Slim Ceiling Mounted Duct Type - Daikin Comfort
Transcript of Slim Ceiling Mounted Duct Type - Daikin Comfort
Slim Ceiling Mounted Duct TypeFXDQ-MVJU
EDUS39-600A-F2202103
Engineering Data
60 Hz
1
FXDQ-MVJU EDUS39-600A-F2
Table of Contents
1. FeaturesandBenefits ................................................................................22. Specifications .............................................................................................33. SimplifiedDimensions ................................................................................64. Dimensions .................................................................................................95. CenterofGravity ......................................................................................126. PipingDiagrams .......................................................................................147. WiringDiagrams .......................................................................................158. Electric Characteristics .............................................................................179. SafetyDevicesSetting .............................................................................1810.CapacityTables ........................................................................................19
10.1CoolingCapacityatTe:43°F(6°C) .................................................1910.2HeatingCapacity .............................................................................1910.3CorrectionFactorforCoolingCapacityatTe:48°F(9°C) ...............19
11.FanPerformances ....................................................................................2012.SoundLevels(ReferenceData) ...............................................................24
2
FXDQ-MVJU EDUS39-600A-F2
1. Features and Benefits
Concealed, Slim, Quiet, ComfortableTheLSPslimconcealedunitisavailableforusewiththeVRVsystemstocomplementtheexistingconcealedceilingunitoptions.Withitslowprofileandlowsoundlevelthisunitcanbeinstalledintolimitedceilingvoid,bulkhead,orsoffitspace.
� Slimheight,atonly7-7/8”andservicespacerequirementofonly9-1/2”,makesitsuitableformostoftheapplicationswhereattic/bulkheadspaceislimited
� Withasoundleveldownto29dB(A)theseunitsareamongthequietestonthemarket � Factoryshippedforrearairinlet—fieldconvertibletobottomairinlet � Washablefilterincluded � Integralcondensatepumpwithverticalliftofupto21-5/8”includedasstandard � Blendsunobtrusivelywithanyinteriordecor;onlythesuctionanddischargegrillsarevisible � Externalstaticpressureselectablebyremotecontroller � Backedby10yearpartslimitedwarranty
27-9/16 in.7-7/8 in.
FXDQ07M / FXDQ09M / FXDQ12M
7-7/8 in.35-7/16 in.
FXDQ18M / FXDQ24M
Easily Convertible from factory rear return to bottom return
3
FXDQ-MVJU EDUS39-600A-F2
2. Specifications
Slim ceiling mounted duct type
Model FXDQ07MVJU FXDQ09MVJUPowersupply 1phase,60Hz,208/230V 1phase,60Hz,208/230V1,3Coolingcapacity Btu/h 7,500 9,5002,3Heatingcapacity Btu/h 8,500 10,500Casing/Color Galvanizedsteelplate GalvanizedsteelplateDimensions:(H×W×D) in. 7-7/8×27-9/16×24-7/16 7-7/8×27-9/16×24-7/16
Coil(crossfincoil)
Rows×Stages×FPI 2×12×17 2×12×17Face area ft² 1.36 1.36
Fan
Model — —Type Siroccofan SiroccofanMotoroutput HP 0.08 0.08Airflowrate(H/L) cfm 280/226 280/226Externalstaticpressure Pa 30-104 30-104
Drive Directdrive Directdrive
Temperaturecontrol Microprocessorthermostatforcoolingandheating Microprocessorthermostatforcoolingandheating
Soundabsorbingthermalinsulationmaterial Foamedpolyethylene Foamedpolyethylene
Airfilter Removal/Washable/Mildewproof Removal/Washable/Mildewproof5Soundpressurelevel(referencedata)(H/L) dBA 33/29 33/29
Weight lbs 51 51
Piping connections
Liquidpipes in. f1/4(flareconnection) f1/4(flareconnection)Gaspipes in. f1/2(flareconnection) f1/2(flareconnection)Drainpipe in. VP20(externaldia.1-1/32,internaldia.25/32) VP20(externaldia.1-1/32,internaldia.25/32)
