SAM2 RMS and Hybrid Controller Product Manual V2.1.5
-
Upload
alex-moolman -
Category
Documents
-
view
360 -
download
17
Transcript of SAM2 RMS and Hybrid Controller Product Manual V2.1.5
PRODUCT MANAUAL Version 2.1.5
SAM2V3 RMS03 Product Manual V2.1.5 2
Table of contents 1. SAM2 RMS03 - Typical Netw ork System Diagram – Outdoor Type .................................................................................................3 2. SAM2 RMS03 - Typical Netw ork System Diagram – Indoor Type ....................................................................................................4 3. General.............................................................................................................................................................................................5 4. User LCD Display .............................................................................................................................................................................6
Menu Structure: .............................................................................................................................................................................6 1. Alarm Status: .............................................................................................................................................................................6 2. Environmental: ...........................................................................................................................................................................6 3. Electrical: ...................................................................................................................................................................................6 4. Generators:................................................................................................................................................................................6 5. Diagnostics: ...............................................................................................................................................................................6
5. SAM2 RMS03 – Controller ...............................................................................................................................................................9 6. SAM2 RMS03 – Cable Termination Unit.........................................................................................................................................10 7. ECS2 – Communications Controller ...............................................................................................................................................10 8. SAM2 RMS03 – Wiring Cable Kit ...................................................................................................................................................11 9. SAM2 RMS03 – Temperature Sensors ..........................................................................................................................................13 10. SAM2 RMS03 – Shelter Humidity/ Temperature Sensor ..............................................................................................................14 11. SAM2 RMS03 – Air Conditioner Control Sw itch ...........................................................................................................................14
Single Phase (1-port) Unit Electrical Specif ications: ....................................................................................................................15 Single Phase (2-port) Unit Electrical Specif ications: ....................................................................................................................15 Single Phase (3-port) Unit Electrical Specif ications: ....................................................................................................................15 Three Phase (2-port) Unit Electrical Specif ications:.....................................................................................................................15
12. SAM2 RMS03 – Reduced Energy Cooling System (REC)............................................................................................................17 Inlet Louver Assembly .................................................................................................................................................................17 Passive Pre-filter Cartridge..........................................................................................................................................................17 Outlet Louver and DC Fan Assembly ..........................................................................................................................................18 DC Ventilation Fan ......................................................................................................................................................................18
13. SAM2 RMS03 – Mains, Phase and Frequency Sensor ................................................................................................................19 14. SAM2 RMS03 – Utility Grid Sensor ..............................................................................................................................................20 15. SAM2 RMS03 – Battery Bank Voltage and Current Monitor .........................................................................................................21
Battery Current Probe (BCP) .......................................................................................................................................................22 Battery Bank Voltage Measurement ............................................................................................................................................22
16. SAM2 RMS03 – Hybrid Extension Module (V00)..........................................................................................................................23 Battery Bank Voltage Measurement ............................................................................................................................................24
17. SAM2 RMS03 – Hybrid Extension Module (V01)..........................................................................................................................25 Battery Bank Voltage Measurement ............................................................................................................................................25
18. SAM2 RMS03 – Navigation Light Sensor – AC Mains Type .........................................................................................................26 19. SAM2 RMS03 – Navigation Light Sensor – DC Supply Type .......................................................................................................27 20. SAM2 RMS03 – Utility Grid Management.....................................................................................................................................28 21. SAM2 RMS03 – Equipment Mains Monitoring Unit .......................................................................................................................29 22. SAM2 RMS03 – Generator Controller ..........................................................................................................................................30
A – SAM2 RMS03 Auxiliary Pow er and RS485 Comms: .............................................................................................................31 B – Fuel Sensor Auxiliary Power and RS485 Comms: ................................................................................................................31 C – Generator Monitored Alarm Inputs: .......................................................................................................................................31 D – Generator 12V Battery Monitoring Inputs: .............................................................................................................................31 E+F - Generator Start/Stop and Reset Control: ...........................................................................................................................31 Generator remote start/reset control sequence ...........................................................................................................................32 G - Generator Start/Stop test button: ...........................................................................................................................................33
23. SAM2 RMS03 – Generator Alarm Monitoring ...............................................................................................................................33 24. SAM2 RMS03 – Fuel Management ..............................................................................................................................................34
Fuel Sensor .................................................................................................................................................................................34 Fuel Tank Lid Sensor...................................................................................................................................................................35 Water in Diesel Sensor ................................................................................................................................................................36
25. SAM2 RMS03 – Hybrid Battery Management...............................................................................................................................36 Hybrid Fail Reasons ....................................................................................................................................................................37
26. SAM2 RMS03 – Rectif ier (SMPS) Alarm Monitoring.....................................................................................................................37 27. SAM2 RMS03 – Generic Sensors ................................................................................................................................................38
Intrusion Sensor ..........................................................................................................................................................................38 Movement Sensor .......................................................................................................................................................................38 Smoke Sensor .............................................................................................................................................................................39 Panic Sensor ...............................................................................................................................................................................39
28. SAM2 RMS03 – Mobile Phone SMS Commands .........................................................................................................................39 29. SAM2 RMS03 – RBS Alarm Outputs ............................................................................................................................................41
SAM2V3 RMS03 Product Manual V2.1.5 3
1. SAM2 RMS03 - Typical Network System Diagram – Outdoor Type
SAM2V3 RMS03 Product Manual V2.1.5 4
2. SAM2 RMS03 - Typical Network System Diagram – Indoor Type
SAM2V3 RMS03 Product Manual V2.1.5 5
3. General
A telecommunications service provider’s wealth is directly proportional to the effectiveness of his network. SAM2 RMS03 is a highly cost-effective cellular remote BTS monitoring system
and hybrid controller designed to assist the customer to maximize revenue from his netw ork assets. Near real-time alarm events and statistical data on pow er
distribution w ill help the customer to rectify malfunctions before they become service-affecting and alarm status reporting w ill allow the customer to respond to emergencies as they occur.
The SAM2 RMS03 is housed in an outdoor IP65 stainless steel (430 S/S) metal enclosure w ith dimensions 330x367x90mm (LxHxD)
Outdoor Housing:
The SAM2 RMS03, HTA BOQ typically comprises of the follow ing items (site type dependent):
The SAM2 RMS03 is designed w ith the emphasis on assisting the technician on site by reducing the amount of time spent w hen commissioning or maintaining the site. The system is also highly expandable and user friendly, making provision for
advanced features that include: » Near Real time remote management through GSM
(GPRS/SMS), Ethernet and E1 alarm and event management.
» Dual GSM redundancy, w ith primary and secondary link fallback selection including GPRS/SMS fallback.
» Generator monitoring and control.
» Generator bulk fuel tank capacity monitoring/fuel consumption.
» Generator bulk fuel tank residual w ater monitoring. » Commercial utility pow er management.
» Shared site DC pow er management. » Shared site AC pow er management. » Single or multiple Battery Bank DoD and SoC
management during Hybrid charge/discharge cycling
(voltage/current/Ah). » Battery cell voltage monitoring during Hybrid
charge/discharge cycling. » Monitoring of shelter temperature and humidity.
» Monitoring and control of air conditioning units. » Intelligent control/management of air conditioners in
conjunction w ith free cooling operation, in general or
during Hybrid battery discharge cycle. » Monitoring of Tow er Navigation Lights (both AC or DC) » Monitoring of various sensors, such as intruder,
movement, f lood, smoke etc.
» Important operating parameters (configuration data) / variables can be modif ied remotely.
» Remote f irmw are upgrading » On-line FIFO alarm log and daily value statistical registers.
» Management platform multi user password protection prevents unauthorized log-on, though secure user groups.
» Remote management via w eb interface.
SAM2V3 RMS03 Product Manual V2.1.5 6
4. User LCD Display
LCD alphanumeric display:
Default display Time (24 hour) and the active alarm count (number of active alarms at point in time)
Menu Structure: LCD display consists of the follow ing main menus:
1. Alarm Status 2. Environmental 3. Electrical 4. Generators
5. Diagnostic To enter any main menus from the default display, press the
dow n arrow key. Use the left and right arrow keys to scroll to the relevant menu to be view ed. Once found press the dow n arrow key to enter the sub menus pertaining to the main menu.
Any action to be performed, such as clearing of history alarms, w ould require pressing the center key (enter). To return from a submenu to the main menus, press the up arrow key.
Alternatively the LCD could be left in the submenu for a timeout period of f ive minutes, before it automatically returns to the default display.
1. Alarm Status:
» View Alarms » Reset Alarms The Alarm View sub menu indicates the current active alarm
inputs, alarm reference number and description. The Reset Alarms sub menu enables the user to reset all active alarm input states, thereby clearing alarm history. The
alarms are reset by pressing the enter button (center) 2. Environmental: » Temperatures
» Humidity » Aircon Stats » Sw ap Aircons » Reset Aircons
The Temperatures sub menu indicates the current temperature of aircon 1 vent, aircon 2 vent, aircon 3 vent, aircon 4 vent
Using the right or left arrow keys indicates the current temperature of shelter (room) versus outside The Humidity sub menu indicates the current relative humidity
reading. The Aircon Stats sub menu indicates the total operational run time of the selected air conditioner unit in hours. Use the left or
right arrow keys to select betw een air conditioner units. The Swap Aircons sub menu enables the user to perform a manual sw ap between the active running air conditioner and the
inactive air conditioner. By pressing the enter key, the air conditioners w ould be swapped over. Note how ever that the air conditioners w ill not sw ap over immediately, due to the pre-
programmed startup delay period. This period is normally set to 3 minutes as default. The Reset Aircon sub menu enables the user to reset the air
conditioning control sw itch. By pressing and holding the enter key the aircon settings w ould be restored to default. 3. Electrical:
» Battery Info » Energy Meter1-4 » Hybrid
» Mains Frequency The Battery Info sub menu indicates the total DC battery supply voltage, battery DC charge current or battery DC
discharge current. Use the left and right arrow keys to scroll betw een battery voltage or current readings. The Energy Meter1-4 sub menu indicates the available AC
mains credit reading in Kw H, total AC mains Kw H usage to date, AC mains voltage per phase, AC mains current per phase and AC mains pow er (watts) per phase. Use the left and right arrow keys to scroll between different meters (up to four meters
in total). The Hybrid sub menu indicates the Hybrid mode activation
period, the inhibit reasons, the suspend reasons and the failed reasons, should Hybrid mode not activate. Use the left and right arrow keys to scroll between the different menus.
The Mains Frequency sub menu indicates the AC mains frequency. 4. Generators:
» Fuel Level » Generator Battery » Run Times
The Fuel Level sub menu indicates the current fuel reading (liters) of the tank being monitored by the fuel sensor. Use the left and right arrow keys to select betw een tanks, if more than one tank monitored.
The Generator Battery sub menu indicates the generator 12V battery voltage level. Use the left and right arrow keys to select
betw een generators, if more than one battery monitored. The Run Times sub menu indicates the total run time of both generators, as w ell as the last service interval of both
generators. The left and right arrow keys are used to scroll betw een the different menus. 5. Diagnostics:
» View Inputs » Test Peripherals » Test BTS Alarms » Test GSM Modem
The View Inputs sub menu indicates all alarm inputs, current state and input description. Use the left and right arrow keys to
select betw een different alarm inputs. The Test Peripheral sub menu allow s the user to select a specif ic alarm input number plus the ability to activate or
deactivate the selected input. Use the enter button to change alarm state. (this sub menu places the SAM2 RMS03 controller in a test mode – press the up arrow key to exit test or alternatively the LCD could be left in the submenu for a timeout
period of f ive minutes, before it automatically returns to the default display, thereby canceling any tests). The Test BTS Alarms sub menu allow s the user to select a
specif ic RBS alarm output number plus the ability to activate or deactivate the selected output. Use the enter button to change alarm state. (this sub menu places the SAM2 RMS03 controller
in a test mode – press the up arrow key to exit test or alternatively the LCD could be left in the submenu for a timeout period of f ive minutes, before it automatically returns to the default display, thereby canceling any tests).
SAM2V3 RMS03 Product Manual V2.1.5 7
Test GSM Modem sub menu: » Signal » Message Format » Last SMS Received
» Last SMS Sent » ESM Server Test » Reset Modem
The Signal sub menu indicates the netw ork signal strength and modem operation
The Message Format sub menu indicates the GSM coding standard – Text or PDU The Last SMS Received sub menu indicates the last
successful SMS message received by the SAM2 RMS03 controller The Last SMS Sent sub menu indicates the last successful
SMS message sent by the SAM2 RMS03 controller The ESM Server Test sub menu executes a SMS test to the management server. By pressing the enter key the test SMS is
sent. Should the server respond, a “working” response should be received. Should the server not respond, a “failed” response should be received.
The Reset Modem sub menu executes a software reset to the SAM2 RMS03 onboard modem. The modem is reset by pressing the enter key.
SAM2V3 RMS03 Product Manual V2.1.5 8
SAM2V3 Product Manual V2.1.4 9
5. SAM2 RMS03 – Controller
The SAM2 RMS03 consists of a series of PCB’s w ith multiple inputs/outputs and communications ports. A combination of these and the interaction of each determine the operation and
functionality of the unit. SAM2 Controller minimum electrical specif ications:
ECS2 Controller minimum electrical specif ications:
Outdoor Type:
The SAM2 RMS03 controller comes in either an indoor or outdoor configuration. In both cased the PCB layout is identical
(BOQ dependent) besides the mounting of the LCD on the outer casing of the indoor type housing. The SAM2 RMS03 controller consists of multiple pluggable
and interconnected PCB modules all performing a specif ic function, as follow s: A – SAM2 Controller (CTL).
This module is the heart of the system and contains all control logic to perform different control and monitoring functions according to predefined user configurable parameters.
B – SAM2 Cable Termination Unit (CTU03) This module is used to terminate all alarm monitoring and control connections as w ell as technicians maintenance, thought LCD or remote management port (serial or USB).
» All generic alarm/control connections are done through dedicated clearly labeled screw terminal connections.
» Generator alarm/control and fuel management in terms of
fuel sensor, w ater sensor and tank lid sensor are connected through dedicated clearly labeled SubD 9-pin female connector.
» External BTS/RBS alarm outputs are connected though
dedicated clearly labeled SubD 37-pin female connector. » LDC control through dedicated multipurpose sw itch
(outdoor unit) or keypad (indoor unit). » Remote management through dedicated USB or serial
port. C – ECS2 Communications Controller This module is used to provide pass through communications
to various secondary devices on site. Default port configuration: » 2x RS485 Ports (one isolated and one non-isolated)
» 3x RS232 Ports (one limited and tw o full f low control) » 2x USB Ports (one host and one device port) » 2x Ethernet Ports (one host and one device port) Optional expansion bays for Ethernet, RS232 and E1 modules.
D – Processor Module ARM9 processor with optional SD memory card expansion slot. Processor responsible for alarm logging and statistical
data management (storage in off -line mode) as w ell as pass through port management.
