SELCO G-Line · G2000 G2200 G2000 G2200 G3000 G3100 SELCO G-Line for Land-based Applications...

6
3 Phase overcurrent Over- and/or undervoltage Over- and underfrequency Reverse or forward power For line-line or line-neutral Adjustable trip level, time delay and hysteresis Phase monitor (G3300) Preset push button defines reference Instant pick-up and delayed trip Two separate contacts for pick-up and trip LED based indication of relay status Optional external reset with latch function A single variant covers all voltages Optional PC based configuration (RS232) Flame retardant DIN rail enclosure Data Sheet SELCO G-Line Generator Protection Relays

Transcript of SELCO G-Line · G2000 G2200 G2000 G2200 G3000 G3100 SELCO G-Line for Land-based Applications...

  • • 3Phaseovercurrent

    • Over-and/orundervoltage

    • Over-andunderfrequency

    • Reverseorforwardpower

    • Forline-lineorline-neutral

    • Adjustabletriplevel,timedelayandhysteresis

    • Phasemonitor(G3300)

    • Presetpushbuttondefinesreference

    • Instantpick-upanddelayedtrip

    • Twoseparatecontactsforpick-upandtrip

    • LEDbasedindicationofrelaystatus

    • Optionalexternalresetwithlatchfunction

    • Asinglevariantcoversallvoltages

    • OptionalPCbasedconfiguration(RS232)

    • FlameretardantDINrailenclosure

    DataSheet

    SELCOG-LineGeneratorProtectionRelays

  • G2000

    G2200

    G2000

    G2200

    G3100G3000

    SELCOG-LineforLand-basedApplicationsSELCO’snewG-LineGeneratorProtectionRelaysaremainlyintendedforuseinland-basedapplications.TheG-Linerangeofrelaysprovidesanefficientsolutioninapplicationswherecostofmaterialsisthemainissue.Despitealowcost,theG-Linerelaysstillprovideanumberofground-breakingfeaturesnotpresentlyofferedbythecompetingrelays.

    InstallationThe SELCO G-Line Generator Protection Relays are easy to install. The relays are housed in a compact enclosure for DIN rail mounting or fixation by two ordi-nary screws. The design matches that of the well proven SELCO T-Line product range.

    ConfigurationConfiguration and setup is easier than ever. Despite the use of modern micro-processor technology, adjustment dials are maintained in order to make confi-guration and test as easy as possible. The reference current, voltage or frequen-cy is easily set by briefly activating a small push button (PRESET).

    Indications and RelaysThe state of the contact sets inside the re-lay is clearly indicated by LEDs located on the front plate. There is one LED for power, one LED for pick-up (activates when the set-point is exceeded) and one LED to indicate the state of the trip relay. The pick-up relay has one contact set and the trip relay has two contact sets.

    One relay covers all voltagesOne variant covers all voltages (nominal 63 to 690V AC). An external supply of +24V DC is required.

    Advanced ConfigurationThe SELCO G-Line Generator Protection Relays provide the optional feature of advanced PC based configuration (using a standard ANSI terminal). An optional programming kit (G0100) will allow the user to reconfigure the function of the relay, as well as the minimum/maxi-mum scales of the dials.

    This makes the G-Line relays even more flexible and versatile to customers requirering adapted functionality. The front plate of the relay can be custom-ized as well.

    DesignG-Line relays are single function units. The single variant principle is an advan-tage, as one version covers all voltages.

    Figure1:TheconnectionoftheG-LineRelays.

    Generator1 Generator2

    BUSBAR

    However, it is possible to choose (using the optional programming kit G0100) whether the relay is for e.g. under-current or overcurrent.

    Features include a level preset function (for reference definition), all optional functions onboard (e.g. latching), PC based configuration of scales, set points etc.

  • G��00 Current Relay

    Overcurrent(Undercurrent)

    8-36VDC/0.75Wat24VDC

    5ACT,max.10A

    35to75Hz

    50to140%(max.10to150%)

    1to10%(max.1to50%)

    3to30sec.(max.1to360sec.)

    380VAC,5A,1250VA150VDC,5A,120W

    ND(NE)Non-latching

    ND(NE)Non-latching(latching)

    Automatic(manuallybyterminal11)

    ±5%

    ±1%

    RJ11-modular

    -20°to70°C

    EN50263

    50hoursbeforefinaltest

    Polycarbonate.Flameretardant

    0.3kg

    73x75x114mm(HxWxD)

    35DINrailortwo4mm(3/16”)screws

    Function

    Supply

    Input voltage

    Input current

    Frequency

    Trip level

    Hysteresis

    Delay

    Relay rating

    Pick-up relay -Normalstate-Latching

    Trip relay -Normalstate-Latching

    Overfrequency relay -Normalstate-Latching

    Underfrequency relay -Normalstate-Latching

    Reset

    Accuracy

    Repeatability

    Serial link

    Operating temperature

    EMC

    Burn-in

    Enclosure material

    Weight

    Dimensions

    Installation

    G�000 Frequency Relay

    Over-andUnderfrequency

    8-36VDC/0.75Wat24VDC

    63to690VAC±30%

    35to75Hz

    OF:85to115%(max.75to125%)UF:85to115%(max.75to125%)

    1to10sec.(max.1to360sec.)

