    Split System Air ConditionersSkyAir

    NU-V1/Y1 Series

    Cooling Only [50Hz]

    ED24 - 631A

  • 7/27/2019 sky-air nu

    2/149

    ED24-631A

    Table of Contents i

    SkyAir NU Series Cooling Only [50Hz] ....................................1

    1. External Appearance...............................................................................2

    2. Model Name, Power Supply and Nomenclature .....................................32.1 Model Name and Power Supply...............................................................3

    2.2 Nomenclature...........................................................................................4

    3. Functions.................................................................................................53.1 NU Series.................................................................................................5

    4. Specifications..........................................................................................6

    5. Dimensions and Service Space ............................................................125.1 Indoor Unit..............................................................................................12

    5.2 Wired Remote Controller........................................................................22

    5.3 Wireless Remote Controller ...................................................................25

    5.4 Outdoor Unit ...........................................................................................26

    5.5 Installation Service Space for R26~56NU..............................................30

    6. Piping Diagrams....................................................................................32

    7. Wiring Diagrams....................................................................................347.1 Indoor Unit..............................................................................................34

    7.2 Remote Controller ..................................................................................38

    7.3 Outdoor Unit ...........................................................................................40

    7.4 Field Wiring ............................................................................................44

    8. Electric Characteristics..........................................................................458.1 R18~26NUV1 / Y1..................................................................................45

    8.2 R36~56NUV1 / Y1..................................................................................46

    9. Capacity Tables ....................................................................................479.1 Capacity Tables......................................................................................47

    9.2 Capacity Correction Factor by the Length of Refrigerant Piping............5110.Operation Limit......................................................................................52

    11.Fan Performance ..................................................................................5311.1 FDBG-NU...............................................................................................53

    11.2 FDMG-NU ..............................................................................................54

    12.Sound Level ..........................................................................................5612.1 Overall Sound Level...............................................................................56

    12.2 Octave Band Level .................................................................................58

    13.Installation .............................................................................................6113.1 Indoor Unit..............................................................................................61

    13.2 Outdoor Unit .........................................................................................10314.Accessories.........................................................................................116

    14.1 Indoor Unit............................................................................................116

    14.2 Outdoor Unit .........................................................................................118

    15.Remote Controller ...............................................................................11915.1 Operation..............................................................................................119

    16.Detail Explanation of Options..............................................................12416.1 Ceiling Mounted Cassette Type (Multi Flow) [FHC] .............................124

    16.2 Ceiling Suspended Type [FH] ..............................................................143

    16.3 Duct Connection Low Static Pressure Type [FDBG]............................144

    16.4 Outdoor Unit .........................................................................................145

  • 7/27/2019 sky-air nu

    3/149

    ED24-631A

    ii Table of Contents

  • 7/27/2019 sky-air nu

    4/149

    ED24-631A

    SkyAir NU Series Cooling Only 1

    SkyAir NU Series Cooling Only [50Hz] Model Series

    Class 18 21 26 36 42 48 51 56

    Indoor Unit

    FHC 18NU 21NU 26NU 36NU 42NU 48NU

    FH 21NU 26NU 36NU 42NU 48NU

    FDBG 18NU 21NU 26NU

    FDMG 26NU 36NU 42NU 48NU 51NU 56NU

    Outdoor Unit R 18NU 21NU 26NU 36NU 42NU 48NU 51NU 56NU

  • 7/27/2019 sky-air nu

    5/149

    External Appearance ED24-631A

    2 SkyAir NU Series Cooling Only

    1. External Appearance

    Indoor Unit

    Wired

    Remote Controller

    Wireless

    Remote Controller

    Outdoor Unit

    FHC-NU FH-NU FDBG-NU FDMG-NU

    BRC1C61(for FHC)

    BRC1NU61(for FH)

    KRC47-1(for FDBG, FDMG)

    KRC47-2KRC47-4

    (for FDBG, FDMG)

    BRC7C613W(for FHC)

    BRC7NU66(for FH)

    R18NU R21NU R26NU

    R36NU R42NU R48 51NU R56NU

  • 7/27/2019 sky-air nu

    6/149

    ED24-631A Model Name, Power Supply and Nomenclature

    SkyAir NU Series Cooling Only 3

    2. Model Name, Power Supply and Nomenclature

    2.1 Model Name and Power Supply

    Note: 1. : New Model or Changed Model

    2. Power Supply Intake : Outdoor Unit

    Indoor Unit Outdoor Unit Power Supply

    FHC18NUV1 R18NUV1

    1 phase 220~240V 50Hz

    FHC21NUV1 R21NUV1

    FHC26NUV1 R26NUV1

    FHC36NUV1 R36NUV1

    FHC26NUV1 R26NUY1

    3 phase 380~415V 50Hz(4 wires)

    FHC36NUV1 R36NUY1

    FHC42NUV1 R42NUY1

    FHC48NUV1 R48NUY1

    FH21NUV1 R21NUV1

    1 phase 220~240V 50HzFH26NUV1 R26NUV1

    FH36NUV1 R36NUV1

    FH26NUV1 R26NUY1

    3 phase 380~415V 50Hz(4 wires)

    FH36NUV1 R36NUY1

    FH42NUV1 R42NUY1

    FH48NUV1 R48NUY1

    FDBG18NUV1 R18NUV1

    1 phase 220~240V 50HzFDBG21NUV1 R21NUV1

    FDBG26NUV1 R26NUV1

    FDBG26NUV1 R26NUY1 3 phase 380~415V 50Hz

    (4 wires)

    FDMG26NUV1 R26NUV1

    1 phase 220~240V 50Hz

    FDMG36NUV1 R36NUV1

    FDMG26NUV1 R26NUY1

    3 phase 380~415V 50Hz(4 wires)

    FDMG36NUV1 R36NUY1

    FDMG42NUV1 R42NUY1

    FDMG48NUV1 R48NUY1

    FDMG51NUV1 R51NUY1

    FDMG56NUV1 R56NUY1

  • 7/27/2019 sky-air nu

    7/149

    Model Name, Power Supply and Nomenclature ED24-631A

    4 SkyAir NU Series Cooling Only

    2.2 Nomenclature

    Indoor Unit

    Outdoor Unit

    Power Supply SymbolV1 : 1 phase 220~240V 50Hz

    Indicates Major Design Category

    Capacity Indication

    DIT Products

    FHC : Ceiling Mounted Cassette Type -Multi Flow-FH : Ceiling Suspended TypeFDB : Duct Connection Low Static Pressure Type

    (Cooling Only)FDM : Duct Connection Middle Static Pressure Type

    (Cooling Only)

    G V118 NUFDM

    Power Supply SymbolV1 : 1 phase 220~240V 50HzY1 : 3 phase 380~415V 50Hz

    Indicates Major Design Category

    Capacity Indication

    Outdoor UnitR : Cooling Only

    R V118 NU

  • 7/27/2019 sky-air nu

    8/149

    ED24-631A Functions

    SkyAir NU Series Cooling Only 5

    3. Functions

    3.1 NU Series

    FHC-NU

    FH-NU

    FDBG-NU

    FDMG-NU

    { : Functions exist.

    : No Functions

    Item Feature Ceiling Mounted Casssete Type (FHC)

    Comfort

    Auto swing {Swing pattern selection {

    Switchable fan speed {

    Program "Dry" {

    High ceiling application {

    Two selectablethermo-sensors

    Wired type {

    Wireless type

    Timer selector {

    Mildew prevention Mold resistant treatment for filter {

    Work & servicing

    Drain water lift-up mechanism {

    Pre-charged for up to 10 m { (18~26)

    Pre-charged for up to 15 m { (36~48)

    Long-life filter {

    Filter sign {

    Ceiling soiling prevention {

    Control features

    Auto-restart {

    Ultra long-life filter {

    High-efficiency filter {

    Fresh air intake kit {

    Others PE fin for outdoor unit {

    Item Feature Ceiling Suspended Type (FH)

    Comfort

    Auto swing {

    Switchable fan speed {

    Program "Dry" {

    Timer selector {

    Mildew preventionMold resistant treatment for filter {

    Mildew-proofing drain pan {

    Work & servicing

    Pre-charged for up to 10 m { (21 26)

    Pre-charged for up to 15 m { (36~48)

    Long-life filter {

    Control features Auto-restart {

    Others PE fin for outdoor unit {

    Item Feature Duct Connection Low Static Pressure Type (FDBG)

    Comfort Switchable fan speed {Work & servicing Pre-charged for up to 10 m { (18~26)

    Control features Auto-restart {

    OthersPE fin for outdoor unit {

    Adjustable external static pressure {

    Item Feature Duct Connection Middle Static Pressure Type (FDMG)

    Comfort Switchable fan speed {

    Work & servicingPre-charged for up to 10 m { (26)

    Pre-charged for up to 15 m { (36~51)

    Control features Auto-restart {

    OthersPE fin for outdoor unit {

    Adjustable external static pressure {

  • 7/27/2019 sky-air nu

    9/149

  • 7/27/2019 sky-air nu

    10/149

  • 7/27/2019 sky-air nu

    11/149

  • 7/27/2019 sky-air nu

    12/149

    ED24-631A Specifications

    SkyAir NU Series Cooling Only 9

    FDBG (Duct Connection Low Static Pressure Type)

    Note: 1. The above data are based on the following conditions.

