7/31/2019 Recloser Smart Grid - GMK Kiosk Brochure
1/8
GMK
OSM AUTOMATIC
CIRCUIT RECLOSER
15kV 27kV & 38kV MOdELS
GROUND MOUNT KIOSK
PRODUCT GUIDE
-
7/31/2019 Recloser Smart Grid - GMK Kiosk Brochure
2/8
Introduction
Cable Entry, Main Earth Bar & High VoltageTerminations
1. Earth Switch Viewing Window
2. Cable Termination
3. Main Earth Bar
4. Gland Plate
The GMK Ground Mount Kiosk is designed for the
connection and protection of underground cables
for voltage classes up to 38kV.
The kiosk houses an OSM automatic circuit
recloser, an RC controller, an interlocked isolation
and earthing mechanism and cable connection
compartment.
The OSM automatic circuit recloser has been
extensively type tested by independent laboratories
to ensure long life and reliability under the harshest
environmental conditions. It is the only solid di-electric insulated recloser to provide controlled
arc fault venting and independent testing provides
verification of this important safety feature.
The RC controller provides all the protection, data
logging and communications functions. An operator
panel is used to operate the device locally.
A two phase VT located in the main compartment
provides low voltage AC auxiliary supply to the RC
controller.
A manual trip mechanism is located above the
RC controller, and is used to manually open and
isolate the OSM. The mechanism is then rotated
using a lever to connect earth switches to the
Load side of the OSM.
Underground cables enter the kiosk through a
metal plate provided in the base of the cable
GMK Ground Mount Kiosk
INTRODUCTION
connection compartment. Six DIN 400 or ANSI
Taper aromatic epoxy bushings are provided to
terminate the cables onto the Load and Source
side of the OSM automatic circuit recloser. An
earth bar is also located in this compartment for
earth bond connections.
1. Product Guide GMK Ground Mount Kiosk
-
7/31/2019 Recloser Smart Grid - GMK Kiosk Brochure
3/8
Introduction 1.2.
The OSM automatic circuit reclosers incorporatevacuum interrupters insie a soli ielectricpolymer housing enclose insie an arc ventestainless steel tan. This ensures the maximum inlife an reliability with a fully insulate arrangementinsie the long life housing.
Voltage is measure on all six (6) bushings usingcapacitively couple screens. Current is measureon all three (3) phases using current transformers.
The recloser mechanism is operate by three (3)
separate magnetic actuators, one per phase. Thesemagnetic actuators are mechanically interloceto guarantee correct three (3) phase operation.The evice is latche in the close position bymagnetic latching. Each magnetic actuator usesa single coil.
The open an close position of the evice isinicate by a green 0 to inicate the evice isopen an a re I to inicate the evice is close,this can be viewe through the winow next to thecontrol cubicle.
The status of the recloser is also reflecte by amicroswitch connecte to the control electronics.The electronic circuit boar where the microswitchis fitte has no active elements which ramaticallyimproves impulse immunity.
The main circuit bushings are manufacture fromUV stable polymer an have a silicone rubber
OVERVIEW
bushing boot to provie the require creepageistance.
The magnetic actuators are operate from storeenergy charge capacitors locate in the RCcontrol cubicle. There is a rating plate locatein the base of the tan that provies tan ratingetails in accorance with the requirements ofANSI C37.60.
The cross sectional iagram below etails theOSM tan configuration an main components.
1. Bushing Connector2. Silicone Rubber Bushing Boot3. Polymer Bushing4. Current Transformers5. Capacitively Couple Voltage Sensor6. Stainless Steel Tan7. Magnetic Actuator8. Opening Spring9. Auxiliary Switches10. Insulate drive Ro11 . Polycarbonate Housing
12. Vacuum Interrupter13. Ceramic Breather14. Mechanical trip Ring
Product Guide GMk Groun Mount kios
OSM Automatic Circuit Recloser
-
7/31/2019 Recloser Smart Grid - GMK Kiosk Brochure
4/8
Introduction
The RC10 control an communications cubicle isa microprocessor base controller that provies airectional overcurrent, earth fault an sensitiveearth fault relay, auto reclosing relay, instantaneousmetering, event log, eman logger an remoteterminal unit (RTU) for remote control in a singlepacage.
