Selection and Application Guide Panelboards and Application Guide Quality Panelboards Engineered for...
Transcript of Selection and Application Guide Panelboards and Application Guide Quality Panelboards Engineered for...
AlabamaBirmingham(205) 879-7030Mobile(334) 621-0822Montgomery(334) 271-4486
AlaskaAnchorage(907) 346-2489
ArizonaPhoenix(602) 944-7956
ArkansasLittle Rock(501) 897-1385
CaliforniaFresno(209) 264-5018Los Angeles(714) 979-6600Sacramento(916) 631-9433San Diego(619) 569-8015San Francisco(510) 429-1200
ColoradoColorado Springs(719) 473-7880Denver(303) 694-3770Ft. Collins(303) 223-2712
ConnecticutWallingford(203) 265-5003
FloridaFt. Lauderdale(305) 484-3888Fort Myers(813) 656-3605Jacksonville(904) 363-0087Miami(305) 592-4106Orlando(407) 894-7771Tampa(813) 287-2450West Palm Beach(407) 627-7408
GeorgiaAtlanta(770) 458-4353Macon(912) 745-6393Savannah(912) 354-5092
HawaiiHonolulu(808) 533-7135
IdahoBoise(208) 342-6852
IllinoisChicago(847) 310-6500Peoria(309) 689-0823
IndianaEvansville(812) 422-9176Fort Wayne(219) 490-6999Indianapolis(317) 848-5500South Bend(219) 232-6050
IowaDes Moines(515) 280-1614
KansasWichita(316) 942-1409
KentuckyLouisville(502) 426-4647
LouisianaBaton Rouge(504) 387-6987New Orleans(504) 837-8500Shreveport(318) 424-0720
MainePortland(207) 854-0021
MarylandLandover(301) 459-2044
MassachusettsAndover(508) 685-6077Worcester(508) 792-4566
MichiganDetroit(810) 253-1000Grand Rapids(616) 530-9777
MinnesotaMinneapolis(612) 942-8888
MississippiJackson(601) 936-9360
MissouriKansas City(913) 491-3740St. Louis(314) 567-3900
NebraskaOmaha(402) 397-1940
NevadaLas Vegas(702) 734-1022
New HampshireManchester(603) 626-0702
New JerseyCranford(908) 276-7227
New MexicoAlbuquerque(505) 881-1611
New YorkAlbany(518) 365-4569Buffalo(716) 834-3815Long Island(516) 484-7560Syracuse(315) 453-2935
North CarolinaAsheville(704) 253-8299Charlotte(704) 536-1201Greensboro(910) 852-1758Raleigh(919) 782-3365Wilmington(910) 313-0034
North DakotaBismarck(701) 258-9555Fargo(701) 293-7709
OhioCincinnati(513) 398-9288Cleveland(216) 642-0701Columbus(614) 766-2204Dayton(513) 279-0458Toledo(419) 893-7197Wooster(216) 262-3268
OklahomaOklahoma City(405) 235-7515Tulsa(918) 665-1806
OregonPortland(503) 635-6700
PennsylvaniaPhiladelphia(215) 646-3800Pittsburgh(412) 788-8060York(717) 854-9776
Rhode IslandProvidence(401) 732-9966
South CarolinaColumbia(803) 359-7715Greenville(803) 288-3490
TennesseeChattanooga(423) 267-7412Johnson City(423) 434-9270Knoxville(615) 690-5172Memphis(901) 761-2123Nashville(615) 367-9403
TexasAustin(512) 416-0181Dallas(817) 652-9653Fort Worth(817) 838-9770Houston(713) 690-3000San Antonio(210) 525-7845
UtahSalt Lake City(801) 266-9612
VirginiaRichmond(804) 288-8311Roanoke(703) 982-2776Virginia Beach(804) 486-0174
WashingtonSeattle(206) 828-6600Spokane(509) 468-3717Tacoma(206) 926-7663
Washington, D.C.(301) 459-2044
West Virginia(304) 522-9732
WisconsinGreen Bay(414) 336-1144Milwaukee(414) 774-9500
CanadaMississauga,Ontario(905) 819-8000Pointe Claire,Quebec(514) 695-7300Vancouver,British Columbia(604) 435-0880
InternationalTel: (770) 751-2291Fax: (770) 751-2496TLX: 822024SEA
IBU UF
Siemens Energy & Automation Sales Offices
1
Sentron® PanelboardsSelection and Application Guide
QualityPanelboardsEngineered
for Lighting and Power Applications
3 easy steps to selecta Sentron Panelboard
S1, S2 and SE and Lighting Panelboards:
Step 1 – Determine voltage, system, amperage and interrupting rating of branch devices, and modificationsif any. example for standard lighting panelboardAmperage 250AVoltage 208Y/1120System 3x4WMain Main LugBranches 10K AIR, 42-20/1Modifications NoneFeed Location TopMounting Surface
Step 2 – Open flap and create catalog number by followingPanelboard Coding System. The BL branch breakers were select-ed from the Branch Breaker Selection table on page 10.
1-S1C42ML250ATS42-20/1 BL
Step 3 – Select enclosure size by the number of circuits asshown in the Panelboard Dimensional chart on page 14.
1-S1C42ML250ATS42-20 BLBox size – 44” high
A unique feature of the S1/S2/SE panels is that they can accommodate either feed-thru lugs or one sub-feed circuit breaker (up to 600A) without any addition in box height. For ourexample changing the branch circuits to 39-20/1 and 1-125/3, we have the following:
1-S1C42ML250ATS39-20/1 BL1-125/3 QJ2Box size – 44” high
The QJ2 subfeed was selected from the table of Subfeed Breakers on page 10. The box height remains the same.
S4, S5, F1 and F2 Power Panelboards:
Step 1 – Same as step 1 above
Step 2 – The branch breaker frames in addition to the mounting height requirements were chosen from the BranchBreaker Selection table on page 22.(Frame) (Mounting Height)6-125/3 QJ2 5” = 15”2-225/3 QJ2 5” = 5”1-250/3 FXD6 5” = 5”
25” Unit Space requiredStep 3 – Based on required Branch Unit Space see ref.Enclosure Data on page 23 to determine Enclosure Height.
400A MLO; 25” Unit Space Enclosure Height = 60”
Then complete Catalog Number:S4C60ML400ATS
Open flap for “How to build a catalog number” Bulletin 4.5-2B
AlabamaBirmingham(205) 879-7030Mobile(334) 621-0822Montgomery(334) 271-4486
AlaskaAnchorage(907) 346-2489
ArizonaPhoenix(602) 944-7956
ArkansasLittle Rock(501) 897-1385
CaliforniaFresno(209) 264-5018Los Angeles(714) 979-6600Sacramento(916) 631-9433San Diego(619) 569-8015San Francisco(510) 429-1200
ColoradoColorado Springs(719) 473-7880Denver(303) 694-3770Ft. Collins(303) 223-2712
ConnecticutWallingford(203) 265-5003
FloridaFt. Lauderdale(305) 484-3888Fort Myers(813) 656-3605Jacksonville(904) 363-0087Miami(305) 592-4106Orlando(407) 894-7771Tampa(813) 287-2450West Palm Beach(407) 627-7408
GeorgiaAtlanta(770) 458-4353Macon(912) 745-6393Savannah(912) 354-5092
HawaiiHonolulu(808) 533-7135
IdahoBoise(208) 342-6852
IllinoisChicago(847) 310-6500Peoria(309) 689-0823
IndianaEvansville(812) 422-9176Fort Wayne(219) 490-6999Indianapolis(317) 848-5500South Bend(219) 232-6050
IowaDes Moines(515) 280-1614
KansasWichita(316) 942-1409
KentuckyLouisville(502) 426-4647
LouisianaBaton Rouge(504) 387-6987New Orleans(504) 837-8500Shreveport(318) 424-0720
MainePortland(207) 854-0021
MarylandLandover(301) 459-2044
MassachusettsAndover(508) 685-6077Worcester(508) 792-4566
MichiganDetroit(810) 253-1000Grand Rapids(616) 530-9777
MinnesotaMinneapolis(612) 942-8888
MississippiJackson(601) 936-9360
MissouriKansas City(913) 491-3740St. Louis(314) 567-3900
NebraskaOmaha(402) 397-1940
NevadaLas Vegas(702) 734-1022
New HampshireManchester(603) 626-0702
New JerseyCranford(908) 276-7227
New MexicoAlbuquerque(505) 881-1611
New YorkAlbany(518) 365-4569Buffalo(716) 834-3815Long Island(516) 484-7560Syracuse(315) 453-2935
North CarolinaAsheville(704) 253-8299Charlotte(704) 536-1201Greensboro(910) 852-1758Raleigh(919) 782-3365Wilmington(910) 313-0034
North DakotaBismarck(701) 258-9555Fargo(701) 293-7709
OhioCincinnati(513) 398-9288Cleveland(216) 642-0701Columbus(614) 766-2204Dayton(513) 279-0458Toledo(419) 893-7197Wooster(216) 262-3268
OklahomaOklahoma City(405) 235-7515Tulsa(918) 665-1806
OregonPortland(503) 635-6700
PennsylvaniaPhiladelphia(215) 646-3800Pittsburgh(412) 788-8060York(717) 854-9776
Rhode IslandProvidence(401) 732-9966
South CarolinaColumbia(803) 359-7715Greenville(803) 288-3490
TennesseeChattanooga(423) 267-7412Johnson City(423) 434-9270Knoxville(615) 690-5172Memphis(901) 761-2123Nashville(615) 367-9403
TexasAustin(512) 416-0181Dallas(817) 652-9653Fort Worth(817) 838-9770Houston(713) 690-3000San Antonio(210) 525-7845
UtahSalt Lake City(801) 266-9612
VirginiaRichmond(804) 288-8311Roanoke(703) 982-2776Virginia Beach(804) 486-0174
WashingtonSeattle(206) 828-6600Spokane(509) 468-3717Tacoma(206) 926-7663
Washington, D.C.(301) 459-2044
West Virginia(304) 522-9732
WisconsinGreen Bay(414) 336-1144Milwaukee(414) 774-9500
CanadaMississauga,Ontario(905) 819-8000Pointe Claire,Quebec(514) 695-7300Vancouver,British Columbia(604) 435-0880
InternationalTel: (770) 751-2291Fax: (770) 751-2496TLX: 822024SEA
IBU UF
Siemens Energy & Automation Sales Offices
Siemens Energy & Automation, Inc.Distribution Products Division3333 Old Milton ParkwayAlpharetta, GA 30202
© 1996 Siemens Energy & Automation, Inc. Bulletin 4.5-2B (Supersedes 4.5-2A)Siemens Is a registered trademark of Siemens AG. 10M1096SP Printed in U.S.A.
AlabamaBirmingham(205) 879-7030Mobile(334) 621-0822Montgomery(334) 271-4486
AlaskaAnchorage(907) 346-2489
ArizonaPhoenix(602) 944-7956
ArkansasLittle Rock(501) 897-1385
CaliforniaFresno(209) 264-5018Los Angeles(714) 979-6600Sacramento(916) 631-9433San Diego(619) 569-8015San Francisco(510) 429-1200
ColoradoColorado Springs(719) 473-7880Denver(303) 694-3770Ft. Collins(303) 223-2712
ConnecticutWallingford(203) 265-5003
FloridaFt. Lauderdale(305) 484-3888Fort Myers(813) 656-3605Jacksonville(904) 363-0087Miami(305) 592-4106Orlando(407) 894-7771Tampa(813) 287-2450West Palm Beach(407) 627-7408
GeorgiaAtlanta(770) 458-4353Macon(912) 745-6393Savannah(912) 354-5092
HawaiiHonolulu(808) 533-7135
IdahoBoise(208) 342-6852
IllinoisChicago(847) 310-6500Peoria(309) 689-0823
IndianaEvansville(812) 422-9176Fort Wayne(219) 490-6999Indianapolis(317) 848-5500South Bend(219) 232-6050
IowaDes Moines(515) 280-1614
KansasWichita(316) 942-1409
KentuckyLouisville(502) 426-4647
LouisianaBaton Rouge(504) 387-6987New Orleans(504) 837-8500Shreveport(318) 424-0720
MainePortland(207) 854-0021
MarylandLandover(301) 459-2044
MassachusettsAndover(508) 685-6077Worcester(508) 792-4566
MichiganDetroit(810) 253-1000Grand Rapids(616) 530-9777
MinnesotaMinneapolis(612) 942-8888
MississippiJackson(601) 936-9360
MissouriKansas City(913) 491-3740St. Louis(314) 567-3900
NebraskaOmaha(402) 397-1940
NevadaLas Vegas(702) 734-1022
New HampshireManchester(603) 626-0702
New JerseyCranford(908) 276-7227
New MexicoAlbuquerque(505) 881-1611
New YorkAlbany(518) 365-4569Buffalo(716) 834-3815Long Island(516) 484-7560Syracuse(315) 453-2935
North CarolinaAsheville(704) 253-8299Charlotte(704) 536-1201Greensboro(910) 852-1758Raleigh(919) 782-3365Wilmington(910) 313-0034
North DakotaBismarck(701) 258-9555Fargo(701) 293-7709
OhioCincinnati(513) 398-9288Cleveland(216) 642-0701Columbus(614) 766-2204Dayton(513) 279-0458Toledo(419) 893-7197Wooster(216) 262-3268
OklahomaOklahoma City(405) 235-7515Tulsa(918) 665-1806
OregonPortland(503) 635-6700
PennsylvaniaPhiladelphia(215) 646-3800Pittsburgh(412) 788-8060York(717) 854-9776
Rhode IslandProvidence(401) 732-9966
South CarolinaColumbia(803) 359-7715Greenville(803) 288-3490
TennesseeChattanooga(423) 267-7412Johnson City(423) 434-9270Knoxville(615) 690-5172Memphis(901) 761-2123Nashville(615) 367-9403
TexasAustin(512) 416-0181Dallas(817) 652-9653Fort Worth(817) 838-9770Houston(713) 690-3000San Antonio(210) 525-7845
UtahSalt Lake City(801) 266-9612
VirginiaRichmond(804) 288-8311Roanoke(703) 982-2776Virginia Beach(804) 486-0174
WashingtonSeattle(206) 828-6600Spokane(509) 468-3717Tacoma(206) 926-7663
Washington, D.C.(301) 459-2044
West Virginia(304) 522-9732
WisconsinGreen Bay(414) 336-1144Milwaukee(414) 774-9500
CanadaMississauga,Ontario(905) 819-8000Pointe Claire,Quebec(514) 695-7300Vancouver,British Columbia(604) 435-0880
InternationalTel: (770) 751-2291Fax: (770) 751-2496TLX: 822024SEA
IBU UF
Siemens Energy & Automation Sales Offices
1
Sentron® PanelboardsSelection and Application Guide
QualityPanelboardsEngineered
for Lighting and Power Applications
3 easy steps to selecta Sentron Panelboard
S1, S2 and SE and Lighting Panelboards:
Step 1 – Determine voltage, system, amperage and interrupting rating of branch devices, and modificationsif any. example for standard lighting panelboardAmperage 250AVoltage 208Y/1120System 3x4WMain Main LugBranches 10K AIR, 42-20/1Modifications NoneFeed Location TopMounting Surface
Step 2 – Open flap and create catalog number by followingPanelboard Coding System. The BL branch breakers were select-ed from the Branch Breaker Selection table on page 10.
1-S1C42ML250ATS42-20/1 BL
Step 3 – Select enclosure size by the number of circuits asshown in the Panelboard Dimensional chart on page 14.
1-S1C42ML250ATS42-20 BLBox size – 44” high
A unique feature of the S1/S2/SE panels is that they can accommodate either feed-thru lugs or one sub-feed circuit breaker (up to 600A) without any addition in box height. For ourexample changing the branch circuits to 39-20/1 and 1-125/3, we have the following:
1-S1C42ML250ATS39-20/1 BL1-125/3 QJ2Box size – 44” high
The QJ2 subfeed was selected from the table of Subfeed Breakers on page 10. The box height remains the same.
S4, S5, F1 and F2 Power Panelboards:
Step 1 – Same as step 1 above
Step 2 – The branch breaker frames in addition to the mounting height requirements were chosen from the BranchBreaker Selection table on page 22.(Frame) (Mounting Height)6-125/3 QJ2 5” = 15”2-225/3 QJ2 5” = 5”1-250/3 FXD6 5” = 5”
25” Unit Space requiredStep 3 – Based on required Branch Unit Space see ref.Enclosure Data on page 23 to determine Enclosure Height.
400A MLO; 25” Unit Space Enclosure Height = 60”
Then complete Catalog Number:S4C60ML400ATS
Open flap for “How to build a catalog number” Bulletin 4.5-2B
AlabamaBirmingham(205) 879-7030Mobile(334) 621-0822Montgomery(334) 271-4486
AlaskaAnchorage(907) 346-2489
ArizonaPhoenix(602) 944-7956
ArkansasLittle Rock(501) 897-1385
CaliforniaFresno(209) 264-5018Los Angeles(714) 979-6600Sacramento(916) 631-9433San Diego(619) 569-8015San Francisco(510) 429-1200
ColoradoColorado Springs(719) 473-7880Denver(303) 694-3770Ft. Collins(303) 223-2712
ConnecticutWallingford(203) 265-5003
FloridaFt. Lauderdale(305) 484-3888Fort Myers(813) 656-3605Jacksonville(904) 363-0087Miami(305) 592-4106Orlando(407) 894-7771Tampa(813) 287-2450West Palm Beach(407) 627-7408
GeorgiaAtlanta(770) 458-4353Macon(912) 745-6393Savannah(912) 354-5092
HawaiiHonolulu(808) 533-7135
IdahoBoise(208) 342-6852
IllinoisChicago(847) 310-6500Peoria(309) 689-0823
IndianaEvansville(812) 422-9176Fort Wayne(219) 490-6999Indianapolis(317) 848-5500South Bend(219) 232-6050
IowaDes Moines(515) 280-1614
KansasWichita(316) 942-1409
KentuckyLouisville(502) 426-4647
LouisianaBaton Rouge(504) 387-6987New Orleans(504) 837-8500Shreveport(318) 424-0720
MainePortland(207) 854-0021
MarylandLandover(301) 459-2044
MassachusettsAndover(508) 685-6077Worcester(508) 792-4566
MichiganDetroit(810) 253-1000Grand Rapids(616) 530-9777
MinnesotaMinneapolis(612) 942-8888
MississippiJackson(601) 936-9360
MissouriKansas City(913) 491-3740St. Louis(314) 567-3900
NebraskaOmaha(402) 397-1940
NevadaLas Vegas(702) 734-1022
New HampshireManchester(603) 626-0702
New JerseyCranford(908) 276-7227
New MexicoAlbuquerque(505) 881-1611
New YorkAlbany(518) 365-4569Buffalo(716) 834-3815Long Island(516) 484-7560Syracuse(315) 453-2935
North CarolinaAsheville(704) 253-8299Charlotte(704) 536-1201Greensboro(910) 852-1758Raleigh(919) 782-3365Wilmington(910) 313-0034
North DakotaBismarck(701) 258-9555Fargo(701) 293-7709
OhioCincinnati(513) 398-9288Cleveland(216) 642-0701Columbus(614) 766-2204Dayton(513) 279-0458Toledo(419) 893-7197Wooster(216) 262-3268
OklahomaOklahoma City(405) 235-7515Tulsa(918) 665-1806
OregonPortland(503) 635-6700
PennsylvaniaPhiladelphia(215) 646-3800Pittsburgh(412) 788-8060York(717) 854-9776
Rhode IslandProvidence(401) 732-9966
South CarolinaColumbia(803) 359-7715Greenville(803) 288-3490
TennesseeChattanooga(423) 267-7412Johnson City(423) 434-9270Knoxville(615) 690-5172Memphis(901) 761-2123Nashville(615) 367-9403
TexasAustin(512) 416-0181Dallas(817) 652-9653Fort Worth(817) 838-9770Houston(713) 690-3000San Antonio(210) 525-7845
UtahSalt Lake City(801) 266-9612
VirginiaRichmond(804) 288-8311Roanoke(703) 982-2776Virginia Beach(804) 486-0174
WashingtonSeattle(206) 828-6600Spokane(509) 468-3717Tacoma(206) 926-7663
Washington, D.C.(301) 459-2044
West Virginia(304) 522-9732
WisconsinGreen Bay(414) 336-1144Milwaukee(414) 774-9500
CanadaMississauga,Ontario(905) 819-8000Pointe Claire,Quebec(514) 695-7300Vancouver,British Columbia(604) 435-0880
InternationalTel: (770) 751-2291Fax: (770) 751-2496TLX: 822024SEA
IBU UF
Siemens Energy & Automation Sales Offices
Siemens Energy & Automation, Inc.Distribution Products Division3333 Old Milton ParkwayAlpharetta, GA 30202
© 1996 Siemens Energy & Automation, Inc. Bulletin 4.5-2B (Supersedes 4.5-2A)Siemens Is a registered trademark of Siemens AG. 10M1096SP Printed in U.S.A.
