8235

AT-8282

ATSHOCK 30

ATSHOCK 30

ATSUB-2P 15

ATSUB-4P 15

AT-8310AT-8398

3xAT-8310AT-8398

AT-8232

AT-8282AT-8217

ATSUB 25

ATSOCK T 25

ATSUB D

ATSUB D

AT-8325AT-8399

AT-8089

AT-8216

AT-8217AT-8133 AT-8133AT-8017 AT-8017

ATSUB-2P 65AT-8238

ATSUB-2P 65AT-8238

ATSUB-4P 65AT-8287

ATSUB-4P 65AT-8287

Single phase Single phase

Single phase Single phase

Three phase Three phase

Three phase Three phase

Yes

No

No

YesYes

Main board

Central meter board

Sub-distribution

board

Residential board

No

Overhead powersupply lines

Is there any existing externallightning protection

Overhead powersupply lines

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

For more info visit

Industrial installation

2

5

4

2

3

37

7

7

6

6

6

61

1

2

3

4

5

6

7

power supply linetelephone linedata lineIT linecoaxial line

TYPE 1(direct lightning effects) ATSHOCK

Is there more than 10m of seperation cable

Decoupling coil

ATLINK

TYPE 2 (attenuated lightning effects)ATSHIELD | ATSUB | ATCOVER

TYPE 3 (attenuated electromagnetic effects)ATSOCKET | ATPLUG

TYPE 2 + 3(coordinated)

ATFONO

ATLINE

ATFREQ

ATLAN

ATSOCKET ATSUB ATCOVER

Power supply

YES NO

Telecomunication amp data

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Residential installation

ATFONO ATPLUG ATSUB ATCOVER 1

2

2

3

3

4

2

1

4

3

power supply linetelephone linecoaxial line

TYPE 1 + 2(attenuated lightning effects)

ATSHIELD ATSUB ATCOVER

TYPE 3(attenuated electromagnetic effects)

ATSOCKET ATPLUG

TYPE 2 + 3(coordinated)

ATFONO

ATFREQ

Telecomunication amp dataPower supply

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Office installation

ATSUB ATLAN

12

3

3

3

3

3

3

5

5

5

5

5

5

5

6

4

4

4

4

4

4

1

2

3

5

4

6

power supply linetelephone lineIT linecoaxial line

TYPE 1(direct lightning effects) ATSHIELD

Is there more than 10m of seperation cable

Decoupling coil

ATLINK

TYPE 2 (attenuated lightning effects)ATSUB | ATCOVER

TYPE 3 (attenuated electromagnetic effects)ATSOCKET | ATPLUG

TYPE 2 + 3(coordinarted)

ATFONO

ATLAN

ATFREQ

Power supply

YES NO

Telecomunication amp data

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Photovoltaic installations

TYPE 1 + 2(direct or attenuated lightning effects)

ATSHIELDATSUB

TYPE 2(attenuated lightning effects ) ATPV

power supply lineDC power line

Direct current Power supply

1 2

ATPV ATSHIELD

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

Follow us

APLICACIONES TECNOLOacuteGICAS SAParque Tecnoloacutegico of Valencia

CNicolaacutes Copeacuternico St4 - 46980 Paterna (Valencia) SPAIN

(+34)961 318 250 atsaat3wcom at3wcom

EXOTHERMICWELDING

EARTHING

PERMANENTOVERVOLTAGES

TRANSIENTOVERVOLTAGES

AIR TERMINALSAND ACCESSORIES

LOCAL STORMDETECTION

Page 3: SOBRETENSIONES DIGITAL PRESENTACIÓN TRANSITORIAS EN › upload › ficheros › TRANSIENT_OVER... · Origen. How they spread TRANSIENT OVERVOLTAGES 2 2 7 11 8 6 1 10 11 6 3 1 1 8

For more info visit

Coordination

For a correct protection against overvoltages stepped and coordinated protection is required with several protection stages acting sequentially so that on one hand they are capable of supporting all the discharge current and on the other hand leave a residual voltage that is not harmful to existing equipment or that which may be installed in the future

