37
OF REV: B SHEET Solid Edge 1 9 ACBL24 ACTIVE CHILLED BEAM LINEAR 24" WIDE 2016/05/17 PROJECT: ENGINEER: CUSTOMER: SUBMITTAL DATE: SPEC. SYMBOL: © Copyright PRICE INDUSTRIES 2017 Submittal Sheet ACTIVE CHILLED BEAM LINEAR 24" WIDE 266851 CT ACBL24-1-1 FACE STYLE: PERFORATED (SHOWN) BAR GRILLE NOZZLE SIZE: 309 416 412 406 510 STANDARD CONSTRUCTION: • ALL METAL ASSEMBLY • 20 GAUGE GALVANIZED STEEL • ALUMINUM FINS • COPPER WATER PIPING ELEVATION SEA LEVEL HIGH ALTITUDE ____________ FT FINISH COLOR (FACE) (VISIBLE FROM ROOM SIDE): B12 WHITE POWDER PAINT B25 SPECIAL POWDER PAINT PLENUM COLOR (NOT VISIBLE FROM ROOM SIDE): UNPAINTED GALVANEAL (DEFAULT) MATCH - MATCHES FINISH COLOR 506 607 604 601 1 7/8" u 1/4" INLET SIZE (D)*: 5" (127) ROUND 6" OVAL EQUIV. (4"Hx7"W) 8" OVAL EQUIV. (4"Hx10.125"W) *AIRFLOW NOT TO EXCEED 750 FPM ACTUAL LENGTH ( L ) 23 3/4" 17 1/16" FACE WIDTH 9 3/8" COOLING 6 1/4" HEATING NOMINAL WIDTH ACTUAL WIDTH (W) 24 23.75 NOMINAL ACTIVE COIL LENGTH LENGTH (L) DRY WET 24 23.750 25 27 36 35.750 38 41 48 47.750 50 55 60 59.750 63 68 72 71.750 75 82 84 83.750 88 95 96 95.750 100 109 108 107.750 113 123 120 119.750 125 136 IMPERIAL WEIGHT (lbs) COIL TYPE: 2P1C = 2 PIPE, 1 CIRCUIT 2P2C = 2 PIPE, 2 CIRCUIT 4P1C = 4 PIPE, 1 CIRCUIT 4P2C = 4 PIPE, 2 CIRCUIT DV = DRAIN & VENTS COIL CONNECTION: 1/2" SWEAT 1/2" NPT - FEMALE 1/2" NPT - MALE 1/2" NPT - 90º FEMALE DISCHARGE DIRECTION 2-WAY SHOWN DISCHARGE DIRECTION 9 1/2" COIL FINISH: UNPAINTED (DEFAULT) BLACK PAINTED COIL PRIMARY AIR CONNECTION WATER COIL CONNECTIONS MOUNTING BRACKETS PERFORATED OR GRILLE FACE NOTE: FACTORY TOLERANCE u 1/32" NOTE: WEIGHTS ARE FOR PERFORATED FACE UNITS **SEE SUBMITTAL 248924 FOR AVAILABLE HOSE AND VALVE PACKAGES INSULATION OPTIONS: 1/2" FIBERFREE - INTERNAL 1/2" FIBERFREE - EXTERNAL INTERNAL & EXTERNAL NONE (DEFAULT) DISCHARGE: 1W - ONE WAY 2W - TWO WAY

Transcript of Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe,...

Page 1: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: BSHEET

Sol

id E

dge

1 9

ACBL24 ACTIVE CHILLED BEAM LINEAR 24" WIDE

2016/05/17

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2017

Submittal Sheet ACTIVE CHILLED BEAM LINEAR 24" WIDE

266851

CT

ACBL24-1-1

FACE STYLE: PERFORATED

(SHOWN) BAR GRILLE

NOZZLE SIZE: 309 416 412 406 510

STANDARD CONSTRUCTION: • ALL METAL ASSEMBLY • 20 GAUGE GALVANIZED STEEL • ALUMINUM FINS • COPPER WATER PIPING

ELEVATION SEA LEVEL HIGH ALTITUDE ____________ FT

FINISH COLOR (FACE)(VISIBLE FROM ROOM SIDE): B12 WHITE POWDER PAINT B25 SPECIAL POWDER PAINT

PLENUM COLOR(NOT VISIBLE FROM ROOM SIDE): UNPAINTED GALVANEAL (DEFAULT) MATCH - MATCHES FINISH COLOR

506 607 604 601

1 7/8" u 1/4"

INLET SIZE (D)*: 5" (127) ROUND 6" OVAL EQUIV. (4"Hx7"W) 8" OVAL EQUIV. (4"Hx10.125"W)*AIRFLOW NOT TO EXCEED 750 FPM

ACTUAL LENGTH ( L )

23 3/4"

17 1/16"FACE WIDTH

9 3/8" COOLING

6 1/4" HEATING

NOMINAL WIDTH

ACTUAL WIDTH (W)

24 23.75NOMINAL ACTIVE COIL

LENGTH LENGTH (L) DRY WET24 23.750 25 2736 35.750 38 4148 47.750 50 5560 59.750 63 6872 71.750 75 8284 83.750 88 9596 95.750 100 109108 107.750 113 123120 119.750 125 136

IMPERIAL

WEIGHT (lbs) 

COIL TYPE: 2P1C = 2 PIPE, 1 CIRCUIT 2P2C = 2 PIPE, 2 CIRCUIT 4P1C = 4 PIPE, 1 CIRCUIT 4P2C = 4 PIPE, 2 CIRCUIT

DV = DRAIN & VENTS

COIL CONNECTION: 1/2" SWEAT 1/2" NPT - FEMALE 1/2" NPT - MALE 1/2" NPT - 90º FEMALE

DISCHARGEDIRECTION2-WAY SHOWN

DISCHARGEDIRECTION

9 1/2"

COIL FINISH: UNPAINTED (DEFAULT) BLACK PAINTED COIL

PRIMARY AIR CONNECTIONWATER COILCONNECTIONS

MOUNTINGBRACKETS

PERFORATED ORGRILLE FACE

NOTE: FACTORY TOLERANCE u 1/32"

NOTE: WEIGHTS ARE FOR PERFORATEDFACE UNITS

**SEE SUBMITTAL 248924 FORAVAILABLE HOSE AND VALVE PACKAGES

INSULATION OPTIONS: 1/2" FIBERFREE - INTERNAL 1/2" FIBERFREE - EXTERNAL INTERNAL & EXTERNAL NONE (DEFAULT)

DISCHARGE: 1W - ONE WAY 2W - TWO WAY

Page 2: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: BSHEET

Sol

id E

dge

2 9

ACBL24 ACTIVE CHILLED BEAM LINEAR 24" WIDE

2016/05/17

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2017

Submittal Sheet ACTIVE CHILLED BEAM LINEAR 24" WIDE

266851

CT

ACBL24-1-1

17 1/2" u 1" SPAN

3/4"

4 5/8"

NOMINAL LENGTH

16 11/16"MOUNTING BRACKET SPAN

5 5/8"

DETAIL A

1 3/8"

1 1/2"

A

MOUNTING BRACKET: FIXED (DEFAULT)

MOUNTING BRACKET: ADJUSTABLE

3 9/16"

1/2"

3/8"

B

DETAIL B

1"

3/8"

7/16"

1 1/2"

24" 36" 48" 60" 72" 84" 96" 108" 120"

QTY 4 4 4 4 8 8 12 12 12

FIXED BRACKET AMOUNT PER LENGTH

NOMINAL LENGTH

24" 36" 48" 60" 72" 84" 96" 108" 120"

QTY 4 4 4 4 4 6 6 6 6

DIN BRACKET AMOUNT PER LENGTH

NOMINAL LENGTH

NOMINAL LENGTH

Page 3: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: BSHEET

Sol

id E

dge

3 9

ACBL24 ACTIVE CHILLED BEAM LINEAR 24" WIDE

2016/05/17

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2017

Submittal Sheet ACTIVE CHILLED BEAM LINEAR 24" WIDE

266851

CT

ACBL24-1-1

2-WAY DISCHARGEINLET LOCATION OPTIONS: A - SIDE A B - SIDE B T - TOP

AIR DISCHARGES THIS DIRECTION(1-WAY DISCHARGE ONLY)

1-WAY DISCHARGECOIL LOCATION OPTION: RH - RIGHT HAND (DEFAULT) LH - LEFT HAND

SIDE B

SIDE A

TOP

L / 2

ACTUAL LENGTH ( L )

DOOR CAN HINGE ON BOTH SIDES

SIDE B(SAME SIDE AS DISCHARGE)

SIDE A

TOP

L / 2

ACTUAL LENGTH ( L )

