R FIGHTER 1210 - · PDF fileGeneral FIGHTER 1210 For Home Owners 2 In order to get the...
Transcript of R FIGHTER 1210 - · PDF fileGeneral FIGHTER 1210 For Home Owners 2 In order to get the...
RINSTALLATION AND MAINTENANCE INSTRUCTIONS
FIGHTER 1210MOS GB 0337-1 611849FIGHTER 1210
LEK
For the Installer
Table of Contents 1
FIGHTER 1210
For Home Owners
General information for the installerTransport and storage ..........................................11Installation ............................................................11Collectors ..............................................................11Inspection of the installation ..................................11Electric boiler mode .............................................. 11Brine pump............................................................ 11
ControlGeneral ................................................................ 12Settings ................................................................ 12Drying process .................................................... 14
Pipe connectionsGeneral ................................................................ 15Pipe connections (collector) ................................ 15Pipe connections (heating medium) .................... 15Pipe connections (water heater) .......................... 16Ventilation recovery .............................................. 16Free cooling ........................................................ 16Pump capacity diagrams, heating medium side .. 17
Electrical connectionsConnecting .......................................................... 18External control of the immersion heater .............. 18Power rating as set at the factory ........................ 18Connecting the outdoor sensor ............................ 18
Commissioning and adjustingPreparations ........................................................ 19Filling and venting the collector system .............. 19Filling the heating/heating medium systems ........ 19Start-up and inspection ........................................ 20Readjustment, heating medium side .................... 20Readjustment, brine side .................................... 20Emptying the water heater .................................. 20
Setting the automatic heating control systemSetting with diagrams............................................ 21Heating curve offset -2 ........................................ 21Heating curve offset 0 .......................................... 21Heating curve offset +2 ........................................ 21
Component locationsComponent locations ............................................ 22
Wiring diagram 4 kW model Wiring diagram 4 kW model .................................. 24
Wiring diagram, 5 – 10 kW model Wiring diagram, 5 – 10 kW model ........................ 25
Circuit diagramCircuit diagram .................................................... 26
List of componentsList of components ................................................ 27
DimensionsDimensions and setting-out coordinates .............. 28
Technical dataTechnical specifications ........................................ 29
Enclosure kit/AccessoriesEnclosed kit .......................................................... 30Accessories ........................................................ 30
Dealing with malfunctionsLow temperature or a lack of hot water ................ 31Low room temperature ........................................ 31High room temperature ........................................ 31Indications ............................................................ 32Helping the circulation pump to start .................... 33Draining, heat medium side .................................. 33Draining, heat transfer side .................................. 33Inspection of the anode ........................................ 34Changing the anode.............................................. 34
GeneralConcise product description .................................. 2Setting table .......................................................... 2
System descriptionPrinciple of operation ............................................ 3
Front panelThe front panel ...................................................... 4Functions .............................................................. 5Setting different operating modes ........................ 5
ControlGeneral ................................................................ 6Setting, heat .......................................................... 6Changing the room temperature .......................... 6Heat production...................................................... 7Domestic hot water ................................................ 7Standby mode ........................................................ 7Information available on the display ...................... 8
General
FIGHTER 1210
For Home Owners
2
In order to get the ultimate benefit from your heat pump FIGHTER 1210 you should read throughthe For Home Owners section in this Installation and Maintenance Instruction.
FIGHTER 1210 is a heat pump central for the production of heating and domestic hot water inhouses. The ground, rock or lakes can be used as the heat source.
FIGHTER 1210 is a Swedish made quality product offering a long life span and safe operation.
Installation date
The serial number (95), should always be stated with all correspondence with NIBE.
689_ _ _ _ _ _ _ _ _ _ _
FIGHTER 1210- _ _ kW
Installation engineers
Anti-corrosionEnamel Stainless steel
Completed by the installation engineer when the heat pump is installed
The type of brine – Mixing proportion/freezing point
Active drilling depth/collector length
Commissioning checksTemperature brine (flow/return)____ / ____ Pump setting__
(Nominal temperature diff 2 – 5 °C)
Temperature heat medium (in/out) ____ / ____ Pump setting ___(Nominal temperature diff 5 – 10 °C)
Settings
Date ____________ Signed________________________________
Menu Basicsetting
2 Temp Sink .............. 8
2b Room * ..............
3 WW-in .............. 53
3 HW start .............. 44
4 Brine Out .............. -12
5 Curve slope .............. 9
5 Room-comp * .............. 4
5b WW-out min .............. 15
5b WW-out max .............. 45
Menu Basicsetting
9b HP-°min .............. 60
9b Add-min .............. 300
10 WW diff HP .............. 13
10 Diff HP-Add .............. 3
11 HP-int .............. 20
11 HWT-stop .............. 50
12 XWW-stop .............. 65
12 XWW interval .............. 14
17 Parallel ..............
18 Shunt 0
* Accessories
The FIGHTER 1210 consists of a heat pump, waterheater, immersion heater, circulation pumps and con-trol computer with display. FIGHTER 1210 is connec-ted to the collector and heating medium circuits.
The heat from the heat source (rock, soil, lake) is takenup via a closed collector system in which a mixture ofwater and antifreeze circulates. Groundwater can alsobe used as a heat source, but this requires an interve-ning heat exchanger.
The brine emits its heat to the refrigerant in the heatpump’s evaporator. It then vaporises and is compres-sed in the compressor. The refrigerant, the temperatu-re of which has now been raised, is passed to the con-denser where it gives off its energy to the heatingmedium circuit and, if necessary, to the water heater.After the condenser there is a built-in immersion hea-ter which cuts in if there is a high demand.
System description 3For Home Owners
FIGHTER 1210
Principle of operation
Hot watercirculation
Heating waterpump
Immersion heater
3 way valve
Heating waterflow
Heating waterreturn
Evaporator
Brine pump
Compressor
Condenser
Expansion valveCooling unit
Double jacket
Brine in
Brine out
Water heater
The heating medium side andthe domestic hot water sidemust be fitted with the neces-sary safety equipment inaccordance with the applica-ble regulations.
Front panel
FIGHTER 1210
For Home Owners
4
Front panel
+20
-2
1
R
0
VB-Fram 49 (50) °CVarmvatten 51 °C
LED indicatorsFunction keys
Display
B
Power switch
A
D
Increase/decrease heat
C
E
NOTE! Make sure there is water in the heat pump
before putting switch (A) into position 1 or R.
WW-out 49(50) °CHot-water 51 °C
Front panel 5For Home Owners
Power switchThree position switch (1 – 0 – R).0 Heat pump off.1 Normal mode. All control functions connec-
ted.R Spare mode, heat medium pump and immer-
sion heater step 2 only.
Function keysChannelSelection of the window menu.
IncreaseTo increase the current value.
DecreaseTo decrease the current value.
Operating modeAdditional heat and/or room heat on/off.See the following section.
Extra hot waterTemporary or periodic increase in the hotwater temperature. See the following sec-tion.
DisplayIn normal operation the display shows:
WW-out: Current flow temperature. (Calculated flow temperature.)
Hot water: Current hot water temperature.
LED indicatorsRoom heating
Shows room heating is allowed when lit(circulation pump in operation).
Heat pumpShows the compressor is running whenlit.
Hot waterShows that hot water charging is in pro-gress when lit.
