A technical manual from the expertsin Business-Critical Continuity™

NetSure™ ITM Site Planning Data and System Drawings – 48V DC UPS Section 6037 (Issue 10, October 21, 2010)

Contents 1. Site Planning Data 2. One Line Diagram 3. System Outline Drawings 4. Connection Details

Section 6037 Emerson Network Power Issue 10, October 20, 2010 NetSure™ ITM

Page 2 Proprietary Information

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

1 SITE PLANNING DATA 1.1 Technical Specifications

NetSure® ITM – Technical SpecificationsPrimary Module 1 Expansion Module 2 Expansion Module 3 Expansion Module 4

Power Rating (full) – kW 70 70 70 70

Power Rating (N + 1) – kW 64 70 70 70

AC Input Specifications

Phase 3

Power Factor 0.99 at full load, 0.98 at 50% load

Frequency – Hz 45-65

Input Voltage – Nominal 400 / 480V, 3 wire + ground

Input Voltage – Range 304-530 VAC; shall withstand up to 600 VAC input without damage.

Input Breaker Rating / AIC Rating – A 150 / 65,000

Max Input Current / Module 480V: 115A @ 384V; 92A @ 480V

400V: 138A @ 320V; 110A @ 400V

380V: 145A @ 304V; 116A @ 380V

Inrush Current Inrush current does not exceed 150% of the rated input steady state peak value

Total Harmonic Distortion <5% from 50-100% of load

DC Output Specifications

Voltage Nominal: -48VDC; normal operation: -54.5 VDC (battery float)

Range: -42 to -58 VDC

System Efficiency 92.5% peak (system level including branch distribution losses)

Energy Optimization Mode: Intelligent Power Matching Allows operation at near-peak efficiency down to 5% overall load

Branch Distribution Options 22 circuit breakers, 100-200A each; optional: 6 fuses, 2x500A + 4x200A

Battery Specification

Type VRLA, Emerson Excellence EB4, 200 Ah

Arrangement 3 strings; eight 6V blocks per string

Backup Time See backup time table at various loads

Design Life 15 years @ 20 °C ; 10 years @ 25 °C

Recharge Time (to 97% of nominal capacity) Less than 3 hours for > 35% load; Less than 4 hours > 15% load

Physical Data

Form Factor Rack

Installed Dimensions (H x W x D) – in. (mm) 83 x 24 x 41 (2100 x 600 x 1040)

Installed Weight – lb. (kg) 3214 (1458)

Environmental Specifications

System Operating Temp. – °F (°C) -5 °C to +35 °C; recommended operation with battery: 20 °C to 25 °C air inlet

System Storage Temp. – °F (°C) -40 to 158 °F (-40 °C to +70 °C)

Relative Humidity 0 to 95%, non condensing

Operating Elevation – ft. (m) 6562 (2000) at full power

Audible Noise < 60dB

Heat Rejection at Full Load – BTU/hr. (kW) 18,096 (5.3) per module

EMI FCC class A

Safety Certifications

Agency Approved CE Marked to EN 60 950-1:2006

UL Listed to 60 950-1 + UL 1801; CSA certified

Monitoring Capability

Standard Web-based monitoring, alarm reporting via SNMP, and integration with SiteScan via SiteLink-E module

Optional Energy Master Remote Supervision

Emerson Network Power Section 6037 NetSure™ ITM Issue 10, October 20, 2010

Proprietary Information Page 3

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

1.2 Battery Run Times Battery Back-up Time (minutes)

Load Single module 70kW

Two modules 140kW

Three modules 210kW

Four modules 280kW

10kW 130 300 480 63020kW 55 130 210 30030kW 28 90 130 18040kW 17 55 90 13050kW 12 41 70 10064kW 7 24 50 7570kW 3 21 43 6980kW 17 34 5590kW 14 27 47

100kW 12 22 40110kW 10 19 34120kW 8 17 28134kW 6 16 25140kW 3 14 22150kW 12 19160kW 10 17170kW 9 15180kW 8 14190kW 7 13204kW 4 11210kW 2 10220kW 9230kW 9240kW 8250kW 7260kW 6274kW 3280kW 1

