Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

23
Chamonix 2009 1 Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System Hugues Thiesen Acknowledgments: K. Dahlerup-Petersen, R. Denz, A. Funken, J. Gomez, V. Montabonnet, D. Nisbet, M. Zerlauth and HCC team

description

Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System. Hugues Thiesen. Acknowledgments:K. Dahlerup -Petersen, R. Denz , A. Funken , J. Gomez, V. Montabonnet , D. Nisbet , M. Zerlauth and HCC team. Contents. UPS overview - PowerPoint PPT Presentation

Transcript of Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

Page 1: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

Chamonix 2009 1

Risks due to UPS malfunctioningImpact on the Superconducting Circuit Protection System

Hugues Thiesen

Acknowledgments: K. Dahlerup-Petersen, R. Denz, A. Funken, J. Gomez, V. Montabonnet, D. Nisbet,M. Zerlauth and HCC team

Page 2: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

2

Contents

UPS overview UPS for Superconducting Circuit Protection System (CPS) Impact of UPS malfunction Actual Situation Conclusions

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

Page 3: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

3

UPS overview

TI 2

T I 8

S P S

In je c tio n

In je c tio n

B e am d um p

Point 5

Point 4

Point 2

Point 3

Point 6

Point 7

Point 1Point 8

Total UPS systems for LHC: > 60 (8 MVA)Total UPS systems for CPS: > 28 (56 UPS units)

CPS (28)Cryo (12)RF (2)General (8)SR (16)

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

Page 4: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

4

Human Safety Access* Fire detection*, ODH* Radiation Monitor*, etc…

Beam Systems Beam Instrumentation BIC, FMCM Beam Dump System RF Vacuum, etc…

Technical Network, etc… Cryogenic System SC Circuit Protection System

Power Converters PIC Energy Extraction System (EE) CLQD, GQD and MPS

UPS overviewRi

sks d

ue to

UPS

mal

func

tioni

ng, H

. Thi

esen

, Cha

mon

ix 2

009

Standard Systems use in all CERNaccelerators

Specific Systems use in LHC

* = internal UPS

Page 5: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

5

Particularities of Superconducting Circuits High current: up to 13 kA High energy stored: up to 1.4 GJ High current density: up to 1000A/mm2 High time constant: up to 400 sec (EE switches opened).

250 s (4 min) for RB to decrease the current from 13 kA to 1 kA800 s (14 min) for RQX to decrease the current from 7 kA to 1 kA

UPS for CPSRi

sks d

ue to

UPS

mal

func

tioni

ng, H

. Thi

esen

, Cha

mon

ix 2

009

Functionalities require for CPS Protect magnets Protect Current Leads Protect Bus-Bars Slow Abort the PCs in case of cryogenic warning Avoid to start without all systems fully operational Save data for analyzing

(UPS specification = 10 min. of autonomy)

Page 6: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

6

UPS_1

UPS_2 EODEBD

Equip.

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

UPS for CPS

UPS redundancy

Each UPS can deliver the requested power (10 min of autonomy) 2 orders of redundancy

If one UPS fails the load is supplied by the second UPS If the second UPS fails the load is supplied by the electrical network

Weak point = breakers (the number of breakers must be optimized and selectivity must be guaranteed)

Characteristics of UPS Network = Characteristics of General Network (see next slide)

F3a

Equip.F3b

Page 7: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

Main Parameters of the LHC 400/230V Electrical Network Nominal values

Nominal voltage: 400/230 V ± 10 % Nominal frequency: 50 Hz ± 0.5 Hz THD: 5 % Voltage unbalance: 2 %

Transients Peak mains surges: 1200 V for 0.2 ms Mains over voltage: 50 % of Un for 10 ms Voltage drops: 50 % of Un for 100 ms

EDMS # 113154: Main Parameters Of The LHC 400/230V Distribution System (G. Fernqvist / J. Pedersen)

UPS for CPS

7

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

Transients = Normal Operation

Page 8: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

8

UPS connected to the PIC Software link for PPermit

"Not possible" to start in case of one UPS warning /fault Hardware link for Energy Extraction (Fast_Abort)

Fast abort in case of two UPS warnings/faults (eg. batteries mode)

UPS_2UPS_1

PIC Supervision

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

UPS for CPS

PPermit

FastAbort

Page 9: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

9

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

C12L C34LR C12RIP8 IP7

UPS_UA83 UPS_RE82 UPS_RE78 UPS_UJ76

4 redundant UPS systems to protect 1 sector 1 UPS in UA => IT, IPQ and IPD 1 UPS in RE => C12L to C34L (77 MB and 24 MQ) 1 UPS in RE => C34R to C12R (77 MB and 24 MQ) 1 UPS in UJ => IT, IPQ and IPD

UPS for CPS

C2nC2n+1 C2n+1 C2n+1 C2n+1

C2n C2n C2n

Page 10: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

10

Diagnostic malfunction Supervision malfunction Interlock malfunction Etc…

Power malfunction Degradation of the output voltage 1 phase loss 3 phases loss Partial network loss Etc…

As for any other systems, the UPS systems can malfunction

Interlock malfunction

Total Loss of the output power

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

UPS for CPS

Page 11: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

11

Impact of UPS malfunction

Interlock malfunction

UPS_2UPS_1

PIC Supervision

If the interlock system of one UPS does not work The PIC does not stop the powering if the second UPS stops working

(UPS system in by-pass).