Safetydevices Fuse,Thermalprotectorforfanmotor Fuse,Thermalprotectorforfanmotor
Refrigerantcontrol Electronicexpansionvalve ElectronicexpansionvalveConnectableoutdoorunit R410AVRV series R410AVRV series
Standardaccessories
Operationmanual,Installation manual,Paperpatternforinstallation,Drainhose,Clampmetal,Insulationforfitting,Sealingpads,Clamps,Screws,Washers,Conduitmounting
plate,Insulationtube
Operationmanual,Installation manual,Paperpatternforinstallation,Drainhose,Clampmetal,Insulationforfitting,Sealingpads,Clamps,Screws,Washers,Conduitmounting
plate,Insulationtube
Note:1. Nominalcoolingcapacitiesarebasedonthefollowingconditions:
Returnairtemperature:80°FDB,67°FWB Outdoortemperature:95°FDB Equivalentrefrigerantpipinglength:25ft(horizontal)
2. Nominalheatingcapacitiesarebasedonthefollowingconditions: Returnairtemperature:70°FDB. Outdoortemperature:47°FDB,43°FWB Equivalentrefrigerantpipinglength:25ft(horizontal)
3. Capacitiesarenet,includingadeductionforcooling(anadditionforheating)forindoorfanmotorheat.4. Externalstaticpressureischangeabletochangeovertheconnectorsinsideelectricalbox,thispressuremeans
“Highstaticpressure–Standard”.5. Anechoicchamberconversionvalue,measuredunderJISconditions.Duringactualoperation,
thesevaluesmaybehigherasaresultofinstallationconditions.
C:3D051780A
4
FXDQ-MVJU EDUS39-600A-F2
Model FXDQ12MVJU FXDQ18MVJUPowersupply 1phase,60Hz,208/230V 1phase,60Hz,208/230V1,3Coolingcapacity Btu/h 12,000 18,0002,3Heatingcapacity Btu/h 13,500 20,000Casing/Color Galvanizedsteelplate GalvanizedsteelplateDimensions:(H×W×D) in. 7-7/8×27-9/16×24-7/16 7-7/8×35-7/16×24-7/16
Coil(crossfincoil)
Rows×Stages×FPI 3×12×17 3×12×17Face area ft² 1.36 1.89
Fan
Model — —Type Siroccofan SiroccofanMotoroutput HP 0.08 0.17Airflowrate(H/L) cfm 280/226 440/350Externalstaticpressure Pa 30-104 44-154
Drive Directdrive Directdrive
Temperaturecontrol Microprocessorthermostatforcoolingandheating Microprocessorthermostatforcoolingandheating
Soundabsorbingthermalinsulationmaterial Foamedpolyethylene Foamedpolyethylene
Airfilter Removal/Washable/Mildewproof Removal/Washable/Mildewproof5Soundpressurelevel(referencedata)(H/L) dBA 33/29 35/31
Weight lbs 51 63
Piping connections
Liquidpipes in. f1/4(flareconnection) f1/4(flareconnection)Gaspipes in. f1/2(flareconnection) f1/2(flareconnection)Drainpipe in. VP20(externaldia.1-1/32,internaldia.25/32) VP20(externaldia.1-1/32,internaldia.25/32)
Safetydevices Fuse,Thermalprotectorforfanmotor Fuse,Thermalprotectorforfanmotor
Refrigerantcontrol Electronicexpansionvalve ElectronicexpansionvalveConnectableoutdoorunit R410AVRV series R410AVRV series
Standardaccessories
Operationmanual,Installation manual,Paperpatternforinstallation,Drainhose,Clampmetal,Insulationforfitting,Sealingpads,Clamps,Screws,Washers,Conduitmounting
plate,Insulationtube
Operationmanual,Installationmanual,Paperpatternforinstallation,Drainhose,Clampmetal,
Insulationforfitting,Sealingpads,Clamps,Screws,Washers,Conduitmountingplate,
Insulationtube
Note:1. Nominalcoolingcapacitiesarebasedonthefollowingconditions:
Returnairtemperature:80°FDB,67°FWB Outdoortemperature:95°FDB Equivalentrefrigerantpipinglength:25ft(horizontal)
2. Nominalheatingcapacitiesarebasedonthefollowingconditions: Returnairtemperature:70°FDB. Outdoortemperature:47°FDB,43°FWB Equivalentrefrigerantpipinglength:25ft(horizontal)
3. Capacitiesarenet,includingadeductionforcooling(anadditionforheating)forindoorfanmotorheat.4. Externalstaticpressureischangeabletochangeovertheconnectorsinsideelectricalbox,thispressuremeans
“Highstaticpressure–Standard”.5. Anechoicchamberconversionvalue,measuredunderJISconditions.Duringactualoperation,
thesevaluesmaybehigherasaresultofinstallationconditions.
