PC57.13.3
IEEE Guide for Grounding of Instrument Transformer Secondary
Circuits and Cases
![Page 2: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/2.jpg)
OUTLINE
ScopeReferencesNeed for grounding; WarningDefinition of Instrument transformersGrounding secondary circuitsGrounding at a single locationConductor size for connecting to ground
![Page 3: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/3.jpg)
Scope
The scope of the guide includes the grounding practices presently used and the practices that were not previously reported. Specifically, the issue of the grounding of cases of electronic transducers is addressed.
![Page 4: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/4.jpg)
Covers
The practices described in this standard apply to all instrument transformers, including capacitive voltage transformers and linear couplers, irrespective of primary voltage or whether the primary windings are connected to, or are in, power circuits or are connected in the secondary circuits of other transformers as auxiliary cts or vts.
![Page 5: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/5.jpg)
Does not cover
This guide does not discuss the grounding of some applications. For example, grounding of gas insulated substations and metal clad switchgear is not discussed in this guide; the reader will find these topics addressed in reference [9] listed in clause 2. The grounding of circuits of core-balance CTs is also not discussed in this guide. The reader can find this information also in reference [9] listed in clause 2. Another issue that is not discussed in this guide is the practice of using separate safety and control grounds. For discussion on this topic, the reader is directed to reference [12] listed in clause 2.
![Page 6: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/6.jpg)
References
[1] NFPA 70-2002, National Electricity Code® (NESC®)[2] ANSI C2-2002, National Electrical Safety Code® (NESC®)[3] C37.103™-2004, IEEE Guide for Differential and Polarizing Relay Circuit Testing[4] C57.13.1™-1981 (Reaffirmed 1999), IEEE Guide for Field Testing of Relaying Current Transformers[5] C37.92™-2004, IEEE Trial Use Standard for Low Energy Analog Signal Inputs to Protective Relaying
![Page 7: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/7.jpg)
References
[6] C62.92™-2000, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems[7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding[8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems[9] Std. 242™*2001, IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems[10] Std. 518™-1982 (R1996), IEEE Guide for the Installation of Electrical Equipment to Minimize Electrical Noise Inputs to Controllers from External Sources
![Page 8: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/8.jpg)
References
[11] Std. 525™-1992, IEEE Guide for the Design and Installation of Cable Systems in Substations[12] Std. 665-1995, IEEE Guide for Generating Station Grounding[13] Std. 1050-1996, IEEE Guide for Instrumentation and Control Equipment Grounding in Generating Stations[14] Std. 1100™-1999, IEEE Recommended Practice for Powering and Grounding Electronic Equipment[15] Std. 1143™-1994 (Reaffirmed 1999), IEEE Guide on Shielding Practice for Low Voltage Cables
![Page 9: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/9.jpg)
Need for Grounding Secondary Circuits
To protect equipment connected to the circuitsTo Protect personnel who might come into contact with the equipmentHow the problem manifestsWhen secondary circuit is not groundedWhen a case is not groundedVoltage due to charge accumulation on an
ungrounded secondary circuit or case
![Page 10: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/10.jpg)
Warning
Grounding of secondary circuits is an issue of safety of personnel and equipment connected to the secondary circuits. The reader is urged to consider it seriously and follow the stipulations of relevant standards and ensure that the stipulations of the National Electrical Code [1] and the National Electric Safety Code [2] are always adhered to.
![Page 11: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/11.jpg)
Warning
Article 90.2 (A) of National Electrical Code [1] lists the installations that are covered by the Code [1] and Article 90.2 (B) lists the installations that are not covered by the Code. For immediate reference of the readers, Article 90.2 of National Electrical Code [1] is reproduced in Annex C.