    2. Capacities are net, including a deduction for cooling for indoor fan motor heat.

    3. Refer to "11. Fan Performance" in detail.

    Model

    Indoor Unit FDBG18NUV1 FDBG21NUV1 FDBG26NUV1

    Outdoor UnitV1 R18NUV1 R21NUV1 R26NUV1

    Y1 - - R26NUY1

    1 2 Cooling Capacity (1) / (2)

    Btu/h 18,100/18,000 21,200/21,000 26,300/26,000

    kW 5.3/5.3 6.2/6.2 7.7/7.6

    kcal/h 4,580/4,560 5,340/5,290 6,630/6,550

    Indoor Unit FDBG18NUV1 FDBG21NUV1 FDBG26NUV1Dimensions HWD mm 260900580 2601,300580 2601,300580

    Coil

    Type Cross Fin Coil

    RowStagesFin Pitch 3101.75 3101.75 3101.75

    Face Area m 0.189 0.231 0.231

    Fan

    Type Sirocco Fan

    Motor Output W 45 65 65

    Air Flow Rate 3 m/min (H) 13 (L) 11 (H) 18 (L) 15 (H) 18 (L) 15

    Mass (Weight) kg 23 31 31

    PipingConnections

    Liquid mm 6.4 (Flare) 6.4 (Flare) 9.5 (Flare)

    Gas mm 15.9 (Flare) 15.9 (Flare) 15.9 (Flare)Drain mm 3/4 B (I.D.21.6 O.D.27.2) 3/4 B (I.D.21.6 O.D.27.2) 3/4 B (I.D.21.6 O.D.27.2)

    Remote Controller(Option)

    Wired KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4

    Wireless - - -

    Outdoor UnitV1 R18NUV1 R21NUV1 R26NUV1

    Y1 - - R26NUY1

    Color Ivory White Ivory

    Dimensions HWD mm 540750270 685800300 770900320

    Coil

    Type Cross Fin Coil

    RowStagesFin Pitch 2222.0 2282.0 2342.0

    Face Area m 0.372 0.465 0.634

    Comp.

    ModelV1 RC70AV1TRT NH41VMDT NH52VNHT

    Y1 - - NH52YDTT

    Type Hermetically Sealed Rotary Type

    Motor Output kW 1.7 2.2 2.5

    Fan

    Model PZ380 PZ430 P47L11S

    Type Propeller

    Motor Output W 45 53 90

    Air Flow Rate m/min 27 40 59

    Mass (Weight) kgV1 42 61 70

    Y1 - - 69

    PipingConnections

    Liquid mm 6.4 (Flare) 6.4 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 15.9 (Flare) 15.9 (Flare)

    Drain mm 18.0 (Hole) 18.0 (Hole) 26.0 (Hole)

    Safety DevicesThermal Protector for Compressor,Outdoor Fan Motor and Indoor FanMotor. Fuse.

    Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor.Internal Protector of Compressor. Reverse Phase Protector (Y1). Fuse.

    Capacity Step % 1000 1000 1000

    Refrigerant Control Capillary Tube

    Ref. PipingMax. Length m 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 30 (Equivalent Length 50m)

    Max. Height Difference m 15 15 20

    RefrigerantModel R-22 R-22 R-22

    Charge (Factory Charge) kg 1.20 (Charged for 10m) 1.50 (Charged for 10m) 2.3 (Charged for 10m)

    Ref. OilModel Refer to the name plate of compressor.

    Charge L 0.85 1.20 1.3

    Drawing No. C : 4D054295B C : 4D054288A

    Conversion Formulae

    kcal/h=kW860

    Btu/h=kW3412cfm=m/min35.3

    Cooling Equivalent Piping Length Hz, Volts

    (1) Indoor:Outdoor:

    27C(81F)DB, 19.5C(67F)WB35C(95F)DB, 24C(75F)WB

    7.5m (Horizontal) 50Hz, 220V(380V)

    (2)Indoor:Outdoor:

    27C(81F)DB, 19.0C(66F)WB35C(95F)DB, 24C(75F)WB

    7.5m (Horizontal)50Hz, 220V

    (380V)

  • 7/27/2019 sky-air nu

    13/149

    Specifications ED24-631A

    10 SkyAir NU Series Cooling Only

    FDMG (Duct Connection Middle Static Pressure Type)

    Note: 1. The above data are based on the following conditions.

    2. Capacities are net, including a deduction for cooling for indoor fan motor heat.

    3. Refer to "11. Fan Performance" in detail.

    Model

    Indoor Unit FDMG26NUV1 FDMG36NUV1 FDMG42NUV1

    Outdoor UnitV1 R26NUV1 R36NUV1 -

    Y1 R26NUY1 R36NUY1 R42NUY1

    1 2 Cooling Capacity (1) / (2)

    Btu/h 26,300/26,000 36,500/36,000 42,700/42,000

    kW 7.7/7.6 10.7/10.6 12.5/12.3

    kcal/h 6,630/6,550 9,200/9,100 10,800/10,600

    Indoor Unit FDMG26NUV1 FDMG36NUV1 FDMG42NUV1Dimensions HWD mm 3051,350680 3051,550680 3051,550680

    Coil

    Type Cross Fin Coil

    RowStagesFin Pitch 3121.75 3121.75 3121.75

    Face Area m 0.290 0.340 0.340

    Fan

    Type Sirocco Fan

    Motor Output W 125 225 225

    Air Flow Rate 3 m/min 23 37 42

    Rated Ext. Static Pressure 3 mmH2O 8.5 9.8 8.0

    Mass (Weight) kg 43 52 52

    PipingConnections

    Liquid mm 9.5 (Flare) 9.5 (Flare) 9.5 (Flare)Gas mm 15.9 (Flare) 19.1 (Flare) 19.1 (Flare)Drain mm 3/4 B (I.D.21.6 O.D.27.2) 3/4 B (I.D.21.6 O.D.27.2) 3/4 B (I.D.21.6 O.D.27.2)

    Remote Controller(Option)

    Wired KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4

    Wireless - - -

    Outdoor UnitV1 R26NUV1 R36NUV1 -

    Y1 R26NUY1 R36NUY1 R42NUY1

    Color Ivory

    Dimensions HWD mm 770900320 1,170900320 1,170900320

    Coil

    Type Cross Fin Coil

    RowStagesFin Pitch 2342.0 1521.4 1521.4

    Face Area m 0.634 1.015 1.015

    Comp.

    ModelV1 NH52VNHT JT125GA-V1@K -

    Y1 NH52YDTT JT125GA-Y1@K JT160GA-Y1@K

    Type Hermetically Sealed Rotary Type Hermetically Sealed Scroll Type

    Motor Output kW 2.5 3.00 3.75

    Fan

    Model P47L11S P47L11S P47L11S2

    Type Propeller

    Motor Output W 90 90 65+90

    Air Flow Rate m/min 59 59 92

    Mass (Weight) kgV1 70 81 -

    Y1 69 79 87

    PipingConnections

    Liquid mm 9.5 (Flare) 9.5 (Flare) 9.5 (Flare)

    Gas mm 15.9 (Flare) 19.1 (Flare) 19.1 (Flare)Drain mm 26.0 (Hole) 26.0 (Hole) 26.0 (Hole)

    Safety Devices

    Thermal Protector for Outdoor FanMotor and Indoor Fan Motor. InternalProtector of Compressor. ReversePhase Protector (Y1). Fuse.

    Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High PressureSwitch. Low Pressure Switch. Internal Protector of Compressor. Reverse PhaseProtector (Y1). Fuse. Thermo Switch (Discharge Pipe).

    Capacity Step % 1000 1000 1000

    Refrigerant Control Capillary Tube

    Ref. PipingMax. Length m 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 30 (Equivalent Length 50m)

    Max. Height Difference m 20 20 20

    RefrigerantModel R-22 R-22 R-22

    Charge (Factory Charge) kg 2.3 (Charged for 10m) 2.0 (Charged for 15m) 2.4 (Charged for 15m)

    Ref. OilModel Refer to the name plate of compressor.

    Charge L 1.3 1.4 1.4

    Drawing No. C : 4D054287A C : 3D052567B

    Conversion Formulaekcal/h=kW860Btu/h=kW3412

    cfm=m/min35.3

    Cooling Equivalent Piping Length Hz, Volts

    (1)Indoor:Outdoor:

    27C(81F)DB, 19.5C(67F)WB35C(95F)DB, 24C(75F)WB

    7.5m (Horizontal)50Hz, 220V

    (380V)

    (2)Indoor:Outdoor:

    27C(81F)DB, 19.0C(66F)WB35C(95F)DB, 24C(75F)WB

    7.5m (Horizontal)50Hz, 220V

    (380V)

  • 7/27/2019 sky-air nu

    14/149

    ED24-631A Specifications

    SkyAir NU Series Cooling Only 11

    FDMG (Duct Connection Middle Static Pressure Type)

    Note: 1. The above data are based on the following conditions.

    2. Capacities are net, including a deduction for cooling for indoor fan motor heat.3. Refer to "11. Fan Performance" in detail.

    ModelIndoor Unit FDMG48NUV1 FDMG51NUV1 FDMG56NUV1

    Outdoor Unit R48NUY1 R51NUY1 R56NUY1

    1 2 Cooling Capacity (1) / (2)

    Btu/h 49,100/48,000 52,200/51,000 57,000/56,000

    kW 14.4/14.1 15.3/15.0 16.7/16.4

    kcal/h 12,400/12,100 13,200/12,900 14,400/14,100

    Indoor Unit FDMG48NUV1 FDMG51NUV1 FDMG56NUV1

    Dimensions HWD mm 3051,550680 3051,900680 3051,900680

    Coil

    Type Cross Fin Coil

    RowStagesFin Pitch 3121.75 3121.75 3121.75

    Face Area m 0.340 0.428 0.428

    Fan

    Type Sirocco Fan

    Motor Output W 225 225 225

    Air Flow Rate 3 m/min 42 42 42

    Rated Ext. Static Pressure 3 mmH2O 8.0 9.8 9.8

    Mass (Weight) kg 52 58 58

    PipingConnections

    Liquid mm 9.5 (Flare) 9.5 (Flare) 9.5 (Flare)

    Gas mm 19.1 (Flare) 19.1 (Flare) 19.1 (Flare)Drain mm 3/4 B (I.D.21.6 O.D.27.2) 3/4 B (I.D.21.6 O.D.27.2) 3/4 B (I.D.21.6 O.D.27.2)

    Remote Controller(Option)

    Wired KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4

    Wireless - - -

    Outdoor Unit R48NUY1 R51NUY1 R56NUY1

    Color Ivory

    Dimensions HWD mm 1,345900320 1,345900320 1,345880370

    Coil

    Type Cross Fin Coil

    RowStagesFin Pitch 1601.4 1601.4 2602.0

    Face Area m 1.172 1.172 1.088

    Comp.