C:3D051780A
5
FXDQ-MVJU EDUS39-600A-F2
Model FXDQ24MVJUPowersupply 1phase,60Hz,208/230V1,3Coolingcapacity Btu/h 24,0002,3Heatingcapacity Btu/h 27,000Casing/Color GalvanizedsteelplateDimensions:(H×W×D) in. 7-7/8×43-5/16×24-7/16
Coil(crossfincoil)
Rows×Stages×FPI 3×12×17Face area ft² 2.44
Fan
Model —Type SiroccofanMotoroutput HP 0.17Airflowrate(H/L) cfm 580/460Externalstaticpressure Pa 44-154
Drive Directdrive
Temperaturecontrol Microprocessorthermostatforcoolingandheating
Soundabsorbingthermalinsulationmaterial Foamedpolyethylene
Airfilter Removal/Washable/Mildewproof5Soundpressurelevel(referencedata)(H/L) dBA 36/32
Weight lbs 71
Piping connections
Liquidpipes in. f3/8(flareconnection)Gaspipes in. f5/8(flareconnection)Drainpipe in. VP20(externaldia.1-1/32,internaldia.25/32)
Safetydevices Fuse,Thermalprotectorforfanmotor
Refrigerantcontrol ElectronicexpansionvalveConnectableoutdoorunit R410AVRV series
Standardaccessories Operationmanual,Installationmanual,Paperpatternforinstallation,Drainhose,Clampmetal,Insulationforfitting,Sealingpads,Clamps,Screws,Washers,Conduitmountingplate,Insulationtube
Note:1. Nominalcoolingcapacitiesarebasedonthefollowingconditions:
Returnairtemperature:80°FDB,67°FWB Outdoortemperature:95°FDB Equivalentrefrigerantpipinglength:25ft(horizontal)
2. Nominalheatingcapacitiesarebasedonthefollowingconditions: Returnairtemperature:70°FDB. Outdoortemperature:47°FDB,43°FWB Equivalentrefrigerantpipinglength:25ft(horizontal)
3. Capacitiesarenet,includingadeductionforcooling(anadditionforheating)forindoorfanmotorheat.4. Externalstaticpressureischangeabletochangeovertheconnectorsinsideelectricalbox,thispressuremeans
“Highstaticpressure–Standard”.5. Anechoicchamberconversionvalue,measuredunderJISconditions.Duringactualoperation,
thesevaluesmaybehigherasaresultofinstallationconditions.
C:3D051780A
6
FXDQ-MVJU EDUS39-600A-F2
3. Simplified Dimensions
FXDQ07-12MVJU
DFT
5183
487
Uni
t: in
. (m
m)
7
FXDQ-MVJU EDUS39-600A-F2
FXDQ18MVJU
DFT
5183
902
Uni
t: in
. (m
m)
8
FXDQ-MVJU EDUS39-600A-F2
FXDQ24MVJU
DFT
5183
913
Uni
t: in
. (m
m)
9
FXDQ-MVJU EDUS39-600A-F2
4. Dimensions
FXDQ07-12MVJU
3D05
1759
Uni
t: in
.
10
FXDQ-MVJU EDUS39-600A-F2
FXDQ18MVJU
3D05
1760
Uni
t: in
.
