RESPITE RELOCATIONS

27
111 MAPLE STREET BUFFALO, NEW YORK 14204 RECOVERY OPTIONS MADE EASY INC. 75 JAMESTOWN STREET GOWANDA, NEW YORK 14072 OWNER: ARCHITECT: 189 Kenmore Avenue, Buffalo, New York 14223 (716) 833-1873 | [email protected] RESPITE RELOCATIONS: OCCUPANCY AND LIFE SAFETY INFO: BUILDING CONSTRUCTION CLASSIFICATION: V-B USE AND OCCUPANCY CLASSIFICATION TYPE: OCCUPANCY: R-4 RESIDENTIAL CARE FACILITY USE / OCCUPANCY CLASSIFICATION AND CONST. TYPE: DATE JOB NO. 2021 - 05 10/28/2021 EXISTING BUILDING BID SET SITE MAP - BUFFALO, NY PROJECT LOCATION

Transcript of RESPITE RELOCATIONS

Page 1: RESPITE RELOCATIONS

111 MAPLE STREET

BUFFALO, NEW YORK 14204

RECOVERY OPTIONS MADE EASY INC.

75 JAMESTOWN STREET

GOWANDA, NEW YORK 14072

OWNER:

ARCHITECT:

189 Kenmore Avenue, Buffalo, New York 14223

(716) 833-1873 | [email protected]

RESPITE RELOCATIONS:

OCCUPANCY AND LIFE SAFETY INFO:

BUILDING CONSTRUCTION CLASSIFICATION: V-B

USE AND OCCUPANCY CLASSIFICATION TYPE:

OCCUPANCY: R-4 RESIDENTIAL CARE FACILITY

USE / OCCUPANCY CLASSIFICATION AND CONST. TYPE:

DATEJOB NO.

2021 - 05 10/28/2021

EXISTING BUILDING

BID SETSITE MAP - BUFFALO, NY

PROJECT

LOCATION

Page 2: RESPITE RELOCATIONS

INDEX TO DRAWINGS:

GENERAL CONSTRUCTION NOTES:

CODES, PERMITS AND REGULATIONS

1. CONTRACTORS ARE RESPONSIBLE FOR SECURING ALL BUILDING PERMITS REQUIRED BY LOCAL GOVERNING AUTHORITIES.

2. CONTRACTORS SHALL MEET ALL LOCAL, COUNTY, STATE AND FEDERAL REGULATIONS OF DEMOLITION, SAFETY AND SANITARY PRECAUTIONS DURING BUILDING OPERATIONS INCLUDING

CONTACTING "LOCAL STATE/CITY UTILITIES PROTECTION SERVICE."

3. ALL WORK SHALL COMPLY WITH APPLICABLE CODES, AMENDMENTS, RULES, REGULATIONS, ORDINANCES, LAWS, ORDERS, APPROVALS, ECT., THAT ARE REQUIRED BY PUBLIC AUTHORITIES, IN THE

EVENT OF CONFLICT, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN. REQUIREMENTS INCLUDE, BUT ARE NOT NECESSARILY LIMITED TO THE CURRENTLY APPLICABLE EDITIONS OR

PUBLICATIONS OF THE FOLLOWING:

A. INTERNATIONAL BUILDING CODE & NYS BUILDING CODE

B. NATIONAL FIRE PROTECTION ASSOCIATION

C. AMERICAN NATIONAL STANDARDS INSTITUTE

D. ALL LOCAL AND MUNICIPAL CODES

4. UPON COMPLETION, OWNER IS RESPONSIBLE FOR POSTING OCCUPANT LOAD, LIVE LOAD, USE GROUP AND CONSTRUCTION TYPE ON A PLACARD AS DESIGNATED BY THE BUILDING OFFICIAL.

5. CONTRACTOR SHALL WAIVE "COMMON PRACTICE" AND "COMMON USAGE" AS CONSTRUCTION CRITERIA WHEREVER DETAILS AND CONTRACT DOCUMENTS OR GOVERNING CODES, ORDINANCES,

ETC., REQUIRE GREATER QUANTITY OR BETTER QUALITY THAN COMMON PRACTICE OR COMMON USAGE WOULD REQUIRE.

6. VERIFY FIELD CONDITIONS PRIOR TO COMMENCEMENT OF EACH PORTIONS OF THE WORK. COORDINATE ALL SITE REQUIREMENTS, ISSUES AND UTILITIES.

ABBREVIATIONS:AB ANCHOR BOLT

A/C AIR CONDITION(ING) (ED)

ACC ACCESSIBLE

ACCU AIR COOLED CONDENSING UNIT

ACI AMERICAN CONCRETE INSTITUTE

ACT ACOUSTICAL CEILING TILE

ACM ASBESTOS CONTAINING MATERIAL

ACS PNL ACCESS PANEL

ADDL ADDITIONAL

ADJ ADJUSTABLE, ADJACENT

ADH ADHESIVE

AFF ABOVE FINISHED FLOOR

AGGR AGGREGATE

AHU AIR HANDLING UNIT

ALT ALTERNATE

ALUM ALUMINUM

ANOD ANODIZED

APPROX APPROXIMATE

ARCH ARCHITECTURAL

AUX RD AUXILIARY ROOF DRAIN

ASD ALLOWABLE STRESS DESIGN

ASTM AMERICAN SOCIETY FOR

TESTING AND MATERIALS

AWP ACOUSTICAL WALL PANEL

BAT BATTEN

B/B BACK TO BACK

BASE BD BASE BOARD

BCNYS BUILDING CODE OF NEW YORK STATE

BLDG BUILDING

BLKG BLOCKING

BM BEAM / BENCHMARK

BOT BOTTOM

BR BEDROOM

BRG BEARING

BSMT BASEMENT

BTWN BETWEEN

BUR BUILT UP ROOFING

BW /EW BOTH WAYS / EACH WAY

CATV CABLE TELEVISION (COAXIAL)

CCTV CLOSED CIRCUIT TELEVISION

CAB CABINET

CB CATCH BASIN, CORNER BEAD

CEM CEMENT

CF CONTRACTOR FURNISHED

CFMF COLD-FORMED METAL FRAMING

CF/CI CONTRACTOR FURNISHED /

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED /

OWNER INSTALLED

CG CORNER GUARD

CI CAST IRON

CIP CAST IN PLACE

CJ CONTROL JOINT

CL CENTERLINE

CLG CEILING

CLO CLOSET

CLR CLEAR / COLOR

CMT CERAMIC MOSAIC TILE

CMU CONCRETE MASONRY UNIT

CNTR COUNTER

CO CLEANOUT

COL COLUMN

CONC CONCRETE

CONF CONFERENCE

CONN CONNECTION

CONSTR CONSTRUCTION

CONT CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

CPT CARPET

CSJ CONSTRUCTION JOINT

CSK COUNTER SUNK

CT CERAMIC TILE / COUNT

CTR CENTER

CW COLD WATER PIPING /

CASEMENT WINDOW

CUH CABINET UNIT HEATER

D DEEP / DEPTH

DBL DOUBLE

DEG DEGREE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL / DIAGRAM

DIM DIMENSION

DIFF DIFFUSER

DIR DIRECTION

DISP DISPENSER

DIV DIVISION

DMPF DAMP PROOFING

DL DEAD LOAD

DN DOWN

DO DITTO

DR DOOR / DRIVE

DS DOWNSPOUT

DW DISHWASHER

DWV DRAINAGE WASTE & VENT

DWG DRAWING

DWL DOWEL

E EAST

EA EACH

EBCNYS EXISTING BUILDING CODE

OF NEW YORK STATE

EC ELECTRICAL CONTRACTOR

EF EACH FACE

EIFS EXTERIOR INSULATION

AND FINISH SYSTEM

EJ EXPANSION JOINT

ELAS ELASTOMERIC

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

EM ENTRY MAT

EMER EMERGENCY

ENCL ENCLOSURE

ENGR ENGINEER

EOS EDGE OF SLAB

EP ELECTRIC PANEL (OR LP)

EQ EQUAL

EQUIP EQUIPMENT

ETC ET CETERA

ETR EXISTING TO REMAIN

EW EACH WAY

EXIST EXISTING

EXC EXCAVATION / EXCAVATE

EXP EXPAND / EXPANSION

EXT EXTERIOR

F/F FACE TO FACE

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FD FLOOR DRAIN

FDTN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FHC FIRE HOSE CABINET

FIN FINISHED

FIXT FIXTURE

FLASH FLASHING

FLEX FLEXIBLE

FLOR FLUORESCENT

FLG FLOORING / FLANGE

FO FINISHED OPENING

FP FIRE PROTECTION

FRTW FIRE RETARDANT TREATED WOOD

FT FOOT, FEET

FTG FOOTING

FURN FURNACE / FURNITURE / FURNISH

GA GAGE

GAL GALLON

GALV GALVANIZED

GB GRAB BAR

GC GENERAL CONTRACTOR

GL GLASS / GROUND LEVEL

GL BLK GLASS BLOCK

GLU LAM GLUED LAMINATED BEAM

GR GRADE / GROSS

GRAN GRANITE

GWT GLAZED WALL TILE

GYP GYPSUM

GYP BD GYPSUM BOARD

HB HOSE BIBB

HC HOLLOW CORE, HOSE CABINET

HCP HANDICAPPED

HDW HARDWARE

HDWD HARDWOOD

HM HOLLOW METAL

HO HOLD OPEN

HORIZ HORIZONTAL

HSS HOLLOW STRUCTURAL SECTION

HT HEIGHT

HTG HEATING

HTR HEATER

HVAC HEATING, VENTILATING

AND AIR CONDITIONING

HW HOT WATER

HYD HYDRANT

ID INSIDE DIAMETER

IIC IMPACT INSULATION CLASS

IN INCHES

INCL INCLUDED

INCAND INCANDESCENT

INFO INFORMATION

INSUL INSULATION

INTERM INTERMEDIATE

INT INTERIOR

JAN JANITOR

JST JOIST

JT JOINT

KIT KITCHEN

KO KNOCKOUT

KPL KICK PLATE

LAM LAMINATED

LAU LAUNDRY

LAV LAVATORY

LB POUND

LBL LABEL

LIN LINEAR

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LOC LOCATION

LT LIGHT

LTG LIGHTING

LWC LIGHT-WEIGHT CONCRETE

MACH MACHINE

MAINT MAINTENANCE

MAS MASONRY

MATL MATERIAL

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

MCB METAL CORNER BEAD

MDF MEDIUM DENSITY FIBERBOARD

MECH MECHANICAL

MEP MECHANICAL, ELECTRICAL,

PLUMBING AND FIRE

PROTECTION

MEZZ MEZZANINE

MFR MANUFACTURER

MH MANHOLE

MM MILLIMETER

MIN MINIMUM

MISC MISCELLANEOUS

MLWK MILLWORK

MO MASONRY OPENING

MTD MOUNTED

MTL METAL

MULL MULLION

N NORTH

NAT NATURAL

NCOMBL NONCOMBUSTIBLE

NIC NOT IN CONTRACT

NO OR # NUMBER

NOM NOMINAL

NORM NORMAL

NTS NOT TO SCALE

O/O OUT TO OUT

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OF/CI OWNER FURNISHED,

CONTACTOR INSTALLED

OF/OI OWNER FURNISHED,

OWNER INSTALLED

OFD OVERFLOW DRAIN

OFF OFFICE

OH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

OPT OPTIONAL

PBD PARTICLEBOARD

PC PLUMBING CONTRACTOR /

PORTLAND CEMENT

PCC PRECAST CONCRETE

PCT PORCELAIN CERAMIC TILE

PED PEDESTAL

PEND PENDANT

PER PERIOD

PERF PERFORATED

PL PLATE / PROPERTY LINE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLB PLUMBING

PLYWD PLYWOOD

PNL PANEL

POL POLISHED

PORC PORCELAIN

POS POSITIVE / POSITION

PT PRESSURE TREATED

PR PAIR

PREFAB PREFABRICATE

PREFIN PREFINISH

PREP PREPARATION

PROJ PROJECT

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PAINT

PTN PARTITION

PVC POLYVINYL CHLORIDE

PVG PAVING

QT QUARRY TILE

QTY QUANTITY

R RISER / RADIUS

RB RESILIENT BASE / RUBBER BASE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN / ROAD

REC RECESSED

REF REFRIGERATOR

REFL REFLECT

REG REGISTER, REGULATION

REINF REINFORCED

REQD REQUIRED

RESIL RESILIENT

REV REVISION

RF RESILIENT FLOORING

RFG ROOFING

RH RIGHT HAND / ROOF HATCH

RM ROOM

RO ROUGH OPENING

ROW RIGHT OF WAY

RTU ROOF TOP UNIT

RV ROOF VENT

RWB RUBBER WALL BASE

S SOUTH

SAB / SAFB SOUND ATTENUATION BATTS

SAN SANITARY

SC SOLID CORE

SCHED SCHEDULE

SEAL SEALER ON FLOOR

SECT SECTION

SF SQUARE FOOT

SHT SHEET

SHT VL SHEET VINYL

SHR SHOWER

SIM SIMILAR

SOG SLAB ON GRADE

SP STANDPIPE / SUMP PIT

SPA SPACES

SPEC SPECIFICATION

SQ SQUARE

SRD SECONDARY ROOF DRAIN

SS SERVICE SINK

SSM SOLID SURFACE MATERIAL

SSP STAINLESS STEEL PIPE

SST STAINLESS STEEL

STC SOUND TRANSMISSION CLASS

STD STANDARD

STL STEEL

STOR STORAGE

STR STRAIGHT / STRINGERS

STRUCT STRUCTURAL

SUSP SUSPENDED

SV SHEET VINYL

T TREAD

T/ TOP OF

T&B TOP AND BOTTOM

T&G TONGUE AND GROOVE

TEL TELEPHONE

THRES THRESHOLD

TEMP TEMPORARY

THK THICKNESS

TMPD TEMPERED

TOC TOP OF CONCRETE

TOM TOP OF MASONRY

TOPO TOPOGRAPHIC

TOS TOP OF STEEL

TOW TOP OF WALL

TSTAT THERMOSTAT

TTH TOILET TOWEL HOLDER

TV TELEVISION

TYP TYPICAL

UC UNDERCUT

UCL UNDER CABINET LIGHTING

UGND UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER'S LABORATORIES

UNEX UNEXCAVATED

UNFIN UNFINISHED

UON UNLESS OTHERWISE NOTED

UTIL UTILITY

UV UNIT VENTILATOR

VARN VARNISH(ED)

VB VINYL BASE

VCT VINYL COMPOSITION TILE

VENT VENTILATION

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

VIN VINYL

VB VAPOR BARRIER

VT VINYL TILE

VWC VINYL WALL COVERING

W WEST

W/ WITH

WC WATER CLOSET / WALL COVERING

W/O WITHOUT

WD WOOD

WNDW WINDOW

WF WIDE FLANGE

WH WATER HEATER

WM WIRE MESH

WP WATERPROOFING

WR WATER REPELLENT /

WEATHER RESISTANT

WSCT WAINSCOT

WT WEIGHT / WATERTIGHT

WWF WELDED WIRE FABRIC

WW WELDED WIRE MESH

SYMBOLS:

F.E. CAB.

RECESSED FIRE

EXTERIOR WINDOW TYPE

INTERIOR WALL TYPE INDICATION

Y

EXTINGUISHER CABINET

2

2

DOOR NUMBER

FRAME TYPE

INTERIOR DOOR TYPE

D 2

01

A2

DETAIL ELEVATION

OFFICE 101 ROOM NUMBER

ROOM NAME

DRAWING NAME

EXTERIOR DOOR TYPE

BUILDING CODES AND REGULATORY COMPLIANCE:

THE CONSTRUCTION DESCRIBED HEREIN MEETS APPLICABLE FEDERAL, STATE AND LOCAL CODES AND REGULATIONS OF AUTHORITIES HAVING JURISDICTION:

-NEW YORK STATE BUILDING CODE, 2020.

-ENERGY CONSERVATION CONSTRUCTION CODE OF NEW YORK STATE 2020.

-FIRE CODE OF NEW YORK STATE, 2020.

-MECHANICAL CODE OF NEW YORK STATE, 2020.

-FUEL GAS CODE OF NEW YORK STATE, 2020.

-PLUMBING CODE OF NEW YORK STATE, 2020.

-NATIONAL ELECTRICAL CODE (NFPA 70).

-ICC/ANSI A117.1-2009 - ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES.

-NFPA 101 CU 32/33

-NFPA 101 A ALTERNATE APPROACHES TO LIFE SAFETY

DRAWING NUMBER

GENERAL INFORMATION:G-001: COVER SHEET

G-002: ABBREVIATIONS, SYMBOLS AND DRAWING INDEX

G-003: ACCESSIBILITY DETAILS

G-004: LIFE SAFETY FLOOR PLAN

ARCHITECTURAL:A-001: EXISTING FLOOR PLAN

A-002: DEMOLITION FLOOR PLAN

A-101: PROPOSED FLOOR PLAN

A-102: PROPOSED REFLECTED CEILING PLAN

A-103: ROOM FINISH SCHEDULE AND INTERIOR WALL TYPES

A-501: LARGE SCALE PLANS AND INTERIOR ELEVATIONS

A-502: DETAILS

MECHANICAL:M-101: PROPOSED MECHANICAL PLAN

M-102: PROPOSED EXHAUST SYSTEMS PLAN

ELECTRICAL:E-001: EXISTING ELECTRICAL PLAN

E-002: ELECTRICAL DEMOLITION PLAN

E-003: LIGHTING DEMOLITION PLAN

E-101: PROPOSED ELECTRICAL PLAN

E-102: PROPOSED LIGHTING PLAN

PLUMBING:P-001: EXISTING PLUMBING PLAN

P-002: PLUMBING DEMOLITION PLAN

P-101: PROPOSED PLUMBING PLAN

FIRE PROTECTION:FP-001: EXISTING FIRE ALARM DETECTION PLAN

FP-002: DEMO FIRE ALARM DETECTION PLAN

FP-101: PROPOSED FIRE ALARM DETECTION PLAN

SP-001: EXISTING SPRINKLER PLAN

SP-002: DEMO SPRINKLER PLAN

SP-101: PROPOSED SPRINKLER PLAN

1

A-101

1

A-101

TYPICAL DRAWING TAG1/4" = 1'-0"SCALE:1

DRAWING SCALEDRAWING NUMBER

1

1

A-101

241

3

INTERIOR ELEVATIONS

SHEET NUMBER

DRAWING NUMBER

SHEET NUMBER

SECTION INDICATOR ALTERNATE ELEVATION INDICATOR

DRAWING NUMBER

SHEET NUMBER

DETAIL BUBBLE

GENERAL COORDINATION OF DRAWINGS:

1. CONTRACTORS SHALL VERIFY THAT NO CONFLICTS EXIST IN LOCATIONS OF PROPOSED WALLS. COORDINATE

ALL MECHANICAL, TELEPHONE, ELECTRICAL, AND PLUMBING EQUIPMENT TO BE REMOVED, RELOCATED OR

INSTALLED (ITEMS TO INCLUDE ARE: ALL PIPING, DUCT WORK, STRUCTURAL MEMBERS AND CONDUIT; AND

EXISTING CONDITIONS). VERIFY THAT ALL REQUIRED CLEARANCES FOR INSTALLATIONS AND MAINTENANCE OF

ABOVE ARE PROVIDED. ELEMENTS TO BE EXPOSED OR CONCEALED SHALL BE DETERMINED AND REVIEWED

WITH ARCHITECT PRIOR TO CONSTRUCTION PROCEEDING.

2. CONTRACTORS AND SUBS SHALL COORDINATE THE LAYOUT AND EXACT LOCATION OF ALL PARTITIONS,

DOORS, ACCESSORIES, ELECTRICAL/TELEPHONE OUTLETS AND LIGHT SWITCHES WITH ARCHITECTURAL

DRAWINGS IN THE FIELD BEFORE PROCEEDING WITH CONSTRUCTION.