DOOR CAN HINGE ON BOTH SIDES

COIL PIPING LOCATIONOPTION (SHOWN)

COIL PIPING LOCATIONOPTION (1-WAY ONLY)

COILPIPING

LEFT HAND (LH) RIGHT HAND (RH)

INLET LOCATION OPTIONS: A - SIDE A B - SIDE B T - TOP

(RH)(LH)

(NOT SELECTABLEFOR 2-WAY)

TOPVIEW

TOPVIEW

Page 4: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: BSHEET

Sol

id E

dge

4 9

ACBL24 ACTIVE CHILLED BEAM LINEAR 24" WIDE

2016/05/17

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2017

Submittal Sheet ACTIVE CHILLED BEAM LINEAR 24" WIDE

266851

CT

ACBL24-1-1

DAMPER OPTIONS (SHIPPED LOOSE):(DAMPERS SHOULD NOT BE MOUNTED DIRECTLY TO THE INLET AND SHOULD ONLY BE USED FOR TRIMMING AIRFLOW)

MQ5 - 5" DAMPER W/MANUAL LOCKING QUADRANT MQ6 - 6" DAMPER W/MANUAL LOCKING QUADRANT MQ8 - 8" DAMPER W/MANUAL LOCKING QUADRANT

VAV5 - 5" DAMPER W/ 24VAC FLOATING POINT ACTUATOR VAV6 - 6" DAMPER W/ 24VAC FLOATING POINT ACTUATOR VAV8 - 8" DAMPER W/ 24VAC FLOATING POINT ACTUATOR

O + 1/2" O + 1/2"

*SEE SUBMITTAL 255245 FOR AVAILABLE FIXEDVOLUME FLOW REGULATORS

Page 5: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: BSHEET

Sol

id E

dge

5 9

ACBL24 ACTIVE CHILLED BEAM LINEAR 24" WIDE

2016/05/17

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2017

Submittal Sheet ACTIVE CHILLED BEAM LINEAR 24" WIDE

266851

CT

ACBL24-1-1

ENCLOSURE OPENINGFOR WATER/ELECTRICAL CONNECTIONS

ABS12 - FACE ACCESSIBLE BLANK SECTION, COIL SIDE (ADD 12" TO ACTIVE COIL LENGTH) (LOCATED ON COIL CONNECTION END)

RET12 - RETURN/EXHAUST SECTION (ADD 12" TO ACTIVE COIL LENGTH)

ADS12 - ADDITIONAL AIR DIFFUSER SECTION (ADD 12" TO ACTIVE COIL LENGTH)

LOCATED OPPOSITE OF COIL CONNECTION END

* OVERALL LENGTH OF BEAM IS INCREASED BY 12". MAXIMUM OVERALL BEAM LENGTH IS 120".

LOCATED OPPOSITE OF COIL CONNECTION END.IF RETURN/EXHAUST ALSO SELECTED, RET IS BETWEENADS AND ACTIVE BEAM SECTION

* OVERALL LENGTH OF BEAM IS INCREASED BY 12". MAXIMUM OVERALL BEAM LENGTH IS 120".

ACTIVE COILLENGTH

NOMINAL 12"

ACTUAL LENGTHL + 12"

* OVERALL LENGTH OF BEAM IS INCREASED BY 12". MAXIMUM OVERALL BEAM LENGTH IS 120".

5 1/16"

+12"

5" O COLLAR

RET12 SHOWN,OPTIONAL

ADS125" O COLLAR

Page 6: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: BSHEET

Sol

id E

dge

6 9

ACBL24 ACTIVE CHILLED BEAM LINEAR 24" WIDE

2016/05/17

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2017

Submittal Sheet ACTIVE CHILLED BEAM LINEAR 24" WIDE

266851

CT

ACBL24-1-1

SLIM - SLIMLINE COUPLING

NOTES: UNITS SHOWN WITHOUT ANY ACCESSORIES UNITS SHIP SEPARATELY. ASSEMBLY ON SITE REQUIRED. GRILLE FACE IS NOT CONTINOUS

TOP

SIDE A

LEFT HAND (LH) RIGHT HAND (RH)

1-WAY DISCHARGES TO SIDE B INLET

SIDE B

COIL PIPINGLOCATION OPTION

(OPTIONAL)

COIL PIPING LOCATION OPTION

(SHOWN)

SLIMLINE SECTION 1(SLIM-1)

SLIMLINE SECTION MID(SLIM-MID)

SLIMLINE SECTION 2(SLIM-2)

BEAMS INSTALLED IN CONTINUOUS LENGTH WITH BUTT END JOINTS

ADDITIONAL MIDDLE BEAMSCAN BE ADDED

ALIGNMENT BRACKET ATTACHES ONEBEAM TO THE NEXT BY A SELF DRILLINGSCREW AND 10-32 SCREW (PROVIDED)

Page 7: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: BSHEET

Sol

id E

dge

7 9

ACBL24 ACTIVE CHILLED BEAM LINEAR 24" WIDE

2016/05/17

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2017

Submittal Sheet ACTIVE CHILLED BEAM LINEAR 24" WIDE

266851

CT

ACBL24-1-1

PATTERN CONTROLLERS ADJUSTABLE PATTERN CONTROLLERS

LOCATED IN DISCHARGE SLOT (FIELD ADJUSTABLE, FACTORY SET AT 0 DEGREE DEFLECTION)

ADJUSTABLEPATTERN CONTROLLERS

FACE DOES NOT HINGE,PULLS STRAIGHT DOWNWITH SAFETY TETHERS

45 DEGREES 30 DEGREES 15 DEGREES 0 DEGREE

VARIOUS PATTERN CONFIGURATIONS, CONTACTAPPLICATION ENGINEERING FOR ASSISTANCE

Page 8: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: BSHEET

Sol

id E

dge

8 9

ACBL24 ACTIVE CHILLED BEAM LINEAR 24" WIDE

2016/05/17

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2017

Submittal Sheet ACTIVE CHILLED BEAM LINEAR 24" WIDE

266851

CT

ACBL24-1-1

WNG6 - WING EXTENSIONS (ENDCAPS SHIPPED LOOSE)

35 7/8"

2 9/16"

PROTECTIVE FILM: PF - PROTECTIVE FILM

ON FACE AND AIR INLET

PEEL

Page 9: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: BSHEET

Sol

id E

dge

9 9

ACBL24 ACTIVE CHILLED BEAM LINEAR 24" WIDE

2016/05/17

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2017

Submittal Sheet ACTIVE CHILLED BEAM LINEAR 24" WIDE

266851

CT

ACBL24-1-1

15/16" TEGULAR EDGE

9/16" TEGULAR EDGESTANDARD EDGE

BORDER OPTIONS: STANDARD LAY-IN (DEFAULT) 9/16" TEGULAR 15/16" TEGULAR

3/16"

5/16"

3/8"

5/16"

Page 10: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: 0SHEET

Solid

Edg

e

1 6

ACBL-HE 12" WIDEACTIVE CHILLED BEAM LINEAR HIGH EFFICIENCY

2016/05/17

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2016

Submittal Sheet

12" WIDE ACTIVE CHILLED BEAM LINEAR - HIGH EFFICIENCY

266523

CT

** SEE SUBMITTAL 248924 FOR AVAILABLE HOSE AND VALVE PACKAGES

FACE STYLE:� PERFORATED (SHOWN)� BAR GRILLE (EXTRUDED ALUMINUM)

NOZZLE SIZE:� 10� 20� 30� 40

COIL FINISH:� UNPAINTED (DEFAULT)

� BLACK PAINTED COIL

STANDARD CONSTRUCTION: • ALL METAL ASSEMBLY • ALUMINUM FINS • COPPER WATER PIPING • STEEL NOZZLE PLATE

ELEVATION:� SEA LEVEL

� HIGH ALTITUDE ___________FT

CASING GAUGE:� 24 GAUGE (DEFAULT)

� 20 GAUGE

FINISH COLOR (FACE):(VISIBLE FROM ROOM SIDE):� B12 WHITE POWDER PAINT� B25 SPECIAL POWDER PAINT

PLENUM COLOR(NOT VISIBLE FROM ROOM SIDE):� UNPAINTED GALVANEAL (DEFAULT)� MATCH - MATCHES FINISH COLOR

� 50� 60� 70� 80

WATER COILCONNECTIONS

PRIMARY AIR CONNECTIOND - 1/8"

HINGED FACE(PERFORATED OR GRILLE)

ADJUSTABLE MOUNTINGBRACKETS SECURED BY #10-24 SCREWS(SCREWS PROVIDED BY OTHERS)DOOR CAN HINGE

BOTH SIDES(REMOVABLE)

INTEGRATED 1/4" (6) PRESSURE PORT(BALANCING/COMMISSIONING)

1 11/16" u 1/4"

* WEIGHTS ARE FOR PERFORATED FACE STYLE UNITS

USE 3/8" THREADED RODSTO SUSPEND TO CEILING(x L = 24" TO 72"),(x L = 84" TO 120")

INLET SIZE (D):� 5" ROUND� 6" ROUND (TOP ONLY)� 6" OVAL EQUIV. (4"Hx7"W)� 8" ROUND (TOP ONLY)� 8" OVAL EQUIV.

