Shear Wall
-
Upload
sadatcharamourthy-n -
Category
Documents
-
view
27 -
download
2
description
Transcript of Shear Wall
INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING
Volume 2, No 2, 2011
© Copyright 2010 All rights reserved Integrated Publishing services
Research article ISSN 0976 – 4399
Received on September, 2011 Published on November 2011 493
Solution of Shear Wall Location in Multi-Storey Building Anshuman. S
1, Dipendu Bhunia
2, Bhavin Ramjiyani
3
1- Assistant Professor, Civil Engineering Group, BITS Pilani, Rajasthan, India
2- Assistant Professor, Civil Engineering Group, BITS Pilani, Rajasthan, India.
3- Higher Degree student, Civil Engineering Group, BITS Pilani, Rajasthan, India
doi:10.6088/ijcser.00202010128
ABSTRACT
Shear wall systems are one of the most commonly used lateral-load resisting systems in high-
rise buildings. Shear walls have very high in-plane stiffness and strength, which can be used
to simultaneously resist large horizontal loads and support gravity loads, making them quite
advantageous in many structural engineering applications. There are lots of literatures
available to design and analyse the shear wall. However, the decision about the location of
shear wall in multi-storey building is not much discussed in any literatures.
In this paper, therefore, main focus is to determine the solution for shear wall location in
multi-storey building based on its both elastic and elasto-plastic behaviours. An earthquake
load is calculated and applied to a building of fifteen stories located in zone IV. Elastic and
elasto-plastic analyses were performed using both STAAD Pro 2004 and SAP V 10.0.5
(2000) software packages. Shear forces, bending moment and story drift were computed in
both the cases and location of shear wall was established based upon the above computations.
Keywords: linear behaviour of shear wall, Non-linear behaviour of shear wall, seismic
analysis, STAAD Pro 2004 and SAP V 10.0.5 (2000)
Introduction
Reinforced concrete framed buildings are adequate for resisting both the vertical and the
horizontal load acting on them. However, when the buildings are tall, beam and column sizes
workout quite heavy, so that there is lot of congestion at these joint and it is difficult to place
and vibrate concrete at these places, which fact, does not contribute to the safety of buildings.
These practical difficulties call for introduction of shear wall. The term „shear wall‟ is rather
misleading as such a walls behave like flexural members. They are usually used in tall
buildings and have been found to be of immense use to avoid total collapse of buildings
under seismic forces. It is always advisable to incorporate them in buildings built in region
likely to experienced earthquake of large intensity or high winds. The design of these shear
wall for wind are design as simple concrete walls. The design of these walls for seismic
forces requires special considerations as they should be safe under repeated loads. Shear
walls may become imperative from the point of view of economy and control of lateral
deflection. There are lots of literatures available [Cardan, B. (1961), Syngellakis et al. (1991),
Wight et al. (1991), Qiusheng et al. (1994), White et al. (1995) and Rosowsky, D.V. (2002)]
to design and analyse the shear wall. However, any of these literatures did not discuss much
about the location of shear wall in multi-storey building.
Hence, this paper has been described to determine the proper location of shear wall based on
its elastic and elasto-plastic behaviours. A RCC medium rise building of 15 stories subjected
to earthquake loading in Zone IV has been considered. In this regard, both STAAD Pro 2004
Solution of Shear Wall Location in Multi-Storey Building
Anshuman. S, Dipendu Bhunia, Bhavin Ramjiyani
International Journal of Civil and Structural Engineering
Volume 2 Issue 2 2011
494
and SAP V 10.0.5 (2000) software packages have been considered as two tools to perform.
Shear forces, bending moments and storey drifts have been calculated to find out the location
of shear wall in the building.
The plan of the building without shear wall as shown in Figure 1 has been considered to carry
out the study. Both STAAD PRO 2004 and SAP V 10.0.5 (2000) software packages have
been considered. The preliminary data as per the Table 1 is taken up for this study.
