Republic of Iraq Northern Technical University Equipments ...
Transcript of Republic of Iraq Northern Technical University Equipments ...
Republic of Iraq
Ministry of Higher Education & Scientific Research
Northern Technical University
Technical Institute /Kirkuk
Equipments & Machineries Dep./ Branch of Ref. & Air Conditioning
A Research Submitted to
((Equipments & Machineries Dep./ Branch of Ref. & Air Conditioning))
Prepared by
Ibrahim Najmaldeen Mahmood Jalal Ali Asgher
Ahmed Bahir Mohammed Ibrahim Ahmed Mohammed
George Odisho Bawith
Supervised by
2018 1439
بسم الله الرحمه الرحم
رب أوزعى أن أشكر وعمتك ﴿
وعلى والدي الت أوعمت عل
وأن أعمل صالحا ترضاي
برحمتك ف عبادك وأدخلى
﴾ الصالحه
عظمال اللهصدق
(19)الات سورة الىمل
إليي لا يطيب الميل إلا بشكرك ولا يطيب النيار إلا بطاعتك ..
.. ولا تطيب المحظات إلا بذكرك
ولا تطيب الآخرة إلا بعفوك ..
ولا تطيب الجنة إلا برؤيتك ..
اذا كان الاىداء يعبر ولو بجزء من الوفاء فالاىداء إلى
.. من بمغ الرسالة وأدى الأمانة .. ونصح الأمة .. إلى نبي الرحمة ونور العالمين
الشموع التي تنير لنا دروب الحياة ..الى الوالدين الحبيبين
اخواننا و اخواتنا الذين يؤازرونا ويدعموننا..الى
اضاف لنا تقدما في الحياة ..ق الى كل صدي
الى اساتذتنا و مربونا ..
لموصول الى ىذه المرحمة ناالــــــى من ميدوا الطريق امام
..نا واجتياد نالكم ثمرة جيد نيدي
لباحثون ا
كن عالما .. فإن لم تستطع فكن متعمما ، فإن لم تستطع فأحب العمماء ،فإن لم"
تستطع فلا تبغضيم"
بعد رحمة بحث و جيد و اجتياد تكممت بإنجاز ىذا البحث ، نحمد الله عز وجل
عمينا فيو العمي القدير ، كما لا يسعنا إلا أن نخص بأسمى انعمياعمى نعمو التي
..ير للأستاذةعبارات الشكر و التقد
كما نتقدم بالشكر الجزيل لكل من أسيم في تقديم يد العون لإنجاز ىذا
..البحث، و نخص بالذكر أستاذتنا الكرام الذين أشرفوا عمى تكوين دفعة
الله العمي القدير ان يجزي الجميع خير الجزاء نسال
يحبو ويرضاه انو سميع مجيب .. وان يوفقيم لما
لباحثون ا
Description Symbols
Coefficient of Performance C.O.P
Pressure P
Enthalpy h
Heat of condenser Qc
Heat of evaporator Qe
Temperature T
Saturated temperature Tsat
Percentage mixing ratio by weight wt
Work of evaporator We
Ozone depletion OD
Global warming GW
Page Item
Chapter One/Introduction
1 1-1 Introduction
1 1-2 Ozone layer
1 1-3 Global Warming
2 1-4 Phase Equilibrium Diagram of Binary Mixture
3 1-5 The Aim of This Work
Chapter Two/Refrigerant Mixtures
4 2-1 Introduction
4 2-2 Background - Refrigerant Mixtures
4 2-3 Refrigerant Criteria
5 2-4 Alternative Refrigerants
7 2-5 Classification of Refrigerants
8 2-6 Azeotropic/Zeotropic Refrigerants
8 2-6-1 Azeotropic Mixtures
9 2-6-2 Non-Azeotropic/Zeotropic Mixtures
11 2-7 Oils
11 2-8 Refrigeration Oil
Chapter Three/Refrigerants Properties
13 3-1 Introduction
13 3-2 Azeotropic Refrigerants
13 3-3 Zeotropic Refrigerants
13 3-4 Saturated Properties Tables for Mixtures
14 3-4-1 For Azeotropic Refrigerants
17 3-4-2 For Zeotropic Refrigerants
21 3-5 Pressure – Enthalpy (P-h) Charts for Mixtures
21 3-5-1 For Azeotropic Refrigerants
24 3-5-2 For Zeotropic Refrigerants
Chapter Four/Conclusion and Recommendation
28 4-1 conclusion
29 4-2 Recommendation
References
30 References
Chapter One
Introduction
1-1 Introduction:-
Many of evolutions and modifications have been carried out compressive
cooling systems since beginning until the present time. Most of studies
focused on the mechanisms and methods of developing those systems, in
terms of performance (C.O.P). And the key factor was energy consuming
and their results, then the focus in researches and studies switched to other
fields which was concentrated on two main hubs, which are, the first is to
maintain a healthy environment by avoiding all harmful gasses accompanied
from engine combustion and air- conditioning refrigerants which have a
great impact on global warming and Ozone depletion, and second, is to
accommodate a natural alternatives instead of classical energy for long
term.
