ShearWallDesignExamples
www.awc.org
2
CopyrightMaterials www.awc.org
This presentation is protected by US and International Copyright laws. Reproduction, distribution, display
and use of the presentation without written permission is prohibited.
American Wood Council 2013
-
Copyright 2013 American Wood CouncilAll rights reserved.
2
3
LearningObjectives www.awc.org
At the end of this program, participants will:
IdentifyandunderstandthebasicshearwallsystemtoresistwindandseismicloadsUnderstandthedifferencebetweensegmentedandperforatedshearwalldesignUnderstandholddowndesignBeabletoidentifyandanalyzeshearwallsperthe IRC,WFCM,and SDPWSandunderstandthedifferencesbetweenthem
Copyright 2013 American Wood Council
4
DesignExample1. 2009IRCBracedWalls2. 2001WFCMHighWindGuide3. 2001WFCMPrescriptive4. 2001WFCMEngineered5. 2008SDPWS
www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
3
5
DesignExampleAssumptions100mph(3secgust)ExposureB5/12roofpitch8'wallsL=36'W=30'WoodStructuralPanelSheathing
www.awc.org
6
DesignExample
Design first floor shear wall
www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
4
7
DesignExample1. 2009IRCBracedWalls2. 2001WFCMHighWindGuide3. 2001WFCMPrescriptive4. 2001WFCMEngineered5. 2008SDPWS
www.awc.org
8
DesignExample IRC2009IRCBracedWalls
www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
5
9
DesignExample IRC2009IRCBracedWalls
30'spanwith5/12roofpitchEavetoridgeheight=6.25'BraceWallLength=13'(0.9)=11.7'
www.awc.org
10
DesignExample IRC2009IRCBracedWalls
' ' OKLess than 3' NG
www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
6
11
DesignExample IRC2009IRCBracedWalls
Assuming 2' panel on perpendicular wall at each corner no hold-downs required (R602.10.1.4.1)
www.awc.org
12
1. 2009IRCBracedWalls2. 2001WFCMHighWindGuide3. 2001WFCMPrescriptive4. 2001WFCMEngineered5. 2008SDPWS
DesignExample www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
7
13
SegmentedShearWallMethod www.awc.org
14
PerforatedShearWallMethod www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
8
15
Shear/uplift anchorage design tables are found here:Wind (Exposure B)Table 3.2 Sill or Bottom Plate Connections (plf capacity)Table 3.2A Wind Shear Loads - 1/2 & 5/8 Anchor Bolts (numbers of bolts in shear wall line)Table 3.2B Wind Shear Loads - 1/2 & 5/8 Anchor Bolts (bolt spacing)Table 3.2C Wind Uplift Loads (bolt spacing)Table 3.4 Rafter/Truss Connections (lbs capacity)
DesignExample www.awc.org
16
2001WFCMHighWindGuide 100mphExp.B
L/W =36/30=1.2
Interpolate=48.6%
DesignExample WFCMHWG www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
9
17
2001WFCMHighWindGuide 100mphExp.B
AssumesPerforatedShearWall(PSW)
DesignExample WFCMHWG www.awc.org
18
7/16 wood structural panel continuous height over wall plates
8d common nails @ 6 OC on panel perimeter
8d common nails @ 12 OC in field
1/2 gypsum wallboard on interior
5d cooler nails @ 7 OC on panel perimeter
5d cooler nails @ 10 OC in field
panel exterior panel interior
Here are standard assembly details for shear wall panels from 2001 WFCM 3.4.4.2
DesignExample WFCM HWG www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
10
19
2001WFCMHighWindGuide 100mphExp.B
36' x48.6%=17.5' < 21' OK
DesignExample WFCMHWG www.awc.org
20
2001WFCMHighWindGuide 100mphExp.B
PSWrequiresholddownsatendsandfullysheathedwall
DesignExample WFCMHWG www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
11
21
2001WFCMHighWindGuide 100mphExp.B
HoldDowns=4,360lbs*
* Need to combine with top floor hold down requirements
DesignExample WFCM HWG www.awc.org
22
1. 2009IRCBracedWalls2. 2001WFCMHighWindGuide3. 2001WFCMPrescriptive4. 2001WFCMEngineered5. 2008SDPWS
DesignExample www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
12
23
2001WFCMPrescriptive interpolate=6.9'DesignExample WFCM www.awc.org
24
Segmentedshearwall
DesignExample WFCM2001WFCMPrescriptive interpolate=6.9'
www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
13
25
2001WFCMPrescriptiveDesignExample WFCM www.awc.org
26
2001WFCMPrescriptive 6.9' x1.3=9'
Whatifwedontcountthegypsumoninterior?
