60 Hz // eSP-133-3
r410a // Hermetic
Scroll comprESSorS
Wider range
OrBit
VariaBLe SPeeD DriVe
2 ESP-133-3
User Selectable Drives
The ORBIT series can be used with BITZER’s intelligent VARIPACK drive, which are pre-configured with relevant parameters and may be easily modified with the BEST software (BITZER Electronics Service Tool). Alternatively, users can choose any drive from their own existing and preferred suppliers.
Design flexibility with reduced inventory costs
Since standard ORBIT compressors are VSD capable, system designers have many options. Even tandems, uneven tandems, and even fixed + variable speed tandems, for example. And, when used with BITZER Advanced Header Technology, it is possible in many cases to offer different efficiency versions of the system with common piping and construction, which greatly reduces factory complexity and inventory carrying costs. Such simple and efficient capacity staging solutions provide benefits for sales, technology, manufacturing and financial functions.
UVW
M
3 ~
T
TT
T
T
U
I
T1
4
3
6
5
2
ZK
30
4545
5555 6060
7575
Hz
4040
50506565
7070
35
8080
ORBIT for variable speed drive (VSD)
While the scroll compressors of the ORBIT series are characterized by high full load and seasonal efficiency, low sound levels, and high reliability, they are also now suitable for use with variable speed drives. VSD capable scroll compressors from BITZER give system designers more solutions to the challenge of maintaining full load and rating point efficiency levels, while also increasing efficiency at part load conditions where equipment operates during most of the year. Using the overspeed potential of the GSD gives the option of downsizing the nominal compressor displacement to cover partly the VSD costs. The wide speed range allows for capacity reduction together with low condensing pressure operation, e. g. in comfort air-conditioning applications, for high system efficiencies. Coupled with BITZER’s unique lower con-densing temperature optimization, system designers have never had so many options to satisfy their customers’ needs.
3ESP-133-3
High cooling capacity
The large capacity range of the ORBIT series is enhanced with the ability to either slow down, or speed up depending on demand. This in creased range can allow users the option to reduce the number, size and variety of compressors used in the system design.
Heat pump application
The ORBIT with VSD capability is an ideal solution for designers looking for high system performance. While a standard scroll compressor must cycle on/off to achieve temperature control in the building, a scroll with VSD can easily follow the characteristics. In addition, BITZER provides a large application envelope precisely in the area most needed by heat pump applications. Off-setting low refrigerant mass flow rates associated with these conditions is now possible with BITZER’s ORBIT with VSD capability.
IPLV advantage
While ORBIT operation is known for its optimization towards IPLV, these benefits are further enhances with the application of VSD technology increasing the IPLV even up to 15%. Designers can take advantage of the lower condensing pressures associated with part-load operation and further reduce their power consumption. This is in particular of advantage with refrigerant-to-air systems but also for chillers with two or more compressors in multi-circuits (one with VSD) for stepless modulation of the required cooling demand.
50
40
30
20
10
40 GSD8018
2V
GSD8038
5V
GSD8042
1V
ORBIT 8 Nominal Speed ORBIT 8 Variable Speed
Cap
acit
y (T
ons
acc
ord
ing
to
AH
RI 5
40)
GSD8023
5V
GSD8029
5VGSD80
485V
Hea
t P
ump
Cap
acit
y [B
tu/h
]
Heat Pump Capacity & Heat Load: Fixed vs. Variable Speed
Ambient Temperature [°F]
SupplementalHeat required
Bivalent Point
IPLV for Refrigerant-to-Air Systems
Btu
/(W
x h
)
25
20
15
BITZER ORBIT
Variable Speed
+15
% S
easo
nal
Ene
rgy
Effi
cien
cy
Required building heat Load Standard Scroll Compressor at fixed speed ORBIT 8 Variable Speed (smaller size compressor)
Bivalent Point: Heating capacity of smaller size compressor at 75 Hz equal to standard scroll at fixed speed (50 Hz)
4 ESP-133-3
160
140
120
100
6060400 20
SDT [°F]
SST [°F]
80
-20
SH = 20°F
35 Hz
Application Limits
BITZER ORBIT with VSD
BITZER ORBIT 8 Boreal with VSD
SST Saturated suction tempeature (°F) SH Suction superheat (°F) SDT Saturated discharge temperature (°F)
-20 804020040
160
140
120
100
80
60
SDT [°F]
SST [°F]
SH = 20°F
35 Hz
5ESP-133-3
ORBIT 6 Performance data
Performance data are based on AHRI 540 boundary conditions.Saturated suction and discharge temperatures correspond to “dew point” conditions (saturated vapor).