1-2 Ozone layer:-
The ozone layer or ozone shield is a region of Earth's stratosphere that
absorbs most of the Sun ultraviolet radiation. It contains high concentrations
of ozone (O3) in relation to other parts of the atmosphere, although still
small in relation to other gases in the stratosphere. Where Refrigerants
containing chlorine or bromine contribute to the breakdown of the ozone
layer.
1-3 Global Warming:-
There is an average increase in earth surface temperature with the increase
of the environmental harmful gases emission such as carbon dioxide
,Methane and other existed gases in the atmosphere . those gases called
greenhouse gases because they contribute in increasing the earth
temperature, this phenomenon is called the Global warming, and the average
of increasing temperature in the air where noticed in the middle of 20th
century as it continues to rise. Whereas the earth temperature was increased
0.74 ± 0.18° C over the last century. Where this increase in temperature
negatively affect the industrial revolution and the advancement of
technology which become one of the risks that surround the earth
environment and must be taken into consideration [1].
1-4 Phase Equilibrium Diagram of Binary Mixture:-
Phase equilibriums of binary mixtures are represented on phase diagrams.
Figure (1-1) depicts a phase diagram for a binary mixture system at constant
pressure. The dew point line represents the dew point temperatures of all the
possible mixture compositions, where Tdew is defined as the temperature at
which a superheated vapor mixture will first begin to condense upon
cooling. The bubble point line represents the bubble point temperatures of
all the possible mixture compositions, where Tbub is defined as the
temperature at which a sub-cooled mixture will first begin to evaporate upon
heating. The composition of one of the components, in this case the
component with the lowest boiling point, is depicted on the lower axis,
where the equilibrium vapor composition Y is that which corresponds to the
liquid composition X at the same temperature. It can be seen from the figure
mentioned above that the saturation temperature of one pure component is
on the left vertical axis while that of the other component is on the right
vertical axis [2].
Figure (1-1) Phase equilibrium diagram at constant pressure for a binary
mixture [2].
1-5 The Aim of This Work:-
The aim of this work is, to identify the blend refrigerant compression
cooling system, which is consists of two or more refrigerant gases and
knowing the proportion of each gas exist in the mixture and studying the
differences in their properties and behavior, as well as comparing them with
compression refrigeration pure gases which consist of one pure refrigerant
gas.
Chapter Two
Refrigerant Mixtures
2-1 Introduction:-
This chapter studies the properties of substances used as working fluids in
compression cycles, and discusses the classification of refrigerants.
Some of the most common refrigerants are presented, as well as the special
phenomena occurring with the use of zeotropic refrigerant mixtures. Finally,
the use of secondary refrigerants and oil in refrigerant are discussed.
2-2 Background - Refrigerant Mixtures:-
Evaporation or condensation of a pure fluid is isothermal. However, a
mixture with two or more components exhibits non-isothermal phase change
behavior. For example, start and finish of evaporation of a mixture occur at
bubble point and dew point temperature respectively [3].