    Model JT170GA-Y1@K JT170GA-Y1@K JT200B-YE

    Type Hermetically Sealed Scroll Type

    Motor Output kW 4.50 4.50 4.50

    Fan

    Model P47L11S2 P47L11S2 P45J11S2

    Type Propeller

    Motor Output W 65+90 65+90 64+56

    Air Flow Rate m/min 97 97 101

    Mass (Weight) kg 92 93 114

    PipingConnections

    Liquid mm 9.5 (Flare) 9.5 (Flare) 9.5 (Flare)Gas mm 19.1 (Flare) 19.1 (Flare) 19.1 (Flare)Drain mm 26.0 (Hole) 26.0 (Hole) 26.0 (Hole)

    Safety DevicesThermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. InternalProtector of Compressor. Reverse Phase Protector (Y1). Fuse. Thermo Switch (Discharge Pipe).

    Capacity Step % 1000 1000 1000Refrigerant Control Capillary Tube

    Ref. PipingMax. Length m 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 50 (Equivalent Length 70m)

    Max. Height Difference m 20 20 30

    RefrigerantModel R-22 R-22 R-22

    Charge (Factory Charge) kg 2.6 (Charged for 15m) 2.7 (Charged for 15m) 2.8 (Charged for 5m)

    Ref. OilModel Refer to the name plate of compressor.

    Charge L 1.4 1.4 1.6

    Drawing No. C : 3D052567B

    Conversion Formulae

    kcal/h=kW860Btu/h=kW3412

    cfm=m/min35.3

    Cooling Equivalent Piping Length Hz, Volts

    (1)Indoor:Outdoor:

    27C(81F)DB, 19.5C(67F)WB35C(95F)DB, 24C(75F)WB

    7.5m (Horizontal)50Hz, 220V

    (380V)

    (2)Indoor:Outdoor:

    27C(81F)DB, 19.0C(66F)WB35C(95F)DB, 24C(75F)WB

    7.5m (Horizontal)50Hz, 220V

    (380V)

  • 7/27/2019 sky-air nu

    15/149

    Dimensions and Service Space ED24-631A

    12 SkyAir NU Series Cooling Only

    5. Dimensions and Service Space

    5.1 Indoor Unit

    5.1.1 FHC (Ceiling Mounted Cassette Type)

    FHC18NU + BYC125K-W1

    FHC21NU + BYC125K-W1

    FHC26NU + BYC125K-W1

    C : 3D054367

    4. When the temperature and humidity in the ceil ing exceed 30C and RH 80%or the fresh air is inducted into the ceiling or the unit continues 24 houroperation, an addit ional insulat ion (th ickness 10mm or more of g lasswool orpolyethylene form) is required.

    Unit (mm)

    C : 3D054368

    Unit (mm)

    4. When the temperature and humidity in the ceil ing exceed 30C and RH 80%or the fresh air is inducted into the ceiling or the unit continues 24 houroperation, an addit ional insulat ion (th ickness 10mm or more of g lasswool orpolyethylene form) is required.

  • 7/27/2019 sky-air nu

    16/149

    ED24-631A Dimensions and Service Space

    SkyAir NU Series Cooling Only 13

    FHC36NU + BYC125K-W1

    FHC42NU + BYC125K-W1

    FHC48NU + BYC125K-W1

    5.1.2 FHC with High-Efficiency Filter

    KAFP556D80 557D80 for FHC18~26NU

    C : 3D052528

    4. When the tempera tu re and humid i ty in the ce i l ing exceed 30C and RH 80%or the fresh a i r i s inducted in to the ce i l ing o r the un i t con t inues 24 houropera t ion , an add i t iona l insu la t ion ( th ickness 10mm or more o f g lasswoo l o rpo lye thylene fo rm) is requ i red .

    Unit (mm)

    Note:When other optional kit is installed, refer to the installationdrawing of its optional kit.

    6

    5

    4

    3

    2

    1

    Number Description

    Drain pipe connection

    Gas pipe connection

    Liquid pipe connection

    High efficiency filter

    Decoration panel

    Indoor unit

    Name

    Unit (mm)

    JC : 3D032975C

    290

  • 7/27/2019 sky-air nu

    17/149

    Dimensions and Service Space ED24-631A

    14 SkyAir NU Series Cooling Only

    KAFP556D160 557D160 for FHC36~48NU

    5.1.3 FHC with Fresh Air Intake Kit (Without T Joint, Duct Fan)

    KDDP55D160 for FHC18~26NU

    Note:When other optional kit is installed, refer to the installationdrawing of its optional kit.

    6

    5

    4

    3

    2

    1

    Number Description

    Drain pipe connection

    Gas pipe connection

    Liquid pipe connection

    High efficiency filter

    Decoration panel

    Indoor unit

    Name

    Unit (mm)

    J : 3D032976C

    Note:1.When installing this kit, Service Access Panel is necessary.(It is necessary when servicing.)

    2.Either one of Service Access Panel must be installed.3.Field construction.4.In case of using wireless remote controller kit, this part

    will be the infrared receiver.5.When both side intakes can not be ensured due to the

    obstacles, one side intake is acceptable.6.When installing the wireless infrared reciever to the unit,

    air inlet must be on the right side as shown.

    5

    4

    3

    2

    1

    Number Description

    Connection chamber(Left)

    Connection chamber(Right)

    Suction chamber

    Decoration panel

    Indoor unit

    Name

    JC : 3D032981D

    Unit (mm)Service Access Panel :450450mm or more

    Service Access Panel :450450mm or more

    Refer to Note 2

    Refer to Note 2

    Installation Service Access Panel

    Connection Chamber (Right)

    How to connect Chamber 4Independently(Refer to Note 5,6)

    RefrigerantPiping

    ViewNote 4

  • 7/27/2019 sky-air nu

    18/149

    ED24-631A Dimensions and Service Space

    SkyAir NU Series Cooling Only 15

    KDDP55D160 for FHC36~48NU

    5.1.4 FHC with Fresh Air Intake Kit (With T Joint, Without Duct Fan)

    KDDP55D160K for FHC18~26NU

    Connection Chamber (Right)

    How to connect Chamber 4Independently(Refer to Note 5,6)

    Service Access Panel :450450mm or more

    Service Access Panel :450450mm or more

    Refer to Note 2

    Refer to Note 2

    Installation Service Access Panel

    Note:1.When installing this kit, Service Access Panel isnecessary. (It is necessary when servicing.)

    2.Either one of Service Access Panel must be installed.3.Field construction.4.In case of using wireless remote controller kit, this part

    will be the infrared receiver.5.When both side intakes can not be ensured due to the

    obstacles, one side intake is acceptable.6.When installing the wireless infrared reciever to the unit,

    air inlet must be on the right side as shown.

    5

    4

    3

    2

    1

    Number Description

    Connecting chamber(Left)

    Connecting chamber(Right)

    Suction chamber

    Decoration panel

    Indoor unit

    Name

    JC : 3D032984D

    Unit (mm)

    RefrigerantPiping

    View Note 4

    Service Access Panel :450450mm or more

    Service Access Panel :450450mm or more

    Refer to Note 2

    Refer to Note 2

    Installation Service Access Panel

    Connecting Chamber (Right)

    How to connect Chamber 4Independently(Refer to Note 5)

    Flexible Duct

    (Accessory)

    Suction Duct (K-KFD9A)

    Optional (Accessory)

    T Joint

    (Accessory)Plate Band (Accessory)

    Note:1.When installing this kit, inspection hatch is necessary.(It is necessary when servicing.)

    2.Either one of inspection hatch must be installed.3.Field construction.

    4.This kit does not take together with Wireless Remoto Controller kit.5.When both side intakes can not be ensured due to the

    obstacles, one side intake is acceptable.

    5

    4

    3

    2

    1Number Description

    Connecting chamber(Left)

    Connecting chamber(Right)

    Suction chamber

    Decoration panel

    Indoor unitName

    JC : 3D032987D

    Unit (mm)

  • 7/27/2019 sky-air nu

    19/149

    Dimensions and Service Space ED24-631A

    16 SkyAir NU Series Cooling Only

    KDDP55D160K for FHC36~48NU

    5.1.5 FHC with Panel Spacer

    KDBP55H160WA for FHC18~26NU

    Service Access Panel :450450mm or more

    Service Access Panel :450450mm or more

    Refer to Note 2

    Refer to Note 2

    Installation Service Access Panel

    Connecting Chamber (Right)

    How to connect Chamber 4Independently(Refer to Note 5)

    Flexible Duct

    (Accessory)

    Suction Duct (K-KFD9A)

    Optional (Accessory)T Joint

    (Accessory)

    Plate Band (Accessory)

    Unit (mm)

    Note:1.When installing this kit, inspection hatch is necessary.(It is necessary when servicing.)

    2.Either one of inspection hatch must be installed.3.Field construction.4.This kit does not take together with Wireless Remoto Controller kit.5.When both side intakes can not be ensured due to the

    obstacles, one side intake is acceptable.