DesignExample WFCM www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
14
27
Segmentedshearwall assumingnointeriorgypsum13' >9' OK
2001WFCMPrescriptive required=9'DesignExample WFCM www.awc.org
28
Segmentedshearwall requiresholddownsoneachsegment
2001WFCMPrescriptive HolddownsDesignExample WFCM www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
15
29
Hold Downs*= 3,488 lbsw/ gypsum
3,488 / 1.3= 2,683 lbsw/o gypsum
* Need to combine with top floor hold down requirements
2001WFCMPrescriptive HolddownsDesignExample WFCM www.awc.org
30
PSWrequiresholddownsatendsandfullysheathedwall
DesignExample WFCM2001WFCMPrescriptive PSW
www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
16
31
% Full-height sheathing21' / 36' = 58%
Interpolated= 1.34
6.9'(1.34) = 9.2'w/ gypsum
9'(1.34) = 12.1'w/o gypsum
21' Full-height sheathing > 12.1' OK
DesignExample WFCM2001WFCMPrescriptive PSW
www.awc.org
32
1. 2009IRCBracedWalls2. 2001WFCMHighWindGuide3. 2001WFCMPrescriptive4. 2001WFCMEngineered5. 2008SDPWS
DesignExample www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
17
33
2001WFCMEngineeredwroof =82plfwfloor =103plfwtotal =185plf185(30')/2=2,775lbs
DesignExample WFCM www.awc.org
34
DesignExample WFCM2001WFCMPrescriptive Engineered
www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
18
35
RequiredCapacity=2,775lbs7/16WSP=240plf240(1.4)=336plf (Footnote1)Gypsum=100plf (Table3C)Total=436plf2,775/436=6.4'(w/gypsum)2,775/336 =8.3' (w/ogypsum)
DesignExample WFCM2001WFCMPrescriptive Segmented
GypsumWallboard2 1/2 5d Cooler Nails Unblocked74
10031253
www.awc.org
36
2,775 lbs
8' > 6.4' assuming interior gypsum OK
DesignExample WFCM2001WFCMEngineered Segmented
www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
19
37
2,775 lbs
13' > 8.3' assuming NO interior gypsum OK
DesignExample WFCM2001WFCMEngineered Segmented
www.awc.org
38
SupplementTable3BV=2,775lbsv=436plf (w/gypsum)v=336plf (w/ogypsum)%FHSheathing=58%InterpolatedFactor =0.62436(0.62)=270plf2,775/270 =10.3' (w/ gypsum)336(0.62)=208plf2,775/208=13.3'(w/ogypsum)
DesignExample WFCM2001WFCMEngineered PSW
www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
20
39
21' Full-height sheathing > 13.3' OK
DesignExample WFCM2001WFCMEngineered PSW
www.awc.org
40
T=vhv=436plf (w/gypsum)v=336plf (w/ogypsum)h=8'T=436(8')=3,488lbsT=336(8')=2,688lbs*Need to combine with top floor
hold down requirements
DesignExample WFCM2001WFCMEngineered Holddowns
www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
21
41
1. 2009IRCBracedWalls2. 2001WFCMHighWindGuide3. 2001WFCMPrescriptive4. 2001WFCMEngineered5. 2008SDPWS
DesignExample www.awc.org
42
2008SDPWS WSPCapacity
ASDCapacity=670/2=335plf
DesignExample SDPWS www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
22
43
ASDCapacity=200/2=100plf
DesignExample SDPWS2008SDPWS GypsumCapacity
www.awc.org
44
RequiredCapacity=2,775lbsWSP=335plfGypsum=100plfTotal=435plf2,775/435=6.4'(w/gypsum)2,775/335=8.3'(w/ogypsum)
DesignExample SDPWS2008SDPWS GypsumCapacity
www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
23
45
2,775 lbs
DesignExample SDPWS2008SDPWS SegmentedShearWall
www.awc.org
46
Co =0.62w/gypsum435(0.62)=2702,775/270=10.3'w/ogypsum335(0.62)=2082,775/208=13.3'21'Fullheightsheathing>13.3' OK
DesignExample SDPWS2008SDPWS PerforatedShearWall
www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
24
47
DesignExample SDPWS2008SDPWS PerforatedShearWall
2,775 lbs
www.awc.org
48
T=vhv=2,775/8' =347plfh=8'T=347(8')=2,775lbs**Need to combine with top floor
hold down requirements
DesignExample SDPWS2008SDPWS Holddowns*(Segmented)
www.awc.org
-
Copyright 2013 American Wood CouncilAll rights reserved.
25
49
V=2,775lbsh=8'Co =0.62Li =21'T=1,705lbs*Need to combine with top floor
hold down requirements
DesignExample SDPWS2008SDPWS Holddowns*(PSW)
www.awc.org
50
Code/Standard Segmented ShearWallLengthPerforatedShear
WallLengthHolddown
Requirements
2009IRCBracedWalls 11.7' n/a none2001WFCMHighWindGuide n/a 17.5' 4,360lbs2001WFCMPrescriptive 6.9'(9') 9.2'(12.1') 3,488(2,683)lbs2001WFCMEngineered 6.4'(8.3') 10.3'(13.3') 3,488(2,688)lbs
2008SDPWS 6.4'(8.3') 10.3'(13.3') 2,775lbs1,705lbs(PSW)
1st of2Story;30' span;5/12pitch; 100mphExp.B
Parentheticalvaluesassume NOinterior gypsum
DesignExample Summary www.awc.org
-