SAM2V3 Product Manual V2.1.4 10
E – Dual GSM Modem (GPRS/SMS) The GSM modem module is used to provide a primary and secondary fall-back communications connection between the SAM2 RMS03 controller and the ESM management platform.
Internal logic manages the availability and sw itching between primary and secondary GSM netw orks and the availability of GPRS versus SMS. (primary alw ays being the preferred communications path)
6. SAM2 RMS03 – Cable Termination Unit The SAM2 RMS03 controller sensor alarm and control w iring
terminations are performed using the cable termination unit (CTU03). The CTU03 has multiple alarm inputs and control outputs that are interconnected w ith the RMS03 controller to form a complete and fully functional system.
The CTU03 consists of the follow ing connections that would be described in detail w ithin this manual: A – Internal factory interconnection between CTU03 and SAM2 CTL for RBS external alarm outputs.
B – Internal factory interconnection between CTU03 and SAM2 CTL for all alarm and control functions. C – External RBS alarm output connection port. D – DG alarm/control communications and auxiliary pow er
connection port w ith RMS03 generator controller unit. E – All alarms, sensors, auxiliary DC supply voltage and control signal w iring terminations. F – HEM (Hybrid Extension Module) w iring terminations. For
monitoring of additional battery banks/DC Load or solar or w ind supply voltage and current. G – LCD Display for view ing alarm status, statistical
information and diagnostic testing. H – Hybrid Active LED indication. Indicates w hen the battery discharge cycle has been activated. I – Multipurpose toggle sw itch for navigation through LCD
display menus. J – Internal factory interconnection between CTU03 and SAM2 CTL for serial diagnostics and configuration. K – USB Serial Port. Technician diagnostic/configuration port.
7. ECS2 – Communications Controller The ECS2 communications controller is used to provide
communications to the netw ork management system, in the form of GSM, Ethernet or E1 as w ell as pass through communications to various secondary devices on site. The ECS2 pow erful ARM9 processor, with optional SD
memory card, is responsible for alarm logging and statistical data management, especially in off-line mode as w ell as pass through port management (connectivity to site devices from management platform).
The ECS2 consists of the follow ing modules and connections:
A – E1 Management Port. Physical E1 termination port should remote management, from centralized server be required using an E1 timeslot or multiple timeslots. This option is currently not used during HTA deployment.
B – 2x Full RS232 Device Ports (modem control). Serial device management ports, such as rectif ier or generator. These ports are currently not used during HTA deployment. C – Standard RS232 Device Port. Serial device management
port, factory interconnected to SAM2 CTL controller. D – Heavy duty relay. Intended for access control lock failsafe override control. This option is currently not used during HTA deployment.
E – Isolated RS485 Device Port. Serial device management port, such as utility grid meter or generator. This port is currently not used during HTA deployment.
F – Non-isolated RS485 Device Port. Serial device management port, factory interconnected to Access Control controller. This option is currently not used during HTA deployment.
G – DC Supply Input. Factory interconnected to SAM2 CTL controller, for common supply input to both modules. H – Optional E1 Management Module. Necessary should remote management, from centralized server be required
using an E1 timeslot or multiple timeslots. I – Optional RS232 Device Port Module. Additional 2x full RS232 device ports (modem control), should it be required. J – Optional Pow er Supply Module. Auxiliary pow er supply
module should it be required for pow ering auxiliary sensors, such as CCTV cameras. K – Processor Module. ECS2 ARM9 processor module w ith
Linux operating system. L – GSM Module. Necessary should remote management, from centralized server be required using a GPRS/SMS type or 3G/GPRS/SMS type netw ork connection. In case of HTA a
GPRS/SMS dual SIM modem is used. M – USB Device Port. USB device management port, such as rectif ier or generator. This port is currently not used during HTA deployment.
N – USB Host Port. Technician diagnostic/configuration port. O – Serial Debug Port. Engineering Debug port. P – Ethernet Device Port. Ethernet device management port, such as rectif ier, generator or fuel cell. This port is currently
not used during HTA deployment. Q – Ethernet Management Port. Physical Ethernet termination port should remote management, from centralized server be
required using an Ethernet connection. This option is currently not used during HTA deployment. R – Optional Ethernet Device Port Module. Additional 2x Ethernet 10/100 Base T device ports, should it be required.
SAM2V3 Product Manual V2.1.4 11
8. SAM2 RMS03 – Wiring Cable Kit
The SAM2 RMS03 system is supplied w ith a custom made w iring kit according to customer and application requirements.
The SAM2 RMS03 Indoor and Outdoor default w iring cable kit consists of the following items:
SAM2 RMS03 Project samples:
Wiring Cable Kit:
The above cable w iring kit is supplied w ith the SAM2 RMS03 controller according to the indicated lengths and quantities or
as specif ied by customer requirements. Item 1:
Aircon Control Sw itch (ACS) Cable – default 8m
The ACS cable is used to connect the aircon control sw itch to the SAM2 RMS03 controller for managing the activation/deactivation activity of the air conditioner units.
Items 2+3: Aircon 1 (AC1) and Aircon 2 (AC2) Temperature Sensor Cables – default 8m each
The AC1 and AC2 temperature sensor cables are used to measure the analogue temperature of the applicable air conditioner vent. This is to ensure the active air conditioner
unit is providing the required cooling capacity. Item 4: Battery Bank Temperature Sensor Cable – default 9m
The battery bank temperature sensor cable is used to measure the analogue temperature of the battery bank. This temperature could be used to allow for compensation during battery recharge cycles or activation of additional cooling
requirements. Item 5: Mains/Phase and Frequency (MPF) Sensor Cable – default
11m
The MPF sensor cable is used to connect the MPF sensor to the SAM2 RMS03 controller for monitoring of mains/phase and frequency supply to the rectif ier.
Item 6: Navigation Light (AWM) Sensor Cable – default 11m
The AWM sensor cable is used to connect the AWM sensor to the SAM2 RMS03 controller for monitoring of tow er navigation
lights. Item 7: Utility Sensor Cable (ACM) – default 3m
SAM2V3 Product Manual V2.1.4 12
The Utility sensor cable is used to connect the ACM sensor to the SAM2 RMS03 DG controller, for monitoring the presence of utility grid supply.
Item 8: Humidity (HUM) Sensor Cable – default 11m
The HUM sensor cable is used on indoor shelter type sites, to monitor the shelter indoor humidity/temperature and trigger a DG start command, in order to activate the aircons, w hen a pre-defined high humidity and/or temperature threshold is
exceeded. The HUM sensor could be replaced w ith a standard temperature sensor only, w hich would result in a DG start trigger based upon temperature only.
Item 9: RBS Alarm Input Cable – default 8m (indoor type) and 12m
(outdoor type)
The RBS alarm input cable is used to w ire the monitored alarms from the SAM2 RMS03 controller to the RBS external
alarm inputs. Item 10: DG Alarm/Control Cable – default 20m
The DG alarm/control cable is used to provide a
communications and auxiliary pow er connection between the SAM2 RMS03 controller and SAM2 RMS03 generator controller unit.
Item 11: Fuel Tank Sensor Cable – default 10m
The fuel tank sensor cable is used to w ire all the sensors related to fuel management, e.g. fuel probe, w ater sensor and fuel tank lid sw itch to the SAM2 RMS03 generator controller. This cable is only required should the distance betw een the
fuel tanks and ATS, w here SAM2 RMS03 generator controller is mounted, exceeds the sensor cable lengths, for extension purposes.
Item 12: Universal Alarm Cable – default 45m (indoor type) and 15m (outdoor type)
The universal alarm cable is used to w ire all optional universal type sensors, such as the shelter Door sw itch, Smoke sensor, Movement sensor, Battery current sensor (BCP) and DG door
sw itches. Item 13: DC Pow er Cable – default 8m (indoor type) and 12m (outdoor
type)
The DC pow er cable is used to w ire the DC supply voltage from the battery bank to the SAM2 RMS03 controller in order to pow er the unit. (ensure this connection is directly from the
battery bank (priority MCB feed) and not via a DC/DC inverter)
SAM2V3 Product Manual V2.1.4 13
Items 14: Accessories – Cable termination box, glands and rivets
The termination box is an optional item used to terminate the fuel tank sensor, w ater sensor and fuel tank lid sw itch to the
fuel tank sensor cable, connected to the SAM2 RMS03 generator controller. This termination box is only required should the sensor cable lengths not reach the SAM2 RMS03
generator controller unit. Items 15: Utility Grid Meter Communications Cable – default 10m
The utility grid meter communications cable is used to connect the utility grid meter to the SAM2 RMS03 generator controller for monitoring/management of utility grid statistical data.
9. SAM2 RMS03 – Temperature Sensors The SAM2 RMS03 controller through the cable termination unit makes provision for the follow ing temperature sensors in order
to perform various cooling related functions. » Battery Temperature Sensor » AC1 Temperature Sensor » AC2 Temperature Sensor
» AC3 Temperature Sensor » AC4 or Shelter Temperature Sensor
The indoor shelter temperature sensor is used to monitor the
shelter ambient temperature. Various configurable temperature setpoints are used to perform the follow ing functions: » High temperature alarm
» Very high temperature alarm » DG start command during battery discharge cycle » Shelter air conditioner and free cooling ventilation system
control
The battery temperature sensor is used to monitor the battery bank or battery cabinet ambient temperature. The monitored battery temperatures are used to perform the follow ing
functions: » Battery cabinet forced cooling ventilation system control » Battery charge temperature compensation
The AC1-4 temperature sensors are used to monitor the air conditioner vent temperature of each air conditioner unit respectively. The monitored vent temperatures are used to
perform the follow ing functions: » Measure cooling capacity of active air conditioner unit » Indicate a cooling fault based upon pre-defined
operational period, versus measured temperature.
(Blue/White and Orange leads used – measure +/- 4.7ohms
betw een leads, when tested) Typical Sensor Location: Shelter Temperature Sensor
» The shelter temperature sensor is placed in the shelter roof, tow ards the door. Ensure the sensor is not located near any heat or cooling generating sources, such as
shelter lights or air condition vents. Battery Temperature Sensor » The battery temperature sensor is placed betw een the
battery cells, center of the total battery bank. Air Conditioner Vent Temperature Sensor » The air conditioner vent temperature sensor is placed in
the air conditioner vent section (portion w here the cold air blow s out). Ensure it is adequately secured.
Installation Steps:
SAM2V3 Product Manual V2.1.4 14
» Connect Shelter temperature sensor to the SAM2 RMS03
cable termination unit T4 (blue/white) and GD (orange) connection of “Temp Probes” screw terminal connection.
» Connect Battery temperature sensor to the SAM2 RMS03 cable termination unit BT (blue/white) and GD (orange) connection of “Temp Probes” screw terminal connection.
» Connect AC1 vent temperature sensor to the SAM2
RMS03 cable termination unit T1 (blue/white) and GD (orange) connection of “Aircon Probes” screw terminal connection.
» Connect AC2 vent temperature sensor to the SAM2 RMS03 cable termination unit T2 (blue/white) and GD (orange) connection of “Aircon Probes” screw terminal connection.
» Connect AC3 vent temperature sensor to the SAM2 RMS03 cable termination unit T3 (blue/white) and GD (orange) connection of “Aircon Probes” screw terminal connection.
» Connect AC4 vent temperature sensor to the SAM2 RMS03 cable termination unit T4 (blue/white) and GD (orange) connection of “Temp Probes” screw terminal connection.
(Input T4 is used for either shelter temperature sensor or AC4 vent temperature sensor. Should 4x aircon vent temperature sensors be required, the shelter reference
temperature w ill have to be monitored by using a humidity/temperature sensor – refer to section 9)
Note:
» Should the shelter temperature sensor not be functional, due to a faulty cable or sensor, the SAM2 RMS03 system w ill indicate a Temperature Probe alarm. (only applicable to shelter temperature sensor)
» A temperature reading of –12C or more refers to a disconnected temperature sensor lead
» A temperature reading of +110C or more, refers to a short circuit sensor lead
10. SAM2 RMS03 – Shelter Humidity/ Temperature Sensor Optionally the Shelter temperature sensor could be replaced w ith a combination Humidity and Temperature sensor (RTH).
Typical Sensor Location: Shelter RTH Sensor » The shelter RTH sensor is normally placed in the shelter
roof, tow ards the door. Ensure the sensor is not located
near any heat or cooling generating sources, such as shelter lights or air condition vents.
Installation Steps:
» Connect Shelter RTH sensor to the SAM2 RMS03 cable termination unit HP (orange) and GD (blue) connection of “Temp Probes” screw terminal connection.
» Ensure that the cable w ith the side marked “Humidity
Sensor” is plugged into the RJ9 socket of the RTH sensor (located inside the sensor).
Note:
» Should the RTH sensor not be functional, due to a faulty cable or sensor, the SAM2 RMS03 system w ill indicate a Humidity Sensor alarm.
» During a humidity sensor failure, as mentioned above, the SAM2 RMS03 assumes a high temperature condition (failsafe), in order to start the generator to ensure the air conditioners are activated.
One of the main purposes of the shelter temperature sensor or RTH (humidity/temperature) sensor combination, is to monitor the shelter temperature threshold at w hich to send a generator
start command (in order to activate the air conditioners), should the configured regulate temperature threshold be exceeded. The default temperature at w hich the generator
start command is activated, is 35C. (user configurable)
11. SAM2 RMS03 – Air Conditioner Control Switch The purpose of the Air Conditioner Control Sw itch (ACS) is to
intelligently control the operation of the air conditioner units in conjunction w ith the SAM2 RMS03 controller unit.
The ACS w ould intelligently control the activation and de-
activation of single or multiple air conditioner units, based upon the monitored shelter temperatures. (up to four air conditioner units could be controlled)
Should the mains supply voltage drop below a pre-defined threshold (220Vac-15% = 187Vac), the ACS w ould cut the mains supply voltage to the air conditioners as a protective measure, w ith an associated alarm indication.
The Air Conditioner Control Sw itch could be used to drive any of the follow ing air conditioning types:
» Single phase (1-port) unit for driving a single air conditioning unit up to 24 000 BTU
» Single phase (2-port) unit for driving 2 independent air conditioning units up to 24 000 BTU
» Single phase (3-port) unit for driving 3 independent air conditioning units up to 24 000 BTU
» Three phase (2-port) unit for driving up to 2 independent air conditioning units of up to 50 000 BTU
» (bigger sw itching capacity rated ACS units available subject to sw itching contactors used)
SAM2V3 Product Manual V2.1.4 15
Single Phase (1-port) Unit Electrical Specifications:
Single Phase (2-port) Unit Electrical Specifications:
Single Phase (3-port) Unit Electrical Specifications:
Three Phase (2-port) Unit Electrical Specifications:
SAM2V3 Product Manual V2.1.4 16
Installation Steps:
» Ensure the Air Conditioner Control Sw itch (ACS) Cable is
plugged into the Aircon IDC terminal of the SAM2 RMS03 controller and the 8-w ay screw terminal on the Air
Conditioner Control Sw itch.