AlabamaBirmingham(205) 879-7030Mobile(334) 621-0822Montgomery(334) 271-4486
AlaskaAnchorage(907) 346-2489
ArizonaPhoenix(602) 944-7956
ArkansasLittle Rock(501) 897-1385
CaliforniaFresno(209) 264-5018Los Angeles(714) 979-6600Sacramento(916) 631-9433San Diego(619) 569-8015San Francisco(510) 429-1200
ColoradoColorado Springs(719) 473-7880Denver(303) 694-3770Ft. Collins(303) 223-2712
ConnecticutWallingford(203) 265-5003
FloridaFt. Lauderdale(305) 484-3888Fort Myers(813) 656-3605Jacksonville(904) 363-0087Miami(305) 592-4106Orlando(407) 894-7771Tampa(813) 287-2450West Palm Beach(407) 627-7408
GeorgiaAtlanta(770) 458-4353Macon(912) 745-6393Savannah(912) 354-5092
HawaiiHonolulu(808) 533-7135
IdahoBoise(208) 342-6852
IllinoisChicago(847) 310-6500Peoria(309) 689-0823
IndianaEvansville(812) 422-9176Fort Wayne(219) 490-6999Indianapolis(317) 848-5500South Bend(219) 232-6050
IowaDes Moines(515) 280-1614
KansasWichita(316) 942-1409
KentuckyLouisville(502) 426-4647
LouisianaBaton Rouge(504) 387-6987New Orleans(504) 837-8500Shreveport(318) 424-0720
MainePortland(207) 854-0021
MarylandLandover(301) 459-2044
MassachusettsAndover(508) 685-6077Worcester(508) 792-4566
MichiganDetroit(810) 253-1000Grand Rapids(616) 530-9777
MinnesotaMinneapolis(612) 942-8888
MississippiJackson(601) 936-9360
MissouriKansas City(913) 491-3740St. Louis(314) 567-3900
NebraskaOmaha(402) 397-1940
NevadaLas Vegas(702) 734-1022
New HampshireManchester(603) 626-0702
New JerseyCranford(908) 276-7227
New MexicoAlbuquerque(505) 881-1611
New YorkAlbany(518) 365-4569Buffalo(716) 834-3815Long Island(516) 484-7560Syracuse(315) 453-2935
North CarolinaAsheville(704) 253-8299Charlotte(704) 536-1201Greensboro(910) 852-1758Raleigh(919) 782-3365Wilmington(910) 313-0034
North DakotaBismarck(701) 258-9555Fargo(701) 293-7709
OhioCincinnati(513) 398-9288Cleveland(216) 642-0701Columbus(614) 766-2204Dayton(513) 279-0458Toledo(419) 893-7197Wooster(216) 262-3268
OklahomaOklahoma City(405) 235-7515Tulsa(918) 665-1806
OregonPortland(503) 635-6700
PennsylvaniaPhiladelphia(215) 646-3800Pittsburgh(412) 788-8060York(717) 854-9776
Rhode IslandProvidence(401) 732-9966
South CarolinaColumbia(803) 359-7715Greenville(803) 288-3490
TennesseeChattanooga(423) 267-7412Johnson City(423) 434-9270Knoxville(615) 690-5172Memphis(901) 761-2123Nashville(615) 367-9403
TexasAustin(512) 416-0181Dallas(817) 652-9653Fort Worth(817) 838-9770Houston(713) 690-3000San Antonio(210) 525-7845
UtahSalt Lake City(801) 266-9612
VirginiaRichmond(804) 288-8311Roanoke(703) 982-2776Virginia Beach(804) 486-0174
WashingtonSeattle(206) 828-6600Spokane(509) 468-3717Tacoma(206) 926-7663
Washington, D.C.(301) 459-2044
West Virginia(304) 522-9732
WisconsinGreen Bay(414) 336-1144Milwaukee(414) 774-9500
CanadaMississauga,Ontario(905) 819-8000Pointe Claire,Quebec(514) 695-7300Vancouver,British Columbia(604) 435-0880
InternationalTel: (770) 751-2291Fax: (770) 751-2496TLX: 822024SEA
IBU UF
Siemens Energy & Automation Sales Offices
1
Sentron® PanelboardsSelection and Application Guide
QualityPanelboardsEngineered
for Lighting and Power Applications
3 easy steps to selecta Sentron Panelboard
S1, S2 and SE and Lighting Panelboards:
Step 1 – Determine voltage, system, amperage and interrupting rating of branch devices, and modificationsif any. example for standard lighting panelboardAmperage 250AVoltage 208Y/1120System 3x4WMain Main LugBranches 10K AIR, 42-20/1Modifications NoneFeed Location TopMounting Surface
Step 2 – Open flap and create catalog number by followingPanelboard Coding System. The BL branch breakers were select-ed from the Branch Breaker Selection table on page 10.
1-S1C42ML250ATS42-20/1 BL
Step 3 – Select enclosure size by the number of circuits asshown in the Panelboard Dimensional chart on page 14.
1-S1C42ML250ATS42-20 BLBox size – 44” high
A unique feature of the S1/S2/SE panels is that they can accommodate either feed-thru lugs or one sub-feed circuit breaker (up to 600A) without any addition in box height. For ourexample changing the branch circuits to 39-20/1 and 1-125/3, we have the following:
1-S1C42ML250ATS39-20/1 BL1-125/3 QJ2Box size – 44” high
The QJ2 subfeed was selected from the table of Subfeed Breakers on page 10. The box height remains the same.
S4, S5, F1 and F2 Power Panelboards:
Step 1 – Same as step 1 above
Step 2 – The branch breaker frames in addition to the mounting height requirements were chosen from the BranchBreaker Selection table on page 22.(Frame) (Mounting Height)6-125/3 QJ2 5” = 15”2-225/3 QJ2 5” = 5”1-250/3 FXD6 5” = 5”
25” Unit Space requiredStep 3 – Based on required Branch Unit Space see ref.Enclosure Data on page 23 to determine Enclosure Height.
400A MLO; 25” Unit Space Enclosure Height = 60”
Then complete Catalog Number:S4C60ML400ATS
Open flap for “How to build a catalog number” Bulletin 4.5-2B
AlabamaBirmingham(205) 879-7030Mobile(334) 621-0822Montgomery(334) 271-4486
AlaskaAnchorage(907) 346-2489
ArizonaPhoenix(602) 944-7956
ArkansasLittle Rock(501) 897-1385
CaliforniaFresno(209) 264-5018Los Angeles(714) 979-6600Sacramento(916) 631-9433San Diego(619) 569-8015San Francisco(510) 429-1200
ColoradoColorado Springs(719) 473-7880Denver(303) 694-3770Ft. Collins(303) 223-2712
ConnecticutWallingford(203) 265-5003
FloridaFt. Lauderdale(305) 484-3888Fort Myers(813) 656-3605Jacksonville(904) 363-0087Miami(305) 592-4106Orlando(407) 894-7771Tampa(813) 287-2450West Palm Beach(407) 627-7408
GeorgiaAtlanta(770) 458-4353Macon(912) 745-6393Savannah(912) 354-5092
HawaiiHonolulu(808) 533-7135
IdahoBoise(208) 342-6852
IllinoisChicago(847) 310-6500Peoria(309) 689-0823
IndianaEvansville(812) 422-9176Fort Wayne(219) 490-6999Indianapolis(317) 848-5500South Bend(219) 232-6050
IowaDes Moines(515) 280-1614
KansasWichita(316) 942-1409
KentuckyLouisville(502) 426-4647
LouisianaBaton Rouge(504) 387-6987New Orleans(504) 837-8500Shreveport(318) 424-0720
MainePortland(207) 854-0021
MarylandLandover(301) 459-2044
MassachusettsAndover(508) 685-6077Worcester(508) 792-4566
MichiganDetroit(810) 253-1000Grand Rapids(616) 530-9777
MinnesotaMinneapolis(612) 942-8888
MississippiJackson(601) 936-9360
MissouriKansas City(913) 491-3740St. Louis(314) 567-3900
NebraskaOmaha(402) 397-1940
NevadaLas Vegas(702) 734-1022
New HampshireManchester(603) 626-0702
New JerseyCranford(908) 276-7227
New MexicoAlbuquerque(505) 881-1611
New YorkAlbany(518) 365-4569Buffalo(716) 834-3815Long Island(516) 484-7560Syracuse(315) 453-2935
North CarolinaAsheville(704) 253-8299Charlotte(704) 536-1201Greensboro(910) 852-1758Raleigh(919) 782-3365Wilmington(910) 313-0034
North DakotaBismarck(701) 258-9555Fargo(701) 293-7709
OhioCincinnati(513) 398-9288Cleveland(216) 642-0701Columbus(614) 766-2204Dayton(513) 279-0458Toledo(419) 893-7197Wooster(216) 262-3268
OklahomaOklahoma City(405) 235-7515Tulsa(918) 665-1806
OregonPortland(503) 635-6700
PennsylvaniaPhiladelphia(215) 646-3800Pittsburgh(412) 788-8060York(717) 854-9776
Rhode IslandProvidence(401) 732-9966
South CarolinaColumbia(803) 359-7715Greenville(803) 288-3490
TennesseeChattanooga(423) 267-7412Johnson City(423) 434-9270Knoxville(615) 690-5172Memphis(901) 761-2123Nashville(615) 367-9403
TexasAustin(512) 416-0181Dallas(817) 652-9653Fort Worth(817) 838-9770Houston(713) 690-3000San Antonio(210) 525-7845
UtahSalt Lake City(801) 266-9612
VirginiaRichmond(804) 288-8311Roanoke(703) 982-2776Virginia Beach(804) 486-0174
WashingtonSeattle(206) 828-6600Spokane(509) 468-3717Tacoma(206) 926-7663
Washington, D.C.(301) 459-2044
West Virginia(304) 522-9732
WisconsinGreen Bay(414) 336-1144Milwaukee(414) 774-9500
CanadaMississauga,Ontario(905) 819-8000Pointe Claire,Quebec(514) 695-7300Vancouver,British Columbia(604) 435-0880
InternationalTel: (770) 751-2291Fax: (770) 751-2496TLX: 822024SEA
IBU UF
Siemens Energy & Automation Sales Offices
Siemens Energy & Automation, Inc.Distribution Products Division3333 Old Milton ParkwayAlpharetta, GA 30202
© 1996 Siemens Energy & Automation, Inc. Bulletin 4.5-2B (Supersedes 4.5-2A)Siemens Is a registered trademark of Siemens AG. 10M1096SP Printed in U.S.A.
1
Siemens distributors offer a broad range of distribution and control materials and displays that educate customers about features and benefits of Siemens products at the point of sale.
In addition to our worldwide presence, Siemens distributors offer a world-class varietyof products that meet almost all customers’ distribution, automation and control needs.
Or order by using our On Route–On Time, On Route–On Time Gold or Quickshipprograms through your Siemens distributor and experience our reliable 100% on time,100% complete programs for urgent shipments.
Technology that Serves Distributorthe Customer Products
Siemens distributors throughoutthe United States carry a full lineof standard products that cantake care of a majority of yourprojects.
Many of these distributors can also provide same dayavailability of:
• Lighting Panelboards
• Power Panelboards
• Switchboards
• Distribution Dry Type Transformers
• Busway
• Busway Plug-in Units
• Molded Case Circuit Breakers
• Enclosed Switches
• Control Products
2
At Siemens Energy & Automation, Inc., our commitment to total quality throughout our company is the hallmark of our business and our pledge to our customers and employees. In recognition of this, we are pleased to participate in
ISO Certification
Thomas J MalottPresident & Chief Executive Officer
Table of Contents
3
Sentron Lighting PanelboardsS1, S2 and SE
Pages 5-14
Sentron Column WidthPanelboards S1 and S2
Pages 15-18
Sentron Power PanelboardsS4, S5, F1 and F2
Pages 19-26
Sentron PanelboardsTechnical Information
Pages 27-32
Sentron TPSTransient Voltage Surge
SuppressionPage 29
Sentron PanelboardsRecommended Specifications
Pages 33-34
SiemensCustomer Support Information
Pages 35-36
Sentron Sentron Column Sentron Power Sentron FusibleLighting Type Lighting Circuit Breaker Switch Power Panelboards Panelboards Panelboards Panelboards
Key Panelboard Features S1 S2 SE S1 S2 S4 S5 F1 F2
Lighting and appliance applications ✔ ✔ ✔ ✔ ✔
Power panelboard applications ✔ ✔ ✔ ✔
Convertible from top feed to bottom feed or vice versa ✔ ✔ ✔
Change from main lug to main breaker or add ✔ ✔ ✔subfeed without changing enclosure sizeSpace-saving, horizontally mounted main breaker ✔ ✔ ✔ ✔ ✔
Short circuit rating label giving performance level ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Labels: Rating label with factory shop order and Danger label ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Standard aluminum ground bus ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Danger label to alert personnel to turn off ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔incoming power before servicingBlank end-walls standard ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Bolted current-carrying parts ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Split neutral ✔ ✔ ✔ ✔ ✔ ✔ ✔
Connection accessible from front ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Screw-type mechanical lugs ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Time-reducing wing nuts to secure interior without tools ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
200 ampere rated branch breaker connector ✔ ✔ ✔ ✔ ✔ 1 1 1 1
Fas-Latch fronts ✔ ✔ ✔
Optional pre-stamped knockouts ✔ ✔ ✔
Main and branch devices connected with ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔case-hardened hardwareFlush lock, concealed door hinges ✔ ✔ ✔and concealed trim screwsMultiple sub-feed breaker mounting capability 2 2 2
Symmetrical interior mounting studs ✔ ✔ ✔ ✔ ✔ ✔ ✔to eliminate upside down mounting of boxJacking screw interior adjustment ✔ ✔ ✔
Star nut interior adjustment ✔ ✔ ✔ ✔
Mix and match fusible switch ✔ ✔ ✔ ✔circuit breaker capabilityShallow depth ✔ ✔
Accepts a wide range of fuse types ✔ ✔
Accepts Vacu-Break® Fusible Switch ✔ ✔
Accepts a wide range of Sentron Circuit Breakers ✔ ✔ ✔ ✔ ✔ ✔ ✔
Accepts ACCESSTM communications tie-in ✔ ✔ ✔ ✔ ✔ ✔ ✔
Optional compression lugs ✔ ✔ ✔ ✔ ✔ ✔ ✔
The Sentron® Panelboard family has been enhanced andextended with the addition of the SE model. The full line is now filled with logical, convenient and practical featuresdesigned to fill almost every application need. You’ll find manyspecial features that make installation easier and faster toexpand the versatility of a particular product category. Fieldreconfiguration, for example, is a feature we’ve made an
important aspect of our new product line. Equally important, isthe ability of our product line to accept a wide range of circuitbreaker and fuse types. To match your application need to ourproduct, take a look at the chart below which clearlydemonstrates feature-to-product. What the chart cannot showhowever, is the built-in quality that is an integral part of theSiemens name.
Sentron® Panelboard Family
4
1 Larger than 200 ampere devices may be installed.2 At 400 and 600 ampere & 240V or less.
5
Sent
ron®
Ligh
ting
Pane
lboa
rds
100A
-600
A
Sentron Lighting Panelboards, the industry’s first modular designthat allows field interchangeability with bussed connected Mains.Change from main circuit breaker to main lugs or from top feed tobottom feed.
Sentron Lighting Panelboards were engineered to be quickly modified as your requirements dictate.
Your Siemens distributor can provide you with Sentron retrofitpanelboard kits “over the counter”.
7
Type SE100-600A600V max.100 KAIC Rating max.
A
B
C
D
E
F
G
H
I
J
K
L
Main Breaker
Branch Breakers
Provisions for adding Sub-feedBreaker or Feed-thru Lugs
NEMA 1 Enclosure
Neutral Lug
Grounding Lug
Adjusting Screws
Dead Front Cover
Fixed Data Label
Numbering Strips
Front
Branch Breaker Connector Strap
H
J
K
Max. Max.Interrupting Rating
BreakerAmps Poles 240V Max 480V 600V 250V DC Type
100 30 10 — — 5 ED242 10 — — 565 18 — 30 ED4
12530 65 25 18 30 ED642 100 42 — 30 HED4
100 65 25 — HHED6
250 30 65 35 22 30 FXD642 100 65 25 30 HFD6
400 42 65 35 25 30 JXD6100 65 35 30 HJD6
600 42 65 35 25 30 LXD6100 65 35 30 HLD6
Main Breaker Selection
Maximum
No. Interrupting
Breaker of Ampere Rating (kA)
Type Poles Rating 240V 480V 600V 250V DC
FXD6 2 / 3 70 – 250 65 35 22 30HFD6 2 / 3 70 – 250 100 65 25 30JXD6 2 / 3 200 – 400 65 35 25 30HJD6 2 / 3 200 – 400 100 65 35 30LXD6 2 / 3 450 – 600 65 35 25 30HLD6 2 / 3 250 – 600 100 65 35 30
Sub-feed Breakers – Limit One Per Panel 1 2
1 When applying in a 42 circuit panel, see lighting and appliance panelboard definition on page 32. Also reference NEC Article 384-16.
2 No increase in box height. Space is already built into SE panel.
No. Maximum Interrupting
of Ampere Rating (kA) BreakerPoles Rating 120V 240V 277V 480V 600V 250V DC Frame
1 10 — — — — —2 15–100 — 10 — — — 5 ED23 — 10 — — — —1 65 — 22 — — —2 15–125 — 65 — 18 — 30 ED43 — 65 — 18 — —2 15–125 — 65 — 25 18 30 ED63 — 65 — 25 18 —1 15–125 100 — 25 — — —2 15–125 — 100 — 42 — 30 HED43 15–125 — 100 — 42 — —2 15–125 — 100 — 65 25 — HHED63 15–125 — 100 — 65 25 —
Branch Breaker Selection
Sentron Lighting Panelboards–Main BreakerFactory AssembledType S1 Type S2100-600A 100-600A240V max. 480Y/277V 3Ø 4W65 KAIC Rating max. 600Y/347V 3Ø 4W
14 KAIC Rating max.
6
S1, S2 and SE Sentron Panelboards are pre-engineered to accept the most common modifications withoutincreasing box height. All S1, S2 and SE panelboardshave space built-in to accept either feed-thru lugs or aminimum of one sub-feed circuit breaker up to 600 amps.
S2 Panelboards are available as Smart Panelboards for use in automated lighting control systems. Inquirethrough your local Siemens sales representative.
A
B
C D
E
F
L
G
I
Max. Max. Interrupting Rating Breaker
Amps Poles 240V Max 480Y/277V 600Y/347V Type
10 — — BL
1822 — — BLH
100 3065 — — HBL
4210 — — ED265 14 — BQD— — 10 BQD6
1865 18 — ED4
125 3065 25 18 ED6
42100 42 — HED4100 65 25 HHED6
18 10 — — QJ2225 30 22 — — QJH2
42 42 — — QJ2-H18 65 35 22 FXD6
250 30 65 35 22 FD642 100 65 25 HFD6
400 42 65 35 25 JXD6100 65 35 HJD6
600 42 65 35 25 LXD6100 65 35 HLD6
Main Breaker Selection
Maximum
No. Interrupting
Breaker of Ampere Rating (kA)
Type Poles Rating 240V 480Y/277V 600Y/347V
ED2 2 / 3 15 – 100 10 — —ED4 2 / 3 15 – 125 65 18 —ED6 2 / 3 15 – 125 65 25 18HED4 2 / 3 15 – 125 100 42 —HHED6 2 / 3 15 – 125 100 65 25QJ2 2 / 3 60 – 225 10 — —QJH2 2 / 3 60 – 225 22 — —QJ2-H 2 / 3 60 – 225 42 — —FXD6 2 / 3 70 – 250 65 35 22HFD6 2 / 3 70 – 250 100 65 25JXD6 2 / 3 200 – 400 65 35 25HJD6 2 / 3 200 – 400 100 65 35LXD6 2 / 3 450 – 600 65 35 25HLD6 2 / 3 250 – 600 100 65 35
1 When applying in a 42 circuit panel, see lighting and appliance panelboarddefinition on page 32. Also reference NEC Article 384-16.
