NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS Section 6037 (Issue AC, April 8, 2013)
Specification Number: 582145500 Model: NetSure™ ITM
Contents 1. Site Planning Data 2. One Line Diagram 3. System Outline Drawings 4. Connection Details
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS
Spec. No: 582145500 Section 6037 Model: NetSure™ ITM Issue AC, April 8, 2013 2
1 SITE PLANNING DATA
1.1 Technical Specifications
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS
Spec. No: 582145500 Section 6037 Model: NetSure™ ITM Issue AC, April 8, 2013 3
1.2 Battery Run Times
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS
Spec. No: 582145500 Section 6037 Model: NetSure™ ITM Issue AC, April 8, 2013 4
2 ONE LINE DIAGRAM
LoadShunts
LoadShunts
BatteryShunts
BatteryFuse Battery
LVD
PCU PCU PCU PCU PCU PCU
Controller and
Communication
Controller and
Communication
Load Breakers
or
Optional Fuses
Load Breakers
or
Optional Fuses
BatteryShunts
BatteryFuse
Battery
LVD
AC Input B
(Optional)
AC Input A
AC Input B
(Optional)
AC Input A
PCUBreakers(Note 4)
Current
Transformer
PCUBreakers(Note 4)
Current
Transformer
ACCircuitBreakers
(Note 3)
ACCircuitBreakers
(Note 3)
InternalDC-link
PRIMARY
DC UPS
MODULE (1)
EXPANSION
DC UPS
MODULES (2-4)
InternalCOM-link
NOTES
1. DUAL AC INPUT VERSION OPTIONAL.
2. RECOMMENDED INPUT WIRE SIZE 2/0 AWG, 90 C (194 F), SEE NEC TABLE 310.16.
3. MAX INPUT CURRENT:
480V: 111A @ 384V; 89A @ 480V
400V: 133A @ 320V; 107A @ 400V
380V: 140A @ 304V; 112A @ 380V
3. SYSTEM AC INPUT BREAKER(S) RATED 150A, 65kAIC.
4. PCU AC INPUT BREAKERS RATED 32A, 5000AIC. TWO (2) PCUs PER BREAKER.
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS
Spec. No: 582145500 Section 6037 Model: NetSure™ ITM Issue AC, April 8, 2013 5
3 SYSTEM OUTLINE DRAWINGS
3.1 Mechanical Installation and Outline Drawings
3.1.1 Individual Cabinet Mechanical Data
3.1.2 System Configurations
23.62(600)
84.33(2142)
top
cabled
84.72(2152)
bottom
cabled
Battery Compartment
Conduits forAC Inputs41.34
(1050)
DC Power SystemCompartment
Z
X
Y
Top Cabled Version
X = 11.81 (300)
Y = 26.38 (670)
Z = 36.61 (930)
Bottom Cabled Version
X = 11.81 (300)
Y = 26.38 (670)
Z = 40.55 (1030)
CENTER OF GRAVITY
26.38(670)
CG
11.81(300)
(Bottomcabled)CG
11.81(300)
36.61(930)
40.55(1030)
CG(topcabled)
23.62(600)
Battery Compartment
Conduits forAC Inputs
41.34(1050)
DC Power SystemCompartment26.38
(670)
CG
11.81(300)
DC UPS MODULE WITH
TOP FEED DC DISTRIBUTION
DC UPS MODULE WITH
BOTTOM FEED DC DISTRIBUTION
Top View Top View
Front View
Notes:
1. Dimensions are in inches (millimeters).
2. Weight (fully loaded): 2925 lbs / 1325 kg.
3. Heat Rejection: 9554 BTU/h at full load (per module).
4. May be installed on concrete slab or raised floor.
System can be expanded either to
the left or the right of the Primary Module.