Figure 1: Plan of the Building without Shear Wall
Table 1: Preliminary Data
Zone IV
External wall 250mm thick
including Plaster
Ground storey
height
4.0m From
Foundation Internal wall
150mm thick
including Plaster
Floor to floor
height 3.35m
Grade of Concrete and
steel M20 and Fe 415
Size of exterior column 300×500 mm2
Number of
storeys FIFTEEN (G+14) Size of interior column 300×300 mm
2
Shear wall
thickness 300 mm
Size of beams in
longitudinal
and transverse direction
300×450 mm2
Depth of slab
150 mm
Ductility design
IS:13920-1993
Loading consideration
Dead Load (DL) and Live load (LL) have been taken as per IS 875 (Part 1) (1987) and IS 875
(Part 2) (1987), respectively. Seismic load calculation has been done based on the IS 1893
(Part 1) (2002)‟s approach.
Results and Discussions
It has been seen from Table 2 that the top deflection (when the seismic load direction is in the
shorter dimension) has been exceeded the permissible deflection, i.e. 0.004 times the total
height of the building [IS 1893 (Part 1) (2002)] in STAAD PRO 2004. It has been exceeded
for the load combinations 1.5(DL+EQ) and 0.9DL+1.5EQ, respectively.
Solution of Shear Wall Location in Multi-Storey Building
Anshuman. S, Dipendu Bhunia, Bhavin Ramjiyani
International Journal of Civil and Structural Engineering
Volume 2 Issue 2 2011
495
Table 2: Maximum Deflection at the Roof without Shear Wall
Software Load
Combination
Calculated
Deflection
(mm)
Permissible Deflection
(mm)
[IS 1893 (Part 1)
(2002)]
STAAD PRO 2004
1.2(DL+LL+EQ) 187.976
203.6
1.5(DL+EQ) 235.725
0.9DL+1.5EQ 235.685
SAP V 10.0.5
(2000)
1.2(DL+LL+EQ) 158.71
1.5(DL+EQ) 198.4
0.9DL+1.5EQ 198.38
Similarly, bending moment and shear force were maximum at the ground level in 1st and 12
th
frames, respectively (Table 3).
Table 3: Maximum Bending Moment and Maximum Shear Force at the Ground Level
without Shear Wall
Frame No. Software Load
Combination
Calculated Bending
Moment
(kN-m)
Calculated
Shear Force
(kN)
1st and
12th
STAAD PRO
2004
1.2(DL+LL+E
Q) 238.041 110.49
1.5(DL+EQ) 294.134 136.43
0.9DL+1.5EQ 288.096 133.26
SAP V 10.0.5
(2000)
1.2(DL+LL+E
Q) 236.98 113.67
1.5(DL+EQ) 296.06 142.04
0.9DL+1.5EQ 302.65 145.26
Hence, for the above reason shear wall was provided in 1st and 12
th frames, respectively
(Figure 2).
Figure 2: Plan of the Building with Shear Wall in 1st and 12th frames
It has been observed from Table 4 that the roof deflection was well within the permissible
limit for all cases after providing the shear wall in 1st
and 12th
frames, respectively.
Solution of Shear Wall Location in Multi-Storey Building
Anshuman. S, Dipendu Bhunia, Bhavin Ramjiyani
International Journal of Civil and Structural Engineering
Volume 2 Issue 2 2011
496
Table 4: Maximum Roof Deflection after Providing Shear Wall in the 1st and 12
th Frame
Software Load
Combination
Calculated Deflection
(mm) Permissible Deflection
(mm)
[IS 1893 (Part 1)
(2002)] Without
Shear Wall
With Shear
Wall
STAAD PRO
2004
1.2(DL+LL+E
Q) 187.976 123.59
203.6
1.5(DL+EQ) 235.725 154.49
0.9DL+1.5EQ 235.685 151.49
SAP V 10.0.5
(2000)
1.2(DL+LL+E
Q) 158.71 91.4
1.5(DL+EQ) 198.4 114.29
0.9DL+1.5EQ 198.38 114.29
It has also seen from Table 5 that both bending moment and shear force were increased at the
ground level in 1st and 12
th frames after providing shear wall in 1
st and 12
th frames.
