S-1 www.hubbell-wiring.com Wiring Device-Kellems ® Section S Trench and Wall Duct Products Index Hubbell Trench Duct Series Page Features and Benefits .......................................... S-2 Trench Duct Series and Fittings .................................. S-3 Additional Trench Duct Fittings .................................. S-4 Hubbell Wall Duct Series Page Features and Benefits .......................................... S-5 Wall Duct Series and Elbows .................................... S-6 Wall Duct Fittings ............................................. S-7 Additional Wall Duct Fittings .................................... S-8 Trench and Wall Duct Series Elbow Fittings Trench Duct Fittings Vertical Riser Fittings Hubbell also manufactures a comprehensive line of Floor Duct and Casino Duct products. Contact your local Hubbell representative for product information. Courtesy of Steven Engineering, Inc. - 230 Ryan Way, South San Francisco, CA 94080-5370 - Main Office: (650) 588-9200 - Outside Local Area: (800) 258-9200 - www.stevenengineering.com

Transcript of Section S Trench and Wall Duct Products - Steven Engineering...OKA/B9-1C-1/4 OKA/C9-2C-1/4...

Page 1: Section S Trench and Wall Duct Products - Steven Engineering...OKA/B9-1C-1/4 OKA/C9-2C-1/4 OKA/B12-2C-1/4 OKA/C12-3C-1/4 OKA/B18-3C-1/4 OKA/C18-4C-1/4 OKA/B24-3C-1/4 OKA/C24-4C-1/4

S-1www.hubbell-wiring.com Wiring Device-Kellems®

Section STrench and Wall Duct Products

Index

Hubbell Trench Duct Series Page

Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .S-2

Trench Duct Series and Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .S-3

Additional Trench Duct Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .S-4

Hubbell Wall Duct Series Page

Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .S-5

Wall Duct Series and Elbows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .S-6

Wall Duct Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .S-7

Additional Wall Duct Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .S-8

Trench and Wall Duct Series

Elbow Fittings

Trench Duct Fittings

Vertical Riser Fittings

Hubbell also manufactures a comprehensive line of Floor Duct and Casino Duct products. Contact your local Hubbell representative for product information.

Courtesy of Steven Engineering, Inc. - 230 Ryan Way, South San Francisco, CA 94080-5370 - Main Office: (650) 588-9200 - Outside Local Area: (800) 258-9200 - www.stevenengineering.com

Page 2: Section S Trench and Wall Duct Products - Steven Engineering...OKA/B9-1C-1/4 OKA/C9-2C-1/4 OKA/B12-2C-1/4 OKA/C12-3C-1/4 OKA/B18-3C-1/4 OKA/C18-4C-1/4 OKA/B24-3C-1/4 OKA/C24-4C-1/4

www.hubbell-wiring.comS-2 Wiring Device-Kellems®

Trench and Wall Duct ProductsHubbell Trench Duct Series Features and Benefits

• High capacity design supports large wiring for single and multiple service requirements

• Open top design allows wire to be easily laid in duct • Cover plates are removable and adjust horizontally

to any point along the duct. Custom lengths of trench and fittings are available. Provided in either galvanized G90 steel or nonferrous aluminum.

• Multiple compartment options allows for multiple circuit and low voltage separation

• Innovative duct support assembly allows for pre-pour leveling

• Packaging and labeling by project floor and room is available

A high capacity trench system for in-floor wire management.

The Hubbell Trench system is an in-floor wire management system that meets today’s high capacity wiring needs that require multiple circuit separation. Trench duct is commonly used as a feeder system for medical wall duct when installing radiology equipment such as X-Ray and MRI machines. Trench duct is also used as a stand alone system for commercial and retail applications where ease of access and high capacity are crucial variables.

Multiple compartments provide more capacity than conventional ducts.

The Hubbell Trench system provides more capacity than conventional conduits and ducts. It features a single, high-capacity duct with up to four compart-ments for easy placement of additional wiring.

It’s open top design allows wiring to be laid in the duct instead of being pulled, eliminating the need for junction boxes.

Removable covers are ¼" thick and lock into the track of the trench. Internal dividers and/or support strips increase load capacity of heavy-duty cover. These removable covers allow free access to wiring and can be placed anywhere along the duct for easy wire exit relocation.