2 No increase in box height. Space is already built into S1/S2 panel.3 Panel can have 1 sub-feed breaker except 2 QJ Type at 400 and 600 ampere.
Sub-feed Breakers1 2 3
Ampere Maximum Interrupting Rating (kA) BreakerRating No. of Poles 240V 480Y/277V 600Y/347V Frame
15 – 70 1 10 — —15 – 100 2 10 — — BL15 – 100 3 10 — —15 – 70 1 22 — —15 – 100 2 22 — — BLH15 – 100 3 22 — —15 – 50 1 65 — —15 – 70 2 65 — — HBL15 – 100 3 65 —15 – 30 1 10 — —
BLF15 – 60 2 10 — —15 – 30 1 22 — —
BLHF15 – 60 2 22 — —15 – 30 2 10 — —
BGL15 – 30 3 10 — —15 – 30 1 10 — —
BLE15 – 60 2 10 — —15 – 100 1 65 14 —15 – 100 2 65 14 — BQD15 – 100 3 65 14 —15 – 100 1 — — 1015 – 100 2 — — 10 BQD615 – 100 3 — — 10
Branch Breaker Selection
7
Type SE100-600A600V max.100 KAIC Rating max.
A
B
C
D
E
F
G
H
I
J
K
L
Main Breaker
Branch Breakers
Provisions for adding Sub-feedBreaker or Feed-thru Lugs
NEMA 1 Enclosure
Neutral Lug
Grounding Lug
Adjusting Screws
Dead Front Cover
Fixed Data Label
Numbering Strips
Front
Branch Breaker Connector Strap
H
J
K
Max. Max.Interrupting Rating
BreakerAmps Poles 240V Max 480V 600V 250V DC Type
100 30 10 — — 5 ED242 10 — — 565 18 — 30 ED4
12530 65 25 18 30 ED642 100 42 — 30 HED4
100 65 25 — HHED6
250 30 65 35 22 30 FXD642 100 65 25 30 HFD6
400 42 65 35 25 30 JXD6100 65 35 30 HJD6
600 42 65 35 25 30 LXD6100 65 35 30 HLD6
Main Breaker Selection
Maximum
No. Interrupting
Breaker of Ampere Rating (kA)
Type Poles Rating 240V 480V 600V 250V DC
FXD6 2 / 3 70 – 250 65 35 22 30HFD6 2 / 3 70 – 250 100 65 25 30JXD6 2 / 3 200 – 400 65 35 25 30HJD6 2 / 3 200 – 400 100 65 35 30LXD6 2 / 3 450 – 600 65 35 25 30HLD6 2 / 3 250 – 600 100 65 35 30
Sub-feed Breakers – Limit One Per Panel 1 2
1 When applying in a 42 circuit panel, see lighting and appliance panelboard definition on page 32. Also reference NEC Article 384-16.
2 No increase in box height. Space is already built into SE panel.
No. Maximum Interrupting
of Ampere Rating (kA) BreakerPoles Rating 120V 240V 277V 480V 600V 250V DC Frame
1 10 — — — — —2 15–100 — 10 — — — 5 ED23 — 10 — — — —1 65 — 22 — — —2 15–125 — 65 — 18 — 30 ED43 — 65 — 18 — —2 15–125 — 65 — 25 18 30 ED63 — 65 — 25 18 —1 15–125 100 — 25 — — —2 15–125 — 100 — 42 — 30 HED43 15–125 — 100 — 42 — —2 15–125 — 100 — 65 25 — HHED63 15–125 — 100 — 65 25 —
Branch Breaker Selection
Sentron Lighting Panelboards–Main BreakerFactory AssembledType S1 Type S2100-600A 100-600A240V max. 480Y/277V 3Ø 4W65 KAIC Rating max. 600Y/347V 3Ø 4W
14 KAIC Rating max.
6
S1, S2 and SE Sentron Panelboards are pre-engineered to accept the most common modifications withoutincreasing box height. All S1, S2 and SE panelboardshave space built-in to accept either feed-thru lugs or aminimum of one sub-feed circuit breaker up to 600 amps.
S2 Panelboards are available as Smart Panelboards for use in automated lighting control systems. Inquirethrough your local Siemens sales representative.
A
B
C D
E
F
L
G
I
Max. Max. Interrupting Rating Breaker
Amps Poles 240V Max 480Y/277V 600Y/347V Type
10 — — BL
1822 — — BLH
100 3065 — — HBL
4210 — — ED265 14 — BQD— — 10 BQD6
1865 18 — ED4
125 3065 25 18 ED6
42100 42 — HED4100 65 25 HHED6
18 10 — — QJ2225 30 22 — — QJH2
42 42 — — QJ2-H18 65 35 22 FXD6
250 30 65 35 22 FD642 100 65 25 HFD6
400 42 65 35 25 JXD6100 65 35 HJD6
600 42 65 35 25 LXD6100 65 35 HLD6
Main Breaker Selection
Maximum
No. Interrupting
Breaker of Ampere Rating (kA)
Type Poles Rating 240V 480Y/277V 600Y/347V
ED2 2 / 3 15 – 100 10 — —ED4 2 / 3 15 – 125 65 18 —ED6 2 / 3 15 – 125 65 25 18HED4 2 / 3 15 – 125 100 42 —HHED6 2 / 3 15 – 125 100 65 25QJ2 2 / 3 60 – 225 10 — —QJH2 2 / 3 60 – 225 22 — —QJ2-H 2 / 3 60 – 225 42 — —FXD6 2 / 3 70 – 250 65 35 22HFD6 2 / 3 70 – 250 100 65 25JXD6 2 / 3 200 – 400 65 35 25HJD6 2 / 3 200 – 400 100 65 35LXD6 2 / 3 450 – 600 65 35 25HLD6 2 / 3 250 – 600 100 65 35
1 When applying in a 42 circuit panel, see lighting and appliance panelboarddefinition on page 32. Also reference NEC Article 384-16.
2 No increase in box height. Space is already built into S1/S2 panel.3 Panel can have 1 sub-feed breaker except 2 QJ Type at 400 and 600 ampere.
Sub-feed Breakers1 2 3
Ampere Maximum Interrupting Rating (kA) BreakerRating No. of Poles 240V 480Y/277V 600Y/347V Frame
15 – 70 1 10 — —15 – 100 2 10 — — BL15 – 100 3 10 — —15 – 70 1 22 — —15 – 100 2 22 — — BLH15 – 100 3 22 — —15 – 50 1 65 — —15 – 70 2 65 — — HBL15 – 100 3 65 —15 – 30 1 10 — —
BLF15 – 60 2 10 — —15 – 30 1 22 — —
BLHF15 – 60 2 22 — —15 – 30 2 10 — —
BGL15 – 30 3 10 — —15 – 30 1 10 — —
BLE15 – 60 2 10 — —15 – 100 1 65 14 —15 – 100 2 65 14 — BQD15 – 100 3 65 14 —15 – 100 1 — — 1015 – 100 2 — — 10 BQD615 – 100 3 — — 10
Branch Breaker Selection
Distributor Stock–Main BreakerSame Day Availability
8
Main Amp. Factory Main Device Front
Rating Assembled No. Interior MCB Surface Flush Box
1 Phase 3 Wire 120/240V
S1A18BL100A I1A18MC250A MBKBL1 S32B F32B B32S1A18BL100C I1A18MC250C MBKBL1 S32B F32B B32
100S1A30BL100A I1A30MC250A MBKBL1 S38B F38B B38S1A30BL100C I1A30MC250C MBKBL1 S38B F38B B38S1A42BL100A I1A42MC250A MBKBL1 S44B F44B B44S1A42BL100C I1A42MC250C MBKBL1 S44B F44B B44S1A18E4125A I1A18MC250A MBKED1 S32B F32B B32S1A18E4125C I1A18MC250C MBKED1 S32B F32B B32
125S1A30E4125A I1A30MC250A MBKED1 S38B F38B B38S1A30E4125C I1A30MC250C MBKED1 S38B F38B B38S1A42E4125A I1A42MC250A MBKED1 S44B F44B B44S1A42E4125C I1A42MC250C MBKED1 S44B F44B B44S1A18QJ225A I1A18MC250A MBKQJ1 S32B F32B B32S1A18QJ225C I1A18MC250C MBKQJ1 S32B F32B B32
225S1A30QJ225A I1A30MC250A MBKQJ1 S38B F38B B38S1A30QJ225C I1A30MC250C MBKQJ1 S38B F38B B38S1A42QJ225A I1A42MC250A MBKQJ1 S44B F44B B44S1A42QJ225C I1A42MC250C MBKQJ1 S44B F44B B44S1A18FX250A I1A18MC250A MBKFD1 S32B F32B B32S1A18FX250C I1A18MC250C MBKFD1 S32B F32B B32
250S1A30FX250A I1A30MC250A MBKFD1 S38B F38B B38S1A30FX250C I1A30MC250C MBKFD1 S38B F38B B38S1A42FX250A I1A42MC250A MBKFD1 S44B F44B B44S1A42FX250C I1A42MC250C MBKFD1 S44B F44B B44
400S1A42JD400A I1A42MC400A SMBKJD1 24S68B 24F68B SBD68S1A42JD400A I1A42MC400C SMBKJD1 24S68B 24F68B SBD68
600S1A42LD600A I1A42MC600A SMBKLD1 24S68B 24F68B SBD68S1A42LD600A I1A42MC600C SMBKLD1 24S68B 24F68B SBD68
3 Phase 4 Wire 208Y/120V
S1C18BL100A I1X18MC250A MBKBL3 S32B F32B B32S1C18BL100C I1X18MC250C MBKBL3 S32B F32B B32
100S1C30BL100A I1X30MC250A MBKBL3 S38B F38B B38S1C30BL100C I1X30MC250C MBKBL3 S38B F38B B38S1C42BL100A I1X42MC250A MBKBL3 S44B F44B B44S1C42BL100C I1X42MC250C MBKBL3 S44B F44B B44S1C18E4125A I1X18MC250A MBKED3 S32B F32B B32S1C18E4125A I1X18MC250C MBKED3 S32B F32B B32
125S1C30E4125A I1X30MC250A MBKED3 S38B F38B B38S1C30E4125A I1X30MC250C MBKED3 S38B F38B B38S1C42E4125A I1X42MC250A MBKED3 S44B F44B B44S1C42E4125A I1X42MC250C MBKED3 S44B F44B B44S1C18QJ225A I1X18MC250A MBKQJ3 S32B F32B B32S1C18QJ225C I1X18MC250C MBKQJ3 S32B F32B B32
225S1C30QJ225A I1X30MC250A MBKQJ3 S38B F38B B38S1C30QJ225C I1X30MC250C MBKQJ3 S38B F38B B38S1C42QJ225A I1X42MC250A MBKQJ3 S44B F44B B44S1C42QJ225C I1X42MC250C MBKQJ3 S44B F44B B44S1C18FX250A I1X18MC250A MBKFD3 S32B F32B B32S1C18FX250C I1X18MC250C MBKFD3 S32B F32B B32
250S1C30FX250A I1X30MC250A MBKFD3 S38B F38B B38S1C30FX250C I1X30MC250C MBKFD3 S38B F38B B38S1C42FX250A I1X42MC250A MBKFD3 S44B F44B B44S1C42FX250C I1X42MC250C MBKFD3 S44B F44B B44
400S1C42JD400A I1X42MC400A SMBKJD3 24S68B 24F68B SBD68S1C42JD400C I1X42MC400C SMBKJD3 24S68B 24F68B SBD68
600S1C42LD600A I1X42MC600A SMBKLD3 24S68B 24F68B SBD68S1C42LD600C I1X42MC600C SMBKLD3 24S68B 24F68B SBD68
S1 Type
Chart has been established to convertS.P.A.C.E. generated catalog number todistributor stock components required to supply factory assembled products.
Example:If you need Factory Assembled CatalogNumber1 S1C18BL100ATS your distributor stocks the following kits that make up this Factory AssembledCatalog Number.
Interior – I1X18MC250A
Main Device – MBKBL3
Front – S32B
Box – B321 Breakers are not included.
A
A
B
C
D
InteriorS1C18BL100A T S
Surface/Flush InstallationTop/Bottom Entry
9
Main Amp. Factory Main Device Front
Rating Assembled No. Interior MCB Surface Flush Box
3 Phase 4 Wire 480Y/277V
S2E18BD100A I2E18MC250A MBKBC3 S32B F32B B32S2E18BD100C I2E18MC250C MBKBC3 S32B F32B B32
100S2E30BD100A I2E30MC250A MBKBC3 S38B F38B B38S2E30BD100C I2E30MC250C MBKBC3 S38B F38B B38S2E42BD100A I2E42MC250A MBKBC3 S44B F44B B44S2E42BD100C I2E42MC250C MBKBC3 S44B F44B B44S2E18E4125A I2E18MC250A MBKED3 S32B F32B B32S2E18E4125C I2E18MC250C MBKED3 S32B F32B B32
125S2E30E4125A I2E30MC250A MBKED3 S38B F38B B38S2E30E4125C I2E30MC250C MBKED3 S38B F38B B38S2E42E4125A I2E42MC250A MBKED3 S44B F44B B44S2E42E4125C I2E42MC250C MBKED3 S44B F44B B44S2E18FD250A I2E18MC250A MBKFD3 S32B F32B B32S2E18FD250C I2E18MC250C MBKFD3 S32B F32B B32
250S2E30FD250A I2E30MC250A MBKFD3 S38B F38B B38S2E30FD250C I2E30MC250C MBKFD3 S38B F38B B38S2E42FD250A I2E42MC250A MBKFD3 S44B F44B B44S2E42FD250C I2E42MC250C MBKFD3 S44B F44B B44
400S2E42JD400A I2E42MC400A SMBKJD3 24S68B 24F68B SBD68S2E42JD400C I2E42MC400C SMBKJD3 24S68B 24F68B SBD68
600S2E42LD600A I2E42MC600A SMBKLD3 24S68B 24F68B SBD68S2E42LD600C I2E42MC600C SMBKLD3 24S68B 24F68B SBD68
S2 Type
Main Amp. Factory Main Device Front
Rating Assembled No. Interior MCB Surface Flush Box
1 Phase 3 Wire 120/240V
SEA30E4125A IEA30MC250A SMBKED1 24S44B 24F44B SBD44
125SEA30E4125C IEA30MC250C SMBKED1 24S44B 24F44B SBD44SEA42E4125A IEA42MC250A SMBKED1 24S50B 24F50B SBD50SEA42E4125C IEA42MC250C SMBKED1 24S50B 24F50B SBD50SEA30FX250A IEA30MC250A SMBKFD1 24S44B 24F44B SBD44
250SEA30FX250C IEA30MC250C SMBKFD1 24S44B 24F44B SBD44SEA42FX250A IEA42MC250A SMBKFD1 24S50B 24F50B SBD50SEA42FX250C IEA42MC250C SMBKFD1 24S50B 24F50B SBD50
400SEA42JD400A IEA42MC400A SMBKJD1 24S68B 24F68B SBD68SEA42JD400C IEA42MC400C SMBKJD1 24S68B 24F68B SBD68
600SEA42LD600A IEA42MC600A SMBKLD1 24S68B 24F68B SBD68SEA42LD600C IEA42MC600C SMBKLD1 24S68B 24F68B SBD68
3 Phase 4 Wire 208Y/120V
SEC30E4125A IEX30MC250A SMBKED3 24S44B 24F44B SBD44
125SEC30E4125C IEX30MC250C SMBKED3 24S44B 24F44B SBD44SEC42E4125A IEX42MC250A SMBKED3 24S50B 24F50B SBD50SEC42E4125C IEX42MC250C SMBKED3 24S50B 24F50B SBD50SEC30FX250A IEX30MC250A SMBKFD3 24S44B 24F44B SBD44
250SEC30FX250C IEX30MC250C SMBKFD3 24S44B 24F44B SBD44SEC42FX250A IEX42MC250A SMBKFD3 24S50B 24F50B SBD50SEC42FX250C IEX42MC250C SMBKFD3 24S50B 24F50B SBD50
400SEC42JD400A IEX42MC400A SMBKJD3 24S68B 24F68B SBD68SEC42JD400C IEX42MC400C SMBKJD3 24S68B 24F68B SBD68
600SEC42LD600A IEX42MC600A SMBKLD3 24S68B 24F68B SBD68SEC42LD600C IEX42MC600C SMBKLD3 24S68B 24F68B SBD68
3 Phase 4 Wire 480Y/277V
SEE30E4125A IEE30MC250A SMBKED3 24S44B 24F44B SBD44
125SEE30E4125C IEE30MC250C SMBKED3 24S44B 24F44B SBD44SEE42E4125A IEE42MC250A SMBKED3 24S50B 24F50B SBD50SEE42E4125C IEE42MC250C SMBKED3 24S50B 24F50B SBD50SEE30FX250A IEE30MC250A SMBKFD3 24S44B 24F44B SBD44
250SEE30FX250C IEE30MC250C SMBKFD3 24S44B 24F44B SBD44SEE42FX250A IEE42MC250A SMBKFD3 24S50B 24F50B SBD50SEE42FX250C IEE42MC250C SMBKFD3 24S50B 24F50B SBD50
400SEE42JD400A IEE42MC400A SMBKJD3 24S68B 24F68B SBD68SEE42JD400C IEE42MC400C SMBKJD3 24S68B 24F68B SBD68
600SEE42LD600A IEE42MC600A SMBKLD3 24S68B 24F68B SBD68SEE42LD600C IEE42MC600C SMBKLD3 24S68B 24F68B SBD68
SE Type
B
C
D
11
Type SE100-600A600V max.100 KAIC Rating max.
A
B
C
D
E
F
G
H
I
J
K
L
Main Lug
Branch Breakers
Provisions for Adding Sub-feedBreakers or Feed-thru Lugs
NEMA 1 Enclosure
Neutral Lug
Grounding Lug
Adjusting Screws
Dead Front Cover
Fixed Data Label
Numbering Strips
Front
Branch Breaker Connector Strap
Maximum
No. Interrupting
Breaker of Ampere Rating (kA)
Type Poles Rating 240V 480V 600V 250V DC
FXD6 2 / 3 70 – 250 65 35 22 30HFD6 2 / 3 70 – 250 100 65 25 30JXD6 2 / 3 200 – 400 65 35 25 30HJD6 2 / 3 200 – 400 100 65 35 30LXD6 2 / 3 450 – 600 65 35 25 30HLD6 2 / 3 250 – 600 100 65 35 30
Sub-feed Breakers – Limit One Per Panel 1 2
1 When applying in a 42 circuit panel, see lighting and appliance panelboard definition on page 32. Also reference NEC Article 384-16.
2 No increase in box height. Space is already built into SE panel.
No. Maximum Interrupting
of Ampere Rating (kA) BreakerPoles Rating 120V 240V 277V 480V 600V 250V DC Frame
1 10 — — — — —2 15–100 — 10 — — — 5 ED23 — 10 — — — —1 65 — 22 — — —2 15–125 — 65 — 18 — 30 ED43 — 65 — 18 — —2 15–125 — 65 — 25 18 30 ED63 — 65 — 25 18 —1 15–125 100 — 25 — — —2 15–125 — 100 — 42 — 30 HED43 15–125 — 100 — 42 — —2 15–125 — 100 — 65 25 — HHED63 15–125 — 100 — 65 25 —
Branch Breaker Selection
Max. Max. Connectors Suitable
Amps No. of Poles for Cu or Al
12530
(1) #6 AWG-350 kcmil42
25030
(1) #6 AWG-350 kcmil42
400 42 (2) #3/0 AWG-500 kcmil600 42 (2) #3/0 AWG-500 kcmil
Main Lug only
Sentron Lighting Panelboards–Main LugFactory AssembledType S1 Type S2100-600A 100-600A240V max. 480Y/277V 3Ø 4W65 KAIC Rating max. 600Y/347V 3Ø 4W
14 KAIC Rating max.
10
A
B
C
D
E
L
F
G
I
Max. Connectors
Max. No. of Suitable for
Amps Poles Cu or Al
18125 30 (1) #6 AWG-350 kcmil
4218
250 30 (1) #6 AWG-350 kcmil42
400 42 (2) #3/0 AWG-500 kcmil600 42 (2) #3/0 AWG-500 kcmil
Main Lug only
S1, S2 and SE Sentron Panelboards are pre-engineered to accept the most common modifications withoutincreasing box height. All S1, S2 and SE panelboardshave space built-in to accept either feed-thru lugs or aminimum of one sub-feed circuit breaker up to 600 amps.
