Technical DatasheetTD 00059E/24/EN/01.13
• Space-saving single/dual channel version
•No additional supply voltage needed• Can be used up to SIL3• Bidirectional HART® transmission
Complete product information:www.e-direct.us/rb223
Specs at a glance:
•Certificates: ATEX II (1) GD EEx ia IIC/IIB ATEX II (1) GD EEx ib IIC/IIB
• HART® communication: Built-in resistance for HART® communication232Ω
•Version: Optional dual-channel version
•Signal transmission: - From non-Ex to Ex-areas - From Ex to non-Ex areas
1 or 2-channel barrier, without power supply
RB223
$ 216.00
![Page 2: RB223](https://reader031.fdocuments.in/reader031/viewer/2022020218/55a4101b1a28ab413d8b4846/html5/thumbnails/2.jpg)
RB223 2
Overview Technical data Dimensions
Electrical connection Price table ContactGo to shop
Application / Function
Application The RB223 isolator can be used to galvanically isolate active signal circuits (0 to 20 mA) in three applications:• Transmission from non-Ex to Ex
areas e.g for active adjusters, controllers or indicators
• Transmission from Ex to non-Ex areas for connection of active, intrinsically safe circuits to the PLC
• Transmission from Ex to non-Ex areas for supply of intrinsically safe transmitters with non-intrinsically safe transmitter power supply
Function The passive isolator transmits signal circuits from the input to the output by galvanic isolation. A HART® signal is also transmitted. The device is optionally available with intrinsically safe input/ output. The device is loop-powered and does not need any additional supply voltage of its own.
Ex area
Valve, actuator display Active
Active
Active
Active
Passive
Passive
Passive
MUS
Active
In
Passive
Process transmitter
Process transmitter
Process transmitter
4 to 20 mA Out
4 to 20 mA In4 to 20 mA
4 to 20 mA
Power supply
4-wire device(sensor, actuator)
2-wire device(sensor, actuator)
Non-Ex area
Applicationexample
![Page 3: RB223](https://reader031.fdocuments.in/reader031/viewer/2022020218/55a4101b1a28ab413d8b4846/html5/thumbnails/3.jpg)
RB223 3
Application / FunctionOverview
Electrical connection Price table ContactGo to shop
DimensionsTechnical data
Technicaldata Dimensions(ininches)
CurrenttransmissiondirectionNon-Ex→Ex;InputFunction range 0 to 40 mA (to 22 mA for specified accuracy)Effective voltage Max. < 26 V for specified accuracyShort circuit current Imax = 100 mALimiting voltage Umax = 30 V
CurrenttransmissiondirectionNon-Ex→Ex;OutputFunction range 0 to 40 mA (to 22 mA for specified
accuracy), max. current depends on loadLoad Loadresistancemax.0to600ΩType of protection Intrinsically safe according to ATEX:
Max. voltage: Uo≤28V Max. current: Io≤93mA Max. power: Po≤660mW
CurrenttransmissiondirectionEx→Non-Ex;InputFunction range 0 to 40 mA (to 22 mA for specified accuracy)Type of protection Intrinsically safe according to ATEX:
Max. voltage: Ui≤30V Max. current: Ii≤100mA Max. power: Pi≤750mW
CurrenttransmissiondirectionEx→Non-Ex;OutputFunction range 0 to 40 mA (to 22 mA for specified
accuracy), max. current depends on loadLoad Loadresistancemax.0to600Ω
Galvanic isolationTest voltage >1.5kVACbetweeninputandoutput
>1.5kVACbetweenthechannels
Power supplyStarting current Ownconsumption<50µAVoltage drop <(1.9V+400Ω×currentloop)
fornonEx→Ex <(3.9V+120Ω×currentloop) forEx→nonEx
Power loss <0.2Wat20mA(perchannel) without HART® <0.3Wat20mA(perchannel) with HART®
0.89 4.41
3.78
4.33
Installation according to instruction manual
AccuracyCurrent transmission <±10µA+0.15%frommeasuredvalueTemperature drift ≤±0.01%/10K
Operating conditionsAmbient temp. -20to+60°C(-4to+140°F)Storage temperature -20to+80°C(-4to+176°F)Climate class ToIEC60654-1classB2Relative humidity <95%withoutcondensationEMC Interference immunity to IEC 61 326
(industry) and NAMUR NE21
Mechanical constructionDimens.(W×H×D) 22.5×96×112(0.89”×3.78”×4.33”)forDIN
railtoIEC60715TH35Weight Approx.150g(5.29oz.)
GeneralCommunication HART® protocol: bi-directional possibleFrequency response 650Hzfor500ΩloadfornonEx->Ex
1300Hzfor500ΩloadforEx->nonEx
ApprovalsEx approvals ATEX II (1) GD [EEx ia] IIC/IIB
ATEX II (1) GD [EEx ib] IIC/IIBSIL Can be used up to SIL3
![Page 4: RB223](https://reader031.fdocuments.in/reader031/viewer/2022020218/55a4101b1a28ab413d8b4846/html5/thumbnails/4.jpg)
RB223 4
Application / FunctionOverview Technical data Dimensions
ContactGo to shopElectrical connection Price table
Ex → Non-Ex 2 channel
Non-Ex
HART
HART
6-5+4+H
3-2+
1+H232
232
30V
30V
26V
26V
10-
9+
8-
7+
channel 2
channel 1
Non-Ex → Ex 2 channel
Non-Ex
HART
HART
10- 6-5+4+H
3-2+
1+H
9+
8-
7+330
330
26V
26V
30V
30V
232
232
channel 2
channel 1
Pricetable
RB223 Order no. Price/pcs. in USDApproval Channel Transmission direction 1to5 6 to 10 11to35Non-hazardousarea 1x In-/Output RB223-A1A 246.00 229.00 216.00
2x In-/Output RB223-A2A 344.00 320.00 303.00ATEX II(1)GD(Ex ia)IIC 1x LPShazardousareatonon-hazardousarea RB223-B1A 266.00 247.00 234.00
2x LPSnon-hazardoustohazardousarea RB223-B1B 266.00 247.00 234.001x LPShazardousareatonon-hazardousarea RB223-B2A 364.00 339.00 320.002x LPSnon-hazardoustohazardousarea RB223-B2B 364.00 339.00 320.00
Accessories Order no. Price/pcs. in USDHousingField,R4182x180x165,5xM20,PCProtectionhousingMinitec.Synthetichousing+transparentcover.ProtectionIP66.4x22.5mm/2x45mm.
52010132 92.00
Prices valid until 09.30.2013 in U.S. dollars per unit (not including shipping and applicable sales tax).See Endress+Hauser, Inc. Terms and Conditions of Sale for shipping, tax, and payment terms.
Complete product information:www.e-direct.us/rb223
Electricalconnection
Moreproductstocompleteyourmeasuringpoint… PaperlessrecorderEcograph T RSG30
DigitalindicatorRIA46
CapacitiveprobeLiquicap T FMI21
![Page 5: RB223](https://reader031.fdocuments.in/reader031/viewer/2022020218/55a4101b1a28ab413d8b4846/html5/thumbnails/5.jpg)