3. IN THE EVENT OF CONFLICT BETWEEN DATA SHOWN ON DRAWINGS AND DATA SHOWN ON THE

SPECIFICATIONS, COORDINATE WITH ARCHITECT. DETAILS DRAWINGS TAKE PRECEDENCE OVER DRAWINGS OF

LARGER SCOPE. SHOULD THE CONTRACTORS AT ANY TIME DISCOVER AN ERROR IN A DRAWING OR

SPECIFICATIONS, OR A DISCREPANCY OR VARIATION BETWEEN DIMENSIONS OR DRAWINGS AND

MEASUREMENTS AT SITE, OR LACK OF DIMENSIONS OR OTHER INFORMATION, HE SHALL NOT PROCEED WITH

THE WORK AFFECTED UNTIL CLARIFICATION HAS BEEN COMPLETED WITH THE ARCHITECT, OR CONTRACTOR

ASSUMES RESPONSIBILITY FOR MODIFICATION OF ALL ASSOCIATED WORK INSTALLED INCORRECTLY AS

DETERMINED BY ARCHITECT.

4. THE FINISHED WORK SHALL BE FIRM, WELL ANCHORED, IN TRUE ALIGNMENT, PLUMB, LEVEL, WITH SMOOTH,

CLEAN, UNIFORM APPEARANCES WITHOUT WAVES, DISTORTIONS, HOLES, MARKS, CRACKS, STAINS OR

DISCOLORATION. JOINTING SHALL BE CLOSE FITTING, NEAT AS WELL SCRIBED. THE FINISH WORK SHALL HAVE

NO EXPOSED UNSIGHTLY ANCHORS OR FASTENERS AND SHALL NOT PRESENT HAZARDOUS, UNSAFE CORNERS.

ALL WORK SHALL HAVE THE PROVISION FOR EXPANSION, CONTRACTION, AND SHRINKAGE AS NECESSARY TO

PREVENT CRACKS, BUCKLING AND WARPING DUE TO TEMPERATURE AND HUMIDITY CONDITIONS.

5. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IN WRITING OF ANY DEFICIENCIES IN THE BUILDING SCOPE

OF WORK AREAS PRIOR TO THE COMMENCEMENT OF WORK. ANY UNREPORTED DEFICIENCIES WILL BECOME

THE RESPONSIBILITY OF THE CONTRACTOR TO CORRECT.

6. ATTACHMENTS, CONNECTIONS, OR FASTENINGS OF ANY NATURE ARE TO BE PROPERLY AND PERMANENTLY

SECURED IN CONFORMANCE WITH BEST PRACTICE AND THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING

THEM ACCORDINGLY AND TO THESE CONDITIONS. THE DRAWINGS SHOW ONLY SPECIAL CONDITIONS TO ASSIST

CONTRACTOR. THEY DO NOT ILLUSTRATE EVERY DETAILED CONNECTION.

7. THE CONTRACTORS ARE RESPONSIBLE FOR VERIFYING THE DIMENSIONS AND ELEVATIONS OF EXISTING

CONDITIONS AT THE SITE. THE CONTRACTORS AND SUBS SHALL COORDINATE THE LAYOUT AND EXACT

LOCATIONS OF ALL ITEMS IN THE FIELD BEFORE PROCEEDING WITH CONSTRUCTION.

8. IT IS THE RESPONSIBILITY OF THE CONTRACTORS TO COORDINATE AND SCHEDULE ALL DELIVERIES AND

DISPOSAL COORDINATION WITH THE ARCHITECT AND SECURITY PERSONNEL.

9. CUSTOM MILLWORK, DOTTED LINE INDICATED MILLWORK ABOVE. SEE INTERIOR ELEVATIONS FOR MORE

INFORMATION.

10. EACH CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AT THE JOB AND SHALL BE RESPONSIBLE

FOR THE PROPER FITTING OF HIS/HER WORK THERE TO.

11. ALL DIMENSIONS ARE SHOWN FROM FACE OF FRAMING TO FACE OF FRAMING U.N.O.

12. DOORS AND CASED OPENINGS INDICATED ADJACENT TO WALL INTERSECTIONS SHALL BE LOCATED WITH

THE EDGE OF FINISH OPENING FOUR (4) INCHES FROM THE ADJACENT WALL UNLESS OTHERWISE INDICATED.

ALL OTHER DOORS AND CASED OPENINGS SHALL BE CENTERED BETWEEN NEAREST ADJACENT WALL

INTERSECTIONS, UNLESS OTHERWISE DIMENSIONED.

OWNERSHIP OF DRAWINGS AND CONTRACT ITEMS:

1. THE CONTRACT DOCUMENTS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE

ARCHITECT WHETHER THE PROJECT FOR WHICH THEY ARE PREPARED IS EXECUTED OR NOT. THE CONTRACT

DOCUMENTS ARE NOT TO BE USED BY OWNER, LANDLORD, OR TENANT FOR OTHER PROJECTS OR EXTENSIONS

TO THE PROJECT NOR ARE THEY TO BE MODIFIED IN ANY MANNER WHATSOEVER EXCEPT BY AGREEMENT IN

WRITING AND WITH APPROPRIATE COMPENSATION TO THE ARCHITECT. IF COPIES ARE REQUIRED, NOTIFY THE

ARCHITECT OF REQUEST FOR INSTRUCTIONS.

2. THE CONTRACT DOCUMENTS CONSIST OF THE FOLLOWING:

A. DRAWINGS AND SPECIFICATIONS

B. ANY AND ALL ADDENDA

3. IF AT ANY TIME BEFORE COMMENCEMENT OF WORK, OR DURING PROGRESS THEREOF, CONTRACTOR'S

METHODS, EQUIPMENT OR APPLIANCES ARE INEFFICIENT OR INAPPROPRIATE FOR SECURING QUALITY OF

WORK, OR RATE OF PROGRESS INTENDED BY CONTRACT DOCUMENTS, OWNERS MAY ORDER CONTRACTOR TO

IMPROVE THE QUALITY OR INCREASE THEIR EFFICIENCY. THIS WILL NOT RELIVE CONTRACTOR OF HIS SURETIES

FROM THEIR OBLIGATIONS TO SECURE QUALITY OR WORK AND RATE OF PROGRESS SPECIFIED IN CONTRACT.

4. THE CONTRACTOR SHALL COORDINATE ALL PORTIONS OF THE WORK AS DESCRIBED IN THE CONTRACT

DOCUMENTS. NOTIFY THE ARCHITECT IN WRITING FOR RESOLUTION OF ALL DISCREPANCIES PRIOR TO

CONSTRUCTION.

DIMENSIONAL COORDINATION OF DRAWINGS:

1. DO NOT SCALE DRAWINGS; DIMENSIONS GOVERN. VERIFY DIMENSIONS WITH FIELD CONDITIONS. IF

DISCREPANCIES ARE DISCOVERED BETWEEN FIELD CONDITIONS AND DRAWINGS OR BETWEEN

DRAWINGS, CONTACT THE ARCHITECT FOR RESOLUTION BEFORE PROCEEDING.

2. HORIZONTAL DIMENSIONS INDICATED ARE TO/FROM FINISHED FACE OF CONSTRUCTION, EXCEPT AS

NOTED.

3. VERTICAL DIMENSIONS ARE FROM TOP OF FLOOR SLAB (OR SUB FLOOR), EXCEPT WHERE NOTED TO

BE FROM ABOVE FINISHED FLOOR. (A.F.F.)

4. DIMENSIONS ARE NOT ADJUSTABLE WITHOUT APPROVAL OF ARCHITECT UNLESS OTHERWISE

NOTED ON DRAWINGS.

5. THE CONTRACTORS SHALL CONTINUOUSLY CHECK ARCHITECTURAL, AND STRUCTURAL

CLEARANCES FOR ACCESSIBILITY OF EQUIPMENT AND MECHANICAL AND ELECTRICAL SYSTEMS. NO

ALLOWANCE OF ANY KIND WILL BE MADE FOR THE CONTRACTOR'S NEGLIGENCE TO FORESEE MEANS

OF INSTALLING EQUIPMENT INTO POSITION INSIDE STRUCTURES OR PROPOSED CONSTRUCTION

ELEVATIONS. THE CONTRACTOR IS RESPONSIBLE TO NOTIFY THE ARCHITECT OF ANY ITEMS THAT

MAY CAUSE A CHANGE FROM THE DIMENSIONS OUTLINED IN THE CONSTRUCTION CAUSE A CHANGE

FROM THE DIMENSIONS OUTLINED IN THE CONSTRUCTION DOCUMENTS FOR THE INSTRUCTIONS TO

CLARIFY OR MODIFY OF THE AREA.

6. FLOOR TOLERANCE: FINISHED FLOOR SLABS TO BE LEVELED TO FLOOR CLASSIFICATION-"VERY

FLAT." TEST AREA FF/FL NUMBERS.

(APPROXIMATE EQUIVALENCE OF FF NUMBERS AND STRAIGHT EDGE MEASUREMENTS IS BETWEEN 1/8'

TO 3/16" GAP UNDER 10'-0" STRAIGHTEDGE.) CONTRACTORS TO IMMEDIATELY VERIFY SLOPE AND

REPORT ANY DEVIATIONS FROM ABOVE STATED TOLERANCE TO THE ARCHITECT PRIOR TO

COMMENCING THE WORK. ALIGNMENT OF DOOR HEADS AND OTHER CRITICAL HORIZONTAL

ELEMENTS SHALL BE MAINTAINED AT A CONSTANT LEVEL AND SHALL NOT FOLLOW VARIATIONS IN

FLOOR PLANES. CONTRACTOR IS RESPONSIBLE TO LEVEL FLOOR TO MEET ACCEPTABLE

TOLERANCES REQUIRED.

7. CONTRACTORS TO LAYOUT ALL PARTITIONS IN CHALK ON FLOOR SLAB FOR APPROVAL BEFORE

BEGINNING CONSTRUCTION.

8. ANY DIMENSION NOTED "VERITY, OR VERIFY IN FIELD (VIF)" MUST BE REVIEWED WITH ARCHITECT

BEFORE BEGINNING CONSTRUCTION.

9. DIMENSIONS INDICATED TO BE "CLEAR" SHALL BE MAINTAINED. ANY DISCREPANCIES OR

VARIATIONS IN THESE DIMENSIONS SHALL BE REVIEWED WITH THE ARCHITECT BEFORE PROCEEDING

WITH WORK IN THE QUESTIONABLE AREA.

10. IN THE EVENT OF A CONFLICT BETWEEN DATA SHOWN ON DRAWINGS AND DATA SHOWN ON THE

SPECIFICATIONS, THE SPECIFICATIONS SHALL GOVERN, BUT IF THERE IS NOT A SPECIFICATION

SECTION PROVIDED FOR A PRODUCT THAT IS CLEARLY INDICATED ON THE DRAWINGS, THE

CONTRACTOR IS RESPONSIBLE TO PROVIDE AND INSTALL THAT PRODUCT AS NOTED ON DRAWINGS

AND REQUEST A SPECIFICATION FROM THE ARCHITECT PRIOR TO ORDERING. DETAIL DRAWINGS TAKE

PRECEDENCE OVER DRAWINGS OF LARGER SCOPE. SHOULD THE CONTRACTORS AT ANY TIME

DISCOVER AN ERROR IN A DRAWING OR SPECIFICATION, OR A DISCREPANCY OR VARIATION BETWEEN

DIMENSIONS OR DRAWINGS AND MEASUREMENTS AT SITE, OR LACK OF DIMENSIONS OR OTHER

INFORMATION, HE SHALL NOT PROCEED WITH THE WORK AFFECTED UNTIL CLARIFICATION HAS BEEN

COMPLETED WITH THE ARCHITECT, OR CONTRACTOR ASSUMES RESPONSIBILITY FOR MODIFICATION

OF ALL ASSOCIATED WORK INSTALLED INCORRECTLY AS DETERMINED BY ARCHITECT.

DOOR NOTES:

1. PARTITION TYPES ABOVE DOORS ARE TO SAME AS THE ADJACENT PARTITIONS (U.N.O.)

2. VERIFY DOOR UNDERCUTS WITH ARCHITECT PRIOR TO INSTALLATION.

ADA (AMERICANS WITH DISABILITIES) ITEMS:

1. PROVIDE A MINIMUM DIMENSION OF 18" CLEAR ON THE PULL SIDE AND 12" CLEAR ON THE PUSH SIDE

OF ALL H.C. ACCESSIBLE DOORS (TYPICAL). NOTIFY THE ARCHITECT OF CONFLICTS FOR

CLARIFICATION.

SCHEDULING ITEMS:

1. CONTRACTOR SHALL ORDER AND SCHEDULE DELIVERY OF MATERIALS IN AMPLE TIME TO AVOID

DELAYS IN CONSTRUCTION. IF AN ITEM IS FOUND TO BE UNAVAILABLE OF HAVE A LONG LEAD TIME,

CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY.

BUILDING REQUIREMENTS AND TENANT ITEMS:

1. GENERAL CONTRACTOR SHALL REVIEW THE BASE BUILDING CONTRACT DOCUMENTS AND SHALL

COMPLY WITH ALL BASE BUILDING REQUIREMENTS AND DESIGN CRITERIA.

BLOCKING AND BRACING:

1. COORDINATE AND PROVIDE BLOCKING/BACKING IN PARTITIONS OR CEILINGS BEHIND ALL MOUNTED

ITEMS. WALLS TO RECEIVE TILE PROVIDE CEMENT BACKER BOARD FOR SECURE MOUNTING. PROVIDE

BLOCKING AT ALL SIDES OF RECESSED ITEMS THAT REQUIRE SECURE ATTACHMENT.

2. ALL PARTITIONS TO STRUCTURE ARE FOR ACOUSTICAL SEPARATION AND/OR SECURITY, NOT FOR

FIRE RATING, UNLESS NOTED OTHERWISE (U.N.O.)

3. PROVIDE AND INSTALL WOOD BLOCKING AS REQUIRED AT ALL WALL HUNG SHELVING, CABINETS,

WOOD PANELS, EQUIPMENT, LIGHT FIXTURES, ETC. U.N.O. VERIFY SHOP STANDARD WITH MILLWORK

SUBCONTRACTOR AND REVIEW WITH ARCHITECT FOR ACCEPTANCE PRIOR TO INSTALLATION.

M.E.P. COORDINATION ITEMS (SEE M.E.P. DRAWINGS)

1. ALL TELEPHONE AND DATA WORK SHALL BE COORDINATED BY THE CONTRACTOR WITH OWNER.

2. COORDINATE LOCATIONS OF DATA, SECURITY, MECHANICAL, ELECTRICAL, ETC. WITH BANK

SECURITY CONTRACTOR.

SUBMITTALS AND SHOP DRAWING QUALITY:

1. MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS, SHOP DRAWINGS AND LAYOUTS SHALL BE

SUBMITTED AS SOON AS POSSIBLE AFTER AWARD OF CONTRACT TO ARCHITECT. NO CONSTRUCTION

SHALL PROCEED UNTIL APPROVAL OF THESE DRAWINGS. ALL OF THE TRADES NOTED ABOVE SHALL

SUBMIT DRAWINGS IN SAME TIME FRAME FOR ARCHITECT TO REVIEW DOCUMENTS FOR

COORDINATION ITEMS AND ISSUES.

2. CONTRACTORS SHALL PROVIDE MANUFACTURER'S SPECIFICATIONS INSTALLATION INSTRUCTIONS,

SHOP DRAWINGS, SAMPLES FOR REVIEW AND APPROVAL OF ALL MATERIALS, METHODS, AND TRADES

TO BE USED PRIOR TO ORDERING OR PROCEEDING WITH THE WORK.

3. CONTRACTORS SHALL PROVIDE MANUFACTURER'S RECOMMENDED SPECIFICATIONS AND

INSTALLATION PROCEDURES. IF THESE DOCUMENTS ARE CONTRARY TO THE CONTRACT

DOCUMENTS, CONTRACTOR SHALL NOTIFY ARCHITECT IN WRITING IMMEDIATELY TO RESOLVE

DISCREPANCIES PRIOR TO PROCEEDING WITH THE WORK.

4. ONLY NEW ITEMS OF RECENT MANUFACTURER, OF STANDARD QUALITY, FREE FROM DEFECTS, WILL

BE PERMITTED ON THE WORK. REJECTED ITEMS SHALL BE REMOVED IMMEDIATELY FROM THE WORK

AND REPLACED WITH ITEMS OF THE QUALITY SPECIFIED. FAILURE TO REMOVE REJECTED MATERIALS

AND EQUIPMENT SHALL NOT RELIVE THE CONTRACTOR FROM THE RESPONSIBILITY FOR QUALITY AND

CHARACTER OF ITEMS USED NOR FROM ANY OTHER OBLIGATIONS IMPOSED ON HIM/HER BY THE

CONTRACT.

5. NO WORK DEFECTIVE IN CONSTRUCTION OR QUALITY OR DEFICIENT IN ANY REQUIREMENTS OF THE

CONTRACT DRAWINGS AND THE SPECIFICATIONS WILL BE ACCEPTABLE IN CONSEQUENCE OF

ARCHITECT'S FAILURE TO DISCOVER OR TO POINT OUT DEFECTS OR DEFICIENCIES DURING

CONSTRUCTION; NOR WILL PRESENCE OF OTHER PARITIES ON SITE, RELIEVE CONTRACTORS FROM

RESPONSIBILITY FOR SECURING QUALITY AND PROGRESS OF WORK AS REQUIRED BY CONTRACT.

DEFECTIVE WORK REVEALED WITHIN REQUIRED TIME GUARANTEES SHALL BE REPLACED BY WORK

CONFORMING WITH INTENT OF CONTRACT. NO PAYMENT, WHETHER PARTIAL OR FINAL, SHALL BE

CONSTRUED AS AN ACCEPTANCE OF DEFECTIVE WORK OR OF IMPROPER MATERIALS.

6. MATERIALS AND WORKMANSHIP SPECIFIED BY REFERENCE TO NUMBER, SYMBOL, TITLE, OF A

SPECIFICATIONS SUCH AS COMMERCIAL STANDARDS, FEDERAL SPECIFICATION, TRADE ASSOCIATION

STANDARD, OR OTHER SIMILAR STANDARD, SHALL COMPLY WITH REQUIREMENTS IN LATEST EDITION

OF REVISION THEREOF AND WITH ANY AMENDMENT OR SUPPLEMENTAL THERETO IN EFFECT ON DATE

OF ORIGIN OF THIS PROJECT'S CONTRACT DOCUMENTS. SUCH STANDARD, EXCEPT AS MODIFIED

HEREIN, SHALL HAVE FORCE AND EFFECTS AS THOUGH PRINTED IN CONTRACT DOCUMENTS.

7. REFERENCES TO MAKES, BRANDS, MODELS, ETC., IS TO ESTABLISH TYPE AND QUALITY DESIRED;

SUBSTITUTIONS OF ACCEPTABLE EQUALS WILL NOT BE PERMITTED UNLESS SPECIFICALLY NOTED

OTHERWISE WHEN MADE ACCORDINGLY TO PROCEDURES FOR SUBSTITUTIONS.

8. CUSTOM MILLWORK, UNLESS NOTED OTHERWISE, ARCHITECTURAL MILLWORK SHALL COMPLY WITH

ARCHITECTURAL WOODWORK INSTITUTE (AWI) QUALITY STANDARDS PREMIUM GRADE, SEAL ALL

WOOD SURFACES NOT RECEIVING PAINT OR PLASTIC LAMINATE, TO PREVENT MOISTURE

PENETRATION.

FIRE EXTINGUISHERS:

1. NEW FIRE EXTINGUISHER BOXES WITH FIRE EXTINGUISHERS TO BE RECESSED, ONE EXTINGUISHER

PER BOX. LOCATIONS AND DIMENSIONS MUST MEET OR EXCEED ALL ADA CODES. MINIMUM OF ONE

(1) FIRE EXTINGUISHER FOR EVERY 75 FEET TRAVEL DISTANCE STANDARD.

2. PROVIDE NEW FIRE EXTINGUISHERS IN LOCATIONS WHERE EXISTING WALL MOUNTS ARE RETAINED.

BB

G -

00

2A

BB

REV

IATI

ON

S, SY

MB

OLS A

ND

DR

AW

ING

S IN

DEX

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

20

21

- 0

5

FIL

E:

DR

AW

N B

Y:

DA

TE

: 1

0/2

8/2

02

1

RESPIT

E R

ELO

CA

TIO

NS

11

1 M

AP

LE

ST

RE

ET

BU

FF

AL

O,

NE

W Y

OR

K 1

42

04

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

75

JA

ME

ST

OW

N S

TR

EE

TG

OW

AN

DA

, N

EW

YO

RK

14

07

2

BID

SET

Page 3: RESPITE RELOCATIONS

ADA NOTES:

1. THIS BUILDING SHALL COMPLY WITH THE PROVISIONS OF THE ADAAG. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO, DOOR SIZES, THRESHOLDS, DOOR PULLS, DOOR

HARDWARE, GRAB BARS, RESTROOM FIXTURES, TOILET PARTITIONS, ECT., THE FOLLOWING EXCERPTS FROM THE ADAAG SHALL BE APPLIED TO THIS BUILDING BUT IN NO

WAY LIMIT THE APPLICABILITY OF THOSE SECTIONS NOT LISTED.