» The follow ing connections needs to be done on the air
conditioner control sw itch:
A – ACS control cable from SAM2 RMS03 controller. B – Mains Input (Live and Neutral) connection for AC1.
C – Mains Input (Live and Neutral) connection for AC2.
D – Mains Input (Earth) connection for AC1. E – Mains Input (Earth) connection for AC2. F – Mains control output for AC1 via industrial 3-pin socket.
G – Mains control output for AC2 via industrial 3-pin socket. (AC1 is located on the left side and AC2 is located on the right side)
Note: » AC1 is activated by default (failsafe), should the ACS
control cable from the SAM2 RMS03 be unplugged or the
DC supply voltage to the SAM2 RMS03 sw itched off. » A single ACS cable is used to control up to three air
condition units in a normal cyclic or piggy back
application. Cyclic – each air conditioner runs for the pre-defined
configurable time period before swapping to the standby unit. (during a configurable high temperature setting, tw o air conditioners run
simultaneously) Piggy Back – air conditioner one and tw o cycle
according to pre-defined configurable time period how ever air conditioner three runs permanently. (during a configurable high temperature setting, all
three air conditioners run simultaneously)
» A special dual ACS t-cable is used to control up to four air condition units making use of tw o Air Conditioner Control Sw itch units in a normal cyclic or co-location application. Cyclic – each air conditioner runs for the pre-defined
configurable time period before swapping to the
next, alw ays two at a time. (during a configurable high temperature set point, all four air conditioners run simultaneously)
Co-location - The air conditioner units are cycled
based upon a pre-defined configurable time period. AC1 and AC3 runs together and AC2 and AC4 runs together. (during a configurable high temperature
setting, all four air conditioners run simultaneously)
SAM2V3 Product Manual V2.1.4 17
12. SAM2 RMS03 – Reduced Energy Cooling System (REC)
The reduced energy cooling ventilation system (also know n as free cooling ventilation system) is an optional item part of the SAM2 RMS03 system applicable to indoor shelter type sites.
The purpose of the REC ventilation system is threefold: » Reduction in operational costs by reducing total energy
consumption of the indoor shelter sites by up to 85% or
more. » To provide adequate ventilation during hybrid battery
discharge cycles, when the site is pow ered from the standby batteries and the generator and air conditioner
units are sw itched off. » Under extreme conditions w hen the indoor shelter
temperature is abnormally high, to assist w ith the cooling process if the air conditioner units cannot adequately
regulate the shelter temperature. The REC ventilation system operates on the principal of regulating the shelter inside temperature according to a pre-
defined user configurable threshold, relative to the outside ambient temperature. Thus if the regulated temperature is set to 30 degrees for example, provided the outside ambient
temperature is low er than the inside shelter temperature, the ventilation system w ill regulate the shelter temperature using the ventilation fan at variable speeds to control the temperature and not the air conditioner units. Only if the
ventilation fan cannot maintain the regulated inside shelter temperature threshold or if the outside ambient temperature is higher than the inside shelter temperature, w ould the air conditioner units be activated.
The SAM2 RMS03 free cooling ventilation system consists of the follow ing items: (all metal parts made from 304 stainless steel):
» Inlet Louver Assembly » Passive Pre-filter Cartridge » Outlet Louver and DC Fan Assembly
Inlet Louver Assembly The inlet louver grill assembly should be f itted to the bottom center of the shelter door, not to obstruct the door mechanism
nor the doorstopper. The inlet louver incorporates an angled grille that prevents the ingress of moisture as w ell as a mesh air f ilter to prevent the ingress of insects.
Installation Steps:
» Make use of the internal dimensions (+5mm per side) to act as a template to mark the inner rectangle of the area to be cut out, using a suitable marker, starting on the outer side of the shelter door.
» Using the markings made prior, drill through both outer and inner sheets of the shelter w all, on all four corners. Make sure to use the outer holes in terms of alignment and orientation for the inner holes.
» Use a ruler and suitable marker to join the previously drilled holes, on the inner side of the shelter w all.
» By using a suitable jigsaw , cut through both w alls of the
shelter separately. Remove sharp edgings w ith a f lat f ile. » Insert the inlet louver assembly from the outside w ith grill
angled dow nwards. Ensure it is completely level before marking the holes to be drilled for rivet mounting. Ensure
to drill these holes through the outer w all only. » Before drilling the rivet holes, remove the inlet louver
assembly to prevent any coating (paint) damage. » Rivet the inlet louver assembly to the outside of the
shelter door. » Use the inner louver connection piece to mark the holes
to be drilled for rivet mounting. Rivet the inner louver connection piece to the inside of the shelter door.
» Insert the removable f ilter media panel (pre-f ilter cartridge) upon completion
» Ensure to seal all edging w ith white polyurethane sealer
Passive Pre-filter Cartridge The inlet louver assembly includes a passive pre-f ilter cartridge. The main purpose of the pre-f ilter is to f ilter dust
particles up to 0.01 micron. The pre-f ilter cartridge f its to the inside of the inlet louver grill assembly. The pre-f ilter cartridge is removed from the inside of
the shelter, for maintenance cleaning or replacement.
Installation Steps:
» Ensure to f it the pre-f ilter cartridge in the direction of airf low as marked.
» The design of the pre-f ilter media provides the ability for the f ilter to be cleaned by rinsing w ith water or simple
replacement.
SAM2V3 Product Manual V2.1.4 18
Outlet Louver and DC Fan Assembly The outlet louver assembly should be f itted to the top left or right hand corner of the air conditioner units, just behind the radio base station equipment, should space permit w ith no
obstruction to airf low . (normally the point w here the most heat is generated) The outlet louver assembly unit incorporates an angled grille
that prevents the ingress of moisture, a low airf low pressure drop grille that further prevents the ingress of moisture, but also keeps cooler air from escaping as w ell as a mesh air f ilter
to prevent the ingress of insects.
Installation Steps:
» Make use of the inner mounting plate to act as a template (+5mm per side). Mark the inner rectangle of the area to be cut out, using a suitable marker, starting on the outer side of the shelter w all.
» Using the markings made prior, drill through both outer and inner sheets of the shelter w all, on all four corners. Make sure to use the outer holes in terms of alignment and orientation for the inner holes.
» Use a ruler and suitable marker to join the previously drilled holes, on the inner side of the shelter w all.
» By using a suitable jigsaw , cut through both w alls of the shelter separately. Remove sharp edgings w ith a f lat f ile.
» The outer grill assembly, DC ventilation fan and low airf low pressure drop grille is already interconnected to form one unit upon delivery. Insert the assembled unit from the outside w ith grill angled dow nwards. View the
depth required for suitable mounting. Remove the unit from the shelter w all and f it the outer mounting plate to the low airf low pressure drop grille, using the rivets
provided according to the depth measured » Insert the assembled unit from the outside w ith the grill
angled dow nwards. Ensure it is completely level before
marking the holes to be drilled for rivet mounting. Ensure to drill these holes through the outer w all only.
» Before drilling the rivet holes, remove the outlet louver assembly to prevent any coating (paint)
damage. » Rivet the drop grille assembled unit to the outside of the
shelter w all » Use the inner mounting plate as a drill template on the
inside w all. » Rivet the inner mounting plate to the inside of the shelter
w all.
» Ensure to seal all edging w ith white polyurethane sealer. DC Ventilation Fan The outlet louver assembly is manufactured in such a w ay to
accommodate a 200mm or 250mm ventilation fan and brush less motor. (default 250mm) The fan housing is made of aluminum die-cast rotor w ith metal
impeller, stove-enameled in black. During operation air blow s over the struts with rotational direction being CCW as seen from rotor side.
The fan could be pow ered from either 24Vdc (16-28Vdc) or 48Vdc (36Vdc-57Vdc).
The fan is supplied w ith a 10 meter electrical cord and has the follow ing connections: Brow n = + (positive) Blue = - (negative)
Yellow /Green = Speed Control Black = Taco Out (RPM) Installation Steps:
» Connect the FAN DC supply voltage to the SAM2 RMS03
controller unit. Ensure to use the same supply voltage that w as used to power the SAM2 RMS03, due to earth
reference potential. Make sure to use a 5Amp breaker for a single fan application and a 10Amp breaker for a dual fan application. (via terminal strip A)
» Connect the DC supply to the fan by making the follow ing
connections:
Fan Brow n lead (+) SAM2 RMS03 controller Yellow lead (+) (via terminal strip A)
Fan Blue lead (-) SAM2 RMS03 controller Black lead (-) (via terminal strip A)
» Connect the Fan speed control by making the follow ing connection:
Fan Yellow /Green lead SAM2 RMS03 controller Blue lead (via terminal strip A)
SAM2V3 Product Manual V2.1.4 19
» Optionally, connect the Fan RPM (Tacho) by making the follow ing connection:
Fan Black lead SAM2 RMS03 controller Violet lead (via terminal strip A)
Note:
» Take note of the follow ing setpoints during (REC)/free
cooling operation: (Refer to SAM2 RMS03 ECT Manual for more detailed information)
Emergency Fan On Setpoint (A):
Shelter temperature at w hich DC ventilation fan w ould be activated at full speed together w ith both air conditioner unit. (normally w hen air conditioners are not capable of regulating shelter temperature)
Room Temp Regulate Setpoint (B):
Refers to the temperature setpoint at w hich the shelter must be regulated w hen using the DC ventilation fan instead of the air conditioner units.
(pressing the “w iz” button activates the software w izard which automatically adjusts all REC/aircon settings to most optimal based upon configured regulate temperature)
Room Temp Regulate Hysteresis (C):
The temperature hysteresis value below the regulate setpoint (B) at w hich the air conditioner units w ill be sw itched off and the DC ventilation fan used for cooling.
Fan Cooling Enable Temperature Differential (D):
Minimum temperature value that the outside temperature must be low er than the shelter temperature for the DC ventilation fan to operate. The fan w ill start full speed (max RPM) and
decrease in speed as the temperature differential decreases to zero.
Aircon Humidity On Setpoint (E):
Shelter relative humidity at w hich aircons would be activated to regulate humidity below this setpoint.
Aircon Humidity Off Setpoint (F):
Shelter relative humidity at w hich aircon would be stopped and DC ventilation fan activated for cooling purposes.
Fan to Aircon Sw itchover Temp (G): Shelter temperature setpoint at w hich air conditioner
units w ould be started to take over from the DC ventilation fan.
DC Fan REC Enable Humidity Diff (H):
Shelter relative humidity hysteresis value below the
aircon on setpoint (E) at w hich the air conditioner units w ill be sw itched off and the DC ventilation fan used for cooling.
Hybrid Aircon Run Time (I):
Minimum time period that air conditioner units w ould
be activated w hen Hybrid discharge cycle fails due to high temperature (REC cooling deactivated due to high temperature).
Aircon Service Interval (J):
Run hour interval at w hich air conditioner units are
due for servicing Fan Speed Control (K):
When selected, enables DC fan variable speed
control based upon the difference between shelter and outside temperature.
DC Fan REC Enable (L):
When selected, enables DC ventilation fan reduced energy (free) cooling functionality.
13. SAM2 RMS03 – Mains, Phase and
Frequency Sensor The SAM2 RMS03 controller through the cable termination unit
makes use of a sensor type Mains, Phase and Frequency monitoring unit (MPF) to accurately detect any mains or phase related failures. The unit also provides an analogue indication of the mains supply frequency.
The purpose of the MPF sensor is to detect the presence or absence of mains supply from the utility supplier or generator output (mains load supply into the radio base station).
Thus, should the utility provider provide the mains supply source, the MPF monitor w ould detect if mains is present on all phases as w ell as the frequency of the supply.
Should the generator provide the mains supply, the MPF monitor w ould detect whether the generator is providing a mains supply output on all phases as w ell as the frequency of the supply.
The mains/phase indications are used by the SAM2 RMS03 controller to determine if the mains supply (utility or generator)
is pow ering the radio base station, thus confirming ATS contactor operation. The MPF does not distinguish betw een utility or generator supply, but merely if the load supply to the radio base station is
w ithin operational limits. Failure of both the utility supply and/or generator to provide an AC load supply w ould cause the SAM2 RMS03 controller to report the relevant mains and/or phase related alarms. The
mains, phase and frequency alarms are masked for a period of f ive minutes (default) to provide ample time betw een utility and generator contactor switchover before activation of any alarms. (alarm mask period to avoid any unw anted alarms during
generator start/stop sequence) The MPF sensor is mounted in the rectif ier AC distribution
section (after the AVR if f itted), normally located w ithin the BTS shelter. The MPF w ould indicate an active alarm state should the input voltage of any phase drop below 187VAC (220VAC-15%)
SAM2V3 Product Manual V2.1.4 20
MPF Unit Electrical Specif ications:
Installation Steps: Sensor cable pinouts:
» Connect MPF sensor cable to the SAM2 RMS03 cable
termination unit +12v (orange/w hite), MF (blue/w hite), PF (orange) and GD/-12v (blue) connection of “MPF Unit” screw terminal connection. MF refers to Mains/Frequency alarms and PF refers to Phase Fail alarm.
» Ensure that the cable w ith the side marked “MPF Sensor” is plugged into the RJ9 socket of the MPF sensor.
» Wire the mains live supply for phase 1,2 and 3 by looping a connection from the output of the mains supply load
MCB to the MPF phase 1,2 and 3 live inputs (ensure mains supply is monitored after the load MCB in case of tripping)
» Wire the mains neutral by looping a connection from the neutral bar to the neutral input of the MPF sensor.
Note: » Should the mains voltage per phase be above 187Vac,
the red LED corresponding to the input w ill be active (on). » Should the voltage of any phase drop below 187Vac, the
corresponding LED w ould be off and a phase alarm generated.
» All mains, phase and frequency alarms are masked for a period of f ive minutes upon activation of a utility grid
failure alarm. This ensures adequate time for all contactors to switch over between utility and generator load supply (generator starting). Should the batteries be
fully charged at this moment, hybrid battery discharge w ould be activated and all mains, phase and frequency alarms masked for the entire duration of the battery discharge cycle.
» All mains, phase and frequency alarms are instant w hen utility grid supply is present. Thus alarms w ill be activated w hen utility grid supply is present, how ever no mains or phase voltage detected by the MPF sensor.
» During installation testing phase, refer to the SAM2 RMS03 craft terminal software application (SAM2 RMS03 ECT) or LCD display to verify true unmasked alarm status “Diagnostics → View Inputs”
14. SAM2 RMS03 – Utility Grid Sensor The SAM2 RMS03 controller through the cable termination unit and generator controller makes use of an optional AC Mains sensor (ACM) to accurately detect any utility grid failures.
The ACM sensor w ould not be required should the utility grid supply already be monitored by the ATS/AMF and an alarm output provided accordingly or should the site have no utility grid supply.
