MAYURAKSHI INSTITUTE OF ENGINEERING & TECHNOLOGY
SUMMER TRANNING AT
OIL & NATURAL GAS CORPORATION LIMITED
TRAINEE RAMLAL CHOUDHARY
![Page 2: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/2.jpg)
![Page 3: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/3.jpg)
COMPANY PROFILE• Established in 1956 in India.• It is ranked 22nd among the Top 250 Global Energy
Companies and 5th in Asia.• ONGC is world's NO. 3 Exploration and production
company.• Founder of ONGC- Late Shri K D Malviya • Head office of ONGC in situated in dehradun , India• ONGC responsible for extraction & production of
crude oil in India .
![Page 4: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/4.jpg)
Principle & operation of generator :-
• A generator is a machine by which mechanical energy is transformed into electrical energy.
• Generators can be sub-divided into two major categories depending on the electric current produced is alternating current (AC) or direct current (DC)
• The basic principle on which both types of generator works is the same
![Page 5: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/5.jpg)
N
N
SS
FIELD WINDINGPOLE
ARMATURE
BASE
COMMUTATOR
YOKE
![Page 6: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/6.jpg)
• The Generator Works upon the Principle of Faraday's law of electromagnetic induction.
• 'when a conductor moves in a magnetic field (cutting the magnetic flux lines), an emf gets induced in the conductor'.
• The direction of induced emf can be determined with help of Fleming's right hand rule
![Page 7: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/7.jpg)
Installed DG SET at KDM Complex• Company name = cummins• Manufacturing Date :- 04 – 05 -2002• Model :- NT-495-G• Rating = 100 KVA• Power factor = 0.8• Output voltage = 415 V• RPM = 1500• Frequency = 50 Hz• Output Current = 139 A• Noise = 65-75 db
![Page 8: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/8.jpg)
Short Comings of Existing DG SET
• Capacity of installed DG SET is not as per actual load it fulfil the utility requirements of KDM complex.
• Generator is not suitable for environment.• Existing DG SET is not energy efficient.• Fuel consumption is high. • High maintenance required.• Generates high noise (65-75db).
![Page 9: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/9.jpg)
ELECTRICAL LOAD AT KDM COMPLEX JODHPUR
TYPES OF ELECTRICAL LOADS INSTALLED
LOADHR SECTION 30,062W
F&A SECTION 28,029W
Geology & Chemistry SECTION 28,153 W
ENGG SECTION 45,440W
HFB & PRODUCTION SECTION 25,731W
CMC SECTION 7,122W
DRILL SECTION 28,268W
SCADA 76,554W
LOGISTIC SECTION 13,877W
MM SECTION 8,856W
SECURITY SECTION 3,751W
CANTEEN 2,780w
WATER MOTORS 11,190w
AREA LIGHTS + STREET LIGHTS 5,718w
TUBE LIGHTS car parking 240w
TOTAL POWER 310805 W
TOTAL POWER CONSUMPTION IN KDM COMPLEX ,JODHPUR 310.805 KW
![Page 10: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/10.jpg)
CALCULATION FOR PROPOSED DG SET
• TOTAL EXISTING LOAD: 311 KW
• CONSIDERING POWER FACTOR =0.8 311/0.8 – 388.75 KVA
• THEN EXISTING LOAD IN KVA=388.75
• SAY TOTAL =400 KVA
![Page 11: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/11.jpg)
PROPOSED DG SET
• Capacity =400 KVA• OUTPUT CURRENT= 400 v• Hz = 50 • Phase = 3 • Rpm = 1500• NOISE (db) = <75
![Page 12: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/12.jpg)
AVALIABLE GENERATORS OF COMPANY
• Cummins Diesel Generator Set (QSN14 Series)
![Page 13: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/13.jpg)
Engine • Cummins QSN14 series, 6 cylinder, 4 stroke, water
cooled engine .• Compact in size with optimum power • Dual fuel filter system .• Water & Fuel sensor are connected .• Coolant in cooling system is circulated in the engine
to maintain temp. in engine.
![Page 14: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/14.jpg)
Alternator• An alternator is an electromechanical device that converts
mechanical energy to electrical energy in the form of alternating current. It may be called an AC.
• Stamford HC alternator Cummins Generator Technologies .• 3 Phase . • Better motor starting capability .• Best in class efficiency .��• Compact design with sealed bearings for longer life and lesser maintenance .• Better mechanical strength .• suitable for operation at 1500 RPM, 415 Volts, 0.8 pf , suitable for 50 Hz, 3 phase, 4 wire system.
![Page 15: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/15.jpg)
Auto start system
• Power Start operates on 12 V DC batteries• Auto start mode accepts a ground signal from
remote devices to automatically start the DG set.
• Engine Starting – The control system supports automatic engine starting .
• Controller provide time delay of 0-300 secs to start after remote start signal and time delay of 0-600 secs prior to shutdown after stop signal.
![Page 16: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/16.jpg)
• SILENCER • Silencer absorb high noise 1m area in 100% working• less Noise create <75db
• VIBRATION PAD • Vibration pad absorb the vibration working condition in dg set.
![Page 17: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/17.jpg)
Technical Data • Power Rating kVA = 400 • No. of Phases = 3• Output Voltage and Frequency (V and Hz) = 415 V, 50 Hz• Power Factor = 0.8 (lagging)• Current (A) = 556• RPM = 1500• Fuel consumption @75% load with radiator and fan* = 67.45 (litre/hr)• Fuel consumption @100% load with radiator and fan* = 88 (litre/hr)• NOISE (db) = <75 db• PRICE = 23,36,706 Rs
![Page 18: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/18.jpg)
S.N Technical Data CUMMINS NEW
CUMMINS OLD
1. FUEL CONSUMPTION100% load
88 (LTRS/HR) 22
75% load 67.45 17
2. POWER RATING(KVA) 400 100
3. O/P VOLTAGE & FREQUENCY
415 V / 50 HZ 400 V / 50 HZ
4. ENGINE Cummins QSN14 series, 6 cylinder, In-line 4 stroke, radiator cooled engine
Cummins 6BT5.9-G2 , 6 cylinder , 4 stroke engine
5. PRICE 23,36,706 Rs 6,25,933 Rs
6. Current (A) 556 150
7. Alternator Stamford Stamford (Single bearing, Brushless, Self-excited)
![Page 19: Ram lal choudhary (DG GENERATOR)](https://reader036.fdocuments.in/reader036/viewer/2022081502/58a386781a28ab9c7e8b5277/html5/thumbnails/19.jpg)