(4"Hx10"W)

NOTES: • FACTORY TOLERANCE +/- 1/32"

ACTIVE COIL LENGTH ( L )

5 5/8"

ACTUAL WIDTH ( W )

11 3/16" u 1"MOUNTING BRACKET SPAN

8 11/16"FACE WIDTH

10 3/16"

NOMINAL

SIZE

ACTUAL

WIDTH (W)

WIDTH 12 11.750

NOMINAL ACTIVE COIL

SIZE LENGTH (L) DRY WET

LENGTH 24 23.750 17 19

LENGTH 36 35.750 26 29

LENGTH 48 47.750 35 39

LENGTH 60 59.750 43 48

LENGTH 72 71.750 52 58

LENGTH 84 83.750 60 67

LENGTH 96 95.750 69 77

LENGTH 108 107.750 78 87

LENGTH 120 119.750 86 96

WEIGHT (lbs)

IMPERIAL

COIL TYPE:� 2P1C = 2 PIPE, 1 CIRCUIT� 2P2C = 2 PIPE, 2 CIRCUIT� 4P1C = 4 PIPE, 1 CIRCUIT� 4P2C = 4 PIPE, 2 CIRCUIT� 2P1C-DV = 2 PIPE, 1 CIRCUIT, w/ DRAIN & VENTS� 2P2C-DV = 2 PIPE, 2 CIRCUIT, w/ DRAIN & VENTS� 4P1C-DV = 4 PIPE, 1 CIRCUIT, w/ DRAIN & VENTS� 4P2C-DV = 4 PIPE, 2 CIRCUIT, w/ DRAIN & VENTS

COIL CONNECTION:� 1/2" SWEAT� 1/2" NPT - FEMALE

DISCHARGEDIRECTION

DISCHARGEDIRECTION

Y

X

X Y

LENGTH 24 3.000 1.000

LENGTH 36 6.000 1.000

LENGTH 48 12.000 4.250

LENGTH 60 12.000 4.250

LENGTH 72 12.000 4.250

LENGTH 84 12.000 4.250

LENGTH 96 36.000 4.250

LENGTH 108 36.000 4.250

LENGTH 120 48.000 4.250

NOMINAL BEAM

LENGTH

MOUNTING DETAIL

2-WAY SHOWN

INSULATION:� 1/8" FIBERFREE - INTERNAL

� 1/2" FIBERGLASS - EXTERNAL� INTERNAL & EXTERNAL

Page 11: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: 0SHEET

Solid

Edg

e

2 6

ACBL-HE 12" WIDEACTIVE CHILLED BEAM LINEAR HIGH EFFICIENCY

2016/05/17

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2016

Submittal Sheet

12" WIDE ACTIVE CHILLED BEAM LINEAR - HIGH EFFICIENCY

266523

CT

2-WAY DISCHARGEINLET LOCATION OPTIONS:� A - SIDE A� B - SIDE B� T - TOP

SIDE B

SIDE A

TOP

DOOR CAN HINGE ON BOTH SIDES

(NOT SELECTABLEFOR 2-WAY)

1-WAY DISCHARGECOIL LOCATION OPTION:� RH - RIGHT HAND (DEFAULT)� LH - LEFT HAND

AIR DISCHARGES THIS DIRECTION(1-WAY DISCHARGE ONLY)

COIL PIPING LOCATIONOPTION (SHOWN)

COIL PIPING LOCATIONOPTION (1-WAY ONLY)

ACTIVE COIL LENGTH ( L )

L / 2

COIL PIPING LOCATION

LEFT HAND (LH) RIGHT HAND (RH)

ONLY SIDE B INLETLOCATION IS AVAILABLE

L / 2

ACTIVE COIL LENGTH (L)

Page 12: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: 0SHEET

Solid

Edg

e

3 6

ACBL-HE 12" WIDEACTIVE CHILLED BEAM LINEAR HIGH EFFICIENCY

2016/05/17

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2016

Submittal Sheet

12" WIDE ACTIVE CHILLED BEAM LINEAR - HIGH EFFICIENCY

266523

CT

DAMPER OPTIONS (SHIPPED LOOSE):(DAMPERS SHOULD NOT BE MOUNTED DIRECTLY TO THE INLET AND SHOULD ONLY BE USED FOR TRIMMING AIRFLOW)

� MQ5 - 5" DAMPER W/MANUAL LOCKING QUADRANT� MQ6 - 6" DAMPER W/

MANUAL LOCKING QUADRANT� MQ8 - 8" DAMPER W/

MANUAL LOCKING QUADRANT

� VAV5 - 5" DAMPER W/ 24VAC FLOATING POINT ACTUATOR� VAV6 - 6" DAMPER W/ 24VAC FLOATING POINT ACTUATOR� VAV8 - 8" DAMPER W/ 24VAC FLOATING POINT ACTUATOR

O + 1/2" O + 1/2"

*SEE SUBMITTAL 255245 FOR AVAILABLE FIXEDVOLUME FLOW REGULATORS

Page 13: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: 0SHEET

Solid

Edg

e

4 6

ACBL-HE 12" WIDEACTIVE CHILLED BEAM LINEAR HIGH EFFICIENCY

2016/05/17

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2016

Submittal Sheet

12" WIDE ACTIVE CHILLED BEAM LINEAR - HIGH EFFICIENCY

266523

CT

���� ABS12 - FACE ACCESSIBLE BLANK SECTION, COIL SIDE (ADD 12" TO ACTIVE COIL LENGTH) (LOCATED ON COIL CONNECTION END)

���� RET12 - RETURN/EXHAUST SECTION (ADD 12" TO ACTIVE COIL LENGTH)

���� ADS12 - ADDITIONAL AIR DIFFUSER SECTION (ADD 12" TO ACTIVE COIL LENGTH)���� ADS24 - ADDITIONAL AIR DIFFUSER SECTION

(ADD 24" TO ACTIVE COIL LENGTH)

O 7 7/8"

LOCATED OPPOSITE OF COIL CONNECTION END

* OVERALL LENGTH OF BEAM IS INCREASED BY 12" MAXIMUM OVERALL BEAM LENGTH IS 120"

LOCATED OPPOSITE OF COIL CONNECTION END.IF RETURN/EXHAUST ALSO SELECTED, ADS IS BETWEENRETURN/EXHAUST AND ACTIVE BEAM SECTION

* OVERALL LENGTH OF BEAM IS INCREASED BY 12" MAXIMUM OVERALL BEAM LENGTH IS 120"

RET12 SHOWN, OPTIONAL

O4 7/8"

* MAXIMUM OVERALL BEAM LENGTH IS 120"

NOMINAL 12"

NOMINAL12" OR24"

INLET SIDE���� A���� B���� T

Page 14: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: 0SHEET

Solid

Edg

e

5 6

ACBL-HE 12" WIDEACTIVE CHILLED BEAM LINEAR HIGH EFFICIENCY

2016/05/17

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2016

Submittal Sheet

12" WIDE ACTIVE CHILLED BEAM LINEAR - HIGH EFFICIENCY

266523

CT

���� SLIM - SLIM-LINE COUPLING NOTES: UNITS SHOWN WITHOUT ANY ACCESSORIES UNITS SHIP SEPARATELY. ASSEMBLY ON SITE REQUIRED GRILLE FACE IS NOT CONTINOUS

BEAMS INSTALLED IN CONTINUOUS LENGTH WITH BUTT END JOINTS

BEAMS INSTALLED IN CONTINUOUS LENGTH WITH BUTT END JOINTS

ALIGNMENT BRACKET SLIDES FROM ONE BEAM TO NEXT AFTER INSTALLATION, AND LOCKS IN PLACE SIMILARTO BEAM MOUNTING BRACKET(SCREWS PROVIDED BY OTHERS)

11 3/4"

OVERALL LENGTH

PIN LATCHES TO OPEN FACES

SLIMLINE SECTION 1(SLIM-1)

SLIMLINE SECTION 2(SLIM-2)

SLIMLINE SECTION MID(SLIM-MID)

ADDITIONAL MIDDLE BEAMSCAN BE ADDED

SIDE B

TOP

SIDE A

COIL PIPINGLOCATION OPTION

(OPTIONAL)LEFT HAND (LH)