S2 Panelboards are available as Smart Panelboards for use in automated lighting control systems. Inquirethrough your local Siemens sales representative.
Maximum
No. Interrupting
Breaker of Ampere Rating (kA)
Type Poles Rating 240V 480Y/277V 600Y/347V
ED2 2 / 3 15 – 100 10 — —ED4 2 / 3 15 – 125 65 18 —ED6 2 / 3 15 – 125 65 25 18HED4 2 / 3 15 – 125 100 42 —HHED6 2 / 3 15 – 125 100 65 25QJ2 2 / 3 60 – 225 10 — —QJH2 2 / 3 60 – 225 22 — —QJ2-H 2 / 3 60 – 225 42 — —FXD6 2 / 3 70 – 250 65 35 22HFD6 2 / 3 70 – 250 100 65 25JXD6 2 / 3 200 – 400 65 35 25HJD6 2 / 3 200 – 400 100 65 35LXD6 2 / 3 450 – 600 65 35 25HLD6 2 / 3 250 – 600 100 65 35
1 When applying in a 42 circuit panel, see lighting and appliance panelboarddefinition on page 32. Also reference NEC Article 384-16.
2 No increase in box height. Space is already built into S1, S2 panel.3 Panel can have 1 sub-feed breaker except 2 QJ Type at 400 and 600 ampere.
Sub-feed Breakers1 2 3
J K
H
Ampere Maximum Interrupting Rating (kA) BreakerRating No. of Poles 240V 480Y/277V 600Y/347V Frame
15 – 70 1 10 — —15 – 100 2 10 — — BL15 – 100 3 10 — —15 – 70 1 22 — —15 – 100 2 22 — — BLH15 – 100 3 22 — —15 – 50 1 65 — —15 – 70 2 65 — — HBL15 – 100 3 65 —15 – 30 1 10 — —
BLF15 – 60 2 10 — —15 – 30 1 22 — —
BLHF15 – 60 2 22 — —15 – 30 2 10 — —
BGL15 – 30 3 10 — —15 – 30 1 10 — —
BLE15 – 60 2 10 — —15 – 100 1 65 14 —15 – 100 2 65 14 — BQD15 – 100 3 65 14 —15 – 100 1 — — 1015 – 100 2 — — 10 BQD615 – 100 3 — — 10
Branch Breaker Selection
11
Type SE100-600A600V max.100 KAIC Rating max.
A
B
C
D
E
F
G
H
I
J
K
L
Main Lug
Branch Breakers
Provisions for Adding Sub-feedBreakers or Feed-thru Lugs
NEMA 1 Enclosure
Neutral Lug
Grounding Lug
Adjusting Screws
Dead Front Cover
Fixed Data Label
Numbering Strips
Front
Branch Breaker Connector Strap
Maximum
No. Interrupting
Breaker of Ampere Rating (kA)
Type Poles Rating 240V 480V 600V 250V DC
FXD6 2 / 3 70 – 250 65 35 22 30HFD6 2 / 3 70 – 250 100 65 25 30JXD6 2 / 3 200 – 400 65 35 25 30HJD6 2 / 3 200 – 400 100 65 35 30LXD6 2 / 3 450 – 600 65 35 25 30HLD6 2 / 3 250 – 600 100 65 35 30
Sub-feed Breakers – Limit One Per Panel 1 2
1 When applying in a 42 circuit panel, see lighting and appliance panelboard definition on page 32. Also reference NEC Article 384-16.
2 No increase in box height. Space is already built into SE panel.
No. Maximum Interrupting
of Ampere Rating (kA) BreakerPoles Rating 120V 240V 277V 480V 600V 250V DC Frame
1 10 — — — — —2 15–100 — 10 — — — 5 ED23 — 10 — — — —1 65 — 22 — — —2 15–125 — 65 — 18 — 30 ED43 — 65 — 18 — —2 15–125 — 65 — 25 18 30 ED63 — 65 — 25 18 —1 15–125 100 — 25 — — —2 15–125 — 100 — 42 — 30 HED43 15–125 — 100 — 42 — —2 15–125 — 100 — 65 25 — HHED63 15–125 — 100 — 65 25 —
Branch Breaker Selection
Max. Max. Connectors Suitable
Amps No. of Poles for Cu or Al
12530
(1) #6 AWG-350 kcmil42
25030
(1) #6 AWG-350 kcmil42
400 42 (2) #3/0 AWG-500 kcmil600 42 (2) #3/0 AWG-500 kcmil
Main Lug only
Sentron Lighting Panelboards–Main LugFactory AssembledType S1 Type S2100-600A 100-600A240V max. 480Y/277V 3Ø 4W65 KAIC Rating max. 600Y/347V 3Ø 4W
14 KAIC Rating max.
10
A
B
C
D
E
L
F
G
I
Max. Connectors
Max. No. of Suitable for
Amps Poles Cu or Al
18125 30 (1) #6 AWG-350 kcmil
4218
250 30 (1) #6 AWG-350 kcmil42
400 42 (2) #3/0 AWG-500 kcmil600 42 (2) #3/0 AWG-500 kcmil
Main Lug only
S1, S2 and SE Sentron Panelboards are pre-engineered to accept the most common modifications withoutincreasing box height. All S1, S2 and SE panelboardshave space built-in to accept either feed-thru lugs or aminimum of one sub-feed circuit breaker up to 600 amps.
S2 Panelboards are available as Smart Panelboards for use in automated lighting control systems. Inquirethrough your local Siemens sales representative.
Maximum
No. Interrupting
Breaker of Ampere Rating (kA)
Type Poles Rating 240V 480Y/277V 600Y/347V
ED2 2 / 3 15 – 100 10 — —ED4 2 / 3 15 – 125 65 18 —ED6 2 / 3 15 – 125 65 25 18HED4 2 / 3 15 – 125 100 42 —HHED6 2 / 3 15 – 125 100 65 25QJ2 2 / 3 60 – 225 10 — —QJH2 2 / 3 60 – 225 22 — —QJ2-H 2 / 3 60 – 225 42 — —FXD6 2 / 3 70 – 250 65 35 22HFD6 2 / 3 70 – 250 100 65 25JXD6 2 / 3 200 – 400 65 35 25HJD6 2 / 3 200 – 400 100 65 35LXD6 2 / 3 450 – 600 65 35 25HLD6 2 / 3 250 – 600 100 65 35
1 When applying in a 42 circuit panel, see lighting and appliance panelboarddefinition on page 32. Also reference NEC Article 384-16.
2 No increase in box height. Space is already built into S1, S2 panel.3 Panel can have 1 sub-feed breaker except 2 QJ Type at 400 and 600 ampere.
Sub-feed Breakers1 2 3
J K
H
Ampere Maximum Interrupting Rating (kA) BreakerRating No. of Poles 240V 480Y/277V 600Y/347V Frame
15 – 70 1 10 — —15 – 100 2 10 — — BL15 – 100 3 10 — —15 – 70 1 22 — —15 – 100 2 22 — — BLH15 – 100 3 22 — —15 – 50 1 65 — —15 – 70 2 65 — — HBL15 – 100 3 65 —15 – 30 1 10 — —
BLF15 – 60 2 10 — —15 – 30 1 22 — —
BLHF15 – 60 2 22 — —15 – 30 2 10 — —
BGL15 – 30 3 10 — —15 – 30 1 10 — —
BLE15 – 60 2 10 — —15 – 100 1 65 14 —15 – 100 2 65 14 — BQD15 – 100 3 65 14 —15 – 100 1 — — 1015 – 100 2 — — 10 BQD615 – 100 3 — — 10
Branch Breaker Selection
Distributor Stock–Main LugSame Day Availability
12
Main Amp. Factory Main Device Front
Rating Assembled No. Interior MLO Surface Flush Box
1 Phase 3 Wire 120/240
S1A18ML250A I1A18MC250A MLKA1 S32B F32B B32S1A18ML250C I1A18MC250C MLKC1 S32B F32B B32
250S1A30ML250A I1A30MC250A MLKA1 S38B F38B B38S1A30ML250C I1A30MC250C MLKC1 S38B F38B B38S1A42ML250A I1A42MC250A MLKA1 S44B F44B B44S1A42ML250C I1A42MC250C MLKC1 S44B F44B B44
400S1A42ML400A I1A42MC400A SMLKA1 24S68B 24F68B SBD68S1A42ML400C I1A42MC400C SMLKA1 24S68B 24F68B SBD68
600S1A42ML600A I1A42MC600A SMLKA1 24S68B 24F68B SBD68S1A42ML600C I1A42MC600C SMLKA1 24S68B 24F68B SBD68
3 Phase 4 Wire 208Y/120V
S1C18ML250A I1X18MC250A MLKA3 S32B F32B B32S1C18ML250C I1X18MC250C MLKC3 S32B F32B B32
250S1C30ML250A I1X30MC250A MLKA3 S38B F38B B38S1C30ML250C I1X30MC250C MLKC3 S38B F38B B38S1C42ML250A I1X42MC250A MLKA3 S44B F44B B44S1C42ML250C I1X42MC250C MLKC3 S44B F44B B44
400S1C42ML400A I1X42MC400A SMLKA3 24S68B 24F68B SBD68S1C42ML400C I1X42MC400C SMLKA3 24S68B 24F68B SBD68
600S1C42ML600A I1X42MC600A SMLKA3 24S68B 24F68B SBD68S1C42ML600C I1X42MC600C SMLKA3 24S68B 24F68B SBD68
S1 Type
Main Amp. Factory Main Device Front
Rating Assembled No. Interior MLO Surface Flush Box
1 Phase 3 Wire 120/240V
SEA30ML250A IEA30MC250A EMLKA1 24S44B 24F44B SBD44
250SEA30ML250C IEA30MC250C EMLKA1 24S44B 24F44B SBD44SEA42ML250A IEA42MC250A EMLKA1 24S50B 24F50B SBD50SEA42ML250C IEA42MC250C EMLKA1 24S50B 24F50B SBD50
400SEA42ML400A IEA42MC400A SMLKA1 24S6BB 24F68B SBD68SEA42ML400C IEA42MC400C SMLKA1 24S68B 24F68B SBD68
600SEA42ML600A IEA42MC600A SMLKA1 24S68B 24F68B SBD68SEA42ML600C IEA42MC600C SMLKA1 24S68B 24F68B SBD68
3 Phase 4 Wire 208Y/120V
SEC30ML250A IEX30MC250A EMLKA3 24S44B 24F44B SBD44
250SEC30ML250C IEX30MC250C EMLKA3 24S44B 24F44B SBD44SEC42ML250A IEX42MC250A EMLKA3 24S50B 24F50B SBD50SEC42ML250C IEX42MC250C EMLKA3 24S50B 24F50B SBD50
400SEC42ML400A IEX42MC400A SMLKA3 24S68B 24F68B SBD68SEC42ML400C IEX42MC400C SMLKA3 24S68B 24F68B SBD68
600SEC42ML600A IEX42MC600A SMLKA3 24S68B 24F68B SBD68SEC42ML600C IEX42MC600C SMLKA3 24S68B 24F68B SBD68
3 Phase 4 Wire 480Y/277V
SEE30ML250A IEE30MC250A EMLKA3 24S44B 24F44B SBD44
250SEE30ML250C IEE30MC250C EMLKA3 24S44B 24F44B SBD44SEE42ML250A IEE42MC250A EMLKA3 24S50B 24F50B SBD50SEE42ML250C IEE42MC250C EMLKA3 24S50B 24F50B SBD50
400SEE42ML400A IEE42MC400A SMLKA3 24S68B 24F68B SBD68SEE42ML400C IEE42MC400C SMLKA3 24S68B 24F68B SBD68
600SEE42ML600A IEE42MC600A SMLKA3 24S68B 24F68B SBD68SEE42ML600C IEE42MC600C SMLKA3 24S68B 24F68B SBD68
SE Type
Chart has been established to convertS.P.A.C.E. generated catalog number todistributor stock components required to supply factory assembled products.
Example:If you need Factory Assembled CatalogNumber 1 S1C18ML250ATS your distributor stocks the following kits thatmake up this Factory Assembled CatalogNumber.
Interior – I1X18MC250A
Main Device – MLKA3
Front – S32B
Box – B321 Breakers are not included.
Main Amp. Factory Main Device Front
Rating Assembled No. Interior MLO Surface Flush Box
3 Phase 4 Wire 480Y/277V
S2E18ML250A I2E18MC250A MLKA3 S32B F32B B32S2E18ML250C I2E18MC250C MLKC3 S32B F32B B32
250S2E30ML250A I2E30MC250A MLKA3 S38B F38B B38S2E30ML250C I2E30MC250C MLKC3 S38B F38B B38S2E42ML250A I2E42MC250A MLKA3 S44B F44B B44S2E42ML250C I2E42MC250C MLKC3 S44B F44B B44
400S2E42ML400A I2E42MC400A SMLKA3 24S68B 24F68B SBD68S2E42ML400C I2E42MC400C SMLKA3 24S68B 24F68B SBD68
600S2E42ML600A I2E42MC600A SMLKA3 24S68B 24F68B SBD68S2E42ML600C I2E42MC600C SMLKA3 24S68B 24F68B SBD68
S2 Type
A
A
InteriorS1C18ML250A T S
Surface/Flush InstallationTop/Bottom Entry
Type 3R/12Gasketed TrimPainted BoxHinged FrontDoor in Door FrontMetal Card HolderSpecial LocksNameplateAluminum Equipment Ground BarCopper Equipment Ground BarInsulated Equipment GroundSub-feed LugsFeed-thru LugsCompression LugsCopper Lugs200% NeutralCopper Main BusRemote Control SwitchTime ClockCircuit Breaker Shunt TripHandle Blocking DevicePadlocking DeviceTVSS Module
13
Sentron Lighting PanelboardsStandard ModificationsType S1, S2 and SE
A
B
C
D
E
F
G
H
I
A
B
C
D
E
F
G
H
I
When required, special constructions or additions to standard panelboards may be specified for factory-assembled panelboards.
Breaker Ampere Line Connectors
Type Rating Aluminum Wire Copper Wire
Line Side
15 – 40 (1) #12–#6 AWG (1) #14–#6 AWG50 – 100 (1) #6–#1/0 AWG (1) #8–#1 AWG
BL, BLH, HBL Load Side
BQD 15 – 20 (1) #12–#8 AWG (1) #14–#8 AWG25 – 35 (1) #8–#4 AWG (1) #8–#6 AWG40 – 50 (1) #8–#4 AWG (1) #8–#6 AWG55 – 70 (1) #8–#2 AWG (1) #8–#4 AWG80 – 100 (1) #2–#1/0 AWG (1) #4–#1/0 AWG
QJ2, QJH2, QJ2H 60 – 225 (1) #4 AWG-300 kcmil (1) #6 AWG-300 kcmil 15 – 20 (1) #12–#10 AWG (1) #14–#10 AWG
ED2, ED4, ED6, HED4, HHED625 (1) #10 AWG (1) #10 AWG30 – 100 (1) #10–#1/0 (1) #10–#1/0
110 – 125 (1) #2/0–1 (1) #3/0–3FXD6, FD6, HFD6 70 – 250 (1) #4 AWG-350 kcmil (1) #6 AWG-350 kcmil JXD2, JXD6, JD6, HJD6 200 – 400 (2) 4/0–500 kcmil (2) 3/0–500 kcmilLXD6, LD6 250 – 600 (2) 4/0–500 kcmil (2) 3/0–500 kcmil
Sentron Lighting PanelboardsDimensions and WeightsType S1, S2 and SE
ED, ED4, ED6, HED4, HHED6
QJ2, QJH2, QJ2-H1
FXD6, FD6, HFD6
JXD6, HJD6
LXD6, HLD6
BL, BLH, HBL
BLF, BLHF
BQD
BL, BLH, HBL
BLF, BLHF
BQD
Reference Letter Panel Width 20” Panel Width 24”
A 6.375 7.750B 5.500 7.125C 6.125 6.000D1 6.500 8.500E 5.250 7.250F — 8.000G — 8.000
Side Gutter Wiring Space (Inches)
Branch Breaker Side Gutters
Max. Unit Box
Max. No. of Space Height Approx.
Amps Circuits (Inches) (Inches) Weight
125 30 15 44 125 lbs.42 21 50 140 lbs.
250 30 15 44 130 lbs.42 21 50 145 lbs.
400 42 21 68 165 lbs.600 42 21 68 175 lbs.
Panelboard Dimensions Approximate Weight SE
Max. Unit Box
Max. No. of Space Height Approx.
Amps Circuits (Inches) (Inches) Weight
100 18 9 32 105 lbs.30 15 38 120 lbs.42 21 44 135 lbs
125 18 9 32 110 lbs.30 15 38 125 lbs.42 21 44 140 lbs.
225 18 9 32 110 lbs.30 15 38 125 lbs.42 21 44 140 lbs.
250 18 9 32 115 lbs.30 15 38 130 lbs.42 21 44 145 lbs.
400 42 21 68 165 lbs.600 42 21 68 175 lbs.
Panelboard Dimensions Approximate Weight S1/S2
1Panel limited to (1) Sub-feed at 250 amperes and (2) Sub-feeds at 400 & 600 amperes.
A
C
D
E
F
G
C
D
E
F
G
A
Side Gutter Neutral Location
Main Breaker 20” w/box 24” w/box 20” w/box 24” w/box
BL, BLH, HBL, BQD 8.500 — 11.500 —ED2, ED4, ED6, HED4 6.125 8.125 11.500 21.00QJ2, QJH2, QJ2-H 6.500 — 11.500 —FD6, FXD6, HFD6 5.250 7.250 11.500 21.00JXD2, JXD6, HSD6 — 8.000 — 26.380LXD6, HLD6 — 8.000 — 26.380
Main Breaker Gutter Dimensions (Inches)
End Gutter Neutral Location
Amp. Rating 20” w/box 24” w/box 20” w/box 24” w/box
125 10.500 11.250 11.500 21.000250 10.500 11.250 11.500 21.000400 — 17.380 — 26.380600 — 17.380 — 26.380
Main Lug End Gutter Dimensions (Inches)
B B
14
Pressure Wire Connectors
Sent
ron®
Colu
mn
Wid
th P
anel
boar
ds
100A
-250
A
Sentron Column Width Lighting Panelboards, theIndustry’s premier lighting grade panelboard to fit insidea standard steel column. Ideal for industrial applications,warehouses, office buildings, convention centers andeducational facilities.
Sentron Column Width Lighting Panelboards, designedto accommodate installation in restricted areas and is available as a smart panelboard for automated lightingcontrol applications.
Sentron Column Width Panelboards are available as SmartPanelboards for use in automated lighting control systems.Inquire through your local Siemens sales representative.
15
17
Modifications
A
B
C
D
E
F
G
H
I
J
K
Main Breaker
Branch Breakers
Provisions for adding Sub-feedBreaker or Feed-thru Lugs
NEMA 1 Enclosure
Neutral Lug
Grounding Lug
Dead Front Cover
Fixed Data Label
Numbering Strips
Front
Branch Breaker Connector Strap
When required, special constructions or additions to standard panelboards may be specified for factory-assembled column panelboards.
Box ModificationsDescriptionGasketedMetal Card HolderNameplateCopper Ground BarInsulated Aluminum Ground LugInsulated Copper Ground Lug
Interior ModificationsDescriptionFeed-thru Lugs1
Handle Padlocking DevicesShunt TripCopper Neutral LugsCopper Main Lugs
Box Sizing ChartCertain modifications such as sub-feed breakers and feed-thrulugs require additional unit space. Use this chart to determineproper enclosure size.