Table 5: Maximum Bending moment and Shear Force at the Ground Level after providing
Shear Wall in the 1st and 12
th Frame
Software Load
Combination
Calculated
Bending Moment
(kN-m)
Calculated Shear Force
(kN)
STAAD PRO 2004
1.2(DL+LL+E
Q) 698.24 337.97
1.5(DL+EQ) 861.27 416.28
0.9DL+1.5EQ 854.41 412.29
SAP V 10.0.5 (2000)
1.2(DL+LL+E
Q) 630.90 308.57
1.5(DL+EQ) 778.78 380.24
0.9DL+1.5EQ 779.73 381.03
Further, shear walls have been provided in the interior frames, i.e. 6th
and 7th
frames as per
the following figure 3.
Figure 3: Plan of the Building with Shear Wall in 6th and 7th frames
It has been seen from the Table 6 that roof deflection was well within the permissible
deflection for all cases after providing the shear wall in 6th
and 7th
frames, respectively.
Solution of Shear Wall Location in Multi-Storey Building
Anshuman. S, Dipendu Bhunia, Bhavin Ramjiyani
International Journal of Civil and Structural Engineering
Volume 2 Issue 2 2011
497
Table 6: Maximum Roof Deflection after Providing Shear Wall in the 6th
and 7th
Frame
Software Load
Combination
Calculated Deflection
(mm) Permissible
Deflection (mm)
[IS 1893 (Part 1)
(2002)] Without Shear
Wall
With Shear
Wall
STAAD PRO
2004
1.2(DL+LL+E
Q) 187.976 106.47
203.6
1.5(DL+EQ) 235.725 133.08
0.9DL+1.5EQ 235.685 135.47
SAP V 10.0.5
(2000)
1.2(DL+LL+E
Q) 158.71 84.72
1.5(DL+EQ) 198.4 105.91
0.9DL+1.5EQ 198.38 105.91
It has also seen from Table 7 that both bending moment and shear force were increased at the
ground level in 6th
and 7th
frames after providing shear wall in 6th
and 7th
frames.
Table 7: Maximum Bending Moment and Maximum Shear Force at the Ground Level after
providing Shear Wall in the 6th
and 7th
Frame
Software Load Combination
Calculated Bending
Moment
(kN-m)
Calculated Shear
Force
(kN)
STAAD
PRO 2004
1.2(DL+LL+EQ) 665.76 324.51
1.5(DL+EQ) 809.79 394.28
0.9DL+1.5EQ 803.14 389.25
SAP V
10.0.5
(2000)
1.2(DL+LL+EQ) 574.87 281.61
1.5(DL+EQ) 732.90 360.92
0.9DL+1.5EQ 729.19 358.67
Elasto-plastic analysis
Mahin and Bertero (1976) employed the wide-column frame analogy to assess the importance
of the strength and stiffness of the coupling beams on the elastic and nonlinear, static, and
dynamic responses of multi-story, coupled shear-wall models to severe earthquake excitation.
In wide column frame analogy shear wall has been modeled as a wide column having same
dimension of shear wall and shear wall is connected to frame by connecting beam. Here shear
walled frame has been modeled in SAP 2000 vs. 10 in which nonlinear analysis is done by
using inbuilt coefficient given by FEMA 356 (FEDERAL EMERGENCY MANAGEMENT
AGENCY) provisions. According to FEMA 356 the displacement of maximum displaced
column is restricted by 4% of height. Analysis is done for the design earthquake which has
the probability of occurrence is 100years and obtains the performance point. Performance
point gives the value of maximum displacement of column which occurs for design earth
quake intensity for particular zone i.e. zone IV. Resultant base shear-displacement curve has
been obtained for structure, which shows behavior of structure with respect to base shear.
Solution of Shear Wall Location in Multi-Storey Building
Anshuman. S, Dipendu Bhunia, Bhavin Ramjiyani
International Journal of Civil and Structural Engineering
Volume 2 Issue 2 2011
498
Figure 3: Graph showing Hinge Formation Levels
In analysis hinge formation has been also been observed. Hinge formation levels are divided
as yield level (B), immediate occupancy level (IO), life safety level (LS), collapse level (CP),
full collapse level (E) [Figure 3]. At the immediate occupancy level structures have no sever
damage and structures can be used for further life of structure. Life safety level indicates
there will not be any casualty due to earthquake but structure cannot be used for further living.