Single Module
70kW (full)
64kW (n+1)
Two Modules
140kW (full)
134kW (n+1)
Three Modules
210kW (full)
204kW (n+1)
Four Modules
280kW (full)
274kW (n+1)
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS
Spec. No: 582145500 Section 6037 Model: NetSure™ ITM Issue AC, April 8, 2013 6
3.1.3 Main Components
3.1.3.1 Bottom Cabled Configuration - Circuit Breaker Load Distribution (Standard)
AC Input Conduit
* PCUs (12 x 5833W)
ACU+ (Controller)
Battery Fuses (800A)
(Battery leads factory
connected and routed to
Battery Compartment.)
SM-AC (AC Input Monitoring)
Battery Return and Load Return
(Battery return leads factory
connected and routed to
Battery Compartment.)
12
1 11
22
AC Input Circuit Breaker(s)
(150A, 65kAIC)
Internal Circuit Breakers (32A)
(Each Circuit Breaker Feeds Two PCUs)
LVD Contactor
PCU* Position
#1
#3
#5
#7
#9
#11
PCU* Position
#2
#4
#6
#8
#10
#12
Feeds PCU Position (left to right)
#1/#2, #3/#4, #5/#6, #7/#8, #9/#10, #11/#12
Front View
(door removed)
Load Distribution Devices
(DC distribution circuit breakers,
22 positions, 100-200A)
(Fuse Option Available)
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS
Spec. No: 582145500 Section 6037 Model: NetSure™ ITM Issue AC, April 8, 2013 7
3.1.3.2 Top Cabled Configuration - Circuit Breaker Load Distribution (Standard)
AC Input
Conduit Openings
* PCUs (12 x 5833W)
ACU+ (Controller)
Battery Fuses (800A)
(Battery leads factory
connected and routed to
Battery Compartment.)
SM-AC (AC Input Monitoring)
Battery Return and Load Return
(Battery return leads factory
connected and routed to
Battery Compartment.)
12
1 11
22
AC Input Circuit Breaker(s)
(150A, 65kAIC) Internal Circuit Breakers (32A)
(Each Circuit Breaker Feeds Two PCUs)
LVD Contactor
PCU* Position
#1
#3
#5
#7
#9
#11
PCU* Position
#2
#4
#6
#8
#10
#12
Feeds PCU Position (left to right)
#1/#2, #3/#4, #5/#6, #7/#8, #9/#10, #11/#12
Front View
(door removed)
Load Distribution Devices
(DC distribution circuit breakers,
22 positions, 100-200A)
(Fuse Option Available)
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS
Spec. No: 582145500 Section 6037 Model: NetSure™ ITM Issue AC, April 8, 2013 8
3.1.4 Bottom Cable Entry
Battery
Compartment
BFU
Distr.
Distr.
Raised Floor
Hot AisleCold Aisle
A
Air Flow
Note 2
Side View
Support
Stand
½” (12mm) FloorAnchoring Bolts
(4 places)
Top
Front
Notes:1. Dimensions are in inches (millimeters).2. Do not block air intake openings.3. Minimum under floor space for underfloor
output cable runs: A = 1f (300mm).4. Run cables not to block air openings for battery
cooling.
BatteryCompartment
Conduits forAC Inputs
DC Power SystemCompartment
35.43(900)
17.72 (450)
8.86(225)
9.84(250)
19.68(500)
9.84(250)
8.86(225) Optional Floor
Opening forBattery Cooling
PCUs
PCUs
PCUs
PCUs
PCUs
PCUs
P/N 547823
36” Tall Floor Stand
P/N 547822
24” Tall Floor Stand
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS
Spec. No: 582145500 Section 6037 Model: NetSure™ ITM Issue AC, April 8, 2013 9
3.1.5 Top Cable Entry
Note 2
Distr.
Distr.
Hot AisleCold Aisle
Air Flow
Concrete
Floor (slab)Side View
Notes:1. Dimensions are in inches (millimeters).2. Do not block air intake openings.
