Using ENERGY STAR Portfolio Manager to Satisfy NYC’s Greener, Greater Buildings Plan
Benchmarking Workshop
Intro
Amber Ackman, LEED A.P.
Energy Consultant
Amber Ackman, LEED A.P.
Energy Consultant
What is ENERGY STAR?
What is ENERGY STAR Portfolio Manager?
A voluntary partnership between business and government (EPA and DOE) which provides an established framework to promote the environmental and financial benefits of improved energy performance
A Web-based interactive energy management tool that allows you to track and assess energy and water consumption across your entire portfolio of facilities in a secure online environment
How does ENERGY STAR Portfolio Manager Work?
Normalizes building variables that affect energy consumption
•Weather•How occupants use space•Operating hours•Occupant density•Plug load (PCs/person)
Creates a whole building “mpg” rating from 1-100
How are Buildings Compared?
Commercial Building Energy Consumption Survey (CBECS)
Similar buildings, of similar use in comparable climate zones are compared to each other, buildings are not being rated against other
buildings entered into ENERGY STAR Portfolio Manager
How is an ENERGY STAR Rating Determined?
EUI (Energy Use Intensity)-EUI is calculated by taking the total energy consumed in
one year (measured in kBtu) and dividing it by the total
floorspace of the building.
• Portfolio Manager Username and Password
A master account is to be set up for you and individual
accounts for each client
• Client Contact and Organization Info
• Building Basics:
Street address, year built, contact information
• Building Gross floor area and Space Use types
Office, data center, garage, etc.
• 12 consecutive months of utility bills for all fuel types
Gas, electricity, steam, fuel oil
What’s Needed to Benchmark a Building?
What information needs to be collected?
•General Building Information•Address, year built
•Space Use Type Information•Office, data center, garage
•Energy Use Information- 12 months•ALL energy that served the building•All energy meters and associated account numbers
How do we satisfy the WATER benchmarking requirement?
Water use will not be required until 2012 when the
Department of Environmental Protection has
installed citywide automated meter reading (AMR)
network
Where do we go to access ENERGY STAR Portfolio Manager?
– ENERGY STAR score is for spaces specifically designed and equipped for high density computing (server racks, data storage silos, etc)
– Typically facilities with an Uninterruptible Power Supply (UPS)
– Usually have dedicated cooling systems
– May include: traditional enterprise services, on-demand enterprise services, high performance computing, internet facilities, hosting facilities
– Typically about 30-50 kW electric load on the UPS• EPA is working on an official size (energy) threshold
– Is not for • Computer training classrooms
• Closet with LAN server
Data Center Definition
Data Center Tips
• IT Energy Estimates
– Intended for buildings with no IT meter(s)
– Only permitted for 2 years (until June 2012), after which IT energy measurements are required
– Can only be applied to buildings with data centers whose square foot is less than 10% of the total energy
– Are permitted for label applications (until June 2012)
• Buildings are required to apply estimates and/or provide measured IT Data
– It is not permissible to subtract the Data Center space and energy
Steam
Adding Energy Use
Very Important Re: Steam
ConEd Bills list:
Mlbs. Steam
ENERGY STAR
Must input as Klbs.