The ACM w ould indicate an active alarm state should the input voltage of the utility mains supply, per phase, drop below
187VAC (220VAC-15%)
ACM Unit Electrical Specif ications:
SAM2V3 Product Manual V2.1.4 21
The ACM sensor could be used in tw o applications: » To monitor the AC pow er distribution through the ATS, to
ensure correct contactor operation (default). Input one is used to monitor the utility grid relay contactor, input tw o to
monitor the load output contactor and input three the DG relay contactor. The corresponding LED w ould be off, should the input voltage drop below 187Vac and the applicable alarm output activated.
» To monitor each phase of the utility grid supply and provide an alarm output once any phase voltage drops below 187Vac, the corresponding LED w ould be off and a
phase alarm generated for the relevant phase. Installation Steps:
Sensor cable pinouts:
» The ACM sensor is located w ithin the generator or ATS in close proximity w ith the AMF panel.
» Make use of the ACM sensor cable (4-pair open ended to
open ended, 3m, part of w iring cable kit).
» Connect the one end of the 4-pair cable to the ACM sensor as follow s (top output terminals):
Blue – Positive Supply – terminal 5 (+12v)
Blue/w hite – Negative Supply – terminal 1 (-12Vdc)
Orange – Utility AC Mains Fail Alarm – terminal 2
Orange/w hite – Utility AC Mains Fail Ground
Reference – terminal 1 Green – Utility on Load Alarm – terminal 3
Green/w hite – Utility on Load Ground Reference –
terminal 1 Brow n – DG on Load Alarm – terminal 4
Brow n/white – DG on Load Ground Reference –
terminal 1
» Wire the other end of the 4-pair ACM sensor cable to the SAM2 RMS03 generator controller (DGC), “SAM2 RS485” terminal as follow s: Blue – Positive Supply – terminal P+ (+12v)
Blue/w hite – Negative Supply – terminal GD
(-12Vdc)
» Wire the remaining pairs of the 4-pair ACM sensor cable to the SAM2 RMS03 generator controller (DGC), “DG Alarm Inputs” terminal as follow s: Orange – Utility AC Mains Fail Alarm – terminal 1
Orange/w hite – Utility AC Mains Fail Ground
Reference – terminal GD
Green – Utility on Load Alarm – terminal 2
Green/w hite – Utility on Load Ground Reference –
terminal GD Brow n – DG on Load Alarm – terminal 3
Brow n/white – DG on Load Ground Reference –
terminal GD » Make use of 1.5mm pow er panel wire (red and black) to
w ire the relevant mains supply inputs to the ACM sensor as follow s (bottom input terminals): Red – Utility Grid Mains Contactor relay (Live)
terminal 1 Black – Utility Grid Mains Contactor relay (Neutral)
terminal 2
Red – Utility Load Output Contactor relay (Live)
terminal 3 Black – Utility Load Output Contactor relay (Neutral)
terminal 4 Red – Generator Load Contactor relay (Live)
terminal 5 Black – Generator Load Contactor relay (Neutral)
terminal 6
(note that the above mains w iring is to the contractor controlling relay and not the actual contactor itself)
Note:
» The ACM sensor is optional and only required on utility grid sites.
15. SAM2 RMS03 – Battery Bank Voltage and Current Monitor The SAM2 RMS03 controller through the cable termination unit makes use of a sensor type 4-20mA Hall Effect current probe (BCP – battery current probe) to measure the battery bank
charge or discharge current during hybrid cycles. The sensor accurately measures the battery load: » Charge current, during utility grid or generator operation » Discharge current, during battery discharge cycle (hybrid
mode) The battery bank voltage is monitored directly by the SAM2
RMS03 controller DC input supply. The battery voltage of the supply feeding the RMS controller is constantly being monitored. For this reason, make sure that the SAM2 RMS03 controller is pow ered directly from the
battery bank supply (priority feed), using a suitable 10A circuit breaker.
SAM2V3 Product Manual V2.1.4 22
Battery Current Probe (BCP) This sensor makes use of hall-technology, in order to measure dc currents with reference to battery charge or discharge currents.
This measurement technique makes it possible to measure current w ithout any electrical connections to the conductor being measured. The unit simply clamps onto the terminal to be monitored and the installation can therefore be done on live
terminals (no need for disconnection) This measurement probe is unique in the sense that it has a
very w ide dynamic range and the ability to detect current reversal. The current sensor has the ability to auto-range, and can measure charge/discharge currents ranging f rom 1Amp to 200Amp, w ith an accuracy of +/-1% on full range.
Auto ranging is necessary, due to the nominal f loat current on the battery banks that could be as low as 1 Amp, w hile the initial charge or discharge currents could be very high. The sensor is connected to a dedicated 4-20mA analogue
input on the SAM2 RMS03 controller unit. Installation Steps:
Sensor cable pinouts
» Connect the current sensor around the battery bank load conductor (connection between rectifier to battery bank). Ensure to clamp all conductors so the entire battery bank capacity is monitored. Only the positive or negative
conductor must be clamped, not both. » If the negative conductor is clamped, the BCP arrow must
face in the direction aw ay from the batteries tow ards the
load.
» If the positive conductor is clamped, the BCP arrow must
face in the direction tow ards the batteries away from the load. (the norm is alw ays to clamp the current carrying conductor, thus not the station earth potential)
» Make use of the universal alarm cable (2-pair, part of w iring cable kit) to connect the BCP sensor to the SAM2 RMS03 cable termination unit +P (blue), GD (blue/w hite)
and –N (orange) connection of “BCP” screw terminal connector. +P refers to positive DC supply voltage, GD to ground connection and –N to negative DC supply voltage.
» Cut the universal alarm cable to the required length and w ire the BCP sensor screw terminal connections according to the follow ing color scheme: Blue lead of blue/w hite pair – positive.
White lead of blue/w hite pair – ground.
Orange lead of orange/white pair – negative.
» Fault f inding: Ensure to measure approximately 15Vdc between
positive and negative pair. With sensor connected to no load (0A), ensure to
measure approximately 0.603V betw een ground and negative.
With sensor connected to SAM2 RMS03 controller,
but not pow ered, ensure to measure approximately 53ohms betw een ground and negative.
Battery Bank Voltage Measurement
The battery bank supply voltage monitoring capability is an integral part of the SAM2 RMS03 controller unit. The battery voltage feeding the controller is constantly being monitored, w ith the ability of monitoring voltages up to 60Vdc, thus
catering for both +24Vdc and -48Vdc sites. This analogue input is part of the SAM2 RMS03 controller and has the ability to auto-range according to the supply voltage
(18-60Vdc)
SAM2V3 Product Manual V2.1.4 23
Wire the DC supply voltage to pow er the SAM2 RMS03 controller directly from the battery bank “PRIORITY” load output supply via a suitable 10A MCB. Make sure not to use the output from a DC to DC converter, as the monitored
voltage is used to determine the battery bank DoD (depth of discharge) during a hybrid (battery discharge) cycle. Indoor type Unit:
Outdoor type Unit:
Note:
» Ensure that the current sensor alarm is not active once the BCP sensor is connected to ensure proper operation.
» Verify that the BCP indicates a charge current reading during a battery charge cycle and a discharge reading
during a discharge cycle. If the readings are inverted, the direction of the BCP sensor (arrow) needs to be inverted.
» Verify that the battery bank supply voltage is monitored directly from the battery bank. During a discharge cycle
the battery voltage must fall by 1-3Vdc within the f irst minute before stabilizing. If the voltage remains constant during a discharge cycle, the SAM2 RMS03 controller is pow ered from a DC to DC converter supply.
16. SAM2 RMS03 – Hybrid Extension
Module (V00) The standard SAM2 RMS03 controller caters for a single 0-
60Vdc analogue voltage input and a single 4-20mA analogue input used for the BCP sensor. These inputs are used during battery cycling to monitor both battery bank voltage (DoD) as w ell as charge/discharge currents (SoC) of a single battery
bank. In some netw ork deployment scenarios it might be necessary to monitor more than one battery bank (part of multiple tenant applications for example), thus the need for the Hybrid
Extension Module (HEM V00).
The HEM V00 module has tw o possible applications: » Monitoring of tw o independent battery banks at the same
BTS site. In some cases different battery banks are used to pow er the RBS radio equipment (+24Vdc) versus the
transmission equipment (-48Vdc). Both battery banks requires to be monitored in order to measure the battery DoD and SoC levels during hybrid cycling.
» In a shared site application it might be required to monitor
the DC load consumed by the shared operator.
In either of the above scenarios the HEM V00 module is used by connecting it to the SAM2 RMS03 controller through a serial RS485 port. Up to three HEM modules could be connected to the SAM2 RMS03 controller via a common serial
RS485 connection w ith the following added monitoring capabilities on a per module basis: » 1x 4-20mA input – BCP sensor » 1x 0-60Vdc input – Battery bank monitor
» 1x Analogue NTC input – Battery temperature sensor » 4x Digital inputs (spare potential free alarm contacts
SAM2V3 Product Manual V2.1.4 24
Installation Steps: » Connect the second current sensor around the additional
battery bank load conductor to be monitored. Ensure to clamp all conductors so the entire battery bank capacity
is monitored. Only the positive or negative conductor must be clamped, not both.
» If the negative conductor is clamped, the BCP arrow must face in the direction aw ay from the batteries tow ards the
load. (refer to section 13) » If the positive conductor is clamped, the BCP arrow must
face in the direction tow ards the batteries away from the
load. (the norm is alw ays to clamp the current carrying conductor, thus not the station earth potential – refer to section 15)
» Connect HEM V00 BCP sensor cable RJ9 connector to
the dedicated socket on the HEM V00 module labeled “BCP2”.
» Ensure that the cable w ith the side marked “BCP2 Sensor” is w ired to the BCP sensor screw terminal
connections according to the follow ing color scheme: Blue lead of blue/w hite pair – positive.
White lead of blue/w hite pair – ground.
Orange lead of orange/white pair – negative.
» Fault f inding:
Ensure to measure approximately 15Vdc between
positive and negative pair.
With sensor connected to no load (0A), ensure to
measure approximately 0.603V betw een ground and negative.
With sensor connected to SAM2 RMS03 controller,
but not pow ered, ensure to measure approximately 53ohms betw een ground and negative.
» Optionally, connect the HEM V00 Battery Temperature
Sensor cable RJ9 connector to the dedicated socket on
the HEM module labeled “Temp”. The battery temperature sensor is normally placed betw een the battery cells, center of total battery block.
Battery Bank Voltage Measurement The additional battery bank supply voltage monitoring is an integral part of the HEM V00 module. The battery voltage
feeding the HEM V00 module is constantly being monitored, w ith the ability of monitoring voltages up to 60Vdc, thus catering for both +24Vdc and -48Vdc battery banks totally isolated from the main battery bank monitored by the SAM2
RMS03 controller. Wire the DC supply voltage to pow er the HEM V00 module directly from the battery bank “PRIORITY” load output supply
via a suitable 1A MCB. Make sure not to use the output from a DC to DC converter, as the monitored voltage is used to determine the battery bank DoD (depth of discharge) during hybrid (battery discharge) cycling.
If required, connect any potential free alarm contacts to be monitored to input 1-4 on the HEM module. (ensure to use the correct polarity as indicated)
» Connect the HEM V00 module to the SAM2 RMS03 cable
termination unit +P (blue), GD (blue/w hite) and –N (orange) connection of “HEM” screw terminal connector.
+P refers to positive DC supply voltage, GD to ground connection and –N to negative DC supply voltage.
Note:
» Before pow ering the HEM V00 module ensure that all w iring connections have been completed (serial connection to SAM2 RMS03 controller, BCP
sensor, Battery bank supply voltage, optional Battery Temp sensor and optional potential free alarm inputs)
» Once pow ered, the HEM V00 pow er/communications LED should f lash slow ly at 3 second intervals, indicating
correct powering sequence. » Once the HEM V00 module address has been set
successfully using the SAM2 RMS03 ECT terminal software program, the pow er/communications LED w ill
f lash faster at 1 second intervals, indicating active communications w ith the SAM2 RMS03 controller.
» Once communications are established w ith the SAM2 RMS03 controller, use the ECT terminal software to verify
that the BCP indicates a charge current reading during a battery charge cycle and a discharge reading during a discharge cycle, battery temperature sensor indicates a
valid temperature reading, battery bank supply voltage is monitored directly from the battery bank and potential free alarm input status.
» Fault f inding: A temperature reading of –12 degrees or more
refers to a disconnected temperature probe lead and temperature reading of +110 degrees or more, refers to a short circuit probe lead.
Should no charge or discharge current values be
displayed, refer to BCP sensor cable connections and w ired polarities (follow test procedures described above)
Confirm change in battery voltage during battery
charge and discharge cycle. If no change visible,
HEM V00 module possibly pow ered through a DC/DC converter.
If no communications established w ith SAM2
RMS03 controller confirm the follow ing: o Serial connection cable w ired polarities
o Configured address
SAM2V3 Product Manual V2.1.4 25
17. SAM2 RMS03 – Hybrid Extension Module (V01)
The standard SAM2 RMS03 controller caters for a single 0-60Vdc analogue voltage input and a single 4-20mA analogue input used for the BCP sensor. These inputs are used during battery cycling to monitor both battery bank voltage (DoD) as
w ell as charge/discharge currents (SoC) of a single battery bank. In some netw ork deployment scenarios it might be necessary
to monitor the load current to multiple tenant sites (DC load consumed by shared operator), thus the need for the Hybrid Extension Module (HEM V01).
The HEM V01 module is used by connecting it to the SAM2
RMS03 controller through a serial RS485 port. Up to three HEM V01 modules could be connected to the SAM2 RMS03 controller via a common serial RS485 connection w ith the
follow ing added monitoring capabilities on a per module basis: » 4x 4-20mA inputs – BCP sensors (up to four tenants) » 1x 0-60Vdc input – Battery bank monitor (common
battery bank to all tenants)
» 1x Analogue NTC input – On-board Battery temperature sensor
Installation Steps: » Connect the tenant current sensor around the particular
DC load supply to be monitored. The DC load supply to the applicable tenant w ill need to be disconnected in
order to f it the relevant current sensors. Ensure to clamp all conductors so the entire load supply to the particular tenant is being monitored. Only the positive or negative conductor must be clamped, not both.
» If the negative conductor is clamped, the BCP arrow must face in the direction from the load (direction of battery).
» If the positive conductor is clamped, the BCP arrow must
face in the direction to the load. (the norm is alw ays to clamp the current carrying conductor, thus not the station earth potential.
» Make use of the universal alarm cable (2-pair, part of
w iring cable kit) to connect the BCP sensors to the HEM V01 module.
» Wire the BCP sensor screw terminal connections according to the follow ing color scheme:
Blue lead of blue/w hite pair – positive.
White lead of blue/w hite pair – negative.
Orange lead of orange/white pair – 4-20mA input.
White lead of orange/w hite pair – ground.