Top
BatteryCompartment
DC PowerSystem
CompartmentOpenings forOutput Cables
FrontCable Tray Supportsif Mounted on Top ofModule
Front View
Cable Tray
Cable Run
Battery
CompartmentPCUs
PCUs
PCUs
PCUs
PCUs
PCUs
Top View
Battery
Compartment
Openings for
Output Cables
Cable Tray23.62(600)
BFU
½” (12mm) FloorAnchoring Bolts
(4 places)
35.43(900)
19.68(500)
Air Exchange
(keep clear)
AC Input
Conduit Openings
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS
Spec. No: 582145500 Section 6037 Model: NetSure™ ITM Issue AC, April 8, 2013 10
4 CONNECTON DETAILS
4.1 Bottom Cable Entry Electrical Connection Detail
DETAIL E
2"
RECOMMENDED COUPLING:RACO TYPE 2628(GRAINGER 3LV08) OR
THOMAS BETTS TYPETK126US
COMMUNICATION LINKS BETWEEN CABINETS:1. RS-485 BUS WIRES (TWISTED YELLOW/WHITE WIRES) SHALL BE CONNECTED TO SM-AC.2. CAN-BUS WIRES (TWISTED BLACK/WHITE WIRES) SHALL BE INTERCONNECTED.3. CONTACTOR CONTROL CABLES SHALL BE INTERCONNECTED.
NOTE
1. WHEN CONNECTING OUTPUT DISTRIBUTION CABLES – START WHITH INNER ROW FIRST.2. THE DC DISTRIBUTION GROUND/RETURN BUSBAR MUST BE CONNECTED VIA A SOLID
SINGLE-POINT GROUNDING LEAD TO THE MAIN BUILDING GROUND. REFER TO NEC,TABLE 250-122 FOR GROUNDING CONDUCTOR SIZE.
DETAIL D
ENTESC
USB
RJ45
USB
INPUT AC CONDUIT(S)SEE DETAIL ”E”
CONTROLLER
SEE DETAIL ”D”INPUT AC CONNECTIONSEE DETAIL ”A”
INPUT AC CABLEROUTING
CABINET GROUNDING
SUITABLE CABLE LUGSWITH HOLE DIA 3/8" (M10)TYPICAL LUG THOMAS& BETTS TYPE 54136RECOMMENDED TORQUE407-434 in-lbs (46-49 Nm).
SIDE PLATES ARE ONLY
DELIVERED ON MAINCABINET. SHALL BEMOVED TO THE LASTEXTENSION CABINET INA ROW
1"
SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10)TYPICAL LUG THOMAS & BETTS TYPE 54209RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm)
DETAIL C (Circuit Breaker Option)
1”
SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10)TYPICAL LUG THOMAS & BETTS TYPE 54109RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm)
DETAIL B (Circuit Breaker Option)
1.7
5"
1.5”
DETAIL C (Fuse Option)
S U ITA B LE C A B LE LU GS W ITH H OLE D IA 1/2" (M12)
TY P IC A L LU G TH OMA S & B E TTS TY P E 54282 (350kcm il)R E C OMM E N D E D TOR QU E 690-743 in-lbs (78-84 Nm)
1.7
5"
1.7
5"
DETAIL B (Fuse Option)
S U ITA B LE C A B LE LU GS W ITH H OLE D IA 1/2" (M12)
TY P IC A L LU G TH OMA S & B E TTS TY P E 54282 (350kcm il)R E C OMM E N D E D TOR QU E 690-743 in-lbs (78-84 Nm)
NEGATIVE BUSBARSEE DETAIL ”C”(LOAD)
POSITIVE BUSBARSEE DETAIL ”B”(RETURN)
INPUT GROUNDINGCONNECTION
LUGS 5/16" (M8)TYPICAL LUG THOMAS &BETTS TYPE 54109RECOMMENDED TORQUE204-221 in-lbs (23-25 Nm)
DETAIL A
ONE OR TWO AC CIRCUIT BREAKERS,NO LUGS NEEDED.MARK CABLES A-L1, A-L2 AND A-L3 (B-L1, B-L2, B-L3)RECOMMENDED TORQUE 124 in-lbs (14 Nm)
factory wiring
L1 L2 L3
AC IN A
L1 L2 L3
AC IN B
GND
Stud
GND
Stud
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS
Spec. No: 582145500 Section 6037 Model: NetSure™ ITM Issue AC, April 8, 2013 11
4.2 Top Cable Entry Electrical Connection Detail
KNOCKOUTS FOR INPUTAC CONDUIT(S) SIZE 2"OR COUPLING(S) SIZE 2"(NOT INCLUDED)
CONTROLLERSEE DETAIL ”D”
INPUT AC CONNECTIONSEE DETAIL ”A”
DETAIL E
2"
RECOMMENDED COUPLING:
RACO TYPE 2628(GRAINGER 3LV08) ORTHOMAS BETTS TYPETK126US
INPUT AC CABLEROUTING
CABINET GROUNDINGSUITABLE CABLE LUGSWITH HOLE DIA 3/8" (M10)TYPICAL LUG THOMAS& BETTS TYPE 54136
RECOMMENDED TORQUE407-434 in-lbs (46-49 Nm).