BoxHeight
Panel Configuration (Inches)
All MLO 18 Circuit 48All MLO 30 Circuit 73All MLO 42 Circuit 85All MLO 18 Circuit with feed-thru lugs 73All MLO 30 Circuit with feed-thru lugs 85All MLO 42 Circuit with feed-thru lugs 85All MLO 18 Circuit with sub-feed breaker 73All MLO 30 Circuit with sub-feed breaker 85All Main Breaker 18 Circuit 48All Main Breaker 30 Circuit 73All Main Breaker 42 Circuit 85All Main Breaker 18 Circuit with feed-thru lugs 73All Main Breaker 30 Circuit with feed-thru lugs 85All Main Breaker 42 Circuit with feed-thru lugs 85All Main Breaker 18 Circuit with sub-feed breaker 73All Main Breaker 30 Circuit with sub-feed breaker 85
Max. Connectors
Max. No. of Suitable for
Amps Poles Cu or Al
18125 30 (1) #6 AWG-350 kcmil
4218
250 30 (1) #6 AWG-350 kcmil42
Main Lug Only
1 For increase in box height see sizing chart above.
J16
Sentron Column Width PanelboardType S1 Type S2250A 250A240V max. 480Y/277V 3Ø 4W65 KAIC Rating max. 600Y/347V 3Ø 4W
14 KAIC Rating
A
B
C
K
D
EF
G
H
I
Max. Max. Interrupting Rating Breaker
Amps Poles 240V Max 480Y/277V 600Y/347V Type
10 — — BL
1822 — — BLH
100 3065 — — HBL
4210 — — ED265 14 — BQD— — 10 BQD6
1865 18 — ED4
125 3065 25 18 ED6
42100 42 — HED4100 65 25 HHED6
18 10 — — QJ2225 30 22 — — QJH2
42 42 — — QJ2-H18 65 35 22 FXD6
250 30 65 35 22 FD642 100 65 25 HFD6
Main Breaker Selection
Breaker Ampere Maximum Interrupting Rating (kA)
Type No. of Poles Rating 240V 480Y/277V 600Y/347V
ED2 2 / 3 15 – 100 10 — —ED4 2 / 3 15 – 125 65 18 —ED6 2 / 3 15 – 125 65 25 18HED4 2 / 3 15 – 125 100 42 —HHED6 2 / 3 15 – 125 100 65 25QJ2 2 / 3 60 – 225 10 — —QJH2 2 / 3 60 – 225 22 — —QJ2-H 2 / 3 60 – 225 42 — —FXD6 2 / 3 70 – 250 65 35 22HFD6 2 / 3 70 – 250 100 65 25JXD6 2 / 3 200 – 400 65 35 25HJD6 2 / 3 200 – 400 100 65 35LXD6 2 / 3 450 – 600 65 35 25HLD6 2 / 3 250 – 600 100 65 35
1 When applying in a 42 circuit panel, see lighting and appliance panelboarddefinition on page 32. Also reference NEC Article 384-16.
2 No increase in box height. Space is already built into S1, S2 panel.
Sub-feed Breakers1 2
Ampere Maximum Interrupting Rating (kA) BreakerRating No. of Poles 240V 480Y/277V 600Y/347V Frame
15 – 70 1 10 — —15 – 100 2 10 — — BL15 – 100 3 10 — —15 – 70 1 22 — —15 – 100 2 22 — — BLH15 – 100 3 22 — —15 – 50 1 65 — —15 – 70 2 65 — — HBL15 – 100 3 65 —15 – 30 1 10 — —
BLF15 – 60 2 10 — —15 – 30 1 22 — —
BLHF15 – 60 2 22 — —15 – 30 2 10 — —
BGL15 – 30 3 10 — —15 – 30 1 10 — —
BLE15 – 60 2 10 — —15 – 100 1 65 14 —15 – 100 2 65 14 — BQD15 – 100 3 65 14 —15 – 100 1 — — 1015 – 100 2 — — 10 BQD615 – 100 3 — — 10
Branch Breaker Selection
17
Modifications
A
B
C
D
E
F
G
H
I
J
K
Main Breaker
Branch Breakers
Provisions for adding Sub-feedBreaker or Feed-thru Lugs
NEMA 1 Enclosure
Neutral Lug
Grounding Lug
Dead Front Cover
Fixed Data Label
Numbering Strips
Front
Branch Breaker Connector Strap
When required, special constructions or additions to standard panelboards may be specified for factory-assembled column panelboards.
Box ModificationsDescriptionGasketedMetal Card HolderNameplateCopper Ground BarInsulated Aluminum Ground LugInsulated Copper Ground Lug
Interior ModificationsDescriptionFeed-thru Lugs1
Handle Padlocking DevicesShunt TripCopper Neutral LugsCopper Main Lugs
Box Sizing ChartCertain modifications such as sub-feed breakers and feed-thrulugs require additional unit space. Use this chart to determineproper enclosure size.
BoxHeight
Panel Configuration (Inches)
All MLO 18 Circuit 48All MLO 30 Circuit 73All MLO 42 Circuit 85All MLO 18 Circuit with feed-thru lugs 73All MLO 30 Circuit with feed-thru lugs 85All MLO 42 Circuit with feed-thru lugs 85All MLO 18 Circuit with sub-feed breaker 73All MLO 30 Circuit with sub-feed breaker 85All Main Breaker 18 Circuit 48All Main Breaker 30 Circuit 73All Main Breaker 42 Circuit 85All Main Breaker 18 Circuit with feed-thru lugs 73All Main Breaker 30 Circuit with feed-thru lugs 85All Main Breaker 42 Circuit with feed-thru lugs 85All Main Breaker 18 Circuit with sub-feed breaker 73All Main Breaker 30 Circuit with sub-feed breaker 85
Max. Connectors
Max. No. of Suitable for
Amps Poles Cu or Al
18125 30 (1) #6 AWG-350 kcmil
4218
250 30 (1) #6 AWG-350 kcmil42
Main Lug Only
1 For increase in box height see sizing chart above.
J16
Sentron Column Width PanelboardType S1 Type S2250A 250A240V max. 480Y/277V 3Ø 4W65 KAIC Rating max. 600Y/347V 3Ø 4W
14 KAIC Rating
A
B
C
K
D
EF
G
H
I
Max. Max. Interrupting Rating Breaker
Amps Poles 240V Max 480Y/277V 600Y/347V Type
10 — — BL
1822 — — BLH
100 3065 — — HBL
4210 — — ED265 14 — BQD— — 10 BQD6
1865 18 — ED4
125 3065 25 18 ED6
42100 42 — HED4100 65 25 HHED6
18 10 — — QJ2225 30 22 — — QJH2
42 42 — — QJ2-H18 65 35 22 FXD6
250 30 65 35 22 FD642 100 65 25 HFD6
Main Breaker Selection
Breaker Ampere Maximum Interrupting Rating (kA)
Type No. of Poles Rating 240V 480Y/277V 600Y/347V
ED2 2 / 3 15 – 100 10 — —ED4 2 / 3 15 – 125 65 18 —ED6 2 / 3 15 – 125 65 25 18HED4 2 / 3 15 – 125 100 42 —HHED6 2 / 3 15 – 125 100 65 25QJ2 2 / 3 60 – 225 10 — —QJH2 2 / 3 60 – 225 22 — —QJ2-H 2 / 3 60 – 225 42 — —FXD6 2 / 3 70 – 250 65 35 22HFD6 2 / 3 70 – 250 100 65 25JXD6 2 / 3 200 – 400 65 35 25HJD6 2 / 3 200 – 400 100 65 35LXD6 2 / 3 450 – 600 65 35 25HLD6 2 / 3 250 – 600 100 65 35
1 When applying in a 42 circuit panel, see lighting and appliance panelboarddefinition on page 32. Also reference NEC Article 384-16.
2 No increase in box height. Space is already built into S1, S2 panel.
Sub-feed Breakers1 2
Ampere Maximum Interrupting Rating (kA) BreakerRating No. of Poles 240V 480Y/277V 600Y/347V Frame
15 – 70 1 10 — —15 – 100 2 10 — — BL15 – 100 3 10 — —15 – 70 1 22 — —15 – 100 2 22 — — BLH15 – 100 3 22 — —15 – 50 1 65 — —15 – 70 2 65 — — HBL15 – 100 3 65 —15 – 30 1 10 — —
BLF15 – 60 2 10 — —15 – 30 1 22 — —
BLHF15 – 60 2 22 — —15 – 30 2 10 — —
BGL15 – 30 3 10 — —15 – 30 1 10 — —
BLE15 – 60 2 10 — —15 – 100 1 65 14 —15 – 100 2 65 14 — BQD15 – 100 3 65 14 —15 – 100 1 — — 1015 – 100 2 — — 10 BQD615 – 100 3 — — 10
Branch Breaker Selection
Sentron Column Width PanelboardsDimensions and WeightsType S1 and S2
18
ED, ED4, ED6, HED4, HED6
QJ2, QJH2, QJ2-H
FXD6, FD6, HFD6
BL, BLH, HBL
BLF, BLHF
BQD
Gutter Dimensions–Cable Bending
A
B
C
D
E
Reference Letter Panel Width 7.625 Panel Width 8.5
A 3.200 —B — 3.300
Side Gutter Wiring Space (Inches)
Reference Letter Panel Width 7.6252 Panel Width 8.52
C 14.700 14.7000D 14.560 —E 13.810 13.810
Main Gutter Wiring Space (Inches)
2 Sub-feed breaker Limit 1 per panel. Not field addable.
Amp Rating Panel Width 7.625 Panel Width 8.5
125 24.000 24.000250 24.000 24.000
Main Lug End Gutter (Inches)
Column ExtensionAvailable in various standard lengths, extensions are 51/4 inchesdeep and 7 inches wide.
Height (Inches) Catalog Number
14 LXX-1420 LXX-2026 LXX-2632 LXX-3238 LXX-3841 LXX-4144 LXX-4453 LXX-5356 LXX-5662 LXX-6265 LXX-6568 LXX-6874 LXX-7480 LXX-8086 LXX-86
Pull BoxesTwo styles of pull boxes are available, top and front mounted.When the panel and its extensions are mounted in a structuralWF beam a front mounted pull box is required. When the panelsare surface mounted, a top mounted pull box may be used.Provisions are made so that the neutral bar may be mounted in the pull box when required.
Description Catalog Number
Top Mount LXXP-TFront Mount 1 LXX50-F
1 Includes 50” extension.1 Includes 50” extension.
19
Sent
ron®
Pow
er P
anel
boar
ds
400A
-120
0ASentron Power Panelboards set the standard of excellence for controlling power and distribution circuits as well as forservice entrance.
This line of robust power panelboards is ideal for handling thetoughest of commercial and industrial applications.
21
Maximum Unit Space Connectors Suitable for
Panel Amperes (Inches) Copper or Aluminum
30(1)—#3/0 AWG-500 kcmilS4 400 45(2)—#3/0 AWG-250 kcmil60
30S4 600 45 (2)—#3/0 AWG-500 kcmil
6030
S4/S5 800 45 (3)—#3/0 AWG-500 kcmil6030
S4/S5 1000 45 (4)—#3/0 AWG-500 kcmil6030
S4/S5 1200 45 (4)—#3/0 AWG-500 kcmil60
S4 and S5 Sentron Panelboard Main Lugs Only
A
B
C
D
E
F
G
H
I
J
K
L
H
I
J
J
K
Mounting Catalog Number
Breaker Type Position S4 S5
BL/BQD Twin SBL SBLBDED Twin SE6 SE6DCED6 Twin SCE SCEDQJ Twin SQJ SQJDFD6 Twin SF6 SF6DCFD6 Single SCF SCFDJXD2, JXD6 Single SJ1 SJ1DJXD2, JXD6 Twin — SJ2DSJD6 Single SSJ1 SSJ1DCJD6 Single SCJ SCJDSCJD6 Single SSCJ SSCJDLD6 Single SL6 SL6DSLD6 Single — SSL6DCLD6 Single SCL SCLDSCLD6 Single — SSCLDLMD6, HLMD6 Single — SLM1DMD6, HMD6, CMD6 Single — SMNDSMD6, SHMD6 Single — SSMNDND6, HND6 Single — SMNDSND6, SHND6, SCND6 Single — SSMND
Connecting Strap Kits 1 —Circuit Breaker
1 Includes cover plate.
B
Sentron Power Panelboards Circuit BreakerType S4 and S5400-1200A600V max.200 KAIC Rating max.
20
To select the proper basic catalog number for an S4 or S5panelboard it is first necessary to determine the enclosure size. An example of how to do this is shown on inside flap of cover.
Voltage Service
120/240 1 phase, 3 wire240/120 3 phase, 4 wire208Y/120 3 phase, 4 wire240 3 phase, 3 wire480Y/277 3 phase, 4 wire480 3 phase, 3 wire600 3 phase, 3 wire600Y/347 3 phase, 4 wire48 DC 2 wire125 DC 2 wire250 DC 2 wire125/250 DC 2 wire
S4 and S5 Sentron Panelboard System
A
C
G
B
D
E
F
L
I
Maximum Interrupting Rating (kA) UnitPanel Ampere Breaker Symmetrical Amperes Space Wire Type Rating Frame 240VAC 480V AC 600V (Inches) Range
JXD2 65 — —JXD6 65 35 25
21.25S4 200–400
JD6 65 35 2536.35
(1-2) 3/0-500 kcmil (Cu)SJD6 65 35 25
51.25(1-2) 4/0-500 kcmil (Al)
HJD6 100 65 35CJD6 200 150 100LXD6 65 35 25
21.25(1-2) 3/0-500 kcmil (Cu)
S4 250–600LD6 65 35 25
36.25(1-2) 4/0-500 kcmil (Al)
HLD6 100 65 3551.25
#1 AWG-500 kcmilCLD6 200 150 100 (Cu or Al)
LMD6 65 50 2521.25
HLMD6 100 65 5036.2551.25 (2) #1 AWG-500 kcmil
S5 400–800 MD6 65 50 2520.00
(Cu or Al)
HMD6 100 65 5035.00
(3) 300-400 kcmil
CMD6 200 100 5050.00
(Cu or Al)
SMD6 65 50 25ND6 65 50 25
20.00S5 800–1200
SND6 65 50 2535.00
(4) 250-500 kcmilHND6 100 65 50
50.00(Cu or Al)
CND6 200 100 50
Main Breaker Selection
Main Breaker (Single Mounted)
Branch Breakers (Twin Mounted)
Connecting Strap Kit
Neutral Lug Assembly
Phase Bus
Base Rail
NEMA 1 Enclosure
Dead Front Cover
Gutter Covers
Ventilated Louvers
Fixed Data Label
End Cover
21
Maximum Unit Space Connectors Suitable for
Panel Amperes (Inches) Copper or Aluminum
30(1)—#3/0 AWG-500 kcmilS4 400 45(2)—#3/0 AWG-250 kcmil60
30S4 600 45 (2)—#3/0 AWG-500 kcmil
6030
S4/S5 800 45 (3)—#3/0 AWG-500 kcmil6030
S4/S5 1000 45 (4)—#3/0 AWG-500 kcmil6030
S4/S5 1200 45 (4)—#3/0 AWG-500 kcmil60
S4 and S5 Sentron Panelboard Main Lugs Only
A
B
C
D
E
F
G
H
I
J
K
L
H
I
J
J
K
Mounting Catalog Number
Breaker Type Position S4 S5
BL/BQD Twin SBL SBLBDED Twin SE6 SE6DCED6 Twin SCE SCEDQJ Twin SQJ SQJDFD6 Twin SF6 SF6DCFD6 Single SCF SCFDJXD2, JXD6 Single SJ1 SJ1DJXD2, JXD6 Twin — SJ2DSJD6 Single SSJ1 SSJ1DCJD6 Single SCJ SCJDSCJD6 Single SSCJ SSCJDLD6 Single SL6 SL6DSLD6 Single — SSL6DCLD6 Single SCL SCLDSCLD6 Single — SSCLDLMD6, HLMD6 Single — SLM1DMD6, HMD6, CMD6 Single — SMNDSMD6, SHMD6 Single — SSMNDND6, HND6 Single — SMNDSND6, SHND6, SCND6 Single — SSMND
Connecting Strap Kits 1 —Circuit Breaker
1 Includes cover plate.
B
Sentron Power Panelboards Circuit BreakerType S4 and S5400-1200A600V max.200 KAIC Rating max.
20
To select the proper basic catalog number for an S4 or S5panelboard it is first necessary to determine the enclosure size. An example of how to do this is shown on inside flap of cover.