Width

¼"

Depth

Trench Duct Range of Offering

Trench ProductDepth ½" Increments Width Compartments Cover Plate

OKA = TrenchOKB = Pull BoxOKC = Exit CoverOKE = End CapOKL = Horizontal LOKR = Vertical RiserOKT = T Junction BoxOKX = X Junction Box

A = 2"B = 2½"C = 3"D = 3½"E = 4"J = 6"N = 8"(Other Depths Available)

9121824

(Other Widths Avail.)

1C = 1 Compartment2C = 2 Compartment3C = 3 Compartment4C = 4 Compartment

1/4 = ¼" thick

Note: For Alumimum Trench Duct or Fittings, add “AL” suffix to catalog number.

Courtesy of Steven Engineering, Inc. - 230 Ryan Way, South San Francisco, CA 94080-5370 - Main Office: (650) 588-9200 - Outside Local Area: (800) 258-9200 - www.stevenengineering.com

Page 3: Section S Trench and Wall Duct Products - Steven Engineering...OKA/B9-1C-1/4 OKA/C9-2C-1/4 OKA/B12-2C-1/4 OKA/C12-3C-1/4 OKA/B18-3C-1/4 OKA/C18-4C-1/4 OKA/B24-3C-1/4 OKA/C24-4C-1/4

S-3www.hubbell-wiring.com Wiring Device-Kellems®

Trench and Wall Duct ProductsHubbell Trench Duct SeriesTrench Duct Series and Fittings

Tren

ch D

uct

DescriptionTrench Depth

Cover Width

No. of Compartments Catalog Number

Straight SectionManufactured in standard 6' lengths with factory installed dividers. Provided with (3) leveling feet on each side, (3) 24" long cover plates and (3) cover plate joint protectors.

2½"3"2½"3"2½"3"2½"3"

9"9"

12"12"18"18"24"24"

12233434

OKA/B9-1C-1/4OKA/C9-2C-1/4OKA/B12-2C-1/4OKA/C12-3C-1/4OKA/B18-3C-1/4OKA/C18-4C-1/4OKA/B24-3C-1/4OKA/C24-4C-1/4

Note: For Alumimum Trench Duct or Fittings, add “AL” suffix to catalog number.

Exi

t C

ove

r Fi

ttin

gs

Description Trench WidthMax Size Conduit Catalog Number

Exit CoverDesigned to provide exit and feed for Trench Duct. Conduit openings are provided for power and communication exit or feed using conventional fittings or service fittings. Cable Exit Cap (OKSK) is for communication cable only. Exit fittings cover may be spaced anywhere along the length of the trench. All exit fitting covers are 6" long.

9"12"18"24"9"12"18"24"

¾"¾"¾"¾"¾"¾"¾"¾"

OKC/9-3/4AOKC/12-3/4AOKC/18-3/4AOKC/24-3/4AOKC/9-3/4COKC/12-3/4COKC/18-3/4COKC/24-3/4C

Cable Exit CapFits opening in Type “A” Exit Cover. Provides outlet for communication cable. Debris barrier included. Cable Exit Cap constructed from die cast aluminum. For use with Type “A” exit covers only.

All — OKSK

Fitt

ing

s

Description Outside CoverNo. of

Compartments Catalog Number

Horizontal “L” FittingManufactured with a single cover and matching internal partitions to form a 90° horizontal “L”. Includes cover plate joint protectors and leveling feet.

12" x 12"12" x 12"15" x 15"15" x 15"21" x 21"21" x 21"27" x 27"27" x 27"

12233434

OKL/B9-1COKL/C9-2COKL/B12-2COKL/C12-3COKL/B18-3COKL/C18-4COKL/B24-3COKL/C24-4C

Horizontal 45° Elbow FittingManufactured with a split cover plate and matching internal partitions to form a 45° Mitered “L”. Other angles available. Includes cover plate joint protectors and leveling feet.

45°45°45°45°45°45°45°45°

12233434

OKL/B9-1Cx45OKL/C9-2Cx45OKL/B12-2Cx45OKL/C12-3Cx45OKL/B18-3Cx45OKL/C18-4Cx45OKL/B24-3Cx45OKL/C24-4Cx45

Single Level “T” Junction FittingManufactured with matching internal partitions and crossovers to isolate power and communications. Includes cover plate joint protectors and leveling feet.