SIDE PLATES ARE ONLYDELIVERED ON MAINCABINET. SHALL BE
MOVED TO THE LASTEXTENSION CABINET INA ROW.
DETAIL B (Circuit Breaker Option)
1”
SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10)TYPICAL LUG THOMAS & BETTS TYPE 54109RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm)
DETAIL C (Circuit Breaker Option)
1"
SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10)TYPICAL LUG THOMAS & BETTS TYPE 54209RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm)
COMMUNICATION LINKS BETWEEN CABINETS:1. RS-485 BUS WIRES (TWISTED YELLOW/WHITE WIRES) SHALL BE CONNECTED TO SM-AC.2. CAN-BUS WIRES (TWISTED BLACK/WHITE WIRES) SHALL BE INTERCONNECTED.3. CONTACTOR CONTROL CABLES SHALL BE INTERCONNECTED.
NOTE1. WHEN CONNECTING OUTPUT DISTRIBUTION CABLES – START WITH INNER ROW FIRST.2. THE DC DISTRIBUTION GROUND/RETURN BUSBAR MUST BE CONNECTED VIA A SOLID
SINGLE-POINT GROUNDING LEAD TO THE MAIN BUILDING GROUND. REFER TO NEC,TABLE 250-122 FOR GROUNDING CONDUCTOR SIZE.
DETAIL D
ENTESC
USB
RJ45
USB
DETAIL A
ONE OR TWO AC CIRCUIT BREAKERS,NO LUGS NEEDED.
MARK CABLES A-L1, A-L2 AND A-L3 (B-L1, B-L2, B-L3)RECOMMENDED TORQUE 124 in-lbs (14 Nm)
DETAIL B (Fuse Option)
1.7
5"
1.7
5"
S U ITA B LE C A B LE LU GS W ITH H OLE D IA 1/2" (M 12)
TY P IC A L LU G TH OM A S & B E TTS TY P E 54282 (350kcmil)R E C OM ME N D E D TOR QU E 690-743 in-lbs (78-84 Nm)
DETAIL C (Fuse Option)
1.7
5"
1.5”
S U ITA B LE C A B LE LU GS W ITH H OLE D IA 1/2" (M 12)
TY P IC A L LU G TH OM A S & B E TTS TY P E 54282 (350kcmil)R E C OM ME N D E D TOR QU E 690-743 in-lbs (78-84 Nm)
NEGATIVE BUSBARSEE DETAIL ”C”
(LOAD)
POSITIVE BUSBARSEE DETAIL ”B”(RETURN)
INPUT GROUNDINGCONNECTIONLUGS 5/16" (M8)TYPICAL LUG THOMAS &BETTS TYPE 54109RECOMMENDED TORQUE
204-221 in-lbs (23-25 Nm)
factory wiring
AC IN AL1 L2 L3
AC IN BL1 L2 L3
GND
Stud
GND
Stud
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS
Spec. No: 582145500 Section 6037 Model: NetSure™ ITM Issue AC, April 8, 2013