At collapse level member will start to collapse and full collapse member will already collapse.
The elastic analysis has been extended to elasto-plastic analysis as per the criterion discussed
above. SAP2000 v10.0.5 software package has been considered to carry out this analysis.
Table 8 is showing the base shear and roof displacement at the performance point. It has been
observed that the performance point for both the conditions (Shear Wall provided in the 6th
and 7th
Frames and Shear Wall provided in the 1st and 12
th Frames) is lying within the IO
level.
Capacity Spectrum
Capacity spectrum is obtained as per IS 1893:2002 for Zone IV with medium soil.
Solution of Shear Wall Location in Multi-Storey Building
Anshuman. S, Dipendu Bhunia, Bhavin Ramjiyani
International Journal of Civil and Structural Engineering
Volume 2 Issue 2 2011
499
Figure 4: Capacity Spectrum for shear wall in in 6th
and 7th
frame
Solution of Shear Wall Location in Multi-Storey Building
Anshuman. S, Dipendu Bhunia, Bhavin Ramjiyani
International Journal of Civil and Structural Engineering
Volume 2 Issue 2 2011
500
Figure 5: Capacity Spectrum for shear wall in in 1st
and 12th
frame
Table 8: Base shear vs. Roof displacement at the performance point
Conditions
Parameters
Base Shear (kN) Roof Displacement
(mm)
Shear Wall provided in the 6th
and 7th Frames
912.677 0.0434
Shear Wall provided in the 1st
and 12th Frames
865.357 0.326
Graph shows that in Non-linear analysis performance point is small i.e. the behaviour of the
structure is within the elastic limit. Hence linear analysis is adequate for this structure.
Results for Shear wall in 6th
and 7th
frames
It has also seen from Table 9 that shear force was increased at the ground level in 6th
and 7th
frames after providing shear wall in 6th
and 7th
frames.
Solution of Shear Wall Location in Multi-Storey Building
Anshuman. S, Dipendu Bhunia, Bhavin Ramjiyani
International Journal of Civil and Structural Engineering
Volume 2 Issue 2 2011
501
Table 9: Shear force for Shear wall in 6th
and 7th
frames
Storey
Level
Height
(m)
Shear force in shear wall for load combination
PUSH 2 (In kN )
Step 0 Step 1
Shear wall
1
Shear wall
2 Shear wall 1 Shear wall 2
14th
Roof level 52.40 - 6.608 - 6.608 - 36.369 - 49.586
14th Level 49.05 + 6.608 + 6.608 + 36.369 + 49.586
13th
14th Level 49.05 - 6.104 - 6.104 - 85.000 - 97.207
13th Level 45.70 + 6.104 + 6.104 + 85.000 + 97.207
12th
13th Level 45.70 - 6.714 - 6.714 - 132.821 - 146.249
12th Level 42.35 + 6.714 + 6.714 + 132.821 +146.249
11th
12th Level 42.35 - 6.983 - 6.983 - 181.334 - 195.299
11th
Level 39.00 + 6.983 + 6.983 + 181.334 + 195.299
10th
11th
Level 39.00 - 7.208 - 7.208 - 230.157 - 244.574
10th Level 35.65 + 7.208 + 7.208 + 230.157 + 244.574
9th
10th Level 35.65 - 7.383 - 7.383 - 279.180 - 293.948
9th Level 32.30 + 7.383 + 7.383 + 279.180 + 293.948
8th
9th Level 32.30 - 7.523 - 7.523 - 328.266 - 343.312
8th Level 28.95 + 7.523 + 7.523 + 328.266 + 343.312
7th
8th Level 28.95 - 7.625 - 7.625 - 377.267 - 392.516
7th Level 25.60 + 7.625 + 7.625 + 377.267 + 392.516
6th
7th Level 25.60 - 7.676 - 7.676 - 426 - 441.358
6th Level 22.25 + 7.676 + 7.676 + 426 + 441.358
5th
6th Level 22.25 - 7.651 - 7.651 - 474.242 - 489.544