– Flashes rapidly when temporary increa-se of the hot water temperature is selec-ted (approx. 60°C during 24 hours).
– Flashes slowly when periodic increaseof the hot water temperature is selected(approx. 60°C in accordance with theselected interval).
Additional heatShows that additional heat is switchedon when lit.
– Flashes slowly when additional heat isallowed.
– Flashing rapidly when only additionalheat is on.
AlarmsFlashes rapidly when a fault has occurred.
Increase/decrease heatThe increase/decrease heat knob raises orlowers the room temperature (changes the tem-perature of WW-out).
B
A
C
E
Functions
D
Normal mode (basic setting): Additional heat ready to start if needed. Hotwater charging cuts in if necessary.
LEDs:Room heating: LitHot water: Lit during hot water chargingAdditional heat Flashes/LitNo additional heat mode:Press the Operating mode button once.LEDs:Room heating: LitHot water: Lit during hot water chargingAdditional heat Not litNo room heating mode (only hot water):Press the Operating mode button again.LEDs:Room heating: Not litHot water: Lit during hot water chargingAdditional heat Not litThe next time Operating mode is pressed you returnto normal mode.
Normal mode No raised hot water temperature activated.
Temporarily raised hot water temperature:Press the Extra hot water button once. A raised hotwater temperature is obtained for 24 hours. The LEDHot water flashes rapidly.Lit during charging.Periodically raised hot water temperature:Press the Extra hot water button once. The increasein hot water temperature takes place according tomenu 12. The LED Hot water flashes slowly. Litduring hot water charging.The next time Extra hot water is pressed you return tonormal mode.
Setting different operating modes
FIGHTER 1210
Control
FIGHTER 1210
For Home Owners
6
The indoor temperature depends on several factors.During the hot season, solar radiation and heat givenoff by people and equipment are sufficient to keep thehouse warm. When it gets colder outside, the heatingsystem must be started. The colder it is outside, thewarmer radiators and floor heating system must be.This adjustment takes place automatically, since theFIGHTER 1210 is equipped with a control computerfor optimal, safe operation. However, the heat pumpmust first be given the correct basic setting.
Control of the heat production is performed based onthe “floating condensing” principle, i.e. the temperatu-re level needed for heating at a specific outdoor tem-perature is produced guided by collected values fromthe outdoor and heat medium flow sensors. As anoption, room sensors can also be used to compensatefor variations in room temperature. Hot water produc-tion is given priority and controlled by means of tem-perature sensors in the water heater and an operatingpressostat.
For general information and more reliable control ofthe function there are also sensors for incoming andoutgoing brine temperatures (collector). If required, aminimum limit can be set for the outgoing brine tempe-rature (for example, with a groundwater system).
General
Setting takes place by programming the Curve slope,see the section Available information and settings onthe display, and by setting the Heating curve offsetusing the Increase/decrease heat knob on the panel.
If you do not know the correct settings use the basicdata from the map opposite.
If the required room temperature is not obtained, read-justment may be necessary.
NOTE! Wait one day between settings so that thetemperatures have time to stabilise.
Readjusting the setting.
Cold weather conditionsIf the room temperature is too low, increase thevalue for the heating curve by one step.
If the room temperature is too high, decrease thevalue for the heating curve by one step.
Warm weather conditionsIf the room temperature is too low, turn the Increa-se/decrease heat knob one step clockwise.
If the room temperature is too high, turn the Incre-ase/decrease heat knob one step anticlockwise.
Changing the room temperature manually.
If you want to temporarily or permanently increase orlower the indoor temperature in relation to the pre-vious heat setting, turn the Increase/decrease heatknob clockwise or anticlockwise. One scale markingcorresponds to a change of about one degree in theroom temperature.
NOTE! An increase in the room temperature may beinhibited by the radiator or floor heating thermostats, ifso these must be open.
Setting, heat
Changing the room temperature
Control 7For Home Owners
FIGHTER 1210
When there is a demand for hot water, the heat pumpgives this priority and devotes its entire output towater heating. No room heat is produced in thismode. When the demand for hot water is high, themaximum time for water heating is approximately 45minutes. After this, room heating is produced for 15minutes before further water heating can take place.
If the immersion heater is activated for heat produc-tion before hot water charging, one step remains ope-rative during hot water operation. Hot water chargingstarts when the hot water sensor has fallen to the setstart temperature (30 – 49 °C). In order to reach themaximum hot water temperature, hot water chargingis stopped by the operating pressostat on the heatpump. In addition, charging can take place when theheat pump has reached its stop-level for heatingmode at the same time as less than 2 °C is neededbefore the start of hot water. The purpose of this is tominimise the number of starts.
NOTE! The indicated hot water temperature is mea-sured on the lower part of the water heater jacket.This means that it is not the exact temperature of thehot water. Usually the outgoing hot water is hotterthan the indicated temperature.
For occasional higher demand of hot water, the Extrahot water function can be used to raise the temperatu-re to about 60 °C for 24 hours (press the Extra hotwater button once”). The immersion heater is used toraise the temperature above 50 °C.
There is also a function to periodically increase thehot water temperature (press the Extra hot water but-ton twice). In this mode, the temperature is raisedtemporarily by means of the immersion heater toabout 60°C for a period of between 1 and 90 days.
The supply of heat to the house is regulated in accor-dance with the chosen setting of the regulating curve(curve slope and offset). After adjustment, the correctamount of heat for the outside temperature is suppli-ed. The heat pump’s flow temperature (WW-out) willhover around the theoretical required value (the valuein brackets on the display). For subnormal temperatu-res the computer calculates a demand in the form ofdegree-minutes, this results in the acceleration of heatproduction. The larger the subnormal temperature, thegreater the heat production.
There are four step to heat production, one for theheat pump and three for the immersion heater. Theoutput of the electrical unit as supplied is 6 kW (FIGHTER 1210–4, 3 kW) but it can be rewired to give9 kW.
In order to produce heat when the collector circuit isdisconnected, or during servicing, the heat pump canbe set to spare mode, in which case heat is producedonly by the immersion heater. Hot water is not produ-ced in spare mode. The compressor and collector sys-tem are then shutoff and only the heating medium cir-cuit and the immersion heater are active. The tempe-rature is controlled by the thermostat (3). To selectspare mode, set the switch (8) to R.
Heat production Domestic hot water
Spare mode
Control
FIGHTER 1210
For Home Owners
8
OutdoorActual outdoor temperature.
RoomActual room temperature. Only shown if a roomsensor is fitted.[P] (Target value set on room sensor.)Setting range: 5 – 30 °C.
In normal mode, the above information appears on theLCD display of the heat pump.WW-out
Current flow temperature(Calculated flow temperature.)
Hot-waterIndication of the hot water temperature.
1
2b
NOTE! Enter the selected values onpage 2 of this Installation
instruction. The details areimportant for service work.
FIGHTER 1210 is equipped with a 2 row LCD display.The heat pump can be set via this display and itsassociated buttons.
Channel selectionThe Channel button lets you browse through thefollowing display modes to find the information
you require. Values within brackets are also described withinbrackets.If a value is programmable, this is denoted by a [P](Programmable) in front of the value.If the next value cannot be changed, you can accessthe next menu by pressing Channel.
