Single Phase Fault Result
1
One-Line Diagram - OLV1 (Short-Circuit Analysis) page 1 19:41:45 Feb 11, 2015 Project File: NMC speciality hospital SINGLE PHASE FAULT RESULT Bus2 0.415 kV 0.23 kV 35.11 kA Bus4 0.415 kV 0.23 kV 35.11 k A ± ± ± ± ± ± ± NMC hospital SWS bus B 11 kV 9.91 kV 1.91 kA SE44PRY1 11 kV 6.88 kV 13.94 kA NMC hospital sws BUS A 11 kV 9.91 kV 1.91 kA Cable3 I> R Cable5 I> R R T1 1.5 MVA R T3 1.5 MVA R 35.11 U1 312 MVAsc 13.94 35.11 Open Bus2 0.415 kV 0.23 kV 35.11 kA NMC hospital sws BUS A 11 kV 9.91 kV 1.91 kA SE44PRY1 11 kV 6.88 kV 13.94 kA NMC hospital SWS bus B 11 kV 9.91 kV 1.91 kA 1.91 Cable3 1.91 1.91 Cable5 1.91 Open Bus4 0.415 kV 0.23 kV 35.11 k A T1 1.5 MVA 35.11 T3 1.5 MVA U1 312 MVAsc 13.94 35.11
description
OK
Transcript of Single Phase Fault Result
![Page 1: Single Phase Fault Result](https://reader035.fdocuments.in/reader035/viewer/2022071703/563dbabc550346aa9aa79ee3/html5/thumbnails/1.jpg)
One-Line Diagram - OLV1 (Short-Circuit Analysis)
page 1 19:41:45 Feb 11, 2015 Project File: NMC speciality hospital
SINGLE PHASE
FAULT RESULT
Bus2
0.415 kV 0.23 k
V
35.11 kA
Bus4
0.415 kV 0.23 k
V
35.11 kA
±
± ±
±
±
±
±
NMC hospital SWS bus B
11 kV 9.91 k
V
1.91 kA
SE44PRY1
11 kV 6.88 k
V
13.94 kA
NMC hospital sws BUS A
11 kV 9.91 k
V
1.91 kA
Cable3
I>
R
Cable5
I>
R
R
T1
1.5 MVA
R
T3
1.5 MVA
R
35.11
U1
312 MVAsc
13.94
35.11
Open
Bus2
0.415 kV 0.23 k
V
35.11 kA
NMC hospital sws BUS A
11 kV 9.91 k
V
1.91 kA
SE44PRY1
11 kV 6.88 k
V
13.94 kA
NMC hospital SWS bus B
11 kV 9.91 k
V
1.91 kA
1.91
Cable3
1.91 1.91
Cable5
1.91
Open
Bus4
0.415 kV 0.23 k
V
35.11 kA
T1
1.5 MVA
35.11
T3
1.5 MVA
U1
312 MVAsc
13.94
35.11