0

12

10

8

6

4

2

0

kV600

500

400

300

200

100

V600

500

400

300

200

100

0

V600

500

400

300

200

100

0

V

0 1 2 micros 0 1 2 micros 0 1 2 micromicro ss0 20 40 60

Transient surge suppression through a stepped protection

COORDINATION IMPEDANCEDECOUPLING COIL OR LENGTH

OF 10+ METERES OF CABLE

DEVICESTYPE 1

DEVICESTYPE 2

DEVICESTYPE 2

PROTECTED EQUIPMENT

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

La soldadura exoteacutermica eficiente APLIWELDreg Secure +TRANSIENT OVERVOLTAGES

Application of 10 820 μs current impulseswith a peak current of 25 kA to obtain theircharacteristics of nominal current (In) andmaximum current (Imax)

Test according to IEC 61643 to determine In andImax up to 250 kA of current wave 820 μs

For more info visit

Protection types 1 2 amp 3 Coordinated protection

Quick selection guide

For more info visit

Domestic Domestic Domestic DomesticIndustrialIndustrial IndustrialIndustrial

ATSUB-2P 65 ATSUB-2P 65 ATSHOCK ATSOCK 25

ATSUB-4P 65 ATSUB-4P 65 ATSHOCK ATSOCK T 25

ATSUB-2P 15 ATSUB-D M 1DIN ATCOVER ATCOVERATSUB-2P 40 ATSUB-2P 40

ATSUB-4P 15 ATSUB-D ATCOVER ATCOVERATSUB 40-D ATSUB 40-D

AT-8238 AT-8238 AT-8350AT-8399 AT-8325AT-8399

AT-8287 AT-8287 3xAT-8350AT-8399 AT-8089

AT-8232 AT-8200 AT-8112 AT-8112AT-8235 AT-8235

AT-8282

ATSHOCK 30

ATSHOCK 30

ATSUB-2P 15

ATSUB-4P 15

AT-8310AT-8398

3xAT-8310AT-8398

AT-8232

AT-8282AT-8217

ATSUB 25

ATSOCK T 25

ATSUB D

ATSUB D

AT-8325AT-8399

AT-8089

AT-8216

AT-8217AT-8133 AT-8133AT-8017 AT-8017

ATSUB-2P 65AT-8238

ATSUB-2P 65AT-8238

ATSUB-4P 65AT-8287

ATSUB-4P 65AT-8287

Single phase Single phase

Single phase Single phase

Three phase Three phase

Three phase Three phase

Yes

No

No

YesYes

Main board

Central meter board

Sub-distribution

board

Residential board

No

Overhead powersupply lines

Is there any existing externallightning protection

Overhead powersupply lines

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

For more info visit

Industrial installation

2

5

4

2

3

37

7

7

6

6

6

61

1

2

3

4

5

6

7

power supply linetelephone linedata lineIT linecoaxial line

TYPE 1(direct lightning effects) ATSHOCK

Is there more than 10m of seperation cable

Decoupling coil

ATLINK

TYPE 2 (attenuated lightning effects)ATSHIELD | ATSUB | ATCOVER

TYPE 3 (attenuated electromagnetic effects)ATSOCKET | ATPLUG

TYPE 2 + 3(coordinated)

ATFONO

ATLINE

ATFREQ

ATLAN

ATSOCKET ATSUB ATCOVER

Power supply

YES NO

Telecomunication amp data

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Residential installation

ATFONO ATPLUG ATSUB ATCOVER 1

2

2

3

3

4

2

1

4

3

power supply linetelephone linecoaxial line

TYPE 1 + 2(attenuated lightning effects)

ATSHIELD ATSUB ATCOVER

TYPE 3(attenuated electromagnetic effects)

ATSOCKET ATPLUG

TYPE 2 + 3(coordinated)