    5

    4

    3

    2

    1

    Number Description

    Connecting chamber(Left)

    Connecting chamber(Right)

    Suction chamber

    Decoration panel

    Indoor unit

    Name

    J : 3D032990D

    View

    Dimensionbetween

    thebottomsurface

    ofboxand

    thesurfaceofceiling

    Thickness

    ofpanelspacer

    3

    2

    1

    Number

    Panel spacer

    Decoration panel

    Indoor unit

    Name Description

    JC : 3D005390E

    Note:When other optional kit is installed, refer to the installation

    drawing of its optional kit

    Unit (mm)

  • 7/27/2019 sky-air nu

    20/149

    ED24-631A Dimensions and Service Space

    SkyAir NU Series Cooling Only 17

    KDBP55H160WA for FHC36~48NU

    5.1.6 FH (Ceiling Suspended Type)

    FH21NU

    View

    Dimensionbetween

    thebottomsurface

    ofboxand

    thesurfaceofceiling

    Thickness

    ofpanelspacer

    3

    2

    1

    Number

    Panel spacer

    Decoration panel

    Indoor unit

    Name Description

    Note:When other optional kit is installed, refer to the installation

    drawing of its optional kit

    JC : 3D005391D

    Unit (mm)

    3D054277

    Unit (mm)

  • 7/27/2019 sky-air nu

    21/149

    Dimensions and Service Space ED24-631A

    18 SkyAir NU Series Cooling Only

    FH26NU

    FH36NU

    FH42NU

    FH48NU

    3D027538F

    Unit (mm)

    3D052469

    Unit (mm)

  • 7/27/2019 sky-air nu

    22/149

    ED24-631A Dimensions and Service Space

    SkyAir NU Series Cooling Only 19

    5.1.7 FDBG (Duct Connection Low Static Pressure Type)

    FDBG18NU

    FDBG21NU

    3D048541A

    Unit (mm)

    3D048542A

    Unit (mm)

  • 7/27/2019 sky-air nu

    23/149

    Dimensions and Service Space ED24-631A

    20 SkyAir NU Series Cooling Only

    FDBG26NU

    5.1.8 FDMG (Duct Connection Middle Static Pressure Type)

    FDMG26NU

    3D048543A

    Unit (mm)

    3D048933B

    Unit (mm)

  • 7/27/2019 sky-air nu

    24/149

    ED24-631A Dimensions and Service Space

    SkyAir NU Series Cooling Only 21

    FDMG36NU

    FDMG42NU

    FDMG48NU

    FDMG51NUFDMG56NU

    3D048934B

    Unit (mm)

    3D048935B

    Unit (mm)

  • 7/27/2019 sky-air nu

    25/149

    Dimensions and Service Space ED24-631A

    22 SkyAir NU Series Cooling Only

    5.2 Wired Remote Controller

    BRC1C61 (for FHC-NU)

    BRC1NU61 (for FH-NU)

    3D028952

    Unit (mm)

    3D052351

    Unit (mm)

  • 7/27/2019 sky-air nu

    26/149

    ED24-631A Dimensions and Service Space

    SkyAir NU Series Cooling Only 23

    KRC47-1 (for FDBG-NU and FDMG-NU)

    KRC47-2 (Digital Remote Controller) (for FDBG-NU and FDMG-NU)

    KRC47-2 contains the following parts, and they are packed in one carton.

    1. Digital Remote Controller

    2. Holder

  • 7/27/2019 sky-air nu

    27/149

    Dimensions and Service Space ED24-631A

    24 SkyAir NU Series Cooling Only

    3. Control Board (Box)

    4. Wire Cable

    Cable length : 4m

    Connecting cable between 1. Digital Remote Controller and 3. Control Board (Box).

    KRC47-4 (Digital Remote Controller for Duct Heater Use) (for FDBG-NU and FDMG-NU)

    1. Digital Remote Controller

    (P0007)

    For other parts 2. Holder, 3. Control Board (Box), 4. Wire Cable will be the same as KRC 47-2.

    POWER

    COOL

    HEAT

    MED

    AUTO

    LOW

    HIGH

    FAN

    TEMP+ TEMP-

  • 7/27/2019 sky-air nu

    28/149

    ED24-631A Dimensions and Service Space

    SkyAir NU Series Cooling Only 25

    5.3 Wireless Remote Controller

    BRC7C613W (for FHC-NU)

    BRC7NU66 (for FH-NU)

    3D005912D

    Unit (mm)

    3D052347

    Unit (mm)

  • 7/27/2019 sky-air nu

    29/149

    Dimensions and Service Space ED24-631A

    26 SkyAir NU Series Cooling Only

    5.4 Outdoor Unit

    R18NU

    R21NU

    3D053564

    Unit (mm)

    3D053561

    Unit (mm)

  • 7/27/2019 sky-air nu

    30/149

    ED24-631A Dimensions and Service Space

    SkyAir NU Series Cooling Only 27

    R26NU

    R36NU

    3D054206

    Unit (mm)

    3D052425

    Unit (mm)

  • 7/27/2019 sky-air nu

    31/149

    Dimensions and Service Space ED24-631A

    28 SkyAir NU Series Cooling Only

    R42NU

    R48NUR51NU

    3D052426

    Unit (mm)

    3D052427

    Unit (mm)

  • 7/27/2019 sky-air nu

    32/149

    ED24-631A Dimensions and Service Space

    SkyAir NU Series Cooling Only 29

    R56NU

    C : 3D052527

    Unit (mm)

  • 7/27/2019 sky-air nu

    33/149

    Dimensions and Service Space ED24-631A

    30 SkyAir NU Series Cooling Only

    5.5 Installation Service Space for R26~56NU

    3D052620A

  • 7/27/2019 sky-air nu

    34/149

    ED24-631A Dimensions and Service Space

    SkyAir NU Series Cooling Only 31

    3D052620A

  • 7/27/2019 sky-air nu

    35/149

    Piping Diagrams ED24-631A

    32 SkyAir NU Series Cooling Only

    6. Piping Diagrams

    R18 21NU

    R26NU

    4D050891B

    3D053984

  • 7/27/2019 sky-air nu

    36/149

    ED24-631A Piping Diagrams

    SkyAir NU Series Cooling Only 33

    R36~56NU

    3D052278

  • 7/27/2019 sky-air nu

    37/149

    Wiring Diagrams ED24-631A

    34 SkyAir NU Series Cooling Only

    7. Wiring Diagrams

    7.1 Indoor Unit

    FHC18NUV1FHC21NUV1FHC26NUV1FHC36NUV1FHC42NUV1FHC48NUV1

    3D052066A

  • 7/27/2019 sky-air nu

    38/149

    ED24-631A Wiring Diagrams

    SkyAir NU Series Cooling Only 35

    FH21NUV1FH26NUV1FH36NUV1FH42NUV1FH48NUV1

    3D052046A

  • 7/27/2019 sky-air nu

    39/149

  • 7/27/2019 sky-air nu

    40/149

    ED24-631A Wiring Diagrams

    SkyAir NU Series Cooling Only 37

    FDMG26NUV1FDMG36NUV1FDMG42NUV1FDMG48NUV1FDMG51NUV1FDMG56NUV1

    3D052109A

  • 7/27/2019 sky-air nu

    41/149

    Wiring Diagrams ED24-631A

    38 SkyAir NU Series Cooling Only

    7.2 Remote Controller

    KRC47-1

    KRC47-2

    P1 P2 P3 P4

    OFF ON

    P5 P6

    D A B C E F

    CONTROL BOARD

    H M

    FAN

    L (ON/OFF)L

    N

    FDBG

    FDMG

    ELECTRONIC

    CONTR

    OL

    TEMPERA

    TURE

    CONTR

    OL

    (P0008-631A)

    When select the high ESP,

    connect the wire as shown

    below.

    P2 P3 P4

    A B C

    Comp.(THERMOSTAT)

    P8 P9

    P4 P3 P2 P1 P7

    LN H M

    FAN

    (ON/OFF)L

    EF A B C DComp.

    (THERMOSTAT)

    CONTROL BOARD

    FDBG

    FDMG

    THERMISTOR

    REMOTE CONTROLLER

    (P0009-631A)

    When select the high ESP,

    connect the wire as shown

    below.

    P3 P2 P1

    A B C

  • 7/27/2019 sky-air nu

    42/149

    ED24-631A Wiring Diagrams

    SkyAir NU Series Cooling Only 39

    KRC47-4

    (P0010-631A)

    When select the high ESP,

    connect the wire as shown

    below.