15" x 12"15" x 12"18" x 15"18" x 15"24" x 21"24" x 21"30" x 27"30" x 27"

12233434

OKT/B9-1COKT/C9-2COKT/B12-2COKT/C12-3COKT/B18-3COKT/C18-4COKT/B24-3COKT/C24-4C

Pull BoxManufactured to attach to trench section replacing end cap. Divided into compartment as shown. Additional depth permits attachment of large conduits. Box is field punched for conduits. Standard depth is 6".

9" x 12"9" x 12"12" x 12"12" x 12"18" x 12"18" x 12"24" x 12"24" x 12"

12233434

OKB/B9-1COKB/C9-2COKB/B12-2COKB/C12-3COKB/B18-3COKB/C18-4COKB/B24-3COKB/C24-4C

Ordering Information Notes: 1. Common use sizes are listed below. Contact factory for other configurations or see page S-2 for Range of Offering table. 2. Trench Duct part numbers are for reference only. All Trench Duct orders are lot billed with a generic TW prefix project specific part numbers. Please contact your local Hubbell Territory Manager for all Hubbell Duct quotations.

Courtesy of Steven Engineering, Inc. - 230 Ryan Way, South San Francisco, CA 94080-5370 - Main Office: (650) 588-9200 - Outside Local Area: (800) 258-9200 - www.stevenengineering.com

Page 4: Section S Trench and Wall Duct Products - Steven Engineering...OKA/B9-1C-1/4 OKA/C9-2C-1/4 OKA/B12-2C-1/4 OKA/C12-3C-1/4 OKA/B18-3C-1/4 OKA/C18-4C-1/4 OKA/B24-3C-1/4 OKA/C24-4C-1/4

www.hubbell-wiring.comS-4 Wiring Device-Kellems®

Trench and Wall Duct ProductsHubbell Trench Duct SeriesTrench Duct Fittings

Fitt

ing

s

DescriptionFor Trench Duct (Width x Depth)

Max Size Conduit Catalog Number

Single Level “X” Junction FittingManufactured with matching internal partitions and crossovers to isolate power and communications. Includes cover plate joint protectors and leveling feet.

15" x 15"15" x 15"18" x 18"18" x 18"24" x 24"24" x 24"30" x 30"30" x 30"

12233434

OKX/B9-1COKX/C9-2COKX/B12-2COKX/C12-3COKX/B18-3COKX/C18-4COKX/B24-3COKX/C24-4C

End CapFits over end of trench run to close trench and prevent foreign material from entering. End cap may be drilled to accept conduit.

9" x 2½" 9" x 3"12" x 2½"12" x 3"18" x 2½"18" x 3"24" x 2½"24" x 3"

¾"1"¾"1"¾"1"¾"1"

OKE/B9OKE/C9OKE/B12OKE/C12OKE/B18OKE/C18OKE/B24OKE/C24

Vertical Riser Fitting (Straight)Manufactured to transition from trench duct to a panel, pull box or to conduit. Mounts on trench in place of cover. Partitioned to separate cells and flanged to attach to a pull box or panel. Removable front cover and top cover. Includes OWV trench-to-wall duct adapter. Standard height above finish floor —12". Standard depth —3½". Available in a sweep version (replace OKR with OKSWR)

9" x 3½" 9" x 3½"12" x 3½"12" x 3½"18" x 3½"18" x 3½"24" x 3½"24" x 3½"

————————

OKR/D9-1COKR/D9-2COKR/D12-2COKR/D12-3COKR/D18-3COKR/D18-4COKR/D24-3COKR/D24-4C

Trench to Wall Duct AdapterManufactured to transition from Trench Duct to Wall Duct. Mounts on trench in place of cover.

9" x 3½"12" x 3½"18" x 3½"24" x 3½"

————

OWV/D9OWV/D12OWV/D18OWV/D24

Tunn

el F

itti

ngs Description No. of Compartments “T” Unit Fitting Type “X” Unit Fitting Type

TunnelsFactory installed inside of multi-compartment “T” and “X” units to maintain separation of services. May be ordered separately and field installed.