2-3 Refrigerant Criteria:-
A working fluid in a compression refrigeration system must satisfy a
number of requirements that can be divided into two groups:
1. The refrigerant should not cause any risk of injuries, fire or property
damage in case of leakage.
2. The chemical, physical and thermodynamic properties of the refrigerant
must suit the system and the working conditions at a reasonable cost.
Table (2-1) show refrigerant criteria but at the same time it is not possible
to fulfill all the requirements above at the same time. The most important
criterion is chemical stability within the refrigeration system. All the
other criteria are meaningless if the refrigerant decomposes or reacts with
the materials used in the system.
Table(2-1) The criteria can be specified more precisely as follows [4]:
2-4 Alternative Refrigerants:-
The vast majority of refrigerating systems use the practical reversed
Rankine cycle. Some alternative systems use the Rankine cycle with
refrigerants which restrict their fields of application but many alternative
systems are cycles or methods which are fundamentally different.
Refrigerants are divided into groups according to their chemical
composition. Following the discovery that some of these chemical
compounds may be harmful to the environment, they are being replaced with
more environmentally friendly alternatives (as show in figure 2-1). The
Stable and inert Chemical
*Non-toxic
*Non-flammable
*Benign to the atmosphere , etc Health & safety &
environmental
*Critical point and boiling point temperatures
appropriate for the application
*low vapor heat capacity
*low viscosity
*High thermal conductivity
Thermal
*Satisfactory oil solubility \ miscibility
*High dielectric strength of vapor
*Low freezing point
*Easy leak detection
*Low cost
Other
process is not easy, and although there are alternatives to old refrigerants,
the new ones are usually not flawless.
Figure (2-1) Alternatives to the "old" refrigerants [4].
Table (2-2) Summary table of the different types of refrigerants.
Table (2-3) Summary table of the different types of refrigerants.
Alternative
refrigerants
HCFC
(with chlorine)
pure
e.g.R22 mixtures
R410A
HFC
(no chlorine)
pure
e.g.R134a mixtures
R407C
Hologen free
pure
e.g.Ammonia
propane
mixtures
e.g.proanel
iso-butane
Glide Safety Series Refrigerant A1 Methane series R32
A1 Ethane series R125
A1 Ethane series R134a
A2 Propane series R245ca
R245a
1K A1\A1 Zeotropic mixture
(44%R125\52%R143a\4%R134a) R404A
7K A1\A1 Zeotropic mixture
(23%R32\25%R125\52%R134a) R407C
Azeotropic mixture
(50%R32\50%R125) R410A
Azeotropic mixture
(50%R125\50%R143a) R507A
Azeotropic mixture
(46%R23\54%R116A) R508B
Atoms in the Molecule Meaning Prefix
CL \ F \ C Chlorofluorocarbn CFC
H \ CL \ F \ C Hydrochlorofluorocarbon HCFC
H \ F \ C Hydrofluorocarbon HFC
H \ C Hydrocarbon HC
Table (2-4) Health and safety classification.
CLASS/GROUP Description
A The toxicity of the refrigerant is not identified at
concentrations below 400 ppm volume.
B Evidence of toxicity identified at concentrations below 400
ppm by volume.
1
No flame propagation in air at 18*c and 101kpas> This
group has the least severe restrictions, but the maximum
amount of refrigerant in the system (g-room volume) is
limited. The purpose of this limitation is that if a pip fracture,
the concentration of refrigerant in the room is kept below the
hazardous level.
2
Lower flammability limit than group 1, but the toxicity is the
largest hazard. These is also a limit on the amount of
refrigeration in the system, depending the category to which
the room in question belongs.
3
Highly flammability. This group has the most severe
restrictions. Depending on the filling licenses are needed in
some cases. If a refrigerant is not classified, it is considered
as group 3 refrigerant until classification.
2-5 Classification of Refrigerants:-
This section is focused only on the primary refrigerants which can be
classified into thfollowing five main groups:
• halocarbons.