Section 6037 Emerson Network Power Issue 10, October 20, 2010 NetSure™ ITM

Page 4 Proprietary Information

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

2 ONE LINE DIAGRAM

LoadShunts

LoadShunts

BatteryShunts

Battery Fuse Battery

LVD

PCU PCU PCU PCU PCU PCU

Controller and Communication

Controller and Communication

Load Breakersor

Optional Fuses

Load Breakersor

Optional Fuses

BatteryShunts

Battery Fuse Battery

LVD

AC Input B(Optional)

AC Input A

AC Input B(Optional)

AC Input A

PCUBreakers(Note 4)

CurrentTransformer

PCUBreakers(Note 4)

CurrentTransformer

ACCircuit Breakers(Note 3)

ACCircuit Breakers(Note 3)

InternalDC-link

PRIMARYDC UPSMODULE (1)

EXPANSIONDC UPSMODULES (2-4)

Internal COM-link

NOTES1. DUAL AC INPUT VERSION OPTIONAL.2. RECOMMENDED INPUT WIRE SIZE 2/0 AWG, 90˚C (194˚F), SEE NEC TABLE 310.16.3. MAX INPUT CURRENT: 480V: 115A @ 384V; 92A @ 480V 400V: 138A @ 320V; 110A @ 400V 380V: 145A @ 304V; 116A @ 380V3. SYSTEM AC INPUT BREAKER(S) RATED 150A, 65kAIC.4. PCU AC INPUT BREAKERS RATED 32A, 5000AIC. TWO (2) PCUs PER BREAKER.

Emerson Network Power Section 6037 NetSure™ ITM Issue 10, October 20, 2010

Proprietary Information Page 5

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

3 SYSTEM OUTLINE DRAWINGS 3.1 Mechanical Installation and Outline Drawings 3.1.1 Individual Cabinet Mechanical Data

Notes:1. Dimensions are in inches (millimeters).2. Weight (fully loaded): 3240 lbs / 1470 kg.3. Heat Rejection: 18096 BTU/h at full load (per module)

.

4. May be installed on concrete slab or raised floor.

23.62(600)

84.33(2142)

topcabled

84.72(2152)bottomcabled

Battery Compartment

Conduits forAC Inputs41.34

(1050)

DC Power SystemCompartment

Z

X

YTop Cabled VersionX = 11.81 (300)Y = 26.38 (670)Z = 36.61 (930)

Bottom Cabled VersionX = 11.81 (300)Y = 26.38 (670)Z = 40.55 (1030)

CENTER OF GRAVITY

26.38(670)

CG

11.81(300)

(Bottomcabled)CG

11.81(300)

36.61(930)

40.55(1030)

CG(topcabled)

23.62(600)

Battery Compartment

Conduits forAC Inputs

41.34(1050) DC Power System

Compartment26.38(670)

CG

11.81(300)

DC UPS MODULE WITHTOP FEED DC DISTRIBUTION

DC UPS MODULE WITHBOTTOM FEED DC DISTRIBUTION

Top View Top View

Front View 3.1.2 System Configurations

System can be expanded either tothe left or the right of the Primary Module.

Single Module70kW (full)64kW (n+1)

Two Modules140kW (full)134kW (n+1)

Three Modules210kW (full)204kW (n+1)

Four Modules280kW (full)274kW (n+1)

Section 6037 Emerson Network Power Issue 10, October 20, 2010 NetSure™ ITM

Page 6 Proprietary Information

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

3.1.3 Main Components 3.1.3.1 Bottom Cabled Configuration - Circuit Breaker Load Distribution (Standard)

AC Input Conduit

* PCUs (12 x 5833W)

ACU+ (Controller)

Battery Fuses (800A)(Battery leads factoryconnected and routed toBattery Compartment.)

Load Distribution Devices(DC distribution circuit breakers,22 positions, 100-200A)(Fuse Option Available)

SM-AC (AC Input Monitoring)

Battery Return and Load Return(Battery return leads factoryconnected and routed toBattery Compartment.)