2, 3, or 4 Consult Factory Consult Factory

Tren

ch D

uct

Acc

esso

ries Description Accessory Type Catalog Number

Permits 1" of pre-pour vertical adjustment and couples sections together. “x” represents screw height (max. 6") and height of trench. Additional vertical adjustment is available by increasing the length of screw “x”.

Single Leveling Foot Assembly

OK/F-x

Provides a 1½" wide surface (with gasket) for cover plate joints. “x” represents trench width.

Single Cover Plate Joint Protector

OK/DSD-x

Separates trench duct compartments. “x” represents trench depth (see catalog number system).

Divider OKP/x

Provided with ⁵�₁₆ x 18 bolts on 6" or 12" centers for increased cover plate weight loading capability.

Support Stud Strip Consult Factory

Ad

dit

iona

l Fit

ting

s

Description Trench Width #1 Trench Width #2 Catalog Number

Reducer FittingManufactured to transition from a wide trench duct width to a narrower trench duct width.

9"12"18"24"

6"9"12"18"

OKARED/B9-6-2COKARED/B12-9-3COKARED/B18-12-3COKARED/B24-18-4C

Fastening AnglesAccessories to join trench sections for field fabrication of horizontal and vertical assemblies.

Horizontal AngleVertical Angle

——

OK/VWIOK/VVW

Ordering Information Notes: 1. Common use sizes are listed below. Contact factory for other configurations or see page S-2 for Range of Offering table. 2. Trench Duct part numbers are for reference only. All Trench Duct orders are lot billed with a generic TW prefix project specific part numbers. Please contact your local Hubbell Territory Manager for all Hubbell Duct quotations.

Courtesy of Steven Engineering, Inc. - 230 Ryan Way, South San Francisco, CA 94080-5370 - Main Office: (650) 588-9200 - Outside Local Area: (800) 258-9200 - www.stevenengineering.com

Page 5: Section S Trench and Wall Duct Products - Steven Engineering...OKA/B9-1C-1/4 OKA/C9-2C-1/4 OKA/B12-2C-1/4 OKA/C12-3C-1/4 OKA/B18-3C-1/4 OKA/C18-4C-1/4 OKA/B24-3C-1/4 OKA/C24-4C-1/4

S-5www.hubbell-wiring.com Wiring Device-Kellems®

Trench and Wall Duct ProductsHubbell Wall Duct SeriesFeatures and Benefits

• Lay in wiring accommodates large cables and connectors to connect equipment

• Corrosion resistant galvanneled A60 steel or non ferrous aluminum versions

• Flush (primarily wall) and Surface (primarily ceiling) mount provides flexibility to address specific equipment placement and unique room design requirements

• Hubbell Wall Duct is utilized with Hubbell Trench Duct • Packaging and labeling by project floor and room

is available

The Hubbell Wall Duct is a UL Listed metal raceway system designed for the enclosure of wiring of MRI or X-Ray equipment in medical applications. The system provides complete lay-in wiring capability in order to accommodate the large cables and connectors used in today’s installations.

Hubbell Wall Duct is available in either flush or surface mount and a combination will usually be required on any job. Vertical runs in the walls are usually flush mounted with horizontal runs on walls and all duct in ceiling plenum are typically surface type.

Wall Duct is available in ferrous steel and non-ferrous aluminum versions.

Wall Duct Range of Offering

Wall Duct ProductDepth ½" Increments Width Cover Style

OWA = Wall DuctOWB = AdapterOWC = CouplingOWD = Reducer CouplingOWE = End ClosureOWF = Cabinet ConnectorOWH = Horizontal Elbow

OWI = Internal ElbowOWL = External ElbowOWP = PartitionOWR = Vertical RiserOWT = T UnitOWV = Trench to Wall Duct AdapterOWX = X Unit

A = 2"B = 2½"C = 3"D = 3½"E = 4"J = 6"N = 8"(Other Depths Available)

6101218

(Other Widths

Available)

S = SurfaceF = Flush

Note: For Alumimum Wall Duct or Fittings, add “AL” suffix to catalog number.