ATFONO

ATFREQ

Telecomunication amp dataPower supply

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Office installation

ATSUB ATLAN

12

3

3

3

3

3

3

5

5

5

5

5

5

5

6

4

4

4

4

4

4

1

2

3

5

4

6

power supply linetelephone lineIT linecoaxial line

TYPE 1(direct lightning effects) ATSHIELD

Is there more than 10m of seperation cable

Decoupling coil

ATLINK

TYPE 2 (attenuated lightning effects)ATSUB | ATCOVER

TYPE 3 (attenuated electromagnetic effects)ATSOCKET | ATPLUG

TYPE 2 + 3(coordinarted)

ATFONO

ATLAN

ATFREQ

Power supply

YES NO

Telecomunication amp data

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Photovoltaic installations

TYPE 1 + 2(direct or attenuated lightning effects)

ATSHIELDATSUB

TYPE 2(attenuated lightning effects ) ATPV

power supply lineDC power line

Direct current Power supply

1 2

ATPV ATSHIELD

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

Follow us

APLICACIONES TECNOLOacuteGICAS SAParque Tecnoloacutegico of Valencia

CNicolaacutes Copeacuternico St4 - 46980 Paterna (Valencia) SPAIN

(+34)961 318 250 atsaat3wcom at3wcom

EXOTHERMICWELDING

EARTHING

PERMANENTOVERVOLTAGES

TRANSIENTOVERVOLTAGES

AIR TERMINALSAND ACCESSORIES

LOCAL STORMDETECTION

Page 4: SOBRETENSIONES DIGITAL PRESENTACIÓN TRANSITORIAS EN › upload › ficheros › TRANSIENT_OVER... · Origen. How they spread TRANSIENT OVERVOLTAGES 2 2 7 11 8 6 1 10 11 6 3 1 1 8

La soldadura exoteacutermica eficiente APLIWELDreg Secure +TRANSIENT OVERVOLTAGES

Application of 10 820 μs current impulseswith a peak current of 25 kA to obtain theircharacteristics of nominal current (In) andmaximum current (Imax)

Test according to IEC 61643 to determine In andImax up to 250 kA of current wave 820 μs

For more info visit

Protection types 1 2 amp 3 Coordinated protection

Quick selection guide

For more info visit

Domestic Domestic Domestic DomesticIndustrialIndustrial IndustrialIndustrial

ATSUB-2P 65 ATSUB-2P 65 ATSHOCK ATSOCK 25

ATSUB-4P 65 ATSUB-4P 65 ATSHOCK ATSOCK T 25

ATSUB-2P 15 ATSUB-D M 1DIN ATCOVER ATCOVERATSUB-2P 40 ATSUB-2P 40

ATSUB-4P 15 ATSUB-D ATCOVER ATCOVERATSUB 40-D ATSUB 40-D

AT-8238 AT-8238 AT-8350AT-8399 AT-8325AT-8399

AT-8287 AT-8287 3xAT-8350AT-8399 AT-8089

AT-8232 AT-8200 AT-8112 AT-8112AT-8235 AT-8235

AT-8282

ATSHOCK 30

ATSHOCK 30

ATSUB-2P 15

ATSUB-4P 15

AT-8310AT-8398

3xAT-8310AT-8398

AT-8232

AT-8282AT-8217

ATSUB 25

ATSOCK T 25

ATSUB D

ATSUB D

AT-8325AT-8399

AT-8089

AT-8216

AT-8217AT-8133 AT-8133AT-8017 AT-8017

ATSUB-2P 65AT-8238

ATSUB-2P 65AT-8238

ATSUB-4P 65AT-8287

ATSUB-4P 65AT-8287

Single phase Single phase

Single phase Single phase

Three phase Three phase

Three phase Three phase

Yes

No

No

YesYes

Main board

Central meter board

Sub-distribution

board

Residential board

No

Overhead powersupply lines

Is there any existing externallightning protection

Overhead powersupply lines

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

For more info visit

Industrial installation

2

5

4

2

3

37

7

7

6

6

6

61

1

2

3

4

5

6

7

power supply linetelephone linedata lineIT linecoaxial line

TYPE 1(direct lightning effects) ATSHOCK

Is there more than 10m of seperation cable

Decoupling coil

ATLINK

TYPE 2 (attenuated lightning effects)ATSHIELD | ATSUB | ATCOVER

TYPE 3 (attenuated electromagnetic effects)ATSOCKET | ATPLUG

TYPE 2 + 3(coordinated)