    P3 P2 P1

    A B C

    CONTROL BOARD

    REMOTE CONTROLLER

    DUCT HEATER(FIELD SUPPLIED)

    H

    P4 P3

    P8 P9

    P2 P1 P7

    EF A B C D

    P6

    M

    FAN

    FDBGFDMG

    (ON/OFF)

    LLN Comp.(THERMOSTAT)

    THERMISTOR

  • 7/27/2019 sky-air nu

    43/149

    Wiring Diagrams ED24-631A

    40 SkyAir NU Series Cooling Only

    7.3 Outdoor Unit

    R18NUV1

    R21NUV1

    3D032199B

    3D032200A

  • 7/27/2019 sky-air nu

    44/149

    ED24-631A Wiring Diagrams

    SkyAir NU Series Cooling Only 41

    R26NUV1

    R26NUY1

    3D053671A

    3D053670A

  • 7/27/2019 sky-air nu

    45/149

    Wiring Diagrams ED24-631A

    42 SkyAir NU Series Cooling Only

    R36NUV1

    R36NUY1

    3D051564A

    3D051536A

  • 7/27/2019 sky-air nu

    46/149

    ED24-631A Wiring Diagrams

    SkyAir NU Series Cooling Only 43

    R42NUY1

    R48NUY1

    R51NUY1

    R56NUY1

    3D051535A

    3D052107

  • 7/27/2019 sky-air nu

    47/149

    Wiring Diagrams ED24-631A

    44 SkyAir NU Series Cooling Only

    7.4 Field Wiring

    C : 4D054220C : 4D052570

  • 7/27/2019 sky-air nu

    48/149

    ED24-631A Electric Characteristics

    SkyAir NU Series Cooling Only 45

    8. Electric Characteristics

    8.1 R18~26NUV1 / Y1

    3D054360A3D054365A

  • 7/27/2019 sky-air nu

    49/149

    Electric Characteristics ED24-631A

    46 SkyAir NU Series Cooling Only

    8.2 R36~56NUV1 / Y1

    3D0525233D0525243D0525253D052526

    3D052573

  • 7/27/2019 sky-air nu

    50/149

    ED24-631A Capacity Tables

    SkyAir NU Series Cooling Only 47

    9. Capacity Tables

    9.1 Capacity Tables

    FHC18NUV1 / FDBG18NUV1 + R18NUV1

    FHC21NUV1 / FH21NUV1 / FDBG21NUV1 + R21NUV1

    3D054363A

    3D054364A

  • 7/27/2019 sky-air nu

    51/149

    Capacity Tables ED24-631A

    48 SkyAir NU Series Cooling Only

    FHC26NUV1 / FH26NUV1 / FDBG26NUV1 / FDMG26NUV1 + R26NUV1

    FHC26NUV1 / FH26NUV1 / FDBG26NUV1 / FDMG26NUV1 + R26NUY1

    FHC36NUV1 / FH36NUV1 / FDMG36NUV1 + R36NUV1FHC36NUV1 / FH36NUV1 / FDMG36NUV1 + R36NUY1

    3D054484A

    3D052745A

  • 7/27/2019 sky-air nu

    52/149

    ED24-631A Capacity Tables

    SkyAir NU Series Cooling Only 49

    FHC42NUV1 / FH42NUV1 / FDMG42NUV1 + R42NUY1

    FHC48NUV1 / FH48NUV1 / FDMG48NUV1 + R48NUY1

    3D052746A

    3D052747A

  • 7/27/2019 sky-air nu

    53/149

    Capacity Tables ED24-631A

    50 SkyAir NU Series Cooling Only

    FDMG51NUV1 + R51NUY1

    FDMG56NUV1 + R56NUY1

    3D052751A

    3D052754A

  • 7/27/2019 sky-air nu

    54/149

    ED24-631A Capacity Tables

    SkyAir NU Series Cooling Only 51

    9.2 Capacity Correction Factor by the Length of Refrigerant Piping

    The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping.

    (The distance between the indoor unit and the outdoor unit)

    Reference Data

    3D052761A

  • 7/27/2019 sky-air nu

    55/149

    Operation Limit ED24-631A

    52 SkyAir NU Series Cooling Only

    10.Operation Limit

    3D049550B

  • 7/27/2019 sky-air nu

    56/149

    ED24-631A Fan Performance

    SkyAir NU Series Cooling Only 53

    11.Fan Performance

    11.1 FDBG-NU

    FDBG18NU

    FDBG21NU

    FDBG26NU

    3D048561A

    3D048562A

  • 7/27/2019 sky-air nu

    57/149

    Fan Performance ED24-631A

    54 SkyAir NU Series Cooling Only

    11.2 FDMG-NU

    FDMG26NU

    FDMG36NU

    4D049493A

    4D049488A

  • 7/27/2019 sky-air nu

    58/149

    ED24-631A Fan Performance

    SkyAir NU Series Cooling Only 55

    FDMG42NU

    FDMG48NU

    FDMG51NU

    FDMG56NU

    4D049489A

    4D049490A

  • 7/27/2019 sky-air nu

    59/149

    Sound Level ED24-631A

    56 SkyAir NU Series Cooling Only

    12.Sound Level

    12.1 Overall Sound Level

    12.1.1 Indoor Unit

    Note: Operation sound is measured in an anechoic chamber.Sound level will vary depending on a range of factors such as the construction (acoustic absorptioncoefficient) of the particular room in which the equipment installed.

    dB(A)

    Model220V 240V

    Measuring LocationH L H L

    FHC18NUV1 33 29 35 31

    FHC-NUFHC21NUV1 35 30 37 32

    FHC26NUV1 35 30 37 32

    FHC36NUV1 42 36 44 38

    FHC42NUV1 42 36 44 38

    FHC48NUV1 42 36 44 38

    FH21NUV1 44 40 46 42

    FH-NU

    FH26NUV1 44 40 46 42

    FH36NUV1 46 40 48 42

    FH42NUV1 48 42 50 44

    FH48NUV1 49 43 51 45

    FDBG18NUV1 41 38 43 40FDBG-NU

    FDBG21NUV1 43 40 45 42

    FDBG26NUV1 43 40 45 42

    FDMG26NUV1 42 38 43 39

    FDMG-NUFDMG36NUV1 45 37 46 40

    FDMG42NUV1 46 37 47 40

    FDMG48NUV1 46 37 47 40

    FDMG51NUV1 47 37 48 39

    FDMG56NUV1 47 37 48 39

    4D054296

    4D054245

    4D054358

    4D049441A

  • 7/27/2019 sky-air nu

    60/149

    ED24-631A Sound Level

    SkyAir NU Series Cooling Only 57

    12.1.2 Outdoor Unit

    Note: Operation sound is measured in an anechoic chamber.Sound level will vary depending on a range of factors such as the construction (acoustic absorptioncoefficient) of the particular room in which the equipment installed.

    dB(A)

    Model 220 V 240 V Measuring Location

    R18NUV1 49 50R18 21NU

    R26~51NU

    R56NU

    R21NUV1 54 55

    R26NUV1 57 57

    R36NUV1 55 56

    Model 380 V 415 V

    R26NUY1 57 57

    R36NUY1 55 56

    R42NUY1 57 58

    R48NUY1 59 60

    R51NUY1 59 60

    R56NUY1 56 58

    4D054355

    4D054333

    4D049423B

  • 7/27/2019 sky-air nu

    61/149

    Sound Level ED24-631A

    58 SkyAir NU Series Cooling Only

    12.2 Octave Band Level

    12.2.1 Indoor Unit

    FHC18NUV1

    FHC21NUV1

    FHC26NUV1

    FHC36NUV1

    FHC42NUV1

    FHC48NUV1

    FH21NUV1FH26NUV1 FH36NUV1 FH42NUV1

    FH48NUV1 Note:

    220V

    240V

    4D054296 4D054293 4D052541A

    4D054245 4D052455 4D052456

    4D052458

  • 7/27/2019 sky-air nu

    62/149

    ED24-631A Sound Level

    SkyAir NU Series Cooling Only 59

    FDBG18NUV1

    FDBG21NUV1

    FDBG26NUV1 FDMG26NUV1

    FDMG36NUV1

    FDMG42NUV1

    FDMG48NUV1

    FDMG51NUV1

    FDMG56NUV1

    Note:220V

    240V

    4D054358 4D054357A 4D049441A

    4D049427B 4D049431B 4D049433B

  • 7/27/2019 sky-air nu

    63/149

    Sound Level ED24-631A

    60 SkyAir NU Series Cooling Only

    12.2.2 Outdoor Unit

    R18NUV1 R21NUV1

    R26NUV1

    R26NUY1

    R36NUV1

    R36NUY1 R42NUY1

    R48NUY1

    R51NUY1

    R56NUY1 Note:V1 : 220V, Y1 : 380V

    V1 : 240V, Y1 : 415V

    4D054355 4D054356 4D054333

    4D052428 4D052429 4D052430

    4D049423B

  • 7/27/2019 sky-air nu

    64/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 61

    13.Installation

    13.1 Indoor Unit

    13.1.1 FHC-NUV1

    3PN07217-2A

    a

    b

    c

    de

    e

    f

    g

    h

    i

    k

    e f

    l

    d

    j

    R42 48

    R18 21 26 36

    Names and functions of parts

    a Indoor unit

    b Outdoor unit

    c Remote controller

    d Inlet air

    e Discharged air

    f Air outlet

    g Air flow flap (at air outlet)h Refrigerant piping, connection

    electric wire

    Drain pipe

    Air inletThe built-in air filter removes dust and dirt.

    Drain pumping out device(built-in)

    Drains water removed from the roomduring cooling.

