Analysis of Protection Malfunctioning in Meshed Distribution Grids

13
Frankfurt (Germany), 6-9 June 2011 Analysis of Protection Malfunctioning in Meshed Distribution Grids Evita PARABIRSING Dr. Edward COSTER Dr. Marjan POPOV Stedin- The Netherlands Stedin – The Netherlands TU Delft – The Netherlands [email protected] [email protected] [email protected] Paper 0374

description

Analysis of Protection Malfunctioning in Meshed Distribution Grids. Evita PARABIRSING Dr. Edward COSTER Dr. Marjan POPOV Stedin- The Netherlands Stedin – The Netherlands TU Delft – The Netherlands - PowerPoint PPT Presentation

Transcript of Analysis of Protection Malfunctioning in Meshed Distribution Grids

Page 1: Analysis of Protection Malfunctioning in Meshed Distribution Grids

Frankfurt (Germany), 6-9 June 2011

Analysis of Protection Malfunctioning in Meshed Distribution Grids

Evita PARABIRSING Dr. Edward COSTER Dr. Marjan POPOVStedin- The Netherlands Stedin – The Netherlands TU Delft – The [email protected] [email protected] [email protected]

Paper 0374

Page 2: Analysis of Protection Malfunctioning in Meshed Distribution Grids

Frankfurt (Germany), 6-9 June 2011

Introduction

Analysis of Short Circuits and Protection Relay Detection in a 25.6 kV Meshed Grid Section

Possible Solution Strategy

Conclusions

Evita N. Parabirsing – The Netherlands – RIF Session 3 – Paper 0374

Presentation Overview

Page 3: Analysis of Protection Malfunctioning in Meshed Distribution Grids

Frankfurt (Germany), 6-9 June 2011

Introduction Problem definition:

Short Circuit

If = If_1 + If_2

If

If_1

If_2

Directional Relay (DIR) mal-operation occurs in networks with similar construction

Page 4: Analysis of Protection Malfunctioning in Meshed Distribution Grids

Frankfurt (Germany), 6-9 June 2011

Analysis of Short Circuits and Protection Relay Detection in a 25.6 kV Meshed Grid Section

25.6 kV Meshed grid section

IOC= overcurrent relay DIR= directional

relay

Page 5: Analysis of Protection Malfunctioning in Meshed Distribution Grids

Frankfurt (Germany), 6-9 June 2011

Analysis of short circuits and circulating fault currents

0% 100%

Short Circuit

k

If

kZ1 (1-k)Z1

Cable length = 1.97

km

Page 6: Analysis of Protection Malfunctioning in Meshed Distribution Grids

Frankfurt (Germany), 6-9 June 2011

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2x 10

4

Fault Location (0%<k<100%)

Thre

e p

hase s

hort

circuit c

urr

ent,

If

IfIf2b

(If - If2b)

0% 100%

18 kA

3,2 kA

14,5 kA

30%

If – If_2b If_2b

I> 840 A

“Dead Zone”

Page 7: Analysis of Protection Malfunctioning in Meshed Distribution Grids

Frankfurt (Germany), 6-9 June 2011

For all types of short circuits there are certain ‘dead zones’ available in the network, caused by low fault currents which are detected by the directional relay (DIR)

System Fault Dead Zone Cable Length

Three Phase Faults0% < k < 8% ~ 160 m of 1,97 km

Double Phase Faults0% < k < 9% ~180 m of 1,97 km

Single Phase to Ground Faults

0% < k < 15% ~300 m of 1,97 km

Double Phase to Ground Faults

0% < k < 8% ~ 160 m of 1,97 km

Page 8: Analysis of Protection Malfunctioning in Meshed Distribution Grids

Frankfurt (Germany), 6-9 June 2011

Overview of ‘dead zones’ in the studied network

Page 9: Analysis of Protection Malfunctioning in Meshed Distribution Grids

Frankfurt (Germany), 6-9 June 2011

Possible solution strategy Is there a possibility that faults within the ‘dead zone’ could be

detected by the I>>, Ie>> settings of the IOC relays ?

Step 1: Detected fault currents for faults within ‘dead zone’

System Fault Within Dead Zone If(IOC)

Three Phase Faults 0% < k < 10% 15.6 kA < If(IOC) < 16 kA

Page 10: Analysis of Protection Malfunctioning in Meshed Distribution Grids

Frankfurt (Germany), 6-9 June 2011

Step 2: Detected fault currents for faults outside the protected area

System Fault Outside Dead Zone If(IOC)

Three Phase Faults 0% < k < 10% 11.4 kA

Page 11: Analysis of Protection Malfunctioning in Meshed Distribution Grids

Frankfurt (Germany), 6-9 June 2011

Proposed I>>, Ie>> and t>>, te>> settings of the IOC relays:

System Fault Inside Dead Zone Outside Dead Zone

Three Phase Faults 15.6 kA < If(IOC) < 16 kA If(IOC)=11.4 kA

I>> Ie>> t>>, te>>

11.4 kA < ( I>> ) < 15.6 kA 0.99 kA < (Ie>>) < 1.36 kA 0.3 seconds

V Z net

Load

IOC

IOC

IOC

DIR

DIR

DIR

Z1

Z2

Z3

Z4

Z5

I>> 14 kAt>> 0.3 secIe>> 1.2 kAte>> 0.3 secI> 840At> 2 secIe 120Ate 2 sec

I> 840At> 0.5 secIe 120Ate 0.5 sec

Page 12: Analysis of Protection Malfunctioning in Meshed Distribution Grids

Frankfurt (Germany), 6-9 June 2011

conclusions Analysis and Simulation results show that there exist ‘dead

zones’ within the protected zones of the studied network

‘Dead zones’ will always be available in network sections with single point of supply. The ‘dead zones’ are caused by the low magnitude of the fault current through the Directional relay

By activating and adjusting the I>>, Ie>> and t>>, te>> settings of the overcurrent protection relays in this study case, selective switching can be achieved for short circuits within ‘dead zones’

Page 13: Analysis of Protection Malfunctioning in Meshed Distribution Grids

Frankfurt (Germany), 6-9 June 2011

Thank You

Paper 0374: Analysis of Protection Malfunctioning in Meshed Distribution Grids

Evita PARABIRSING Dr. Edward COSTER Dr. Marjan POPOVStedin- The Netherlands Stedin – The Netherlands TU Delft – The [email protected] [email protected] [email protected]