    380VAC,5A,1250VA150VDC,5A,120W

    NE(ND)Non-latching(latching)

    NE(ND)Non-latching(latching)

    Automatic(manuallybyterminal11)

    ±5%

    ±1%

    RJ11-modular

    -20°to70°C

    EN50263

    50hoursbeforefinaltest

    Polycarbonate.Flameretardant

    0.3kg

    73x75x114mm(HxWxD)

    35DINrailortwo4mm(3/16”)screws

    G�000 Power Relay

    ReversePower(ForwardPower)

    8-36VDC/0.75Wat24VDC

    63to690VAC±30%

    5ACT,max.10A

    35to75Hz

    RP:2to20%(max.2to50%)FP:50to140%(max.50to150%)

    1to10%(max.1to50%)

    2to20sec.(max.1to360sec.)

    380VAC,5A,1250VA150VDC,5A,120W

    ND(NE)Non-latching

    ND(NE).Non-latching(latching)

    Automatic(manuallybyterminal11)

    ±5%

    ±1%

    RJ11-modular

    -20°to70°C

    EN50263

    50hoursbeforefinaltest

    Polycarbonate.Flameretardant

    0.3kg

    73x75x114mm(HxWxD)

    35DINrailortwo4mm(3/16”)screws

    Specifications (Specificationsinparenthesesrequiresetupbyseriallink)

    Thespecificationsaresubjecttochangewithoutnotice.

  • G�600 Voltage Relay

    Over-andUndervoltage

    8-36VDC/0.75Wat24VDC

    63to690VAC±30%

    35to75Hz

    80to120%(max.70to130%)80to120%(max.70to130%)

    1to10sec.(max.1to360sec.)

    380VAC,5A,1250VA150VDC,5A,120W

    ND(NE)Non-latching

    NE(ND)Non-latching(latching)

    Automatic

    (manuallybyterm.11)

    ±5%

    ±1%

    RJ11-modular

    -20°to70°C

    EN50263

    50hoursbeforefinaltest

    Polycarbonate.Flameretardant

    0.3kg

    73x75x114mm(HxWxD)

    35DINrailortwo4mm(3/16”)screws

    Function

    Supply

    Input voltage

    Frequency

    Trip level -1sttriplevel-2ndtriplevel

    Hysteresis

    Delay

    Relay rating

    Phase monitor

    Pick-up (phase) relay -Normalstate-Latching

    Trip relay -Normalstate-Latching

    Overvoltage relay -Normalstate-Latching

    Undervoltage relay -Normalstate-Latching

    Reset

    Accuracy

    Repeatability

    Serial link

    Operating temperature

    EMC

    Burn-in

    Enclosure material

    Weight

    Dimensions

    Installation

    G��00 Voltage Relay

    3PhaseOvervoltage(Undervoltage)

    8-36VDC/0.75Wat24VDC

    63to690VAC±30%

    35to75Hz

    100to120%(max.1to130%)

    1to10%(max.1to50%)

    1to10sec.(max.1to360sec.)

    380VAC,5A,1250VA150VDC,5A,120W

    Phasefailure,phaseorder&symmetry

    ND(NE)Non-latching

    ND(NE)Non-latching

    Automatic

    (manuallybyterm.11)

    ±5%

    ±1%

    RJ11-modular

    -20°to70°C

    EN50263

    50hoursbeforefinaltest

    Polycarbonate.Flameretardant

    0.5kg

    73x75x114mm(HxWxD)

    35DINrailortwo4mm(3/16”)screws

    Specifications (Specificationsinparenthesesrequiresetupbyseriallink)

    Thespecificationsaresubjecttochangewithoutnotice.

    G�100 Voltage Relay

    Overvoltage(Undervoltage)

    8-36VDC/0.75Wat24VDC

    63to690VAC±30%

    35to75Hz

    100to120%(max.70to130%)

    1to10%(max.1to50%)

    1to10sec.(max.1to360sec.)

    380VAC,5A,1250VA150VDC,5A,120W

    ND(NE).Non-latching

    ND(NE)Non-latching(latching)

    Automatic

    (manuallybyterm.11)

    ±5%

    ±1%

    RJ11-modular

    -20°to70°C

    EN50263

    50hoursbeforefinaltest

    Polycarbonate.Flameretardant

    0.3kg

    73x75x114mm(HxWxD)

    35DINrailortwo4mm(3/16”)screws

  • SelcoG-LineConnections

    SELCO’s product philosophy is to offer easy-to-install, serviceable and reliable modular system components for mounting on switchboards and control consoles. Systems based on such components provide high flexibility, easy troubleshooting and require very little maintenance and serv-ice, which give our customers a low Total Cost of Ownership (TCO).

    Dimensions.

    G2200CurrentRelay

    G3300VoltageRelay

    G2000PowerRelay

    G3100VoltageRelay

    G3000FrequencyRelay

    G3600VoltageRelay

    75 114

    607,5

    50 73

    10

    Fixing holes2 x ø 4,5 mm.

    Dimensions in mm.

  • Argentina Australia Austria Belgium BrazilBulgaria ChinaCroatiaCzech RepublicEgypt Finland

    MainOffice:SELCOA/SBetonvej 10DK- 4000 RoskildeDenmarkPhone: + 45 - 70 26 11 22Fax: + 45 - 70 26 25 22e-mail: [email protected]

    SELCOWorldwideMalaysiaMorocco NetherlandsNorway Pakistan PhilippinesPoland Portugal Romania Russia SingaporeSouth Africa

    France GermanyGreeceHong KongHungary Iceland IndiaIndonesiaIranItaly Japan Korea

    SpainSwedenTaiwanThailandTurkeyUkraineUnited KingdomU.S.A.

    SELCODenmarkSELCOsubsidiarySELCOrepresentationAreaofsupply

    Q1

    00

    3 -6

    4 E