• hydrocarbons.
• inorganic compounds.
• azeotropic mixtures.
• nonazeotropic mixtures.
Figure (2-2) refrigerant classification[1].
2-6 Azeotropic/Zeotropic Refrigerants:-
A refrigerant may be either a pure compound or a mixture (blend) of two
or more refrigerants. Examples of pure refrigerants are R12, R22 and R134a.
Examples of mixtures are R502, R404A and R407C. A mixture can behave
either as a pure refrigerant (azeotropic mixtures), or differently (non-
azeotropic, or zeotropic, mixtures).
2-6-1 Azeotropic Mixtures:-
Although it contains two or more refrigerants, at a certain pressure an
azeotropic mixture evaporates and condenses at a constant temperature.
Because of this, azeotropic mixtures behave like pure refrigerants in all
practical aspects. Figure (2-3a) shows that the temperature is constant in the
liquid-vapor mixture region for a given pressure. For example
1- R500 consist of (R12/R152)(73.8/26.2)wt%
2- R502 consist of (R22/R115)(8.8/51.2)wt%
3- R503 consist of (R23/R13)(40.1/59.9)wt%
2-6-2 Non-Azeotropic/Zeotropic Mixtures:-
Zeotropic mixtures have a gliding evaporation and condensing temperature
[show Figures (2-4) and (2-5)]. When evaporating, the most volatile
component will boil off first and the least volatile component will boil off
last. The opposite happens when gas condenses into liquid. Figure (2-
3b) shows that for a given pressure, the temperature will change in the
liquid-vapor mixture region. This results in a gliding evaporation and
condensing temperature along the heat transfer surface. In practice, the
saturation temperature at the inlet of the evaporator will be lower than at the
outlet. In the condenser, the saturation temperature at the inlet will be higher
than at the outlet.For example
1- R404a consist of (R122/R143/R134a)(44/52/4)wt%
2- R407c consist of (R32/R125/R134a)(23/25/52)wt%
3- R410a consist of (R32/R125)(50/50)wt%
4- R413a consist of (R600a/R218/R134a)(3/9/88)wt%
Figure (2-3)….(a): Pure refrigerant or azeotropic mixture (no glide). (b):
Non-azeotropic (zeotropic) mixture (glide) [5].
Figure (2-4) Condenser and evaporator temperature program, counter-
current flow [5].
Figure (2-5) Condenser and evaporator temperature program, co-current
flow [5].
Zeotropic mixtures have a gliding evaporation and condensing temperature
When evaporating, the most volatile component will boil off first and the
least volatile component will boil off last. The opposite happens when gas
condenses into liquid .change in the liquid-vapor mixture region. This results
in a gliding evaporation and condensing temperature along the heat transfer
surface. In practice, the saturation temperature at the inlet of the evaporator
will be lower than at the outlet. In the condenser, the saturation temperature
at the inlet will be higher than at the outlet [6].
2-7 Oils:-
Oil is normally present in a refrigeration system, and the interaction
between the oil and the refrigerant must be considered. High oil solubility is
used in hermetic compressors, but immiscible oils are normally used when
the working fluid is ammonia.
2-8 Refrigeration Oil:-
The moving parts of a compressor assembly must be lubricated for smooth
operation and prevention of damage. Oil is also used at the seals and gaskets.
In addition, a small amount of oil is added to the refrigerant in the system to
maintain the thermostatic expansion valve in proper operating condition.
The classification of refrigeration oil is based on three factors such as
viscosity, compatibility with refrigerants, and pour point. R-12 requires oil
with a viscosity rating of about 300 for air-conditioning service; however oil
up to 1000 viscosity rating has been used in some systems.
The refrigerant oil must be compatible with the refrigerant used in the
system, and there must not be any change or separation by chemical
interaction. The temperature at which oil just flows is its pour point. The
properties of good refrigeration oil are low wax content, good thermal and
chemical stability, low viscosity, and a low pour point.