COIL PIPING LOCATION OPTION

(SHOWN)RIGHT HAND (RH)

1-WAY DISCHARGES TO SIDE B INLET ONLY

Page 15: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: 0SHEET

Solid

Edg

e

6 6

ACBL-HE 12" WIDEACTIVE CHILLED BEAM LINEAR HIGH EFFICIENCY

2016/05/17

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2016

Submittal Sheet

12" WIDE ACTIVE CHILLED BEAM LINEAR - HIGH EFFICIENCY

266523

CT

PROTECTIVE FILM:� PF - PROTECTIVE FILM

ON FACE AND AIR INLET

PEEL

���� WNG6 - WING EXTENSIONS (SHIPPED ASSEMBLED)

OVERALL LENGTH+ 3/4"

23 3/4"

10 3/16"3 5/8"

Page 16: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV:G

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET

Solid

Edg

e

1 2

PCBLPASSIVE CHILLED BEAM LINEAR

2012/09/04

254721

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2012

Submittal Sheet

STANDARD CONSTRUCTION: • ALL METAL ASSEMBLY • EXTRUDED ALUMINUM FINS • ALUMINUM PERFORATED FACE • COPPER WATER PIPING • DRAIN AND VENTS ON WATER COIL • HOUSING, STEEL 24 GA

FINISH:� B17 BLACK PAINT� B12 WHITE PAINT� OTHER

NOTES: • FACTORY TOLERANCE +/- 1/32" (1)

** SEE SUBMITTAL 248924 FOR AVAILABLE HOSE AND VALVE PACKAGES

FACE STYLE:� PERFORATED

ALUMINUM� BAR GRILLE

(EXTRUDED ALUMINUM)� NONE (SHOWN)

END CONDITIONOPTIONS:� 1/2" SWEAT� 1/2" NPT

(FEMALE)

* ANY COMBINATION OF THE ABOVE WIDTHAND LENGTH CAN BE SELECTED

NATURAL CONVECTION AIR FLOWADJUSTABLE MOUNTING

BRACKETS

OPTIONAL FACE(PERFORATED OR BAR GRILLE)

PCBL - PASSIVE CHILLED BEAM LINEAR

USE 5/16" (8) THREADED RODSTO SUSPEND TO CEILING.X2 FOR LENGTHS 84" (2100) AND LESSX3 FOR LENGTHS 96" (2400) AND GREATER

WATERCONNECTIONS

10.000 (254)

11.750 (298)

W

W - 1/4" (6)

PROTECTIVE FILM:� PF - PROTECTIVE FILM ON FACE AND COIL

.900(23)

4.000(102)

L

W - 5.200 (132)

2.600 (66)

2.600 (66)

NOMINAL

SIZE

ACTUAL SIZE

(W)

NOMINAL

SIZE

ACTUAL SIZE

(W)

WIDTH 12 11.750 (298) 300 11.575 (294)

WIDTH 18 17.750 (451) 450 17.480 (444)

WIDTH 24 23.750 (603) 600 23.386 (594)

NOMINAL

SIZE

ACTUAL SIZE

(L)

NOMINAL

SIZE

ACTUAL SIZE

(L)

LENGTH 24 23.750 (603) 600 23.386 (594)

LENGTH 36 35.750 (908) 900 35.197 (894)

LENGTH 48 47.750 (1213) 1200 47.008 (1194)

LENGTH 60 59.750 (1518) 1500 58.819 (1494)

LENGTH 72 71.750 (1822) 1800 70.630 (1794)

LENGTH 84 83.750 (2127) 2100 82.441 (2094)

LENGTH 96 95.180 (2418) 2400 94.252 (2394)

LENGTH 108 107.750 (2737) 2700 106.063 (2694)

LENGTH 120 119.750 (3042) 3000 117. 874 (2994)

-

IMPERIAL METRIC

DRY WET DRY WET DRY WET

LENGTH 24 12 13 14 16 17 19

LENGTH 36 17 20 21 24 25 29

LENGTH 48 23 26 28 32 33 38

LENGTH 60 28 32 34 40 41 47

LENGTH 72 33 39 41 48 49 57

LENGTH 84 39 45 48 56 57 66

LENGTH 96 45 52 56 65 66 77

LENGTH 108 50 59 62 72 74 86

LENGTH 120 56 65 69 80 82 96

NOMINAL SIZE

12" WIDE 18" WIDE 24" WIDE

WEIGHT (lbs)

1.000 (25)

W - 2.000 (51)

1.000 (25)

W

* WEIGHTS ARE WITH PERFORATED FACE

Page 17: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV:G

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET

Solid

Edg

e

2 2

PCBLPASSIVE CHILLED BEAM LINEAR

2012/09/04

254721

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2012

Submittal Sheet

PCBL - PASSIVE CHILLED BEAM LINEAR

���� - AF : ACTIVE FACE OPTION TO MATCH ACBL LOOK

ACTIVE FACE STYLE:� AFP - PERFORATED

ALUMINUM� AFG - BAR GRILLE

(EXTRUDED ALUMINUM)

END CONDITIONOPTIONS:� 1/2" SWEAT� 1/2" NPT (FEMALE)

STANDARD CONSTRUCTION: • ALL METAL ASSEMBLY • EXTRUDED ALUMINUM FINS • ALUMINUM PERFORATED FACE • COPPER WATER PIPING • DRAIN AND VENTS ON WATER COIL • ACBL STYLE MOUNTING BRACKET • HOUSING, STEEL 24 GA

FINISH:� BLK - B17 BLACK INTERIOR PAINT WITH B12 WHITE FACE� B12 WHITE POWDER COAT

NOTES: • FACTORY TOLERANCE +/- 1/32" (1)

WATERCONNECTIONS NATURAL CONVECTION

AIR FLOW

W

L

24" (600 mm) NOMINAL WIDTH

W

HINGED FACE(PERFORATED OR GRILLE)

HINGED SIDE

ADJUSTABLE MOUNTINGBRACKETS

10.000(254)

10.000(254)

ACBL STYLEMOUNTING BRACKET

ACBL STYLEMOUNTING BRACKET

USE 3/8" (8) THREADED RODSPER BRACKET TO SUSPEND TO CEILINGX4 FOR LENGTHS 84" (2100) AND LESSX6 FOR LENGTHS 96" (2400) AND GREATER2.500

(64)

12" (300 mm) NOMINAL WIDTH

W

W - 6.000 (152)

11.600MOUNTING BRACKETSPAN

18.600 (MOUNTING BRACKET SPAN)

1.000 (25) 9.750 (248)

15.750 (400)1.000(25)

9.200(234)

7.824(199)

7.824(199)

9.200(234)

1.000 (25)

1.000 (25)

* WEIGHTS ARE WITH PERFORATED FACE

DRY WET DRY WET

LENGTH 24 12 13 14 16

LENGTH 36 17 20 21 24

LENGTH 48 23 26 28 32

LENGTH 60 28 32 34 40

LENGTH 72 33 39 41 48

LENGTH 84 39 45 48 56

LENGTH 96 45 52 56 65

LENGTH 108 50 59 62 72

LENGTH 120 56 65 69 80

NOMINAL SIZE

12" WIDE 18" WIDE

WEIGHT (lbs)

Page 18: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV B

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET 1 1

PCBL-R

PASSIVE CHILLED BEAM LINEAR

W/ INTEGRATEDRETURN

259760

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2012

Submittal Sheet

PCBL-R : PASSIVE CHILLED BEAM LINEAR W/ INTEGRATED RETURN

2012/09/04

INTEGRATED RETURNPLENUM

WATERCONNECTIONS

W

ADJUSTABLE MOUNTINGBRACKETS

USE 5/16" (8) THREADED RODSTO SUSPEND TO CEILINGX2 FOR LENGTH 84" (2100) AND LESSX3 FOR LENGTHS 96" (2400) AND GREATER

OPTIONAL FACE(PERFORATED OR BAR GRILLE)

12.000(305)

14.400(366)

W - 1/4" (6)

** SEE SUBMITTAL 248924 FOR AVAILABLE HOSE AND VALVE PACKAGES

FACE STYLE:� PERFORATED ALUMINUM� BAR GRILLE

(EXTRUDED ALUMINUM)� NONE (SHOWN)

END CONDITIONOPTIONS:� 1/2" SWEAT� 1/2" NPT (FEMALE)

* ANY COMBINATION OF THE ABOVE WIDTH AND LENGTH CAN BE SELECTED

STANDARD CONSTRUCTION: • ALL METAL ASSEMBLY • EXTRUDED ALUMINUM FINS • ALUMINUM PERFORATED FACE • COPPER WATER PIPING

FINISH:� B17 BLACK PAINT� B12 WHITE PAINT� OTHER

NOTES: • FACTORY TOLERANCE +/- 1/32" (1)