ATFONO

ATLINE

ATFREQ

ATLAN

ATSOCKET ATSUB ATCOVER

Power supply

YES NO

Telecomunication amp data

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Residential installation

ATFONO ATPLUG ATSUB ATCOVER 1

2

2

3

3

4

2

1

4

3

power supply linetelephone linecoaxial line

TYPE 1 + 2(attenuated lightning effects)

ATSHIELD ATSUB ATCOVER

TYPE 3(attenuated electromagnetic effects)

ATSOCKET ATPLUG

TYPE 2 + 3(coordinated)

ATFONO

ATFREQ

Telecomunication amp dataPower supply

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Office installation

ATSUB ATLAN

12

3

3

3

3

3

3

5

5

5

5

5

5

5

6

4

4

4

4

4

4

1

2

3

5

4

6

power supply linetelephone lineIT linecoaxial line

TYPE 1(direct lightning effects) ATSHIELD

Is there more than 10m of seperation cable

Decoupling coil

ATLINK

TYPE 2 (attenuated lightning effects)ATSUB | ATCOVER

TYPE 3 (attenuated electromagnetic effects)ATSOCKET | ATPLUG

TYPE 2 + 3(coordinarted)

ATFONO

ATLAN

ATFREQ

Power supply

YES NO

Telecomunication amp data

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Photovoltaic installations

TYPE 1 + 2(direct or attenuated lightning effects)

ATSHIELDATSUB

TYPE 2(attenuated lightning effects ) ATPV

power supply lineDC power line

Direct current Power supply

1 2

ATPV ATSHIELD

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

Follow us

APLICACIONES TECNOLOacuteGICAS SAParque Tecnoloacutegico of Valencia

CNicolaacutes Copeacuternico St4 - 46980 Paterna (Valencia) SPAIN

(+34)961 318 250 atsaat3wcom at3wcom

EXOTHERMICWELDING

EARTHING

PERMANENTOVERVOLTAGES

TRANSIENTOVERVOLTAGES

AIR TERMINALSAND ACCESSORIES

LOCAL STORMDETECTION

Page 5: SOBRETENSIONES DIGITAL PRESENTACIÓN TRANSITORIAS EN › upload › ficheros › TRANSIENT_OVER... · Origen. How they spread TRANSIENT OVERVOLTAGES 2 2 7 11 8 6 1 10 11 6 3 1 1 8