» Fault f inding:
Using a multimeter (0 to 20Vdc Range) measure the DC supply voltages:
Measure across GD and –V screw terminals: -11 to -
13Vdc Measure across GD and +V screw terminals: +11 to
+13Vdc BCP Sensor Output Signal:
Using a multimeter (0 to 10Vdc Range) measure the
voltage on the output of the sensor: Measure across GD and IP screw terminals: +0.8 to
+5.5Vdc depending on the load current (0 to 30A)
» The HEM V01 has an integrated Temperature Sensor for the purpose of monitoring the ambient temperature. (useful if HEM V01 placed w ithin the battery distribution
cabinet)
Battery Bank Voltage Measurement The battery bank supply voltage monitoring is an integral part
of the HEM V01 module. The battery voltage feeding the HEM V01 module is constantly being monitored, w ith the ability of monitoring voltages up to 60Vdc, thus catering for both +24Vdc and -48Vdc battery banks totally isolated from the
main battery bank monitored by the SAM2 RMS03 controller. Wire the DC supply voltage to pow er the HEM V01 module directly from the battery bank “PRIORITY” load output supply
via a suitable 1A MCB. Make sure not to use the output from a DC to DC converter, as the monitored voltage is used in conjunction w ith the monitored load currents, part of an algorithm to calculate the total tenant DC load.
SAM2V3 Product Manual V2.1.4 26
» Connect the HEM V01 module to the SAM2 RMS03 cable
termination unit +P (orange), GD (blue/w hite) and –N (orange/white) connection of “HEM MOD” screw terminal connector. Connect 12V (blue) to the “MOVE” screw
terminal connector. +P refers to positive RS485 communications, GD to supply ground connection, –N to negative RS485 communications and 12V to positive supply voltage.
Note: » Before pow ering the HEM V01 module ensure that all
w iring connections have been completed
(serial connection to SAM2 RMS03 controller, BCP sensors, Battery bank supply voltage)
» Once pow ered, the HEM V01 pow er/communications LED should f lash slow ly at 3 second intervals, indicating
correct powering sequence. » Once the HEM V01 module address has been set
successfully using the SAM2 RMS03 ECT terminal
software program, the pow er/communications LED w ill f lash faster at 1 second intervals, indicating active communications w ith the SAM2 RMS03 controller.
» Once communications are established w ith the SAM2
RMS03 controller, use the ECT terminal software to verify that the BCP’s indicates a load current reading (on a per tenant basis), battery temperature sensor indicates a valid temperature reading and battery bank supply
voltage is monitored directly from the battery bank.
» Fault f inding: A temperature reading of –12 degrees or more
refers to a disconnected temperature sensor and
temperature reading of +110 degrees or more, refers to a short circuit.
Should no load current values be displayed, refer to
BCP sensor cable connections and w ired polarities (follow test procedures described above)
Confirm change in battery voltage during battery
charge and discharge cycle. If no change visible, HEM V01 module possibly pow ered through a DC/DC converter.
If no communications established w ith SAM2 RMS03 controller confirm the follow ing:
o Serial connection cable w ired polarities o Configured address
18. SAM2 RMS03 – Navigation Light Sensor – AC Mains Type The SAM2 RMS03 makes use of a sensor type Navigation Light monitoring (AWM) unit to accurately detect any failure of one or more tow er lamps. The SAM2 RMS03 system has tw o
types of navigation light sensors, one for AC type navigation lights and one for DC type navigation lights. The installation procedure for both is practically the same. (ensure how ever that the correct type is used for the applicable site application)
The AWM AC mains type sensor is located w ithin the AC distribution box and w ired in series with the live supply (output of NAV light MCB) of the navigation tow er lights and calibrated according to the amount of current draw n by the lamps. Any
deviation in the current drawn will cause an active alarm. Due to the AWM sensor being calibrated on a per site basis, virtually any amount or type of lamps could effectively be
monitored by the unit. AWM AC-type Unit Electrical Specif ications:
Installation Steps:
Sensor cable pinouts:
» Connect optional AWM sensor cable (RJ9 (4x4) to open ended – 12m) to the SAM2 RMS03 cable termination unit 12V (orange/white), NL (orange), SL (optional) and GD (blue) connection of “AWM Unit” screw terminal
connection. NL refers to Navigation Light alarm and SL refers to optional Security Light alarm.
» Ensure that the cable w ith the side marked “AWM Sensor” is plugged into the RJ9 socket of the AWM
sensor.
SAM2V3 Product Manual V2.1.4 27
» Wire the mains live supply from the navigation light MCB output to the AWM sensor input as follow s: IN1 Input – if total pow er drawn by tower lamps less
than 20W. IN2 Input – if total pow er drawn by tower lamps less
than 40W.
IN3 Input – if total pow er drawn by tower lamps less
than 60W. » Wire the output, OUT, of the AWM sensor to the mains
supply cable feeding the tow er lamps.
» In order to calibrate the AWM sensor, the follow ing procedure has to be follow ed: (note – repeat this procedure upon any lamp change)
Connect the AWM sensor as indicated in the
diagram above. Sw itch on the AWM MCB and ensure all tow er
lamps are functional. Using a small screw driver, adjust the “sensitivity”
screw on the AWM sensor fully clockwise, thus
maximum sensitivity. Both AWM LED’s must be on (“Lights On” and “Calibrate”).
Turn the “sensitivity” screw slowly in an anti-
clockw ise direction, thus decreasing sensitivity, until the red “Calibrate” LED goes off. Only the green
“Lights On” LED must now be on. For the best performance, the sensitivity setting
should be as close as possible to the point w here the red “Calibrate” LED is constantly on. It is normal
for the “Calibrate” LED to f lash every now and then. If the “Calibrate” LED is constantly on, it means the sensitivity has been set to high (out of calibration) or the mains supply voltage is momentarily too
high/low , resulting in in/decreased current f low. Verify correct operation by turning off the power to
the tow er lamps. Both LED’s must now be of f and the SAM2 RMS03 unit should indicate an alarm condition. (note that the navigation lights alarm is
masked in daylight hours and must be view ed in the unmasked state using the SAM2 RMS03 LCD display or technician craft terminal software application)
Turn on the pow er to the tow er lamps and verify that
the AWM green LED “Lights On” is burning. The SAM2 RMS03 should indicate no alarm condition.
To achieve maximum range w ith the sensitivity
screw, ensure to w ire the input corresponding to the total current drawn by the lamps.
Note: » Ensure that all the lamps are sw itched on and functional
before calibrating the AWM sensor. » Ensure to re-calibrate the AWM sensor upon lamp
replacements. » AWM alarm indication is masked during daytime
operation to compensate for daylight sensors. (from 4am to 8pm).
» During installation testing phase, refer to the SAM2 RMS03 craft terminal software application (SAM2 RMS03
ECT) or LCD display to verify true unmasked alarm status “Diagnostics → View Inputs”
19. SAM2 RMS03 – Navigation Light Sensor – DC Supply Type
The SAM2 RMS03 makes use of a sensor type Navigation Light monitoring (AWM) unit to accurately detect any failure of one or more tow er lamps. The SAM2 RMS03 system has tw o types of navigation light monitors, one for AC type navigation
lights and one for DC type navigation lights. The installation procedure for both are the same. (ensure how ever that the correct type is used for the applicable site application)
The DC type AWM sensor is located in the DC distribution box and w ired in series w ith the DC supply (output of NAV light MCB) of the navigation tow er lights and calibrated according to
the amount of current draw n by the lamps. Any deviation in the current drawn will cause an active alarm. Due to the AWM sensor being calibrated on a per site basis,
virtually any amount of lamps could effectively be monitored by the unit. AWM DC-type Unit Electrical Specif ications:
Installation Steps:
Sensor cable pinouts:
» Connect optional AWM sensor cable (RJ9 (4x4) to open
ended – 12m) to the SAM2 RMS03 cable termination unit
SAM2V3 Product Manual V2.1.4 28
12V (orange/white), NL (orange), SL (optional) and GD (blue) connection of “AWM Unit” screw terminal connection. NL refers to Navigation Light alarm and SL refers to optional Security Light alarm.
» Ensure that the cable w ith the side marked “AWM Sensor” is plugged into the RJ9 socket of the AWM DC sensor.
» Wire the negative DC supply from the navigation light
MCB output to the AWM DC input “IN”. » Wire the output “OUT” of the AWM DC to the supply
cable feeding the tow er lamps (DC supply).
» In order to calibrate the DC type AWM sensor, the
follow ing procedure has to be follow ed: (note – repeat this procedure upon any lamp change)
Connect the AWM DC sensor as indicated in the
diagram above. Sw itch on the AWM MCB and ensure all tow er
lamps are functional.
Using a small screw driver, adjust the “sensitivity”
screw on the AWM DC sensor fully clockwise, thus maximum sensitivity. Both AWM LED’s must be on (“Lights On” and “Calibrate”).
Turn the “sensitivity” screw slowly in an anti-
clockw ise direction, thus decreasing sensitivity, until
the red “Calibrate” LED goes off. Only the green “Lights On” LED must now be on.
For the best performance, the sensitivity setting
should be as close as possible to the point w here the red “Calibrate” LED is constantly on. It is normal
for the “Calibrate” LED to f lash every now and then. If the “Calibrate” LED is constantly on, it means the sensitivity has been set to high (out of calibration) or
the DC supply voltage is momentarily too high/low , resulting in in/decreased current f low.
Verify correct operation by turning off the power to
the tow er lamps. Both LED’s must now be of f and the SAM2 RMS03 unit should indicate an alarm
condition. (note that the navigation lights alarm is masked in daylight hours and must be view ed in the unmasked state using the SAM2 RMS03 LCD display or technician craft terminal software
application) Turn on the pow er to the tow er lamps and verify that
the AWM DC green LED “Lights On” is burning. The SAM2 RMS03 should indicate no alarm condition.
Note: » Ensure that all the lamps are sw itched on and functional
before calibrating the AWM DC sensor.
» Ensure to re-calibrate the AWM DC sensor upon lamp replacements.
» AWM DC alarm indication is masked during daytime operation to compensate for daylight sensors. (from 4am
to 8pm). » During installation testing phase, refer to the SAM2
RMS03 craft terminal software application (SAM2 RMS03 ECT) or LCD display to verify true unmasked alarm status
“Diagnostics → View Inputs”
20. SAM2 RMS03 – Utility Grid Management
The SAM2 RMS03 controller through the cable termination unit and generator controller makes use of an optional 3-phase utility grid check meter for the purpose of monitoring the utility grid supply in terms of voltage, current and Kw H consumption.
(on a per phase basis) The SAM2 RMS03 communicates w ith the utility grid meter, using a serial RS485 connection.
The utility grid meter is deployed as a check meter w ith the follow ing features: » Statistical Kw H counters – based upon actual load
consumption and/or total load consumption over a 24 hour period.
» Statistical voltage per phase indication. » Statistical load current per phase indication.
» Optional, manual or automated load disconnect function. (in conjunction w ith meter control relay – U1) The SAM2 RMS03 controller has the ability to disconnect the utility AC load and run the generator or battery
backup, should the grid pow er prove to be unstable. The grid pow er is constantly monitored in terms of
the configured mains fail stability criteria period (one minute default). If the mains voltage drops below the configured voltage threshold, on any of the phases,
the utility grid load w ill be disconnected and the generator started or battery discharge cycle started, in order to carry the load.
Should the mains voltage regain stability based
upon the configured voltage and stability duration (f ive minutes default), on all three phases, the utility grid load supply w ill be reconnected and the generator stopped or the battery discharge cycle
ended. » Utility grid Hybrid Control. In certain cases it w ould be
beneficial to cycle the site batteries in conjunction w ith the utility grid supply. The SAM2 RMS03 controller could
be configured to disconnect the utility grid supply, once the required battery SOC (state of charge) is reached. The utility grid supply w ould be reconnected once the battery reaches the configured DoD (depth of discharge)
level. (generator control forms part of the above control logic to ensure the generator is started should utility grid failure occur)
Installation Steps:
» Make use of the utility grid meter communications cable
(4-pair, part of w iring cable kit) to connect the utility meter to the SAM2 RMS03 generator controller, P+ (blue), N-
(blue/w hite) and GD (orange) connection of “SAM2 RS485” screw terminal connection. P+ refers to RS485 Positive, N- refers to RS485 Negative and GD to supply Ground connection.
» Terminate the other end of the utility grid meter communications cable to the RJ12 6-pin connector provided as follow s:
Orange – Ground – Pin1
SAM2V3 Product Manual V2.1.4 29
Blue – Positive RS485 – Pin2
Blue/White – Negative RS485 – Pin3
» Ensure to plug the cable into the RJ12 “communications interface” socket of the utility grid meter. (left communications socket as indicated below )
» Connect the utility meter phases as follow s:
Phase 1 (Red) In – Terminal L1 IN
Phase 1 (Red) Out – Terminal L1 OUT
Phase 2 (Blue) In – Terminal L2 IN
Phase 2 (Blue) Out – Terminal L2 OUT
Phase 3 (Yellow ) In – Terminal L3 IN
Phase 3 (Yellow ) Out – Terminal L3 OUT
Neutral (Black) In – Terminal N IN
Neutral (Black) Out – Terminal N OUT
» The utility meter is normally connected to the mains 3-phase input supply directly from the utility grid supplier.
Optionally, in some cases the utility meter is connected to the 3-phase load supply from the ATS. In this case the utility meter is capable of measuring both the utility grid and generator 3-phase supply. (data is stored in tw o
separate registers for utility versus generator AC mains statistics)
» The utility meter is not w eather proof and needs to be placed in the optional outdoor enclosure should inadequate space be available indoors during installations.
Note: » Ensure all utility grid phases are connected as illustrated
above. Ensure to measure the desired 230Vac per phase on terminals (L1, L2, L3 – IN, w ith reference to N – IN)
» If meter connection is through to the load, ensure to measure the same voltage on terminals (L1, L2, L3 – OUT, w ith reference to N - OUT)
» Ensure the meter Kw H indicator is pulsing (1-2 second intervals) indicating presence of utility mains pow er.
» Use the SAM2 RMS03 LCD display or technician terminal software program to verify operation of the meter. (meter
communications alarm should be clear and voltage/current per phase reading visible)
21. SAM2 RMS03 – Equipment Mains Monitoring Unit The utility grid meter is used to monitor and verify the utility AC mains grid and/or generator supply to site. In some netw ork deployment scenarios it might be necessary
to monitor the distributed AC load current to multiple tenant sites (AC load consumed by shared operator), thus the need for the Equipment Mains Monitoring Unit (EMU).
The EMU module is used by connecting it to the SAM2 RMS03 controller through a serial RS485 port. Up to three EMU modules could be connected to the SAM2 RMS03 controller
via a common serial RS485 connection w ith the follow ing added monitoring capabilities on a per module basis: » 6x voltage inputs – Current Transformer (CT’s) (up to tw o
3-phase tenants or up to six single phase tenants).