5th Level 18.90 + 7.651 + 7.651 + 474.242 + 489.544
4th
5th Level 18.90 - 7.509 - 7.509 - 521.617 - 536.635
4th Level 15.55 + 7.509 + 7.509 + 521.617 + 536.635
3rd
4
th Level 15.55 - 7.187 - 7.187 - 567.604 - 581.977
3rd
Level 12.20 + 7.187 + 7.187 + 567.604 + 581.977
2nd
3
rd Level 12.20 - 6.563 - 6.563 - 611.447 - 624.572
2nd
Level 8.85 + 6.563 + 6.563 + 611.447 + 624.572
1st
2nd
Level 8.85 - 5.666 - 5.666 - 651.843 - 663.174
1st Level 5.50 + 5.666 + 5.666 + 651.843 + 663.174
Ground
1st Level 5.50 - 2.261 - 2.261 - 689.286 - 693.808
Ground
Level 1.50 + 2.261 + 2.261 + 689.286 + 693.808
Footing
Ground
Level 1.50 - 2.158 - 2.158 - 727.732 - 732.047
Footing
Level 0 + 2.158 + 2.158 + 727.732 + 732.047
It has also seen from Table 10 that bending moment was increased at the ground level in 6th
and 7th
frames after providing shear wall in 6th
and 7th
frames.
Table 10: Bending moment for Shear wall in 6th
and 7th
frames
Storey
Level
Height
(m)
Bending Moment in shear wall for load combination
PUSH 2 (In kN )
Step 0 Step 1
Shear wall Shear wall Shear wall 1 Shear wall 2
Solution of Shear Wall Location in Multi-Storey Building
Anshuman. S, Dipendu Bhunia, Bhavin Ramjiyani
International Journal of Civil and Structural Engineering
Volume 2 Issue 2 2011
502
1 2
14th
Roof
level 52.40 + 11.782 + 11.782 + 63.369 + 86.932
14th Level 49.05 - 10.356 - 10.356 - 58.467 - 79.179
13th
14th Level 49.05 + 9.929 + 9.929 + 145.893 + 165.751
13th Level 45.70 - 10.520 - 10.520 - 138.854 - 159.894
12th
13th Level 45.70 + 11.171 + 11.171 + 225.789 + 248.131
12th Level 42.35 - 11.321 - 11.321 - 219.162 - 241.805
11th
12th Level 42.35 + 11.623 + 11.623 + 306.858 + 330.104
11th
Level 39.00 - 11.769 - 11.769 - 300.612 - 324.151
10th
11th
Level 39.00 + 12.018 + 12.018 + 388.278 + 412.315
10th Level 35.65 - 12.128 - 12.128 - 382.753 - 407.007
9th
10th Level 35.65 + 12.322 + 12.322 + 469.905 + 494.549
9th Level 32.30 - 12.412 - 12.412 - 465.355 - 490.178
8th
9th Level 32.30 +12.566 +12.566 + 551.499 + 576.631
8th Level 28.95 - 12.636 - 12.636 - 548.193 - 573.465
7th
8th Level 28.95 + 12.748 + 12.748 + 632.814 + 656.311
7th Level 25.60 - 12.795 - 12.795 - 631.029 - 656.618
6th
7th Level 25.60 + 12.851 + 12.851 + 713.536 + 739.237
6th Level 22.25 - 12.863 - 12.863 - 713.585 - 739.312
5th
6th Level 22.25 + 12.835 + 12.835 + 793.225 + 818.896
5th Level 18.90 - 12.796 - 12.796 - 795.485 - 821.077
4th
5th Level 18.90 + 12.638 + 12.638 + 871.226 + 896.502
4th Level 15.55 - 12.517 - 12.517 - 876.193 - 901.227
3rd
4
th Level 15.55 + 12.159 + 12.159 + 946.551 + 970.869
3rd
Level 12.20 - 11.916 - 11.916 - 954.922 - 978.754
2nd
3
rd Level 12.20 + 11.227 + 11.227 + 1017.803 + 1040.258
2nd
Level 8.85 - 10.757 - 10.757 - 1030.546 - 1052.061
1st
2nd
Level 8.85 + 9.732 + 9.732 + 1084.901 + 1104.372
1st Level 5.50 - 9.248 - 9.248 - 1098.766 - 1117.263
Ground
1st Level 5.50 + 5.567 + 5.567 + 1354.254 + 1365.388
Ground
Level 1.50 - 3.475 - 3.475 - 1402.894 - 1409.844
Footing
Ground
Level 1.50 + 2.215 + 2.215 + 457.035 + 461.465
Footing
Level 0 - 1.021 - 1.021 - 634.563 - 636.606
It has been seen from the Table 11 that roof deflection was well within the permissible
deflection for all cases after providing the shear wall in 6th
and 7th
frames, respectively.