Quick selection guide

For more info visit

Domestic Domestic Domestic DomesticIndustrialIndustrial IndustrialIndustrial

ATSUB-2P 65 ATSUB-2P 65 ATSHOCK ATSOCK 25

ATSUB-4P 65 ATSUB-4P 65 ATSHOCK ATSOCK T 25

ATSUB-2P 15 ATSUB-D M 1DIN ATCOVER ATCOVERATSUB-2P 40 ATSUB-2P 40

ATSUB-4P 15 ATSUB-D ATCOVER ATCOVERATSUB 40-D ATSUB 40-D

AT-8238 AT-8238 AT-8350AT-8399 AT-8325AT-8399

AT-8287 AT-8287 3xAT-8350AT-8399 AT-8089

AT-8232 AT-8200 AT-8112 AT-8112AT-8235 AT-8235

AT-8282

ATSHOCK 30

ATSHOCK 30

ATSUB-2P 15

ATSUB-4P 15

AT-8310AT-8398

3xAT-8310AT-8398

AT-8232

AT-8282AT-8217

ATSUB 25

ATSOCK T 25

ATSUB D

ATSUB D

AT-8325AT-8399

AT-8089

AT-8216

AT-8217AT-8133 AT-8133AT-8017 AT-8017

ATSUB-2P 65AT-8238

ATSUB-2P 65AT-8238

ATSUB-4P 65AT-8287

ATSUB-4P 65AT-8287

Single phase Single phase

Single phase Single phase

Three phase Three phase

Three phase Three phase

Yes

No

No

YesYes

Main board

Central meter board

Sub-distribution

board

Residential board

No

Overhead powersupply lines

Is there any existing externallightning protection

Overhead powersupply lines

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

For more info visit

Industrial installation

2

5

4

2

3

37

7

7

6

6

6

61

1

2

3

4

5

6

7

power supply linetelephone linedata lineIT linecoaxial line

TYPE 1(direct lightning effects) ATSHOCK

Is there more than 10m of seperation cable

Decoupling coil

ATLINK

TYPE 2 (attenuated lightning effects)ATSHIELD | ATSUB | ATCOVER

TYPE 3 (attenuated electromagnetic effects)ATSOCKET | ATPLUG

TYPE 2 + 3(coordinated)

ATFONO

ATLINE

ATFREQ

ATLAN

ATSOCKET ATSUB ATCOVER

Power supply

YES NO

Telecomunication amp data

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Residential installation

ATFONO ATPLUG ATSUB ATCOVER 1

2

2

3

3

4

2

1

4

3

power supply linetelephone linecoaxial line

TYPE 1 + 2(attenuated lightning effects)

ATSHIELD ATSUB ATCOVER

TYPE 3(attenuated electromagnetic effects)

ATSOCKET ATPLUG

TYPE 2 + 3(coordinated)

ATFONO

ATFREQ

Telecomunication amp dataPower supply

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Office installation

ATSUB ATLAN

12

3

3

3

3

3

3

5

5

5

5

5

5

5

6

4

4

4

4

4

4

1

2

3

5

4

6

power supply linetelephone lineIT linecoaxial line

TYPE 1(direct lightning effects) ATSHIELD

Is there more than 10m of seperation cable

Decoupling coil

ATLINK

TYPE 2 (attenuated lightning effects)ATSUB | ATCOVER

TYPE 3 (attenuated electromagnetic effects)ATSOCKET | ATPLUG

TYPE 2 + 3(coordinarted)

ATFONO

ATLAN

ATFREQ

Power supply

YES NO

Telecomunication amp data

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Photovoltaic installations

TYPE 1 + 2(direct or attenuated lightning effects)

ATSHIELDATSUB

TYPE 2(attenuated lightning effects ) ATPV

power supply lineDC power line

Direct current Power supply

1 2

ATPV ATSHIELD

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

Follow us

APLICACIONES TECNOLOacuteGICAS SAParque Tecnoloacutegico of Valencia

CNicolaacutes Copeacuternico St4 - 46980 Paterna (Valencia) SPAIN

(+34)961 318 250 atsaat3wcom at3wcom

EXOTHERMICWELDING

EARTHING

PERMANENTOVERVOLTAGES

TRANSIENTOVERVOLTAGES

AIR TERMINALSAND ACCESSORIES

LOCAL STORMDETECTION

Page 6: SOBRETENSIONES DIGITAL PRESENTACIÓN TRANSITORIAS EN › upload › ficheros › TRANSIENT_OVER... · Origen. How they spread TRANSIENT OVERVOLTAGES 2 2 7 11 8 6 1 10 11 6 3 1 1 8

For more info visit

Industrial installation

2

5

4

2

3

37

7

7

6

6

6

61

1

2

3

4

5

6

7

power supply linetelephone linedata lineIT linecoaxial line

TYPE 1(direct lightning effects) ATSHOCK

Is there more than 10m of seperation cable

Decoupling coil

ATLINK

TYPE 2 (attenuated lightning effects)ATSHIELD | ATSUB | ATCOVER

TYPE 3 (attenuated electromagnetic effects)ATSOCKET | ATPLUG

TYPE 2 + 3(coordinated)