11
FXDQ-MVJU EDUS39-600A-F2
FXDQ24MVJU
3D05
1761
Uni
t: in
.
12
FXDQ-MVJU EDUS39-600A-F2
5. Center of Gravity
FXDQ07-12MVJU
FXDQ18MVJU4D051766
Unit: in.
4D051767
Unit: in.
13
FXDQ-MVJU EDUS39-600A-F2
FXDQ24MVJU
4D051768
Unit: in.
14
FXDQ-MVJU EDUS39-600A-F2
6. Piping Diagrams
FXDQ07-24MVJU
Unit:in.Model Gas Liquid
FXDQ07-18MVJU f1/2 f1/4FXDQ24MVJU f5/8 f3/8
4D043864N
15
FXDQ-MVJU EDUS39-600A-F2
7. Wiring Diagrams
FXDQ07-24MVJU
C: 3
D05
0501
C
NO
TES)
1.
: T
ERM
INAL
,
: C
ON
NEC
TOR
2.
: FI
ELD
WIR
ING
3. IN
CAS
E U
SIN
G C
ENTR
AL R
EMO
TE C
ON
TRO
LLER
, CO
NN
ECT
IT T
O T
HE
UN
IT IN
AC
CO
RD
ANC
E W
ITH
TH
E AT
TAC
HED
INST
ALLA
TIO
N M
ANU
AL.
4. R
EMO
TE C
OTR
OLL
ER M
OD
EL V
ARIE
S AC
CO
RD
ING
TO
TH
E C
OM
BIN
ATIO
N S
YSTE
M, C
ON
FIR
M E
NG
INEE
RIN
G M
ATER
IALS
AN
D C
ATAL
OG
S, E
TC. B
EFO
RE
CO
NN
ETIN
G.
5. W
HEN
CO
NN
ECTI
NG
TH
E IN
PUT
WIR
ES F
RO
M O
UTS
IDE,
FO
RC
ED O
FF O
R O
N/O
FF C
ON
TRO
L O
PER
ATIO
N C
AN B
E SE
LEC
TED
BY
REM
OTE
CO
NTR
OLL
ER.
IN
DET
AILS
, REF
ER T
O T
HE
INST
ALLA
TIO
N M
ANU
AL A
TTAC
HED
TO
TH
E U
NIT
.6.
SYM
BOLS
SH
OW
AS
FOLL
OW
S: R
ED: R
ED B
LK: B
LAC
K W
HT:
WH
ITE
YLW
: YEL
LOW
PPL
: PU
RPL
E G
RY:
GR
AY B
LU: B
LUE
PN
K: P
INK
OR
G: O
RAN
GE
GR
N: G
REE
N7.
CLA
SS 2
WIR
E
16
FXDQ-MVJU EDUS39-600A-F2
FXDQ07-24MVJU
ELECTRICALCOMPONENTSANDWIRINGCONNECTORSFORINDOORUNITA1P PRINTEDCIRCUITBOARDC1 CAPACITOR(M1F)F1U FUSE(F5A/250V)HAP LIGHTEMITTINGDIODE(SERVICEMONITORGREEN)KPR MAGNETICRELAY(M1P)M1F MOTOR(INDOORFAN)M1P MOTOR(DRAINPUMP)Q1M THERMALPROTECTOR(M1FEMBEDDED)R1T THERMISTOR(AIR)R2T THERMISTOR(COIL-1)R3T THERMISTOR(COIL-2)S1L FLOATSWITCHT1R TRANSFORMER(208-230V/25V)V1TR PHASECONTROLCIRCUITX1M TERMINALBLOCKX2M TERMINALBLOCKY1E ELECTRONICEXPANSIONVALVEZ1C·Z2C NOISEFILTER(FERRITECORE)CONNECTORFOROPTIONALPARTSX16A CONNECTOR(ADAPTORFORWIRING)X18A CONNECTOR(WIRINGADAPTORFORELECTRICALAPPENDICES)
C:3D050501C
17
FXDQ-MVJU EDUS39-600A-F2
8. Electric Characteristics
FXDQ07-24MVJU
ModelPowersupply IFM Input(W)
SCCRHz Volts Voltagerange MCA MOP KW FLA Cooling Heating
FXDQ07MVJU
60 208/230V Max.253VMin.187V
0.9 15 0.062 0.7 92 73
SCCRkArms,Symmetrical
@600VMAX:5
FXDQ09MVJU 0.9 15 0.062 0.7 92 73FXDQ12MVJU 0.9 15 0.062 0.7 95 76FXDQ18MVJU 1.3 15 0.13 1.0 185 170FXDQ24MVJU 1.4 15 0.13 1.1 192 179
Symbol:MCA: Min.CircuitAmps(A)MOP: Max.OvercurrentProtectiveDevice(A)KW: FanMotorRatedOutput(kW)FLA: FullLoadAmps(A)IFM: IndoorFanMotorSCCR:Short-CircuitCurrentRating
Note:1.Voltagerange Unitsaresuitableforuseonelectricalsystemswherevoltagesuppliedtounitterminalsisnotbeloworabovelistedrangelimits.