Table 11: Storey drift of shear wall in 6th
and 7th
frames
STOREY
NO.
Height
( m )
Storey Drift of shear wall for load
combination
PUSH 2
(mm)
Solution of Shear Wall Location in Multi-Storey Building
Anshuman. S, Dipendu Bhunia, Bhavin Ramjiyani
International Journal of Civil and Structural Engineering
Volume 2 Issue 2 2011
503
Step 0 Step 1
ROOF 52.40 0.0030 194
14TH
49.05 0.0002 170
13TH
45.70 0.0002 139.8
12TH
42.35 0.0001 134
11TH
39.00 0.0000 127..4
10TH
25.65 0.0000 119.9
9TH
32.30 0.0000 111.6
8TH
28.95 0.0000 102.6
7TH
25.60 0.0000 92.7
6TH
22.25 0.0000 82.2
5TH
18.90 0.0000 70.9
4TH
15.55 0.0000 59.1
3RD
12.20 0.0000 46.9
2ND
8.85 0.0000 34.2
1ST
5.50 0.0000 21.3
GROUND 1.50 0.0000 1.5
Results for Shear wall in 1st
and 12th
frames
It has also seen from Table 12 that shear force was increased at the ground level in 1st and
12th
frames after providing shear wall in 1st and 12
th frames.
Table 12: Shear force for shear wall in 1st and 12
th frame
Storey
Level
Height
(m)
Shear force in shear wall for load combination
PUSH 2 (In kN )
Step 0 Step 1
Shear wall
1
Shear wall
2 Shear wall 1 Shear wall 2
14th
Roof level 52.40 - 6.179 - 6.179 - 22.726 - 35.795
14th Level 49.05 + 6.179 + 6.179 + 22.726 + 35.795
13th
14th Level 49.05 - 2.129 - 2.129 - 59.632 - 63.918
13th Level 45.70 + 2.129 + 2.129 + 59.632 + 63.918
12th
13th Level 45.70 - 2.705 - 2.705 - 91.758 - 91.173
12th Level 42.35 + 2.705 + 2.705 + 91.758 + 91.173
11th
12th Level 42.35 - 2.799 - 2.799 - 124.576 - 130.178
11th
Level 39.00 + 2.799 + 2.799 + 124.576 + 130.178
10th
11th
Level 39.00 - 2.935 - 2.935 - 157.513 - 163.380
10th Level 35.65 + 2.935 + 2.935 + 157.513 + 163.380
9th
10th Level 35.65 - 3.055 - 3.055 - 190.516 - 196.623
9th Level 32.30 + 3.055 + 3.055 + 190.516 + 196.623
8th
9th Level 32.30 - 3.165 - 3.165 - 223.456 - 229.782
8th Level 28.95 + 3.165 + 3.165 + 223.456 + 229.782
7th
8th Level 28.95 - 3.256 - 3.256 - 256.192 - 262.701
7th Level 25.60 + 3.256 + 3.256 + 256.192 + 262.701
6th
7th Level 25.60 - 3.316 - 3.316 - 288.553 - 295.182
6th Level 22.25 + 3.316 + 3.316 + 288.553 + 295.182
5th
6th Level 22.25 - 3.325 - 3.325 - 320.312 - 326.960
5th Level 18.90 + 3.325 + 3.325 + 320.312 + 326.960
Solution of Shear Wall Location in Multi-Storey Building
Anshuman. S, Dipendu Bhunia, Bhavin Ramjiyani
International Journal of Civil and Structural Engineering
Volume 2 Issue 2 2011
504
4th
5th Level 18.90 - 3.257 - 3.257 - 351.159 - 357.670
4th Level 15.55 + 3.257 + 3.257 + 351.159 + 357.670
3rd
4
th Level 15.55 - 3.074 - 3.074 - 380.655 - 386.802
3rd
Level 12.20 + 3.074 + 3.074 + 380.655 + 386.802
2nd
3
rd Level 12.20 - 2.702 - 2.702 - 408.206 - 413.608
2nd
Level 8.85 + 2.702 + 2.702 + 408.206 + 413.608
1st
2nd
Level 8.85 - 2.234 - 2.234 - 432.798 - 736.366