PROTECTIVE FILM:� PF - PROTECTIVE FILM

ON FACE AND COIL

NOMINAL

SIZE

ACTUAL SIZE

(W)

NOMINAL

SIZE

ACTUAL SIZE

(W)

WIDTH 24 23.750 (603) 600 23.386 (594)

DRY WET

LENGTH 24 23.750 (603) 600 23.386 (594) 21 24

LENGTH 36 35.750 (908) 900 35.197 (894) 31 36

LENGTH 48 47.750 (1213) 1200 47.008 (1194) 41 48

LENGTH 60 59.750 (1518) 1500 58.819 (1494) 51 60

LENGTH 72 71.750 (1822) 1800 70.630 (1794) 61 72

LENGTH 84 83.750 (2127) 2100 82.441 (2094) 71 84

LENGTH 96 95.180 (2418) 2400 94.252 (2394) 81 95

LENGTH 108 107.750 (2737) 2700 106.063 (2694) 91 107

LENGTH 120 119.750 (3042) 3000 117. 874 (2994) 101 119

IMPERIAL METRIC

NOMINAL

SIZE

ACTUAL SIZE

(L)

NOMINAL

SIZE

ACTUAL SIZE

(L)

WEIGHT (lbs)

* WEIGHTS ARE WITH PERFORATED FACE

7.900(201)

9.200(234)

4.000(102)

L

7.000 (178)

9.750 (248)

7.000 (178)

2.600 (66)

W - 5.000 (132)

2.600 (66)

1.300 (33)

Page 19: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

ACBM

254720

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

Submittal Sheet

ACBM - 4 WAY ACTIVE CHILLED BEAM MODULAR

2012/04/12

ACTIVE CHILLED BEAM MODULAR 4-WAY

OF REV: FSHEET 1 1© Copyright PRICE INDUSTRIES 2011

** SEE SUBMITTAL 248924 FOR AVAILABLE HOSE AND VALVE PACKAGES

W

7.000(178)

L

L/2 W/2

1.500 (38)

USE 3/8" THREADED RODSTO SUSPEND TO CEILING.

PRIMARYAIR CONNECTION(D - 1/8")

23.620 (600)(MOUNTINGBRACKETS)

REMOVABLE FACE(PERFORATED OR GRILLE)

ADJUSTABLE MOUNTINGBRACKETS (LOCKABLE)

HEATING WATER CONNECTIONS(NOT SUPPLIED ON 2 PIPE)

COOLING WATERCONNECTIONS

NOZZLE SIZE:� 20� 30� 40� 50� 60� 70

INLET SIZE (D):� 5" (125)� 6" (152)� 8" (203)

COIL TYPE:� 2 PIPE, 1 CIRCUIT� 4 PIPE, 1 CIRCUIT

4 WAY AIR DISCHARGE

NOMINAL

SIZE

ACTUAL SIZE

(W)

NOMINAL

SIZE

ACTUAL SIZE

(W)

WIDTH 24 23.750 (603) 600 23.386 (594)

NOMINAL

SIZE

ACTUAL SIZE

(L)

NOMINAL

SIZE

ACTUAL SIZE

(L)

LENGTH 24 23.750 (603) 600 23.386 (594)

LENGTH 48 47.750 (1213) 1200 47.008 (1194)

IMPERICAL METRIC

-

FACE STYLE:� PERFORATED ALUMINUM (SHOWN)� BAR GRILLE

(EXTRUDED ALUMINUM)

PIPING CONNECTION:� 1/2" SWEAT� 1/2" NPT - FEMALE (SHIPPED LOOSE)

STANDARD CONSTRUCTION: • ALL METAL ASSEMBLY • ALUMINUM FINS • COPPER WATER PIPING • STEEL NOZZLE PLATE • 24 GAUGE STEEL CONSTRUCTION

FINISH (FACE):� B17 BLACK POWDER PAINT� B12 WHITE POWDER COAT

INTERIOR COLOR:� B17 BLACK POWDER PAINT (DEFAULT)� B12 WHITE POWDER COAT

NOTES: • FACTORY TOLERANCE +/- 1/32" (1)

INTEGRATED 1/4" PRESSURE PORT(BALANCING/COMMISSIONING)(ACCESSIBLE FROM FACE SIDE)

INSULATION:� 1/8" FIBERFREE - INTERNAL� 1/2" FIBERGLASS - EXTERNAL� INTERNAL & EXTERNAL

PROTECTIVE FILM:� PF - PROTECTIVE FILM

ON FACE AND INLET

4.700(119)

14.400(366)

9.400(239)

7.100(181)

NOTE: WEIGHTS ARE FOR A PERFORATED FACE STYLE UNIT

DRY WET

24" x 24" 30 33

24" x 48" 47 53

24" x 24" 30 34

24" x 48" 47 55

WEIGHT (lbs)NOMINAL SIZE

(W x L)

COIL

TYPE

2 PIPE

4 PIPE

41.409(1052)

Page 20: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: 0SHEET

Sol

id E

dge

1 5

ACBR ACTIVE CHILLED BEAM RECESSED

2017/05/9

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2017

Submittal SheetACBR - ACTIVE CHILLED BEAM RECESSED

268015

KHH

ACBR-1-1

STANDARD CONSTRUCTION: • ALL METAL ASSEMBLY • ALUMINUM FINS • COPPER WATER PIPING • 20 GAUGE STEEL CONSTRUCTION

ELEVATION: SEA LEVEL HIGH ALTITUDE ________FT

FINISH: UNPAINTED GALVANNEAL

(STANDARD) SPECIAL COLOR

INSULATION: 1/2" FIBERFREE - INTERNAL 1/2" FIBERFREE - EXTERNAL INTERNAL & EXTERNAL

COIL TYPE: 2P1C = 2 PIPE, 1 CIRCUIT 2P2C = 2 PIPE, 2 CIRCUIT 4P1C = 4 PIPE, 1 CIRCUIT 4P2C = 4 PIPE, 2 CIRCUIT

DV = DRAIN AND VENT

NOZZLE SIZE: 406 605 506 603 608 601

PROTECTIVE FILM: PF - PROTECTIVE FILM ON WATERCOIL, INLET, AND OUTLET

NOTES: • FACTORY TOLERANCE +/- 1/32"

** SEE SUBMITTAL 248924 FORAVAILABLE HOSE AND VALVEPACKAGES.

INLET SIZE: 3" ROUND 4" ROUND 5" OVAL EQUIV. (4"X6") 6" OVAL EQUIV. (4"X7") * 5", 6" INLET ONLY AVAILABLE INC/D/E INLET LOCATIONS

DRAIN PAN: DRAIN PAN

* DRAIN PAN ONLY AVAILABLE FORVD, VU ORIENTATION

LINT SCREEN: LINT SCREEN

PIPING CONNECTION: 1/2" SWEAT 1/2" NPT - MALE 1/2" NPT - FEMALE

** SEE PRICE CATALOG SECTIONS A AND D FOR SUPPLY /INDUCTION DIFFUSERS & GRILLES, TRANSITIONS TO BEFIELD FABRICATED & INSTALLED BY OTHERS.

NOMINAL 

LENGTHDRY (LBS) WET (LBS)

24 36 38

36 53 57

48 69 74

60 86 92

72 102 109

84 119 127

96 135 144

UNIT WEIGHT

NOTE: DETAILED DIMENSIONSSHOWN ON PAGE 2, 3, AND 4.