2. THIS BUILDING SHALL BE ACCESSIBLE AT ALL PRIMARY ENTRANCES AND SUCH ACCESSIBLE ROUTE SHALL CONNECT ALL ACCESSIBLE SPACES AND ELEMENTS WITHIN

THE BUILDING. ALL OBJECTS WHICH OVERHANG OR PROTRUDE INTO CIRCULATION PATHS SHALL COMPLY WITH SECTION 4.4 OF THE ADAAG. GROUND FLOOR SURFACES

ALONG ACCESSIBLE ROUTES AND IN ACCESSIBLE ROOMS AND SPACES SHALL COMPLY WITH 4.5 OF THE ADAAG. (ADAAG 4.1.3 ACCESSIBLE BUILDINGS: NEW

CONSTRUCTION) ACCESSIBLE ROUTE SHALL INCLUDE ACCESS FROM ACCESSIBLE PARKING SPACES TO THE ACCESSIBLE ENTRY OF THE BUILDING AND INTERIOR

ACCESSIBLE AREAS.

3. GROUND FLOOR SURFACES ALONG ACCESSIBLE ROUTES AND IN ACCESSIBLE ROOMS AND SPACES INCLUDING FLOORS, WALKS, RAMPS, STAIRS, AND CURB RAMPS,

SHALL BE STABLE, FIRM, SLIP-RESISTANT, AND SHALL COMPLY WITH 4.5. (ADAAG 4.5.1)

4. CHANGES IN LEVEL UP TO 1/4 INCH VERTICAL MAY BE WITHOUT EDGE TREATMENT. CHANGES IN LEVEL BETWEEN 1/4 INCH AND 1/2 INCH SHALL BE BEVELED WITH

SLOPE NO GREATER THAN 1:2. CHANGES IN LEVEL GREATER THAN 1/2 INCH SHALL BE ACCOMPLISHED BY MEANS OF A RAMP THAT COMPLIES WITH ADAAG 4.7 OR 4.8.

(ADAAG 4.5.2)

5. IF CARPET OR CARPET TILE IS USED ON A GROUND OR FLOOR SURFACE, THEN IT SHALL BE SECURELY ATTACHED; HAVE A FIRM CUSHION, PAD, OR BACKING, OR NO

CUSHION OR PAD; AND HAVE A LEVEL LOOP, TEXTURED LOOP, LEVEL CUT PILE, OR LEVEL CUT/UNCUT PILE FIXTURE. THE MAXIMUM PILE THICKNESS SHALL BE 1/2 INCH.

EXPOSED EDGES OF CARPET SHALL BE FASTENED TO FLOOR SURFACES AND HAVE TRIM ALONG THE ENTIRE LENGTH OF THE EXPOSED EDGE. CARPET EDGE TRIM SHALL

COMPLY. (ADAAG 4.5.3)

6. PER ADAAG, THE HEIGHT OF ALL ELECTRICAL OUTLETS, SWITCHES, AND CONTROLS SHALL BE MAX. 48" AFF. MIN. 15" (ADAAG 4.2.7.3)

7. PROVIDE PATH OF TRAVEL WITH RUNNING SLOPES NOT TO EXCEED 5% AND CROSS SLOPES NOT TO EXCEED 2% (ADAAG 4.3.7)

2'-3

" O

R B

ELO

W

4" MAX

6'-8

"_ >

X

FIGURE 307.2

LIMITS OF PROTRUDING OBJECTS

FIGURE 308.2.2

OBSTRUCTED HIGH FORWARD REACH

FIGURE 308.3.1

OBSTRUCTED SIDE REACH

FIGURE 308.3.2

OBSTRUCTED HIGH SIDE REACH

FIGURE 308.2.1

OBSTRUCTED FORWARD REACH

3'-8

" M

AX

1'-8" - 2'-1"> 10" MAX

1'-3

" M

IN

4'-0

" M

AX

10" MAX

1'-3

" M

IN

4'-0

" M

AX

(a) (b)

2'-1

0" M

AX

4'-0

" M

AX

2'-1

0" M

AX

3'-1

0" M

AX

10"- 2'-0">

4'-0

" M

AX

1'-8" MAX

(a) (b)

FIGURE 605.2

HEIGHT OF URINALS

1'-5

" M

AX

3'-8

" M

AX

FLUSH LEVER

FIGURE 606.2 (a)

HEIGHT OF LAVATORIES AND SINKS

1'-5" MIN - 1'-10" MAX

9" M

IN

2'-1

0" M

AX

2'-3

" M

IN

3'-4

" M

AX

5" MAX 1'-3" MAX

FIGURE 406.2

DRINKING FOUNTAIN SPOUT LOCATION

(a) FORWARD APPROACH

1'-6" MIN

(a) FRONT APPROACH, PULL SIDE

5'-0

" M

IN

3'-0" MIN

(c) HINGE APPROACH, PULL SIDE

3'-6

" M

IN *

*

1'-10" MIN

(e) HINGE APPROACH, PUSH SIDE

1'-0" MIN *4'-0

" M

IN

1'-0" MIN *

5'-0

" M

IN

(b) FRONT APPROACH, PUSH SIDE

4'-6

" M

IN

3'-6" MIN

(d) HINGE APPROACH, PULL SIDE

2'-0" MIN

(f) LATCH APPROACH, PULL SIDE

4'-0

" M

IN *

3'-6

" M

IN *

(g) LATCH APPROACH, PUSH SIDE

2'-0" MIN

* If both closer and latch are provided

* 4'-6" min if closer is provided

* If both closer and latch are provided

** 4'-0" min if both closer and latch provided

* 4'-0" min if closer is provided

FIGURE 404.2.3.2

MANEUVERING CLEARANCES AT

MANUAL SWINGING DOORS

FIGURE 604.5.1

SIDE WALL GRAB BAR FOR WATER CLOSET

2'-9

" -

3'-0

"

3'-3

" -

3'-5

"1'

-6"

MIN

1'-0" MAX

3'-3" - 3'-5"

3'-6" MIN

4'-6" MIN

2'-9

" -

3'-0

"

CL

1'-0" MIN2'-0" MIN

3'-0" MIN

FIGURE 604.5.2

REAR WALL GRAB BAR FOR WATER CLOSET

FLUSH HANDLE

ON OPEN SIDE

1'-5

" -

1'-7

"

1'-6"

CL

1'-6

" M

IN

2'-0" MIN3'-6" MAX

112"

MIN

CLE

AR

(a) PROTRUDING DISPENSER

BELOW GRAB BAR

FIGURE 604.7

DISPENSER OUTLET LOCATION

(b) PROTRUDING DISPENSER

ABOVE GRAB BAR(c) RECESSED DISPENSER

2'-0" MIN

3'-0" MAX

4'-0

" M

AX

1'-0

" M

IN2'-0" MIN

3'-0" MAX

4'-0

" M

AX

1'-6

" M

IN

3'-6" MAX

5'-0" MIN

4'-8

" M

IN

OTHER FIXTURES NOT

ALLOWED WITHIN THIS AREA

FIGURE 604.3

SIZE OF CLEARANCE FOR WATER CLOSET

1'-3" MIN

CL

5'-0" MIN

4'-8

" M

IN

FIGURE 604.9.2

WHEELCHAIR ACCESSIBLE TOILET COMPARTMENTS

(a) WALL-HUNG WATER CLOSET - ADULT

4'-1

1" M

IN

(b) FLOOR-MOUNTED WATER CLOSET - ADULT

WALL-HUNG AND FLOOR-MOUNTED WATER CLOSET - CHILDREN

5'-0" MIN

4" MAX6" TOE

3'-6

" M

IN

5'-0

" M

IN

FIGURE 604.9.3.1 (c)

WHEELCHAIR ACCESSIBLE COMPARTMENT DOOR

OPENINGS - ALTERNATE

DOOR SHALL NOT SWING INTO

THE REQUIRED MINIMUM AREA

OF THE COMPARTMENT

4'-11" MIN

4'-8" MIN

(FLOOR MOUNTED W.C.) - ADULT

WALL AND FLOOR MOUNTED W.C. - CHILDREN

(WALL MOUNTED W.C.) - ADULT

1'-0

" -

1'-6

" C

HIL

DR

EN

1'-4

" -

1'-6

" A

DU

LT

CL

CLEAR 9" HIGH

2'-8" CLEAR DOOR

1'-6" MIN

(a) PULL SIDE

5'-0

" M

IN

FIGURE 404.2.3.5

MANEUVERING CLEARANCE AT RECESSED DOORS

8">

X 4'-0

" M

IN

(b) PUSH SIDE

8">

X 4'-0

" M

IN

(c) PUSH SIDE, DOOR PROVIDED

WITH BOTH CLOSER AND LATCH

8">

X 1'-0" MIN 5'-0" MIN

4'-0

" M

IND

OO

R W

IDT

H

FIGURE 404.2.5

TWO DOORS IN A SERIES

12"

MA

X

14"

MA

X

21

14"

- 1

2"

21

(a)

(b)

FIGURE 303.3

BEVELED CHANGES IN ELEVATION

5'-0"

(a) CIRCULAR

(b) T-SHAPED

5'-0"

5'-0

"3'-0

" M

IN2'

-0"

MIN

3'-0" 1'-0" MIN1'-0" MIN

FIGURE 304.3

SIZE OF TURNING SPACE(a) ELEVATION (b) PLAN

2'-6

" M

IN

2'-1" MAX

2'-3

" 9" M

IN

8" MIN

11" MIN

4'-0"

FIGURE 306.3

KNEE CLEARANCE

(a) ELEVATION (b) PLAN

2'-6

" M

IN

1-5" - 2'-1"

9" M

IN

8" MIN

6" MAX

4'-0"

FIGURE 306.2

TOE CLEARANCE

AREA OF

REFUGE

AREA OF

REFUGE

5'-0

" M

AX

4'-0

" M

IN

GRADE 2 BRAILLE

NOTE: FOR BRAILLE MOUNTING HEIGHT SEE SECTION 703.4.5

FIGURE 703.4.5

HEIGHT OF BRAILLE CHARACTERS ABOVE FLOOR

MEN.....

6" M

IN

FIGURE 703.5

PICTOGRAM FIELD

201 1

12CURB RAMP MAXIMUM SLOPEADJOINING SURFACE MAXIMUM SLOPE

FIGURE 406.2

COUNTER SLOPE OF SURFACES

ADJACENT TO CURB RAMPS

6" M

AX

RIS

E

WIT

HO

UT

HA

ND

RA

IL

404.2.6 DOOR HARDWARE:

HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE PARTS ON ACCESSIBLE DOORS SHALL HAVE A

SHAPE THAT IS EASY TO GRASP WITH ONE HAND AND DOES NOT REQUIRE TIGHT GRASPING, PINCHING, OR

TWISTING OF THE WRIST TO OPERATE. OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 INCHES MINIMUM

AND 48 INCHES MAXIMUM ABOVE THE FLOOR. WHERE SLIDING DOORS ARE IN THE FULLY OPEN POSITION,

OPERATING HARDWARE SHALL BE EXPOSED AND USABLE FROM BOTH SIDES.

404.2.7 DOOR CLOSING SPEED

DOOR CLOSERS SHALL BE ADJUSTED SO THAT FROM AN OPEN POSITION OF 90 DEGREES, THE TIME REQUIRED

TO MOVE THE DOOR TO AN OPEN POSITION OF 12 DEGREES SHALL BE 5 SECONDS MINIMUM.

406.1 GENERAL

RAMPS ALONG ACCESSIBLE ROUTES SHALL COMPLY WITH SECTION 405.

CURB RAMPS ON ACCESSIBLE ROUTES SHALL COMPLY WITH SECTIONS 406, 405.2, 405.3, AND 405.10.

602 DRINKING FOUNTAINS

602.1 GENERAL

ACCESSIBLE DRINKING FOUNTAINS SHALL COMPLY WITH SECTION 602 AND 307.

602.4 SPOUT OUTLET HEIGHT

SPOUT OUTLETS OF WHEELCHAIR ACCESSIBLE DRINKING FOUNTAINS SHALL BE 36 INCHES MAXIMUM ABOVE

THE FLOOR. SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSON SHALL BE 38 INCHES MINIMUM

AND 43 INCHES MAXIMUM ABOVE THE FLOOR.

602.5 SPOUT LOCATION

THE SPOUT SHALL BE LOCATED 15 INCHES MINIMUM FROM THE VERTICAL SUPPORT AND 5 INCHES MAXIMUM

FROM THE FRONT EDGE OF THE DRINKING FOUNTAIN INCLUDING BUMPERS. WHERE ONLY A PARALLEL

APPROACH IS PROVIDED, THE SPOUT SHALL BE LOCATED 3 1/2" INCHES MAXIMUM FROM THE FRONT EDGE OF

THE DRINKING FOUNTAIN, INCLUDING BUMPERS.

603 TOILET AND BATHING ROOMS

603.2 CLEARANCES

A TURNING SPACE COMPLYING WITH "T" OR CIRCULAR WITHIN ROOM.

603.2.1 OVERLAP

CLEAR FLOOR SPACES, CLEARANCE AT FIXTURES, AND TURNING SPACES

603.2.2 DOOR SWING

DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE FOR ANY FIXTURE UNLESS THE

ROOM IS FOR INDIVIDUAL USE AND A CLEAR FLOOR SPACE OF 30 X 48" IS PROVIDED WITHIN THE ROOM BEYOND

THE ARC OF THE DOOR SWING.

603.3 MIRRORS

WHERE MIRRORS ARE LOCATED ABOVE LAVATORIES, A MIRROR SHALL BE LOCATED OVER THE ACCESSIBLE

LAVATORY AND SHALL BE MOUNTED WITH THE BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES

MAXIMUM ABOVE THE FLOOR. WHERE MIRRORS ARE LOCATED ABOVE COUNTERS THAT DO NOT CONTAIN

LAVATORIES, THE MIRROR SHALL BE MOUNTED WITH THE BOTTOM EDGE OF THE REFLECTING SURFACE 40

INCHES MAXIMUM ABOVE THE FLOOR.

603.4 COAT HOOKS AND SHELVES

COAT HOOKS SHALL BE LOCATED WITHIN ONE OF THE REACH RANGES SPECIFIED IN SECTION 308. SHELVES

SHALL BE 40 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FLOOR.

604.5 GRAB BARS

SEE TYPICAL FIGURE 604.3 FOR DETAILS.

604.5.1 FIXED SIDE WALL GRAB BARS

FIXED SIDE-WALL GRAB BARS SHALL BE 42 INCHES MINIMUM IN LENGTH, LOCATED 12 INCHES MAXIMUM FROM

THE REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAL WALL. IN ADDITION, A VERTICAL GRAB

BAR 18 INCHES MINIMUM IN LENGTH SHALL BE MOUNTED WITH THE BOTTOM OF THE BAR LOCATED 39 INCHES

MINIMUM AND 41 INCHES MAXIMUM ABOVE THE FLOOR, AND WITH THE CENTER LINE OF THE BAR LOCATED 39

INCHES MINIMUM AND 41 INCHES MAXIMUM FROM THE REAR WALL.

607.4.1.2.1HORIZONTAL GRAB BARS

A HORIZONTAL GRAB BAR 24" MINIMUM IN LENGTH SHALL BE PROVED ON THE CONTROL END WALL AT THE

FRONT EDGE OF THE BATHTUB.

609.8 STRUCTURAL STRENGTH

ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS USED WHERE A VERTICAL OR HORIZONTAL

FORCE OF 250 POUNDS IS APPLIED AT ANY POINT ON THE GRAB BAR, FASTENER, MOUNTING DEVICE OR

SUPPORTING STRUCTURE.

CHAPTER 7 COMMUNICATION ELEMENTS AND FEATURES

702 ALARMS

ACCESSIBLE AUDIBLE AND VISUAL ALARMS AND NOTIFICATION APPLIANCES SHALL BE INSTALLED IN

ACCORDANCE WITH NFPA 72.

HEIGHT ABOVE FLOOR TO

BASELINE OF CHARACTER

40" TO LESS THAN OR

EQUAL TO 70"

GREATER THAN 70" TO

LESS THAN OR EQUAL TO

120"

GREATER THAN 120"

LESS THAN 6'-0"

MINIMUM CHARACTER

HEIGHT

HORIZONTAL VIEWING

DISTANCE

5/8"

LESS THAN 15'-0" 2"

LESS THAN 21'-0" 3"

6'-0" AND GREATER5/8", PLUS 1/8" PER FOOT OF

VIEWING DISTANCE ABOVE 6'-0"

15'-0" AND GREATER

21'-0" OR GREATER

2", PLUS 1/8" PER FOOT OF

VIEWING DISTANCE ABOVE 15'-0"

3", PLUS 1/8" PER FOOT OF

VIEWING DISTANCE ABOVE 21'-0"

703 SIGNS112" CLEAR

1-14" - 2"

FIGURE 609.2

SIZE OF GRAB BARS

AC

CESSIB

ILIT

Y D

ETA

ILS

BB

G -

00

3

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

20

21

- 0

5

FIL

E:

DR

AW

N B

Y:

DA

TE

: 1

0/2

8/2

02

1

RESPIT

E R

ELO

CA

TIO

NS

11

1 M

AP

LE

ST

RE

ET

BU

FF

AL

O,

NE

W Y

OR

K 1

42

04

REC

OV

ER

Y O

PTIO

NS M

AD

E E

ASY

IN

C.

75

JA

ME

ST

OW

N S

TR

EE

TG

OW

AN

DA

, N

EW

YO

RK

14

07

2

BID

SET

Page 4: RESPITE RELOCATIONS

155

R-2 1

202

R-2 2

206

R-2 2

153

R-2 1

165

R-2 1

154

R-2 1

163

R-2 1

133

R-2 1

156

R-2 1

155

R-2 1

148

R-2 1

148

R-2 1

162

B 2

156

B 2

128

B 2

131

R-2 1

86

R-2 1

55

R-2 1

55

R-2 1

56

R-2 1

54

R-2 152

R-2 1

104

R-2 1

108

R-2 1

102

B 2

126

B 2

136

R-2 1

138

R-2 1

158

R-2 1

546

R-2 3

453

R-2 3

110

R-2 1

160

R-2 1

160

R-2 1

24

R-2 1

20

R-2 1

18

R-2 1

18

R-2 1

102

B 2

132

B 2

146

B 2

119

B 2

124

B 2

61

R-2 1

82

R-2 1

54

R-2 1

160

R-2 157

B 1

100

R-2 1

342

R-2 2

127BEDROOM

129BEDROOM

132BEDROOM

133BEDROOM

134BEDROOM

135BEDROOM

124BEDROOM122BEDROOM

137BEDROOM 138BEDROOM 139BEDROOM 140BEDROOM

143ACTIVITY

141LAUNDRY

146BATH

144HALL

147LIV/DIN

136LIV/DIN

148KITCHEN

150KITCHEN

153HALL

151OFFICE

154OFFICE

156OFFICE

155STOR

116HALL123HALL

108HALL

157MECH

159BREAK

102CALL CNTR103RECEPTION105OFFICE 104OFFICE107EXAM 106EXAM

110LIV/DIN

109OFFICE 112STOR

113STOR

114BATH

160CONFERENCE

125HALL

111KITCHEN

117

STOR

118

STOR121DATA119MECH 120ELEC.

158HALL

101VEST

115TOILET

126LAUNDRY

130BATH

131BATH

152

128HALL

142HALL

145

HALL

PORCH

PORCH

CANOPY

RAMP

CONC. WALK

CONC. WALK

CONC. WALK

20

20 20 20

20

20

20

20

20

20

20

20

20

20

202020

20

20 20C

20 2020

20

20 20

20

20

20

75

R-2 1

2020

250'-0"

40'-0"

20

250'-0"

38'-0"

250'-0"

38'-0"

250'-0"

44'-0"

250'-0"

56'-0"

250'-0"

47'-0"

250'-0"

36'-0"

250'-0"

52'-0"

250'-0"

47'-0"

20

20

20

F.E.