Voltage Service
120/240 1 phase, 3 wire240/120 3 phase, 4 wire208Y/120 3 phase, 4 wire240 3 phase, 3 wire480Y/277 3 phase, 4 wire480 3 phase, 3 wire600 3 phase, 3 wire600Y/347 3 phase, 4 wire48 DC 2 wire125 DC 2 wire250 DC 2 wire125/250 DC 2 wire
S4 and S5 Sentron Panelboard System
A
C
G
B
D
E
F
L
I
Maximum Interrupting Rating (kA) UnitPanel Ampere Breaker Symmetrical Amperes Space Wire Type Rating Frame 240VAC 480V AC 600V (Inches) Range
JXD2 65 — —JXD6 65 35 25
21.25S4 200–400
JD6 65 35 2536.35
(1-2) 3/0-500 kcmil (Cu)SJD6 65 35 25
51.25(1-2) 4/0-500 kcmil (Al)
HJD6 100 65 35CJD6 200 150 100LXD6 65 35 25
21.25(1-2) 3/0-500 kcmil (Cu)
S4 250–600LD6 65 35 25
36.25(1-2) 4/0-500 kcmil (Al)
HLD6 100 65 3551.25
#1 AWG-500 kcmilCLD6 200 150 100 (Cu or Al)
LMD6 65 50 2521.25
HLMD6 100 65 5036.2551.25 (2) #1 AWG-500 kcmil
S5 400–800 MD6 65 50 2520.00
(Cu or Al)
HMD6 100 65 5035.00
(3) 300-400 kcmil
CMD6 200 100 5050.00
(Cu or Al)
SMD6 65 50 25ND6 65 50 25
20.00S5 800–1200
SND6 65 50 2535.00
(4) 250-500 kcmilHND6 100 65 50
50.00(Cu or Al)
CND6 200 100 50
Main Breaker Selection
Main Breaker (Single Mounted)
Branch Breakers (Twin Mounted)
Connecting Strap Kit
Neutral Lug Assembly
Phase Bus
Base Rail
NEMA 1 Enclosure
Dead Front Cover
Gutter Covers
Ventilated Louvers
Fixed Data Label
End Cover
Breaker Mounting Height Maximum Interrupting Rating (kA)
Ampere Breaker Ampere (Inches) Panel Symmetrical Amperes _________________ ________________________________________________________________________________________Rating Frame Rating Twin Single Type 120V AC 120/240V AC 240V AC 277V AC 480Y/277V AC 480V AC 600V AC 250V DC
BL (120) 15 - 100 3.751 — S4/S5 — 10 — — — — — —BL (240V) 15 - 100 3.751 — S4/S5 — — 10 — — — — —
100BLH 15 - 100 3.751 — S4/S5 — 22 22 — — — — —HBL 15 - 100 3.751 — S4/S5 — 65 65 — — — — —BQD 15 - 100 3.751 — S4/S5 — — 65 14 14 — — 14ED2 15 - 100 3.751 — S4/S5 10 — 10 — — — — 5ED4 15 - 125 3.751 — S4/S5 65 — 65 22 18 18 — 30ED6 15 - 125 3.751 — S4/S5 — — 65 — — 25 18 30
125 HED4 15 - 125 3.751 — S4/S5 100 — 100 653 42 42 — 30HHED6 15 - 125 3.751 — S4/S5 — — 100 — — 65 25 —CED6 15 - 125 3.751 — S4/S5 — — 200 — — 200 100 30QJ2 125 - 225 5 — S4/S5 — — 10 — — — — —
225 QJH2 125 - 225 5 — S4/S5 — — 22 — — — — —QJ2-H 125 - 225 5 — S4/S5 — — 42 — — — — —FXD6 70 - 250 5 — S4/S5 — — 65 — — 35 18 30
250FD6 70 - 250 5 — S4/S5 — — 65 — — 35 18 30HFD6 70 - 250 5 — S4/S5 — — 100 — — 65 25 30CFD6 70 - 250 — 5 S4/S5 — — 200 — — 200 100 30JXD2 200 - 400 2 8.75 S4/S5 — — 65 — — — — 30JXD6 200 - 400 2 8.75 S4/S5 — — 65 — — 35 25 30JD6 200 - 400 2 8.75 S4/S5 — — 65 — — 35 25 30
400SJD6 200 - 400 2 8.75 S4/S5 — — 65 — — 35 25 —HJD6 200 - 400 2 8.75 S4/S5 — — 100 — — 65 35 30SHJD6 200 - 400 2 8.75 S4/S5 — — 100 — — 65 35 —CJD6 200 - 400 — 8.75 S4/S5 — — 200 — — 150 100 30
. SCJD6 200 - 400 — 8.75 S4/S5 — — 200 — — 150 100 —LXD6 450 - 600 — 8.75 S4/S5 — — 65 — — 35 25 30LD6 250 - 600 — 8.75 S4/S5 — — 65 — — 35 25 30SLD6 300 - 600 — 8.75 S5 — — 65 — — 35 25 —
600 HLD6 250 - 600 — 8.75 S4/S5 — — 100 — — 65 35 30SHLD6 300 - 600 — 8.75 S5 — — 100 — — 65 35 —CLD6 450 - 600 — 8.75 S4/S5 — — 200 — — 150 100 30SCLD6 300 - 600 — 8.75 S5 — — 200 — — 150 100 —
800LMD6 500 - 800 — 8.75 S5 — — 65 — — 50 25 30HLD6 500 - 800 — 8.75 S5 — — 100 — — 65 50 30MD6, MXD6 500 - 800 — 10 S5 — — 65 — — 50 25 30SMD6 600 - 800 — 10 S5 — — 65 — — 50 25 —
800HMD6 500 - 800 — 10 S5 — — 100 — — 65 50 30SHMD6 600 - 800 — 10 S5 — — 100 — — 65 50 —CMD6 500 - 800 — 10 S5 — — 200 — — 100 50 30SCMD6 600 - 800 — 10 S5 — — 200 — — 100 50 —ND6, NXD6 800 -1200 — 10 S5 — — 65 — — 50 25 30SND6 800 -1200 — 10 S5 — — 65 — — 50 25 —
1200HND6 800 -1200 — 10 S5 — — 100 — — 65 50 30SHND6 800 -1200 — 10 S5 — — 100 — — 65 50 —CND6 900 -1200 — 10 S5 — — 200 — — 100 50 30SCND6 800 -1200 — 10 S5 — — 200 — — 100 50 —
Branch Breaker Selection
22
1 Mounting height: 1-6 poles require 3.75 inches of mounting height. All breakers are double-branch mounted.2 Consult enclosure selection chart on page 23. 400A twin mounted branches require 38 inch wide box.3 HED4 1-pole: 15-30A = 65,000A IR
35-100A = 25,000A IR
Branch Breakers
25
Mounting Height(in Inches) Connectors Suitable
Panel Ampere Number Twin Single AC Cables Per for Copper Type Rating of Poles Mounted Mounted Voltage Connector or Aluminum
30/30 2, 3 2.5 — 240 1 #14-#8 AWG (Cu Only)30/30 2, 3 5 — 240 1 #14-#4 AWG30/60 2, 3 5 — 240 1 #14-#4 AWG60/60 2, 3 5 — 240 1 #14-#4 AWG
F1/F2 60/100 2, 3 7.5 — 240 1 #10-#1/0 AWG100/100 2, 3 7.5 — 240 1 #10-#1/0 AWG200/200 3 10 — 240 1 #6 AWG-350 kcmil200 2 — 7.5 240 1 #6 AWG-350 kcmil200 3 — 10 240 1 #6 AWG-350 kcmil400 2, 3 — 15 240 2 #4/0 AWG-500 kcmil
F2600 2, 3 — 15 240 2 #4/0 AWG-500 kcmil800 2, 3 — 16.25 600 3 #3/0 AWG-500 kcmil
1200 2, 3 — 16.25 600 3 #3/0 AWG-500 kcmil30/30 2, 3 7.5 — 600 1 #14-#4 AWG30/60 2, 3 7.5 — 600 1 #14-#4 AWG60/60 2, 3 7.5 — 600 1 #14-#4 AWG
F1/F260/100 2, 3 7.5 — 600 1 #10-#1/0 AWG
100/100 2, 3 7.5 — 600 1 #10-#1/0 AWG200/200 3 10 — 600 1 #6 AWG-350 kcmil100 2, 3 — 7.5 600 1 #10-#1/0 AWG200 3 — 10 600 1 #6 AWG-350 kcmil400 2, 3 — 15 600 2 #4/0 AWG-500 kcmil
F2600 2, 3 — 15 600 2 #4/0 AWG-500 kcmil800 2, 3 — 16.25 600 3 #3/0 AWG-500 kcmil
1200 2, 3 — 16.25 600 3 #3/0 AWG-500 kcmil
Branch Switches
A
B
C
D
E
F
G
H
I
J
K
G
H
I
I
J
InterruptingClass Amperes Volts Ratings I2t, Ip Circuits
H 1-600A250 and 600V
10,000— Less than
or less AC — 10,000A available
K1 1-600A250 and 600V
100,000A — Feeder circuitsor less AC
J 1-600A 600V or less To 200,000AI2t-Low Feeder circuitsIp-Low (motor load small %)
RK1 1/10-600A600V or less
To 200,000AI2t-Slightly>J Feeder circuits
250V or less Ip-Slightly>J (motor load small %)
RK5 1/10-600A600V or less
To 200,000AI2t->RK-1 Motor starting
250V or less Ip->RK-1 currents a factor
T 1-600A300 and 600V
To 200,000AI2t-Low
Non-motor loadsor less AC Ip-Low
L 601-1200A 600V or less To 200,000AI2t-Low Feeder circuitsIp-Low (motor load small %)
UL Fuse Classes
1 Fuses do not prohibit the use of Class H type fuse in switch.
Branch Switch SelectionSentron Power PanelboardsFusible SwitchType F1 and F2400-1200A600V max.200 KAIC Rating max.
24
Panel Unit Space Connectors Suitable for
Type Amperes (Inches) Copper or Aluminum
10020
(1)—#10-#1/0 AWGF1
35
20020
(1)—#6 AWG-300 kcmil35
40025 (2)—#3/0 AWG-500 kcmil40 (2)—#3/0 AWG-250 kcmil
60025
(2)—#3/0 AWG-500 kcmilF2 40
80028.75
(3)—#3/0 AWG-500 kcmil43.75
120028.75
(3)—#3/0 AWG-500 kcmil43.75
Panel Maximum Unit Space Connectors Suitable for
Type Panel Amperes (Inches) Copper or Aluminum
30(1)—#3/0 AWG-500 kcmilF1 400 45(2)—#3/0 AWG-250 kcmil60
30F1 600 45 (2)—#3/0 AWG-500 kcmil
6030
F1/F2 800 45 (3)—#3/0 AWG-500 kcmil6030
F1/F2 1000 45 (4)—#3/0 AWG-500 kcmil6030
F1/F2 1200 45 (4)—#3/0 AWG-500 kcmil60
Main Lugs Only
Voltage Service
120/240 1 phase, 3 wire240/120 3 phase, 4 wire208Y/120 3 phase, 4 wire240 3 phase, 3 wire480Y/277 3 phase, 4 wire480 3 phase, 3 wire600 3 phase, 3 wire600Y/347 3 phase, 4 wire
48 DC 2 wire125 DC 2 wire250 DC 2 wire125/250 DC 2 wire
F1 and F2 Sentron Panelboard SystemA
B
C
D
E
F
H
K
Main Switch
Catalog Number
Ampere Rating F1 F2
30 – 30 F602 F602D30 – 30 F657 F657D30 – 60 F657 F657D60 – 60 F657 F657D60 – 100 F657 F657D
100 – 100 F657 F657D100 F607 F607D200 F607 F607D200 F671 F671D200 – 200 F672 F672D400 – 600 — F6150D800 – 1200 — F6162D
Connecting Strap KitsFusible
To select the proper basic catalog number for an F1 or F2panelboard it is first necessary to determine the enclosure size. An example of how to do this is shown on flap of inside cover.
Main Switch
Branch Switch
Neutral Lug Assembly
Phase Bus
Base Rail
NEMA 1 Enclosure
Dead Front Cover
Gutter Covers
Ventilated Louvers
Fixed Data Label
End Cover
25
Mounting Height(in Inches) Connectors Suitable
Panel Ampere Number Twin Single AC Cables Per for Copper Type Rating of Poles Mounted Mounted Voltage Connector or Aluminum
30/30 2, 3 2.5 — 240 1 #14-#8 AWG (Cu Only)30/30 2, 3 5 — 240 1 #14-#4 AWG30/60 2, 3 5 — 240 1 #14-#4 AWG60/60 2, 3 5 — 240 1 #14-#4 AWG
F1/F2 60/100 2, 3 7.5 — 240 1 #10-#1/0 AWG100/100 2, 3 7.5 — 240 1 #10-#1/0 AWG200/200 3 10 — 240 1 #6 AWG-350 kcmil200 2 — 7.5 240 1 #6 AWG-350 kcmil200 3 — 10 240 1 #6 AWG-350 kcmil400 2, 3 — 15 240 2 #4/0 AWG-500 kcmil
F2600 2, 3 — 15 240 2 #4/0 AWG-500 kcmil800 2, 3 — 16.25 600 3 #3/0 AWG-500 kcmil
1200 2, 3 — 16.25 600 3 #3/0 AWG-500 kcmil30/30 2, 3 7.5 — 600 1 #14-#4 AWG30/60 2, 3 7.5 — 600 1 #14-#4 AWG60/60 2, 3 7.5 — 600 1 #14-#4 AWG
F1/F260/100 2, 3 7.5 — 600 1 #10-#1/0 AWG
100/100 2, 3 7.5 — 600 1 #10-#1/0 AWG200/200 3 10 — 600 1 #6 AWG-350 kcmil100 2, 3 — 7.5 600 1 #10-#1/0 AWG200 3 — 10 600 1 #6 AWG-350 kcmil400 2, 3 — 15 600 2 #4/0 AWG-500 kcmil
F2600 2, 3 — 15 600 2 #4/0 AWG-500 kcmil800 2, 3 — 16.25 600 3 #3/0 AWG-500 kcmil
1200 2, 3 — 16.25 600 3 #3/0 AWG-500 kcmil
Branch Switches
A
B
C
D
E
F
G
H
I
J
K
G
H
I
I
J
InterruptingClass Amperes Volts Ratings I2t, Ip Circuits
H 1-600A250 and 600V
10,000— Less than
or less AC — 10,000A available
K1 1-600A250 and 600V
100,000A — Feeder circuitsor less AC
J 1-600A 600V or less To 200,000AI2t-Low Feeder circuitsIp-Low (motor load small %)
RK1 1/10-600A600V or less
To 200,000AI2t-Slightly>J Feeder circuits
250V or less Ip-Slightly>J (motor load small %)
RK5 1/10-600A600V or less
To 200,000AI2t->RK-1 Motor starting
250V or less Ip->RK-1 currents a factor
T 1-600A300 and 600V
To 200,000AI2t-Low
Non-motor loadsor less AC Ip-Low
L 601-1200A 600V or less To 200,000AI2t-Low Feeder circuitsIp-Low (motor load small %)
UL Fuse Classes
1 Fuses do not prohibit the use of Class H type fuse in switch.
Branch Switch SelectionSentron Power PanelboardsFusible SwitchType F1 and F2400-1200A600V max.200 KAIC Rating max.
24
Panel Unit Space Connectors Suitable for
Type Amperes (Inches) Copper or Aluminum
10020
(1)—#10-#1/0 AWGF1
35
20020
(1)—#6 AWG-300 kcmil35
40025 (2)—#3/0 AWG-500 kcmil40 (2)—#3/0 AWG-250 kcmil
60025
(2)—#3/0 AWG-500 kcmilF2 40
80028.75
(3)—#3/0 AWG-500 kcmil43.75
120028.75
(3)—#3/0 AWG-500 kcmil43.75
Panel Maximum Unit Space Connectors Suitable for
Type Panel Amperes (Inches) Copper or Aluminum
30(1)—#3/0 AWG-500 kcmilF1 400 45(2)—#3/0 AWG-250 kcmil60
30F1 600 45 (2)—#3/0 AWG-500 kcmil
6030
F1/F2 800 45 (3)—#3/0 AWG-500 kcmil6030
F1/F2 1000 45 (4)—#3/0 AWG-500 kcmil6030
F1/F2 1200 45 (4)—#3/0 AWG-500 kcmil60
Main Lugs Only
Voltage Service
120/240 1 phase, 3 wire240/120 3 phase, 4 wire208Y/120 3 phase, 4 wire240 3 phase, 3 wire480Y/277 3 phase, 4 wire480 3 phase, 3 wire600 3 phase, 3 wire600Y/347 3 phase, 4 wire
48 DC 2 wire125 DC 2 wire250 DC 2 wire125/250 DC 2 wire
F1 and F2 Sentron Panelboard SystemA
B
C
D
E
F
H
K
Main Switch
Catalog Number
Ampere Rating F1 F2
30 – 30 F602 F602D30 – 30 F657 F657D30 – 60 F657 F657D60 – 60 F657 F657D60 – 100 F657 F657D
100 – 100 F657 F657D100 F607 F607D200 F607 F607D200 F671 F671D200 – 200 F672 F672D400 – 600 — F6150D800 – 1200 — F6162D
Connecting Strap KitsFusible
To select the proper basic catalog number for an F1 or F2panelboard it is first necessary to determine the enclosure size. An example of how to do this is shown on flap of inside cover.
Main Switch
Branch Switch
Neutral Lug Assembly
Phase Bus
Base Rail
NEMA 1 Enclosure
Dead Front Cover
Gutter Covers
Ventilated Louvers
Fixed Data Label
End Cover
23
Sentron Power PanelboardsStandard Modifications and Dimensional DataType S4 and S5
Material
Design Criteria Aluminum Copper
Temperature Rise Standard Optionalover Ambient750 Ampere/Sq. in. Optional Optional1000 Ampere/Sq. in. Optional OptionalPlating Standard Tin Plate Silver
(Alstan Process)1 Standard per UL 67.
Conductor Material 1
Standard Modifications• Type 3R/12 Enclosures• Sub-feed lugs for 400 and 600A main lug panels• Feed-thru lugs for 400 through 1200A panels• Split bus for 400 through 1200A panels• Compression lugs for main lug panelboards• Compression lugs for main and branch circuit breakers• Remote control switches up to 300 amperes• Time clocks• Ground fault on main circuit breaker• Optional main bus• J, R, T or L fuse clips for fusible switches• Full range of accessories for molded case circuit breakers
Branch Breaker Side Gutters
Panel Width (Inches)
Reference Letter 32 (S4) 38 (S5)
A 11.000 14.000B 7.000 10.000C 5.750 8.750D 5.250 8.250E — 7.925F 4.615 7.615G 8.769 11.769H 10.425 13.425I 5.725 8.956J — 13.000K — 12.000
BLBLH, HBL
A
B
C
D
E
F
G
H4
I
J
K
BLBLH, HBL
ED2, ED4, ED6HED4, HHED6
ED2, ED4, ED6HED4, HHED6
QJ2, QJH2QJ2H
QJ2, QJH2QJ2H
FXD6, FD6,HFD6
FXD6, FD6,HFD6
JXD2, JXD6, JD6,SJD6, HJD6, SHJD6
JXD2, JXD6, JD6,SJD6, HJD6, SHJD6
CED6 CED6
CFD6
JXD2, JXD6, JD6, LXD6, LD6, SLD6HJD6, SJD6, SHJD6, HLD6, SHLD6
CJD6, SCJD6, CLD6, SCLD6
MD6, ND6, CMD6, CND6, HMD6, HND6
SMD6, SND6, SCMD6, SCND6, SHMD6, SHND6
5 Standard trim is four piece without door. Surface or flush one piece trim is availablefor 32” wide circuit breaker panel at no extra charge if specified on the order.
4 Single Mount in 32” enclosure for JD frame only.
3 Standard trim is four piece without door. Surface or flush one piece trim is availablefor 32” wide circuit breaker panel at no extra charge if specified on the order.
Type
3R/12 Type 1 Enclosure Available Unit Space (Inches)
Catalog Catalog Height Main Lug Main Breaker
Number Number (Inches) 400A 600A 800A 1200A 400A 600A
WP260 B60 60 30 30 30 30 — —WP275 B75 75 45 45 45 45 38.25 38.25WP280 B90 90 60 60 60 60 51.25 51.25
S4 Sentron Panelboard Enclosure Selection Data3
32” Wide, 10” Deep600A Maximum Breaker, 200A Fusible Switch
Type
3R/12 Type 1 Enclosure Available Unit Space (Inches)
Catalog Catalog Height Main Lug Main Breaker
Number Number (Inches) 800A 1200A 800A 1200A
WP860 B860 60 30 30 — —WP875 B875 75 45 45 35 35WP890 B890 90 60 60 50 50
S5 Sentron Panelboard Enclosure Selection Data5
38” Wide, 12.75” Deep Type 1; 38” Wide, 14.25” Deep Type 3R/12; 1200A Maximum Breaker, 600A Fusible Switch
Amp. Std. Oversize Crimp Std. Lugs Std. Lugs
Rating Lugs Lugs Lugs With Sub-feed With Feed-thru
400 16.494 16.494 19.181 16.745 16.494600 16.745 21.745 18.246 15.967 16.745800 15.967 25.963 18.676 — —1000 15.967 25.963 18.246 — —1200 15.967 25.963 18.246 — —
Main Breaker Gutter Dimensions
Main Breaker Side Gutter
LMXD6, LMD6, HLMD6 10.425MXD6, MD6, HMD6, ND6, HND6 13.000SJD6,SHJDD6, SLD6, SHLD6 10.425CJD6, SCJD6, CLD6, SCLD6 15.925JXD2, JXD6, JD6, HJD6LXD6, LD6, HLD6 10.425FXD6, FD6, HFD6 18.618
Main Breaker Gutter Dimensions (Inches)2
Main Lug End Gutter Dimensions (Inches)
2 Neutral Location 13.119
Breaker Mounting Height Maximum Interrupting Rating (kA)
Ampere Breaker Ampere (Inches) Panel Symmetrical Amperes _________________ ________________________________________________________________________________________Rating Frame Rating Twin Single Type 120V AC 120/240V AC 240V AC 277V AC 480Y/277V AC 480V AC 600V AC 250V DC
BL (120) 15 - 100 3.751 — S4/S5 — 10 — — — — — —BL (240V) 15 - 100 3.751 — S4/S5 — — 10 — — — — —
100BLH 15 - 100 3.751 — S4/S5 — 22 22 — — — — —HBL 15 - 100 3.751 — S4/S5 — 65 65 — — — — —BQD 15 - 100 3.751 — S4/S5 — — 65 14 14 — — 14ED2 15 - 100 3.751 — S4/S5 10 — 10 — — — — 5ED4 15 - 125 3.751 — S4/S5 65 — 65 22 18 18 — 30ED6 15 - 125 3.751 — S4/S5 — — 65 — — 25 18 30
125 HED4 15 - 125 3.751 — S4/S5 100 — 100 653 42 42 — 30HHED6 15 - 125 3.751 — S4/S5 — — 100 — — 65 25 —CED6 15 - 125 3.751 — S4/S5 — — 200 — — 200 100 30QJ2 125 - 225 5 — S4/S5 — — 10 — — — — —
225 QJH2 125 - 225 5 — S4/S5 — — 22 — — — — —QJ2-H 125 - 225 5 — S4/S5 — — 42 — — — — —FXD6 70 - 250 5 — S4/S5 — — 65 — — 35 18 30
250FD6 70 - 250 5 — S4/S5 — — 65 — — 35 18 30HFD6 70 - 250 5 — S4/S5 — — 100 — — 65 25 30CFD6 70 - 250 — 5 S4/S5 — — 200 — — 200 100 30JXD2 200 - 400 2 8.75 S4/S5 — — 65 — — — — 30JXD6 200 - 400 2 8.75 S4/S5 — — 65 — — 35 25 30JD6 200 - 400 2 8.75 S4/S5 — — 65 — — 35 25 30
400SJD6 200 - 400 2 8.75 S4/S5 — — 65 — — 35 25 —HJD6 200 - 400 2 8.75 S4/S5 — — 100 — — 65 35 30SHJD6 200 - 400 2 8.75 S4/S5 — — 100 — — 65 35 —CJD6 200 - 400 — 8.75 S4/S5 — — 200 — — 150 100 30
. SCJD6 200 - 400 — 8.75 S4/S5 — — 200 — — 150 100 —LXD6 450 - 600 — 8.75 S4/S5 — — 65 — — 35 25 30LD6 250 - 600 — 8.75 S4/S5 — — 65 — — 35 25 30SLD6 300 - 600 — 8.75 S5 — — 65 — — 35 25 —
600 HLD6 250 - 600 — 8.75 S4/S5 — — 100 — — 65 35 30SHLD6 300 - 600 — 8.75 S5 — — 100 — — 65 35 —CLD6 450 - 600 — 8.75 S4/S5 — — 200 — — 150 100 30SCLD6 300 - 600 — 8.75 S5 — — 200 — — 150 100 —
800LMD6 500 - 800 — 8.75 S5 — — 65 — — 50 25 30HLD6 500 - 800 — 8.75 S5 — — 100 — — 65 50 30MD6, MXD6 500 - 800 — 10 S5 — — 65 — — 50 25 30SMD6 600 - 800 — 10 S5 — — 65 — — 50 25 —
800HMD6 500 - 800 — 10 S5 — — 100 — — 65 50 30SHMD6 600 - 800 — 10 S5 — — 100 — — 65 50 —CMD6 500 - 800 — 10 S5 — — 200 — — 100 50 30SCMD6 600 - 800 — 10 S5 — — 200 — — 100 50 —ND6, NXD6 800 -1200 — 10 S5 — — 65 — — 50 25 30SND6 800 -1200 — 10 S5 — — 65 — — 50 25 —
1200HND6 800 -1200 — 10 S5 — — 100 — — 65 50 30SHND6 800 -1200 — 10 S5 — — 100 — — 65 50 —CND6 900 -1200 — 10 S5 — — 200 — — 100 50 30SCND6 800 -1200 — 10 S5 — — 200 — — 100 50 —
23
Sentron Power PanelboardsStandard Modifications and Dimensional DataType S4 and S5
Material
Design Criteria Aluminum Copper
Temperature Rise Standard Optionalover Ambient750 Ampere/Sq. in. Optional Optional1000 Ampere/Sq. in. Optional OptionalPlating Standard Tin Plate Silver
(Alstan Process)1 Standard per UL 67.