ATFONO

ATLINE

ATFREQ

ATLAN

ATSOCKET ATSUB ATCOVER

Power supply

YES NO

Telecomunication amp data

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Residential installation

ATFONO ATPLUG ATSUB ATCOVER 1

2

2

3

3

4

2

1

4

3

power supply linetelephone linecoaxial line

TYPE 1 + 2(attenuated lightning effects)

ATSHIELD ATSUB ATCOVER

TYPE 3(attenuated electromagnetic effects)

ATSOCKET ATPLUG

TYPE 2 + 3(coordinated)

ATFONO

ATFREQ

Telecomunication amp dataPower supply

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Office installation

ATSUB ATLAN

12

3

3

3

3

3

3

5

5

5

5

5

5

5

6

4

4

4

4

4

4

1

2

3

5

4

6

power supply linetelephone lineIT linecoaxial line

TYPE 1(direct lightning effects) ATSHIELD

Is there more than 10m of seperation cable

Decoupling coil

ATLINK

TYPE 2 (attenuated lightning effects)ATSUB | ATCOVER

TYPE 3 (attenuated electromagnetic effects)ATSOCKET | ATPLUG

TYPE 2 + 3(coordinarted)

ATFONO

ATLAN

ATFREQ

Power supply

YES NO

Telecomunication amp data

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Photovoltaic installations

TYPE 1 + 2(direct or attenuated lightning effects)

ATSHIELDATSUB

TYPE 2(attenuated lightning effects ) ATPV

power supply lineDC power line

Direct current Power supply

1 2

ATPV ATSHIELD

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

Follow us

APLICACIONES TECNOLOacuteGICAS SAParque Tecnoloacutegico of Valencia

CNicolaacutes Copeacuternico St4 - 46980 Paterna (Valencia) SPAIN

(+34)961 318 250 atsaat3wcom at3wcom

EXOTHERMICWELDING

EARTHING

PERMANENTOVERVOLTAGES

TRANSIENTOVERVOLTAGES

AIR TERMINALSAND ACCESSORIES

LOCAL STORMDETECTION

Page 7: SOBRETENSIONES DIGITAL PRESENTACIÓN TRANSITORIAS EN › upload › ficheros › TRANSIENT_OVER... · Origen. How they spread TRANSIENT OVERVOLTAGES 2 2 7 11 8 6 1 10 11 6 3 1 1 8

For more info visit

Residential installation

ATFONO ATPLUG ATSUB ATCOVER 1

2

2

3

3

4

2

1

4

3

power supply linetelephone linecoaxial line

TYPE 1 + 2(attenuated lightning effects)

ATSHIELD ATSUB ATCOVER

TYPE 3(attenuated electromagnetic effects)

ATSOCKET ATPLUG

TYPE 2 + 3(coordinated)

ATFONO

ATFREQ

Telecomunication amp dataPower supply

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Office installation

ATSUB ATLAN

12

3

3

3

3

3

3

5

5

5

5

5

5

5

6

4

4

4

4

4

4

1

2

3

5

4

6

power supply linetelephone lineIT linecoaxial line

TYPE 1(direct lightning effects) ATSHIELD

Is there more than 10m of seperation cable

Decoupling coil

ATLINK

TYPE 2 (attenuated lightning effects)ATSUB | ATCOVER

TYPE 3 (attenuated electromagnetic effects)ATSOCKET | ATPLUG

TYPE 2 + 3(coordinarted)

ATFONO

ATLAN

ATFREQ

Power supply

YES NO

Telecomunication amp data

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Photovoltaic installations

TYPE 1 + 2(direct or attenuated lightning effects)

ATSHIELDATSUB

TYPE 2(attenuated lightning effects ) ATPV

power supply lineDC power line

Direct current Power supply

1 2

ATPV ATSHIELD

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

Follow us

APLICACIONES TECNOLOacuteGICAS SAParque Tecnoloacutegico of Valencia

CNicolaacutes Copeacuternico St4 - 46980 Paterna (Valencia) SPAIN

(+34)961 318 250 atsaat3wcom at3wcom

EXOTHERMICWELDING

EARTHING

PERMANENTOVERVOLTAGES

TRANSIENTOVERVOLTAGES

AIR TERMINALSAND ACCESSORIES

LOCAL STORMDETECTION

Page 8: SOBRETENSIONES DIGITAL PRESENTACIÓN TRANSITORIAS EN › upload › ficheros › TRANSIENT_OVER... · Origen. How they spread TRANSIENT OVERVOLTAGES 2 2 7 11 8 6 1 10 11 6 3 1 1 8