F.E.

F.E.

F.E.

F.E.

F.E.

F.E.

F.E.

36"

180

11

36"

180

15

36"

180

12

36"

180

8

36"

180

11

36"

180

6

36"

180

5

C

149ACTIVITY

LIFE SAFETY SYMBOLS KEY:

20

F.E.

C

EXIT, EXIT ACCESS OR

EXIT ACCESS DOOR

##'-##" TOTAL TRAVEL DISTANCE LISTED IN

FEET TO REQUIRED EXITS (WORST CASE)

CODE LIMIT IN FEET NOT TO EXCEED

ROOM AREA IN SQUARE FEET

CALCULATED OCCUPANCY LOAD

(FLOOR AREA ALLOWANCES - IBC TABLE 1004.1.2)

OCCUPANCY CLASSIFICATION

NEW 20 MIN DOOR WITH CLOSER

####

#-# ###

####

####

####

DOOR / STAIR WIDTH IN INCHES

CAPACITY IN PERSONS ALLOWED

ACTUAL PERSON CAPACITY

FIRE EXTINGUISHER CABINET

##'-##" EXIT ACCESS DOORWAY REMOTENESS

ROOM OR SPACE DIAGONAL

ACTUAL DIMENSION NOT TO EXCEED 1/3 DIAG.##'-##"

##'-##"

EXISTING 45 MINUTE UL 'C' LABEL DOOR

AND FRAME WITH CLOSER

(1) ONE HOUR FIRE PARTITION BETWEEN

DWELLING UNITS AND CORRIDOR OR

BETWEEN DWELLING UNITS (TYPICAL)

CARRIED TO RATED ASSEMBLY ABOVE *SEE

INTERIOR WALL TYPES AND PLANS.

20 EXISTING 20 MIN DOOR WITH CLOSER

BUILDING CODE AND LIFE SAFETY SUMMARY

APPLICABLE CODES:

USE AND OCCUPANCY CLASSIFICATION:

CONSTRUCTION CLASSIFICATION AND TYPE:

FIRE SEPERATION DISTANCE:

BUILDING HEIGHT AND AREAS:

FIRE DETECTION AND PROTECTION SYSTEMS:

OCCUPANT LOADS:

FIRE RATED CONSTRUCTION:

ACCESSIBILITY:

EGRESS DOORS AND CORRIDOR WIDTHS:

-2020 INTERNATIONAL BUILDING CODE AS ADOPTED BY NEW YORK STATE

-ICC / ANSI A117.1 2009 - ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES

-2020 INTERNATIONAL EXISTING BUILDING CODE AS ADOPTED BY NEW YORK STATE

-NFPA 101 - LIFE SAFETY CODE (2000)

R-4 - GROUP RESIDENTIAL CARE FACILITY

ACCESSORY USES ARE LESS THAN 10% OF FLOOR AREA AS PER IBC 508.2.

SEE FIRE RATED CONSTRUCTION BELOW FOR SPECIFIC R-4 REQUIREMENTS

TYPE V-B - COMBUSTIBLE WOOD CONSTRUCTION

FIRE RESISTANCE RATINGS REQUIRED BY CONSTRUCTION TYPE (IBC TABLE 601):

PRIMARY STRUCTURAL FRAME - 0 HOUR

BEARING WALLS (EXTERIOR) - 0 HOUR

BEARING WALLS (INTERIOR) - 0 HOUR

FLOOR CONSTRUCTION - 0 HOUR

ROOF CONSTRUCTION - 0 HOUR

NON BEARING WALLS- 0 HOUR

EXISTING BUILDING.

ALLOWABLE VALUES (AS PER IBC TABLES 503, 504, 505):

MAX BUILDING HEIGHT: 60 FEET

MAX STORIES ABOVE GRADE PLANE: 4 STORIES

MAX FLOOR AREA: 28,000 S.F.

MAX BUILDING AREA: 112,000 S.F.

ACTUAL BUILDING HEIGHT:

ACTUAL BUILDING STORIES: 1 STORIES

1ST FLOOR GROSS AREA: 10,080 S.F.

TOTAL AREA: 10,080 S.F.

AS PER IBC SECTIONS 420.5, 903.2.8 & 903.3.1.2:

-NFPA 13 SPRINKLERS TO BE INSTALLED AT ALL AREAS.

-EXISTING SIMPLEX FIRE ALARM SYSTEM / SMOKE ALARM TO BE REUSED IN

ACCORDANCE WITH IBC 907.2.9.1.

-FIRE EXTINGUISHERS PROVIDED AS PER IBC TABLE 906.3(1) - MAX TRAVEL 75'

CALCULATED AS IBC TABLE 1004.1.2:

FIRST FLOOR: DWELLING OCCUPANTS: 20 OCCUPANTS

ACCESSORY SPACES: 48 OCCUPANTS

TOTAL BUILDING OCCUPANT LOAD: 68 OCCUPANTS

TYPE V-B REQUIRES NO BASE FIRE RATINGS.

ADDITIONAL RATINGS REQUIRED / PROVIDED ARE AS FOLLOWS:

DWELLING UNIT HORIZONTAL AND VERTICAL SEPARATION (IBC 420, 708 & 711):

SLEEPING ROOM SEPARATION WALLS - 1 HOUR MIN. FIRE PARTITIONS

REQUIRED CORRIDOR RATING - 1 HOUR CORRIDOR RATING

-MAIN BUILDING CIRCULATION PATH IS ENTIRELY ACCESSIBLE.

-BATHROOMS ARE ACCESSIBLE.

-ALL EGRESS DOORS AND STAIR DOORS TO BE MINIMUM 36" WIDTH (PROVIDED)

-CORRIDORS TO BE 44" MINIMUM IN WITH (54" WORST CASE PROVIDED)

TRUSS IDENTIFICATION:

TRUSS IDENTIFICATION:

PRODUCT INFORMATION:

MANUFACTURER: MYSAFETYSIGNS.COM

SIZE 6" DIAMETER ENGINEERING GRADE

REFLECTIVE (ADHESIVE BACKED)

MODEL: TRUSS-NY10

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

20

21

- 0

5

FIL

E:

DR

AW

N B

Y:

DA

TE

: 1

0/2

8/2

02

1

RESPIT

E R

ELO

CA

TIO

NS

11

1 M

AP

LE

ST

RE

ET

BU

FF

AL

O,

NE

W Y

OR

K 1

42

04

REC

OV

ER

Y O

PTIO

NS M

AD

E E

ASY

IN

C.

75

JA

ME

ST

OW

N S

TR

EE

TG

OW

AN

DA

, N

EW

YO

RK

14

07

2

BID

SET

LIF

E S

AFETY

FLO

OR

PLA

N

BB

/ S

E

G -

00

4

LIFE SAFETY FLOOR PLAN1/8" = 1'-0"SCALE:1 N

Page 5: RESPITE RELOCATIONS

SCALE: 1/8"= 1'-0"

EXISTING FLOOR PLAN-

CANOPY

VEST.

PORCH

PORCH

MECH. ELEC.

RAMP

CONC. WALK

CONC. WALK

CONC. WALK

CONC. WALK

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

EX

ISTI

NG

FLO

OR

PLA

N 2

02

1-0

5

FIL

E:

DR

AW

N B

Y: S

E

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

A -

00

1

DW

ELEC.

PANELS

DA

TE

: 10/2

8/2

021

1

BID

SET

Page 6: RESPITE RELOCATIONS

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

DEM

OLIT

ION

FLO

OR

PLA

N 2

02

1-0

5

FIL

E:

DR

AW

N B

Y: S

E

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

A -

00

2

SCALE: 1/8"= 1'-0"

DEMO FLOOR PLAN-

PORCH

PORCH

8"

5'-

0"

R.O

.

- REMOVE EXISTING PLUMBING FIXTURES CUT AND AND CAP ALL

UNUSED PIPING PATCH ALL DISTURBED AREAS TO MATCH EXISTING.

1

- REMOVE EXISTING DOOR AND PART OF WALL PATCH FLOOR , CEILING

AND WALLS. REUSE DOOR AT NEW LOCATION.SEE PROPOSED PLAN.

21

1

11 1

1

1

1

1

1

9

1

2

3

4

5

5

5

6

6

7

2

22

4

1

3

3

3

3

3

- REMOVE PART OR ENTIRE WALL STRUCTURE. PATCH FLOOR CEILING

AND ADJACENT WALLS. CUT AND CAP ALL PIPING AND ELECTRICAL

WIRING AND HVAC DUCTS AS NEC.

3

- REMOVE EXISTING DOOR AND FRAME. REUSE DOORS AT DESIGNATED

ROOMS IN THE PROPOSED PLAN. RETURN UNUSED DOORS TO OWNER.

4

4

44

44

4

4

4

4 4

4 4

2'-

0"

5'-

0"

+/-

R.O

.

5'-

0"

+/-

5'-

0"

+/-

R.O

.

15

'-0

"+

/-

RE

MO

VE

9'-6"+/-

9'-6"+/-

6'-

0"

+/-

RE

MO

VE

- REMOVE PART OF WALL TO CREATE NEW OPENING FOR NEW

WINDOW. PATCH WALLS AND SIDING, INSTALL NEW HEADER.

5

- REMOVE EXISTING DOOR AND FRAME. PREPARE OPENING TO RECEIVE

NEW WINDOW USE THE SAME ROUGH OPENING.PATCH WALLS AND

FLOOR.

6

7 - REMOVE PART OF WALL TO CREATE NEW OPENING FOR NEW DOOR.

PATCH WALLS AND SIDING, INSTALL NEW HEADER.

8

8 - REMOVE ALL KITCHEN CABINETS AND ISLAND. STORE AND REUSE IN

THE NEW KITCHEN LAYOUT. ADJUST TO FIT.

8

9 - REMOVE GAS CHIMNEY INSERT AND FLUE. CUT, REMOVE AND CAP GAS

LINE. RETURN CHIMNEY TO OWNER.

EXISTING WALLS TO BE REMOVED

TYPES FOR CONSTRUCTION)

NEW WALLS (SEE INTERIOR WALL

ROOM NAME

SYMBOLS

EXISTING WALLS TO REMAIN

OFFICE ROOM NUMBER102

EXISTING DOOR TO REMAIN

NEW DOOR

REMOVE EXISTING FLOOR FINISH,

CEILING FINISH AT AREAS TO BE

RENOVATED

2

3

3

3

3

4

3

3

3

3 4 3

ELEC.

PANELS

1

1

DA

TE

: 10/2

8/2

021

1

BID

SET

Page 7: RESPITE RELOCATIONS

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

PR

OPO

SED

FLO

OR

PLA

N 2

02

1-0

5

FIL

E:

DR

AW

N B

Y: S

E

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

A -

10

1

DA

TE

: 10/2

8/2

021

SCALE: 1/8"= 1'-0"

PROPOSED FLOOR PLAN-

CLO

W

D

W D

PORCH

PORCH

CLOCLO

WNDWNEW

DOORNEW

LO

CK

ER

S

CANOPY

RAMP

CONC. WALK

CONC. WALK

CONC. WALK

CONC. WALK

WNDWNEW

127BEDROOM

129BEDROOM

132BEDROOM

133BEDROOM

134BEDROOM

135BEDROOM

124BEDROOM122BEDROOM

137BEDROOM 138BEDROOM 139BEDROOM 140BEDROOM

143ACTIVITY141LAUNDRY

146BATH

144HALL147LIV/DIN

136LIV/DIN

148KITCHEN

150KITCHEN

153HALL

149ACTIVITY

151OFFICE

154OFFICE

156OFFICE

155STOR

116HALL 123HALL

108HALL

157MECH

159BREAK

102CALL CNTR103RECEPTION

105OFFICE 104OFFICE

107EXAM 106EXAM

110LIV/DIN

109OFFICE 112STOR

113STOR

2

10

'-0

"4

'-6

"

2

7'-0"

2

114BATH

160CONFERENCE

125HALL

111KITCHEN

117STOR

118STOR

121DATA119MECH 120ELEC.WNDWNEW

WNDWNEW

1

1

X

158HALL

101VEST8'-0" 8'-4"

3'-

4"

11

'-0

"+

/-

8'-0" 5'-10"+/-

10'-5"+/-

10

'-0

"5

'-0

"

11

'-0

"4

'-1

0"

7'-

10

"8

'-5

"5

'-6

"2

'-6

"+

/-

11'-9"

4'-

4"

15

'-4

"2

1'-

0"

+/-

11'-4" 6'-4" 8'-0" 12'-0"+/- 12'-5" 15'-0"+/-

9'-

6"

+/-

9'-

6"

9'-

0"

9'-

0"

+/-

115TOILET

126LAUNDRY

130BATH

131BATH

152PANT

1

B

1

B

1

C

1

C

1

B

1

B

1

B

1

B

1

B

1

C

1

B

1

C

1

B

1

A

1

C

1

C

1

C

1

A

1

A

1

A

1

A

1

A

CLO CLO CLO CLO

CLO

CLO

128HALL

142HALL145HALL

D104 D102

D105

D108

D159

D160

D151

D154

D155

D140

D137

D110

1

B

D109

D113

D114

1

B

D135

D134

D122

D133

D201

D129

D127

D152

1

B

D12318'-0"

5'-

6"

15'-10"

11'-9"

13

'-0

"

1

1

1

1

4

1

1

1

1 1

1

1

1

4

2

2

2

4

4

4

4

3

4

44

3

3

34

4

4 4 4 4

4

2 2 2

6'-

0"

4'-

6"

+/-

44

4

4 4

4

4

444

4

4

D138

D139

1

A

1

A

D144

D136

EX-1

1

A

1

A

1

F.E.

F.E.

F.E.

F.E.

F.E.

F.E.

F.E.

F.E.

BID

SET

Page 8: RESPITE RELOCATIONS

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

PR

OPO

SED

REFLEC

TED

CEIL

ING

PLA

N 2

02

1-0

5

FIL

E:

DR

AW

N B

Y: B

B

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

A -

10

2

DA

TE

: 10/2

8/2

021

SCALE: 1/8"= 1'-0"

PROPOSED REFLECTED CEILING PLAN-

127BEDROOM

129BEDROOM

132BEDROOM

133BEDROOM

134BEDROOM

135BEDROOM

124BEDROOM122BEDROOM

137BEDROOM 138BEDROOM 139BEDROOM 140BEDROOM

143ACTIVITY 141LAUNDRY146BATH

144HALL147LIV/DIN

136LIV/DIN

148KITCHEN150KITCHEN

153HALL

149ACTIVITY

151OFFICE

154OFFICE

156OFFICE

155STOR

116HALL

123HALL

108HALL

157MECH

159BREAK

102CALL CNTR103RECEPTION105OFFICE 104OFFICE107EXAM 106EXAM

110LIV/DIN

109OFFICE 112STOR

113STOR

114BATH

160CONFERENCE

125HALL

111KITCHEN

118STOR

121DATA119MECH 120ELEC.

158HALL

101VEST

115TOILET

126LAUNDRY

130BATH

152

128HALL

142HALL

KEY:

101

NOTES:

ROOM NAME

NEW 2' X 2' A.C.T

CEILING AT ADJACENT AREAS

1. ABOVE PLANS DEPICT CEILING HEIGHTS AND MATERIALS THROUGHOUT

THE FLOOR REFERENCED. SEE MECHANICAL, ELECTRIC AND FIRE

PROTECTION DRAWINGS AS APPLICABLE TO COORDINATE PLACEMENT OF

FIXTURES FROM OTHER TRADES.

2. MINIMIZE SHIFTS IN A.C.T. GRID TO THE GREATEST EXTENT POSSIBLE

BETWEEN ADJACENT AREAS.

3. A.C.T. GRID TO BE CENTERED ON EACH CORRIDOR AS DEPICTED IN

ABOVE DIAGRAMS.

4. WHERE A.C.T. GRIDS CONTIGUOUS TO EACH OTHER ARE MOUNTED AT

DIFFERENT HEIGHTS, CONTRACTOR IS TO SMOOTHLY TRANSITION

GRIDS AT A 45 DEGREE ANGLE BETWEEN CONTIGUOUS AREAS.

5. REFER TO M/P SETS TO VERIFY ALL FIXTURE AND DIFFUSER LOCATIONS.

EXISTING CEILING TO REMAIN

DROPPED SOFFIT SEPARATION 12" BELOW LOWEST

NEW SUSPENDED GYP. BOARD

ROOM NAME, NUMBER(SEE FINISH SCHEDULE FOR CEILING HEIGHTS)

117STOR

131BATH

145HALL

1

CL

CL

2'x2' STEEL ACCESS PANEL (1 HOUR FIRE RATING)

PROVIDE AND INSTALL 2'x2' 1-HOUR FIRE RATED STEEL

ACCESS PANELS, TYPICAL. INSTALL APPROXIMATELY

10' O.C. AT CORRIDORS INDICATED. VERIFY ACCESS

PANEL LAYOUT WITH ELECTRICAL, MECHANICAL AND

FIRE PROTECTION CONSIDERATIONS AS NECESSARY.

BID

SET

Page 9: RESPITE RELOCATIONS

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

RO

OM

FIN

ISH

SC

HED

ULE

AN

D IN

TER

IOR

WA

LL T

YPES

20

21

-05

FIL

E:

DR

AW

N B

Y: S

E

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

A -

10

3

DA

TE

: 10/2

8/2

021

REMARKS

ROOM FINISH SCHEDULE

FLOORMTRL. MTRL.FINISH

WALLSBASEFINISH

CEILING TRIMNORM

NAMEROOM

103

104

105

106

107

108

110

111

112

113

114

115

116

117

118

119

120

121

122

102

101

RECEPTION

OFFICE

EXAM

EXAM

STORAGE

STORAGE

ELEC

HALL

HALL

STORAGE

STORAGE

CALL CNTR

VEST.

OFFICE

HEIGHT

123

124

DATA

125

OFFICE

KITCHEN

BATH

TOILET

MECH

VINYL VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

-

-

-

PAINT

PAINT

130

126

127

128

129

VINYL GYP. BD. PAINT

VINYL GYP. BD. PAINT

VINYL GYP. BD. PAINT

VINYL GYP. BD. PAINT

VINYL GYP. BD. PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

109

LIV/DIN

BEDROOM

HALL

BEDROOM

HALL

LAUNDRY

BEDROOM

HALL

BEDROOM

BATH

VINYL GYP. BD. PAINT PAINT

VINYL GYP. BD. PAINT PAINT

PAINT PAINT

PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

* MATCH EXISTING AT NEW WORK

A.C.T.2'x2'

A.C.T.2'x2'

A.C.T.2'x2'

A.C.T.2'x2'

GYP. BD.*

132

133

134

135

136

137

138

140

141

142

143

144

145

146

147

148

151

152

153

154

131

BEDROOM

BEDROOM

BEDROOM

LIV/DIN

BEDROOM

HALL

ACTIVITY

PANT

BEDROOM

BATH

LIV/DIN

KITCHEN

BATH

BEDROOM

155

156

HALL

157

BEDROOM

LAUNDRY

HALL

HALL

ACTIVITY

KITCHEN

OFFICE

VINYL VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

VINYL

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

158

159

160

VINYL GYP. BD. PAINT

VINYL GYP. BD. PAINT

VINYL GYP. BD. PAINT

GYP. BD. PAINT

VINYL GYP. BD. PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

139

BEDROOM

149

150

OFFICE

STORAGE

OFFICE

MECH

HALL

BREAK

CONFERENCE VINYL GYP. BD. PAINT PAINT

PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

VINYL PLANK

GYP. BD.

EXIST. PAINT

GYP. BD.

GYP. BD.

GYP. BD.

*

*

*

*

EXIST. EXIST. EXIST. PAINT EXIST. -

VINYL VINYL GYP. BD. PAINT -PLANK A.C.T.

2'x2'PAINT

*

VINYL PLANK A.C.T.

2'x2'

PAINT

EXIST.

EXIST.

EXIST.

EXIST.

VINYL CER.TILE*

EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

EXIST. EXIST. EXIST. EXIST.

PAINT

PAINT

PAINT

* EXIST. PAINT

EXIST. EXIST. EXIST.

EXIST. EXIST. EXIST.

PAINT

PAINT

EXIST.

EXIST.