OPTIONAL REMOVABLE DRAIN PAN

OPTIONAL REMOVABLELINT SCREEN

FIXED MOUNTING BRACKET

1/2" MNPT PIPE SIZEDRAIN PAN CONNECTION

O1/2" OD SWEAT COILCONNECTIONS

VERTICAL DOWN (VD) ORIENTATION, LH COIL CONNECTION SHOWN

Page 21: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: 0SHEET

Sol

id E

dge

2 5

ACBR ACTIVE CHILLED BEAM RECESSED

2017/05/9

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2017

Submittal SheetACBR - ACTIVE CHILLED BEAM RECESSED

268015

KHH

ACBR-1-1

INSTALLATION ORIENTATION: VD = VERTICAL DOWN VU = VERTICAL UP H = HORIZONTAL

** NOTE: DRAIN PAN NOT AVAILABLE FOR HORIZONTAL ORIENTATION.

VD (VERTICAL DOWN)ORIENTATION

VU (VERTICAL UP)ORIENTATION

H (HORIZONTAL)ORIENTATION

9.000

7.000

OUTLET AIR

SECONDARY AIR

PRIMARY AIR

OUTLET AIR

SECONDARY AIR

OUTLET AIR

SECONDARY AIRPRIMARY AIR

PRIMARY AIR

17.000

2.029.432

3.482DISCHARGE WIDTH

DRAIN PAN LOCATION DRAIN PAN LOCATION

4.6662.029

Page 22: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: 0SHEET

Sol

id E

dge

3 5

ACBR ACTIVE CHILLED BEAM RECESSED

2017/05/9

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2017

Submittal SheetACBR - ACTIVE CHILLED BEAM RECESSED

268015

KHH

ACBR-1-1

NOMINAL LENGTH UNIT SIZE (L)OVERALL LENGTH 

(L1)

VD, VU MOUNTING 

LENGTH (L2)

SUPPORT MOUNTING 

LENGTH (L3)

H MOUNTING 

LENGTH (L4)24 24.000 24.906 21.924 14.357 25.000

36 36.000 36.906 33.924 17.786 37.000

48 48.000 48.906 45.924 21.214 49.000

60 60.000 60.906 57.924 24.643 61.000

72 72.000 72.906 69.924 28.071 73.000

84 84.000 84.906 81.924 31.500 85.000

96 96.000 96.906 93.924 34.929 97.000

DIMENSIONS

MOUNTING BRACKETS FOR H ORIENTATION

MOUNTING BRACKETS FOR VD AND VU ORIENTATIONS

L4

L3

15.000

1.000

L L2

L1

L3

8.0009.000

3.750

L

3.750

.500

CENTER MOUNTING BRACKETS ONLYFOR NOM. LENGTH OF 72" AND UP.

CENTER MOUNTING BRACKETS ONLYFOR NOM. LENGTH OF 72" AND UP.

OUTLET AIR

SECONDARY AIR

OUTLET AIR

L1

1.930INLET COLLAR

1.000BRACKET WIDTH

1.649DRAIN PAN EXTENSION

OUTLET AIR

Page 23: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: 0SHEET

Sol

id E

dge

4 5

ACBR ACTIVE CHILLED BEAM RECESSED

2017/05/9

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2017

Submittal SheetACBR - ACTIVE CHILLED BEAM RECESSED

268015

KHH

ACBR-1-1

INLET LOCATION OPTIONS: A - SIDE A D - SIDE D B - SIDE B E - SIDE E C - SIDE C

SECONDARY AIR

E INLET

B INLETD INLET

A INLET

C INLET

COIL FACE

COIL CONNECTIONLOCATION OPTIONS: LEFT HAND (LH) RIGHT HAND (RH)

* HAND CONFIGURATION IS DETERMINEDBY VIEWING THE UNIT LOOKINGTOWARDS WATER COIL WITH THEOUTLET AIR DIRECTED DOWNWARDS.

*COIL CONNECTION AND DRAIN PANCONNECTION ARE ALWAYS ON THESAME SIDE.

COLD PIPE CONNECTION DIMENSIONS ARECONSISTENT THROUGHOUT ALL COIL TYPES.

OUTLET AIR

D INLET

C INLETB INLETA INLET

LH COIL CONNECTION SIDE

RH COIL CONNECTION SIDE

LH WATERCOIL CONNECTION DIMENSIONS

RH WATERCOILCONNECTION DIMENSIONS

1.720

2.803

2.946

.626

7.804

.624

5.000

.624

7.180

.626

5.000

5.2804.197

THESE CONNECTIONS DO NOT EXIST FOR 2PIPE CONFIGURATIONS.

3.570RH COIL CONNECTION SIDE

LH COIL CONNECTION SIDE

Page 24: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: 0SHEET

Sol

id E

dge

5 5

ACBR ACTIVE CHILLED BEAM RECESSED

2017/05/9

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2017

Submittal SheetACBR - ACTIVE CHILLED BEAM RECESSED

268015

KHH

ACBR-1-1

DAMPER OPTIONS (SHIPPED LOOSE):(DAMPERS SHOULD NOT BE MOUNTED DIRECTLY TO THE INLET AND SHOULD ONLY BE USED FOR TRIMMING AIRFLOW)

MQ4 - 4" DAMPER W/ MANUAL LOCKING QUADRANT MQ5 - 5" DAMPER W/ MANUAL LOCKING QUADRANT MQ6 - 6" DAMPER W/ MANUAL LOCKING QUADRANT

VAV4 - 4" DAMPER W/ 24VAC FLOATING POINT ACTUATOR VAV5 - 5" DAMPER W/ 24VAC FLOATING POINT ACTUATOR VAV6 - 6" DAMPER W/ 24VAC FLOATING POINT ACTUATOR

O + 1/2" O + 1/2"

*SEE SUBMITTAL 255245 FOR AVAILABLE FIXEDVOLUME FLOW REGULATORS

Page 25: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: C

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET

Solid

Edg

e

1 2

ACBCCHILLED CEILING SYSTEM

ACTIVE CHILLED BEAM CABINET

2013/06/13

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2012

Submittal Sheet

ACBC - ACTIVE CHILLED BEAM CABINET

258825

STANDARD CONSTRUCTION: • ALL METAL ASSEMBLY • ALUMINUM FINS • COPPER WATER PIPING • STEEL NOZZLE PLATE • VENT/DRAINS ON WATER COIL • 16 GAUGE EXTERIOR CASE

EXTERIOR FINISH: • B12 WHITE POWDER PAINT (STANDARD)

INTERIOR FINISH: • B17 BLACK POWDER PAINT (STANDARD)

NOTES: • FACTORY TOLERANCE +/- 1/32" (1)

INLET LOCATION OPTIONS:(CHOOSE ONE)� LEFT - 1L� RIGHT - 1R� BOTH - 1L1R

COIL CONNECTION LOCATIONOPTIONS (CHOOSE ONE):� LEFT - LH (SAME SIDE AS 1L)� RIGHT - RH (SAME SIDE AS 1R)

INLET SIZE (D):� 5" (125)� 6" (152)

DRAIN PAN:� DRAIN PAN (1/4" MNPT)

** SEE SUBMITTAL 248924 FOR AVAILABLE HOSE AND VALVE PACKAGES

PIPING CONNECTION:� 1/2" SWEAT� 1/2" NPT - FEMALE

COIL TYPE:� 2 PIPE, 1 CIRCUIT� 2 PIPE, 2 CIRCUIT� 4 PIPE, 1 CIRCUIT� 4 PIPE, 2 CIRCUIT

� 50� 60� 70

OUTLET AIR DISCHARGES FROMBOTTOM LOUVER FACE

PROTECTIVE FILM:� PF - PROTECTIVE FILM ON FACE AND INLET

WALL MOUNTINGBRACKETS

* WEIGHTS ARE FOR A LOUVEREDFACE STYLE UNITS

LENGTH (L)

13.696

IL AIR INLET LEFT COIL CONNECTION

INTEGRATED PRESSURE PORT

WATER CONNECTIONS (LEFT HAND)

4.022NON COIL SIDE4.022

WATER CONNECTIONS (RIGHT HAND)

IR AIR INLET RIGHT COIL CONNECTION

30.000

8.555

10.000

3.600

25.125

PRIMARY AIR INLET D - 1/8"

1/4 TURN LATCHES FOR FACE REMOVAL

NOZZLE SIZE:� 20� 30� 40

DRY WETLENGTH 24 24 46 50LENGTH 36 36 79 84LENGTH 48 48 112 118LENGTH 60 60 145 152LENGTH 1500 67.750 (1721) 167 175LENGTH 72 72 178 186LENGTH 2000 87.438 (2201) 222 232LENGTH 96 96 244 255

WEIGHT (lbs)LENGTH (L)NOMINAL

� 80� 90

Page 26: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: C

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET

Solid

Edg

e

2 2

ACBCCHILLED CEILING SYSTEM

ACTIVE CHILLED BEAM CABINET

2013/06/13

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

© Copyright PRICE INDUSTRIES 2012

Submittal Sheet

ACBC - ACTIVE CHILLED BEAM CABINET

258825

FACE OPTIONS:

� PERFORATED

� TWIST LOUVER

Page 27: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: D

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET

Solid

Edg

e

1 6

�������

�������HOSE AND VALVE PACKAGES

2012/10/18

248924

��� ��

���������

�������

��������������� �� ��������

© Copyright PRICE INDUSTRIES 2012

���������������

�������� �������!��!��� �����

� SH: SINGLE HOSE - UNIT TO UNIT

� DH: DOUBLE HOSE - UNIT TO HEADER

������������

UNIT

SUPPLY

RETURN

CONSTRUCTION: • BRAIDED STAINLESS STEEL • 1/2" NPT (MALE) HOSE CONNECTION

NOTE:HOSE KITS ARE PRESSURE TESTED AND SHIPPED LOOSE FOR FIELD INSTALL BY OTHERS.