Conductor Material 1
Standard Modifications• Type 3R/12 Enclosures• Sub-feed lugs for 400 and 600A main lug panels• Feed-thru lugs for 400 through 1200A panels• Split bus for 400 through 1200A panels• Compression lugs for main lug panelboards• Compression lugs for main and branch circuit breakers• Remote control switches up to 300 amperes• Time clocks• Ground fault on main circuit breaker• Optional main bus• J, R, T or L fuse clips for fusible switches• Full range of accessories for molded case circuit breakers
Branch Breaker Side Gutters
Panel Width (Inches)
Reference Letter 32 (S4) 38 (S5)
A 11.000 14.000B 7.000 10.000C 5.750 8.750D 5.250 8.250E — 7.925F 4.615 7.615G 8.769 11.769H 10.425 13.425I 5.725 8.956J — 13.000K — 12.000
BLBLH, HBL
A
B
C
D
E
F
G
H4
I
J
K
BLBLH, HBL
ED2, ED4, ED6HED4, HHED6
ED2, ED4, ED6HED4, HHED6
QJ2, QJH2QJ2H
QJ2, QJH2QJ2H
FXD6, FD6,HFD6
FXD6, FD6,HFD6
JXD2, JXD6, JD6,SJD6, HJD6, SHJD6
JXD2, JXD6, JD6,SJD6, HJD6, SHJD6
CED6 CED6
CFD6
JXD2, JXD6, JD6, LXD6, LD6, SLD6HJD6, SJD6, SHJD6, HLD6, SHLD6
CJD6, SCJD6, CLD6, SCLD6
MD6, ND6, CMD6, CND6, HMD6, HND6
SMD6, SND6, SCMD6, SCND6, SHMD6, SHND6
5 Standard trim is four piece without door. Surface or flush one piece trim is availablefor 32” wide circuit breaker panel at no extra charge if specified on the order.
4 Single Mount in 32” enclosure for JD frame only.
3 Standard trim is four piece without door. Surface or flush one piece trim is availablefor 32” wide circuit breaker panel at no extra charge if specified on the order.
Type
3R/12 Type 1 Enclosure Available Unit Space (Inches)
Catalog Catalog Height Main Lug Main Breaker
Number Number (Inches) 400A 600A 800A 1200A 400A 600A
WP260 B60 60 30 30 30 30 — —WP275 B75 75 45 45 45 45 38.25 38.25WP280 B90 90 60 60 60 60 51.25 51.25
S4 Sentron Panelboard Enclosure Selection Data3
32” Wide, 10” Deep600A Maximum Breaker, 200A Fusible Switch
Type
3R/12 Type 1 Enclosure Available Unit Space (Inches)
Catalog Catalog Height Main Lug Main Breaker
Number Number (Inches) 800A 1200A 800A 1200A
WP860 B860 60 30 30 — —WP875 B875 75 45 45 35 35WP890 B890 90 60 60 50 50
S5 Sentron Panelboard Enclosure Selection Data5
38” Wide, 12.75” Deep Type 1; 38” Wide, 14.25” Deep Type 3R/12; 1200A Maximum Breaker, 600A Fusible Switch
Amp. Std. Oversize Crimp Std. Lugs Std. Lugs
Rating Lugs Lugs Lugs With Sub-feed With Feed-thru
400 16.494 16.494 19.181 16.745 16.494600 16.745 21.745 18.246 15.967 16.745800 15.967 25.963 18.676 — —1000 15.967 25.963 18.246 — —1200 15.967 25.963 18.246 — —
Main Breaker Gutter Dimensions
Main Breaker Side Gutter
LMXD6, LMD6, HLMD6 10.425MXD6, MD6, HMD6, ND6, HND6 13.000SJD6,SHJDD6, SLD6, SHLD6 10.425CJD6, SCJD6, CLD6, SCLD6 15.925JXD2, JXD6, JD6, HJD6LXD6, LD6, HLD6 10.425FXD6, FD6, HFD6 18.618
Main Breaker Gutter Dimensions (Inches)2
Main Lug End Gutter Dimensions (Inches)
2 Neutral Location 13.119
Branch Breaker Selection
22
1 Mounting height: 1-6 poles require 3.75 inches of mounting height. All breakers are double-branch mounted.2 Consult enclosure selection chart on page 23. 400A twin mounted branches require 38 inch wide box.3 HED4 1-pole: 15-30A = 65,000A IR
35-100A = 25,000A IR
Branch Breakers
Fuse
Cartridge Maximum I2t Let-Through Amps2 Seconds x 103 Maximum Ip Let-Through Amps, Instantaneous
Size,
Amperes Class J Class RK-1 Class RK-5 Class T Class L Class J Class RK-1 Class RK-5 Class T Class L
0 – 30 7 11 50 7 — 12,000 12,000 14,000 12,000 —31 – 60 30 50 200 30 — 16,000 16,000 26,000 16,000 —61 – 100 80 100 500 80 — 20,000 20,000 32,000 20,000 —
101 – 200 300 400 2,000 300 — 30,000 30,000 50,000 30,000 —201 – 400 1,100 1,600 6,000 1,100 — 45,000 50,000 75,000 45,000 —401 – 600 2,500 4,000 12,000 2,500 — 70,000 70,000 100,000 70,000 —601 – 1800 — — — — 10,000 — — — — 80,000801 – 1200 — — — — 15,000 — — — — 120,000
Note: Chart based on 200,000A available fault current.
26
The proper fuse type for the application isselected using the following parameters:• voltage requirements• conductor ampacity• horsepower requirements• maximum available RMS fault current• UL fuse class
Padlocking MemberProvides easier locking of handle in the“ON” or “OFF” position.
Voidable Cover InterlockPermits authorized personnel to void thedoor interlock and open door with switch“ON”. Foolproof mechanism will notpermit door to be closed with the handlein the wrong position.
Quick-Make Quick-BreakAssured by design of cam mechanism and powerful springs. Positive operation in “ON” or “OFF” position results fromdesign of the cross arm and Vacu-Breakhead linkage.
Exclusive Vacu-Break Clampmatic Arc ControlHazardous switching arcs are safelyconfined and controlled in Vacu-Breakchamber.
Vacu-Break SwitchSide Gutter Wiring Space
Standard Modifications• Type 3R/12 Enclosures• Sub-feed lugs 400 and 600A main
lug panels• Feed-thru lugs for 400 through 1200A
panels• Split bus for 400 through 1200A panels• Compression lugs for main lug
panelboards• Compression lugs for main and branch
circuit breakers• Remote control switches up to
300 amperes• Time clocks• Ground fault on main circuit breaker• Optional main bus• J, R, T or L fuse clips for fusible switches• Full range of accessories for molded
case circuit breakers
600V AC
A
B
C
D
E
F
G
H
I
J
K
L
M
N
250V AC
v
v
v
v
v v
v v
v v
Reference Switch Panel Width (in Inches)
Letter Amperes 32 (F1) 38 (F2)
600V AC
A 1200 — 12.0800 — 12.0
B 600 — 19.3400 — 19.3
C 200 17.5 10.5D 100 17.5 10.5E 200/200 15.0 18.0F 100/100 15.0 18.0G 30/30 17.0 10.0
60/60 17.0 10.0
250V AC
H 1200 — 12.0800 — 12.0
I 600 — 18.5400 — 18.5
J 200 10.0 13.0K 200/200 15.0 18.0L 100/100 17.0 10.0M 60/60 10.0 13.0N 30/30 10.0 13.0
v
v
v
v v
v v
v v
v v
1 Standard trim is four piece without door.Surface or flush one piece trim is available for 32” wide circuit breaker panel at no extra charge if specified onthe order.
Type
3R/12 Type 1 Enclosure Available Unit Space – (Inches)
Catalog Catalog Height Main Lugs Main Switch
Number Number (Inches) 400A 600A 800A 1200A 200A
WP260 B60 60 30 30 30 30 20WP275 B75 75 45 45 45 45 35WP290 B90 90 60 60 60 60 —
F1 Sentron Panelboard Enclosure Selection Data132” Wide, 10” Deep600A Maximum Breaker, 200A Fusible Switch
Type
3R/12 Type 1 Enclosure Available Unit Space – (Inches)
Catalog Catalog Height Main Lugs Main Switch
Number Number (Inches) 800A 1200A 400A 600A 800A 1200A
WP860 B860 60 30 30 — — — —WP875 B875 75 45 45 25.0 25.0 28.75 28.75WP890 B890 90 60 60 40.0 — 43.75 43.75
F2 Sentron Panelboard Enclosure Selection Data138” Wide, 12.75” Deep Type 1; 38” Wide, 14.25” Deep Type 3R/12;1200A Maximum Breaker, 1200A Fusible Switch
UL Fuse Classes
Sentron Power Panelboards Standard Modifications and Dimensional DataType F1 and F2
Sent
ron®
Pane
lboa
rds
Tech
nica
l Inf
orm
atio
nThe end product of an outstanding ancestry, our new family ofSentron Panelboards represents the high level of engineeringinnovation our customers have come to expect from Siemens.We’ve added additional strength to an already rugged and durablepanelboard design. At the same time, we’ve trimmed the exteriorsize of many models, adding flexibility, taking up less space andmaking them easier to install. These new designs also simplifywiring and reduces material requirements, saving additionalinstallation time.
27
Features and BenefitsSentron Lighting PanelboardsS1, S2 and SE
28
Feature: Bolt-on interiors.Benefit: Insures integrity of the engineer's specification. Plug-inbreakers cannot be mixed as with some other designs.
Feature: Field convertible mains (bussed connected) – S1,S2 and SE panels are convertible from main lug to main breaker and vice versa.Benefit: Interiors can be field converted with no increase in box height.
Feature: Field-addable mains (bussed connected) sub-feedbreaker or feed-thru lug kits.Benefit: S1, S2 and SE panels are designed for field additions ofsub-feed breaker up to 600 amperes or feed-thru lug with noincrease in box height.
Feature: 125 and 250 ampere main busing.Benefit: Standard main lugs are 125 and 250 ampere, an industry first.
Feature: Split neutrals.Benefit: Neutral connections for each breaker are next to thebreaker. Wiring is faster with less clutter in the wiring gutter.
Feature: Copper branch breaker connectors on either aluminum or copper interiors.Benefit: Makes for a superior, cooler running joint.
Feature: S1, S2 and SE interiors are either top orbottom feed.Benefit: Factory assembled is easily converted if orderedin error. No special orders; no delays. Same enclosure sizefor main lug or main breaker.
Feature: S1 interi-ors accept the fullline of BL bolt-incircuit breakers.Benefit:Interrupting ratingsof 10,000 AIR,22,000, or 65,000 AIR.
Feature: S1 andS2 250A Max.interiors mount instandardgalvanized boxes.Benefit: S1 and S2mount in samebox.
Feature: Blankremovable end-walls as standard.Benefit: Contractoris not handicappedby non-standard "standard" KO patterns.
Feature: S1, S2 and SE panels arelabeled suitable for use as serviceequipment when NEC is compliedwith.Benefit: No special SUSE label. No needto specify SUSE.
Feature: Only 6 box sizes.Benefit: Simpler, less items to stock forthe distributor.
Feature: S1, S2 and SE interiors utilizes Siemens’ widelyaccepted Fas-Latch fronts with concealed hinges.Benefit: Convenient screws that securely attach trim to deadfront with only a few quick turns of a screwdriver.
Feature: Door-in-door and hinged fronts are available.Benefit: S1, S2 and SE panels can be converted to door-in-doorand hinged fronts by replacing the Fas-Latch front.
Feature: New catalog numbering system.Benefit: Easy to understand system for all Sentron family panelboards.
Feature: Interior adjusting screw.Benefit: The adjusting screw makes interior adjustment on flush installation easy and quick.
Feature: 200 ampere rated branch connector.Benefit: Two 100 ampere breakers may be mounted acrossfrom each other.
Feature: Lay-in main lugs (S1 and S2 250A Max.).Benefit: Lay-in lugs simplify wiring for contractors.
Feature: Wide range of 100 thru 600 ampere Sentroncircuit breakers available as mains.Benefit: Proven performance in circuit protectionfrom Siemens.
Feature: Main breakers are bus-connected to main bus bar.Benefit: No cable connection from main breaker to lugs.
Feature: Aluminum equipment ground bus is standard.Benefit: Each panel comes standard with an aluminum equipment ground. Contractors do not have to specify.
Feature: Horizontally mounted main breakers.Benefit: Saves space-minimizing panel height. Allowsinteriors to be inverted to convert from top feed to bottomfeed or vice versa.
Feature: Optional 200 percent capacity neutral.Benefit: Can be field installed.
Feature: Flush latch and lock.Benefit: Adds functional style.
A
A
C
C
C
B
B
29
Features and BenefitsSentron Power PanelboardsS4, S5 Circuit BreakerF1, F2 Fusible Switch
Feature: Widest selection of available main breakersup to 600 amperes (S4, F1) and 1200 amperes (S5, F2).Benefit: Proven performance in circuit protectionfrom Siemens.
Feature: Star nut for interior adjustment.Benefit: Interior adjustment on flush installations is quicklyaccomplished.
Feature: Split neutrals.Benefit: Wiring is faster with less clutter in the gutter.
Feature: Panel mount 800A/1200A switch.Benefit: Allows fusible branches up to 1200A and requiresonly 16.25 inches of unit space.
Feature: Wide selection at Sentron branch breakers.Benefit: Full range including current limiting and solid statethrough 600 amperes (S4, F1) and 1200 amperes (S5, F2).
Feature: Mix and match circuit breaker andfusible branches.Benefit: Maximum flexibility in circuit protection.
Feature: Reduced enclosure size.Benefit: Only 32” wide by 10” deep (F1 only).
Feature: One-piece front with door available (S4 only).Benefit: Locking door adds security. Can be flush-mounted.
Feature: Extensive list of modifications andoptions available.Benefit: Panel can be engineered for a wide variety of applications.
Feature: Type 3R/12 enclosure available.Benefit: Dual-rated enclosure can be used outdoors forType 3R applications, or indoors for Type 12.
Feature: Only 6 box sizes.Benefit: Simpler, less items to stock for the distributor.
Feature: New catalog numbering system.Benefit: Easy to understand system for all Sentron familypanelboards. Makes selection and ordering a snap.
Feature: Main breakers and main switches are bus-connected to main bus bar.Benefit: No cable connection from main breaker to lugs.
Feature: Aluminum equipment ground bus is standard.Benefit: Each panel comes standard with an aluminum equipment ground. Contractors do not have to specify.
Feature: Horizontally mounted main breakers.Benefit: Saves space, minimizing enclosure height.
Feature: Twin 200 ampere fusible switches.Benefit: Two 200 ampere switches in the space of one. Saves space.
Sentron TPSTransient Voltage Surge Suppression
Today more and more businesses depend on electronic equipment to provide critical information to operate their business with efficiency and, most importantly, accuracy.
Microprocessor-based controls depend on continuous qualitypower, in order to consistently provide you the efficiency andaccuracy of information your business depends on.
The Sentron TPS Surge Suppression Panelboard protects youruse of personal computers in the office, it protects your criticalprocesses from lightning strikes and other switching transients.
If your facility is already equipped with Sentron S1, S2 or SEPanelboards, the TPS Surge Suppressor Kit enables a quick, easyretrofit. If your facility is not equipped with Sentron Panelboards,consult your local Siemens distributor for availability.
• TPS system, mounted within the standard Sentron S1, S2 and SEpanelboard, eliminates extra wiring and space requirements.
• 80 or 160 kA peak current per phase.
• MOV-based design providing 2 nanoseconds reaction time.
• Field installation kits available for retrofit applications.
• Direct bolted connection to panelboard busbars.
• Audible alarm with silence switch and test button for immediate problem notification.
• Top or bottom feed.
• MB or MLO.
• Optional surge counter.
• Line-to-Neutral, Line-to-Ground and Neutral-to-Ground protection modes.
• Each 40mm MOV is individually fused at 200k AIC in the line-to-ground and line-to-neutral modes.
• LED indicators for voltage and diagnostic monitoring.
• Dry output contacts through DB-9 connector.
Sub-feed Lugs (Double Lugs)
Sub-feed lugs are mounted directly beside the main incominglugs and are used to connect two or more panelboards to the incoming feeder. The feeder cables are brought intoPanelboard 1 and connected to the main lugs. Another set ofcables that are the same size are connected to the sub-feedlugs of Panelboard 1 and are carried over to the main lugs ofPanelboard 2.
Bussing Sequence
Sentron interiors are designed to accommodate top or bottom feed. Regardless of which is specified, the uppermost pole is always on “A” phase; the second poledown is always on “B” phase, and the third pole down isalways on “C” phase.
As standard, branch breakers shall be mounted at the top of the panel with “spaces” at the bottom, regardless of thedirection panel is fed.
All breakers have bolted connections except plug-in type. The high-impact main bus supports provide bracing up to200,000A IR UL short circuit rating. Case-hardened, thread-forming screws are used on branch bus.
Feed-thru Lugs
Feed-thru lugs are mounted at the opposite end of the mainbus from the main lugs or main breaker and are used to connect two or more panelboards to the incoming feeder.The feeder cables are brought into Panelboard 1 and connected to the main lugs or main breaker. Cables interconnecting the two panelboards are connected to thefeed-thru lugs in Panelboard 1 and are carried over to themain lugs in panelboard 2. This arrangement could bereversed with the main lugs located at the top and the feed-thru lugs at the bottom end of the panel.
Lug Data, Space Required for Mounting of Double Panels
Use two or more panelboards with feed-thru or sub-feed lugswhen:1. Lighting and appliance panelboards are required withmore than 42 circuits.2. More circuit mounting space is required than is providedin the largest box size.
30
Lugs, Bussing Data, Double Panels
Shown mounted in wall
Shown mounted on surface of wall
PANELBOARD 1 PANELBOARD 2
MainLugs
MainBreaker
Incoming Feeder Cables
Feed-thruLugs
Neutral
Neutral
PanelPanel
PANELBOARD 1 PANELBOARD 2
MainLugs
MainLugs
Sub-feedLugs
Incoming Feeder Cables
Neutral Neutral
PanelPanel
1.75”
.25”
31
Ground Fault and Enclosures for Adverse Conditions
Symmetrical Interrupting AmpereBreaker
NumberRating (Amperes)
Unit Ratings___________ ________________________ _____________________________________________Maximum
TypeBreaker of Ampere Space For Load
Load Connectors
Amperes Bolt-On Frame Poles Rating 120V 120/240V (Inches) Connectors Aluminum Wire Copper Wire
30 X BLF 1 15-30 10,000 — 1 10-40A (1)#12 AWG to #6 AWG (1)#14–#6 AWG60 X BLF 2 15-60 — 10,000 2 50-100A (1)#6 AWG to #1/0 AWG (1)#8–#1 AWG30 X BLHF 1 15-30 22,000 — 1 10-40A (1)#8 AWG (1)#8 AWG60 X BLHF 2 15-60 — 22,000 2 50-100A (1)#6 AWG to #1/0 AWG (1)#8–#1 AWG
GFCI Ground Fault Personnel Protection (5 ma): 120, 120/240 Volts AC
GFCI Ground Fault Equipment Protection (30 ma): 120 Volts AC
Symmetrical Interrupting AmpereBreaker
NumberRating (Amperes)
Unit Ratings___________ ________________________ _____________________________________________Maximum
TypeBreaker of Ampere Space For Load
Load Connectors
Amperes Bolt-On Frame Poles Rating 120V 120/240V (Inches) Connectors Aluminum Wire Copper Wire
30 X BLE 1 15-30 10,000 — 1 10-40A (1)#12 AWG to #10 AWG (1)#14–#10 AWG60 X BLE 2 15-60 — 10,000 2 50-100A (1)#6 AWG to #1/0 AWG (1)#8–#1 AWG
Maximum Use With-
Amperes Breaker Types Bolt-On Number of Poles Unit Space (Inches) Available As (Description)
ED2, ED4 Basic Kit15-125 ED6 X 1,2,3 1 Basic Kit with normally open bell alarm
HED4, HHED6 Basic Kit with normally closed alarm
Ground Fault Sensing Relay Kit Equipment Protection (30 ma)
Type 3R EnclosureFor outdoor use, primarily to help protect against rain, sleet andexternal ice formations.