2.Maximumallowablevoltageunbalancebetweenphasesis2%.3.MCA/MOP MCA=1.25×FLA MOP≤4×FLA (Nextlowerstandardfuseraring.Min.15A)
4.SelectwiresizebasedontheMCA.
C:4D051757
18
FXDQ-MVJU EDUS39-600A-F2
9. Safety Devices Setting
Model FXDQ07MVJU FXDQ09MVJU FXDQ12MVJU FXDQ18MVJU FXDQ24MVJUPrintedcircuitboardfuse A1P 250V,5A 250V,5A 250V,5A 250V,5A 250V,5A
Fanmotorthermalprotector °F OFF:266±9ON:181±27
OFF:266±9ON:181±27
OFF:266±9ON:181±27
OFF:266±9ON:181±27
OFF:266±9ON:181±27
C:3D051758
19
FXDQ-MVJU EDUS39-600A-F2
10. Capacity Tables10.1 Cooling Capacity at Te: 43°F (6°C)
Model
Indoorairtemp.°FWB(°CWB)(Te:43°F(6°C))61(16.1) 64(17.8) 67(19.4) 70(21.1) 72(22.2) 75(23.9)
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH
FXDQ07MVJU 5.9 5.2 6.7 6.1 7.5 6.3 8.0 6.4 8.1 6.5 8.2 6.5FXDQ09MVJU 7.5 6.2 8.5 7.2 9.5 7.3 10.1 7.1 10.2 7.1 10.4 7.0FXDQ12MVJU 9.5 7.5 10.7 7.9 12.0 8.8 12.7 8.6 12.9 8.5 13.1 8.5FXDQ18MVJU 14.2 10.8 16.1 12.7 18.0 12.9 19.1 12.6 19.3 12.5 19.7 12.2FXDQ24MVJU 18.9 14.0 21.5 16.1 24.0 16.4 25.5 17.3 25.8 16.8 26.3 15.8
TC: Totalcapacity:MBHSHC:Sensibleheatcapacity:MBH
Note:1.ThesecapacitytablescanbeusedwhenselectingaVRVindoorunit.TheactualcapacityoftheVRVsystemdependsonfactorssuchastheselectedmodelofoutdoorunits,outdoorairtemperatureandpipinglength.PleaseconfirmthatthecorrectedcapacityoftheVRVsystemsatisfiestherequiredheatload.
2. showsratedcondition.
10.2 Heating Capacity
Model
Indoorairtemp.°FDB(°CDB)(Tc:115°F(46°C))62(16.7) 65(18.3) 68(20.0) 70(21.1) 72(22.2) 75(23.9)
TC TC TC TC TC TCMBH MBH MBH MBH MBH MBH
FXDQ07MVJU 9.3 9.2 8.7 8.5 8.1 7.7FXDQ09MVJU 11.8 11.7 11.1 10.5 10.3 9.7FXDQ12MVJU 14.9 14.7 14.0 13.5 13.0 12.3FXDQ18MVJU 22.3 22.1 21.0 20.0 19.5 18.4FXDQ24MVJU 29.7 29.5 28.0 27.0 26.0 24.5
TC:Totalcapacity:MBH
Note:1.ThesecapacitytablescanbeusedwhenselectingaVRVindoorunit.TheactualcapacityoftheVRVsystemdependsonfactorssuchastheselectedmodelofoutdoorunits,outdoorairtemperatureandpipinglength.PleaseconfirmthatthecorrectedcapacityoftheVRVsystemsatisfiestherequiredheatload.