*

*

*

*

*

*

*

*

*

*

EXIST.

EXIST.

** NEW OR MATCH EXISTING AT NEW WORK **

**

**

**

**

**

** MATCH EXISTING AT NEW WORK

** NEW OR MATCH EXISTING AT NEW WORK

** NEW OR MATCH EXISTING AT NEW WORK

** NEW OR MATCH EXISTING AT NEW WORK

** MATCH EXISTING AT NEW WORK

EXIST.

EXIST.

*

GYP. BD.*

PAINT

GYP. BD.*

PAINT

*

*

*

*

*

*

*

*

*

GYP. BD.*

GYP. BD.*

PAINT

PAINT

EXIST.

EXIST.

EXIST.

EXIST.

GYP. BD.*

*

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* PATCH AND REPLACE ALL DAMAGED AREAS

* FULL HT. CERAMIC TILE AT SHOWER AREA

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

** NEW OR MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

* MATCH EXISTING AT NEW WORK

INTERIOR WALL TYPESSCALE: N.T.S.

METAL STUDS AT

16" O.C.

5/8" GYP. BD. BOTH SIDES

8'-

10

"+

/-

NEW WALLS TO

UNDERSIDE OF ROOF

DECK MATCH EXIST.

CONC.

TOP OF

TYPICAL INTERIOR

PARTITION WALL AT

EXISTING BEDROOM

WALL SEPERATION

2

EXIST.METAL STUDS

AT 16" O.C.

8'-

10

"+

/-"

W/ EXISTING

EXIST. FRAMING

INSULATION

CONC.

TOP OF

ALL CORRIDOR WALLS

30 MIN. RATING WITH

1 HR. CORRIDOR

CEILING MINIMUM

4

CONC.

TOP OF

EXISTING

CORRIDOR WALLS TO

UNDERSIDE OF TRUSS

SYSTEM

CORRIDOR

5/8" TYPE C GYP. BD. BOTH

SIDES

SEAL ALL JOINTS TO

CREATE A COMPLETELY

SEALED CORRIDOR.

A.C.T. AND

REMOVE EXIST.

GRID

5/8" GYP. BD.

BOTH SIDES

2'-

0"

+/-

EX

IST

ING

8'-

0"

W/ EXISTING

EXIST. FRAMING

INSULATION

VINYL BASE, BOTH SIDES

5/8" GYP. BD. BOTH SIDES

8'-

10

"+

/-

WALLS TO UNDERSIDE OF

WOOD TRUSS

CONC.

TOP OF

TYPICAL INTERIOR

PARTITION WALL

ASSEMBLY NOT RATED

1

W/ EXISTING

EXIST. FRAMING

INSULATION

5/8" GYP. BD. BOTH SIDES

TOP AND BOTTOM

TRACKS

VINYL BASE, BOTH SIDES

5/8" GYP. BD. BOTH SIDES

8'-

10

"+

/-

WALLS TO UNDERSIDE OF

ROO DECK

CONC.

TOP OF

3

W/ EXISTING

EXIST. FRAMING

INSULATION

5/8" GYP. BD. BOTH SIDES

EXISTING

3-5/8"METAL STUDS

AT 16" O.C.

EXISTING

EXISTING GYP. BD.

OR A.C.T.

TOP AND BOTTOM

TRACKS

TYPICAL INTERIOR

PARTITION WALL AT

NEW BEDROOM WALL

SEPERATION

3-5/8"METAL STUDS

AT 16" O.C.

TOP AND BOTTOM

TRACKS

EXISTING GYP. BD.

OR A.C.T.

EXISTING GYP. BD.

OR A.C.T.

EXISTING GYP. BD.

OR A.C.T.

EXISTING GYP. BD.

OR A.C.T.

8" 16 GA METAL

JOISTS AT 16" O.C.

8" 16 GA METAL

STUD CONT.

CUT OUT A POCKET

AT EXISTING WALL

RUN NEW FRAMING

TO SEAL WALL

CAVITY

TOP AND BOTTOM

TRACKS

VINYL PLANK

EXIST. PAINT

-

PAINT

PAINT

EXIST. *PAINT

GYP. BD. PAINT

EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

*

GYP. BD.

*

GYP. BD. PAINT

EXIST.

GYP. BD.

PAINT

PAINT

PAINTEXIST.

GYP. BD.*

GYP. BD.*

GYP. BD.*

GYP. BD.*

PAINT

PAINT

PAINT

PAINT

PAINT

*

*

*

*

EXIST.

EXIST.

EXIST.

PAINT

PAINT

*

*

*

*PAINT

EXIST.*

PAINT

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

PAINT

PAINT

PAINT

PAINT

EXIST. EXIST. EXIST. EXIST. PAINT

*GYP. BD. PAINT

*

PAINT

PAINT

GYP. BD.**

PAINT

*

PAINT

PAINT

PAINT

PAINT

PAINT

PAINT

PAINTEXIST. EXIST.*

*

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

GYP. BD.

EXIST.

GYP. BD.

GYP. BD.

GYP. BD.

PAINT

PAINT

PAINT

BID

SET

Page 10: RESPITE RELOCATIONS

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

LA

RG

E S

CA

LE P

LA

NS A

ND

20

21

-05

FIL

E:

DR

AW

N B

Y: S

E

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

A -

50

1

DA

TE

: 10/2

8/2

021

INTE

RIO

R E

LEV

ATI

ON

S

SCALE: 1/4"= 1'-0"

LARGE SCALE PLANS

W

D

W D

141LAUNDRY

148KITCHEN

150KITCHEN

159BREAK

114BATH

111KITCHEN

126LAUNDRY

5'-0"6"

3'-

0"

11'-0"

10

'-0

"

13'-10"+/-

12'-0"12'-0"

1'-6"

4" BASE

WASHERDRYER

4'-

0"

6"

3'-

0"

5'-

6"

36

FILLER

1'-

6"

15" DEEP CABINETS

DISH

36

SINK

12

24

24 24

3'-

0"

1'-

6"

2'-

6"

P. LAM. BACKSPLASH

24

30

24

2430

MICROWAVE

RANGE

36

36

REFRIG.

33

36

15

FILLER

36

36

15

FILLER

1 2

5'-0"

6'-

6"

3'-

6"

2'-

11

"

S.C.R.

SOAP

DISH

CORNER

SHELVES

C.T. SURROUND

CONT.

G.B.

EXISTING SINK

TO REMAIN

24"x36"

TILT-TYPE

MIRROR

5'-

0"

2'-

11"

1'-6"

CL

24" G.B.

M.R. GYP. BD.

CL

FLUSH VALVE LOCATED

TOWARDS OPEN SIDE

OF THE BATHROOM

3'-4"

4" BASE

2'-

11

" T.T.H.

8"

1'-

6"

18" VERT. G.B.

42" G.B.

5'-

0"

1'-0"

M.R. GYP. BD.

2'-

11

"

6'-

6"

3'-

6"

S.C.R.

3'-0"

C.T. SURROUND

CONT.

G.B.

2'-6"

60" HOSE

AND GLIDE BAR

CONTROLS

REFRIG.

33

36

18

3'-

0"

1'-

6"

2'-

6"

7

36

36

FILLER

18

OPEN

COUNTER

REF.SINK

LOCKERS

8 9

3'-

0"

12"W.X15"D.X36"

DOUBLE TIER METAL

LOCKERS

3 4 5

3'-

0"

1'-

6"

2'-

6"

30

3330

MICROWAVE

RANGE

REFRIG.

33

36

18 30

36

DISH

36

SINK

12 24

24

24

24

36

33 12

33

3312

3'-

0"

1'-

6"

2'-

6"

3'-

0"

1'-

6"

2'-

6"

11

3'-

0"

1'-

6"

2'-

6"

3'-

0"

1'-

6"

2'-

6"

30

3330

MICROWAVE

RANGE

REFRIG.

33

36

18 30

36

DISH

36

SINK

12 24

24

24

24

36

33 12

33

3312

3'-

0"

1'-

6"

2'-

6"

3'-

0"

1'-

6"

2'-

6"

4" BASE

WASHER DRYER

4'-

0" 5'-

6"

36

FILLER

1'-

6"

15" DEEP CABINETS

36

10

12 13

14 15 16

2

1

43

5REF.

SINKDW

RANGE

78

9

10131211

1415 15

3'-

6"

3'-

6"

REF.

REF.

SINK

SINK

DW

RANGE

RANGE

DW

P. LAM COUNTER

BACK SPLASH

P. LAM COUNTER

P. LAM COUNTER

BACK SPLASH

P. LAM COUNTER

P. LAM COUNTER

BACK SPLASH

P. LAM COUNTER

P. LAM COUNTER

BACK SPLASH

P. LAM COUNTER

P. LAM COUNTER

BACK SPLASH

P. LAM COUNTER

P. LAM COUNTER

BACK SPLASH

P. LAM COUNTER

P. LAM COUNTER

BACK SPLASH

P. LAM COUNTER

1'-6"

P. LAM. BACKSPLASH

2'-

11

"

6'-

6"

3'-

6"

S.C.R.

3'-0"

C.T. SURROUND

CONT.

G.B.

2'-6"

6

6

BID

SET

Page 11: RESPITE RELOCATIONS

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

DETA

ILS

20

21

-05

FIL

E:

DR

AW

N B

Y: S

E

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

A -

50

2

C

STAIN

1-3/4" FLUSH SOLID

6'-

8"

3'-0"

CORE WOOD

B

8" 5"

20

"1

2"

3'-0"

6'-

8"

SCALE: 1/8"=1'-0"

DOOR SCHEDULE #204 JAMB DETAILS #205SCALE: NTS

"1

15

16

1"

15

16

5"

7 8

"8

5

2"

5/8" GYP. BD. BOTH SIDES

HOLLOW METAL FRAME

3 ANCHORS PER JAMB (MIN.)

AT ALL METAL FRAMES

1

3-1/2" MET. STUDS

A

STAIN

1-3/4" FLUSH SOLID

6'-

8"

3'-6"

CORE WOOD

20 MINUTE RATED WITH LABEL

STAIN

1-3/4" FLUSH SOLID CORE WOOD

20 MINUTE RATED WITH LABEL

5/8"

GYP. BD.

27"W X 36"H X 27"D

W/D COUNTER DETAIL

SCALE: 3/4"=1'-0"

WASHER/DRYER SPACE

CLEAR

4'-

5"

+/-

SILL

P. LAM.

@ 24' O.C.

2 X 6's

CAULK

GRAB BAR MOUNTING DETAIL

SCALE: 1 1/2"=1'-0"

M. R. GYP. BOARD

2 X 8 FLAT

CERAMIC TILE

2'-

1"

R.O

.2

'-0

"

FIN. FLOOR

FIRE EXTINGUISHER

CABINET DETAILS

SCALE: 3/4"=1'-0"

PLAN ELEVATION

2 X 8 STUDS

11 1/2"

R.0.

RECESSED

F.E. CAB

SCALE: 3/4"=1'-0"

KITCHEN CABINET DETAIL

BOTH SIDES

W/ GYP. BD.

2 x 4 STUD WALL

MATCH CABINETS

WOOD FACE TO

OPEN COUNTER DETAIL

1 1

/4"

2"

-10

"

GRANITE COUNTERTOP

SUPPORT EA. SIDESOLID AS REQ.

C.T. BACKSPLASH

LOW WALL WHERE USED

3'-

0"

1-1

/4"

BASE

4" RES.

1'-

6"

2'-

6"

P.LAM.BACKSPLASH

TWO ROLL OUT TRAYS

AT BASE CABINETS

WOOD CABINETS

WOOD CABINETS

1'-1"SCALE: 3/4"=1'-0"

P.LAM. OUNTERTOP

SCALE: 3"=1'-0"

MARBLE SADDLE DETAIL

WIDTH

FLOOR

FRAMING

1/2

" M

AX

. L.V.T.

CERAMIC TILE WALL SADDLEMARBLE

MEMBRANE

UNCOUPLING

WOOD TRIM

JAMB EXTENSION

BENCHMARK WOOD

FRAME AND

METAL DOOR

FINISH FLOOR-

SEE FINISH

VINYL SIDING

SHIM

BENCHMARK 3-PIECE

THRESHOLD

EXTERIOR DOOR DETAIL SCALE: 3"=1'-0"

2

2

2 6

2 6

SCALE: 3"=1'-0"

TYPICAL WINDOW DETAIL

ACCESSIBLE

VINYL SIDING

SEALANT AT

SCREEN

SHEATHING

HEADER

GYP. BD.

SHIMS/BLOCKING

AS REQUIRED

JAMB EXTENSION

WOOD TRIM

FIBERGLASS

INSULATION

SCHEDULE

RO

UG

H O

PE

NIN

G

WOOD TRIM

JAMB EXTENSION

FLASHING

TYVEK TAPE

HEAD, JAMBS

AND SILL

TYVEK TAPE

FLASHING

FILL CAVITY

WITH RIGID

UNFACED INSUL.

TYVEK TAPE

FLASHING

UNFACED INSUL.

WITH RIGID

FILL CAVITY

SEALANT AT

HEAD AND JAMBS

W/ ALUMN.1x6 TRIM COVER

W/ ALUMN.1x6 TRIM COVER

W/ ALUMN.1x6 TRIM COVER

21

WINDOW SCHEDULE SCALE: 1/4"=1'-0"

VINYL WINDOW

LOW 'E' INSULATING GLASS

5.7 S.F. OPENING EGRESS UNIT

DOUBLE HUNG

VINYL WINDOW

LOW 'E' INSULATING GLASS

5.7 S.F. OPENING EGRESS UNIT

DOUBLE HUNG

2'-

3"

+/-

5'-

9"

3'-6"

R.O.

6'-0"

R.O

.

R.O.

U-0.27 MIN. U-0.27 MIN.

FULL SCREEN FULL SCREEN

MA

TC

H E

XIS

T.

FLASHING

FLASHING

SCALE: 1/2"=1'-0"

ELEVATION

1'-

6"

1'-

4"

1'-

4"

1'-

4"

1'-

0"

DEEP.

SHELVING 16"

WIRE MESH

SHELVINGAS MANUF. BY K&V.

PANTRY SHELVING DETAIL

R.O.

R.O

.

INSULATED TEMPERED GLASS

INSULATED SIDELIGHT

INSULATED METAL DOOR W/

PAINT

HANDICAPPED THRESHOLD

6'-

10

"

10'-0"

3'-0"

X

DA

TE

: 10/2

8/2

021

BID

SET

Page 12: RESPITE RELOCATIONS

127

129

132

133

134

135

124122

137 138 139 140

143

141

146

144147

136

148

150

153

149

151

154

156

155

116

123

108

157

159

103105 104107 106

110

109

112

113

114

160

125

111

117

118

121

119 120

158

101

115

126

130

131

152

128

142145

DW

W

D

102

THERMOSTATTHERMOSTATTHERMOSTATTHERMOSTAT

THERMOSTAT

THERMOSTAT

THERMOSTAT

THERMOSTAT

THERMOSTAT

THERMOSTAT

THERMOSTAT

THERMOSTAT

THERMOSTAT

THERMOSTATTHERMOSTAT

THERMOSTAT

V

V

V

V

V

V

V

V

V

V

V V V V

V

V

V

V

V

V

V

V

V

V

V

V

V V

V

8"x8" RR

12"x8"

H 150 CFM

A

A

H

H 150 CFM

F

EX. EHAUST

REGISTER 100 CFM

REMOVE EXISTING EXHAUST

REGISTERS - CAP DUCT AT MAIN

REMOVE EX. ER -

CAP DUCT AT MAIN

H

200 CFM

H

200 CFM

H

200 CFM

H

F

EX. EHAUST

REGISTER 100 CFM

EXISTING RTU-1

EXISTING RTU-2

NOTE: CHECK, TEST AND START-UP EXISTING "TRANE" ROOF TOP

UNITS / SYSTEMS. ADJUST AIRFLOWS PER UNITS SPECIFICATIONS.

REPLACE AIR FILETERS WITH MERV-13-2" FILTERS.

8"x8" RR

A

A

8"x8" RR

A

12"x12" RR

12"x12" RR

CAP

CAP

A

A

150 CFM 150 CFM

A

A

150 CFM

100 CFM

CAP

225 CFM

A

200 CFM 125 CFM

A A

CAP

200 CFM

A

H

H

E

H 100 CFM

12"x12" RR

A

A

A

150 CFM

150 CFM

150 CFM

150 CFM

H 150 CFM

H

100 CFM

CAP

A

A

6"x6" RR

12"x12" RR

12"x10"

A

A

6"x6" RR

A

A

CAP

8"x8" RR

6"x6" RR

H

HH

100 CFM

A

6"x6" RR

H

HH

12"x8"

A

12"x12" RR

A

VAV - 400 CFM

B

H

VAV - 200 CFM

B

B

B

B

B

B

BB B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

B

A

H

H

150 CFM

B

B

A

A

A A A

6"x6" RR

6"x6" RR

CAP

B

B

A

A

A

150 CFM

150 CFM

B

VAV - 600 CFM

200 CFM

200 CFM

12"x8"B

100 CFM

VAVs - 150 CFM

EX. EXST.

DUCT

A

A

NEW ER

150 CFM

NEW ER

150 CFM

CAP

B

B

50 CFM

150 CFM

B

100 CFM

100 CFM

A

VAV - 400 CFM

B

175 CFM175 CFM

AA

VAVs - 200 CFM

NEW 8x8 ER W/ 8" EXH. DUCT -

CONN. TO EX. MAIN EXH. DUCT

EX. ER

100 CFM

EX.

BPD EX.

BPD

EX. ER

100 CFM

EX. ER

100 CFM

EX. ER

100 CFM

EA EA

EA

EA

EA

RA

RA

RA

SA

SA

EX. ER

100 CFM

A 8"x8" RR

8"x8" RR

B

B

B

B

SA

SA

INDICATES EXISTING

VAV TERMINAL, TYP

RA

RA

RA

INDICATES EXISTING

VAV TERMINAL, TYP

TYPICAL EXISTING

THERMOSTAT

I

I

RA

SA SA

400 CFM

INDICATES EXISTING

VAV TERMINAL, TYP

INDICATES EXISTING

VAV TERMINAL, TYP

SA

I

12"x8"

RETURN GRILLE

LEGEND:

SUPPLY GRILLE

THERMOSTAT

(NEW OR RELOCATED)

EXHAUST / RETURN AIRFLOW

MANUAL BALANCING DAMPER

RETURN DUCT

SUPPLY DUCT

EXHAUST DUCT

CFM CUBIC FEET PER MINUTE

SA SUPPLY AIR

RR RETURN REGISTER

EA EXHAUST AIR

WC WALL CAP

SD SUPPLY DIFFUSER

EXHAUST GRILLE

FIRE RATED GRILLE

RETURN GRILLE

SUPPLY GRILLE

RETURN DUCT

SUPPLY DUCT

EXHAUST DUCT

DEMOLISHED GRILLE

EXISTING

EXISTING

EXISTING

EXISTING

EXISTING

THERMOSTAT

EXISTING

THERMOSTAT

THERMOSTAT

RELOCATE

THERMOSTAT

DEMOLISH DUCT

V

V

VEXISTING VAV

DEMOLISHED VAV

NEW VAV

CAPPED DUCT

ER EXHAUST REGISTER

VAV VARIABLE AIR VOLUME

RA RETURN AIR

THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATE THE SIZE AND

GENERAL ARRANGEMENT OF PIPING, DUCTWORK, EQUIPMENT, ETC. EXACT

LOCATIONS AND ROUTINGS SHALL BE DETERMINED IN THE FIELD BEFORE AND AS

THE WORK PROGRESSES. CAREFULLY COORDINATE THE WORK OF THIS TRADE

WITH ALL OTHER TRADES.

DRAWINGS DO NOT INDICATE ALL OFFSETS, CHANGES IN ELEVATION, ETC. WHICH

MAY BE REQUIRED BY ACTUAL FIELD CONDITIONS. THE CONTRACTOR IS TO FIELD

VERIFY CONDITIONS PRIOR TO INSTALLATION AND MAKE SUCH CHANGES IN PIPING,

DUCTWORK, EQUIPMENT LOCATIONS, ETC. AS NECESSARY TO ACCOMMODATE

FIELD CONDITIONS. COORDINATE ALL CHANGES WITH OTHER TRADES AND

ARCHITECT/ENGINEER.

