VRV CEILING MOUNTED DUCT CONNECTION TYPE - Daikin FX… · DUCT CONNECTION TYPE VRV CEILING MOUNTED...

2
DUCT CONNECTION TYPE DUCT CONNECTION TYPE VRV CEILING MOUNTED VRV CEILING MOUNTED Cooling Only (50HZ) FXMQ300DSPMY1 Series FXMQ400DSPMY1 Series FXMQ300DSPMY1 Series FXMQ400DSPMY1 Series FLEXIBILITY OF AIR SUPPLY Model using belt driven blower such that the air volume and static required can be adjusted according to the requirement. This flexibility allows for wider application. BIGGEST COOLING CAPACITY Ceiling Ducted VRV Indoor Units with the biggest cooling capacity of 34.9kW and 45kW in the market. COMPACT AND SPACE SAVING Ability to hang at ceiling space (Outdoor) (Indoor) FXMQ300 / FXMQ400 CEILING FLOOR LEVEL RA FCU SA RA FCU SA • MACHINERY ROOM • • FACTORY PRODUCTION • • INDUSTRIAL PLANT • EXCELLENT USE FOR

Transcript of VRV CEILING MOUNTED DUCT CONNECTION TYPE - Daikin FX… · DUCT CONNECTION TYPE VRV CEILING MOUNTED...

DUCT CONNECTION TYPEDUCT CONNECTION TYPEVRV CEILING MOUNTEDVRV CEILING MOUNTED

Cooling Only (50HZ)

FXMQ300DSPMY1 SeriesFXMQ400DSPMY1 SeriesFXMQ300DSPMY1 SeriesFXMQ400DSPMY1 Series

FLEXIBILITY OF AIR SUPPLYModel using belt driven blower such that the air volume and static required can be adjusted according to the requirement. This flexibility allows for wider application.

BIGGEST COOLING CAPACITYCeiling Ducted VRV Indoor Units with the biggest cooling capacity of 34.9kW and 45kW in the market.

COMPACT AND SPACE SAVINGAbility to hang at ceiling space

(Outdoor)

(Indoor)FXMQ300 / FXMQ400

CEILING

FLOOR LEVEL

RA FCU SARAFCUSA

• MACHINERY ROOM •

• FACTORY PRODUCTION •

• INDUSTRIAL PLANT • EXCELLENT USE FOR

SPECIFICATIONSSPECIFICATIONS

MODEL FXMQ300DSPMY1

Power supply 3 phase, 50Hz, 380-415V

Cooling capacity*1

kW 34.9Btu/h 119,114kcal/h 30,008

CoilType Cross fin coil (Fine louver fins and Hi-XA-tubes)Rows x Stages x Fin Pitch 3 x 26 x 1.5Face area m2 0.784

Fan

Type Sirocco fanDrive Belt driveMotor output kW 2.2 / 1.5*5

Air flow ratem3/min 93

cfm 3284External static pressure Pascal 200 / 127*3

Dimensions H x W x D mm 625 x 1,620 x 850Casing / Colour Galvanized steelWeight kg 170Sound Level*2 dB(A) 56 / 53*5

Air Filter NilSafety Device Fuse. Fan motor over current

Pipingconnections

Liquid mm Ø12.7 (Brazing)Gas mm Ø28.6 (Brazing)Drain*4 mm PS 1B internal thread

Remote controller(option)

Wired BRC1E63Wireless Nil

Temperature control Microprocessor thermostat for coolingRefrigerant control Electronic Expansion Valve

FXMQ400DSPMY1

45.0154,00038,700

4738153*3

134.22.2

58

DAIKIN AIRCONDITIONING (SINGAPORE) PTE LTD10 Ang Mo Kio Industrial Park 2 Singapore 569501Tel: 6583 8888 Fax: 6349 7311 Email: [email protected] www.daikin.com.sg

Duct Connection High Static Pressure Type

Recommended Field Ducting Installation ExampleField ducting installation example to lower operating sound level.

Notes: *1. Indoor temp.:27oCDB,19oCWB / Outdoor temp.:35oCDB / Equivalent piping length:7.5m, level difference: 0m. *2. Anechoic chamber conversion value, measured at a point downward from the unit centre, FCU with 2-meter supply duct and 1-meter return duct. These values are normally somewhat higher during actual operation as a result of ambient conditions. *3. External static pressure (ESP) can be modified by changing the motor pulleys size. The External static pressure shown is factory setting the rated value exclude filter static loss. *4. Field supply insulated condensate drainage outlet pipe with proper U-trap installation is required. Fan coil unit drainage is without drain pump system design. *5. For FXMQ300DSPMY1, if specify external static pressure fall below 127 Pascal, 1.5kW motor with motor pulley size B140-24 is recommend. Revised sound level ~53dBA. *6. FXMQ300DSPMY1 / FXMQ400DSPMY1 Capacity Index is 400. Total Capacity index of connectable indoor units must be 50%-130% of the capacity index of the outdoor unit.