Performance data based on 20°F suction superheat and 15°F subcooling ➀.
Compressor type
Ü
SST (°F) 45 45 45 45 45 45 45 45 45
SDT (°F) 130 130 130 120 120 120 100 100 100Frequency (Hz) 35 60 75 35 60 75 35 60 75
R410A ➂
Q 69.93 125.92 159.65 75.83 135.36 170.79 87.41 153.40 192.39
GSD60120VA P 7.29 10.92 14.28 6.50 9.78 12.92 5.12 7.86 10.56
EER 9.59 11.53 11.18 11.67 13.85 13.22 17.07 19.51 18.21
Q 79.63 139.86 171.21 86.32 149.99 184.53 98.28 169.76 210.26
GSD60137VA P 7.48 12.20 15.35 6.59 10.91 13.75 5.14 8.84 11.14
EER 10.65 11.47 11.15 13.10 13.75 13.42 19.12 19.21 18.87
Q 89.38 156.85 195.21 97.03 168.24 210.43 110.74 190.37 239.22
GSD60154VA P 8.10 13.61 17.38 7.14 12.18 15.57 5.58 9.87 12.56
EER 11.04 11.53 11.23 13.60 13.81 13.52 19.84 19.28 19.05
Q 104.78 185.63 235.35 114.14 199.52 252.28 131.62 225.81 284.53
GSD60182VA P 9.61 16.06 20.61 8.47 14.48 18.51 6.62 11.85 15.07
EER 10.90 11.56 11.42 13.47 13.78 13.63 19.89 19.06 18.88
Qo 134.72 241.00 295.88 145.42 258.64 320.01 165.29 291.78 365.41
GSD60235VA P 12.27 21.50 27.21 11.00 19.25 24.39 8.95 15.59 19.78
EER 10.98 11.21 10.87 13.22 13.43 13.12 18.47 18.72 18.47
Cooling capacity Power consumption Energy Efficiency Ratio EERQo Pe ➁
[kBTU] [kW]
ORBIT 6
Tentative data
➀ Running-in period 72 hours.
➁ Power consumption at motor terminals; power consumption at inverter intake depends on the individually applied inverter model.
6 ESP-133-3
ORBIT 8 Performance data
Performance data are based on AHRI 540 conditions.Saturated suction and discharge temperatures correspond to “dew point” conditions (saturated vapor).
Performance data based on 20°F suction superheat and 15°F subcooling ➀.
Compressor type
Ü
SST (°F) 45 45 45 45 45 45 45 45 45
SDT (°F) 130 130 130 120 120 120 100 100 100Frequency (Hz) 35 60 75 35 60 75 35 60 75
R410A ➂
Q 114.71 244.05 288.93 128.23 265.87 312.89 154.10 305.44 357.14
GSD80235VA P 13.19 23.94 27.99 11.21 20.85 24.76 8.14 15.83 19.59
EER 8.70 10.19 10.32 11.44 12.75 12.64 18.93 19.29 18.23
Q 157.03 304.15 373.16 175.09 328.41 404.15 210.58 373.46 462.03
GSD80295VA P 18.19 27.48 34.92 15.55 24.23 31.00 11.45 19.05 25.03
EER 8.63 11.07 10.69 11.26 13.55 13.04 18.40 19.60 18.46
Q 221.44 395.23 484.81 242.19 426.25 521.51 280.91 484.78 591.26
GSD80385VA P 22.64 35.53 44.64 19.50 31.54 39.93 14.78 25.12 32.29
EER 9.78 11.12 10.86 12.42 13.51 13.06 19.01 19.30 18.31
Q 236.17 425.59 515.89 260.43 459.64 556.17 304.64 522.53 632.89
GSD80421VA P 23.78 38.62 51.28 20.28 34.12 46.15 15.15 26.98 37.82
EER 9.93 11.02 10.06 12.84 13.47 12.05 20.11 19.37 16.74
Q 267.76 483.19 542.12 297.87 519.05 585.59 349.71 586.23 668.00
GSD80485VA P 28.31 43.89 58.79 24.11 38.93 53.13 18.01 30.97 43.90
EER 9.46 11.01 9.22 12.35 13.33 11.02 19.42 18.93 15.22
Ü
SST (°F) 45 45 45 45 45 45 45 45 45