For more info visit

Office installation

ATSUB ATLAN

12

3

3

3

3

3

3

5

5

5

5

5

5

5

6

4

4

4

4

4

4

1

2

3

5

4

6

power supply linetelephone lineIT linecoaxial line

TYPE 1(direct lightning effects) ATSHIELD

Is there more than 10m of seperation cable

Decoupling coil

ATLINK

TYPE 2 (attenuated lightning effects)ATSUB | ATCOVER

TYPE 3 (attenuated electromagnetic effects)ATSOCKET | ATPLUG

TYPE 2 + 3(coordinarted)

ATFONO

ATLAN

ATFREQ

Power supply

YES NO

Telecomunication amp data

TRANSIENT OVERVOLTAGES Protection types 1 2 amp 3 Coordinated protection

For more info visit

Photovoltaic installations

TYPE 1 + 2(direct or attenuated lightning effects)

ATSHIELDATSUB

TYPE 2(attenuated lightning effects ) ATPV

power supply lineDC power line

Direct current Power supply

1 2

ATPV ATSHIELD

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

Follow us

APLICACIONES TECNOLOacuteGICAS SAParque Tecnoloacutegico of Valencia

CNicolaacutes Copeacuternico St4 - 46980 Paterna (Valencia) SPAIN

(+34)961 318 250 atsaat3wcom at3wcom

EXOTHERMICWELDING

EARTHING

PERMANENTOVERVOLTAGES

TRANSIENTOVERVOLTAGES

AIR TERMINALSAND ACCESSORIES

LOCAL STORMDETECTION

Page 9: SOBRETENSIONES DIGITAL PRESENTACIÓN TRANSITORIAS EN › upload › ficheros › TRANSIENT_OVER... · Origen. How they spread TRANSIENT OVERVOLTAGES 2 2 7 11 8 6 1 10 11 6 3 1 1 8

For more info visit

Photovoltaic installations

TYPE 1 + 2(direct or attenuated lightning effects)

ATSHIELDATSUB

TYPE 2(attenuated lightning effects ) ATPV

power supply lineDC power line

Direct current Power supply

1 2

ATPV ATSHIELD

TRANSIENT OVERVOLTAGESProtection types 1 2 amp 3 Coordinated protection

Follow us

APLICACIONES TECNOLOacuteGICAS SAParque Tecnoloacutegico of Valencia

CNicolaacutes Copeacuternico St4 - 46980 Paterna (Valencia) SPAIN

(+34)961 318 250 atsaat3wcom at3wcom

EXOTHERMICWELDING

EARTHING

PERMANENTOVERVOLTAGES

TRANSIENTOVERVOLTAGES

AIR TERMINALSAND ACCESSORIES

LOCAL STORMDETECTION

Page 10: SOBRETENSIONES DIGITAL PRESENTACIÓN TRANSITORIAS EN › upload › ficheros › TRANSIENT_OVER... · Origen. How they spread TRANSIENT OVERVOLTAGES 2 2 7 11 8 6 1 10 11 6 3 1 1 8

Follow us

APLICACIONES TECNOLOacuteGICAS SAParque Tecnoloacutegico of Valencia

CNicolaacutes Copeacuternico St4 - 46980 Paterna (Valencia) SPAIN

(+34)961 318 250 atsaat3wcom at3wcom

EXOTHERMICWELDING

EARTHING

PERMANENTOVERVOLTAGES

TRANSIENTOVERVOLTAGES

AIR TERMINALSAND ACCESSORIES

LOCAL STORMDETECTION