SettingThe first step when changing a value is to pressthe Increase button once. A cursor (line) thenappears under the value. Now you can eitherincrease or decrease the value with the Increa-se or Decrease buttons.
Available information and on-display settings
Outdoor Actual outdoor temperature.
Temp SinkTemperature drop, the heating curve is lowered,for example, by 8 degrees when the contact inthe room unit (accessories) makes. If the roomunit is connected a room sensor cannot be con-nected.[P] (The set Set point value for temperatur dropp.)Setting range: 5 – 30 °C.
2
WW-out 47(52) °CHot-water 48 °C
Outdoor -14 °CRoom 20,5(20) °C
Outdoor -14 °CTemp Sink 8 °C
Control 9For Home Owners
Brine InTemperature of brine in.
Brine OutTemperature of brine out.[P] (Min permitted temperature of brine from heat
pump.) This setting should only be changed by a specia-list. It is used for minimum limiting with alarm, forexample as an anti-freezing function in ground-water systems or exhaust air systems.A suitable setting with an intermediate heatexchanger would be 0 °C. When the lowest value(-12) is set, minimum limiting and the alarm aredisabled.Setting range: -12 – +10 °C.
WW-inActual temperature of incoming heating medium.[P] (Max permitted heat medium return tempera-
ture.)Setting range: 40 – 55°C and A.
Setting WW-inMaximum permitted return temperature for com-pressor operation. To change, press the Increa-se button once. A cursor will appear under thefigure for WW-in. Press the Increase or Decrea-se button to obtain the required value. If thevalue A is selected, (automatic indirect control ofthe return temperature) the operational pressureswitch will indirectly limit the return temperature.Press the Channel button to continue.
HW startActual temperature in lower part of water heaterouter jacket. [P] (Chosen start level for hot water production.)Setting range: 30 – 49 °C.
Setting HW startPress the Channel button. A cursor then appearswithin the brackets for HW start. Press the Incre-ase or Decrease button to select the start tempe-rature for the hot water heating.Press the Channel button to continue.
3
4
Curveslope[P] Set heating curve.Setting range: 1 – 15.
Setting the curveslopePress the Increase button once. A cursor appe-ars under the figure for curveslope. Press eitherthe Increase or Decrease button to set the requi-red curveslope.
Press the Channel button to continue.
Room-comp[P] When the room temperature differs by 1 °Cchange the set point value WW-out with the indi-cated value.A higher value gives a quicker reaction to excessor low indoor temperatures. The normal value fora radiator system is 4. Setting range: 0 – 6 °C)
Setting Room-comp(Only applies if a room sensor is connected).
After setting the curve slope, press the Channelbutton. The cursor moves under the figure forRoom-comp. Change the figure using the Increa-se or Decrease buttons. A higher value gives aquicker reaction to excess or low indoor tempera-tures. The normal value for a radiator system is 4.
5
Available information and on-display settings
FIGHTER 1210
WW-in 37(53) °CHW start 49(44) °C
Curveslope 9Room comp 4 °C
Brine In +3 °CBrine O 0(-12) °C
Control
FIGHTER 1210
For Home Owners
10
5b
7
8
This menu is a submenu to menu 5a and is activatedby placing the cursor under the value for Curveslope(or Room comp if a room sensor is connected) andpressing the Channel button.WW-out min
[P] Setting for the minimum calculated heatmedium flow. Setting range: 10 – 50 °C.Preset value: 15 °C
WW-out max[P] Setting for the maximum calculated heatmedium flow. Setting range: 30 – 70 °C.The preset value is 45 °C. Therefore this valuemust normally be increased when a radiator system is used.
As the heat medium flow temperature normally hoversin relation to the calculated temperature, values aboveand below the set value can temporarily occur.For example, the suitable values for floor heating withfloating condensing could be min 18°C, max 40°C.Setting WW-out min and WW-out max
Press the Increase button once. A cursor willappear under the figure for WW-out min". Presseither the Increase or Decrease button to set therequired WW-out min value.
Press the Channel button to move to WW-out max and change as required.
HP-time: Shows the total number of operating hours forthe heat pump.
Add-time: Shows the total hours of operation for addi-tional heat.
Basic: Change the left figure from 0 to 1 using the Incre-ase button at the same time as pressing the Operatingmode button to return to the basic settings.The two figures to the right specify the selected opera-ting mode. The middle figure specifies the operatingmode for room heating.0 signifies Normal mode.1 signifies No addition.2 signifies No room heating.The right figure specifies the operating mode for hotwater.0 signifies Normal mode.1 signifies temporary increased hot water temp.2 signifies periodically increased hot water temp.English: Selected language.Setting of languageLanguage selection is accessed the next time Chan-nel is pressed. Press Increase to change language.When the required language is selected, press theChannel button. You then return to display 1.
6
HPstart: Calculates the number of times the heatpump has started (accumulated).HP off: Shows the operating mode: “HP off”, “HP on”,“HP start in X minutes” or “WW in high”.
WW in high means that the return heating mediumtemperature to the heat pump is too high.
Available information and on-display settings
WW-out min 15 °CWW-Out max 45 °C
HP-time 40 hAdd-time 0 h
HP start 10HP off
Basic 0 00English
General information for the installer 11For the Installer
FIGHTER 1210
Current regulations require the heating installation tobe inspected before it is commissioned. The inspec-tion must be carried out by a suitably qualified personand should be documented. The above applies to clo-sed heating systems. If the heat pump is replaced, theinstallation must be inspected again.
FIGHTER 1210 is placed on a firm base, preferably aconcrete floor or foundation. Install FIGHTER 1210with its back to an outside wall, ideally in a room whe-re noise does not matter. If this is not possible, avoidplacing it against a wall behind a bedroom or otherroom where noise may be a problem. Irrespective ofthe placement the wall should be sound insulated.Route pipes so they are not fixed to an internal wallthat backs on to a bedroom or living room.
FIGHTER 1210 should be transported and stored ver-tically in the dry. The FIGHTER 1210 may however becarefully laid on its back when being moved into a buil-ding.
Transport and storage
Installation
Inspection of the installation
The length of the collector hose varies depending onthe rock/ground conditions and on the heating system,i. e. radiators or floor heating.
The unit can be used exclusively as an electric boiler,to produce heat and hot water, for example before thecollector installation is complete. For this mode, thehot water temperature is preset to 50 °C. See “Set-tings, menu 14”.
The brine pump (35) normally follows the operation ofthe heat pump. There is a special operating mode forcontinuous operation for 10 days, followed by returnto normal mode (this may be used before stable circu-lation has been established). See “Settings, menu14”.
Electric boiler mode
Brine pump
Collectors
ControlFor the Installer
12
FIGHTER 1210
Hold the Channel button down for about 7 seconds toaccess the following menus.
Then press Channel again until you reach the desireddisplay mode. To change the value of a displayed vari-able, first press the Increase button once. A cursor willappear under the value. The value can now be chan-ged by pressing the Increase or Decrease buttons.Pressing the Channel button again moves the cursorto the value below, which in some cases can now bechanged.
Control of the immersion heater for best comfort ismanaged by the computer. It calculates the flow tem-perature deficit in the form of degree-minutes.