Compressor type SDT (°F) 130 130 130 120 120 120 100 100 100Frequency (Hz) 35 60 75 35 60 75 35 60 75
Q 117.68 245.84 285.16 132.36 266.58 307.73 158.10 303.62 352.24
GSD80235VW P 14.12 23.45 28.53 11.84 20.31 24.82 8.19 15.27 18.84
EER 8.33 10.48 9.99 11.18 13.13 12.40 19.30 19.89 18.70
Q 147.80 294.39 358.24 166.27 318.95 386.69 198.61 364.09 442.61
GSD80295VW P 17.62 28.70 35.74 14.77 24.72 31.09 10.22 18.28 23.59
EER 8.39 10.26 10.02 11.25 12.90 12.44 19.44 19.92 18.76
Q 183.87 375.65 456.40 209.75 408.36 498.42 253.03 467.99 574.22
GSD80385VW P 22.62 36.57 46.65 18.92 31.56 40.52 13.36 23.47 30.93
EER 8.13 10.27 9.78 11.09 12.94 12.30 18.94 19.94 18.56
Q 202.32 415.04 494.89 230.55 449.42 538.63 278.39 516.41 618.63
GSD80421VW P 24.37 39.71 49.17 20.40 34.44 42.71 14.45 25.90 32.37
EER 8.30 10.45 10.06 11.30 13.05 12.61 19.26 19.94 19.11
Q 233.32 461.57 567.00 264.95 501.06 613.11 320.79 577.76 705.15
GSD80485VW P 27.13 44.81 55.40 22.80 38.87 48.38 16.16 29.19 36.96
EER 8.60 10.30 10.23 11.62 12.89 12.67 19.85 19.79 19.08
Cooling capacity Power consumption Energy Efficiency Ratio EERQo Pe ➁
[kBTU] [kW]
ORBIT 8 optimized for air-cooled systems and reversible chillers
ORBIT 8 Boreal optimized for systems with low condensing temperature
Tentative data
➀ Running-in period 72 hours.
➁ Power consumption at motor terminals; power consumption at inverter intake depends on the individually applied inverter model.
7ESP-133-3
For dimensional drawings see brochure ESP-135.
ORBIT 6 Technical data
Compressortype
Displacement with 45 .. 65 Hz
CFM
Speed range➀
Oilcharge
➁
fl.oz
Weight
lbs
DLDischarge line
inch
SLSuction line
inch
Motor connection
➂
Rated load amps(RLA)
Amp. ➃
StartingcurrentLRA(Amp.)
Amp. ➄
GSD60120VA 8.2 .. 17.6 35 .. 75 Hz 91 195 7/8 1 3/8
Con
tact
BIT
ZER
See
BIT
ZER
Sof
twar
e
See
BIT
ZER
Sof
twar
e
GSD60137VA 9.2 .. 19.8 35 .. 75 Hz 91 195 7/8 1 3/8
GSD60154VA 10.3 .. 22.0 35 .. 75 Hz 91 195 7/8 1 3/8
GSD60182VA 12.1 .. 26.0 35 .. 75 Hz 91 195 7/8 1 3/8
GSD60235VA 15.6 .. 33.4 35 .. 75 Hz 91 195 7/8 1 3/8
Pipe connections ODS Electrical data compressor
➀Preliminary data. Speed range at time of publication. These data are subject to change as a result of BITZER’s policy of continuous improvement. Contact your local BITZER representative for application assistance.
➁Charged with polyvinyl ether BVC32.
➂Motor selection for FI operation depends on application considerations. For full envelope and over-speed capability, selection of the 208/230 V motor is generally required. Less demanding applications focused on IPLV consideration may be handled by either standard motor, or 380 V motors. Contact BITZER for assistance in proper selection.
➃ For the selection of contactors, cables and fuses the rated load amps (RLA) and the max. power consumption must be considered (“Electrical data”). RLA (MCC/1.56).