![Page 12: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/12.jpg)
Grounding of Instrument Transformer Secondary Circuits
Definition of a secondary circuit for the purposes of the guideIssuesGrounding at a single locationMinimum size of the grounding conductor
![Page 13: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/13.jpg)
Issues
Grounding at a single locationVoltage at different locations of the physical
ground and circuits connected to ground is different when fault currents flow
Convenience of testing a secondary circuitProblem with forming a common neutral of
more than one instrument transformers and then grounding the neutral busIsolation of all secondary circuits from
ground
![Page 14: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/14.jpg)
Issues
Recommended point of grounding switchboard or relay panel
Grounding unused secondary windingsGrounding examples
![Page 15: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/15.jpg)
Grounding 3 4 Wire VT Circuits
![Page 16: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/16.jpg)
PA
PB
PC
PB
PC
OPENDELTA
WYE
PA
CONNECTIONS TOGROUND BUS ATSWITCHBOARD(#12 AWG CUMINIMUM)
NEUTRAL NOT BROUGHT
OUT
GROUND ISOLATINGCONNECTION
Grounding 3 3 Wire VT Circuits
![Page 17: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/17.jpg)
Grounding unused CTs
![Page 18: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/18.jpg)
ISSUES
Minimum size of grounding conductor 12 AWG required by NESC©
![Page 19: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/19.jpg)
TYPICAL APPLICATIONS
VT circuitsVoltage provided from distribution transformers
![Page 20: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/20.jpg)
Using Voltage from a Distribution Transformer
![Page 21: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/21.jpg)
GROUND ISOLATING CONNECTION
PG
PN
RTO RELAYS,OSCILLOGRAPH,ETC.
TO GENNEUTRAL
STATION GROUNDMAT
SWITCHBOARDGROUND
Generator Neutral Grounding Transformer
![Page 22: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/22.jpg)
Generator Neutral Grounding Transformer
CENTER TAP GROUND SOMETIMESUSED SO THAT ACCIDENTAL GROUNDON PG WILL NOT COMPLETELY DISABLEGENERATOR GROUND PROTECTION
OPTIONALCONNECTION
PG
PN
R TO RELAYS,OSCILLOGRAPH,ETC.
TO GENNEUTRAL
STATION GROUNDMAT
![Page 23: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/23.jpg)
Generator Neutral Grounding Transformer
![Page 24: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/24.jpg)
Generator Grounding Transformer
R
GROUNDINGTRANSFORMER
TO RELAYS,OSCILLOGRAPH,ETC.
![Page 25: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/25.jpg)
Basic Synchroscope Circuit
PB
PN
SCOPE
PN
PB2525
CKT. 2 CKT. 1
GROUNDING ISOLATIONCONNECTION
RUN INC
![Page 26: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/26.jpg)
Synchroscope with Multiple Incoming Circuits
![Page 27: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/27.jpg)
Synchroscope with Multiple Incoming and Running Circuits
PB
PN
SCOPE
PN
PB25-125-1
CKT. 3 CKT. 1
GROUNDING ISOLATIONCONNECTION
RUN INC
25-2 PB25-2
25-1
25-2 PN
CKT. 2
GROUNDS NOT NECESSARILYELECTRICALLY CLOSE
25-1
25-2PN
CKT. 4
PB
![Page 28: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/28.jpg)
Synchroscope with Multiple Incoming and Running Circuits using Isolating Transformers
PB
PN
SCOPE
PN
PB25-125-1
CKT. 3 CKT. 1
GROUNDING ISOLATIONCONNECTION
RUN INC
25-2 PB25-2
PN
CKT. 2
PN
CKT. 4
PB
1 - 1 ISOLATINGTRANSFORMERS
![Page 29: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/29.jpg)
Synchroscope with Synchronizing Lights
PB
PN
SCOPE ORSYNC-CHECKRELAY
PN
PB2525
CKT. 2 CKT. 1
GROUNDING ISOLATIONCONNECTION
RUN INC
GROUNDS SHOULD BEELECTRICALLYAS CLOSE AS PRACTICAL
THIS CONTACT PERMITS THE TWO VOLTAGECIRCUITS TO BE SEPARATELY GROUNDED
SYNCHRONIZING LIGHTS
25
![Page 30: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/30.jpg)
Grounding Distribution Station with one used for Instrumentation
G(N)
PN
NOTE: BECAUSE OF THE TWO GROUNDSON G(N), IT SHOULD BE SUFFICIENTLYHEAVY SO THAT STATION GROUNDFAULTS WILL NOT CAUSE DAMAGE TOG(N)
SWITCHBOARD TERMINALS
GROUND ISOLATIONCONNECTION
![Page 31: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/31.jpg)
Grounding 1 CT Circuit
CP
CN
BURDEN
![Page 32: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/32.jpg)
Grounding 1 CT Circuit
GROUND ISOLATIONCONNECTION
BURDEN
CP
CN
![Page 33: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/33.jpg)
Grounding 3 CT Circuit
![Page 34: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/34.jpg)
Grounding 3 CT Circuit
![Page 35: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/35.jpg)