If, for example, the heat medium flow temperature hasbeen 3 degrees lower than the calculated heat medi-
um flow temperature for 60 minutes; 3 x 60 = 180degree-minutes is registered by the computer. Usingthe standard setting the number of degree-minutesshould amount to 360 (60 + 300) before the immersionheater’s first step is connected. After which the follo-wing steps are connected with a further 100 degreeminutes difference. The output step remains actuateduntil the degree-minute demand for each step hasbeen compensated, which means that the heat medi-um flow temperature must be as many degree-minu-tes above the calculated flow level as it was previouslyunder. This is how the average heat medium flow tem-perature calculated by the computer is obtained.
General
Settings
GM[P] Actual value for number of degree-minutes.
For example, this value can be changed to acce-lerate the start of heating production.
Setting range: -3050 – +100.
WW diff HP[P] The highest temperature variation from thenominal value for the heat medium (WW) beforepositive operation of the heat pump takes place.
Basic setting: 13.
Setting range: 3 – 25.
Diff HP-Add[P] Variation downwards from WW diff HP atwhich the value positive operation of additionalheat (Add) takes place.
Basic setting: 3.
Setting range: 1 – 8.
9
9b
10
This menu is a submenu to menu 9 and is activated byusing the Increase button, set the cursor under thevalue for GM and press the Channel button.
The first step of additional heat (if used) is not activa-ted until the sum of the HP-°min and Add-°min set inthis menu is reached. Any other steps are connectedbetween 360 degree-minutes and 560 degree-minu-tes at even intervals.
HP-°min[P] Degree-minute demand before the heatpump can start.
Basic setting: 60.
Setting range: 5 – 250.
Add-°min[P]Additional degree-minute demand before thefirst step of supplementary heat (Add) is allowedto be activated.
Basic setting: 300.
Setting range: 50 – 2500.
HP-int[P] Min interval in minutes between heat pumpstarts.
Basic setting: 20.Setting range: 20 – 60.
HWT-stop[P] Stop temperature for water heater chargingwhen operating with additional heat only.
Basic setting: 50. Setting range: 10 – 70.
11
GM 0
HP-°min 60Add-°min 300
WW diff HP 13Diff HP-Add 3
HP-int 20 mHWT-stop 50 °C
Control 13For the Installer
FIGHTER 1210
Settings
DriftPShows the status of the operating pressostat
(1 = closed, 0 = open).HP/MS
Shows the status of the high pressure pressos-tat/motor protection (1 = closed, 0 = open). Givesa permanent alarm. Manual resetting of the motor protection.
LPShows the status of the low-pressure pressostat
(1 = closed, 0 = open). Gives a permanent alarm.
NOTE! Enter the chosen settings in the
table on page 2 of this manual.
The information is important for future servicing.
68: Start contactor, HP69: Operating contactor, HP35: Brine pumpXX: 3 way valve16: Heating medium pumpL: Not activeS-: Step 1S+: Step 2x3: Not active
Brine-pumpPositive operation of brine pump. Change 0 to 1 using the Increase button at the same time as pressing the Operating mode button.1 is then replaced by KB. Returns to normal mode after 10 days or with a restart.
Add-driftIf electric boiler operation is required (e.g. beforecollector installation is complete), toggle 0 to 1 andpress the Mode button”. The 1 is then supplemen-ted with “1EB”.Option 2 – 5 may not be used.Select the correct operating mode before Add-driftis activated. (Add-drift locks the operating modefunction).
Man: Manual test of outputs. Change Man 0 to Man 1or Man 2 to test different functions. Man 0 must be setbefore you can exit the menu.
12
13
14
15
16
XWW-stop[P] Extra hot water stop temperature.Basic setting: 65. Setting range: 60 – 65.
XWW-int[P] Interval in days for periodic extra hot water.Basic setting: 14. Setting range: 1 – 90.
Cal. Out[P] Calibration of outdoor sensors.
Room[P] Calibration of room sensor.
Brine In[P] Calibration of brine flow temperatur sensor.
Brine Out[P] Calibration of brine return temperatur sensor.
Setting range for all quantities: -5 – +5.
Operating mode button
XWW-stop 65 °CXWW-int 14d
DriftP 1HP/MS 1 LP 1
Brine-pump 0Add-drift 0
Cal.Out 0Room 0BrinIn 0BrinO 0
Man 0
Man: 1 68 0 69 035 0 XX 0
Man: 2 16 0 L 0S- 0 S+0 x3 0
Control (also with accessories)
FIGHTER 1210
For the Installer
14
18
Shunt 0Shunt = “0”, Control, supplement electric boileror oil boiler.
19
19bIt is important with some concrete floors to maintainthe right floor temperature during an initial period. Thisis so the floor dries correctly. FIGHTER 1210 has a function for this drying process.The process can be divided into two periods wherethe number of days and temperature are set forrespective periods. This setting is made on the chan-nel 19.
FDP int 1Shows the number of days at step 1.
WW-outShows the flow temperature at step 1.
FDP int 2Shows the number of days at step 2.
WW-outShows the flow temperature at step 2.
It is possible to set the number of days from 1 to 10and the temperature from 15 to 50 °C. Once the dry-ing process is finished the FIGHTER 1210 automati-cally returns to normal control.If a power failure occurs during the drying process thecurrent time and temperature are stored. When thepower returns the drying process continues with thesettings that applied before the power failure. Thusthe drying process is carried out to a 100%.
Drying process
ServicetimeChange from 0 to 1 to speed up the period oftime by 60 times. Resets 8 minutes after the lastbutton was pushed.
ParallelSetting of Increase/Decrease heat potentiometerto displace the heating curve (parallel offset).To return to display 9, press the Channel button.You then return to the original display 1. Pressthe Channel button and keep it held down forabout 7 seconds to return to service mode, dis-play 9.
17
Settings
NOTE! The shunt must be set to 0.
Servicetime 0Parallel 0
Shunt 0
FDP-int1 8dWW-out 25 °C
FDP-int2 8dWW-out 40 °C
Pipe connections 15For the Installer
FIGHTER 1210
Factors to be taken into account when designing thecollector layout are geographical position, type ofrock/soil and cover factor of the heat pump.
When installing the collector hose ensure it rises con-stantly towards the heat pump to avoid air pockets. Ifthis is not possible, install high points to vent the air.
All collector pipes in heated rooms must be insulatedagainst condensation. The level vessel (NK) must beinstalled as the highest point in the collector systemand on the incoming pipe before the brine pump. Notethat condensation may drip from the level vessel.Position the vessel so that this does not harm otherequipment.
Since the temperature in the collector system may fallbelow 0 °C, the system must be protected from free-zing by mixing, for example, a proprietary ethanolsuch as Svedol or Brineol, with water. The mixtureshould be around 30% ethanol and the rest water. Asa guide to working out the amount required, one litreof mixed brine is used per metre of collector hose (thisapplies to PEM-hose 40 x 2.4 PN 6.3).
Details of the antifreeze used must be shown on thelevel vessel.
The collector circuit may be connected from the left orfrom the right. The lower side panels are swappedover to suit the chosen connection option. The enclo-sed connecting pipes for the brine, are secured usingthe clips in the punched tabs that are folded down onthe side in question.
Shut-off valves should be installed as close to theheat pump as possible. Fit the supplied particle filteron the incoming pipe.