� ��������������������������������

��������������

� ��������������������������������

LENGTH:� 12"� 18"� 24"� 36"

LENGTH:� 12"� 18"� 24"� 36"

RETURN

�������

�������

CONSTRUCTION: • BRAIDED STAINLESS STEEL • 1/2" NPT (MALE) HOSE CONNECTION

NOTE:WATER COILS SHOULD BE ORDERED WITH FNPT 1/2" FITTINGS, OTHERWISE ADAPTERS(BY OTHERS) ARE REQUIRED

Page 28: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: D

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET

Solid

Edg

e

2 6

�������

�������HOSE AND VALVE PACKAGES

2012/10/18

248924

��� ��

���������

�������

��������������� �� ��������

© Copyright PRICE INDUSTRIES 2012

���������������

�������� �������!��!��� �����

� DHSO: DOUBLE HOSE W/ SHUT OFFS - UNIT TO HEADER

UNIT

SUPPLY����� �� �� � � ����� �� �� � � ����� �� �� � � ����� �� �� � � ����� �� �� � � ����� �� �� � �

������� ���

LENGTH:� 12"� 18"� 24"� 36"

� ����������������� ������

NOTES: • ON/OFF ACTUATOR CONTROL ARE SPRING RETURN EQUIPPED. • COIL CONNECTIONS ARE FEMALE SWEAT, TRUNK CONNECTIONS ARE FEMALE NPT. • BASIC PACKAGES SHIPPED AS SEPERATE COMPONENTS FOR FIELD ASSEMBLY AND INSTALLATION BY OTHERS. • HOSE KITS ARE PRESSURE TESTED AND SHIPPED LOOSE FOR FIELD INSTALL BY OTHERS.

RETURN

�����������������

�����������������

����� �� �� � � ����� �� �� � � ����� �� �� � � ����� �� �� � � ����� �� �� � � ����� �� �� � �

������ ���

CONSTRUCTION: • BRAIDED STAINLESS STEEL • SHUT OFF VALVES • 1/2" VALVE BODY • SWIVEL CONNECTION TO UNIT/COIL • 1/2" FNPT VALVE CONNECTIONS TO TRUNK/HEADER

VALVE BODY CONNECTION:� 1/2" SWEAT� 1/2" FNPT

����������������� ���� ��������������

����� ���������������!��������������������"����� ��

Page 29: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: D

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET

Solid

Edg

e

3 6

�������

�������HOSE AND VALVE PACKAGES

2012/10/18

248924

��� ��

���������

�������

��������������� �� ��������

© Copyright PRICE INDUSTRIES 2012

���������������

�������� �������!��!��� �����

� DHMB: DOUBLE HOSE W/ SHUT OFFS AND MANUAL BALANCER - UNIT TO HEADER

NOTES: • ON/OFF ACTUATOR CONTROL ARE SPRING RETURN EQUIPPED. • COIL CONNECTIONS ARE FEMALE SWEAT, TRUNK CONNECTIONS ARE FEMALE NPT. • ALL VALVES ARE NORMALLY CLOSED (NC), PLEASE CONTACT FACTORY IF NORMALLY OPEN (NO) IS REQUIRED • CV MUST BE SELECTED ON PACKAGES AS CLOSE TO YOUR DESIGN GPM TO ENSURE PROPER CV ON BALANCING VALVE IS RECIEVED • BASIC PACKAGES SHIPPED AS SEPERATE COMPONENTS FOR FIELD ASSEMBLY AND INSTALLATION BY OTHERS • ATC IS SIEMENS STANDARD, HOWEVER OTHER ATCs CAN BE SUPPLIED AS SPECIAL • HOSE KITS ARE PRESSURE TESTED AND SHIPPED LOOSE FOR FIELD INSTALL BY OTHERS.

CONSTRUCTION: • BRAIDED STAINLESS STEEL • SHUT OFF VALVES • 1/2" VALVE BODY • SWIVEL CONNECTION TO UNIT/COIL • 1/2" FNPT VALVE CONNECTIONS TO TRUNK/HEADER • PRESSURE TAPS

OPTIONALAUTOMATICTEMPERATURECONTROLVALVE (ATC)

����� �� �� � � ����� �� �� � � ����� �� �� � � ����� �� �� � � ����� �� �� � � ����� �� �� � �

UNIT

���������������

SUPPLY

RETURN����� �� �� � �

�����������������������

�����������������������������������

������������ ���������������

������

������

LENGTH:� 12"� 18"� 24"� 36"

ACTUATOR CONTROL (ATC):� ON/OFF @ 024 VOLT (024V)� ON/OFF @ 120 VOLT (120V)� ON/OFF @ 208 VOLT (208V)� ON/OFF @ 230 VOLT (230V)� ON/OFF @ 277 VOLT (277V)� FLOATING POINT (FLP)� MODULATING (MOD)� NONE

CV SELECTION (GPM @ 1 PSI):� 0.23� 0.46� 0.87� 1.80� 3.30� 5.40

�������������������������� ����������

VALVE BODY CONNECTION:� 1/2" SWEAT� 1/2" FNPT

Page 30: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: D

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET

Solid

Edg

e

4 6

�������

�������HOSE AND VALVE PACKAGES

2012/10/18

248924

��� ��

���������

�������

��������������� �� ��������

© Copyright PRICE INDUSTRIES 2012

���������������

�������� �������!��!��� �����

� DHAB: DOUBLE HOSE W/ SHUT OFFS AND AUTO BALANCER - UNIT TO HEADER

����� �� �� � � ����� �� �� � � ����� �� �� � � ����� �� �� � � ����� �� �� � � ����� �� �� � �

������� ���

UNIT

� ���� ����������

SUPPLY

RETURN

OPTIONALAUTOMATICTEMPERATURECONTROLVALVE (ATC)

������������ ������������������� ����

������

FLOW

� ���� ����������

NOTES: • ON/OFF ACTUATOR CONTROL ARE SPRING RETURN EQUIPPED. • COIL CONNECTIONS ARE FEMALE SWEAT, TRUNK CONNECTIONS ARE FEMALE NPT. • ALL VALVES ARE NORMALLY CLOSED (NC), PLEASE CONTACT FACTORY IF NORMALLY OPEN (NO) IS REQUIRED • GPM MUST BE SELECTED ON PACKAGES AS CLOSE TO YOUR DESIGN GPM TO ENSURE PROPER CV ON BALANCING VALVE IS RECIEVED • BASIC PACKAGES SHIPPED AS SEPERATE COMPONENTS FOR FIELD ASSEMBLY AND INSTALLATION BY OTHERS • ATC IS SIEMENS STANDARD, HOWEVER OTHER ATCs CAN BE SUPPLIED AS SPECIAL • HOSE KITS ARE PRESSURE TESTED AND SHIPPED LOOSE FOR FIELD INSTALL BY OTHERS.

LENGTH:� 12"� 18"� 24"� 36"

ACTUATOR CONTROL (ATC):� ON/OFF @ 024 VOLT (024V)� ON/OFF @ 120 VOLT (120V)� ON/OFF @ 208 VOLT (208V)� ON/OFF @ 230 VOLT (230V)� ON/OFF @ 277 VOLT (277V)� FLOATING POINT (FLP)� MODULATING (MOD)� NONE

FLOW RATE SELECTION (GPM):� 0.50� 0.75� 1.00� 1.50

� 1.75� 2.00� 2.50� 3.00

� 3.50� 4.00� 4.50� 5.00

�������������������������������������

CONSTRUCTION: • BRAIDED STAINLESS STEEL • SHUT OFF VALVES • 1/2" VALVE BODY • SWIVEL CONNECTION TO UNIT/COIL • 1/2" FNPT VALVE CONNECTIONS TO TRUNK/HEADER • PRESSURE TAPS

Page 31: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: D

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET

Solid

Edg

e

5 6

�������

�������HOSE AND VALVE PACKAGES

2012/10/18

248924

��� ��

���������

�������

��������������� �� ��������

© Copyright PRICE INDUSTRIES 2012

���������������

�������� �������!��!��� �����

FACTORY MOUNTING (AVAILABLE ON DH, DHSO, DHMB AND DHAB):� FMC - FACTORY MOUNTED ON COLD WATER CONNECTION (CHOOSE THIS FOR 2-PIPE COIL)� FMH - FACTORY MOUNTED ON HOT WATER CONNECTION

��������������� �������������� ���������

NOTES: • FACTORY MOUNTED RADKITS ARE CONNECTED AND LEAK TESTED AT THE FACTORY • CHILLED BEAM MUST BE ORDERED WITH NPT CONNECTIONS • CONTROL VALVES SHOULD BE MOUNTED ON THE RETURN