Grounding V Connected CT Circuit
![Page 36: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/36.jpg)
Delta-Delta Connected CTs in a Differential Protection Relay
![Page 37: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/37.jpg)
Delta-Wye Connected CTs in a Differential Protection Relay
SWITCHBOARDTERMINALS
GROUND ISOLATIONCONNECTION
DIFF.RELAYS
A B C ABC
CBA
CBB
CBA
CBB
CBC CBC
![Page 38: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/38.jpg)
Percentage Bus Differential Scheme
SWITCHBOARDTERMINALS
GROUND ISOLATIONCONNECTION
CD1N
CD1A
CD1B
CD1C
CD2A
CD2B
CD2C
CD3A
CD3B
CD3C
CD2N
CD3N
CKT. 1
TO CTSON CKT. 2
TO CTSON CKT. 3
RESTRAINT
OPERATE
PHASE A
PHASE B
PHASE C
ABC
![Page 39: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/39.jpg)
Ring Bus or Breaker and a Half Scheme
SWITCHBOARD TERMINALS(MAY BE SLIDING LINKTYPETO FACILITATE TESTING)
GROUNDISOLATINGCONNECTION
TERMINALSAT CT LOCATION
CONTROL HOUSEGROUND BUS
TO METERS,RELAYS, ETC.
TERMINALSAT CT LOCATION
![Page 40: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/40.jpg)
Multiple use of CTs
51-
A 51-
A51-B
51-B
51-C
51-C
![Page 41: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/41.jpg)
Grounding of Cases
Grounding metallic conductive casesInsulated cases with conductive internal partsUngrounded metallic cases or internal parts Protected by suitable barriers or elevated to
prevent contact if operating voltage exceeds 1,000 V
![Page 42: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/42.jpg)
Exceptions to Grounding
If the primary windings of instrument transformer circuits are connected to circuits of less than 1000 V with no live parts or wiring exposed or accessible to other than qualified persons, the circuits may not be grounded.
![Page 43: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/43.jpg)
Exceptions to Grounding
For instrument transformer cases, the cases or frames of CTs may not be grounded if the primary windings are not over 150 V to ground and are used exclusively to supply current to meters.
![Page 44: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/44.jpg)
Exceptions to Grounding
Cases of instruments, meters, and relays operating at less than 1000 V on switchboards having exposed live parts on the front of panels are not usually grounded. Mats of insulating rubber or other suitable floor insulation is provided where the voltage to ground exceeds 150 V.
![Page 45: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/45.jpg)
Exceptions to Grounding
Instruments, meters, and relays, whose current-carrying parts operate at voltages to ground of 1000 V and over, are isolated by elevating them or protecting them by suitable barriers, grounded metal or insulating covers, or guards. In such situations, the cases are not usually grounded.
![Page 46: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/46.jpg)
Grounding of Low-Energy Transducers
![Page 47: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/47.jpg)
Grounding of Low-Energy Transducers
![Page 48: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/48.jpg)
Grounding of Low-Energy Transducers
![Page 49: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/49.jpg)
Annex A
Grounding of shielded cablesTo consider current carrying capacity of the
shieldCables with spiral design shields are grounded
at both endsCables with drain wires are grounded at one
end
![Page 50: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/50.jpg)
Annex A
CTs installed over shielded cables
![Page 51: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/51.jpg)
Annex B
IEEE Standards reviewed by the WG
![Page 52: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/52.jpg)
Annex C
Clause 90.2, Scope of National Electricity CodeType of installations covered by the CodeType of installations not covered bye the CodeSpecial permission
![Page 53: I13presentation.ppt [Read-Only] · [7] Std. 80™-2000, IEEE Guide for Safety in AC Substation Grounding [8] Std. 142™-1991, IEEE Recommended Practice for Grounding of Industrial](https://reader030.fdocuments.in/reader030/viewer/2022041007/5ead97c98d6c8974e477813a/html5/thumbnails/53.jpg)
ANNEX D
Survey of Grounding PracticesApproximately one-third of the respondents do
not ground voltage transformers “at the first point of use” as described in the Guide. The Working Group is of the opinion that grounding “at the first point of use” is better than grounding at other locations.
Almost all respondents indicated that current transformers are grounded “at the first point of use” as described in the Guide.