In the case of connection to an open groundwatersystem, an intermediate frost-protected circuit mustbe provided, because of the risk of dirt and freezing inthe evaporator. This requires an additional heatexchanger.
Pipe installation must be carried out in accordancewith current norms and directives. The heat pump canonly operate up to a return temperature of about 50 °Cand an outgoing temperature of about 60 °C from theheat pump. Since the FIGHTER 1210 is not fitted withshut-off valves, these must be fitted outside of theheat pump to make future servicing easier.
During assembly of FLM 30 the pipes for the heatmedium and water heater and possibly hot water cir-culation are diected backwards. The distance bet-ween FIGHTER 1210 and the wall ought to be 50 mm.
General
Pipe connections for the heat medium side are madeat the top. All required safety devices, shut-off valves(as close to the heat pump as possible), and particlefilter (supplied) are fitted.
When connecting to a system with thermostats on allradiators, a relief valve must be fitted, or some of thethermostats must be removed to ensure sufficientflow.
Pipe connections (heating medium)
Pipe connections (collector)
Pipe connections
FIGHTER 1210
For Home Owners
16
SF
Köldb in
Köldb ut
EXP
P
SF
Cirk.pump
Värmepump
Varmvatten
Tillsatsvärme
Larm
Kontrollera att vatten finns i pan-nan innan den in-kopplas.
1
R
0
NK
AV
SÄV
Varmvatten-cirkulation
The water heater must be fitted with the necessaryvalve equipment.The heat pump should be supplemented with an elec-tric water heater if a bubble pool or other significantconsumer of hot water is installed.
The installation can be supplemented with the exhaustair module FLM 30 to provide ventilation recovery.
To avoid condensation, all pipes and other cold surfa-ces must be insolated with diffusion-proof material.
Pipe connections (water heater)
NK Level vesselSF Particle filter
SÄV Safety valveAV Shut-off valve
EXP Expansion vessel
Fan convector
Inlet to heat pump
Outlet from heat pump
Rock-/soil collector
EXP
P
The equipment can be supplemented with a fan coilunit to make the connection of ambient cold possible.
To avoid condensation, all pipes and other cold surfa-ces must be insolated with diffusion-proof material.
Where the cooling demand is high, fan coil units witha drip dish and drain connection are needed.
Free cooling
Ventilation recovery
Brine in
Brine out
FIGHTER 1210
FLM 30
Exhaust airØ 160
Extract airØ 160
Cirk.pump
Värmepump
Varmvatten
Tillsatsvärme
Larm
Kontrollera att vatten finns i pan-nan innan den in-kopplas.
1
R
0
Hot watercirculation
Brine In
Brine Out
Brine InBrine Out
Pipe connections 17For the Installer
FIGHTER 1210
00
mvpkPa
250 500 7500
l/h1000
2
4
8
20
80
40
Tryckfall
Flöde
1250 1500 1750
60 6
00
mvpkPa
250 500 7500
l/h1000
2
4
8
20
80
40
Tryckfall
Flöde
1250 1500 175025002250 250022502000 2000
60 6
00
mvpkPa
250 500 7500
l/h1000
2
4
8
20
80
40
Tryckfall
Flöde
1250 1500 1750
60 6
00
mvpkPa
250 500 7500
l/h1000
2
4
8
20
80
40
Tryckfall
Flöde
1250 1500 175025002250 250022502000 2000
60 6
FIGHTER 1215 4 kW
FIGHTER 1215 7 kW FIGHTER 1215 8,5 kW
FIGHTER 1215 10 kW
FIGHTER 1215 5 kW
00
mvpkPa
250 500 7500
l/h1000
2
4
8
20
80
40
Tryckfall
Flöde
1250 1500 1750 250022502000
60 6
100 10
Pump capacity diagrams, heating medium side
Available pressure setup
FIGHTER 1210 4 kW FIGHTER 1210 5 kW
FIGHTER 1210 7 kW FIGHTER 1210 8.5 kW
FIGHTER 1210 10 kWPressure drop
Pressure drop Pressure drop
Pressure dropPressure drop
Flow Flow
Flow Flow
Flow
Electrical connections18
FIGHTER 1210
For the Installer
■ If an insulation test is to be carried out in the buil-ding, disconnect the heat pump.
■ The heat pump is connected on terminal (9) to 400V 3-phase, neutral + earth via a distribution boardwith fuses.
■ FIGHTER 1210 does not include an isolator switchon the incoming electrical supply. An isolatorswitch should therefore be installed before theinstallation.
■ A heat pump must not be connected without thepermission of the electricity supplier and must beconnected under the supervision of a qualifiedelectrician.
■ If a miniature circuit breaker is used this shouldhave motor characteristic “D” (compressor opera-tion). For fuse ratings, see Technical data.
■ Disconnection of the immersion heater is achievedby connecting an external potential-free make (NO)contact to terminal (30) pos 1. and 2.
■ Disconnection of the immersion heater, with thepossibility to use Extra hot water while the power isdisconnected is achieved by connecting an exter-nal potential-free make (NO) contact to terminal(30) pos 1. and 3.
■ Disconnection of the immersion heater by step isachieved by connecting the accessory “Load moni-tor EBV 200” to terminal (30) pos 1. and 2.
■ Connections pos 2 and 3 should be connectedtogether to block the compressor as well as thesupplement. Connection pos 1 is then connected toeach side of the contact that controls the blocking.
FIGHTER 1210 has an immersion heater which isconnected for 6 kW on delivery (FIGHTER 1210–4, 3 kW immersion heater output). The output of theimmersion heater as supplied is 6 kW (FIGHTER1210–4, 3 kW) but it can be rewired to give 9 kW. See“Wiring diagram”
■ Install the outdoor sensor in the shade on a wallfacing north or north-west, so it is not exposed tothe morning sun. The sensor is connected with twowires to positions “7” and “8” on the relay board’s(29) terminal (30). The minimum wire cross sectionshould be 0.4 mm2 up to lengths of 50 metres, forexample EKKX or LiYY. Relay board is placedbehind the control computer.
■ If the outdoor sensor wire runs close to power wire,shielded wire must be used.
Connecting Power rating as set at the factory
Connecting the outdoor sensor
External control of the immersion heater
NOTE! Electrical installation and service
must be carried out under thesupervision of a qualified electrician.The electrical installation and wiringmust conform to current regulations.
SE
LV+
BA
–B
+–
ART
GEX
T.EL.
UG
15
12
34
56
78
30+2
0-2
1
R
0
VB-Fram 49 (50) °CVarmvatten 51°C
30
9
Commissioning and adjusting 19
FIGHTER 1210
For the Installer
The heating medium system is filled with water untilthe required pressure is reached and then vented.
To fill the collector system, mix about 30% antifreezewith water in an open container and connect with fillerpump and hoses as illustrated. Close the valve on themain pipe between the service connections and fillthrough the connection under the level vessel (NK)(which has been removed) until the fluid emerges fromthe return hose. Then make the following settings onthe control panel.■ Set the switch (8) to 1.■ Go to the Brine-pump menu, Add-drift in the ser-
vice menu. Set Brine-pump to 1 and press Opera-ting mode. Set Add-drift to 1 an press Operatingmode.
Before starting up the system, check that the heating,collector and hot water circuits are full and throughlyvented. Check the pipe systems for leaks.