    Ground wireWire to ground from the outdoor unitto prevent electrical shocks.

    i

    j

    k

    l

  • 7/27/2019 sky-air nu

    65/149

    Installation ED24-631A

    62 SkyAir NU Series Cooling Only

    3PN07218-2B-5

  • 7/27/2019 sky-air nu

    66/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 63

    3PN07218-2B-6

  • 7/27/2019 sky-air nu

    67/149

    Installation ED24-631A

    64 SkyAir NU Series Cooling Only

    3PN07218-2B-7

  • 7/27/2019 sky-air nu

    68/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 65

    3PN07218-2B-8

  • 7/27/2019 sky-air nu

    69/149

    Installation ED24-631A

    66 SkyAir NU Series Cooling Only

    3PN07218-2B-9

  • 7/27/2019 sky-air nu

    70/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 67

    3PN07218-2B-10

  • 7/27/2019 sky-air nu

    71/149

    Installation ED24-631A

    68 SkyAir NU Series Cooling Only

    3PN07218-2B-11

  • 7/27/2019 sky-air nu

    72/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 69

    3PN07218-2B-12

  • 7/27/2019 sky-air nu

    73/149

    Installation ED24-631A

    70 SkyAir NU Series Cooling Only

    3PN07218-2B-13

  • 7/27/2019 sky-air nu

    74/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 71

    C : 3PN07218-2B-14

  • 7/27/2019 sky-air nu

    75/149

    Installation ED24-631A

    72 SkyAir NU Series Cooling Only

    3PN07218-2B-15

  • 7/27/2019 sky-air nu

    76/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 73

    3PN07218-2B-16

  • 7/27/2019 sky-air nu

    77/149

    Installation ED24-631A

    74 SkyAir NU Series Cooling Only

    3PN07218-2B-17

  • 7/27/2019 sky-air nu

    78/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 75

    3PN07218-2B-18

  • 7/27/2019 sky-air nu

    79/149

    Installation ED24-631A

    76 SkyAir NU Series Cooling Only

    3PN07218-2B-19

  • 7/27/2019 sky-air nu

    80/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 77

    3PN07218-2B-20

  • 7/27/2019 sky-air nu

    81/149

    Installation ED24-631A

    78 SkyAir NU Series Cooling Only

    3PN07218-2B-21

  • 7/27/2019 sky-air nu

    82/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 79

    3PN07218-2B-22

  • 7/27/2019 sky-air nu

    83/149

  • 7/27/2019 sky-air nu

    84/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 81

    13.1.2 FH-NUV1

    3PN07087-1A

    b

    d

    e

    k

    j

    a k

    i

    h

    f

    f

    c

    e

    e

    dd

    g

    Names and functions of parts

    a Indoor unit

    b Outdoor unit

    c Remote controller

    d Inlet air

    e Discharged air

    f Air outlet

    g Air flow flap (at air outlet)

    h Refrigerant piping, connection electric wire

    i Drain pipe

    j Air inletThe built-in air filter removes dust and dirt.

    kGround wireWire to ground from the outdoor unit to prevent electrical shocks.

  • 7/27/2019 sky-air nu

    85/149

    Installation ED24-631A

    82 SkyAir NU Series Cooling Only

    1PN07240B

  • 7/27/2019 sky-air nu

    86/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 83

    1PN07240B

  • 7/27/2019 sky-air nu

    87/149

  • 7/27/2019 sky-air nu

    88/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 85

    1PN07240B

  • 7/27/2019 sky-air nu

    89/149

  • 7/27/2019 sky-air nu

    90/149

  • 7/27/2019 sky-air nu

    91/149

    Installation ED24-631A

    88 SkyAir NU Series Cooling Only

    1PN07241A

  • 7/27/2019 sky-air nu

    92/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 89

    1PN07241A

  • 7/27/2019 sky-air nu

    93/149

    Installation ED24-631A

    90 SkyAir NU Series Cooling Only

    1PN07241A

  • 7/27/2019 sky-air nu

    94/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 91

    1PN07241A

  • 7/27/2019 sky-air nu

    95/149

    Installation ED24-631A

    92 SkyAir NU Series Cooling Only

    1PN07241A

  • 7/27/2019 sky-air nu

    96/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 93

    13.1.3 FDBG-NUV1

    1PN07524

  • 7/27/2019 sky-air nu

    97/149

    Installation ED24-631A

    94 SkyAir NU Series Cooling Only

    1PN07524

  • 7/27/2019 sky-air nu

    98/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 95

    1PN07524

  • 7/27/2019 sky-air nu

    99/149

    Installation ED24-631A

    96 SkyAir NU Series Cooling Only

    1PN07524

  • 7/27/2019 sky-air nu

    100/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 97

    1PN07524

  • 7/27/2019 sky-air nu

    101/149

    Installation ED24-631A

    98 SkyAir NU Series Cooling Only

    13.1.4 FDMG-NUV1

    1PN06319D

  • 7/27/2019 sky-air nu

    102/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 99

    1PN06319D

  • 7/27/2019 sky-air nu

    103/149

    Installation ED24-631A

    100 SkyAir NU Series Cooling Only

    1PN06319D

  • 7/27/2019 sky-air nu

    104/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 101

    1PN06319D

  • 7/27/2019 sky-air nu

    105/149

    Installation ED24-631A

    102 SkyAir NU Series Cooling Only

    1PN06319D

  • 7/27/2019 sky-air nu

    106/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 103

    13.2 Outdoor Unit

    13.2.1 R18 21NUV1

    1PN07605

  • 7/27/2019 sky-air nu

    107/149

    Installation ED24-631A

    104 SkyAir NU Series Cooling Only

    1PN07605

  • 7/27/2019 sky-air nu

    108/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 105

    1PN07605

  • 7/27/2019 sky-air nu

    109/149

    Installation ED24-631A

    106 SkyAir NU Series Cooling Only

    1PN07605

  • 7/27/2019 sky-air nu

    110/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 107

    1PN07605

  • 7/27/2019 sky-air nu

    111/149

    Installation ED24-631A

    108 SkyAir NU Series Cooling Only

    13.2.2 R26~56NUV1/Y1

    1PN07127A

    1PN07128B

  • 7/27/2019 sky-air nu

    112/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 109

    1PN07128B

  • 7/27/2019 sky-air nu

    113/149

    Installation ED24-631A

    110 SkyAir NU Series Cooling Only

    1PN07128B

  • 7/27/2019 sky-air nu

    114/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 111

    1PN07128B

  • 7/27/2019 sky-air nu

    115/149

    Installation ED24-631A

    112 SkyAir NU Series Cooling Only

    1PN07128B

  • 7/27/2019 sky-air nu

    116/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 113

    1PN07128B

  • 7/27/2019 sky-air nu

    117/149

    Installation ED24-631A

    114 SkyAir NU Series Cooling Only

    1PN07128B

  • 7/27/2019 sky-air nu

    118/149

    ED24-631A Installation

    SkyAir NU Series Cooling Only 115

    1PN07128B

  • 7/27/2019 sky-air nu

    119/149

    Accessories ED24-631A

    116 SkyAir NU Series Cooling Only

    14.Accessories

    14.1 Indoor Unit

    14.1.1 FHC-NU

    Standard

    Accessories

    3PN07218-2B-3

    Optional

    Accessories

    C : 3D054362C : 3D052565

    Note: 1. Installation box for adaptor PCB (KRP1B98) is necessary.2. Wire for remote controller : Field supplied.3. Refer to the Option Handbook for the detail.4. When using the filter (HighEfficiency Filter or Ultra LongLife Filter) and the Fresh Air Intake Kit together, this kit is necessary.

    Name of Option RemarkKit Name

    FHC18~26NU FHC36~48NU

    Decoration Panel BYC125KW1

    Sealing Member of Air Discharge Outlet KDBHJ55K160Panel Spacer KDBP55H160WA

    Fresh Air Intake Kit 3 Chamber Type Without T Joint KDDP55D160

    With T Joint KDDP55D160K

    Direct Installation Type KDDJ55X160

    Chamber Connection Kit 4 KKSJ55K160

    HighEfficiency Filter (Colorimetric Method 65%) KAFP556D80 KAFP556D160

    (Colorimetric Method 90%) KAFP557D80 KAFP557D160

    Replacement HighEfficiencyFilter

    (Colorimetric Method 65%) KAFP552H80 KAFP552H160

    (Colorimetric Method 90%) KAFP553H80 KAFP553H160

    HighEfficiency Filter Chamber KDDFP55D160

    Replacement LongLife Filter Resin Net (Gravimetric Method 50%) KAFJ551K160

    Ultra LongLife Filter KAFP55D160

    Replacement Ultra LongLife Filter KAFJ55K160H

    Branch Duct Chamber KDJ55K80 KDJ55K160

    Remote Controller Wired Type 2 BRC1C61

    Wireless Type BRC7C613W

    Wired LCD Remote Controller with Weekly Schedule Timer BRC1D61

    Central Remote Controller DCS302CA61

    Unified ON/OFF Controller DCS301BA61

    Schedule Timer DST301BA61

    intelligent Touch Controller DCS601C51

    Adaptor for Wiring (Interlock for Fresh Air Intake Fan) 1 KRP1B57

    Wiring Adaptor for Electrical Appendices 1 KRP4A53

    Interface Adaptor for SkyAir Series DTA102A52

    Installation Box for Adaptor PCB KRP1B98

  • 7/27/2019 sky-air nu

    120/149

    ED24-631A Accessories

    SkyAir NU Series Cooling Only 117

    14.1.2 FH-NU

    Standard

    Accessories

    1PN07240B

    Optional

    Accessories

    3D0542253D052467

    Note: 1. Wire for remote controller : Field supplied.

    14.1.3 FDBG-NU

    Standard

    Accessories

    1PN07524

    Optional

    Accessories

    4D048550A

    Note: 1. If you use local remote controller, 3 minutes timer is necessary for the recycling guard of compressor.2. Central controls using with VRV controller are available on request. Please consult DAIKIN.

    Name of Option RemarkKit Name

    FH21 26NU FH36~48NU

    Replacement LongLife Filter KAFJ501D80 KAFJ501D160

    LType Piping Kit For Upward Direction KHFJ5F80 KHFJ5F160Remote Controller Wired Type 1 BRC1NU61

    Wireless Type BRC7NU66

    Name of Option RemarkKit Name

    FDBG18NU FDBG21 26NU

    Remote Controller with 3 Minutes Timer KRC47-1

    Digital Remote Controller with 3 Minutes Timer KRC47-2

    Digital Remote Controllerwith 3 Minutes Timer

    With Switch for Duct Heater KRC47-4

    Suction Grille KDGF19A45 KDGF19A71

    Drain Pan Cover KKD19A1

  • 7/27/2019 sky-air nu

    121/149

    Accessories ED24-631A

    118 SkyAir NU Series Cooling Only

    14.1.4 FDMG-NU

    Standard

    Accessories

    1PN06319D

    Optional

    Accessories

    4D0544004D052569

    Note: 1. If you use local remote controller, 3 minutes timer is necessary for the recycling guard of compressor.2. Central controls using with VRV controller are available on request. Please consult DAIKIN.