1st Level 5.50 + 2.234 + 2.234 + 432.798 + 736.366
Ground
1st Level 5.50 - 0.388 - 0.388 - 454.607 - 455.384
Ground
Level 1.50 + 0.388 + 0.388 + 454.607 + 455.384
Footing
Ground
Level 1.50 - 1.632 - 1.632 - 477.792 - 474.527
Footing
Level 0 + 1.632 + 1.632 + 477.792 + 474.527
It has also seen from Table 13 that bending moment was increased at the ground level in 1st
and 12th
frames after providing shear wall in 1st and 12
th frames.
Table 13: Bending moment for shear wall in 1st and 12
th frame
Storey
Level
Height
(m)
Bending Moment in shear wall for load combination
PUSH 2 (In kN )
Step 0 Step 1
Shear wall
1
Shear wall
2 Shear wall 1 Shear wall 2
14th
Roof level 52.40 + 13.361 + 13.361 + 37.465 + 65.808
14th Level 49.05 - 7.338 - 7.338 - 38.668 - 54.107
13th
14th Level 49.05 + 3.144 + 3.144 + 102.956 - 109.291
13th Level 45.70 - 3.989 - 3.989 - 96.811 - 104.835
12th
13th Level 45.70 + 4.529 + 4.529 + 156.377 - 165.444
12th Level 42.35 - 4.531 - 4.531 - 151.013 - 160.086
11th
12th Level 42.35 + 4.646 + 4.646 + 211.267 +220.565
11th
Level 39.00 - 4.731 - 4.731 - 206.064 - 215.529
10th
11th
Level 39.00 + 4.880 + 4.880 + 266.199 + 275.958
10th Level 35.65 - 4.951 - 4.951 - 261.487 - 271.367
9th
10th Level 35.65 + 5.084 + 5.084 + 321.148 + 331.311
9th Level 32.30 - 5.151 - 5.151 - 317.079 - 327.376
8th
9th Level 32.30 + 5.272 + 5.272 + 375.891 - 386.428
8th Level 28.95 - 5.331 - 5.331 - 372,689 - 383.342
7th
8th Level 28.95 + 5.431 + 5.431 + 430.188 + 441.045
7th Level 25.60 - 5.476 - 5.476 - 428.056 - 439.004
6th
7th Level 25.60 + 5.542 + 5.542 + 483.739 + 494.819
6th Level 22.25 - 5.566 - 5.566 - 482.914 - 494.040
5th
6th Level 22.25 + 5.575 + 5.575 + 536.142 + 547.288
5th Level 18.90 - 5.564 - 5.564 - 536.905 - 548.028
4th
5th Level 18.90 + 5.487 + 5.487 + 586.833 + 597.804
4th Level 15.55 - 5.422 - 5.422 - 589.551 - 600.392
3rd
4
th Level 15.55 + 5.219 + 5.219 + 635.012 + 645.447
3rd
Level 12.20 - 5.079 - 5.079 - 640.183 - 650.338
2nd
3
rd Level 12.20 + 4.669 + 4.669 + 679.624 + 688.962
2nd
Level 8.85 - 4.381 - 4.381 - 687.866 - 696.626
Solution of Shear Wall Location in Multi-Storey Building
Anshuman. S, Dipendu Bhunia, Bhavin Ramjiyani
International Journal of Civil and Structural Engineering
Volume 2 Issue 2 2011
505
1st
2nd
Level 8.85 + 3.840 + 3.840 + 720.792 + 728.471
1st Level 5.50 - 3.643 - 3.643 - 729.081 - 736.366
Ground
1st Level 5.50 + 1.519 + 1.519 + 891.424 + 894.463
Ground
Level 1.50 - 0.035 - 0.035 - 927.003 - 927.073
Footing
Ground
Level 1.50 + 1.861 + 1.861 + 288.393 + 284.671
Footing
Level 0 - 0.587 - 0.587 - 428.294 - 427.119
It has been seen from the Table 14 that roof deflection was well within the permissible
deflection for all cases after providing the shear wall in 1st and 12
th frames, respectively.