» 1x 3-phase AC Mains supply input – Tenant distributed mains supply voltage.
» 1x Alarm output – AC Mains low voltage alarm.
Installation Steps: » Connect the tenant current transformers around the
particular AC load supply to be monitored (either Single
Phase load supply or 3-Phase Load supply). The AC load supply to the applicable tenant w ill need to be disconnected in order to f it the relevant current sensors. Ensure to clamp all conductors so the entire load supply
to the particular tenant is being monitored. (the current transformers are not directional, thus could be f itted in any direction)
» The current transformers are normally located w ithin the
AC distribution box, after the MCB feeding the particular tenant.
» The current transformers are factory terminated on a 650mm w iring harness (CT1-3, cable harness 1 and CT4-
6, cable harness 2). Make sure to connect the correct cable harness to the appropriate EMU monitoring input.
» The tenants AC Mains 3-Phase supply voltage monitoring is an integral part of the EMU module. The AC mains supply voltage feeding the EMU module is constantly being monitored, w ith the ability of monitoring voltages up
to 260Vac
SAM2V3 Product Manual V2.1.4 30
» A low voltage alarm output (default 187vac) could optionally be w ired to any of the SAM2 RMS03 controller spare inputs. The alarm threshold is configurable using the SAM2 RMS03 craft terminal software application
(SAM2 RMS03 ECT) and is activated if any one of the monitored phases drops below this setpoint.
» Connect the EMU module to the SAM2 RMS03 cable termination unit +P (orange), GD (blue/w hite) and –N (orange/white) connection of “HEM MOD” screw terminal connector. +P refers to positive RS485 communications,
GD to supply ground connection and –N to negative RS485 communications.
Note: » Before pow ering the EMU module ensure that all w iring
connections have been completed (serial connection to SAM2 RMS03 controller, CT
sensors, mains supply voltage)
» Once pow ered, the EMU pow er/communications LED should f lash each time interrogated by the SAM2 RMS03 controller, indicating communications.
» Once communications are established w ith the SAM2
RMS03 controller, use the ECT terminal software to verify that the CT’s indicates a load current reading (on a per tenant basis) and AC mains supply w ithin range.
» Fault f inding: Should no load current values be displayed, refer to
CT sensor cable harness connections. Confirm AC mains voltage on all phases.
If no communications established w ith SAM2
RMS03 controller confirm serial connection cable w ired polarities
22. SAM2 RMS03 – Generator
Controller One of the primary functions of the SAM2 RMS03 controller is
to perform generator remote start/stop control part of hybrid battery cycling. The SAM2 RMS03 controller does not replace the existing site AMF/ATS unit, but w orks in conjunction w ith these units to
perform the follow ing basic functions: » Generator Control:
Automatic start/stop dependent upon the state of the
utility grid ac mains supply. Automatic start/stop part of hybrid battery
charge/discharge cycling.
Remote start/stop part of system test.
Remote Reset upon activated fault condition.
» Alarm Monitoring: Utility Grid AC Mains Fail.
Generator Running (DG started successfully).
Generator Fault (DG generic fault indication).
Generator Start Fail (DG failed to start successfully)
Generator Manual Override (DG remains running
after a DG stop control signal). Generator on Load (DG load contactor activated).
Generator Oil Pressure (DG LLOP fault indication).
Generator Temperature (DG HT fault indication).
Generator Low fuel (optional DG low level fuel
sw itch) Generator Door (optional DG canopy intrusion)
Generator Emergency Stop (optional DG emergency
stop button)
The SAM2 generator controller (DGC) module operates in conjunction w ith the SAM2 RMS03 controller to perform the above mentioned functions.
The DGC consists of the following connections that would be
described in detail w ithin this section of the manual: A – SAM2 RMS03 auxiliary pow er and RS485 communications connection.
SAM2V3 Product Manual V2.1.4 31
B – Fuel sensor auxiliary power and RS485 communications connection. C – Generator monitored alarm inputs. D – Generator 12V battery monitoring inputs.
E – Generator tw o start/stop and reset control. F – Generator one start/stop and reset control. G – Generator start/stop test button.
A – SAM2 RMS03 Auxiliary Power and RS485 Comms: Installation Steps:
» Connect the DG Alarm/control cable SubD9 pin
connector to the SAM2 RMS03 cable termination unit “DG Control” connector.
» Route the open end of the cable to the generator ATS/AMF panel w here the SAM2 generator controller (DGC) w ould be installed.
» Terminate the cable pairs on the DGC “SAM2 RS485”
screw terminal connector as follows:
Note: » The blue and blue/w hite pair is used for RS485 serial
communications betw een the SAM2 RMS03 controller
and DGC controller. » The orange and orange/w hite pair is used for the auxiliary
12Vdc supply to pow er the DGC controller from the SAM2 RMS03 controller.
» The green and green/w hite pair carries the same auxiliary 12Vdc supply as the orange pair and w ould thus be bundled together to ensure a proper stable 12V supply.
» The brow n and brown/white pair carries the same
auxiliary 12Vdc supply as the orange pair and w ould thus be bundled together to ensure a proper stable 12V supply.
B – Fuel Sensor Auxiliary Power and RS485 Comms: Refer to section 24 of this manual – SAM2 RMS03 Fuel Management.
C – Generator Monitored Alarm Inputs: Refer to section 23 of this manual – SAM2 RMS03 Generator Alarm Monitoring.
D – Generator 12V Battery Monitoring Inputs: Installation Steps:
» Use any of the 4-pair alarm cable off -cuts to w ire the DG
12V battery monitoring inputs. » Generator one 12V battery is connected to the DGC
“DG1” screw terminal connector, blue to +12V connection and blue/w hite to GD (ground) connection.
» Generator tw o 12V battery is connected to the DGC
“DG2” screw terminal connector, orange to +12V connection and orange/w hite to GD (ground) connection.
Note:
» The generator 12V battery connection could be tapped from the AMF panel dc supply input, as it is normally pow ered directly from the generator standby battery. (before connecting, ensure that the above input is in fact
the generator 12V battery and not a standby battery) E+F - Generator Start/Stop and Reset Control:
Installation Steps:
Under normal conditions the SAM2 RSM03 controller issues a remote start command once a utility grid AC mains supply failure is detected. How ever at this point tw o conditions are verif ied, that could
influence this sequence: » Batteries fully charged according to the configured SoC,
the DG w ill not be started and a hybrid battery discharge
cycle activated. » If the DG did not run in the last user configurable period
(default 24 hours), the DG w ill be started under test by the SAM2 RMS03 controller for a user configurable
timeframe (default 5 minutes). Should the battery be charged to the required SoC, the DG w ill be stopped and the battery discharge cycle activated. If not, the DG w ill remain running until battery
SoC reached or utility grid mains supply returns. Each DG start sequence is controlled through a single relay w ith dual sw itchover contacts by the SAM2 RMS03 controller
in conjunction w ith the generator controller.
SAM2V3 Product Manual V2.1.4 32
» Make use of the 4-pair DG Alarm/control cable, off-cuts, to connect the DGC generator start/top and reset connections to the generator AMF/ATS.
» In case of single generator control, make the follow ing
connections on the DGC “Start-1” screw terminal connector: DG1 Remote Start NO (normally open relay) contact
- Blue of Blue/w hite pair. DG1 Remote Start NC (normally closed relay)
contact – Blue of Blue/w hite pair.
DG1 Remote Start CM (common) contact – White of
Blue/w hite pair. (before connecting the remote start controlling pair, ensure to determine w hether a NO or NC contact is required and w ire accordingly)
» In case of dual generator control, make the follow ing
connections on the DGC “Start-2” screw terminal connector:
DG2 Remote Start NO (normally open relay) contact
- Green of Green/w hite pair. DG1 Remote Start NC (normally closed relay)
contact – Green of Green/w hite pair. DG1 Remote Start CM (common) contact – White of
Green/w hite pair. (before connecting the remote start controlling pair,
ensure to determine w hether a NO or NC contact is required and w ire accordingly)
Note:
The NC contact (inverted logic) of the SAM2 RMS03 controller is closed (failsafe) upon a DG start command, resulting in de-energizing the dual sw itchover relay located on the generator
controller unit: » Wire the required contact NC (short circuit) or NO (open
circuit) relay contact to the applicable ATS/AMF, remote start input.
» The above contacts are potential free and could be referenced to ground or +12V, based upon the requirements from the ATS/AMF.
The DG reset sequence for both generators are controlled through a single relay w ith dual sw itchover contacts by the SAM2 RMS03 controller in conjunction w ith the generator controller.
» Make use of the 4-pair DG Alarm/control cable, off-cuts, to connect the DGC generator start/top and reset connections to the generator AMF/ATS.
» Tw o relay w iring positions are provided in case of single
or dual generator control, both operating simultaneously. In case of single generator control, make the follow ing connections on the DGC “Reset-1” screw terminal connector:
DG1 Remote Reset NO (normally open relay)
contact - Orange of Orange/w hite pair. DG1 Remote Reset NC (normally closed relay)
contact – Orange of Orange/w hite pair. DG1 Remote Reset CM (common) contact – White
of Orange/w hite pair. » In case of dual generator control, make the follow ing
connections on the DGC “Reset-2” screw terminal connector: DG2 Remote Reset NO (normally open relay)
contact - Brow n of Brown/white pair.
DG2 Remote Reset NC (normally closed relay)
contact – Brow n of Brown/white pair. DG2 Remote Reset CM (common) contact – White
of Brow n/white pair. (before connecting the remote reset controlling pair, ensure to determine w hether a NO or NC contact is
required and w ire accordingly)
Note: The NO contact of the SAM2 RMS03 controller is closed upon
a DG reset command, resulting in energizing the dual sw itchover relay located on the generator controller unit: » Wire the required contact NC (short circuit) or NO (open
circuit) relay contact to the applicable ATS/AMF, remote
reset input. » The above contacts are potential free and could be
referenced to ground or +12V, based upon the
requirements from the ATS/AMF.
» During a DG start command from the SAM2 RMS03 controller ensure the ATS/AMF sends a start pulse to the
DG by cranking the engine. » During a DG reset command from the SAM2 RMS03
controller ensure the ATS/AMF fault condition is cleared. Should the fault condition return, DG maintenance or
repairs w ould be necessary. Generator remote start/reset control sequence The SAM2 RMS03 controller has a specif ic sequence in w hich
a single or dual generator is remotely started, w hich is hardcoded in the f irmw are with limited user configurable settings.
» When the DG needs to be started, due to a utility mains grid failure alarm (A) or due to a low battery threshold (DoD reached), the remote start N/C relay is de-energized. The duration of the remote start contact is
user configurable between 0-255 seconds (default 30 seconds). The DG start pulse is delayed by a user configurable “DG start delay” period (B) betw een 0-255 seconds (default 60 seconds).
» When the DG needs to be stopped, due to utility grid mains being restored (A) or due to hybrid battery discharge activation, the remote start N/C relay is
SAM2V3 Product Manual V2.1.4 33
energized. The sw itchover of the DG start contact is delayed by a user configurable “DG stop delay” period (C) betw een 0-255 seconds (default 60 seconds).
» Should the DG not be started upon the f irst start attempt
the SAM2 RMS03 w ill issue another remote start command. The remote start attempts are f ixed to four (hardcoded in the f irmw are), at w hich a “DG fail to start” (D+E) alarm is activated.
» The pause/reset intervals between the remote start pulses are f ixed to 30 seconds and hardcoded in the f irmw are.
» Once a “DG fail to start” alarm is activated for a particular DG the SAM2 RMS03 controller w ill no longer try and start the DG unless one of the follow ing conditions are met:
Whenever any of the hybrid suspend conditions
changes state. Alarms conditions such as shelter temperature for example.
Whenever hybrid battery discharge is deactivated.
Both DG are off due to the presence of grid utility
mains supply DG remote start command
DG remote reset command
DG sw ap (either manual or auto)
Decreasing BTS battery voltage (every 1volt drop in
threshold)
Note: Once the “DG fail to start” alarm is cleared, the above sequence is repeated.
» A control command executed from the management platform or technicians craft terminal (F), in terms of:
DG remote start command (G)
DG remote stop command (G)
DG remote reset command (G)
DG remote sw ap command (G),
w ould cause the generator to respond immediately, thus zero delay (H), besides the netw ork SMS/GPRS/Edge message delays.
G - Generator Start/Stop test button: Test Procedure:
» The DGC is equipped w ith a “DG Test” button used to
perform the follow ing tests:
When DG is off – Pressing the button w ill start and
run the DG for the default test duration (5 min). When DG is running – Pressing the button w ill stop
the DG for the default test duration (5 min). (The DG w ill only be stopped if the site batteries are at the required SoC, otherw ise the DG w ill remain running)
23. SAM2 RMS03 – Generator Alarm
Monitoring The SAM2 RMS03 controller in conjunction w ith the generator
controller unit makes provision to monitor eight general purpose (dry contacts) generator alarm indications. (configurable for N/O or N/C alarm state) One DGC could be used to control and monitor single or dual
generators. Should additional alarm inputs be required or the distance betw een the generators do not w arrant a single DGC, tw o DGC units could be installed on the same RS485 communications cable pairs.
Installation Steps:
» Make use of the 4-pair DG Alarm/control cable, off-cuts (tw o pieces), to connect the DGC generator alarm inputs to the generator AMF/ATS and AMC (AC Mains) sensor.
» The default alarm indications for single generator monitoring are as follow s: (user configurable) Alarm 1 (Blue) – Utility AC Mains Fail
Alarm 2 (Orange) – Mains on Load
Alarm 3 (Green) – DG1 on Load
Alarm 4 (Brow n) – DG1 Run
Alarm 5 (Blue) – DG1 Fault
Alarm 6 (Orange) – DG1 High Temperature
Alarm 7 (Green) – DG1 Low Oil Pressure
Alarm 8 (Brow n) – DG1 Door (Intrusion)
» All alarm inputs (1-8) uses the same ground (DG) connection. Ensure to w ire all the common “w hite” leads of all alarm inputs to the “GD” terminal.
SAM2V3 Product Manual V2.1.4 34
Dependent upon the ATS/AMF type, the input alarm signals could be referenced to ground (0V) or +12V. Ensure to move the reference links (IP1-IP8) corresponding to each alarm input accordingly. (link in 0V and link out +12V)
» The default alarm indications for dual generator (using a
single DGC) monitoring are as follow s: (user configurable) Alarm 1 (Blue) – Utility AC Mains Fail
Alarm 2 (Orange) – Mains on Load
Alarm 3 (Green) – DG1 on Load
Alarm 4 (Brow n) – DG1 Run
Alarm 5 (Blue) – DG1 Fault
Alarm 6 (Orange) – DG2 on Load
Alarm 7 (Green) – DG2 Run
Alarm 8 (Brow n) – DG2 Fault
» All alarm inputs (1-8) uses the same ground (DG) connection. Ensure to w ire all the common “w hite” leads of all alarm inputs to the “GD” terminal.