Chapter Three
Refrigerants Properties
3-1 Introduction:-
Refrigerants mixtures as a refrigerant has thermodynamic properties, in
vapor compression refrigeration cycles design must know these properties to
study refrigerant conditions and decide the acceptable design.
A program (REFPROP) were used to accomplished fluids mixing process
(Zeotropic and Azeotropic) and getting properties table and (p-h) schemes
and studying properties behaviour those mixtures [7].
In this work, seven refrigerants- as Examples for both Azeotropic and
Zeotropic types - will be studded and comparing their properties:
3-2 Azeotropic Refrigerants:-
4- R500 consist of (R12/R152)(73.8/26.2)wt%
5- R502 consist of (R22/R115)(8.8/51.2)wt%
6- R503 consist of (R23/R13)(40.1/59.9)wt%
3-3 Zeotropic Refrigerants:-
5- R404a consist of (R122/R143/R134a)(44/52/4)wt%
6- R407c consist of (R32/R125/R134a)(23/25/52)wt%
7- R410a consist of (R32/R125)(50/50)wt%
8- R413a consist of (R600a/R218/R134a)(3/9/88)wt%
3-4 Saturated Properties Tables for Mixtures:-
For these tables the range of properties depending on pressure was (1 to 25)
bar by (1 decrement) was shown in following tables (3-1 , 3-2,3-3,3-4,3-5,3-
6 and 3-7).
3-4-1 For Azeotropic Refrigerants:-
1- R500 consist of (R12/R152)(73.8/26.2)wt%
Tables (3-1) saturated properties for R500.
2- R502 consist of (R22/R115)(8.8/51.2)wt%
Tables (3-2) saturated properties for R502.
3- R503 consist of (R32/R125)(50/50)wt%
Tables (3-3) saturated properties for R503.
3-4-2 For Zeotropic Refrigerants:-
1- R404A consist of (R122/R143/R134a)(44/52/4)wt%
Tables (3-4) saturated properties for R404A.
2- R407C consist of (R32/R125)(50/50)wt%
Tables (3-5) saturated properties for R407C.
3- R410A consist of (R32/R125)(50/50)wt%
Tables (3-6) saturated properties for R410A.
4- R4013a consist of (R600a/R218/R134a)(3/9/88)wt%
Tables (3-7) saturated properties for R413a.
3-5 Pressure – Enthalpy (P-h) Charts for Mixtures:-
For these charts the range of pressure (Y axis) was (1 to 20) bar and of
enthalpy ( X axis) was (100 -600) kJ/Kg shown in following figures [(3-1)
, (3-2),(3-3),(3-4),(3-5),(3-6) and (3-7)].
3-5-1 For Azeotropic Refrigerants:-
1- R500 consist of (R12/R152)(73.8/26.2)wt%
Figure (3-1) saturated properties for R500.
2- R502 consist of (R22/R115)(8.8/51.2)wt%
Figure (3-2) saturated properties for R502.
3- R503 consist of (R23/R13)(40.1/59.9)wt%
Figure (3-3) saturated properties for R503.
3-5-2 For Zeotropic Refrigerants:-
1- R404A consist of (R122/R143/R134a)(44/52/4)wt%
Figure (3-4) saturated properties for R404A.
2- R407C consist of (R32/R125/R134a)(23/25/52)wt%
Figure (3-5) saturated properties for R407C.
3- R410A consist of (R32/R125)(50/50)wt%
Figure (3-6) saturated properties for R410.
4- R4013a consist of (R600a/R218/R134a)(3/9/88)wt%
Figure (3-7) saturated properties for R413.
Chapter Four
Conclusion and Recommendation
4-1 Conclusion:-
1- Pure refrigerants which have low OD and GW are very limited and
the number of diverse applications of refrigeration is ever increasing.
If a pure refrigerant cannot meet the requirements. But mixture
refrigerant offer the advantage of tailoring the composition to suit
various temperature requirements. It is also possible to control the
properties such as toxicity, flammability, oil miscibility by
manipulating the composition. Hence, they are finding greater use.