Filling the heating- /heating medium system
Filling and venting the collector system
Preparations
AVT DrainingSÄV Safety valveNK Level vesselSF Particle filter
BK Rock collectorJK Ground collectorVV Hot water
Operating mode button
Evaporator
Brine pump
CompressorCondenser
Heating waterpump
Expansion valveCooling unit
Immersion heater
3 way valve
Double jacket
Water heater
Heating waterflow
Heating waterreturn
Hot watercirculation
AVT
Closed
BK / JK
NK
SÄV
SF
Brine in
Brine out
The heat pump cannot start as the operating mode“EB” (electric boiler mode only) is selected. The brinepump is now operational together with the filling pump.The fluid can circulate via the mixing vessel until fluid,without air, returns to the return hose. Now stop thebrine pump by setting Brine-pump to “0”. Stop the filling pump and clean the particle filter. Thenstart the filling pump again. Open the valve on themain pipe between the service branches while the fil-ling pump is still operational (to release the air bet-ween the branches). Now close the valve by the returnhose. Pressurise the system (to max 3 bar) with the fil-ler pump. Close the valve where the level vessel is fit-ted and stop the filler pump.Remove the filler hoses and refit the level vessel. Fillthe vessel about three-quarters full with the fluid. Nowshut the filling plug and open the valve under the ves-sel. Reset normal mode by setting EB to “0”.
Air is initially released from the hot water and ventingmay be necessary. If bubbling sounds can be heardfrom the heat pump, the entire system requires furtherventing. When the system is stable (correct pressureand all air eliminated) the automatic heating controlsystem can be set as required.
Check the fluid level in the level vessel (85). If thelevel has dropped, close the valve under the vessel.You can then fill through the connection at the top ofthe vessel. After filling, open the valve again. To raise the pressure, close the valve on the incomingmain pipe when the brine pump is running and thelevel vessel is open, so that water is drawn in from thevessel.
The siphon principle is used to empty the water hea-ter. This can be done either via the drain valve on theincoming cold water pipe or by inserting a hose intothe cold water connection.
Readjustment, brine side
Emptying the water heater
Commissioning and adjustingFor the Installer
20
FIGHTER 1210
■ Set the switch (8) to 1.■ Check the settings on the control computer, and
adjust so there is a heating requirement.■ Go to the Brine-pump menu, Add-drift in the ser-
vice menu. Set the Brine-pump to position 1 andpress Operating mode. Set Add-drift in position 1and press Operating mode.
■ Ensure the brine and heating medium pumps arevented and help the pumps to start if necessary.
■ Go to the Brine In, Brine Out menu. Ensure thatthe temperature corresponds with the ground/rocktemperature, which indicates the brine flow.
■ Go to the Brine-pump menu, Add-drift in the ser-vice menu. Set Add-drift to 0, the compressorstarts, and go to the Brine In, Brine Out menu.Read the brine fluid temperatures. The differencebetween these two temperatures should be 2 –5°C when the system has come into balance. Ahigh difference indicates a low brine flow. A low dif-ference indicates a high brine flow.
■ Particular attention should be given to the level inthe collector system a few days after start-up.Some topping-up may be necessary.
■ Read the heat medium temperatures WW-out andWW-in. The difference between these two tempe-ratures, with floating condensing, should be 5 –10°C when the heat pump heats the heating waterwithout additional heat. A high difference coulddepend on a low heat medium flow.
■ Fill in the commissioning report on page 2.■ Set the control computer to suit the needs of the
building.
Readjustment, heating medium side
Start-up and inspection
Setting the automatic heating control system 21For the Installer
FIGHTER 1210
FIGHTER 1210 is equipped with an outdoor tempera-ture controlled automatic heating system. This meansthe heat medium flow temperature is regulated in rela-tion to the current outdoor temperature.
The relationship between outdoor temperature andflow temperature is set using the control computer;see “Control” “Setting the heating”.
The diagram is based on the dimensioned outdoortemperature in the area and the dimensioned heatmedium flow temperature of the heating system.When these two values meet, the heating control’scurve slope can be read.
The Increase/decrease heat knob (heating curve off-set) is then set. A suitable value for floor heating is -1and for radiator systems -2.
30
40
50
60
70°C
FR
AM
LE
DN
ING
ST
EM
PE
RA
TU
R
- 40 °C
UTETEMPERATUR
- 10010 - 20 - 30
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
KURVLUTNING
- 5
+ 5
PARALLELLFÖRFLYTTNING
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
- 40 °C
UTETEMPERATUR
- 10010
- 5
+ 5
30
40
50
60
70°C
FR
AM
LE
DN
ING
ST
EM
PE
RA
TU
R
- 20 - 30
PARALLELLFÖRFLYTTNING
KURVLUTNING
1514 13 12 11 108
7
6
5
4
3
2
1
- 40 °C
UTETEMPERATUR
- 10010
- 5
+ 5
30
40
50
60
70°C
FR
AM
LE
DN
ING
ST
EM
PE
RA
TU
R
- 20 - 30
PARALLELLFÖRFLYTTNING
9
KURVLUTNING
Heating curve offset 0
Heating curve offset -2Setting with diagrams
Heating curve offset +2
HEATING CURVE
HEATING CURVE
HEATING CURVE
HEATING CURVEOFFSET
HEATING CURVEOFFSET
HEATING CURVEOFFSET
HEA
T M
EDIU
M F
LOW
H
EAT
MED
IUM
FLO
W
HEA
T M
EDIU
M F
LOW
OUTDOOR TEMPERATURE
OUTDOOR TEMPERATURE
OUTDOOR TEMPERATURE
Component locations22
FIGHTER 1210
For the Installer
LEK
65
17
27
7
42
48
4118
2833
+20
-2
1
R
0
VB-Fram 49 (50) °CVarmvatten 51 °C
88
75 38
!
LEK
11*
12*
69
39
68
13
14*
26
* Only FIGHTER 1210 4 kW** Not FIGHTER 1210 4 kW and 5 kW
LEK
69
39
68
13
97**
26
!
Component locations 23For the Installer
FIGHTER 1210
1
R
0
+2-2
VL-Temp 47(52) °CWW-Temp 48°C
LEK
!
3
106
67
25
8
9
34
29
30
3137
!