    14.2 Outdoor Unit

    14.2.1 R-NU

    Optional

    Accessories

    4D052475B

    Name of Option RemarkKit Name

    FDMG26~56NU

    Remote Controller with 3 Minutes Timer KRC47-1

    Digital Remote Controller with 3 Minutes Timer KRC47-2

    Digital Remote Controllerwith 3 Minutes Timer

    With Switch for Duct Heater KRC47-4

    Name of OptionKit Name

    R18NU R21NU R26~56NU

    Drain Piping Kit - KIS95 -

    Central Drain Plug - - KKPJ5F180

  • 7/27/2019 sky-air nu

    122/149

    ED24-631A Remote Controller

    SkyAir NU Series Cooling Only 119

    15.Remote Controller

    15.1 Operation

    15.1.1 Wired Remote Controller : BRC1C61 (for FHC)

    3PN07217-2A

    2

    1011

    3

    14

    6

    7

    8

    13

    1415 16 17

    18

    19

    20

    21

    9

    12

    5

  • 7/27/2019 sky-air nu

    123/149

    Remote Controller ED24-631A

    120 SkyAir NU Series Cooling Only

    15.1.2 Wired Remote Controller : BRC1NU61 (for FH)

    3PN07204-2

  • 7/27/2019 sky-air nu

    124/149

    ED24-631A Remote Controller

    SkyAir NU Series Cooling Only 121

    15.1.3 Wireless Remote Controller : BRC7C613W (for FHC)

    C : 3PA63363-4P

    Fig.1 Fig.2

  • 7/27/2019 sky-air nu

    125/149

    Remote Controller ED24-631A

    122 SkyAir NU Series Cooling Only

    15.1.4 Wireless Remote Controller : BRC7NU66 (for FH)

    FIgure 1

    3PN07204-1-4

  • 7/27/2019 sky-air nu

    126/149

    ED24-631A Remote Controller

    SkyAir NU Series Cooling Only 123

    FIgure 2 (Explanation of Receiver)

    3PN07204-1-5

  • 7/27/2019 sky-air nu

    127/149

    Detail Explanation of Options ED24-631A

    124 SkyAir NU Series Cooling Only

    16.Detail Explanation of Options

    16.1 Ceiling Mounted Cassette Type (Multi Flow) [FHC]

    16.1.1 BYC125KW1S Decoration Panel

    BEFORE INSTALLATION

    PRECAUTIONS

    Refer also to the installation manual attached to the indoor unit.

    ACCESSORIES

    Installation manual.

    NOTE TO INSTALLER

    Be sure to instruct the customer how to properly operate the system showing him/her the attached operation manual.

    HANDLING OF DECORATION PANELS

    Never place the panel facing down nor lean it against a wall nor leave it on a projecting object. Never touch or put pressure on the swing flap.

    (The swing flap may malfunction.)

    (1) Remove the suction grille from the decoration panel.

    1) Push the suction grille lever inward and lift up the lever side.

    (Refer to Fig. 1.)

    PREPARATION OF DECORATION PANEL

    Lever

    Fig. 1

    45

    Fig. 2

    2) Detach the suction grille from the decoration panel by lifting the

    grille up approximately 45 degrees. (Refer to Fig. 2.)

    Fig. 3

    (2) Remove the service cover on the corner.

    Slide the service cover outward to remove. (Refer to Fig. 3.)

  • 7/27/2019 sky-air nu

    128/149

    ED24-631A Detail Explanation of Options

    SkyAir NU Series Cooling Only 125

    INSTALLATION OF THE DECORATION PANEL TO THE

    INDOOR UNIT BODY

    (1) Set the decoration panel to the indoor unit body by matching the position of the swing flap motor of the decoration panel to thepiping position of the indoor unit as shown in Fig. 4.

    (2) Install the decoration panel.1) Temporarily install the decoration panel to the indoor unit by hanging the latch on the opposite side of the swing flap motor of

    the decoration panel to the hook of the indoor unit body. (2 positions)2) Temporarily hang the remaining 2 latches to the hooks on the sides of the indoor unit.

    (Be careful not to let the swing motor lead wire get caught in the sealing material.)3) Screw all 4 hexagon head screws located right beneath the latches in approximately 5 mm. (Panel will rise.)4) Adjust the decoration panel by turning it to the arrowed direction in Fig. 4 so that the ceiling opening is completely covered.5) Tighten the screws until the thickness of the sealing material between the decoration panel and the indoor unit body reduces

    to 58 mm.Indoor unit

    Ceiling material

    Sealing material

    Decoration panelAir outlet

    5 ~ 8 mm

    1)

    2)

    2)

    3)

    4)

    Hook

    Latch

    Piping position

    Swing flap motor

    Fig. 4

    PRECAUTIONS

    Improper screwing of the screws may cause the troubles shown in

    Fig. 5. Screw properly.

    Air leak

    Air leak from ceiling

    Contamination Dew formation, dew dripping

    Fig. 5

  • 7/27/2019 sky-air nu

    129/149

    Detail Explanation of Options ED24-631A

    126 SkyAir NU Series Cooling Only

    If gap is still left between the ceiling and the decoration panel after screwing

    the screws, readjust the indoor unit body height. (Refer to Fig. 6.)

    (3) Wiring of the decoration panel (Refer to Fig. 7.)

    6) Connect the connectors for swing flap motor lead wire

    installed on the decoration panel.

    Adjustment of the indoor unit body height from theholes in the corner of the decoration panel ispossible if the indoor unit is kept leveled and thedrain piping, etc. is unaffected.

    Fig. 6

    No gaps is allowed.

    If connectors are not connected, the malfunction

    display (A7) appears on the remote controller.

    Connect the connectors properly.

    Make sure that the swing flap motor lead wire is

    not caught between the indoor unit and the

    decoration panel.

    6)

    Indoorunit side

    Decorationpanel side

    Wiring Instruction Diagram

    (It differs from the actual state.)Fig. 7

    INSTALLATION OF SUCTION GRILLE AND SERVICE COVER

    (1) Install the suction grille.

    Install by reversing the procedure shown in PREPARATION OF DECORATION PANEL.

    It is possible to install the suction grille in 4 directions by turning the suction grille.

    Change the direction when adjusting the direction of the suction grille of multiple units or in meeting customers demands.

    NOTE)

    Be careful not to get swing flap motor lead wire get caught when installing the suction grille.

    (2) Install the service cover on the corner.

    1) Attach the string of the service cover to the pin of thedecoration panel as in Fig. 8.

    Pin

    Fig. 8

    Install the service cover by

    sliding 4 latches to fit into the

    holes on the decoration panel.

    2) Install the service cover over the decoration panel.

  • 7/27/2019 sky-air nu

    130/149

    ED24-631A Detail Explanation of Options

    SkyAir NU Series Cooling Only 127

    16.1.2 KDBHJ55K160 Sealing Member of Air Discharge Outlet

    Caution

    zRefer to the installation manual for both indoor unit and the decoration panel.

    zWhen you install other optional kit, it may not be possible to select the 3-way or 2-way air discharge. For details, refer to the

    manual for the optional kit or the catalogue.

    zContents of Kit Prior to installation make sure you have the complete kit of parts.

    J : 1P012222B

    Name Sealing material(A) Sealing material(B) Sealing material(C) Sealing material(D)Quantity 1 piece 1 piece 1 piece 1 piece

    Shapeand

    marking

    Name Insulation for top plate Insulation for side plate Moisture absorber for bell-mouth Moisture absorber for horizontal vane

    Quantity 1 piece 1 piece 1 piece 2 pieces 1 piece 2 pieces 1 piece 5 kinds

    Shapeand

    marking

  • 7/27/2019 sky-air nu

    131/149

    Detail Explanation of Options ED24-631A

    128 SkyAir NU Series Cooling Only

    Installation of the insulation3

    (1) Installation to the side plate

    Adhere insulation for side plate to the side of indoor unit.

    (2) Installation to the top plate

    Adhere insulation for top plate , to the top of the indoor unit.

    (3) Adhere the moisture absorber for horizontal vane to the

    edge of the horizontal vane of air outlet (Fig. 2).

    (Choose the same color as panel.)

    (4) Adhere the moisture absorber in accordance with the

    reference surface without wrinkles. (Fig. 4)

    Adhere the moisture absorber in accordance with the

    reference line . (Fig. 5)

    26 class 48 class

    Put the wirethrough the slit ofthe insulation.

    When adheringinsulation, align its edge

    with the bottom line ofcasing.

    When adheringinsulation, align its edge

    with the bottom line ofcasing.

    Fig. 1

    Fig. 4

    Moisture absorberfor horizontal vane

    Horizontal vane

    Fig. 2

    (Fig. 3)

    Align it with the upper edge of horizontal vane.

    Horizontal

    vaneMoisture absorberfor horizontal vane

    Swing connector

    Swing motor

    Sticking

    reference

    Bellmouth

    Fig. 5

    JC : 1P012222B

    Reference surface

    Adhere it from the edge ofswitch box.