Page 32: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: D

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET

Solid

Edg

e

6 6

�������

�������HOSE AND VALVE PACKAGES

2012/10/18

248924

��� ��

���������

�������

��������������� �� ��������

© Copyright PRICE INDUSTRIES 2012

���������������

�������� �������!��!��� �����

ACTUATOR CONTROL (ATC):� ON/OFF @ 024 VOLT (024V)� ON/OFF @ 120 VOLT (120V)� MODULATING (MOD) (0-10 Vdc)� NONE

Cv FLOWRATE:(GPM @ 1 PSI)� 1.0� 2.5

� 2-Way � 3-Way

2-WAY VALVE BODY:� 1/2" SWEAT (A=2.660 AND B=4.980)� 1/2" NPT (A=2.760 AND B=5.130)

CONSTRUCTION: • 1/2" BRASS VALVE BODY • ON/OFF ACTUATORS ARE NORMALLY CLOSED (NC) SPRING RETURN

� ATC: AUTOMATIC TEMPERATURE CONTROL VALVE

����� �����

��� ���

3-WAY VALVE BODY:� 1/2" SWEAT (A=2.660 AND B=5.760)� 1/2" NPT (A=2.760 AND B=5.840)

Page 33: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: 0

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET

So

lid E

dg

e

1 2

�������

�������QUICK CONNECT HOSES

AND SHUT OFFS2010/09/09

255683

��� ��

���������

�������

��������������� �� ��������

© Copyright E.H.PRICE LIMITED 2009

���������������

�������� �� �� ��� ��!���������!���""�

CONSTRUCTION:

• BRAIDED STAINLESS STEEL • 1/2" PUSH-ON QUICK CONNECTS ON BOTH ENDS

�������

� SHQ2: SINGLE HOSE QUICK CONNECT

� SHQ1: SINGLE HOSE QUICK CONNECT

CONSTRUCTION:

• BRAIDED STAINLESS STEEL• 1/2" PUSH-ON QUICK CONNECT & 1/2" NPT (FEMALE) HOSE CONNECTIONS

�������

LENGTH:

� 12"� 18"

LENGTH:

� 12"� 18"� 24"

� DHQ1: DOUBLE HOSE QUICK CONNECT

UNIT

CONSTRUCTION:

• BRAIDED STAINLESS STEEL• 1/2" PUSH-ON QUICK CONNECT & 1/2" NPT (FEMALE) HOSE CONNECTIONS

� �

� �

LENGTH:

� 12"� 18"� 24"

������� ��

������� ��

SUPPLY

RETURN

� ������������

� ������������

� ������������

� ������������

�������������

�������������

�������������

� ������������

Page 34: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: 0

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET

So

lid E

dg

e

2 2

�������

�������QUICK CONNECT HOSES

AND SHUT OFFS2010/09/09

255683

��� ��

���������

�������

��������������� �� ��������

© Copyright E.H.PRICE LIMITED 2009

���������������

�������� �� �� ��� ��!���������!���""�

� SHSOQ1: SINGLE HOSE W/ SHUT-OFF & QUICK CONNECT

CONSTRUCTION:

• BRAIDED STAINLESS STEEL• 1/2" PUSH-ON QUICK CONNECT & NPT (FEMALE) HOSE CONNECTIONS• SHUT OFF VALVES

LENGTH:

� 12"� 18"

� DHSOQ1: DOUBLE HOSE W/ SHUT OFF & QUICK CONNECT

CONSTRUCTION:

• BRAIDED STAINLESS STEEL• 1/2" PUSH-ON QUICK CONNECT & NPT (FEMALE) HOSE CONNECTIONS• SHUT OFF VALVES

UNIT

� DHQ2: DOUBLE HOSE QUICK CONNECT

CONSTRUCTION:

• BRAIDED STAINLESS STEEL • 1/2" PUSH-ON QUICK CONNECTS ON BOTH ENDS

�������� �

�������� �

LENGTH:

� 12"� 18"

UNIT

LENGTH:

� 12"� 18"

������� ��

������� ��

������� ��

SUPPLY

RETURN

SUPPLY

RETURN

��������������

�������������������

� ������������

�������������

� ������������

� ������������

� ������������

� �������������������� �����������

� �������������������� �����������

� �������������������� �����������

�������������

�������������

Page 35: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV: 0

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET

Solid

Edg

e

1 1

���VOLUME FLOW REGULATOR

2010/09/07

������

��� ����

�������

���� ������ ������������

© Copyright E.H.PRICE LIMITED 2006

������������ �

����!�����������"���������

255245 SIZES 4, 5, 6, 8

STANDARD CONSTRUCTION: • BLACK ABS PLASTIC, UL94V-0 RATED • UL2043 LISTED • SIZED TO FIT INSIDE STANDARD RIGID ROUND DUCTING • INTEGRATED GASKET FOR SEALING AGAINST INSIDE OF DUCT

PERFORMANCE: • CONTROLS AIRFLOW WITHIN 10% OF RATED FLOW (15% FOR UNITS 50CFM OR LESS) FOR 0.2" TO 0.8" W.C.

NOTES: • FACTORY TOLERANCE +/- 1/32" (1)

��

�� ���

Duct Size A B C AIRFLOW SELECTIONS (CFM)

4" (100) 3.800 4.100 2.300 10, 20, 25, 30, 35, 45, 50, 60

5" (125) 4.800 5.100 3.500 35, 50, 60, 75, 90, 105

6" (150) 5.800 6.100 3.500 75, 90, 105, 125, 140, 160, 175

8" (200) 7.600 8.100 3.500 125, 140, 160, 175, 205, 235, 265, 295

����������� �����������������

������

Page 36: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV A

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET 1 2

������

HYDRONIC PRODUCTS

CONTROLLER256033

������

� ����

�������

����������� ������������

© Copyright E.H.PRICE LIMITED 2008

������������ �

2010/12/22

TRANSFORMER OPTIONS:

� 115/24 VAC 96 VA TRANSFORMER� 277/24 VAC 96 VA TRANSFORMER

NOTES:

• 96 VA CLASS 2 TRANSFORMER • ETL CERTIFIED • TOTAL CONNECTED LOAD NOT TO EXCEED 2 AMPS MAXIMUM 12 AIR DAMPERS TOTAL • ONE PLENUM RATED CONNECTION CABLE

PROVIDED WITH EACH VAV INLET • POWER DISCONNECT SWITCH • POWER AND SIGNAL STATUS LED'S • 22 GAUGE GALV. STEEL ENCLOSURE

APPLICATION:

� INPUT SIGNAL FROM DDC CONTROLLER (NO THERMOSTAT) (0 -10V DC COOLING)� PIC-TS-SENS PRICE ROOM SENSOR THERMOSTAT (SEE SUBMITTAL 250050-100)� PIC-TS-PRICE DIAL THERMOSTAT (SEE SUBMITTAL 250051-100)� PIC-TS-LCD PRICE LCD THERMOSTAT (CELCIUS OR FAHRENHEIT OPTION) (SEE SUBMITTAL 250052-100)� PIC-TS-MOTION PRICE MOTION SENSOR WITH LCD THERMOSTAT (CELCIUS OR FAHRENHEIT OPTION) (SEE SUBMITTAL 250053-100)

� WIRELESS D OPTION - WIRELESS THERMOSTAT (DIAL) AND BASE.

��������������� ��

������������������

���������������

������������������ �����������!�������������������

�����

�����

���� !"��#$%

���&'�

�'�'��

Page 37: Retrofit Terminal Units - Price Industries · (4"hx7"w) 8" oval equiv. ... 1 circuit 2p2c = 2 pipe, 2 circuit ... 12" wide active chilled beam linear - high efficiency 266523 ct

OF REV A

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SHEET 2 2

������

HYDRONIC PRODUCTS

CONTROLLER256033

������

� ����

�������

����������� ������������

© Copyright E.H.PRICE LIMITED 2008

������������ �

2010/12/22

� FACTORY MOUNTED PIC-HP OPTION

������������ ����� ���� ��� �����������������������

ENCLOSURE IS INSTALLED ON BEAM CASING. WHEN ORDERINGTAG THE PIC-HP LINE WITH THE SAME TAG FOR THE REQUIREDBEAM TO ENSURE THEY MATCH UP CORRECTLY

������������� �� �������������������������������������������

������������������ ���������������������

� CONDENSATE SENSOR (SHIPPED LOOSE)

•SENSOR CAN BE MOUNTED TO COIL CONNECTIONS OFCOIL OR UPSTREAM OF THE BEAM ON THE TUBING

�������� ����������� ������� ��������������� ���

������������