INSTALL ALL PIPING, DUCTWORK, EQUIPMENT, ETC. TO AVOID INTERFERENCE WITH

THE OPERATION AND SERVICING OF ALL NEW EQUIPMENT. IN GENERAL, DO NOT INSTALL

ANYTHING ABOVE OR WITHIN 3 FT. IN FRONT OF ELECTRICAL GEAR.

THE WORK INCLUDED IN THIS CONTRACT ENCOMPASSES BOTH THE DRAWINGS

AND SPECIFICATIONS. WORK INCLUDED ON THE DRAWINGS ONLY, OR IN THE

SPECIFICATION ONLY, SHALL BE INCORPORATED AS IF INCLUDED IN BOTH.

SYSTEMS ARE INTENDED TO BE COMPLETE AND FULLY FUNCTIONING. IT IS NOT

INTENDED TO SHOW EVERY ITEM OF WORK OR MINOR PIECE OF EQUIPMENT. THE

CONTRACTOR SHALL PROVIDE SUCH COMPONENTS, ETC. AS NECESSARY OR

REQUIRED FOR A FULLY FUNCTIONING SYSTEM.

ALL DUCT AND GRILLE / REGISTER SIZES SHOWN ON PLAN ARE GIVEN IN INCH UNITS.

GENERAL NOTES:

DUCTWORK AND ACCESSORIES:

TYPE SYSTEM: LOW PRESSURE. ALL DUCTWORK AND FITTINGS, SELECTIONS,

APPLICATIONS, AND INSTALLATION SHALL BE IN ACCORDANCE WITH "SMANCA" - "HVAC

DUCT CONSTRUCTION STANDARDS". CONSTRUCTION: LOW PRESSURE DUCTWORK

SHALL BE CONSTRUCTED OF GALVANIZED STEEL SHEETS. DUCTWORK SHALL CONFORM

ACCURATELY TO THE DIMENSIONS INDICATED AND SHALL BE STRAIGHT AND SMOOTH ON

THE INSIDE WITH JOINTS NEATLY FINISHED. DUCTS SHALL BE SECURE AND ANCHORED

TO THE BUILDING STRUCTURAL COMPONENTS AND FRAMING, AND SHALL BE FABRICATED

AND SUPPORTED IN SUCH A MANNER TO PREVENT VIBRATION AND PULSATION UNDER

OPERATING CONDITIONS. BUTTON PUNCH OR BOLD CONNECTIONS IN STANDING SEAMS

SHALL BE SPACED AT NOT GREATER THAN 6-INCH ON CENTERS. LONGITUDINAL LOCKS

OR SEAMS TERMED "BUTTON PUNCH SNAP LOCK" ARE ACCEPTABLE IN LIEU OF

PITTSBURGH LOCKS. ELBOWS HALL BE RADIUS TYPE WITH A CENTER RADIUS OF 1-1/2

TIME THE WIDTH OR DIAMETER OF THE DUCT. WHERE SPACE DOES NOT PERMIT, THE

USE OF SHORT RADIUS ELBOWS HAVING A MINIMUM RADIUS OF 1.0 TIMES THE WIDTH OR

DIAMETER OF THE DUCT, OR SQUARE ELBOWS WITH FACTOR FABRICATED TURNING

VANES MAY BE USED. ALL DUCT JOINTS AND TRANSVERSE AND LONGITUDINAL SEAMS

SHALL BE SEALED WITHE A LATEX TYPE DUCT SEALER APPROVED BY THE ENGINEER.

FITTINGS: SQUARE ELBOWS, FITTINGS, AND BRANCH TAKE-OFFS SHALL BE DESIGNED

AND CONSTRUCTED AS SPECIFIED IN SMACNA. ALL GENERAL VENTILATION ITEMS SHALL

COMPLY WITH NFPA BULLETIN 90A. SLEEVED AND FRAMED OPENINGS: SPACE BETWEEN

THE SLEEVED OR FRAMED OPENING AND THE DUCT AND THE DUCT INSULATION SHALL BE

PACKED WITH MINERAL WOOL OR OTHER APPROVED MATERIAL TO MEET THE

REQUIREMENTS OF WALL CONSTRUCTION FOR SMOKE OR FIRE CONTROL.

ACOUSTICAL DUCT LINING:

LOCATION: RETURN AIR DUCTS OR AS INDICATED ON THE PLANS.

TYPE: "k-FLEX" DUCT LINER GRAY, A CLOSED CELL FLEXIBLE ELASTOMERIC FOAM

INSULATION, THICKNESS AS INDICATED ON MECHANICAL PLAN. FIRE RATING 25/50 PER

ASTM E84, UL181 RATED FOR AIR EROSION. DUCT DIMENSIONS ON DRAWINGS ARE

INSIDE CLEAR DIMENSIONS.

INSULATION - DUCTWORK - CONCEALED LOCATIONS

PROVIDE ALL LABOR, MATERIALS, ECT - REQUIRED TO PRODUCE A COMPLETELY

FINISHED INSULATION SYSTEM FOR THE FOLLOWING:

SUPPLY AIR DUCTWORK.

DUCTWORK NOTED ON PLANS.

FLAME AND SMOKE RATINGS: PROVIDE COMPOSITE MECHANICAL INSULATION

(INSULATION JACKETS, COVERINGS, SEALERS, MASTICS, AND ADHESIVES WITH FRAME

SPREAD RATING OF 25 OR LESS, AND SMOKE DEVELOPMENT RATING OF 50 OR LESS, AS

TESTED BY ASNSI/ASTM E84 (NFPA 255) METHODS.

DUCT INSULATION:

MAKE: OWENS CORNING, CERTAINTEED, KEENE.

TYPE: BLANKET FIBERGLASS IN CONCEALED AREAS, RIGID TYPE IN EXPOSED AREAS.

PROVIDE WITH FIRE RETARDANT JACKET.

APPLICATION: SEAT JOINTS AND LAB WITH VAPOR VAPOR BARRIER MASTIC AND

FASTENERS AT NO MORE THAN 18" O.C. THE PINS SHALL BE COVERED WITH

BENJAMIN/FOSTER 30-35 MASTIC AND CAPS.

SCHEDULE: (UNLESS OTHERWISE NOTED): R-6 FOR SUPPLY DUCTWORK. R-4 FOR

EXHAUST AIR.

FIRE RATED CEILING SUPPLY, RETURN AND EXHAUST REGISTERS AND DIFFUSERS:

DIFFUSERS SHALL BE FIRE RATED ASSEMBLIES LISTED IN THE UL, UNDERWRITERS

LABORATORIES FIRE RESISTANCE DIRECTION (UL CATEGORY BZZU) AND IN THE ULC,

UNDERWRITERS LABORATORIES OF CANADA EQUIPMENT AND MATERIALS DIRECTORY

(ULC CATEGORY 40U18.1-1/2A). DIFFUSERS SHALL MEET UL TIME VS. TEMPERATURE TEST

CRITERIA AND NFPA 90A REQUIREMENTS. THE LOUVER FACE SCREEN SHALL BE STEEL.

DIFFUSER SHALL INCORPORATE A NON-ADJUSTABLE BUTTERFLY-TYPE CEILING

RADIATION DAMPER, A 165 DEGREE F (74 DEGREE C) FUSIBLE LINK, A VOLUME

CONTROLLER, AND A NON-ASBESOTS THERMAL BLANKET.

STYLE: FOR GYPSUM CEILING USE LOUVER FACE SQUARE.

ACCEPTABLE PRODUCT: PRICE MODEL 530-FR - GRILLES; SCD-FR-DIFFUSERS.

MATERIAL: STEEL.

SIZE: SIZES SHOWN FOR NEW UNITS ARE ON DRAWINGS AND ARE NECK SIZE. VERIFY

SIZES OF EXISTING UNITS TO BE REPLACED, ON SITE.

FINISH: BAKED POWDER ELECTORSTATICALLY APPLIED FINISH, COLOR AS SELECTED

BY ARCHITECT.

MECHANICAL SPECIFICATIONS:

PR

OPO

SED

MEC

HA

NIC

AL P

LA

N

BB

M -

10

1

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

20

21

- 0

5

FIL

E:

DR

AW

N B

Y:

DA

TE

: 1

0/2

8/2

02

1

RESPIT

E R

ELO

CA

TIO

NS

11

1 M

AP

LE

ST

RE

ET

BU

FF

AL

O,

NE

W Y

OR

K 1

42

04

REC

OV

ER

Y O

PTIO

NS M

AD

E E

ASY

IN

C.

75

JA

ME

ST

OW

N S

TR

EE

TG

OW

AN

DA

, N

EW

YO

RK

14

07

2

BID

SET

DRAWING NOTES:

CONNECT NEW DUCT TO EXISTING.

DISCONNECT AND REMOVE EXISTING DIFFUSER, GRILLE, DUCT, ECT. - PATCH DUCT

TO MATCH MATCH EXISTING.

NEW VAV TERMINAL - CONNECT INTO EXISTING "TRANE" CONTROL SYSTEM. EXTEND

EXISTING CONTROL SYSTEM TO SEQUENCE NEW CONTROLS. NEW VAV TERMINALS

TO BE "TRANE" - MATCH TO EXISTING SYSTEM. PROVIDE WITH ACCESS DOORS IN

DRYWALL CEILINGS AT UNITS.

PROVIDE VOLUME DAMPER IN ALL NEW BRANCH DUCTS.

PROVIDE EXHAUST DUCT AND HOOD WALL CAP WITH DAMPER FOR RANGE HOOD.

PROVIDE ALUMINUM DRYER VENT AND WALL CAP WITH DAMPER FOR DRYER.

VERIFY ALL EXISTING CONDITIONS.

INDICATES FIRE RATE GRILLE / REGISTER OR DIFFUSER. FIELD MEASURE EXISTING

TO BE REPLACED.

DISCONNECT AND REMOVE EXISTING VAV TERMINAL, DUCTWORK, DIFFUSERS /

CONTROLS. PATCH DUCTWORK / INSULATION.

A

B

C

D

E

F

G

H

I

PROPOSED MECHANICAL PLAN1/8" = 1'-0"SCALE:

1 N

Page 13: RESPITE RELOCATIONS

127

129

132

133

134

135

124122

137 138 139 140

143

141

146

144147

136

148

150

153

149

151

154

156

155

116

123

108

157

159

103105 104107 106

110

109

112

113

114

160

125

111

117

118

121

119 120

158

101

115

126

130

131

152

128

142145

102

CAP CAPCAP

CAP

EXISTING EXHAUST FAN -

ADJUST FOR 800 CFM

CAP

CAP

EX. EHAUST

REGISTER 100 CFM

EX. ER

100 CFM

EX. ER

100 CFM

EX. EHAUST

REGISTER 100 CFM

EX. EHAUST

REGISTER 100 CFM

DISCONNECT AND REMOVE

EXISTING EXHAUST SYSTEM

EXISTING EXHAUST FAN -

ADJUST FOR 400 CFM

NEW EXHAUST - 150 CFM

EACH - SEE 1/M-101

NEW EXHAUST -

SEE 1/M-101

REMOVE, TYPICAL

REMOVE, TYPICAL

DISCONNECT AND REMOVE

EXISTING EXHAUST SYSTEM

EXISTING TO

REMAIN, TYP

EXISTING TO

REMAIN, TYP

EXISTING TO

REMAIN, TYP

REMOVE, TYPICAL

REMOVE EXISTING U. HTR., CAP

GAS PIPE AT MAIN CAP FLUE

REMOVE, TYPICAL

CAP

CAPCAP

EX. 100 CFM

REMOVE REMOVE

EX. 100 CFM

200 CFM

CAP

RETURN GRILLE

LEGEND:

SUPPLY GRILLEEXHAUST / RETURN AIRFLOW

MANUAL BALANCING DAMPER

EXHAUST DUCT

EXHAUST GRILLE

FIRE RATED GRILLE

RETURN GRILLE

SUPPLY GRILLE

EXHAUST DUCT

DEMOLISHED GRILLE

EXISTING

EXISTING

EXISTING

CAPPED DUCT

DEMOLISH DUCT

EXHAUST FAN

EXISTING

REMOVE EXISTING HEATER

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

20

21

- 0

5

FIL

E:

DR

AW

N B

Y:

DA

TE

: 1

0/2

8/2

02

1

RESPIT

E R

ELO

CA

TIO

NS

11

1 M

AP

LE

ST

RE

ET

BU

FF

AL

O,

NE

W Y

OR

K 1

42

04

REC

OV

ER

Y O

PTIO

NS M

AD

E E

ASY

IN

C.

75

JA

ME

ST

OW

N S

TR

EE

TG

OW

AN

DA

, N

EW

YO

RK

14

07

2

BID

SET

PR

OPO

SED

EX

HA

UST S

YSTEM

S P

LA

N

BB

M -

10

2

PROPOSED EXHAUST SYSTEMS PLAN1/8" = 1'-0"SCALE:

1 N

Page 14: RESPITE RELOCATIONS

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

EX

ISTI

NG

ELEC

TRIC

AL P

LA

N 2

02

1-0

5

FIL

E:

DR

AW

N B

Y:

JT

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

E -

00

1

DA

TE

: 1

0/2

8/2

02

1

SCALE: 1/8"= 1'-0"

EXISTING ELECTRICAL PLAN

CANOPY

VEST.

PORCH

PORCH

MECH. ELEC.

RAMP

CONC. WALK

1

LEGEND:

EXISTING CAN

EXISTING

LINEAR LIGHT

EXISTING 2'x2'

LIGHT

OR

EXISTING WALL

SCONCE

EXISTING

EXIT SIGN

EXISTING

OUTLET

EXISTING SURFACE OR

PENDANT LIGHT FIXTURE

BID

SET

Page 15: RESPITE RELOCATIONS

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

20

21

-05

FIL

E:

DR

AW

N B

Y:

JT

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

E -

00

2

DA

TE

: 1

0/2

8/2

02

1

ELEC

TRIC

AL D

EM

OLIT

ION

PLA

N

SCALE: 1/8"= 1'-0"

ELECTRICAL DEMOLITION PLAN

CANOPY

VEST.

PORCH

PORCH

MECH. ELEC.

RAMP

CONC. WALK

REMOVE EXISTING

OUTLETS SHOWN IN

CLOUDED AREAS

REMOVE EXISTING

OUTLETS SHOWN IN

CLOUDED AREAS

REMOVE EXISTING

OUTLETS SHOWN IN

CLOUDED AREAS

REMOVE EXISTING

OUTLETS SHOWN IN

CLOUDED AREAS

REMOVE EXISTING

OUTLETS SHOWN IN

CLOUDED AREAS

REMOVE EXISTING

OUTLETS SHOWN IN

CLOUDED AREAS

REMOVE EXISTING

OUTLETS SHOWN IN

CLOUDED AREAS

REMOVE EXISTING

OUTLETS SHOWN IN

CLOUDED AREAS

REMOVE EXISTING

OUTLETS SHOWN IN

CLOUDED AREAS

1

GENERAL DEMOLITION NOTES:

1. EXISTING ELECTRICAL EQUIPMENT SHOWN ON DRAWING IS DIAGRAMMATIC

AND INDICATES THE GENERAL ARRANGEMENT OF SAME. THE ELECTRICAL

CONTRACTOR SHALL DISCONNECT AND REMOVE ALL EXISTING ELECTRICAL

EQUIPMENT IN THE AREAS INDICATED. DISCONNECT AND REMOVE EXISTING

CONDUITS, WIREMOLD, RACEWAY, LIGHTING FIXTURES, RECEPTACLES,

COMPUTERS / TELEPHONE OUTLETS, LIGHTING SWITCHES, ETC. AND ALL

ASSOCIATED WIRING AND CONDUIT BACK TO SOURCE FIELD AS REQUIRED.

THE CONTRACTOR IS HEREBY ADVISED THAT THESE DRAWINGS MAY NOT

LOCATE ALL EXISTING WIRING DEVICES AND / OR EQUIPMENT WHICH MUST BE

REMOVED, REWORKED OR RELOCATED, ETC. TO ACCOMMODATE DEMOLITION

AND RECONSTRUCTION WORK IN THE EXISTING BUILDING. WHERE POSSIBLE,

MAJOR PORTIONS OF THE ELECTRICAL SYSTEM HAVE BEEN SHOWN ON THE

DRAWINGS TO ASSIST THE CONTRACTOR ONLY. FIELD OBSERVATIONS OF THE

EXISTING CONDITIONS WILL GIVE THE CONTRACTOR THE MOST ACCURATE

DETAIL AND BETTER UNDERSTANDING OF THE WORK INVOLVED.

2. WHERE REQUIRED, CONTRACTOR SHALL DISCONNECT EXISTING

MECHANICAL EQUIPMENT BEING REMOVED BY MECHANICAL CONTRACTOR.

REMOVE ALL ASSOCIATED WIRE AND CONDUITS BACK TO ITS POINT OF ORIGIN

AT THE PANELBOARD. COORDINATE ALL DEMOLITION WORK WITH

MECHANICAL CONTRACTOR, REFER TO MECHANICAL DRAWINGS FOR

ADDITIONAL ELECTRICAL DEMOLITION WORK.

3. MAINTAIN AND RESTORE IF INTERRUPTED, ALL CONDUITS AND FEEDERS

PASSING THOROUGH RENOVATED AREAS AND SERVICING UNDISTURBED

AREAS.

4. DISCONNECT AND REMOVE EXISTING ELECTRICAL WORK NOT NECESSARY

FOR EXISTING OR NEW INSTALLATION, BUT INTERFERING WITH NEW

INSTALLATION.

5. ALL COST FOR CUTTING, PATCHING, AND PAINING OF EXISTING WALL,

CEILINGS, AND FLOORS TO ACCOMMODATE THE INSTALLATION OF ELECTRICAL

WORK SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. MATERIALS FOR

THE RESTORATION OF EXISTING SURFACES SHALL MATCH THE EXISTING

MATERIALS.

6. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING

THE FIRE RATING OF ANY EXISTING WALLS CUT AND PATCHED TO

ACCOMMODATE THE INSTALLATION OF ELECTRICAL WORK. MATERIALS FOR

THE RESTORATION OF EXISTING SURFACES SHALL MATCH THE EXISTING

MATERIALS.

7. THE ELECTRICAL CONTRACTOR SHALL HAVE THE OPTION THAT, WHERE

PRACTICAL, IT WILL BE ACCEPTABLE TO RE-USE EXISTING CONCEALED

CONDUITS AND OUTLET BOXES REMAINING AFTER DEMOLITION WORK FOR

NEW BRANCH CIRCUITING (e.g. CONDUIT BETWEEN SWITCH OUTLET BOX AND

LIGHT FIXTURE OUTLET BOX), CONDUITS OR RACEWAYS BEING RE-USED MUST

NOT BE DAMAGED, BUT BE IN GOOD PHYSICAL CONDITION, PROPERLY

SUPPORTED AND UTILIZED IN ACCORDANCE WITH THE PROJECT

SPECIFICATIONS AND NATIONAL ELECTRICAL CODE REQUIREMENTS

GOVERNING THE INSTALLATION OF SAME. FIELD COORDINATE REMOVALS /

DEMOTION WITH GENERAL CONTRACTOR.

8. WHERE EXISTING CIRCUITING IS DISTURBED BY DEMOLITION WORK, THE

CONTRACTOR SHALL REWORK AND OR EXTEND EXISTING CIRCUITING AS

REQUIRED TO MAINTAIN CONTINUITY TO ALL REMAINING LOADS ON THE

AFFECTED CIRCUITS. WHERE WIRING FEEDING LIGHTING, RECEPTACLES, AND

PANELBOARDS, ETC,. IN SPACES NOT INCLUDED IN THE ALTERATIONS ARE

REQUIRED FOR REUSE AND ARE CUT; THEY SHALL BE EXTENDED AND

RECONNECTED AS REQUIRED. WHEN MAKING SPLICES TO EXISTING

CONDUCTORS, NEW CONDUCTORS SHALL MATCH EXISTING CONDUCTORS

(COPPER OR ALUMINUM, AWG, SIZE AND INSULATION). FIELD VERIFY PRIOR TO

ORDERING WIRE.

LEGEND:

EXISTING OUTLET

TO REMAIN

REMOVE

OUTLET

BID

SET

Page 16: RESPITE RELOCATIONS

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

20

21

-05

FIL

E:

DR

AW

N B

Y:

JT

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

E -

00

3

DA

TE

: 1

0/2

8/2

02

1

SCALE: 1/8"= 1'-0"

LIGHTING DEMOLITION PLAN

CANOPY

VEST.