12

1 11

22

AC Input Circuit Breaker(s)(150A, 65kAIC)

Internal Circuit Breakers (32A)(Each Circuit Breaker Feeds Two PCUs)

LVD Contactor

PCU* Position#1

#3

#5

#7

#9

#11

PCU* Position#2

#4

#6

#8

#10

#12

Feeds PCU Position (left to right)#1/#2, #3/#4, #5/#6, #7/#8, #9/#10, #11/#12

Front View(door removed)

Emerson Network Power Section 6037 NetSure™ ITM Issue 10, October 20, 2010

Proprietary Information Page 7

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

3.1.3.2 Top Cabled Configuration - Circuit Breaker Load Distribution (Standard)

SUITABLE FO R MO UNT ING O N CO NCRET E

O R O THER NO N-COMBUST IBLE SURFACE O NLY.

AC InputConduit Openings

* PCUs (12 x 5833W)

ACU+ (Controller)

Battery Fuses (800A)(Battery leads factoryconnected and routed toBattery Compartment.)

Load Distribution Devices(DC distribution circuit breakers,22 positions, 100-200A)(Fuse Option Available)

SM-AC (AC Input Monitoring)

Battery Return and Load Return(Battery return leads factoryconnected and routed toBattery Compartment.)

12

1 11

22

AC Input Circuit Breaker(s)(150A, 65kAIC) Internal Circuit Breakers (32A)

(Each Circuit Breaker Feeds Two PCUs)

LVD Contactor

PCU* Position#1

#3

#5

#7

#9

#11

PCU* Position#2

#4

#6

#8

#10

#12

Feeds PCU Position (left to right)#1/#2, #3/#4, #5/#6, #7/#8, #9/#10, #11/#12

Front View(door removed)

Section 6037 Emerson Network Power Issue 10, October 20, 2010 NetSure™ ITM

Page 8 Proprietary Information

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

3.1.4 Bottom Cable Entry

BatteryCompartment

BFU

Distr.

Distr.

Raised Floor

Hot AisleCold Aisle

A

Air Flow

Note 2

Side View

SupportStand

½” (12mm) FloorAnchoring Bolts

(4 places)

Top

Front

Notes:1. Dimensions are in inches (millimeters).2. Do not block air intake openings.3. Minimum under floor space for underfloor

output cable runs: A = 1f (300mm).4. Run cables not to block air openings for battery

cooling.

BatteryCompartment

Conduits forAC Inputs

DC Power SystemCompartment

35.43(900)

17.72 (450)

8.86(225)

9.84(250)

19.68(500)

9.84(250)

8.86(225) Optional Floor

Opening forBattery Cooling

PCUs

PCUsPCUsPCUsPCUsPCUs

P/N 54782336” Tall Floor Stand

P/N 54782224” Tall Floor Stand

Emerson Network Power Section 6037 NetSure™ ITM Issue 10, October 20, 2010

Proprietary Information Page 9

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

3.1.5 Top Cable Entry

Note 2

Distr.

Distr.

Hot AisleCold Aisle

Air Flow

ConcreteFloor (slab)Side View

Notes:1. Dimensions are in inches (millimeters).2. Do not block air intake openings.

Top

BatteryCompartment

DC PowerSystem

Compartment Openings forOutput Cables

FrontCable Tray Supportsif Mounted on Top ofModule

Front View

Cable Tray

Cable Run

BatteryCompartment

PCUs

PCUsPCUsPCUsPCUs

PCUs

Top View

BatteryCompartment

Openings forOutput Cables

Cable Tray23.62(600)

BFU

½” (12mm) FloorAnchoring Bolts

(4 places)

35.43(900)

19.68(500)

Air Exchange(keep clear)

AC InputConduit Openings

Section 6037 Emerson Network Power Issue 10, October 20, 2010 NetSure™ ITM

Page 10 Proprietary Information

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

4 CONNECTON DETAILS 4.1 Bottom Cable Entry Electrical Connection Detail

DETAIL E

2"

RECOMMENDED COUPLING:RACO TYPE 2628(GRAINGER 3LV08) ORTHOMAS BETTS TYPE TK126US

COMMUNICATION LINKS BETWEEN CABINETS:1. RS-485 BUS WIRES (TWISTED YELLOW/WHITE WIRES) SHALL BE CONNECTED TO SM-AC. 2. CAN-BUS WIRES (TWISTED BLACK/WHITE WIRES) SHALL BE INTERCONNECTED.3. CONTACTOR CONTROL CABLES SHALL BE INTERCONNECTED.