The operator control panel is provie with a largebaclit LCd isplay an eypa to provie localcontrol functions.
The control cubicle has three (3) main moules:
The operator panel moule which proviesthe man machine interface.
The Switchgear Interface Moule (SIM) whichprovies the power supply battery chargeran incorporates the capacitors that proviethe tripping an closing energy to the OSMtan.
The Relay moule which provies the mainmicroprocessor an dSP functionality.
Temperature compensate float charging is
provie to the seale lea aci batteries locatein the RC10 control cubicle.
There is space provie insie the control cubicleto install any communications equipment to beconnecte to the inbuilt RTU or I/O moule.
The equipment has been esigne for the RC10control cubicle to operate over a temperature rangeof -40 to +55C insie the IP65 seale enclosure.
The cubicle is constructe out of power coatestainless steel for a long, maintenance free lifetime.The roof features a ceramic base insulating
RC10 CONTROL &
COMMUNICATIONS CUBICLE
coating that provies a 16C reuction in internaltemperature when the cubicle is expose to 1.1Wof solar raiation.
The entry point for the control cable is housewithin a vanal-proof enclosure an the cubicleoor has a three point hanle locing mechanismmaing it extremely ifficult to brea into.
Control an Communications Cubicle
3. Product Guide GMk Groun Mount kios
Trip/Close Auxiliaryswitches
3 Phase HV Line CVT CVT
PhaseVacuum
OSM
Recloser
Control Cable
Power
Data
Control / Indicaton
Relay
I/O
modules
AC Power
Supply
PC with CMSsoftware
RTU or
Radio /
modem
RC10
Cubicle
SCADA
Comms.
USB
RS485
RS232PSM
Panel
UPS &
Switchgear
Control
SIM
RechargeableBattery
3 x Inputs(Internaluse only)
-
7/31/2019 Recloser Smart Grid - GMK Kiosk Brochure
5/8
Introduction 4.Product Guide GMk Groun Mount kios
4 Inepenent Protection Groups directional over current an earth fault protection Current Setting Range 10-1280A Setting Resolution 1A
Inverse Time Protection Inepenent Curve Selection for Forwar
& Reverse direction 4 x IEC255 Curves 8 x ANSI Curves User define Curves 42 x Custom Curves
definite Time Protection 0-120 secons
Time Resolution 0.01 secons High set Instantaneous element
directional Sensitive Earth Fault Protection Current Setting Range 4-80A 1-80A option available Setting Resolution 1A definite Time 0-120 secons Time Resolution 0.01 secons
Voltage Protection Element Phase unervoltage balance element
(UV1) 3 phase loa sheing Multiplier setting range: 0.6-1 of system voltage Multiplier setting resolution: 0.01 Trip time range: 0-180 sec Trip time setting resolution: 0.01 sec
Phase-to-Phase Unervoltage Element(UV2) Multiplier setting range: 0.6-1 of system voltage Multiplier setting resolution: 0.01 Trip time range: 0-180 sec Trip time setting resolution: 0.01 sec
Loss of Supply (UV3) Trip time range: 0-180 sec
Trip time setting resolution: 0.01 sec Reclose time: 0-180 sec Reclose time resolution: 0.01 sec
Phase (OV1) & Line-to-Line (OV2) OverVoltage Trip time range: 0-180 sec Multiplier Setting Range: 1.00 -1.20
Frequency Protection Element Uner Frequency (UF) Picup Range:
46-50Hz (50Hz system), 55-60Hz(60Hz system)
Over Frequency (OF) Picup Range: 50-55Hz (50Hz system), 60-65Hz (60Hz
system) Frequency settings resolution: 0.01Hz Trip time range: 0-120 sec Trip time setting resolution: 0.01 sec
Voltage reclose control with automatic bacfee restoration provies loop automationfunctionality.