PORCH

PORCH

MECH. ELEC.

RAMP

REMOVE EXISTING LIGHT

FIXTURES SHOWN IN

CLOUDED AREAS

REMOVE EXISTING LIGHT

FIXTURES SHOWN IN

CLOUDED AREAS

REMOVE EXISTING LIGHT

FIXTURES SHOWN IN

CLOUDED AREAS

REMOVE EXISTING LIGHT

FIXTURES SHOWN IN

CLOUDED AREAS

REMOVE EXISTING LIGHT

FIXTURES SHOWN IN

CLOUDED AREAS

REMOVE EXISTING LIGHT

FIXTURES SHOWN IN

CLOUDED AREAS

LIG

HTI

NG

DEM

OLIT

ION

PLA

N

1

A

B

DRAWING NOTES:

REMOVE AND SALVAGE EXISTING EXIT SIGN. REINSTALL AT APPROXIMATELY SAME

LOCATION. COORDINATE FINAL LOCATION WITH LIGHTING AND MECHANICAL

CONSIDERATIONS AS REQUIRED, TYPICAL.

REMOVE AND SALVAGE EXISTING EXIT SIGN. REINSTALL AS PER NOTED ON PLAN

(SEE 1/E-102 FOR NEW LOCATIONS). COORDINATE FINAL LOCATION WITH LIGHTING

AND MECHANICAL CONSIDERATIONS AS REQUIRED, TYPICAL.

A

B

B

B

B

B

A

A

A

A

HALL 108

LIV / DIN 147

HALL 123

HALL 116

HALL 158

LEGEND:EXISTING LIGHT

TO REMAIN

REMOVE EXISTING

LINEAR LIGHT

REMOVE

EXISTING LIGHT

REMOVE EXISTING

2'x2' LIGHT

OR

EXISTING EXIT SIGN - REMOVE &

SALVAGE (SEE NOTES BELOW) OR

OR

EXISTING WALL

SCONCE TO REMAIN

EXISTING EXIT

SIGN TO REMAIN

REMOVE EXISTING

WALL SCONCE

A

BID

SET

Page 17: RESPITE RELOCATIONS

A. ALL WIRING / CONDUIT SHALL BE CONCEALED (EXCEPT IN BOILER ROOMS, ELECTRICAL AND MECHANICAL SPACES). ALL CONDUITS SHALL BE INSTALLED AS HIGH AS POSSIBLE ABOVE FINISHED CEILINGS AND CONCEALED IN WALLS UNLESS OTHERWISE

INDICATED. UNDER NO CIRCUMSTANCES SHALL ANY RACEWAY OR WIRING BE INSTALLED EXPOSED IN EXISTING ROOMS, CORRIDORS OR FINISHED AREAS.

B. CIRCUIT NUMBERS INDICATED ON THE DRAWINGS ARE SHOWN FOR THE PURPOSE OF CLARIFYING THE GROUPING OF OUTLETS. THE ACTUAL NUMBER ASSIGNED TO THE CIRCUIT IN THE PANELBOARD SHALL SUIT THE BUSSING AND BRANCH CIRCUITING TO THE

PANEL. PROVIDE COMPLETE AND ACCURATE TYPEWRITTEN PANEL DIRECTORIES FOR ALL BRANCH CIRCUIT PANELBOARDS.

C. LOCATIONS INDICATED FOR LIGHT FIXTURES ARE APPROXIMATE. LOCATE FIXTURES AS REQUIRED TO AVOID INTERFERENCE BUILDING FRAMING / STRUCTURE, PIPING, DUCTWORK, SECURITY DEVICES, SMOKE DETECTORS, ETC. FIELD COORDINATE THE

LOCATIONS AS NEAR AS POSSIBLE TO THOSE INDICATED ON THE PLAN. ALSO COORDINATE ALL LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS.

D. EXACT LOCATIONS OF CEILING MOUNTED SMOKE DETECTORS AND EXIT SIGNS SHALL BE COORDINATED WITH OTHER CEILING MOUNTED EQUIPMENT TO AVOID CONFLICT. LOCATE DEVICES AS NEAR AS POSSIBLE TO THE LOCATION INDICATED. FIRE ALARM,

SMOKE AND HEAT DETECTORS SHALL BE REQUIRED TO BE INSTALLED A MINIMUM OF (3) FEET AWAY FROM SUPPLY OR RETURN AIR GRILLS OR PER SYSTEM MANUFACTURERS INSTALLATION REQUIREMENTS AND NFPA 72.

E. THE CONTRACTOR SHALL BE RESPONSIBLE TO REVIEW OTHER TRADES PROJECT CONTRACT DOCUMENTS TO DETERMINE MOUNTING HEIGHTS FOR ELECTRICAL DEVICES OR EQUIPMENT. THE LOCATIONS FOR MECHANICAL AND PLUMBING EQUIPMENT THAT

REQUIRES ELECTRICAL CONNECTIONS ARE SHOWN ON THE MECHANICAL AND PLUMBING DRAWINGS. COORDINATE EXACT MOUNTING LOCATIONS AND HEIGHTS IN THE FIELD WITH OTHER TRADES PRIOR TO INSTALLATION.

F. CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL NECESSARY PERMITS REQUIRED TO BEGIN AND PROCEED WITH CONSTRUCTION.

G. VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS IN FIELD. NOTIFY ARCHITECT IF ANY DISCREPANCIES ARE FOUND ON DRAWINGS PRIOR TO START OF WORK.

H. ALL CONDUIT PASSING THROUGH A FIRE ZONE SHALL HAVE A FIRE RATED INSTALLATION. PROVIDE PROPER FIRE-STOPPING AS REQUIRED.

I. ALL WORK SHALL BE IN ACCORDANCE WITHE NEC, OSHA AND ALL LOCAL CODES AND ORDINANCES. UNDER NO CIRCUMSTANCES SHALL THE ELECTRICAL CONTRACTOR INSTALL ANY WORK NOT IN ACCORDANCE WITH CODES.

GENERAL DRAWING NOTES:(THESE NOTES APPLY TO ALL ELECTRICAL DRAWINGS)

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

PR

OPO

SED

ELEC

TRIC

AL P

LA

N 2

02

1-0

5

FIL

E:

DR

AW

N B

Y:

JT

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

E -

10

1

DA

TE

: 1

0/2

8/2

02

1

SCALE: 1/8"= 1'-0"

PROPOSED ELECTRICAL PLAN

W

D

W D

PORCH

PORCH

RAMP

127BEDROOM

129BEDROOM

132BEDROOM

133BEDROOM

134BEDROOM

135BEDROOM

124BEDROOM122BEDROOM

137BEDROOM 138BEDROOM 139BEDROOM 140BEDROOM

143ACTIVITY141LAUNDRY

146BATH

144HALL147LIV/DIN

136LIV/DIN

148KITCHEN

150KITCHEN

153HALL

149ACTIVITY

151OFFICE

154OFFICE

156OFFICE

155STOR

116HALL 123HALL

108HALL

157MECH

159BREAK

102CALL CNTR

103RECEPTION

105OFFICE 104OFFICE

107EXAM 106EXAM

110LIV/DIN

109OFFICE 112STOR

113STOR

114BATH

160CONFERENCE

125HALL

111KITCHEN

117STOR

118STOR

121DATA119MECH 120ELEC.

158HALL

101VEST

115TOILET

126LAUNDRY

130BATH

131BATH

152PANT

128HALL

142HALL145HALL

1

ELECTRICAL SYMBOL SCHEDULE

LIGHTING PANEL

GROUND FAULT INTERRUPTER

OVER COUNTER (UC=UNDER COUNTER)

WALL MOUNTED

LP

G.F.I.

O.C.

W

NEW SINGLE POLE TOGGLE SWITCH

WIRING HOME RUN TO PANEL

DUPLEX RECEPTACLE - G.F.I.

EXISTING DUPLEX RECEPTACLE

NEW THREE WAY SWITCH

WIRING CONCEALED IN WALL, FLOOR OR CEILING

LP

3S

S

TV

WALL BOX TELEVISION OUTLET - MOUNT AT TELEVISION

HEIGHT (COORDINATE W/ ARCHITECT / OWNER). PROVIDE

4" RECESSED BACK BOX WITH MUD RING AND 1" CONDUIT

W/ BUSHINGS AND PULLSTRING STUBBED INTO

ACCESSIBLE CEILING SPACE.

WALL BOX TELEPHONE / DATA OUTLET, + 18" A.F.F.

UNLESS NOTED OTHERWISE. PROVIDE 4" RECESSED

BACK BOX WITH MUD RING AND 1" CONDUIT W/ BUSHING

AND PULLSTRING STUBBED INTO ACCESSIBLE CEILING

SPACE.

NEW DUPLEX RECEPTACLE

EXISTING SWITCHS

220 V

220 V

BID

SET

Page 18: RESPITE RELOCATIONS

ELECTRICAL SYMBOL SCHEDULE

LIGHTING PANEL

GROUND FAULT INTERRUPTER

OVER COUNTER (UC=UNDER COUNTER)

WALL MOUNTED

LP

G.F.I.

O.C.

W

NEW SINGLE POLE TOGGLE SWITCH

WIRING HOME RUN TO PANEL

DUPLEX RECEPTACLE - G.F.I.

EXISTING DUPLEX RECEPTACLE

NEW THREE WAY SWITCH

WIRING CONCEALED IN WALL, FLOOR OR CEILING

LP

3S

S

TV

WALL BOX TELEVISION OUTLET - MOUNT AT TELEVISION

HEIGHT (COORDINATE W/ ARCHITECT / OWNER). PROVIDE

4" RECESSED BACK BOX WITH MUD RING AND 1" CONDUIT

W/ BUSHINGS AND PULLSTRING STUBBED INTO

ACCESSIBLE CEILING SPACE.

WALL BOX TELEPHONE / DATA OUTLET, + 18" A.F.F.

UNLESS NOTED OTHERWISE. PROVIDE 4" RECESSED

BACK BOX WITH MUD RING AND 1" CONDUIT W/ BUSHING

AND PULLSTRING STUBBED INTO ACCESSIBLE CEILING

SPACE.

LOCAL SWITCHES 44" ABOVE FLOOR TO CENTER

RECEPTACLES 1'-6" ABOVE FLOOR TO CENTER

WALL MOUNTED HEIGHT AS DIRECTED

FIXTURES

MOTOR CONTROLS 4'-0" ABOVE FLOOR TO CENTER

DISCONNECT AND 4'-0" ABOVE FLOOR TO CENTER

SAFETY SWITCHES

PANELBOARDS 6'-6" ABOVE FLOOR TO CENTER

OF TOP MOST DEVICE HANDLE

PANELBOARDS 48" A.F.F. TO CENTER OF TOP-MOST

(APARTMENTS): DEVICE HANDLE

TELEPHONE OUTLET 1'-6" ABOVE FLOOR TO CENTER

(DESK TYPE) OR

COMPUTER OUTLET

TELEVISION OUTLET VERIFY WITH OWNER / ARCHITECT

& ASSOCIATED

RECEPTACLE OUTLET

RECEPTACLES & COORDINATE W/ ARCH. DRAWINGS OR

SWITCHES OVER HEIGHT AS INDICATED WHERE THE

COUNTERS OBSTRUCTED HIGH REACH SHALL NOT

EXCEED 48" MAX. FOR REACH DEPTH

OF 20" MAX., 44" MAX. FOR A REACH

DEPTH THAT EXCEEDS 20" BUT NOT

MORE THAN 25" MAX.

EXIT LIGHTS 95" ABOVE FLOOR TO CENTER

(WALL MOUNTED) 9" ABOVE DOOR HEAD TO CENTER

FIRE ALARM OPERATING HANDLE BETWEEN

PULL STATION 42" AND 48" A.F.F.

FIRE ALARM ENTIRE LENS ABOVE 80", AND NO

AUDIO / VISUAL UNIT GREATER THAN 96" A.F.F.

MOUNTING HEIGHTS:

UNLESS OTHERWISE INDICATED OR CALLED FOR, OR BECAUSE OF SPECIAL

CONDITIONS, THE MOUNTING HEIGHT OF ALL OUTLETS SHALL GENERALLY BE AS

FOLLOWS:

NEW DUPLEX RECEPTACLE

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

PR

OPO

SED

LIG

HTI

NG

PLA

N 2

02

1-0

5

FIL

E:

DR

AW

N B

Y:

JT

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

E -

10

2

DA

TE

: 1

0/2

8/2

02

1

SCALE: 1/8"= 1'-0"

PROPOSED LIGHTING PLAN

W

D

W D

PORCH

PORCH

RAMP

127BEDROOM

129BEDROOM

132BEDROOM

133BEDROOM

134BEDROOM

135BEDROOM

124BEDROOM122BEDROOM

137BEDROOM 138BEDROOM 139BEDROOM 140BEDROOM

143ACTIVITY141LAUNDRY146BATH

144HALL

147LIV/DIN

136LIV/DIN

148KITCHEN

150KITCHEN

153

149ACTIVITY

151OFFICE

154OFFICE

156OFFICE

155STOR

116HALL

123HALL

108HALL

157

159BREAK

102CALL CNTR103RECEPTION105OFFICE 104OFFICE107EXAM 106EXAM

110LIV/DIN

109OFFICE

112STOR

113STOR114BATH

160CONFERENCE

125HALL

111KITCHEN

117STOR

118STOR

121DATA119MECH 120ELEC.

158HALL

101VEST

115TOILET

126LAUNDRY

130BATH

131BATH

152

128HALL

142145

S S S S

S

S

S

S

S

S

S

S

S

S

S

SSSS

S

S

SS

S S

S

S

3

TV

TV

TV

TV

TV TV

TV

TV

TV

TV

TV

TV

TV

TV

FIXTURE LEGEND:A - NEW CAN

DOWN-LIGHT:

B - NEW

24x24" LIGHT:

EXISTING CAN

DOWN-LIGHT:

LIGHTING FIXTURE SCHEDULE NOTES:

1. PROVIDE ALL FIXTURE LAMPS, ACCESSORIES AND SPARE PARTS.

2. VERIFY ALL FINAL FIXTURE COLORS / FINISHES WITH ARCHITECT PRIOR TO PURCHASING FIXTURES.

3. PROVIDE LIGHTING FIXTURES THAT ARE LISTED, LABELED AND APPROVED BY UNDERWRITERS

LABORATORIES INC. FOR USE WITH THE SPECIFIED CEILING TYPE AND RATING. COORDINATE WITH

ARCHITECTURAL DRAWINGS, REFLECTED CEILING PLANS AND FIELD VERIFICATION OF EXISTING

CEILING TYPES AND CONDITIONS BY CONTRACTOR.

4. PROVIDE ALL REQUIRED MOUNTING HARDWARE FOR A COMPLETE INSTALLATION.

5. FOR ALL LIGHTING FIXTURES, PROVIDE TRIM KITS AS REQUIRED. COORDINATE EXACT

REQUIREMENTS WITH ARCH. REFLECTED CEILING PLAN FOR GYP BOARD / GRID CEILING PLACEMENTS.

FOR EXISTING CEILINGS, FIELD VERIFY TYPES PRIOR TO PURCHASE.

1

TV TV

A A A A A

A A A A A

AAA

AAA

AAA

AAA

AAA

A A

A

AA

A

A

AA

A A A A

A A A

AAA

AAAA

A

A

A

AA

A

A

AA

A A

ELECTRIC PANEL

S3S3

S

S

S

S

S

S

S3

S

A

AA

S3

S3

CCC

C

C

C

B

B S

C C

B

B

B

B

B

B

B

B

B

BS

B

B

B

S

3

S

3B B B B

A AAA

S

C C C

C C

S3

S3

LP

LPLP

LP LP LP

LP

LP

LPLPLPLP

LP

LP

LP

C C

C C

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

LP

S3

S3

S3

S

SLP LP

LP

C

C

C

C

S3

S

CC

LP

LP

S3

S3

S

LPLP

LP

C

LP

S3

LP

LP

LP

LP LP

LP

C

LP

S

C

C C

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION

A6" ROUND RECESSED LED DOWNLIGHT, UL WET LOCATION LISTED, 0-10V

DIMMING STANDARD. 50,000 HOURS MINIMUM LED LIFETIME (L70). PROVIDE

W/ SPECULAR CLEAR FINISH WITH POLISHED FLANGE.

MANUFACTURER & CATALOG NO.

EATON / HALO COMMERCIAL SERIES

PD6-15-ED010-PDM6A-835-61V-C OR APPROVED EQUAL.

MOUNTING VOLTAGE / BALLAST LAMPS

RECESSED1500 LUMEN, 17.1 WATT (87

LPW) LED PACKAGE, 3500K

NOTES

UNV VOLTAGE (120-277V)

ELECTRONIC 0-10 V

DIMMING LED DRIVER

COORDINATE CEILING TRIMS REQUIRED WITH CEILING

TYPES SHOWN ON ARCHITECTURAL CEILING PLANS.

B2'x2' RECESSED LED VOLUMETRIC TROFFER WITH 20 GAUGE STEEl HOUSING

AND HIGH REFLECTANCE WHITE MATTE FINISH, 0-10V DIMMIN STANDARD.

50,000 HOURS MINIMUM LED LIFETIME (L70).

EATON / METALUX "ACCORD LED"

22AC-LD5-34-UNV-L835-CD1 OR APPROVED EQUAL.RECESSED / GRID3466 LUMEN, 30.2 WATT (115

LPW) LED PACAKGE, 3500K

UNV VOLTAGE (120-277V)

ELECTRONIC 0-10 V

DIMMING LED DRIVER

COORDINATE CEILING TRIMS REQUIRED WITH CEILING

TYPES SHOWN ON ARCHITECTURAL CEILING PLANS.

EXISTING SWITCHS

C2'x2' SURFACE MOUNTED LED VOLUMETRIC TROFFER WITH 20 GAUGE STEEl

HOUSING AND HIGH REFLECTANCE WHITE MATTE FINISH, 0-10V DIMMIN

STANDARD. 50,000 HOURS MINIMUM LED LIFETIME (L70).

EATON / METALUX "ACCORD LED"

22AC-LD5-34-UNV-L835-CD1 OR APPROVED EQUAL.SURFACE / PROVIDE

SURFACE MOUNT KIT

3466 LUMEN, 30.2 WATT (115

LPW) LED PACAKGE, 3500K

UNV VOLTAGE (120-277V)

ELECTRONIC 0-10 V

DIMMING LED DRIVER

C - NEW 24x24" LIGHT

SURFACE MOUNTED:

C

C

C

C

C

C

C

C

CCC

C C C C C C

C CC C

C C

B

B

B

EXISTING WALL

SCONCE

EXISTING LINEAR

LIGHT

B

S3

DRAWING NOTES:

REINSTALL SALVAGED EXIT SIGN. REINSTALL AT APPROXIMATELY SAME LOCATION.

COORDINATE FINAL LOCATION WITH LIGHTING AND MECHANICAL CONSIDERATIONS

AS REQUIRED, TYPICAL.

REINSTALL SALVAGED EXIT SIGN. REINSTALL AS INDICATED ON PLAN COORDINATE

FINAL LOCATION WITH LIGHTING AND MECHANICAL CONSIDERATIONS AS REQUIRED,

TYPICAL.

PROVIDE AND INSTALL NEW CEILING MOUNTED EXIT SIGN AS INDICATED (SEE FIXTURE

SCHEDULE).

A

B

C

C

A

AA

AA

B

B

A

LED EXIT SIGN WITH BATTERY BACKUP, RED LETTERS ON WHITE HIGH IMPACT

THERMOPLASTIC HOUSING. PROVIDE WITH SEALED NICAD BATTERY, MINIMUM

90 MIN. DURATION WITH REMOTE CAPACITY TO POWER (2) REMOVE LAMP HEADS.EATON "SURE-LITES" LPXH SERIES OR APPROVED EQUAL.

WALL MOUNT OR

PENDANT MOUNT

RED LED'S120 / 277 VAC SEE REFLECTED CEILING PLAN FOR MOUNTING TYPE

AND DIRECTION ARROWS.

BID

SET

Page 19: RESPITE RELOCATIONS

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

EX

ISTI

NG

PLU

MB

ING

PLA

N 2

02

1-0

5

FIL

E:

DR

AW

N B

Y:

SE

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

P-0

01

CANOPY

VEST.