NOTE1. WHEN CONNECTING OUTPUT DISTRIBUTION CABLES – START WHITH INNER ROW FIRST.

DETAIL D

ENTESC

USB

RJ45

USB

INPUT AC CONDUIT(S) SEE DETAIL ”E”

CONTROLLERSEE DETAIL ”D”

INPUT AC CONNECTION SEE DETAIL ”A”

INPUT AC CABLE ROUTING

CABINET GROUNDINGSUITABLE CABLE LUGSWITH HOLE DIA 3/8" (M10)TYPICAL LUG THOMAS & BETTS TYPE 54136RECOMMENDED TORQUE407-434 in-lbs (46-49 Nm).

SIDE PLATES ARE ONLY DELIVERED ON MAIN CABINET. SHALL BE MOVED TO THE LAST EXTENSION CABINET IN A ROW

1"

SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10)TYPICAL LUG THOMAS & BETTS TYPE 54209RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm)

DETAIL C (Circuit Breaker Option)

1”

SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10)TYPICAL LUG THOMAS & BETTS TYPE 54109RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm)

DETAIL B (Circuit Breaker Option)

1.75

"

1.5”

DETAIL C (Fuse Option)

S U IT A B LE C A B LE LU GS W IT H H OLE D IA 1 /2 " (M 12)T Y P IC A L LU G T H OM A S & B E T T S T Y P E 54282 (350kcm il)R E C OM M E N D E D T OR QU E 690-743 in-lbs (78-84 Nm)

1.75

"1.

75"

DETAIL B (Fuse Option)

S U IT A B LE C A B LE LU GS W IT H H OLE D IA 1 /2 " (M 12)T Y P IC A L LU G T H OM A S & B E T T S T Y P E 54282 (350kcm il)R E C OM M E N D E D T OR QU E 690-743 in-lbs (78-84 Nm)

NEGATIVE BUSBARSEE DETAIL ”C”(LOAD)

POSITIVE BUSBARSEE DETAIL ”B”(RETURN)

INPUT GROUNDINGCONNECTIONLUGS 5/16" (M8)TYPICAL LUG THOMAS &BETTS TYPE 54109RECOMMENDED TORQUE204-221 in-lbs (23-25 Nm)

DETAIL A

ONE OR TWO AC CIRCUIT BREAKERS,NO LUGS NEEDED.MARK CABLES A-L1, A-L2 AND A-L3 (B-L1, B-L2, B-L3)RECOMMENDED TORQUE 124 in-lbs (14 Nm)

factory wiring

L1 L2 L3AC IN A

L1 L2 L3AC IN B

GNDStud

GNDStud

Emerson Network Power Section 6037 NetSure™ ITM Issue 10, October 20, 2010

Proprietary Information Page 11

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

4.2 Top Cable Entry Electrical Connection Detail KNOCKOUTS FOR INPUT AC CONDUIT(S) SIZE 2"OR COUPLING(S) SIZE 2" (NOT INCLUDED)

CONTROLLERSEE DETAIL ”D”

INPUT AC CONNECTION SEE DETAIL ”A”

DETAIL E

2"

RECOMMENDED COUPLING:RACO TYPE 2628(GRAINGER 3LV08) ORTHOMAS BETTS TYPE TK126US

INPUT AC CABLE ROUTING

CABINET GROUNDINGSUITABLE CABLE LUGSWITH HOLE DIA 3/8" (M10)TYPICAL LUG THOMAS& BETTS TYPE 54136RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm).

SIDE PLATES ARE ONLY DELIVERED ON MAIN CABINET. SHALL BE MOVED TO THE LAST EXTENSION CABINET IN A ROW.