Dependent upon the ATS/AMF type, the input alarm signals could be referenced to ground (0V) or +12V. Ensure to move the reference links (IP1-IP8) corresponding to each alarm input
accordingly. (link in 0V and link out +12V) Note: » Meaning of the follow ing visible alarm indications:
LED1 – DG Low Battery Indication.
(On - Any of the monitored DG batteries, <11.3V). LED2 – SAM2 RMS03 Communications.
o On – Tw o w ay communications. o Flashing – One w ay communications.
LED3 – Utility Grid Supply (UAC)
o On – Utility Alarm clear, Mains on Load active.
o Off – Utility Alarm active, Mains on Load clear.
o Flashing – Utility Alarm clear, Mains on Load clear.
LED4 – DG Load Supply (DGAC)
o On – DG Run active, DG on Load active.
o Off – DG Run clear, DG on Load clear.
o Flashing – DG Run active, DG on Load clear.
LED5 – Hybrid Status (HS)
o On – Hybrid battery discharge active. o Off – Site on AC pow er (charging).
o Flashing – Site Battery discharging but not in hybrid mode.
» The above alarm connections needs to be tested on the SAM2 RMS03 controller by activating each individually as follow s: Utility AC Mains Fail – Fail the utility AC Mains
supply by disconnecting the load MCB.
Mains on Load – Restore the utility AC Mains MCB
and confirm that the mains contactor carries the load supply.
DG on Load – Fail the utility AC Mains supply and
ensure the DG is started. Confirm that the site load is shifted to the DG contactor to carry the load
supply. DG Run – Execute a remote DG start command and
confirm the DG starts successfully. DG Fault – By activating any temperature or oil
pressure alarm before the DG is running. DG High Temperature – Short the temperature
sensor to ground w hile the DG is running.
DG Low Oil Pressure – Short the oil pressure sensor
to ground w hile the DG is running. DG Door (Intrusion) – Open the generator canopy
doors.
24. SAM2 RMS03 – Fuel Management The SAM2 RMS03 controller through the generator controller
makes provision to monitor dual fuel tanks of virtually any shape, size and capacity. The SAM2 RMS03 fuel management option consists of the
follow ing items: » Fuel Sensor » Fuel Tank Lid Sensor » Water in Diesel Sensor
The SAM2 RMS03 controller has the ability to measure the actual amount of diesel stored in the fuel tank and to detect
w hen the fuel tank lid is open. The w ater detection sensor is used to indicate that w ater is present in the diesel tank. Fuel Sensor
The fuel management option consists of an analogue pressure sensor (submersible or externally mount) that is accurately calibrated according to the tank dimension using the SAM2 RMS03 diagnostics and configuration software. The measured
pressure is converted to a fuel level expressed in litres or gallons. Alternatively an ultrasonic sensor could be used if more suitable to the installation environment. The measured time for
a high frequency sound wave echo to reflect from the measured fuel level is converted to a fuel level expressed in litres or gallons.
Communication betw een the SAM2_RMS03 controller and the fuel sensor is through a serial RS485 port. The fuel sensor is pow ered by one of the SAM2 RMS03 controller auxiliary
12Vdc supplies.
SAM2V3 Product Manual V2.1.4 35
Installation Steps: » Should the distance betw een the fuel tank and the
AMF/ATS (w here the DGC is located) be too far, make
use of the Fuel Tank sensor cable (4-pair, part of w iring cable kit), in order to extend the cabling, to connect the fuel probe to the DGC.
» The cable termination box is used to securely join all
cable connections betw een the fuel sensor and fuel tank sensor cabling. The cable termination box is rated IP65 and can be used outdoors.
» Connect the fuel sensor to the DGC as follow s:
P+ terminal (RS485 Positive) to Blue of fuel sensor.
N- terminal (RS495 Negative) to Yellow of fuel
sensor.
12V terminal (Positive supply) to Black of fuel
sensor. GD terminal (Negative supply) to White of fuel
sensor. (pairs are polarity sensitive, thus do not invert).
» When using a submersible pressure sensor, f it the fuel sensor ensuring that it is lying at the bottom of the tank.
» The SAM2 RMS03 controller through the DGC uses a single cable-pair to communicate w ith the fuel sensor via
RS485 and a separate pair for the 12Vdc supply to power the probe.
» The fuel sensor cable has a clear plastic “Breather” pipe at the center of its core, this pipe must not be bent or
sealed as “unobstructed” airf low via this pipe is necessary for correct operation of the sensor. The fuel sensor cable has a screen and a red lead; both
are not used and may be cut.
Note: » During installation each fuel sensor needs to be
calibrated according to tank capacity and volumetric pressure to ensure maximum accuracy. Tank calibration is done using the SAM2 RMS03 serial diagnostics and configuration software – “Fuel Probe Wizard” application.
» Before starting the fuel sensor calibration process, ensure the follow ing: The fuel sensor is communicating w ith the SAM2
RMS03 controller. Should the fuel sensor not communicate w ith the
SAM2 RMS03 controller a “Fuel Probe1 Fail” alarm
w ould be active. (verify wiring connections to clear alarm)
Make sure the DG is not running to ensure minimum
fuel level vibration during the calibration process. Ensure the tank is clean and free of sludge (bottom
residue) and equipped w ith suitable “breather” pipe
in terms of pressure buildup part of daily temperature changes.
Fuel Tank Lid Sensor The optional fuel tank lid kit is a custom made tank lid sw itch and sensor, universal to most types of tanks available.
The sensor kit consists of an active switch and magnetic sensor. The sw itch is mounted w ithin the tank inlet and the magnetic sensor in the tank lid. Once the lid is opened an alarm is
activated and upon closure of the tank the alarm is deactivated. This concept is used to determine w hen the fuel tank is either being f illed or possibly fuel being siphoning.
The SAM2 RMS03 controller takes a fuel reading upon alarm status change, thus fuel added or removed. These fuel readings are used part of the customized fuel management
reports. Installation Steps:
» Should the distance betw een the fuel tank lid kit and the AMF/ATS (w here the DGC is located) be too far, make use of the Fuel Tank sensor cable (4-pair, part of w iring cable kit), in order to extend the cabling, to connect the
fuel tank lid kit to the DGC. » The cable termination box is used to securely join all
cable connections betw een the fuel tank lid kit and fuel tank sensor cabling. The cable termination box is rated
IP65 and can be used outdoors.
SAM2V3 Product Manual V2.1.4 36
» Connect the fuel tank lid sensor to the DGC as follow s:
“DG Alarm Inputs” screw connection, input terminal
8 to Blue of fuel tank lid sensor. (note, any spare alarm input could be used)
12V terminal (Positive supply) to Brow n of fuel tank
lid sensor. GD terminal (Negative supply) to Black of fuel tank
lid sensor. (note, the negative supply also acts as the alarm input ground) (pairs are polarity sensitive, thus do not invert).
» Physically mount the active sw itch (A) to the inlet of the fuel tank. Ensure the beveled edge of the active pickup
faces upwards, with the cable facing dow nwards. » The rotation of the mounting bracket (B) w ould be
determined by the type of thank.
» Mount the magnetic sensor (C) in the center of the tank lid.
Note:
» During installation ensure that the mounting bracket, active sw itch and magnetic sensor are securely and neatly attached to the fuel tank.
» Align the active sw itch and magnetic sensor to ensure the
alarm clears w hen tank lid is closed and alarm activates w hen tank lid is opened.
» The tank lid alarm state could be tested using SAM2 RMS03 serial diagnostic and configuration software or
LCD display. Water in Diesel Sensor
The optional w ater in diesel sensor (submersible or externally mount) is used to detect w ater contamination of the diesel fuel. The sensor is a custom-made liquid level, solid-state device
designed to detect the presence or absence of an electrically conductive liquid. Each sensor contains integral, high-temperature-rated electronics that generate an alternating voltage to the stainless steel tip. The presence of an
electrically conductive liquid completes the circuit w hich, in turn, changes the condition of the transistor output (alarm state).
Installation Steps: » Should the distance betw een the w ater in diesel sensor
and the AMF/ATS (w here the DGC is located) be too far, make use of the Fuel Tank sensor cable (4-pair, part of w iring cable kit), in order to extend the cabling, to connect the w ater in diesel sensor to the DGC.
» The cable termination box is used to securely join all cable connections betw een the water in diesel sensor and fuel tank sensor cabling. The cable termination box is rated IP65 and can be used outdoors.
» Connect the w ater in diesel sensor to the DGC as follows: “DG Alarm Inputs” screw connection, input terminal
7 to Blue of w ater in diesel sensor. (note, any spare alarm input could be used)
12V terminal (Positive supply) to Brow n of water in
diesel sensor. GD terminal (Negative supply) to Black of w ater in
diesel sensor. (note, the negative supply also acts as the alarm input ground) (pairs are polarity sensitive, thus do not invert).
» Fit the w ater detection sensor ensuring that it is lying at
the bottom of the tank.
Note: » By placing the w ater detection sensor at the bottom of the
fuel tank, an alarm is generated once the probe tip is
submerged w ith w ater (+/-10-13mm required). The probe needs to be raised if a higher alarm detection level is required.
» The w ater in diesel sensor alarm state could be tested
using SAM2 RMS03 serial diagnostic and configuration software or LCD display.
25. SAM2 RMS03 – Hybrid Battery Management
One of the primary functions of the SAM2 RMS03 is Hybrid battery charge/discharge monitoring and control. The main purpose of hybrid control is to gain maximum
operational cost reduction by reducing generator operation and utilizing the backup energy sources, such as batteries, solar and w ind turbines in an intelligent and controlled manner.
Hybrid battery management is mostly used in the follow ing manner: » Cycling of the BTS load supply betw een utility grid AC
mains, generator AC mains and backup battery bank.
» Indoor shelter type sites have the added component, temperature, to be monitored and managed.
The Hybrid Battery Management control logic can be configured in the follow ing manner, using the SAM2 RMS03 serial diagnostics and configuration software:
» A – Hybrid control could be configured to include any monitored alarm condition or threshold as follow s:
SAM2V3 Product Manual V2.1.4 37
Shelter temperature. Indoor shelter type sites run
the risk of high temperature conditions during a hybrid battery discharge cycle, due to air conditioners not running and not equipped w ith effective DC free cooling ventilation systems. A
shelter temperature could be configured (default
35C) at w hich the SAM2 RMS03 controller w ould suspend the hybrid cycle and start the generator to run the air conditioner unit.
Humidity. Typically for indoor shelter type sites, w hereby the generator would be started once
predefined humidity setpoint is exceeded. Rectif ier Override Control. The SAM2 RMS03
controller has the ability to except an external alarm/control signal to effectively control the hybrid
charge/discharge cycle. Override control is normally supported by hybrid rectif iers with the ability to control battery charge/discharge cycles.
» B – Hybrid control could be configured to use various
timers as follow s: Start and End Period. Due to excessive daytime
heat, indoor shelter type sites could be configured to activate a hybrid discharge cycle at certain times of the day only (nighttime w hen cooler). Tw o
independent daily time schedules could be configured.
Continuous. Hybrid cycle configured for continuous
operation, thus not time related. SAM2 RMS03 w ill activate battery charge/discharge based upon
monitored SoC (state of charge) or DoD (depth of discharge).
Alarm Inhibit. An alarm configured part of the inhibit
criteria w ill prevent a hybrid battery discharge cycle if active. The alarm needs to be present for a period
of 5min (default) before it has an effect on hybrid battery discharge activation. Only once the alarm has cleared for a period of 60min (default) w ould a
hybrid battery discharge cycle be activated. Any state change of the alarm in this group, during a hybrid battery discharge cycle would have no effect to discharge operation.
Alarm Suspend. An alarm configured part of the
suspend criteria w ill either prevent a hybrid battery discharge cycle from activating, or temporarily suspend the hybrid cycle once activated. The alarm has a programmable activation delay and requires to
be cleared for a period of 3min (default) before the hybrid battery discharge cycle would be activated. Any state change of the alarm during the hybrid battery discharge cycle would suspend hybrid
discharge and start the generator. Alarm Mask. Various alarms could be configured to
be masked during a hybrid battery discharge cycle. Alarms such as AC Mains and AC phase fail are masked. Reason being, these alarms are
automatically activated during a battery discharge cycle, but not relevant due to a controlled/scheduled event.
Boost Charge Cycle. Depending upon the battery
type being used for hybrid cycling, it may be necessary to periodically equalize or “overcharge” the battery to ensure it meets w ith the manufacturer’s specification and lifecycle. OPzV
batteries falls into this criteria and should be configured to be charged to 100% every x10 discharge cycles as a norm.
» C – Battery Monitoring. Default hybrid control utilizes the
follow ing battery criteria: Battery Bank Voltage. The battery bank DoD (depth
of discharge) is used to determine w hen the hybrid discharge cycle is ended, thereby starting the generator. The configured DoD is indicated as a
percentage to w hich the battery bank should be discharge. (do not exceed 80% DoD in order to prevent permanent battery damage)
Charge/Discharge Current. The battery current is continuously monitored during a battery discharge
and charge cycle. Effectively the calculated Ah
removed during a battery discharge is replaced during the battery charge cycle. The battery SoC (state of charge) is configured to replace the Ah removed during discharge plus the percentage offset
(overcharge), in order to compensate for equipment ineff iciencies.
» D – Utility Control. Utility grid AC mains pow er takes precedence over a hybrid battery discharge cycle. Once
utility grid AC mains fails: The generator is either started in test mode for 5
minutes (default) if it has not run in the last user configurable timeframe.
Hybrid battery discharge cycle activated, should all configured criteria be met (alarms, battery SoC) and
if the generator has run in the last user configurable timeframe.
Automated utility grid AC mains disconnect and
reconnect based upon configured upper and low er voltage limits.
» E – Generator Control. Remote start, stop and reset control of the generator. Automated control of the
generator w orks in conjunction with the monitored criteria as listed above.
» F – REC Control. Indoor shelter type sites DC ventilation system control (reduced energy cooling).
» G – Aircon Control. Indoor shelter type sites air conditioner control in terms of the follow ing: Aircon start/stop based upon shelter temperature.
Aircon single or dual operation based upon shelter
temperature. Aircon cycling based upon operational hours.
Aircon REC sw itchover based upon hybrid battery
discharge cycle and/or shelter temperature.