Table 14: Storey drift of shear wall in 1st and 12
th frame
STOREY
NO.
Height
( m )
Storey Drift of shear wall for load
combination
PUSH 2
(mm)
Step 0 Step 1
ROOF 52.40 0.0031 102.9
14TH
49.05 0.0017 100.1
13TH
45.70 0.0004 96.7
12TH
42.35 0.0000 92.7
11TH
39.00 0.0000 88.1
10TH
25.65 0.0000 83.0
9TH
32.30 0.0000 77.2
8TH
28.95 0.0000 70.9
7TH
25.60 0.0000 64.0
6TH
22.25 0.0000 56.7
5TH
18.90 0.0000 48.8
4TH
15.55 0.0000 40.6
3RD
12.20 0.0000 32.1
2ND
8.85 0.0000 23.4
1ST
5.50 0.0000 14.5
GROUND 1.50 0.0000 1.0
Conclusions
The above study shows the idea about the location for providing the shear wall which was
based on the elastic and inelastic analyses in this paper.
It has been observed that the top deflection was reduced and reached within the permissible
deflection after providing the shear wall in any of the 6th
& 7th
frames and 1st and 12
th frames
in the shorter direction.
Solution of Shear Wall Location in Multi-Storey Building
Anshuman. S, Dipendu Bhunia, Bhavin Ramjiyani
International Journal of Civil and Structural Engineering
Volume 2 Issue 2 2011
506
It has been also observed that the both bending moment and shear force in the 1st and 12
th
frame were reduced after providing the shear wall in any of the 6th
& 7th
frames and 1st and
12th
frames in the shorter direction.
It has been observed that the in inelastic analysis performance point was small and within the
elastic limit.
Thus result obtained using elastic analyses are adequate.
Hence, it can be said that shear wall can be provided in 6th
and 7th
frames or 1st and 12
th
frames in the shorter direction.
References
1. Bureau of Indian Standards: IS-875, part 1 (1987), dead loads on buildings and
Structures, New Delhi, India.
2. Bureau of Indian Standards: IS-875, part 2 (1987), live loads on buildings and
Structures, New Delhi, India.
3. Bureau of Indian Standards: IS-1893, part 1 (2002), “Criteria for Earthquake
Resistant Design of Structures: Part 1 General provisions and Buildings”, New
Delhi, India.
4. Bernhard Cardan (September 1961), “Concrete Shear Walls Combined with
Rigid Frames in Multistory Buildings Subject to Lateral Loads”, Journal of
American Concrete Institute, 58, pp 299-316,
5. Li Qiusheng, Cao hong and Li Guiqing “analysis of free vibrations of tall
buildings” ASCE.
6. David V. Rosowsky (November 2002), “Reliability-based seismic design of
wood shear walls” Journal of Structural Engineering” ASCE.
7. SAP2000: Advanced 10.0.5 (2006), static and Dynamic Finite Element Analysis
of Structures, Computers and Structures Inc., Berkeley, CA.
8. Stavros Syngellakis' and Idris A. Akintilo (1991), “nonlinear dynamics of
coupled shear walls using transfer matrices” ASCE.
9. Maurice W. White and J. Daniel Dolan (1995), “Nonlinear shear wall analysis”
Technical Notes, Journal of Structural Engineering” ASCE.
10. John Bolander Jr. and James K. Wight (1991), “Finite element modeling of
shearwall- dominant buildings” ASCE.