2- A refrigerant may be either a pure compound or a mixture (blend) of
two or more refrigerants. Examples of pure refrigerants are R12, R22
and R134a. Examples of mixtures are R502, R404A and R407C. A
mixture can behave either as a pure refrigerant (azeotropic mixtures),
or differently (non-azeotropic, or zeotropic, mixtures).
3- Zeotropic mixture is one whose composition in liquid face differs to
that in vapour phase. Zeotropic refrigerants therefore do not boil at
constant temperature unlike azeotropic refrigerants. For example
9- R404a consist of (R122/R143/R134a)(44/52/4)wt%
10- R407c consist of (R32/R125/R134a)(23/25/52)wt%
11- R410a consist of (R32/R125)(50/50)wt%
12- R413a consist of (R600a/R218/R134a)(3/9/88)wt%
4- Azeotropic mixture is a stable mixture of two or several refrigerants
whose vapour and liquid phases retain identical compositions over a
wide range of temperature. For example
7- R500 consist of (R12/R152)(73.8/26.2)wt%
8- R502 consist of (R22/R115)(8.8/51.2)wt%
9- R503 consist of (R23/R13)(40.1/59.9)wt%
5- Different zeotropic mixtures have different temperature glides. For
Ex. zeotropic mixture R152a/R245fa has a higher temperature glide
than R21/R245fa. A larger gap between the boiling points creates a
larger temperature glide between the boiling curve and dew curve at a
given mass fraction. However, with any zeotropic mixture, the
temperature glide decreases when the mass fraction of a component
approaches 1 or 0 (when the mixture is almost separated into its pure
components) because the boiling and dew curves get closer near these
mass fractions.
4-2 Recommendation:-
1- Drawing compression cycle for the fluids (R404a, R413a, R500,
R502, ….) scheme for each fluid and conducting practical calculation,
such as (C.O.P , We , Qe , Qc).
2- Charging refrigeration system by two kinds of blends and study the
differences between them practically.
[1] Thomas F. Stocker, Dahe Qin, Pauline M. Midgley, "Climate Change
2013 The Physical Science Basis", Working Group I Contribution to the
Fifth Assessment Report of the Intergovernmental Panel on Climate Change,
Printed in the United States of America, (2013).
[2] Reinhard Radermacher and Yunho Hwang, "Vapor Compression Heat
Pumps with Refrigerant Mixtures", by Taylor & Francis Group, LLCCRC
Press is an imprint of Taylor & Francis Group, (2005).
[3] Leelananda Rajapaksha, "Zeotropic Refrigerant Mixtures in Vapour
Compression Refrigeration Systems - Issues and Implications" ENGINEER
- Vol. XXXVIII, No. 04, pp. 52-59, (2005).
[4] Ibrahim Dincer, "Energy Solutions to Combat Global Warming",
University of Ontario, Canada (2017).
[5] Xiayan Z., Changfa J., Xiuling Y., "Prediction Method for Evaporation
Heat Transfer of Non-Azeotropic Refrigerant Mixtures Flowing Inside
Internally Grooved Tubes", Applied Thermal Engineering, Vol. 28, Issues
14-15, pp. 1974-1983, (2007).
[6] Ibrahim D. "Refrigeration Systems and Application", John & Wiley,
England (2003).
[7] NIST Standard Reference Database 23, Version 9.0 E.W. Lemon, M.L.
Huber and M.O. Mclinden , Copy right 2010 by U.S. Secretary of commerce
on behalf of the United States of America.
References
جميورية العراق وزارة التعميم العالي والبحث العممي
الجامعة التقنية الشمالية/كركوكالتقني معيدال
فيفرع التبريد والتكيقسم المكائن والمعدات/
بحث مقدم الى
(( ن والمعدات / فرع التبريد والتكييفمكائقسم ال ))
من اعداد
ابراهيم نجم الدين محمود جلال علي اصغر
ابراهيم احمد محمد احمد باهر محمد
جورج عوديشو باوث
باشراف
2018 1439