Courtesy of Steven Engineering, Inc. - 230 Ryan Way, South San Francisco, CA 94080-5370 - Main Office: (650) 588-9200 - Outside Local Area: (800) 258-9200 - www.stevenengineering.com

Page 6: Section S Trench and Wall Duct Products - Steven Engineering...OKA/B9-1C-1/4 OKA/C9-2C-1/4 OKA/B12-2C-1/4 OKA/C12-3C-1/4 OKA/B18-3C-1/4 OKA/C18-4C-1/4 OKA/B24-3C-1/4 OKA/C24-4C-1/4

www.hubbell-wiring.comS-6 Wiring Device-Kellems®

Trench and Wall Duct ProductsHubbell Wall Duct SeriesWall Duct Series and Elbows

Elb

ow

Fit

ting

s

DescriptionOverall Depth Body Width

Cover Width

FlushCatalog Number

Cover Width

SurfaceCatalog Number

Internal ElbowForms a sharp 90° Internal “L”. Provided with one cover plate, one coupling and necessary screws.

3½"3½"3½"

9¹³⁄₁₆"11¹³⁄₁₆"17¹³⁄₁₆"

12"14"20"

OWI/D10FOWI/D12FOWI/D18F

10"12"18"

OWI/D10SOWI/D12SOWI/D18S

Internal Elbow, SweepForms a chamfered 90° Internal “L” for increased cable bend radius. Provided with one cover plate, one coupling and necessary screws.

3½"3½"3½"

9¹³⁄₁₆"11¹³⁄₁₆"17¹³⁄₁₆"

12"14"20"

OWSWI/D10FOWSWI/D12FOWSWI/D18F

10"12"18"

OWSWI/D10SOWSWI/D12SOWSWI/D18S

Internal 45° ElbowForms a 45° Vertical “L”. Provided with one cover plate, one coupling and necessary screws.

3½"3½"3½"

9¹³⁄₁₆"11¹³⁄₁₆"17¹³⁄₁₆"

12"14"20"

OWI45/D10FOWI45/D12FOWI45/D18F

10"12"18"

OWI45/D10SOWI45/D12SOWI45/D18S

Horizontal ElbowForms a 90° Horizontal “L”. Provided with one cover plate, one coupling and necessary screws. Corner divider “OWCP” ordered separately.

3½"3½"3½"

9¹³⁄₁₆"11¹³⁄₁₆"17¹³⁄₁₆"

12"14"20"

OWH/D10FOWH/D12FOWH/D18F

10"12"18"

OWH/D10SOWH/D12SOWH/D18S

Horizontal 45° ElbowForms a 45° Horizontal “L”. Provided with one cover plate, one coupling and necessary screws.

3½"3½"3½"

9¹³⁄₁₆"11¹³⁄₁₆"17¹³⁄₁₆"

12"14"20"

OWH45/D10FOWH45/D12FOWH45/D18F

10"12"18"

OWH45/D10SOWH45/D12SOWH45/D18S

External ElbowForms a sharp 90° External “L”. Provided with two cover plates, one coupling and necessary screws.

3½"3½"3½"

9¹³⁄₁₆"11¹³⁄₁₆"17¹³⁄₁₆"

12"14"20"

OWL/D10FOWL/D12FOWL/D18F

10"12"18"

OWL/D10SOWL/D12SOWL/D18S

Note: Images shown are surface mount.

Wal

l Duc

t

DescriptionOverall Depth Body Width

Cover Width

FlushCatalog Number

Cover Width

SurfaceCatalog Number

Wall and Ceiling Duct Manufactured in standard 60" lengths with two 30" long cover plates. Provided with one coupling and necessary screws.

3½"3½"3½"

9¹³⁄₁₆"11¹³⁄₁₆"17¹³⁄₁₆"

12"14"20"

OWA/D10FOWA/D12FOWA/D18F

10"12"18"

OWA/D10SOWA/D12SOWA/D18S

Note: For Alumimum Wall Duct or Fittings, add “AL” suffix to catalog number.

Ordering Information Notes: 1. Common use sizes are listed below.Contact factory for other configurations or see page S-2 for Range of Offering table. 2. Trench Duct part numbers are for reference only. All Trench Duct orders are lot billed with a generic TW prefix project specific part numbers. Please contact your local Hubbell Territory Manager for all Hubbell Duct quotations.