Hybrid Fail Reasons The SAM2 RMS03 controller has various reason codes as to w hy a hybrid battery discharge cycle does not activate. These
reason codes could be verif ied using the SAM2 RMS03 serial diagnostics and configuration software. The follow ing table refers to the meaning of each Hybrid Fail
Reason Code:
26. SAM2 RMS03 – Rectifier (SMPS) Alarm Monitoring
The SAM2 RMS03 controller through the cable termination unit makes provision to monitor three alarm indications from the installed rectif ier (SMPS). These inputs are dedicated to the SMPS, how ever should additional inputs be required, any
spare alarm inputs could be used for this purpose and configured accordingly. In general these dry contact digital alarm inputs are defined as follow s: (configurable using the SAM2 RMS03 serial diagnostic
and configuration software) R1 – Rectif ier 1 Fail (Module Fail - minor)
R2 – Rectif ier 2 Fail (System Fail - major)
HO – Hybrid Override (optional SMPS hybrid
control)
SAM2V3 Product Manual V2.1.4 38
Installation Steps:
» Make use of the general purpose alarm cable (2-pair, part
of w iring cable kit) and connect to the “REC Alarms” screw terminal connection on the SAM2 RMS03 cable termination unit.
» Connect R1 (blue), R2 (orange), HO (optional, spare) and
DG (both blue/w hite and orange/w hite) » R1 refers to Rectif ier non-urgent and R2 Rectif ier urgent
alarms.
» Connect the other end of the cable to the relevant SMPS non-urgent and urgent alarm relay output contacts.
» The HO input refers to the “Hybrid Override” control,
normally obtained from a SMPS w ith hybrid cycling capabilities. This input is optionally used in conjunction w ith a hybrid pow er system. This means the hybrid battery charge/discharge cycle is determined by the
hybrid SMPS and used by the SAM2 RMS03 controller for hybrid reporting purposes.
27. SAM2 RMS03 – Generic Sensors Intrusion Sensor
A robust magnetic type reed sw itch is used to alert against intrusion. The intrusion sensor could be used in the follow ing applications: » As shelter door intrusion.
» As generator canopy intrusion.
Installation Steps:
» Make use of the universal alarm cable (2-pair, part of w iring cable kit) to connect the intrusion sensor to the SAM2 RMS03 cable termination unit S1(blue) and GD (blue/w hite) connection of the “Spare I/PS” screw terminal
connector. S1 refers to spare alarm input 1 and GD to ground connection.
» The intrusion sensor is by default an N/C contact and the alarm input needs to be configured accordingly on the
SAM2 RMS03 controller.
» When using multiple intrusion sensors as used on the generator canopy doors, ensure to use a single pair of
universal alarm cable to interconnect all the sensors in parallel. Connect the open-ended side of the cable to the generator controller “DG Alarm Inputs” screw terminal,
input 8 (brow n) and GD (brow n/white). Ensure that “DG1 Door” alarm is configured as N/O input on the SAM2 RMS03 controller.
Note: » Ensure to test the intrusion alarms by closing/opening the
shelter door, all the generator doors and view ing the status of the each alarm. Open each door individually to
confirm alarm activation (should the alarm not clear/activate accordingly, investigate wiring).
Movement Sensor
An indoor shelter type movement PIR (passive infra-red) or an outdoor perimeter type movement PIR is available, both uses quad zone logic and provides multi segmented detection
zones throughout the detection area. An alarm signal is created by the cumulative total IR energy of each zone. It is designed to provide 4-8 zones for a human sized object, in order to provide sharp and maximum signals
for stable detection. Spot temperature changes, i.e. by rodents etc., may affect only one or tw o zones at the same time creating a smaller detection signal, thus f iltering out false alarm detection.
The SAM2 RMS03 is configured (default) to keep a triggered movement alarm active for a period of three minutes. This action prevents multiple alarm events for the same condition
as movement occurs within the detection area. The triggered movement alarm w ould only be cleared if no movement has been detected for a period of three minutes w ithin the monitored detection area.
The SAM2 RMS03 provides the auxiliary 12Vdc supply to pow er the movement sensor.
SAM2V3 Product Manual V2.1.4 39
Installation Steps: » Make use of the universal alarm cable (2-pair, part of
w iring cable kit) to connect the movement sensor to the
SAM2 RMS03 cable termination unit 12V (blue), GD (blue/w hite) and MA (orange) connection of the “Move” screw terminal connector. 12V refers to positive supply, GD to the negative supply and MA to the movement
alarm input. » Ensure to w ire the movement sensor according to the
same colors as indicated above. (Use a multi-meter to
verify polarity and DC supply output) Note: » Upon an activated alarm the SAM2 RMS03 w ill keep the
alarm activated until no movement is detected for the configured clear delay period.
Smoke Sensor
An optical smoke sensor is used due to proven stability in air movements associated w ith air conditioning systems, thus ideal selection for GSM BTS sites.
The sensor operates on the light scatter principal: Under normal conditions, light pulses in the Smoke Chamber do not reach the light sensor. With smoke in the Smoke
Chamber, light is deflected into the light sensor, triggering an alarm. The SAM2 RMS03 monitors both a smoke alarm, but also the
smoke sensor itself. Any malfunction or removal of the sensor from its base plate w ould result in an alarm (smoke detector alarm). The SAM2 RMS03 is configured (default) to keep a triggered
smoke alarm active for a period of three minutes, to ensure that no alarms are re-triggered as the smoke dissipates. The SAM2 RMS03 provides the auxiliary 24Vdc supply to
pow er the smoke sensor.
Installation Steps: » Make use of the universal alarm cable (2-pair, part of
w iring cable kit) to connect the smoke sensor to the
SAM2 RMS03 cable termination unit +P(blue) and -N (blue/w hite) connection of the “Smoke” screw terminal connector. +P refers to positive supply and -N to the negative supply. GD is not used.
» Ensure to w ire the smoke sensor according, terminal (5) refers to positive supply and terminal (3) to negative supply.
» Use a multi-meter to verify polarity and DC supply output
from SAM2 RMS03 on smoke sensor. (ensure to measure 24Vdc – confirm correct polarity)
Note: » Should the smoke sensor detect smoke w ithin the shelter,
a smoke alarm w ould be activated (the red LED on the smoke sensor w ould be active). Once the alarm is
activated, it w ould remain active for a period of three minutes (user configurable) before the alarm w ould clear, provided no additional smoke is detected w ithin the shelter.
» Upon an active smoke alarm condition both air conditioner units and DC ventilation system is shut down as a failsafe measure against possible fire venting.
Panic Sensor A w ater resistant push type button is used for the purpose of emergency panic situations.
An alarm w ill be generated once the button is pushed, in order to alert the NMC of a possible emergency situation.
The alarm w ill auto latch for a period of tw o minutes (user configurable) once pressed, whereby it w ill automatically reset.
Installation Steps: » Make use of the universal alarm cable (2-pair, part of
w iring cable kit) to connect the panic sensor to the SAM2
RMS03 cable termination unit S2(blue) and GD (blue/w hite) connection of the “Spare I/PS” screw terminal connector. S2 refers to spare alarm input 2 and GD to ground connection.
» Use the open-ended side of the cable and connect the blue and blue/w hite leads to N/C contact (blue and red leads) of the panic sensor. The N/O (green) lead is not
used and not connected.
28. SAM2 RMS03 – Mobile Phone SMS
Commands The SAM2 RMS03 mobile phone SMS commands is a feature
that provides the technician w ith the ability to retrieve vital information from the monitored site, using a SMS text message through a normal mobile handset.
The follow ing list of SMS text messages are available: » Send text message “Test010101” to management
server shortcode number. Management server responds with site SIM card’s mobile number and text “Working”. The above facility is used to test communications
betw een the SAM2 RMS03 controller SIM and the server shortcode. The test SMS is also available as a “Test Button” in the SAM2 RMS03 serial diagnostics and configuration software
» Send text message “TS” to site mobile number: Test
SAM. Response:
RMS Controller f irmw are number
Site ID
Date and Time
Number of active alarms
» Send text message “AS” to site mobile number:
Alarm Status Response:
Site ID
List of active alarms
(multiple sms’s may be transmitted should many alarms be active)
SAM2V3 Product Manual V2.1.4 40
» Send text message “AS##” to site mobile number: Alarm Status for Specific Alarm Number Response: Site ID
Alarm Name
Alarm Status (active, clear, disabled)
Date and Time
Refer to the follow ing default alarm numbers: Alarm 1 – DG1 Fault
Alarm 2 – DG1 Door
Alarm 3 – DG1 Running
Alarm 4 – Fuel Tank Lid
Alarm 5 – DG2 Fault
Alarm 6 – DG2 Door
Alarm 7 – DG2 Running
Alarm 8 – Utility AC Mains Fail
Alarm 9 – Rectif ier System Fail
Alarm 10 – Rectif ier Module Fail
Alarm 11 – Spare
Alarm 12 – Hybrid Override
Alarm 13 – Spare
Alarm 14 – Spare
Alarm 15 – Spare
Alarm 16 – Spare
Alarm 17 – Spare
Alarm 18 – Spare
Alarm 19 – DG2 on Load
Alarm 20 – DG2 Engine Temp
Alarm 21 – DG2 Oil Pressure
Alarm 22 – DG2 Emergency Stop
Alarm 23 – DG2 Water in Diesel
Alarm 24 – Mains on Load Alarm 25 – DG1 on Load
Alarm 26 – DG1 Engine Temp
Alarm 27 – DG1 Oil Pressure
Alarm 28 – DG1 Emergency Stop
Alarm 29 – DG1 Water in Diesel
Alarm 30 – Door Open (Intruder)
Alarm 31 – Panic Alarm
Alarm 32 – Movement
Alarm 33 – AC Phase Fail
Alarm 34 – Navigation Lights
Alarm 35 – Aircon 1 Pow er
Alarm 36 – Aircon 2 Pow er
Alarm 37 – Aircon 3 Pow er
Alarm 38 – Aircon 4 Pow er
Alarm 39 – Ventilation Fan Pow er
Alarm 40 – AC Mains Fail
Alarm 41 – Smoke Alarm
Alarm 42 – Smoke Detector
Alarm 43 – Aircon 1 Fail (Temp)
Alarm 44 – Aircon 2 Fail (Temp)
Alarm 45 – Aircon 3 Fail (Temp)
Alarm 46 – Aircon 4 Fail (Temp)
Alarm 47 – High Temperature
Alarm 48 – Very High Temperature
Alarm 49 – Multi AC (Dual Aircon)
Alarm 50 – 12V DC Fail
Alarm 51 – Config Corrupt
Alarm 52 – Fuel Tank1 Low
Alarm 53 – Fuel Tank1 Full
Alarm 54 – Fuel Tank2 Low
Alarm 55 – Fuel Tank2 Full
Alarm 56 – Fuel Probe1 Fail
Alarm 57 – DG Controller Fail
Alarm 58 – Utility Meter
Alarm 59 – Credit Low (not implemented)
Alarm 60 – Credit Very Low (not implemented)
Alarm 61 – Credit Zero (not implemented)
Alarm 62 – Humidity Probe
Alarm 63 – Humidity High
Alarm 64 – Modem Fail
Alarm 65 – Hybrid Active
Alarm 66 – Hybrid Cancelled
Alarm 67 – DG1 Start Fail
Alarm 68 – Mains Frequency
Alarm 69 – Fuel Removed
Alarm 70 – Fuel Added
Alarm 71 – DG1 Battery Low
Alarm 72 – Current Probe
Alarm 73 – A/C Service Due Alarm 74 – DG11 Service Due
Alarm 75 – Fuel Probe 2 Fail
Alarm 76 – BTS Battery Bank Low
Alarm 77 – DG2 Battery Low
Alarm 78 – DG2 Start Fail
Alarm 79 – DG Manual Override
Alarm 80 – DG2 Service Due
Alarm 81 – HEM 1
Alarm 82 – HEM 2
Alarm 83 – HEM 3
Alarm 84 – Solar Under Current
» Send text message “PS” to site mobile number: Power Status Response: Site ID
Pow er Alarm Status (active, clear, disabled)
» Send text message “HS” to site mobile number: Hybrid Status Response: Site ID
Hybrid Status (active, cancelled, disabled)
Battery Voltage
Battery Charge/Discharge Current
» Send text message “FS” to site mobile number: Fuel Status Response: Sites ID
Date and Time
Fuel tank related alarms (tank lid, fuel probe, fuel
removed, fuel f illed)
Fuel Level (in litres)
» Send text message “RG” to site mobile number:
Reset Generators Response, 120 seconds delayed as follows:
Site ID
Date and Time
Generator related alarms
Number of Active alarms
» Send text message “SG1” to site mobile number:
Start Generator 1 Response, 120 seconds delayed as follows:
Site ID
Date and Time
Generator related alarms
Number of active alarms
» Send text message “SG2” to site mobile number:
Start Generator 2 Response, 120 seconds delayed as follows:
Site ID
Date and Time
Generator related alarms
Number of active alarms
Note: » The generator reset and start SMS commands react
exactly the same as w hen executed using the SAM2
RMS03 serial diagnostics and configuration software or remote management platform.
» The sms text messages/commands are not case sensitive (HS, Hs, hS, hs).
SAM2V3 Product Manual V2.1.4 41
29. SAM2 RMS03 – RBS Alarm Outputs The SAM2 RMS03 controller through the cable termination unit
makes provision to provide sixteen general purpose (transistor) RBS alarm outputs, to be w ired to the BTS radio external alarm inputs. The SAM2 RMS03 controller has the ability to map any of the
monitored alarm inputs to any of the sixteen RBS alarm outputs, using the SAM2 RMS03 serial diagnostic and configuration software. Multiple alarm inputs could be mapped to a single alarm output. The alarm outputs could additionally
be configured as N/O or N/C. (N/C advisable to ensure alarm status is activated during a SAM2 RMS03 controller malfunction)
Installation Steps:
» Make use of the RBS alarm input cable (20-pair w ith subD37 pin male connector, part of w iring cable kit) to connect to the “BTS/RBS External Alarms” SubD37 pin female connector located on the SAM2 RMS03 cable
termination unit. » Ensure w hen working w ith the 20-pair cable that all pairs
are tw isted together, thus avoiding split pairs and unnecessary fault f inding.
» Wire the open end of the 20-pair RBS alarm input cable to relevant RBS external alarm inputs via the existing “DDF” type connection block. (the DDF terminations vary
from RBS type) » Wire the 20-pair RBS alarm input cable according to the
follow ing color scheme: (pairs are polarity sensitive, thus do not invert positive and negative legs).
Note: » The above alarm connections are just an example of
possible interconnection to the RBS radio equipment via
a (krone block type) DDF. Other varieties could be used on various sites.
» The alarm connections need to be tested on the SAM2 RMS03 controller by activating each individually to
ensure alarm activation w ithin the BTS radio. » Each alarm output could be inverted from N/C to N/O
using the SAM2 RMS03 serial diagnostic and
configuration software in order to conduct the above mentioned test. (ensure to restore the configuration once completed)
» By using a multimeter, each alarm can be tested on the
“SAM2 RBS Alarm Ouputs” krone block. Active alarms should indicate 0Vdc and inactive alarms 5Vdc or 24Vdc
(RBS type dependent). (referenced to A-leg being positive and B-leg being negative)
» The RBS alarm outputs could also be tested by simulating an alarm state change (on/off) using the SAM2
RMS03 LCD display – Diagnostic - Test BTS Alarms, menu.
END OF DOCUMENT