LEK
58
75 7295
73
70
100
71
74
LEK
16
76
87
24
35
96
19
4 86 9477
717089
5
Wiring diagram 4 kW model
FIGHTER 1210
For the Installer
24
10R
T
P
25
4
3
2
1
6
7
8
9
10
12
13
14
15
16
17
18
19
20
21
22
23
24
26
11
5
Re 1
Re 2
Re 3
Re 4
Re 5
Re 6
Re 7
Re 8
Re 9
230
V
12 V
27
12
11 14
8
6
19 16 35
10
24
67 68
26
33
13
9
253
69
5 63 41 2
5 6 7 8 9 103 41 2L2 L3N L1
T
M
29
12345678
weißer Anschluss3 x 1 kW
roter Anschluss3 x 2 kW
2A
5B
1A
4B
3A
6B
34
15
30
41
2888
8994
8687
3 kW
P
31
37
5 63 41 2
Red connection3 x 2 kW
White connection3 x 1 kW
Wiring diagram, 5 – 10 kW model 25For the Installer
FIGHTER 1210
10R
T
P
25
4321
6789
10
12131415161718192021222324
26
11
5
Re 1
Re 2
Re 3
Re 4
Re 5
Re 6
Re 7
Re 8
Re 9
230
V
12 V
27
34
15
30
4128
88
8994
8687
8
6
19 16 35
10
24
67 68
26
33
13
9
253
69
5 63 41 2
5 6 7 8 9 103 41 2L2 L3N L1
T
M
29
12345678
roter Anschluss 3 x 2 kW
weißer Anschluss 3 x 1 kW
2A
5B
1A
4B
3A
6B
6 kW
P
31
37
5 63 41 2
97*
10
24
67
9 kW
weißer Anschluss 3 x 1 kW
roter Anschluss 3 x 2 kW
Red connection3 x 2 kW
Red connection3 x 2 kW
Whiteconnection3 x 1 kW
Whiteconnection3 x 1 kW
* Not FIGHTER 1210, 5 kW
Circuit diagram
FIGHTER 1210
For the Installer
26
P
T
T
X9L1
X9L2
X9L3
X2911A
3A2A
4B T5AH
6B5B
X292
X2914
X131
X132
Re3
Re9
Re8
Re6
Re7
Re5
Re4
X925
X2917
X2911
X2913
X2916
X2915
X2919
X64
X61 X13
9
X1310
X137
X135
X138
X136
X63
1
35
2
46
1
35
2
46
1
35
2
46
C
SR
1
35
2
46
1
35
2
46
1
35
2 CSR
1
2
546
X2922
X2923 X29
18
X2920
X22 L3
X22 L1X22 L2
X2912
X22N
X134
X2921
X62
X293
X9N PE
X2924
X133
833
3
26
68
68
68 26
69
69
68 26 69
35
67
10
19
16
27
27
12
11 14
2467
10
25
5 – 15 kW 3-phasig
4 kW 1-phasig
6 kW
3 kW
10R
97*
5 - 15 kW 3-phase
4 kW 1-phase
* Not FIGHTER 1210, 5 kW
List of components 27
FIGHTER 1210
For the Installer
3 Operating thermostat, spare mode
4 Collector connection, brine in
5 Collector connection, brine out
6 Terminal block, pumps, reversing valve
7 Service connection, high pressure
8 Switch, 1 – 0 – R
9 Terminal block, incoming electric power
10 Contactor, immersion heater step 1
11 * Starting capacitor, compressor
12 * Start relay
13 Terminal block, compressor control
14 * Operating capacitor, compressor
15 Outdoor sensor
16 Heating medium pump
17 Evaporator
18 Condenser
19 3 way valve, heating system/water heater
24 Immersion heater 9 kW, supplied connected 6 kW (1210-4, 3 kW)
25 Overheating protection, immersion heater
26 Motor protection
27 Compressor
28 Operating pressostat
29 Relay board with power supply unit
30 Terminal block, relay board
31 Terminal block
33 High pressure pressostat
34 Computer with display, including sensor
35 Brine pump
37 External switch for the brine, accessory
38 Anode (enamel)
39 Reset, motor protection
41 Low pressure pressostat
42 Service connection, low pressure
48 Expansion valve
52 Safety valve, collector side
58 Cover (enamel)
63 Particle filter (KB) R25 female.
65 Drying filter
67 Contactor, electric unit step 2
68 Contactor, compressor start
69 Contactor, compressor operation
70 Connection, heat medium flow ø 22 mm o.d.
71 Connection, heat medium return ø 22 mm o.d.
72 Hot water circulation (VVC)
Stainless steel: Ø 15 mm o.d.
Enamel: G 20
73 Cold water
Stainless steel: Ø 22 mm o.d.
Enamel: G 20
74 Hot water
Stainless steel: Ø 22 mm o.d.
Enamel: G 20
75 Venting valve, double jacket
76 Drainage for heating system
77 Venting valve, collector system
81 Particle filter (WW) R20 female.
85 Level vessel, connection to system, R25 male
86 Temperature sensor, brine In, 87 Temperature sensor, brine Out, 88 Temperature sensor, “hot water”
89 Temperature sensor, “WW-out”, heat medium flow
94 Temperature sensor, “WW-in”, heat medium return
95 Type plate/serial number
96 Type plate, cooling unit
97** Starting current limiter
100 Wire gland, power supply
* Only 4 kW FIGHTER 1210** Not FIGHTER 1210, 4 kW and 5 kW
Dimensions28
FIGHTER 1210
For the Installer
Dimensions and setting-out coordinates
598
179
525
525
30
399
454
144
321
46
99
242
288
625
30 –
50
630
1745
50
200
132
47
5 5
54
4
5
4
5
+20
-2
1
R
0
HM flow 49 (50) °CHot water 51 °C
A free area should be left tothe right of the heat pump forservice work.When FLM 30 is fitted onFIGHTER 1210 the distanceto the wall should be 50 mm.
Technical data 29For the Installer
FIGHTER 1210
* Compressor output only. ** Refers to brine flow temperature / heating medium flow temperature, in accordance with EN 255.*** With feet and connections dismantled the height is 1890 mm.
Size 4 5 7 8,5 10
Operating voltage 3 x 400 V + N + PE 50 Hz
Max operating current, compressor(A) 8.0 (1-phase) 3,6 5,5 6,7 7,9
Fuse (incl. imm. heater 9 kW) (A) 25 20 20 25 25
Output, heat medium pump (W) 75 75 75 75 170
Connection heating medium, o.d. ø (mm) 22
Max pressure in water heater (MPa) 0.9 (9 bar)
Refrigerant quantity (R407C) (kg) 1,4 1,7 2,2 2,4 2,4
Pressure drop, evaporator (kPa) 22 21 23 23 19
Max pressure brine system (bar) 3
Heating medium flow (l/s) 0,10 0,13 0,18 0,22 0,26
Max temp. (heat medium flow/return line) (°C) 60/50
IP 21
Volume, water heater (litres) 160
Starting current (A) 42 30 30 30 30
Fuse (incl. imm. heater 6 kW) (A) 16 16 16 20 20
Output, brine pump (W) 130 130 170 170 250
Connection collector fluid o.d. Ø (mm) 28
Volume, double jacket (litres) 45
Max pressure in double jacket volume (MPa) 0.25 (2.5 bar)
Brine flow (l/s) 0,25 0,35 0,48 0,58 0,65
Available pressure, brine system (kPa) 45 40 58 53 70
Operating temperature brine system (°C) -10 – +20
Operating pressostat (bar) 24
Cut-out value pressostat HP (bar) 27
Difference pressostat HP (bar) -7
Difference pressostat LP (bar) +1,5
Cut-out value pressostat LP (bar) 1,5
Net weight (kg) 280 285 300 305 310
Output/Input power * at 0/35 °C ** (kW) 4.8/1.0 6,0/1,3 8,8/1,9 10,3/2,2 11,7/2,5Output/Input power * at 0/50 °C ** (kW) 3.9/1.2 4,8/1,5 7,1/2,2 8,5/2,5 9,9/2,9
Required headroom (mm) 1950 ***
Pressure drop, condenser (kPa) 2,7 2,6 3,4 3,2 4,4
Enclosed kit/Accessories
FIGHTER 1210
30For the Installer
Accessories
LE
K
21
3
4
5678 9
25 A
2525
24 6
810 A
TillBegränsningStröm
Marginal
Effektvakt 100
5V
Room sensor RG 20Part no 418 345
LEK
LEK
LEK
Load monitor EBV 200Part no 418 346
LEK
Connecting pipes, collector,with insulation
LEK
NIBE AB
Utetemperatur givare
Outdoor temperature sensor
Aussentemperatur fühler
Artikel 018764
Outdoor sensorParticle filters
ClipsConex connectors
Enclosed kit
6315
Level vessel with safety valve
LEK
85
52
4
5
LEK
81
LEK
Exhaust air module FLM 30Part no 089 268
Room unit RT 20Part no 418 645
Impressed current anodePart no 089 308
Level switch NV 10Part no 089 315
LEK
Dealing with malfunctions 31
FIGHTER 1210
For the Installer
NOTE! The
product’s serial numbershould always be stated with all
correspondence with NIBE.689_ _ _ _ _ _ _ _ _ _ _
Cause: Incorrect setting of the Curve slope and/orIncrease/decrease heat.