Courtesy of Steven Engineering, Inc. - 230 Ryan Way, South San Francisco, CA 94080-5370 - Main Office: (650) 588-9200 - Outside Local Area: (800) 258-9200 - www.stevenengineering.com

Page 7: Section S Trench and Wall Duct Products - Steven Engineering...OKA/B9-1C-1/4 OKA/C9-2C-1/4 OKA/B12-2C-1/4 OKA/C12-3C-1/4 OKA/B18-3C-1/4 OKA/C18-4C-1/4 OKA/B24-3C-1/4 OKA/C24-4C-1/4

S-7www.hubbell-wiring.com Wiring Device-Kellems®

Trench and Wall Duct ProductsHubbell Wall Duct SeriesWall Duct Fittings

Inte

rnal

/ E

xter

nal E

lbo

ws

DescriptionOverall Depth Body Width

Cover Width

Flush Catalog Number

Cover Width

Surface Catalog Number

Internal / External ElbowTransitions from surface wall duct to surface style ceiling duct. Flush wall duct to surface style ceiling duct available upon request. Provided with two cover plates, one coupling and necessary screws.

3½"3½"3½"

9¹³⁄₁₆"11¹³⁄₁₆"17¹³⁄₁₆"

12"14"20"

———

10"12"18"

SPOWI/D10SSPOWI/D12SSPOWI/D18S

Internal / External Elbow, SweepTransitions from surface wall duct to surface style ceiling duct. Flush wall duct to surface style ceiling duct available upon request. Provided with two cover plates, one coupling and necessary screws.

3½"3½"3½"

9¹³⁄₁₆"11¹³⁄₁₆"17¹³⁄₁₆"

12"14"20"

———

10"12"18"

SPOWSWI/D10SSPOWSWI/D12SSPOWSWI/D18S

“T”

Uni

ts

Vertical “T” UnitForms a 90° Vertical “T”. Provided with three cover plates, two couplings and necessary screws.

3½"3½"3½"

9¹³⁄₁₆"11¹³⁄₁₆"17¹³⁄₁₆"

12"14"20"

OWVT/D10FOWVT/D12FOWVT/D18F

10"12"18"

OWVT/D10SOWVT/D12SOWVT/D18S

Horizontal “T” UnitForms a 90° Horizontal “T”. Provided with one cover plate, one coupling and necessary screws. Tunnels are ordered separately.

3½"3½"3½"

9¹³⁄₁₆"11¹³⁄₁₆"17¹³⁄₁₆"

12"14"20"

OWT/D10FOWT/D12FOWT/D18F

10"12"18"

OWT/D10SOWT/D12SOWT/D18S

“X”

Uni

t

“X” UnitForms intersection of four perpendicular ducts. Provided with one cover plate, two coupling and necessary screws. Tunnels are ordered separately.

3½"3½"3½"

9¹³⁄₁₆"11¹³⁄₁₆"17¹³⁄₁₆"

12"14"20"

OWX/D10FOWX/D12FOWX/D18F

10"12"18"

OWX/D10SOWX/D12SOWX/D18S

Ad

apte

r Fi

ttin

g DescriptionOverall Depth

Flush Wall Duct Body Width

Surface Cover Width Catalog Number

Flush to Surface AdapterTransitions from flush wall duct to perpendicular surface wall duct. Provided with one cover plate, two couplings and necessary screws.

3½"3½"3½"3½"

9¹³⁄₁₆"11¹³⁄₁₆"17¹³⁄₁₆"17¹³⁄₁₆"

10"18"12"18"

OWB/D10-10OWB/D12-18OWB/D18-12OWB/D18-18

Vert

ical

Ris

er F

itti

ngs

DescriptionFor Trench

WidthFor Wall Duct

(Width x Depth)Flush Catalog Number

Surface Catalog Number

Vertical Riser Fitting, StraightTransitions from trench duct to a vertical run of wall duct. Mounts on trench in place of cover. Removable front cover. Standard height above finish floor —12" (7" for OWR/D12x10). Standard depth — 3½". Provided with one coupling and necessary screws.

10"12"18"12"

10" x 3½"12" x 3½"18" x 3½"10" x 3½"

OWR/D10FOWR/D12FOWR/D18FOWR/D12-10F

OWR/D10SOWR/D12SOWR/D18SOWR/D12-10S

Vertical Riser Fitting, SweepTransitions from trench duct to a vertical run of wall duct. Mounts on trench in place of cover. Removable front cover. Standard height above finish floor —12". Standard depth —3½". Provided with one coupling and necessary screws.