    Switch box

    Sticking reference

  • 7/27/2019 sky-air nu

    132/149

    ED24-631A Detail Explanation of Options

    SkyAir NU Series Cooling Only 129

    16.1.3 KDBP55H160WA Panel Spacer

    Installation

    1P136564E

  • 7/27/2019 sky-air nu

    133/149

    Detail Explanation of Options ED24-631A

    130 SkyAir NU Series Cooling Only

    1P136564E

  • 7/27/2019 sky-air nu

    134/149

    ED24-631A Detail Explanation of Options

    SkyAir NU Series Cooling Only 131

    16.1.4 KDDP55D160(K) Fresh Air Intake Kit (Chamber Type)

    Installation

    C : 3K011144A

    SkyAir FHC18~48NU

    240298

    18~26NU

    36~48NU

  • 7/27/2019 sky-air nu

    135/149

    Detail Explanation of Options ED24-631A

    132 SkyAir NU Series Cooling Only

    3K011144A

  • 7/27/2019 sky-air nu

    136/149

    ED24-631A Detail Explanation of Options

    SkyAir NU Series Cooling Only 133

  • 7/27/2019 sky-air nu

    137/149

    Detail Explanation of Options ED24-631A

    134 SkyAir NU Series Cooling Only

    16.1.5 KDDJ55X160 Fresh Air Intake Kit (Direct Installation Type)

    Installation

    The fresh air is taken into the unit by the indoor unit fan or duct fan, which is field supplied. The location of fresh air intake port will be

    changeable by installing the duct fan.

    J : D3K2175

    Dimension

    2P066796C

  • 7/27/2019 sky-air nu

    138/149

    ED24-631A Detail Explanation of Options

    SkyAir NU Series Cooling Only 135

    2P066796C

  • 7/27/2019 sky-air nu

    139/149

    Detail Explanation of Options ED24-631A

    136 SkyAir NU Series Cooling Only

    16.1.6 KAFP556D80 160 HighEfficiency Filter (Including Filter Chamber)

    KAFP557D80 160 HighEfficiency Filter (Including Filter Chamber)

    Combination table

    16.1.7 KAFP552H80 160 Replacement HighEfficiency Filter

    KAFP553H80 160 Replacement HighEfficiency Filter

    Specifications

    Precaution at use1. The highefficiency filter, and the other filter can not be installed together.

    2. The unit should be operated with 4-way discharge when the highefficiency filter is installed.

    It can not be applied to the high ceiling room.

    3. Field setting by remote controller is necessary when the highefficiency filter is installed.

    16.1.8 KRP1B98 Installation Box for Adaptor PCB

    HighEfficiency Filter (Set) Replacement HighEfficiency Filter HighEfficiency Filter Chamber

    KAFP556D80KAFP557D80

    KAFP552H80KAFP553H80

    KDDFP55D160KAFP556D160

    KAFP557D160

    KAFP552H160

    KAFP553H160

    Replacement HighEfficiency Filter KAFP552H80 KAFP552H160 KAFP553H80 KAFP553H160

    HighEfficiency Filter Chamber KDDFP55D160

    Collecting Efficiency (%) 65% (NBS Colorimetric method) 90% (NBS Colorimetric method)

    Initial Pressure Loss (Pa) 34 or less

    Final Pressure Loss (Pa) 98 or less

    Filter Nonwoven Fabric of Synthetic Fiber Nonwoven Fabric of Synthetic Fiber

    Life (h) 2,500 h (Dust Concentration 0.15 mg / m3) 1,800 h (Dust Concentration 0.15 mg / m3)

    Models to be Applied 18~26NU 36~48NU 18~26NU 36~48NU

    Dimension

    560

    AA

    560

    100

    -2540 10

    J : D3K04256A

    Model AA

    KAFP552H80, KAFP553H80 25

    KAFP552H160, KAFP553H160 45

    KRP1B98

    FHC18~48NU

    KRP1B57

    KRP4A53

    Dimension

    D3K2169

    Model No.

    Item

    Applicable Model

    Adaptor for Wiring

  • 7/27/2019 sky-air nu

    140/149

    ED24-631A Detail Explanation of Options

    SkyAir NU Series Cooling Only 137

    16.1.9 KDDFP55D160 HighEfficiency Filter Chamber

    Installation

    C : 3K011148B

    SkyAir

    SkyAir FHC36~48NU

    FHC18~26NU

  • 7/27/2019 sky-air nu

    141/149

    Detail Explanation of Options ED24-631A

    138 SkyAir NU Series Cooling Only

    3K011148B

  • 7/27/2019 sky-air nu

    142/149

    ED24-631A Detail Explanation of Options

    SkyAir NU Series Cooling Only 139

    16.1.10 KAFJ551K160 Replacement LongLife Filter for Decoration Panel

    Specifications

    16.1.11 KAFP55D160, KAFJ55K160H (Replacement) Ultra LongLife Filter

    (Including Filter Chamber)

    Specifications

    Collecting Efficiency (%) 65 (Gravity Method)

    Initial Pressure Loss (Pa) 8 or less

    Final Pressure Loss (Pa) 49 or less

    Filter MildewProof Resin Net

    Number of Sheets Included 1

    Life (h) 2,500 h (Dust Concentration 0.15 mg / m3)

    Models to Be Applied 18~48NU

    J : D3K2170C

    Ultra LongLife Filter KAFP55D160 Precaution at use

    1. The Ultra longlife filter, and other filter can not be installed

    together.

    2. Field setting by remote controller is necessary when the Ultra

    longlife filter is installed.

    Refer to the installation manual of Ultra longlife filter for

    setting.

    3. Filter cleaning period can not be displayed on the monitor when

    the Ultra longlife filter is installed.

    Refer to the left table and clean (with water) the filter

    periodically.

    Replacement Ultra LongLife Filter KAFJ55K160H

    HighEfficiency Filter Chamber KDDFP55D160

    Collecting Efficiency (%) 50 (Gravity Method)Initial Pressure Loss (Pa) 8 or less

    Final Pressure Loss (Pa) 49 or less

    Filter MildewProof Resin Net

    Life (h)5,000 h

    (Dust Concentration 0.3 mg / m3)

    Models to Be Applied 18~48NU

    J : D3K2174A

    Installation Iocation

    Dirty Area

    Not Dirty Area

    Filter Cleaning Period

    Every 5,000 hrs

    Every 10,000 hrs

  • 7/27/2019 sky-air nu

    143/149

    Detail Explanation of Options ED24-631A

    140 SkyAir NU Series Cooling Only

    16.1.12 KKSJ55K160 Chamber Connection Kit

    Dimension

    Installation

    J : D3K2186

    3P089651C

  • 7/27/2019 sky-air nu

    144/149

    ED24-631A Detail Explanation of Options

    SkyAir NU Series Cooling Only 141

    16.1.13KDJ55K80 160 Branch Duct Chamber

    Installation

  • 7/27/2019 sky-air nu

    145/149

    Detail Explanation of Options ED24-631A

    142 SkyAir NU Series Cooling Only

  • 7/27/2019 sky-air nu

    146/149

    ED24-631A Detail Explanation of Options

    SkyAir NU Series Cooling Only 143

    16.2 Ceiling Suspended Type [FH]

    16.2.1 KAFJ501D80 160 Replacement LongLife Filter

    Specifications

    J : D3K3074A

    16.2.2 KHFJ5F80 160 LType Piping Kit

    Application purpose

    This kit must be bent inside the unit as shown below, when the refrigerant piping is carried out in a ceiling

    space. This L shape kit is an optional accessory which has been developed for improving the work of the

    processing on site.

    ModelItem

    KAFJ501D56 KAFJ501D80 KAFJ501D112 KAFJ501D160

    Effective Life, Average Efficiency 2,500 hours (at Dust Particle Concentration of 0.15 mg/m3), 45% (by Weight Method)

    Initial Pressure Loss (Pa) 10 or lessFinal Pressure Loss (Pa) 59 or less

    Filter Materials Mold Prevention Resin Net Mold Prevention Resin Net

    Nos. Required 2 pieces 3 pieces

    Applicable Model - 21 26NU - 36~48NU

    ModelItem

    KHFJ5F50 KHFJ5F60 KHFJ5F80 KHFJ5F160

    Applicable Model - - 21 26NU 36~48NU

    KHFJ5F50~160 Installation

  • 7/27/2019 sky-air nu

    147/149

    Detail Explanation of Options ED24-631A

    144 SkyAir NU Series Cooling Only

    16.3 Duct Connection Low Static Pressure Type [FDBG]

    16.3.1 KKD19A1Drain Pan Cover

    Installation

    FDBG182126NUV1

    C : 1P067376A

  • 7/27/2019 sky-air nu

    148/149

    ED24-631A Detail Explanation of Options

    SkyAir NU Series Cooling Only 145

    16.4 Outdoor Unit

    16.4.1 KIS95 Drain Piping Kit

    Use this plug to connect a drain hose to an outdoor unit.

    Outlook

    Note: 1. This is the joint for attaching a vinyl hose (field supplied).

    This is used between the drain hole which is on the bottom plate of outdoor unit and vinyl hose.

    2. Drain water accumulate to the bottom of outdoor unit it depends on the situation of operation. But it isnecessary to connect drain hose not to be spread the drain water over the neighbors, when it is installed

    on the wall.

    3. The position of holes are unfit to connect with outdoor units in some models.

    In this case, use it without Y joint.

    16.4.2 KKPJ5F180 Central Drain Plug

    KIS95

    Drain hose connection dia 16ID.

    KIS95

    Drain piping

    (With Y joint)

    plug (3 pcs.)

  • 7/27/2019 sky-air nu

    149/149

    Warning Daikin Industries, Ltd.s products are manufactured for export to numerous countries throughout the

    world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a

    particular country. Prior to purchase, please therefore confirm with your local authorized importer,

    distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for

    use, in the region where the product will be used. This statement does not purport to exclude, restrict

    or modify the application of any local legislation.

    Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.

    Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

    Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or

    contractor to install those parts and accessories. Use of unauthorized parts and accessories or

    improper installation of parts and accessories can result in water or refrigerant leakage, electrical

    shock, fire or explosion.

    Read the User's Manual carefully before using this product. The User's Manual provides important

    safety instructions and warnings. Be sure to follow these instructions and warnings.

    If you have any inquiries, please contact your local importer, distributor and/or retailer.