2. showsratedcondition.
10.3 Correction Factor for Cooling Capacity at Te: 48°F (9°C)
Refertothecorrectionfactortablebelowwhenamini-splitindoorunit isconnectedtoaVRVHeatPumpsystemusingaBranchPortbox.
ModelIndoorairtemp.°FWB(°CWB)(Te:48°F(9°C))
57(13.9) 61(16.1) 64(17.8) 67(19.4) 70(21.1) 72(22.2) 75(23.9)TC SHF TC SHF TC SHF TC SHF TC SHF TC SHF TC SHF
FXDQ07MVJU 0.68 1.12 0.70 1.17 0.75 1.12 0.79 1.09 0.82 1.06 0.84 1.05 0.85 1.05FXDQ09MVJU 0.68 1.12 0.70 1.17 0.75 1.12 0.79 1.09 0.82 1.06 0.84 1.05 0.85 1.05FXDQ12MVJU 0.69 1.13 0.71 1.17 0.75 1.13 0.78 1.09 0.80 1.07 0.82 1.06 0.84 1.06FXDQ18MVJU 0.68 1.14 0.70 1.17 0.75 1.12 0.79 1.08 0.82 1.07 0.83 1.06 0.86 1.05FXDQ24MVJU 0.67 1.15 0.71 1.16 0.76 1.11 0.80 1.08 0.83 1.06 0.84 1.06 0.86 1.05
TC: TotalcapacitySHF:Sensibleheatfactor
CA14A307C
20
FXDQ-MVJU EDUS39-600A-F2
11. Fan Performances
FXDQ07-09MVJU
3D052851
Note:1.Theremotecontrollercanbeusedtoswitchbetween“high”and“low”.2.Theairflowissetto“standard”beforeleavingthefactory. Itispossibletoswitchbetween“standardESP”and“highESP”bytheremotecontroller.
21
FXDQ-MVJU EDUS39-600A-F2
FXDQ12MVJU
3D052852
Note:1.Theremotecontrollercanbeusedtoswitchbetween“high”and“low”.2.Theairflowissetto“standard”beforeleavingthefactory. Itispossibletoswitchbetween“standardESP”and“highESP”bytheremotecontroller.
22
FXDQ-MVJU EDUS39-600A-F2
FXDQ18MVJU
3D052853
Note:1.Theremotecontrollercanbeusedtoswitchbetween“high”and“low”.2.Theairflowissetto“standard”beforeleavingthefactory. Itispossibletoswitchbetween“standardESP”and“highESP”bytheremotecontroller.
23
FXDQ-MVJU EDUS39-600A-F2
FXDQ24MVJU
3D052854
Note:1.Theremotecontrollercanbeusedtoswitchbetween“high”and“low”.2.Theairflowissetto“standard”beforeleavingthefactory. Itispossibletoswitchbetween“standardESP”and“highESP”bytheremotecontroller.
24
FXDQ-MVJU EDUS39-600A-F2
12. Sound Levels (Reference Data)
FXDQ07-09MVJU
4D052846
25
FXDQ-MVJU EDUS39-600A-F2
FXDQ12MVJU
4D052848
26
FXDQ-MVJU EDUS39-600A-F2
FXDQ18MVJU
4D052849
27
FXDQ-MVJU EDUS39-600A-F2
FXDQ24MVJU
4D052850
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.
Cautions on product corrosion
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any inquiries, please contact your local importer, distributor and/or retailer.
©All rights reserved 03/21 FS
●Specifications, designs and other content appearing in this brochure are current as of March 2021 but subject to change without notice.