10"12"18"12"

10" x 3½"12" x 3½"18" x 3½"10" x 3½"

OWSWR/D10FOWSWR/D12FOWSWR/D18FOWSWR/D12-10F

OWSWR/D10SOWSWR/D12SOWSWR/D18SOWSWR/D12-10S

Ordering Information Notes: 1. Common use sizes are listed below.Contact factory for other configurations or see page S-2 for Range of Offering table. 2. Trench Duct part numbers are for reference only. All Trench Duct orders are lot billed with a generic TW prefix project specific part numbers. Please contact your local Hubbell Territory Manager for all Hubbell Duct quotations.

Courtesy of Steven Engineering, Inc. - 230 Ryan Way, South San Francisco, CA 94080-5370 - Main Office: (650) 588-9200 - Outside Local Area: (800) 258-9200 - www.stevenengineering.com

Page 8: Section S Trench and Wall Duct Products - Steven Engineering...OKA/B9-1C-1/4 OKA/C9-2C-1/4 OKA/B12-2C-1/4 OKA/C12-3C-1/4 OKA/B18-3C-1/4 OKA/C18-4C-1/4 OKA/B24-3C-1/4 OKA/C24-4C-1/4

www.hubbell-wiring.comS-8 Wiring Device-Kellems®

Wall and Trench Duct ProductsHubbell Wall Duct SeriesWall Duct Fittings

Par

titi

ons

Fit

ting

s DescriptionFor Overall

Raceway DepthSurface

Cover Width

For Fitting Style

Straight Horizontal “L” Internal Sweep Elbow

Internal Duct PartitionsDivides raceway and fittings into compartments. Screws provided.

3½"3½"3½"

10"12"18"

OWP/D10——

—OWC/PD

——

OWSWP/D

Tunn

el F

itti

ngs

Description No. of Compartments “T” Unit Fitting Type “X” Unit Fitting Type

TunnelsField installed inside of multi-compartment “T” and “X” units to maintain separation of services. May be factory installed.

2, 3, or 4 Consult Factory Consult Factory

Ad

dit

iona

l Fit

ting

s

DescriptionOverall Depth

Cover Width

Flush Catalog Number Cover Width

Surface Catalog Number

Split Cover PlateProvides wire egress from raceway. Provided with assembly screws and grommet material.

———

12"14"20"

OWSC/10FOWSC/12FOWSC/18F

10"12"18"

OWSC/10SOWSC/12SOWSC/18S

End CapCloses off end of wall duct. Screws provided.

3½"3½"3½"

12"14"20"

OWE/D10FOWE/D12FOWE/D18F

10"12"18"

OWE/D10SOWE/D12SOWE/D18S

Cabinet ConnectorConnects wall duct to enclosures. Designed to be positioned around outside surface of duct and secured with screws from inside of duct. Screws provided.

3½"3½"3½"

12"14"20"

———

10"12"18"

OWF/D10OWF/D12OWF/D18

CouplingJoins surface or flush wall duct sections together. Designed to be positioned around outside surface of duct and secured with screws from inside of duct. Screws provided.

3½"3½"3½"

12"14"20"

———

10"12"18"

OWC/D10OWC/D12OWC/D18

Trench to Wall Duct AdapterTransitions from trench duct to a vertical run of wall duct when not using the OWR series Vertical Riser. Mounts on trench in place of cover. Provided with necessary screws.

3½"3½"3½"

12"14"20"

———

10"12"18"

OWV/D10OWV/D12OWV/D18

Reducer CouplingJoins two sizes of surface or flush wall duct sections together. Designed to be positioned around outside surface of duct and secured with screws from inside of duct. Screws provided.

3½"3½"

12"14"

——

18" to 10"18" to 12"

OWD/D (18-10)OWD/D (18-12)

Ordering Information Notes: 1. Common use sizes are listed below.Contact factory for other configurations or see page S-2 for Range of Offering table. 2. Trench Duct part numbers are for reference only. All Trench Duct orders are lot billed with a generic TW prefix project specific part numbers. Please contact your local Hubbell Territory Manager for all Hubbell Duct quotations.