DETAIL B (Circuit Breaker Option)

1”

SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10)TYPICAL LUG THOMAS & BETTS TYPE 54109RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm)

DETAIL C (Circuit Breaker Option)

1"

SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10)TYPICAL LUG THOMAS & BETTS TYPE 54209RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm)

COMMUNICATION LINKS BETWEEN CABINETS:1. RS-485 BUS WIRES (TWISTED YELLOW/WHITE WIRES) SHALL BE CONNECTED TO SM-AC. 2. CAN-BUS WIRES (TWISTED BLACK/WHITE WIRES) SHALL BE INTERCONNECTED.3. CONTACTOR CONTROL CABLES SHALL BE INTERCONNECTED.

NOTE1. WHEN CONNECTING OUTPUT DISTRIBUTION CABLES – START WITH INNER ROW FIRST.

DETAIL D

ENTESC

USB

RJ45

USB

DETAIL AONE OR TWO AC CIRCUIT BREAKERS,NO LUGS NEEDED.MARK CABLES A-L1, A-L2 AND A-L3 (B-L1, B-L2, B-L3)RECOMMENDED TORQUE 124 in-lbs (14 Nm)

DETAIL B (Fuse Option)

1.75

"1.

75"

S U IT A B LE C A B LE LU GS W IT H H OLE D IA 1 /2 " (M 12)T Y P IC A L LU G T H OM A S & B E T T S T Y P E 54282 (350kcm il)R E C OM M E N D E D T OR QU E 690-743 in-lbs (78-84 Nm)

DETAIL C (Fuse Option)

1.75

"

1.5”

S U IT A B LE C A B LE LU GS W IT H H OLE D IA 1 /2 " (M 12)T Y P IC A L LU G T H OM A S & B E T T S T Y P E 54282 (350kcm il)R E C OM M E N D E D T OR QU E 690-743 in-lbs (78-84 Nm)

NEGATIVE BUSBARSEE DETAIL ”C”(LOAD)

POSITIVE BUSBARSEE DETAIL ”B”(RETURN)

INPUT GROUNDINGCONNECTIONLUGS 5/16" (M8)TYPICAL LUG THOMAS &BETTS TYPE 54109RECOMMENDED TORQUE204-221 in-lbs (23-25 Nm)

factory wiring

AC IN AL1 L2 L3

AC IN BL1 L2 L3

GNDStud

GNDStud

Emerson Network Power.The global leader in enabling Business-Critical Continuity™ .

AC Power

Connectivity

Embedded Computing

Embedded Power

Infrastructure Management & Monitoring

Outside Plant Racks & Integrated Cabinets

ServicesPower Switching & Controls

Surge Protection

Emerson Network PowerEnergy Systems, North America4350 Weaver Parkway, Warrenville, IL 60555Toll Free: 800-800-1280 (USA and Canada)Telephone: 440-246-6999 Fax: 440-246-4876Web: EmersonNetworkPower.com/EnergySystemsEnergyNet: Secure.EmersonNetworkPower.com

.

DC Power Precision Cooling

EmersonNetworkPower.com

Emerson (NYSE: EMR), based in St. Louis, is a global leader in bringing technology and engineering together to provideinnovative solutions for customers in industrial, commercial, and consumer markets through its network power, processmanagement, industrial automation, climate technologies, and appliance and tools businesses. For more information,visit: Emerson.com.

Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™

from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson NetworkPower provides innovative solutions and expertise in areas including AC and DC power, precision cooling, embeddedcomputing and power, integrated racks and enclosures, power switching and controls, infrastructure management, andconnectivity. All solutions are supported globally by local Emerson Network Power service technicians. For moreinformation on Emerson Network Power’s full suite of solutions specifically supporting the communications networkinfrastructure, visit: EmersonNetworkPower.com/EnergySystems.

Learn more about the NetSure™ ITM DC UPS from Emerson at: EmersonNetworkPower.com/NetSureITM.

This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North America, Inc. in writing) may not beused, applied or reproduced for any purpose or form part of any order or contract or be regarded as a representation relating to the products or services concerned. EmersonNetwork Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or conditions of supply of any product or service.Emerson®, Emerson Network Power™, Business-Critical Continuity™, Efficiency Without Compromise™, Albér®, EnergyMaster™, Liebert®, NetSure®, SiteScan™ and SiteWeb™

are trademarks of Emerson Electric Co. and/or one of its subsidiaries.

Code: Section 6037, Issue 10