➄ Data for direct start. With VSD stepless rise of current up to actual load amps – maximum up to rated load amps (RLA).
Oil heater (option) 90 W/115 V, 230 V, 460 V, 575 V.
8 ESP-133-3
ORBIT 8 Technical data
Compressortype
Displace-ment with 35 .. 75 Hz
Speed range Oilcharge
➀
fl.oz
Weight
lbs
DLDischarge
line
inch
SLSuction
line
inch
DLDischarge line
inch
SLSuction line
inch
Motor connec-tion
➂
Rated load amps(RLA)
Amp. ➃
StartingcurrentLRA(Amp.)
Amp. ➄
GSD80182VA(B/R)2 12 .. 26 35 .. 75 Hz 179 320 1 3/8 1 5/8 1 3/4 – 12 UNF 2 1/4 – 12 UNF
Con
tact
BIT
ZER
See
BIT
ZER
Sof
twar
e
See
BIT
ZER
Sof
twar
e
GSD80235VA(B/R)2 16 .. 34 35 .. 75 Hz 179 326 1 3/8 1 5/8 1 3/4 – 12 UNF 2 1/4 – 12 UNF
GSD80295VA(B/R)2 20 .. 43 35 .. 75 Hz 179 333 1 3/8 1 5/8 1 3/4 – 12 UNF 2 1/4 – 12 UNF
GSD80385VA(B/R)2 26 .. 55 35 .. 75 Hz 179 337 1 3/8 1 5/8 1 3/4 – 12 UNF 2 1/4 – 12 UNF
GSD80421VA(B/R)2 28 .. 60 35 .. 65 Hz 179 336 1 3/8 1 5/8 1 3/4 – 12 UNF 2 1/4 – 12 UNF
GSD80485VA(B/R)2 32 .. 69 35 .. 65 Hz 179 372 1 3/8 1 5/8 1 3/4 – 12 UNF 2 1/4 – 12 UNF
GSD80235VW(B/R)2 16 .. 34 35 .. 75 Hz 179 326 1 3/8 1 5/8 1 3/4 – 12 UNF 2 1/4 – 12 UNF
Con
tact
BIT
ZER
See
BIT
ZER
Sof
twar
e
See
BIT
ZER
Sof
twar
e
GSD80295VW(B/R)2 20 .. 43 35 .. 75 Hz 179 333 1 3/8 1 5/8 1 3/4 – 12 UNF 2 1/4 – 12 UNF
GSD80385VW(B/R)2 26 .. 55 35 .. 75 Hz 179 337 1 3/8 1 5/8 1 3/4 – 12 UNF 2 1/4 – 12 UNF
GSD80421VW(B/R)2 28 .. 60 35 .. 65 Hz 179 336 1 3/8 1 5/8 1 3/4 – 12 UNF 2 1/4 – 12 UNF
GSD80485VW(B/R)2 32 .. 69 35 .. 65 Hz 179 338 1 3/8 1 5/8 1 3/4 – 12 UNF 2 1/4 – 12 UNF
Connection thread Version “R” ➁
Pipe connections ODS Version “B” ➁
Electrical data compressor
ORBIT 8 optimized for air-cooled systems and reversible chillers
ORBIT 8 Boreal optimized for systems with low condensing temperature
➀Charged with polyvinyl ether BVC32.
➁B = Direct brazing connections, R = Rotalock connections.
➂Motor selection for FI operation depends on application considerations. For full envelope and over-speed capability, selection of the 208/230 V motor is generally required. Less demanding applications focused on IPLV consideration may be handled by either standard motor, or 380 V motors. Contact BITZER for assistance in proper selection.
➃ For the selection of inverter.
➄ Data for direct start. With VSD stepless rise of current up to actual load amps – maximum up to rated load amps (RLA).
GSD80182V .. GSD80485V: Oil heater (option) 140 W/115 V, 230 V, 460 V, 575 V.
CFM
9ESP-133-3
Notes
10 ESP-133-3
Notes
11ESP-133-3
Notes
Bitzer Kühlmaschinenbau GmbHEschenbrünnlestraße 15 // 71065 Sindelfingen // Germany
Tel +49 (0)70 31 932-0 // Fax +49 (0)70 31 932-147 [email protected] // www.bitzer.de
Subject to change // 80171203 // 12.2016