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

No action before loss of the UPS system output power

Page 12: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

12

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

QHPSCLQD GQDEEPICPC

SC Circuit Protection System Three protection systems

The Magnet Protection System (MQD + QHPS) The CL Protection System The Global Protection System

The Energy Extraction System The PIC The PC

Ref. M MQD

Impact of UPS malfunction

Power malfunction Cold PartWarm Part

Page 13: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

13

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

Impact on PC (1)

UPS for power converter Only DCCTs and FGC for high current power converters are on UPS (MB,

MQ, IPQ, IPD and IT). The power part is not supplied by UPS Gateway and computing network are on UPS to assure the control of

the PCs

PCFGC

CRGW

DCCT

FIPCCC Network

Page 14: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

14

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

Impact on PC (2)

PCFGC

CRGW

DCCT

FIPCCC Network

Loss of FGC and DCCT The power converter switches off The CR fires (not need power) PC PM data is lost The quench loop does not open (except if water failure)

Loss of GW After 10mn, all power converters connected on this GW switch off Their CR fire PC PM data is stored inside FGCs

Loss of Computing Network The control of the PC is lost (Only PC with PIC can be switched off). The 60A PCs can not be switched off

Page 15: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

15

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

Impact on EE system

ENCCC Network

Loss of EE system Electronic The Energy Extraction Switch opens The Quench Loop opens

The power converter switches off and its CR fires The EE system PM data is lost

Loss of communication with the CCC Nothing happens The EE system remains fully operational

Page 16: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

16

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

Impact on CLPS system

Loss of CLPS Electronic The Quench loop opens

The EE switch opens The power converter switches off and its CR fires

The CLPS PM data is lost Loss of the communication with the CCC

Nothing happens The CLPS remains fully operational

CLPSCCCNetwork

Page 17: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

17

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

Impact on GQPS system

Loss of GQPS Electronic The Quench loop opens

The EE switch opens The power converter switches off and its CR fires

The GQPS PM data is lost Loss of the communication with the CCC

Nothing happens The GQPS remains fully operational

CLPS GQPS Ref. M

CCC Network

Page 18: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

18

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

Impact on MQPS system (1)

MQPS Implemented only for the high current circuits (MB, MQ, IPQ, IPD and IT) For the IPQ, IPD and IT circuits, the MQPS protects also the busbars Single phase powering

QHPS The QHPS are not in the Quench Loop and can be only fired by the QD 4 QHPS per magnets and 1 is needed to protect correctly the magnet The QHPS are connected to the Power Permit

QD QHPSCCCNetwork

Page 19: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

19

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

Impact on MQPS system (2)

Loss of QD/QHPS (same single phase feeder) The Quench loop opens

The EE switch opens The power converter switches off and its CR fires

The MQPS PM data is lost To avoid a "sector quench" in case of UPS loss the QHPS are not fired. The

consequence is the magnet is not protected during the current decay. Loss of the communication with the CCC

Nothing happens The MQPS system remains fully operational

QD QHPSCCCNetwork

Page 20: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

20

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

Impact on PIC

PIC Level All HW interlock loops of this PIC open

All EE switches of concerned circuits open All power converters of concerned circuits switch off and their CR fire

The PIC PM data after the event is lost Loss of the communication with the CCC

Slow Abort after 30 seconds The currents of concerned circuits decays to 0 A

The PIC remains fully operational

PICCCCNetwork

Page 21: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

21

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

Resume

PC PIC EE CLQD GQD MPS*13kA ok ok ok ok ok nokIT ok ok - ok - nokIPQ/IPD ok ok - ok - nok600A-EE ok ok ok ok ok -600A-NoEE ok ok - ok ok -120A ok ok - ok - -60A ½ ok - - ok - -

Pb with MPS

No Issue

Issue with PC control

QHPSCLQD GQDEEPICPC Ref. M MQD

* To avoid a "sector quench" in case of UPS loss the QHPS are not fired.The consequence is the magnet is not protected during the current decay.

Page 22: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

22

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

Actual Situation

Tested UPS IST Devices IST

No tested Devices on UPS network (verification on going during AUG tests) UPS with theirs loads

Page 23: Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System

23

Risk

s due

to U

PS m

alfu

nctio

ning

, H. T

hies

en, C

ham

onix

200

9

Conclusions

Conclusions UPS has not been tested with its load. Tests of UPS systems (with load)

are recommended. New devices will be installed on UPS network (nQPS system). "AUG

tests" in operational conditions are recommended. UPS is important for the LHC safety. Annual tests after each shut down

are recommended. High Current magnets are not protected in case of UPS powering

failure. This issue must be clarified by MPWG (to fire or not to fire?). QHPS are not interlocked. This issue must be clarified by MPWG

(software interlock could be implemented?). The PM files are lost in case of UPS powering failure. 10 min of UPS autonomy are not enough to protect correctly the RQX

circuits (1.8 kA after 10 min). 20 min of autonomy are recommended. What is the situation for the other systems?