Type 3R/12 EnclosureFor indoor/outdoor use, primarily to help protect against dust,falling dirt and dripping water.
Type 4X EnclosureFor indoor/outdoor use, primarily to help protect againstwindblown dust, rain, splashing water, hose-directed water and corrosion. Enclosures available are fiberglass, epoxy coated steel and stainless steel.
Sentron Lighting Panelboards Sentron Column Panelboards Sentron Power Panelboards Sentron Fusible Panelboards
Description S1 S2 SE S1 S2 S4 S5 F1 F2
Voltage 240V 480Y/277V 600V 240V 480Y/277V 600V 600V 600V 600V(maximum) 600Y/347V (maximum) (maximum) (maximum) (maximum) (maximum) (maximum)
System 1-phase, 3-wire 3-phase, 4-wire 1-phase, 3-wire 1-phase, 3-wire 3-phase, 4-wire 1-phase, 3-wire 1-phase, 3-wire 1-phase, 3-wire 1-phase, 3-wire3-phase, 4-wire 3-phase, 3-wire 3-phase, 4-wire 3-phase, 4-wire 3-phase, 4-wire 3-phase, 4-wire 3-phase, 4-wire
3-phase, 4-wire 3-phase, 3-wire 3-phase, 3-wire 3-phase, 3-wire 3-phase, 3-wireMain Lugs 125A-600A 125A,600A 125A-600A 125A-250A 125A, 250A 400A-1200A 800A-1200A 225A-1200A 800A-1200AMain Breaker 100A-600A 100A-600A 100A-600A 100A-250A 100A-250A 400A-600A 800A-1200A 400A-600A 800A-1200AMain Switch — — — — — 100A-200A 400A, 600A 100A, 200A 400A, 600ACircuits 18, 30, 42 18, 30, 42 30, 42 18, 30, 42 18, 30, 42 — — — —Branch Circuit BL, BLH, HBL BQD ED BL, BLH, HBL BQD All 15-600A All 15-1200A 30A-200A VB 30A-600A VBBreakersSub-feed ED4, ED6, HED4, HHED6 ED4, ED6, HED4, HHED6 FXD6, FD6, HFD6, JXD6 ED4, ED6, HED4, ED4, ED6, HED4, — — — —Circuit HED6, QJ2, QJH2, HED6, FXD6, FD6, JD6, HJD6, LXD6, LD6, HHED6, QJ2, QJH2, HHED6, FXD6,Breakers QJ2-H, FXD6, FD6, FD6, HFD6, JXD6, JD6, HJD6, HLD6 QJ2-H, FXD6, FD6, FD6, HFD6
JXD6, JD6, HJD6, LXD6, LD6, HLD6 HFD6, LXD6, LD6, HLD6
Enclosure 32”, 38”, 44”, 68” 32”, 38”, 44”, 68” 44”, 50”, 68” 48”, 73”, 85” 48”, 73”, 85” 60”, 75”, 90” 60”, 75”, 90” 60”, 75”, 90” 60”, 75”, 90”HeightsStandard Fas-Latch Fas-Latch Fas-Latch Fas-Latch Fas-Latch Four Piece Front Four Piece Front Four Piece Front Four Piece FrontTrims Surface or Flush Surface or Flush Surface or Flush Surface Surface
32
Panelboard Ratings
Sentron Panelboard Ratings
Class CTL PanelboardsClass CTL panelboards incorporate physical features which in conjunction with the physical size, configuration, or othermeans provided in Class CTL circuit breakers, are designed to prevent the installation of more overcurrent protective poles than that number for which the device is designated and rated. Per UL 67.
Service Entrance EquipmentWhen a panelboard is used as service entrance equipment, it must be located near the point of entrance of building supply conductors.
In a panel having main lugs only, the number of breakers or switches directly connected to the main bus must be limited to six.
In a panel having a main breaker or main switch, the number of circuits are not limited except as may be provided under other panelboard requirements, i.e. lighting and appliance branch circuit panelboards.
Also panel must include a connector for bonding and grounding neutral conductor.
Panelboard Code Data42-Circuit Rule: NEC Paragraph 384-14 defines a lighting and appliance branch circuit panelboard as one having more than 10 percent of its overcurrent devices rated 30 amperes or less, for which neutral connectors are provided. NEC paragraph 384-15 states not more than 42 overcurrent devices (other than those provided for in the mains)of a lighting and appliance branch-circuit panelboard shall be installed in any one cabinet. For the purpose of this article a two-pole circuit breaker shall be considered two overcurrentdevices; a three-pole circuit breaker shall be considered threeovercurrent devices. (NEC 384-14 and -15 do not apply to panelboards feeding communication circuits. Panelboards for this application must be so marked.)
Integrated EquipmentShort Circuit RatingThe term “Integrated Equipment Short Circuit Rating” refers to the application of series connected circuit breakers in a combination that allows some breakers to have lower individual interrupting ratings than the available fault current. This is permitted as long as the series combination has been tested and certified by UL. Consult Siemens sales office.
33
Recommended Specifications
GeneralFurnish and install circuit breaker lighting and appliance panel-boards where shown on the drawings and as indicated in the panelboards schedule.
Panelboards shall comply with the following industry standard:a. NEMA Standard PB-1b. UL Standards
Cabinets and Boxes-UL 50Panelboards-UL 67
c. National Electrical Code
Panelboards shall be labeled as suitable for use as service equipment in accordance with Article 384 of the National Electrical Code.
BoxThe panel box shall not be less than 20 inches wide and fabricated from galvanized or galvannealed steel. Box shall haveadjustment screws to provide easy alignment for flush mountedapplications. Removable end walls to be (blank) (with KO’s).Panelboard box is to have separate UL label and minimum wire bending and gutter requirements to meet the NEC and UL standards. Wiring gutters shall be completely free of any part of trim clamp to prevent damaging wire insulation.
Interior – Type S1, S2 and SEAll interiors shall be completely factory-assembled. The design ofthe interior should permit replacement of circuit breakers withoutdisturbing adjacent units and without machine drilling or tapping.All circuit breaker connections shall be in a hole tapped by themanufacturer. Main bus shall be tin finished 55 percent conductivityaluminum (standard) or temperature rated copper (optional). Branchbus shall be temperature rated copper only. Sizing of conductorshall be in accordance with UL 67. Bus bars shall be supported bya VO rated, UL recognized, polymeric material. Bus sequenceshall start at the top left phase bus of the interior for both top andbottom fed panels. Main lug panels shall be rated 125A, 250A,400A or 600A maximum. Main circuit breaker panels shall berated 100A, 125A, 225A, 250A, 400A or 600A.
Interiors shall be designed to permit installation of feed-thru lugs or a sub-feed circuit breaker, up to 600 amperes, withoutincreasing the enclosure size. Main and sub-feed breakers shall be bus connected, not cabled. Interior shall be convertible frommain lug to main breaker with the addition of an appropriate field-installable kit. Interior shall be changeable from top to bottom feed and vice-versa, while maintaining readability of dead-front labeling.
Dead-front shall be provided with a flange for easy attachment of trim. Incoming cable lugs shall be grouped at one end to separate them from the load side cables. Main lugs rated 250Ashall be lay-in construction to facilitate connections. Neutralbussing shall have a lug for each out-going branch requiring a neutral connection. For easy wiring and shortest cable run possible, load size neutral connection lugs to be split with eachside taking 50% of load neutral connections. The interior shall be provided with wing nuts for securing to box without tools.
Fas-Latch TrimThe panel trim shall be surface or flush as indicated on the drawings. It shall be fabricated from cold-rolled steel, painted withan ANSI-61 light gray finish and equipped with concealed hinges,flush lock and a holder for circuit directory card. Trim shall havetwo separate supports designed to engage the box flange to stabilize and secure the trim during installation. Trim screws to be located behind the lockable door for tamper resistance.
DescriptionThe panelboards shall be Sentron type for use one of the following systems as indicated on each panelboard schedule:
• 120/240 volts, 1 phase, 3 wire• 480 volts, 3 phase, 3 wire• 208Y/120 volts, 3 phase, 4 wire• 480Y/277 volts, 3 phase, 4 wire• 125/250 volts DC, 3 wire• 600Y/347 volts, 3 phase, 4 wire• other ___________________
The panelboard enclosures shall be NEMA Type 1 construction for (top) (bottom) cable entrance and suitable for (surface) (flush)mounting unless otherwise noted on panelboard schedules.
Short circuit rating shall be _____ amperes symmetrical based on (the smallest rating on any circuit breaker installed in the panelboard) (an integrated equipment short circuit rating).
Provide main lug only or main circuit breaker panelboards asshown on panelboard schedules. Also provide branch and sub-feed circuit breakers of the quantity, trip rating and number of poles as shown on schedules.
Molded case circuit breakers shall be thermal-magnetic, quick-make, quick-break, trip free. Multi-pole breakers shall be common trip. If current limiting circuit breaker mains are indicated on schedules, provide breakers with inverse time delay,instantaneous circuit protection and limit let-through l2t to a valueless than l2t of one-half cycle wave of the symmetrical prospectivecurrent without any fusible elements. If solid state circuit breakermains are shown on schedules for 400A or 600A panelboards,provide breakers with solid state sensing. Solid state breakersshall have adjustable continuous current settings and adjustableinstantaneous current settings. All breakers shall be equipped withantiturn solderless, pressure type connectors. All provisions shallbe located at the bottom of the panelboard and be fully bussedcomplete with all necessary mounting hardware less the breaker.
Provide sub-feed lugs, feed-thru lugs, handle blocking devices,padlocking devices, shunt trips and ground bus bars as shown on schedules.
Panelboards shall be manufactured by the Electrical ApparatusDivision of Siemens Energy and Automation, Inc.
34
General, Sentron Power Panelboards1200 Amperes, 600 Volts or LessFor distribution and power panelboards as shown in the panelboard schedule and shown on the plans, furnish and install Siemens Sentron Type S4/S5 and Type F1/F2 panelboards.All panelboards shall meet the requirements of the latest NationalElectrical Code (NEC) and applicable UL and NEMA Standards.
Distribution and power panel-boards shall be of the NEMApanel mounted type. The sec-tion shall be designed so thatcircuit breakers and fusibleswitches may be installed inthesame section. The branchprotective devices shall meetthe requirements of underbranch protective devices.
BoxThe panelboard assemblyshall be enclosed in a steelenclosure as specified in ULStandard 50 for cabinets.Wiring gutters for branchdevices shall be per ULStandard 67. Fronts shall befour piece for surface or flushinstallations as indicated onthe drawings. Fronts shall be of code gauge steel, painted ANSI-61.
InteriorBus bars and breaker branchbus shall be manufacturedfrom 55% conductivity tin-finished aluminum or 98% conductivity copper. Bus bars shall be supported by glass-filled polyester type insulators. Porcelain insulators or supports shall not be used. All bolts and screws used to connect current-carrying parts together shall be case-hardened, and be accessible for tightening from the front of thepanel. Attached to the dead-front cover shall be a nameplatewhich identifies: the name of the panel manufacturer, the manufacturer’s shop order number, panelboard type, system voltage, ampacity, and short circuit withstand rating.
Install main breaker or main switch panels as indicated on thedrawings. The connection from the load side of a main breaker to the panel bus shall be bus bar. The use of insulated wire shall not be permitted. Panelboards for use as service entranceequipment shall be so labeled.
An individual terminal or lug shall be provided for each neutralwire. Connecting several neutral wires to a common terminal shall not be permitted.
Branch Protective DevicesAll molded case circuit breakers and fusible switches used as aprotective device in a branch circuit shall meet the requirementsof the appropriate paragraph below.
Molded case circuit breakers shall be of the quick-make, quick-break, trip-free ___ Thermal magnetic type ___ solid-state, withframe, trip, and voltage ratings, either two pole or three pole, asindicated on the plans. All breakers shall have an interruptingcapacity of not less than ___ amperes RMS symmetrical at thesystem voltage. All breakers shall be removable from the front ofthe power panelboard without disturbing adjacent units. The
power panelboard shall have space or provision for future units, asshown on the plans. Sentron Current Limiting circuit breakers shallprovide inverse time delay, instantaneous circuit protection, andalso limit the let-though l2t to a value less than the l2t of the one-half cycle wave of the symmetrical prospective current without any fusible elements. Breakers shall have an interruptingcapacity of not less than ___ amperes RMS symmetrical at thesystem voltage.
Fusible switches shall be quick-make, quick-break units utilizingthe double-break principle of circuit rupturing to minimize arcingand pitting, and shall conform to the ratings shown on the plans.
Each switch shall have an individual door over the front, equippedwith a voidable interlock that prevents the door from beingopened when the switch is in the “ON” position, unless the inter-lock is purposely defeated by activation of the voiding mechanism.
All switches have externally operated handles. Switches shall beequipped with NEC standard, Class R rejection type fuse holder___ H, ___ K1, ___ K5, ___ RK1, ___ RK5, ___ J, ___ T fuses ofampere rating and type as indicated on the plans suitable for application on system with ___ ampere symmetrical available fault current.
Panel- Max.
board Amp.
Product Type Rating Zone 0-1 Zone 2 Zone 3 Zone 4
Panelboards S1 600A Std. Std. Mod. Mod.S2 600A Std. Std. Mod. Mod.SE 600A Std. Std. Mod. Mod.S4 1200A Std. Std. Mod. Mod.S5 1200A Std. Std. Mod. Mod.F1 1200A Std Std. Mod. Mod.F2 1200A Std. Std. Mod. Mod.
Seismic Requirements
0
1
2A
2B
3
4
35
On a national basis Siemens is committed to supporting thegrowth and prominence of Siemens products and services throughtrade journal and TV advertising, trade show participation, andother industry-wide activities. On a local basis Siemens offersdistributors a broad range of tools and programs designed tosupplement their selling efforts in the local marketplace, and toimprove their efficiency of doing business.
Sent
ron®
Pane
lboa
rds
Cust
omer
Sup
port
Info
rmat
ion
36
The Siemens Advantage:State-Of-The-Art Tools and Local Support
SPACE (Siemens Proposal Automation Calculation & Entry)In addition to automating the pricing process for most Siemensproducts, this user-friendly PC-based program generates com-plete bills of material and can produce high quality layout draw-ings for submittal purposes. Electronic order entry into theSiemens OMNIS network is also a feature of this program.
EDI (Electronic Data Interchange)Siemens fully supports electroniccommerce initiatives with distribu-tors. The current system supportsNAED-approved and EDI-Pro certi-fied transactions sets for incomingPO’s (#850), invoices (#810), andorder acknowledgements (#997 ͗). Additional transaction setsscheduled for late 1996 will add VMI (Vendor Managed Inventory)capabilities for interested Siemensdistributors.
Industry Standard (UPC) Bar-CodingAll Siemens standard products areroutinely bar-coded to assist inreceiving identification and ware-house automation.
Answer-PRO and KRISElectronic Catalog AvailabilitySiemens is an active contributor tothe new generation of CD-ROMbased electronic catalog servicesfrom NAED (Answer-PRO) and fromAHTD (KRIS). All standard distribution equipmentand controls are included in thesenew tools.
Comprehensive Training ToolsThe widely acclaimed STEP2000 training program series is available free of charge to all Siemens distributors. This self-paced program currently offers 10 training modules on topicsranging from the Basics of Electricity to the Basics of PLC’s. The STEP2000 modules are supplemented by local training programs conducted by Siemens sales engineers, as well ascomprehensive factory-based programs for advanced training.
Distributor Marketing ProgramsUnderscoring Siemens commitment to and support ofDistribution are the ROI and GEMS programs. These programsoffer Siemens distributors a wide array of incentives and toolsfrom which to choose in building a business plan with Siemens.Innovative new tools such as the PromoPAX promotion plan-ning software provide critical assistance in raising the profes-sionalism of marketing efforts by distributors.
Local SupportThe focal point of Siemens support for Distribution is the localSales Engineer. This individual is highly motivated to assistSiemens Distributors in growing their Siemens business, andshould be the first point of contact in all communications. Anational network of field service engineers and factory expertsalso stands ready to provide the 24-hour per day specializedassistance that some customers require.
How to Builda Catalog Number
Main Breaker Coding (Breaker Type) Code(BL)BL, (BLH)LH, (HBL)HL, (BQD)BD, (ED4)E4, (ED6)E6, (HED4)H4, (QJ2)QJ,(QJH2)QH, (QJ2-H)Q2, (FXD6)FX, (HFD6)HF, (JD6)J6, (JXD6)JX, (HJD6)HJ,(CJD6)CJ, (SJD6)SJ, (LXD6)LX, (LD6)L6, (HLD6)HL, (LMD6)LM, (HLMD6)HD,(MD6)M6, (HMD6)HM, (CMD6)CM, (SMD6)SM, (ND6)N6, (HND6)HN, (CND6)CN,(SND6)SN
Factory Assembled Panel Coding System
for Lighting Column Type Panelboards
Type of PanelS1 (C1)S2 (C2)Voltage and SystemA = 120/240V 1 Phase 3 Wire (S1)C = 208Y/120V 3 Phase 4 Wire (S1)E = 480Y/277V 3 Phase 4 Wire (S2)CircuitsS1, S2 – 18, 30, 42Main Lug (ML)Main Breaker (See Main Breaker Coding below)Amperage100-250 = S1, S2Bus MaterialA = Tin Plated Aluminum Temp Rated (Standard All Panels) (S1, S2)C = Copper Temp Rated (Optional) (S1, S2)Feed LocationT = TopB = BottomMountingS = Surface
C 1 C 4 2 M L 2 5 0 A T S
Type of PanelS1, S2, SE, S4, S5, F1, F2Voltage and SystemA = 120/240V 1 Phase 3 Wire (S1, SE, S4, S5, F1, F2)B = 240/120V 3 Phase 4 Wire (SE, S4, S5, F1, F2)C = 208Y/120V 3 Phase 4 Wire (S1, SE, S4, S5, F1, F2)D = 240V 3 Phase 3 Wire (SE, S4, S5, F1, F2)E = 480Y/277V 3 Phase 4 Wire (S2, SE, S4, S5, F1, F2)F = 480V 3 Phase 3 Wire (SE, S4, S5, F1, F2)G = 600V 3 Phase 3 Wire (SE, S4, S5, F1, F2)L = 600Y/347V 3 Phase 4 Wire (S2, SE, S4, S5, F1, F2)N = 125V DC (SE, S4, S5, F1, F2)O = 250V DC (SE, S4, S5, F1, F2)Circuits or Enclosure HeightS1, S2 – 18, 30, 42 S4, S5, F1, F2 – 60, 75, 90SE – 30, 42Main Lug (ML)Main Breaker (See Main Breaker Coding below)Main Switch (MS)Amperage100-600 = S1, S2 and SE400-1200 = S4, S5, F1, F2Bus MaterialA = Tin Plated Aluminum Temp Rated (Standard All Panels)B = 750A/in2 Al (Optional) All PanelsC = Copper Temp Rated (Optional) All PanelsD = 1000A/in2 Cu (Optional) All PanelsE = Silver Plated Cu (Optional) All Panels1
Feed LocationT = TopB = BottomMountingS = SurfaceF = Flush
S 1 C 4 2 M L 2 5 0 A T S
Factory Assembled Panel Coding Systemfor Lighting and Power Panelboards
1Not available on 250A temp. rated bus S1 and S2.