Action: Adjust the setting.
Cause: Large amounts of hot water were used.
Action: Wait until the water heater reheats.
Cause: Compressor and/or immersion heater does not heat up.
Action: Check and replace blown circuit and mainfuses.
Cause: Too low start temperature setting on thecontrol computer (34).
Action: Adjust the start temperature setting.
Cause: Possible earth circuit-breaker tripped.
Action: Reset the earth circuit-breaker, if the earthcircuit-breaker trips repeatedly, call anelectrician.
Cause: Compressor and immersion heater do not heat.
Action: Check and replace blown circuit and mainfuses.
Cause: The compressor does not run because of atoo low set value on the control curve.
Action: Check and possibly raise Increase/decreaseheat (knob on the front panel) or Curveslope.
Cause: The compressor standstills due to theinternal overheating protection tripping.
Action: Automatic resetting after cooling for a fewhours.
Cause: Possible earth circuit-breaker tripped.Action: Reset the earth circuit-breaker, if the earth
circuit-breaker trips repeatedly, call anelectrician.
Low hot water temperature or no hot water
In the event of malfunction or operating disturbances first check the points below:
High room temperature
Low room temperature
If the operating disturbance cannot be rectified by means of the above an installation engineer should be called.
Dealing with malfunctions
FIGHTER 1210
For the Installer
32
The alarm lamp flashes and the text“HP/MSalarm” is displayedCause: Bad circulation in the heating medium
circuit.Action: Check the heating medium pump (16).
Possibly open the radiator thermostats.Check that the particle filter (63) is notclogged.
Once the fault cause has been set switch (8) to “0”and then to “1”.If the alarm lamp still flashes the motor cut-out hastripped due to the following causes.
Cause: Dropped phase or temporary main power disturbance.
Action: Check the fuses.
Cause: Overloaded compressor (27)Action: Call qualified service personnel.
Cause: Mechanical fault on the compressor (27)Action: Call qualified service personnel.
Cause: Defective motor protection (26).Action: Call qualified service personnel.
Cause: Fuse on the relay board has blown.Action: Replace the fuse.
The alarm light flashes and the text:“LPalarm” is displayedCause: Start up of cold installationAction: Use Electric boiler mode.
Cause: Bad circulation in collector system due toinferior venting/low pressure or ice (if icehas formed the brine pump (35) will bewarm).
Action: Vent and top up the fluid. Wait a few hours.
Cause: Brine pump (35) not running.Action: Check the brine pump.
Cause: Lack of refrigerant or other fault in the cooling unit.
Action: Call qualified service personnel.
Cause: Iced evaporator due to too low antifreezeconcentration
Action: Check the freezing point of the brine.
After taking action, check that the difference on thedisplay between Brine In and Brine Out is 2 – 5 °Cwhen the compressor is running. (See ControlInformation available on the display, menu 4).Once the fault cause has been, set switch (8) to “0”and then to “1”.In the event of a temperature sensor error, this isindicated on the display, e.g. “out error”NOTE!
The fault status must not berepeatedly reset, as there is a risk
of overheating the motorwindings.
Indications
Dealing with malfunctions 33For the Installer
FIGHTER 1210
Close the shut-off valves in heating medium system.Now open the drain valve (76). A small amount ofwater runs out, however, to fully empty the heatingmedium side requires the connector that joins the hea-ting medium side and the connection on the heatpump WW-out to be loosened a little to allow air toenter so the remaining water can run out. When theheating medium is empty the requisite service can becarried out.
When replacing the brine pump (35) or drive side orwhen cleaning the pump, the shut-off valves in theheat transfer system should be closed. The hose bet-ween the evaporator’s upper section and the brinepump is loosened on the evaporator. The loose hoseend can now be bent down and emptied in a smallbowl. Now loosen the connection on Brine In a little toallow air to enter so the heat pump’s collector side isemptied completely. When the circuit is empty therequisite service can be carried out.
Draining, heat medium side Draining, collector side
■ Shut down FIGHTER 1210 by the switch (8) to “0”.■ Open the front cover.■ Loosen the venting screw with a screwdriver. Hold
a cloth around the screwdriver blade as a certainamount of water may run out.
■ Insert a screwdriver and turn the pump rotor.■ Tighten the venting screw.■ Start FIGHTER 1210 and check whether the circu-
lation pump runs.It is usually easier to start the circulation pump withFIGHTER 1210 running, switch (8) set to “1”. If hel-ping the circulation pump to start is performed withFIGHTER 1210 running, be prepared for the screwdri-ver to jerk when the pump starts.
Helping the circulation pump to start
Luftningsskruv
16
LE
K
GR
UN
DFO
SType
UP
S25 -
60
130
P/N
:59526447
230V
-
HE
JS
AN
PC
;0017N
IBD
K50H
z
IP 44
TF
110
Cla
ss H
Max. 1
0bar
2.5
uF
45
0.2
065
0.3
090
0.4
0
1m(A
)P,
(W)
Venting screw
Dealing with malfunctions
FIGHTER 1210
For the Installer
34
Check the anode within a year. And then regularly in relation to its use. When the anode is new it has a diameter of approx. 34 mm. When this has decreased (in its most used area) to under 10 mm theanode is consumed and must be replaced.
If anode consumption has not occurred after a fewyears, this may be due to inferior conductivity in thewater and a water analysis is recommended.
Checking the sacrificial anode (enamel)
There is a sacrificial anode mounted on a flange at thetop of the hot water heater. Anode replacement takesplace as follows:■ Remove the heat pump's circuit fuses in the distribu-
tion cabinet.■ Empty the hot water heater, see the chapter “Com-
missioning and adjustment” – “Emptying the waterheater”
■ Dismantle the cover plate (58) as illustrated.■ Dismantle the flange.■ Replace the anode mounted on the flange.■ Re-assemble in the reverse order.
Replacing the sacrificial anode (enamel)
NOTE! Protect electrical and electroniccomponent parts from moisture!
LEK
58
35
FIGHTER 1210
36
FIGHTER 1210
NIBE ABSWEDEN
R
Tel: +46 - (0)433 - 73 000Fax: +46 - (0)433 - 73 190www.nibe.com
Box 14Järnvägsgatan 40SE-285 21 MARKARYD