Zone Sequence Co-orination Col Loa Picup Col loa time ramp up: 1-400 min Col loa time ramp own: 0-60 min Col loa time resolution: 1 min Col loa multiplier: 1-5 times picup current Col loa multiplier resolution: 0.1
Inrush Restraint
Inrush time: 0.01-10 sec Inrush time resolution: 0.01 sec Inrush multiplier: 1-20 Inrush multiplier resolution: 0.1
Temporary Time Aition
Provies a steppe time elay toautomatically isolate faulte sections ina feeer or correct graing of evices inseries.
duty Cycle O-0.1sec-CO-1sec-CO-1sec-CO-60sec
recovery time
Reclosing Times 1st reclosing time range 0.1 - 180 secons 2n reclosing time range 1 - 180 secons 3r reclosing time range 1 - 180 secons Setting resolution 0.01 secons
Auto Reclose User configurable 1-4 trips to locout,
inepenently settable for overcurrentearth fault, sensitive earth fault an voltageprotection.
Live Line Function & Hot Line Tag Function
Local Control Panel
PROTECTION
-
7/31/2019 Recloser Smart Grid - GMK Kiosk Brochure
6/8
Introduction5. Product Guide GMK Ground Mount Kiosk
Voltage is measured on all six (6) bushings andcurrent is measured on all three (3) phases of theOSM recloser using capacitively coupled voltagesensors and current transformers.
Phase to Earth Voltage:Range 0.3 - 22.0kV, Accuracy 1% or 0.1kV
Phase to Phase Voltage:Range 0.5 - 38.0kV, Accuracy 2% or 0.1kV
Phase Current:Range 0 - 630A, Accuracy 1% or 4A
Residual Current:Range 0 - 100A, Accuracy 5% or 0.5A
Active, Reactive and Total Power:Range 40 - 630A, 4.5 - 38kV, Accuracy 2%
Single and Three Phase Active, Reactive andTotal Power:Range 0 - 30,000 kW/kVAR/kVA, Accuracy 2%
Frequency:Range 46-55Hz, 55-65HzAccuracy at dF/dT < 0.2Hz/s: 0.025Hz
Range 46-55Hz, 55-65HzAccuracy at dF/dT < 0.5Hz/s: 0.05Hz
Power Factor:Range 0-1, Accuracy 0.02
A USB front panel interface is provided to connect
to a PC running CMS. This provides full settingsand data management facilities. An RS232 RTUinterface offering 300-19.2k & 3xUSB port baud,full and half duplex modes, is provided to connectto remote control systems. NOJA Power RecloserApp is available for IPhone and IPad.
DNP3 communications protocol is provided inthe standard product combined with our abilityto engineer new protocols to meet specifiedcustomer requests.
The control cubicle has space to mount a radioor modem. The onboard radio power supply is
rated at 12V 20W continuous duty, 30 watts 50%duty cycle.
I/O modules with eight (8) user configurableinputs and eight (8) user configurable outputs canbe ordered as options in the RC10 control. Upto two I/O modules can be fitted extending thisto sixteen inputs and sixteen outputs. Three (3)user configurable sanitated inputs are included asstandard.
MEASUREMENT
EVENT LOG
LOAD PROFILE LOG
REMOTE CONTROL
The RC10 control provides two method to accessthe event logs time and date stamped to a 0.01sec resolution.
The first is method is from the RC LCD display, itprovides critical operations data for the linesmanand includes close/open operations, fault types,
phase and peak level of fault current.
The second is method is by PC upload usingCMS. It provides a full log of all operational historyincluding setting changes, operations and faulthistory.
The fault history logs include 50 cycles of pre-triphistory to allow analysis of the fault propagation.
The Load Profile is logged with a user configuredintegration period of either 1, 5, 10, 15, 30, 60 and120 minutes.
The following parameters are logged separately forboth positive and negative power flow.
Up to 10000 events can be stored in the memorywhich corresponds to a 417 day, 60 minute,integration period.