PORCH

PORCH

MECH. ELEC.

RAMP

CONC. WALK

SCALE: 1/8"= 1'-0"

EXISTING PLUMBING PLAN

DW

1

DA

TE

: 1

0/2

8/2

02

1

BID

SET

Page 20: RESPITE RELOCATIONS

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

PLU

MB

ING

DEM

OLIT

ION

PLA

N 2

02

1-0

5

FIL

E:

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

P -

00

2

SCALE: 1/8"= 1'-0"

PLUMBING DEMOLITION PLAN

CANOPY

VEST.

PORCH

PORCH

MECH. ELEC.

RAMP

CONC. WALK

DW

REMOVE EXISTING TOILET,

SINK, AND SHOWER TO

PREPARE AREA FOR

RENOVATIONS

REMOVE EXISTING TOILET,

SINK, AND SHOWER TO

PREPARE AREA FOR

RENOVATIONS

REMOVE EXISTING TOILET,

SINK, AND SHOWER TO

PREPARE AREA FOR

RENOVATIONS

REMOVE EXISTING SINK TO

PREPARE AREA FOR

RENOVATIONS

REMOVE EXISTING TOILET,

SINK, AND SHOWER TO

PREPARE AREA FOR

RENOVATIONS

REMOVE EXISTING FLOOR

DRAIN TO PREPARE AREA FOR

RENOVATIONS

REMOVE AND SALVAGE

EXISTING TOILET TO BE

REUSED AT NEW

LOCATION

REMOVE EXISTING TOILET

AND SINK TO PREPARE

AREA FOR RENOVATIONS

REMOVE EXISTING SINK TO

PREPARE AREA FOR

RENOVATIONS

REMOVE EXISTING SINK TO

PREPARE AREA FOR

RENOVATIONS

REMOVE EXISTING

COMMERCIAL SINKS AND

DISHWASHER TO PREPARE

AREA FOR RENOVATIONS

DR

AW

N B

Y:

JT

REMOVE EXISTING SINK TO

BE PREPARE AREA FOR

RENOVATION

1

DA

TE

: 1

0/2

8/2

02

1

SINK TO REMAIN

SINK AND TOILET TO REMAIN

REMOVE SINK

DRAWING NOTES:

1. REMOVE ALL OXYGEN OUTLETS AT ROOMS ETC. PATCH WALLS TO MATCH EXISTING.

REMOVE EXISTING OXYGEN SUPPORT

SYSTEM. BLEED SYSTEM AS REQUIRED.

VIF ANY ADDITIONAL REMOVAL

CONSIDERATION AS REQUIRED.

REMOVE EXISTING OXYGEN SUPPORT

SYSTEM BOARDS. PATCH AS REQUIRED

TO MATCH EXISTING.

BID

SET

Page 21: RESPITE RELOCATIONS

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

PR

OPO

SED

PLU

MB

ING

PLA

N 2

02

1-0

5

FIL

E:

DR

AW

N B

Y:

JT

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

P -

10

1

SCALE: 1/8"= 1'-0"

PROPOSED PLUMBING PLAN

W

D

W D

PORCH

PORCH

RAMP

127BEDROOM

129BEDROOM

132BEDROOM

133BEDROOM

134BEDROOM

135BEDROOM

124BEDROOM122BEDROOM

137BEDROOM 138BEDROOM 139BEDROOM 140BEDROOM

143ACTIVITY141LAUNDRY

146BATH

144HALL147LIV/DIN

136LIV/DIN

148KITCHEN

150KITCHEN

153HALL

149ACTIVITY

151OFFICE

154OFFICE

156OFFICE

155STOR

116HALL 123HALL

108HALL

157MECH

159BREAK

102CALL CNTR103RECEPTION

105OFFICE 104OFFICE

107EXAM 106EXAM

110LIV/DIN

109OFFICE 112STOR

113STOR

114BATH

160CONFERENCE

125HALL

111KITCHEN

117STOR

118STOR

121DATA119MECH 120ELEC.

158HALL

101VEST

115TOILET

126LAUNDRY

130BATH

131BATH

152PANT

128HALL

142HALL145HALL

DESCRIPTION

PLUMBING FIXTURE SCHEDULE

P-2

LETTER

P-1

DRAINAGE

SS V

SUPPLY

CW HW

HANDWASH SINKP-3 1 1/2" 1/2" 1/2"1 1/2"

PLUMBING NOTES:

1. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE TO BE USED AS GUIDELINE ONLY.

2. PLUMBING CONTRACTOR TO SUBMIT COMPLETE SET OF SUBMISSION WITH CATALOG CUTS TO CITY OF BUFFALO (IF

REQUIRED).

3. INSTALL:

- FOUR (4) KITCHEN SINKS

- TWO (2) WASH HAND SINKS IN VANITIES

- ONE (1) SHOWER

- THREE (3) DISHWASHERS

-TWO (2) WASHING MACHINES

4. ALL HOT WATER AND COLD WATER PIPING TO BE TYPE "L".

5. ALL FITTINGS TO BE WROUGHT OR CAST BRONZE.

6. ALL JOINTS TO BE 95-5 TIN AND ANTIMONY, LEAD FREE.

7. WASTE AND VENT PIPE TO BE PVC SCHEDULE 40.

8. WASTE AND VENT PIPE JOINTS TO BE SOLVENT CEMENT WELDED AS PER MANUFACTURERS REQUIREMENTS.

9. PROVIDE FIRE STOPPING AT RATED WALL PENETRATIONS.

10. PROVIDE ALL HOES AND SUPPLIES AS REQUIRED.

11. VERIFY ALL EXISTING PIPE SIZES AND ROOTINGS IN FIELD.

P-4

P-5 SHOWER 3" 1 1/2" 1/2" 1/2"

DISHWASHER 1 1/2" 1/2" 1/2"1 1/2"

KITCHEN SINK 1 1/2" 1/2" 1/2"1 1/2"

WASHER 1 1/2" 1/2" 1/2"1 1/2"P-6

KITCHEN SINK (HC) 1 1/2" 1/2" 1/2"1 1/2"

5. PROVIDE 3/4" GAS LINE TO DRYERS, RANGES.

GENERAL PLUMBING NOTES:

1. ALL MATERIALS AND METHODS SHALL COMPLY WITH ALL FEDERAL,

2. THE PLUMBING CONTRACTOR SHALL FURNISH AND FILE WITH LOCAL AUTHORITIES

3. NEW WASTE AND VENT PIPING SHALL BE D.W.V. COPPER WITH CAST FITTINGS AND

4. INSULATE ALL HOT AND COLD WATER LINES.

AND INSPECTIONS CONNECTED WITH THIS CONTRACT.

CAST FITTINGS AND SOLDERED 95/5 JOINTS.

STATE AND LOCAL CODES.

ALL DRAWINGS REQUIRED AND SHALL OBTAIN, AND PAY FOR, ALL PERMITS, LICENSES

SOLDERED 95/5 JOINTS. NEW WATER PIPING SHALL BE TYPE "L" COPPER WITH

GAS PIPING TO BE STANDARD WEIGHT BLACK STEEL PIPE.

P-1

P-1

P-1 P-4

P-2

P-4P-4

P-5

P-3 P-3

P-6

P-6

CONNECT TO

SS AND VENTEXISTING CW,HW,

CONNECT TO

SS AND VENTEXISTING CW,HW,

CONNECT TO

SS AND VENTEXISTING CW,HW,

CONNECT TO

SS AND VENTEXISTING CW,HW,

CONNECT TO

SS AND VENTEXISTING CW,HW,

CONNECT TO

SS AND VENTEXISTING CW,HW,

CONNECT TO

EXISTING GAS LINE

CONNECT TO

EXISTING GAS LINE

CONNECT TO

EXISTING GAS LINE

REINSTALL SALVAGED

TOILET AT INDICATED

LOCATION (SEE A-SERIES)

1

DA

TE

: 1

0/2

8/2

02

1

HW

HW

HW

HW

HW

HW

CW

CW

CW

CW

CW

CW

CW

CW

HW

HW

HW

HW

HW

HW

HW

SS

V

SS

V

SSV

V

V

SS

SS

V

SS

SS

CW

CW

CW

HW

SS

V

SS

V

V

SS

V

SS

CW

CW

HW

HW

CWHW

CWHW

SS

V

V

SS

SS

V

V

SS

SS

V

V

SS

SS

V

V

SS

HW

CW

CW

HW

HW

HW

CW

CW

SS

V

VSS

SS

V

HW

HW

CW

CW

CW

HW

G

G

G

G

G

G

BID

SET

Page 22: RESPITE RELOCATIONS

SCALE: 1/8"= 1'-0"

EXISTING FIRE ALARM DETECTION PLAN

CANOPY

VEST.

PORCH

PORCH

MECH. ELEC.

RAMP

CONC. WALK

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

EX

ISTI

NG

FIR

E A

LA

RM

DETE

CTI

ON

PLA

N 2

02

1-0

5

FIL

E:

DR

AW

N B

Y:

SE

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

FP

-00

1

F

F

F

F

SD

SD

SD

SD

SD

SD

SD

SD

SD SD

SDSD

SDSDSDSD

SD SD SDSD

SD

SD

SD

SDSD

SD SD SD

SD SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SDSD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/VF

A/V

F

A/V

F

A/V

F

A/V

F

A/V

FIRE

ALARM

PANEL

FA

P

1

DA

TE

: 1

0/2

8/2

02

1

LEGEND:

F EXISTING FIRE ALARM PULL STATION

FEXISTING FIRE ALARM AUDIO / VISUAL DEVICE

EXISTING FIRE ALARM SMOKE DETECTORSD

A/V

FAP EXISTING FIRE ALARM PANEL

BID

SET

Page 23: RESPITE RELOCATIONS

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

DEM

O F

IRE A

LA

RM

DETE

CTI

ON

PLA

N 2

02

1-0

5

FIL

E:

DR

AW

N B

Y:

SE

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

FP

-00

2

SCALE: 1/8"= 1'-0"

DEMO FIRE ALARM DETECTION PLAN

CANOPY

VEST.

PORCH

PORCH

MECH. ELEC.

RAMP

CONC. WALK

F

F

F

F

SD

SD

SD

SD

SD

SD

SD

SD

SD SD

SD

SD

SDSDSDSD

SD SD SDSD

SD

SD

SDSD

SD

SD SD

SD SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SDSD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

F

F

A/V

F

F

A/V

FF

A/V

F

A/V

F

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

F

F

F

A/V

F

A/V

F

A/V

F

A/V

SD

R R

R

R

R

R

R

R

R

R

R

RR

R

R

R

R

R

R

R

RR

1

DA

TE

: 1

0/2

8/2

02

1

LEGEND:

F FIRE ALARM PULL STATION

FFIRE ALARM AUDIO / VISUAL DEVICE -EXISTING TO REMAIN

FIRE ALARM SMOKE DETECTOR - TO BE REMOVEDSD

F A/VFIRE ALARM AUDIO / VISUAL DEVICE - TO BE TREMOVED

OR RELOCATED

OR RELOCATED

FIRE ALARM SMOKE DETECTOR - EXISTING TO REMAINSD EX

A/V

EX

R

R

BID

SET

Page 24: RESPITE RELOCATIONS

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

PR

OPO

SED

FIR

E A

LA

RM

DETE

CTI

ON

PLA

N 2

02

1-0

5

FIL

E:

DR

AW

N B

Y:

JT

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

FP

- 1

01

SCALE: 1/8"= 1'-0"

PROPOSED FIRE ALARM DETECTION PLAN

W

D

W D

PORCH

PORCH

RAMP

127BEDROOM

129BEDROOM

132BEDROOM

133BEDROOM

134BEDROOM

135BEDROOM

124BEDROOM122BEDROOM

137BEDROOM 138BEDROOM 139BEDROOM 140BEDROOM

143ACTIVITY141LAUNDRY

146BATH

144HALL147LIV/DIN

136LIV/DIN

148KITCHEN

150KITCHEN

153HALL

149ACTIVITY

151OFFICE

154OFFICE

156OFFICE

155STOR

116HALL 123HALL

108HALL

157MECH

159BREAK

102CALL CNTR103RECEPTION

105OFFICE 104OFFICE

107EXAM 106EXAM

110LIV/DIN

109OFFICE 112STOR

113STOR

114BATH

160CONFERENCE

125HALL

111KITCHEN

117STOR

118STOR

121DATA119MECH 120ELEC.

158HALL

101VEST

115TOILET

126LAUNDRY

130BATH

131BATH

152PANT

128HALL

142HALL145HALL

F

F

F

F

SD

SD

SD

SD

SD

SD

SD

SD

SD

SDSDSDSD

SD SD SDSD

SD

SDSD

SD

SD SD

SD SD

SD

SD

SD

SD

SD

SD

SD

SD SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

F

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

SD

N

SD

N

SD

N

SD

N

SD

N

SD

N

SD

N

SD

N

SD

N

SD

NF

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

F

A/V

CO

N

CO

N

CO

N

CO

N

CO

N

CO

N

190F

190F

CO

N

190F

EX EX

EX

EXEXEX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX EX

EXEX

EX

EX EXEX

EX EX EXEX

EX

EX

EX

EX EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

N

N

N

N

N

N

NN

NNNN

NN

FIRE

ALARM

PANEL

FA

P

N

N

N

FIRE DETECTION SYMBOL SCHEDULE

CARBON MONOXIDE DETECTOR- NEW CEILING MOUNTED

FIRE ALARM SMOKE DETECTOR - NEW CEILING MOUNTEDSD

CO

HEAT DETECTION190

F

F FIRE ALARM PULL STATION

FFIRE ALARM AUDIO / VISUAL DEVICE -EXISTING TO REMAIN

FAP FIRE ALARM PANEL

FIRE ALARM SMOKE DETECTOR - TO BE REMOVEDSD

F A/VFIRE ALARM AUDIO / VISUAL DEVICE - TO BE TREMOVED

OR RELOCATED

OR RELOCATED

FIRE ALARM SMOKE DETECTOR - EXISTING TO REMAINSD EX

N

N

A/V

EX

FFIRE ALARM AUDIO / VISUAL DEVICE - NEW WALL MOUNTED

A/V

N

R

R

EX

EXEX

EX

EX

NF

A/V

N

N

EX

N

N

EX

EX

N

EX

CO

N

EX

A/V

N

1

DA

TE

: 1

0/2

8/2

02

1

DRAWING NOTES:

TIE IN NEW DEVICES TO EXISTING FIRE ALARM PANEL (SIMPLEX 4010)

EX

EX

BID

SET

Page 25: RESPITE RELOCATIONS

SCALE: 1/8"= 1'-0"

EXISTING SPRINKLER PLAN

CANOPY

VEST.

PORCH

PORCH

MECH. ELEC.

RAMP

CONC. WALK

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

EX

ISTI

NG

SPR

INK

LER

PLA

N 2

02

1-0

5

FIL

E:

DR

AW

N B

Y:

SE

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

SP

-00

1

1

DA

TE

: 1

0/2

8/2

02

1

BID

SET

Page 26: RESPITE RELOCATIONS

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

DEM

O S

PR

INK

LER

PLA

N 2

02

1-0

5

FIL

E:

DR

AW

N B

Y:

SE

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

SP

-00

2

SCALE: 1/8"= 1'-0"

DEMO SPRINKLER PLAN

CANOPY

VEST.

PORCH

PORCH

MECH. ELEC.

RAMP

CONC. WALK

R

R

R

R

RR

R

R

R

R

R

R

R

R

R

R

R

R

1

DA

TE

: 1

0/2

8/2

02

1

BID

SET

Page 27: RESPITE RELOCATIONS

LEGEND

EXISTING PENDANT SPRINKLER HEADTO BE REMOVED OR RELOCATED

SPRINKLER PIPING

1. SPRINKLER HEADS AND PIPING SHALL BE INSTALLED IN ACCORDANCE WITH

THE NFPA 13, AND THE FIRE CODE OF THE STATE OF NEW YORK (IFC 2015).

2. CONTRACTOR SHALL VERIFY WATER PRESSURES AVAILABLE AND SIZE PIPING

ACCORDINGLY.

3. FIRE PROTECTION CONTRACTOR SHALL DESIGN AND INSTALL A COMPLETE

HYDRAULICALLY CALCULATED FIRE SPRINKLER SYSTEM IN ACCORDANCE WITH

ALL NFPA ,LOCAL CODE DESIGN AND EQUIPMENT REQUIREMENTS., PLUS

OPWDD/OFPC REQUIREMENTS.

4. ALL MATERIALS AND EQUIPMENT USED SHALL BE UL LISTED AND FM

APPROVED.

5. CONTRACTOR SHALL SUBMIT PLANS AND CALCULATIONS TO LOCAL

AUTHORITIES, ENGINEER AND OWNER FOR APPROVAL.

6. SPRINKLER HEADS SHALL CONFORM TO THE MINIMUM REQUIREMENTS OF

THE LATEST EDITION OF NFPA 13, AND SHALL BE UL LISTED AND FM

APPROVED.

7. FULLY TEST FINAL SYSTEM PER NFPA, LOCAL, STATE, AND INSURANCE

PROVIDER REQUIREMENTS.

8. CONTRACTOR SHALL REMOVE ALL WALLS, FLOORS, CEILINGS, ETC. AS

REQUIRED TO INSTALL ALL MATERIALS NOTED ON THIS DOCUMENT. UPON

COMPLETION OF CONSTRUCTION CONTRACTOR SHALL RESTORE ALL AREA

DISTURBED TO MATCH EXISTING CONDITIONS USING LIKE MATERIALS.

9. CONTRACTOR SHALL PROVIDE ALL WIRING AND MONITORING CONNECTIONS

TO THE EXISTING FIRE ALARM PANEL ASSOCIATED WITH NEWLY INSTALLED

EQUIPMENT (INCLUDING NEW FIRE SERVICE TAMPER SWITCHES)

10. ALL NEW SPRINKLER HEADS TO BE QUICK RESPONSE RESIDENTIAL HEADS.

VERIFY LAYOUT AND THROW DISTANCE, PROVIDE ADDITIONAL HEADS IF

REQUIRED TO PROVIDE A WHOLE BUILBING NFPA 13 COMPLIANT SYSTEM.

PENDANT SPRINKLER HEAD

REV

ISIO

NS

NO

.D

ES

CR

IPT

ION

DA

TE

JO

B T

ITLE

DR

AW

ING

TIT

LE

DR

AW

ING

NO

.JO

B N

O.

RESPIT

E R

ELO

CA

TIO

NS

111 M

APLE S

TREET

BU

FFA

LO

, N

EW

YO

RK

14204

REC

OV

ER

Y O

PTI

ON

S M

AD

E E

ASY

IN

C.

EX

ISTI

NG

SPR

INK

LER

PLA

N 2

02

1-0

5

FIL

E:

DR

AW

N B

Y:

SE

75 J

AM

ESTO

WN

STR

EET

GO

WA

ND

A, N

EW

YO

RK

140

72

SP

-10

1

SCALE: 1/8"= 1'-0"

PROPOSED SPRINKLER PLAN

CLO

W

D

W D

PORCH

PORCH

CLOCLO

RAMP

127BEDROOM

129BEDROOM

132BEDROOM

133BEDROOM

134BEDROOM

135BEDROOM

124BEDROOM122BEDROOM

137BEDROOM 138BEDROOM 139BEDROOM 140BEDROOM

143ACTIVITY141LAUNDRY

146BATH

144HALL147LIV/DIN

136LIV/DIN

148KITCHEN

150KITCHEN

153HALL

149ACTIVITY

151OFFICE

154OFFICE

156OFFICE

155STOR

116HALL 123HALL

108HALL

157MECH

159BREAK

102CALL CNTR103RECEPTION

105OFFICE 104OFFICE

107EXAM 106EXAM

110LIV/DIN

109OFFICE 112STOR

113STOR

114BATH

160CONFERENCE

125HALL

111KITCHEN

117STOR

118STOR

121DATA119MECH 120ELEC.

158HALL

101VEST

115TOILET

126LAUNDRY

130BATH

131BATH

152PANT

CLO CLO CLO CLO

CLO

CLO

128HALL

142HALL145HALL

EXISTING PENDANT SPRINKLER HEAD

N

N NN

N

N

N

N

N

NN

N

N

N

R

1

DA

TE

: 1

0/2

8/2

02

1

NOTES:

BID

SET