CMS can be used to upload and plot the data.
-
7/31/2019 Recloser Smart Grid - GMK Kiosk Brochure
7/8
Introduction
COMPONENTS
1. Earth Connection Viewing Winow2. Loa Sie Bushings3. Source Sie Bushings4. Earth Bar5. dIN 47636 series 400 630A Interface Bushing6. Earth Switch7. Phase To Phase VT8. Interloc Operator Shown In Normal Position8A. Interloc Operator Shown In Isolate Position9. Seale Lea Aci Battery10. Power Supply an driver Moules11. Main Processor Moule12. LV Mole Case Breaers an General Purpose Outlet13. Lifting Lugs14. Sling Guies15. Recloser Status Viewing Winow16. Removable Operating Arm Shown In Isolate But
Not Earthe Position.16A.Removable Operating Arm Shown In Isolate an
Earthe Position
Top View B
Front View Bac View
Sie View
Top View A
6.Product Guide GMk Groun Mount kios
-
7/31/2019 Recloser Smart Grid - GMK Kiosk Brochure
8/8
OSM15-16-6303 x Current Transformers
6 x Voltage ScreensRC 1015.5kV630A16kA40kA16kA30,00030,00020016kA/4 secs630A25A10A
110kV110kV50kV50kV-40C to +55C0-100%3000M720kg
Part NumberCurrent Sensing
Voltage SensingControl TypeRated Maximum VoltageRated Continuous CurrentFault Make Capacity RMSFault Make Capacity PeakFault Break CapacityMechanical OperationsFull Load OperationsFault Break Capacity OperationsShort Time Current WithstandMainly Active Breaking CapacityCable Charging CurrentLine Charging Current
Impulse Withstand Phase to Earth & Phase to PhaseImpulse Across the InterrupterPower Frequency Withstand Phase to Earth (Dry)
Across the InterrupterAmbient TemperatureHumidity
AltitudeWeight of the Tank
OSM27-12-6303 x Current Transformers
6 x Voltage ScreensRC 1027kV630A12.5kA31.5kA12.5kA30,00030,00020012.5kA/4 secs630A25A5A
125kV (150kV option)125kV (150kV option)60kV60kV-40C to +55C0-100%3000M720kg
OSM38-12-6303 x Current Transformers
6 x Voltage ScreensRC 1038kV630A12.5kA31.5kA12.5kA30,00030,00020012.5kA/3 secs630A40A5A
195kV170kV70kV70kV-40C to +55C0-100%3000M775kg
Altitudes above 1000m should be derated in accordance with ANSI C37.60-2003
NOJA-552-02
NOJA Power is a registered trademarks of NOJA Power Switchgear Pty Ltd. This document is copyright and is intended for users and distributors of NOJA Power Switchgear product. It contains information that is the intellectual
property of NOJA Power Switchgear and the document, or any part thereof, should not be copied or reproduced in any form without written permission from NOJA Power Switchgear.NOJA Power Switchgear applies a policy of continued fundamental research and development and reserves the right to change designs and specifications of this product without notice. NOJA Power Switchgear does not accept
any responsibility for loss or damage incurred by anyone as a result of acting or refraining from action based on information in this Product Guide.
Scan o v
NOJA Po
bs
NOJA POwer AuStrAliACOrPOrAte OffiCe & fACtOry
NOJA Po Schga P ld
16 Archimedes Place, Murarrie
Brisbane Qld 4172, Australia
Phone: +61 (7) 3907 8777Fax: +61 (7) 3399 6777
Email: [email protected]
Web: www.nojapower.com.au
NOJA POwer uKSAleS OffiCe
NOJA Po lmd
4 Stalyhill Drive, StalybridgeCheshire SK 15 2TR
United Kingdon
Phone: +44 (01865) 58 94 99Fax: +44 (01865) 58 9400
Email: [email protected]
Web: www.nojapower.co.uk
NOJA POwer CHileSAleS OffiCe
NOJA Po SpA
Av 11 d spmb 1881, O 1415
Povdnca, Sanago