Page 1 of 27 © Copyright 2003 Manual No.: 2100-416D Supersedes: 2100-416C File: Vol II Tab 14 Date: 02-10-06 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. QC SERIES CHILLED WATER UNIT INSTALLATION INSTRUCTIONS Model: QC501 MIS-1554

Transcript of QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Page 1: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 1 of 27

© Copyright 2003

Manual No.: 2100-416DSupersedes: 2100-416CFile: Vol II Tab 14Date: 02-10-06

Bard Manufacturing CompanyBryan, Ohio 43506Since 1914...Moving ahead, just as planned.

QC SERIESCHILLED WATER UNITINSTALLATION

INSTRUCTIONSModel: QC501

MIS-1554

Page 2: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 2 of 27

CONTENTS

Getting Other Information and PublicationsFor more information, contact these publishers: ...... 3

QC General InformationQC Model Nomenclature ......................................... 4Shipping Damage .................................................... 7Unit Removal From Skid .......................................... 7Handling Unit After Removal From Skid .................. 7Removal of Wall Bracket from Shipping Location ... 8General .................................................................... 8Minimum Installation Height ..................................... 8Duct Work ............................................................... 11Filters ...................................................................... 11Condensate Drain .................................................. 12Mist Eliminator Service .......................................... 13

FiguresFigure 1 Unit Dimensions ..................................... 6Figure 2 Removal of Unit From Skid .................... 7Figure 3 Proper Handling of Unit After Removal

from Skid ................................................ 8Figure 4 Installation of Unit w/Wall Sleeve .......... 9Figure 5 Installation With Free Blow Plenum ..... 10Figure 6 Ducted Application ............................... 10Figure 7 Supply Duct Connections ..................... 11Figure 8 Filter Location ....................................... 11Figure 9A Side Drain (Side View) ......................... 12Figure 9B Optional Rear Drain ............................. 12Figure 9C Rear Drain (Top View) .......................... 12Figure 10 Fresh Air Damper Removal .................. 14Figure 11 Removal of QTEC ERV ......................... 15Figure 12 Remove Locking Screws from Wheels 16Figure 13 Unit Mounting Without Wall Sleeve ..... 17Figure 14 Component Location ............................ 18Figure 15 Low Voltage Wire Harness Plug .......... 20Figure 16 Remote Thermostat Wiring "X" Option 21Figure 17 Remote Thermostat Wiring "D" Option 22Figure 18 Internal 2-Way Valve Piping ................. 26Figure 19 Internal 3-Way Valve Piping ................. 27

TablesTable 1 Factory Built-In Electric Heat ................... 4Table 2 Electrical Specifications ........................... 4Table 2A Cooling Performance Chart ...................... 5Table 3 Operating Voltage Range ....................... 19Table 4 Wall Thermostats and Subbase

Combinations ......................................... 19Table 5 Indoor Blower Performance ................... 23

Installation InstructionsMounting the Unit .................................................. 16Wiring – Main Power ............................................. 19Wiring – Low Voltage Wiring ................................. 19General Information ............................................... 19Fluid Connections .................................................. 19Low Voltage Connections ...................................... 20

Start UpOptional CFM ........................................................ 23Important Installer Note ......................................... 23Service Hints ......................................................... 23Sequence of Operation .......................................... 23

Troubleshooting ECM Blower Motors ............. 24-25

Page 3: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 3 of 27

GETTING OTHER INFORMATION AND PUBLICATIONS

These publications can help you install the airconditioner or heat pump. You can usually find these atyour local library or purchase them directly from thepublisher. Be sure to consult current edition of eachstandard.

National Electrical Code ......................ANSI/NFPA 70

Standard for the Installation ..............ANSI/NFPA 90Aof Air Conditioning andVentilating Systems

Standard for Warm Air ...................... ANSI/NFPA 90BHeating and AirConditioning Systems

Load Calculation for Residential ...... ACCA Manual JWinter and SummerAir Conditioning

Duct Design for Residential ............. ACCA Manual DWinter and Summer Air Conditioningand Equipment Selection

Closed-Loop/Ground Source Heat Pump ........ IGSHPASystems Installation Guide

Grouting Procedures for Ground-Source ........ IGSHPAHeat Pump Systems

Soil and Rock Classification for the Design ... IGSHPAof Ground-Coupled Heat Pump Systems

Ground Source Installation Standards ............. IGSHPA

Closed-Loop Geothermal Systems – Slinky ... IGSHPAInstallation Guide

FOR MORE INFORMATION, CONTACTTHESE PUBLISHERS:

ACCA Air Conditioning Contractors of America1712 New Hampshire AvenueWashington, DC 20009Telephone: (202) 483-9370Fax: (202) 234-4721

ANSI American National Standards Institute11 West Street, 13th FloorNew York, NY 10036Telephone: (212) 642-4900Fax: (212) 302-1286

ASHRAE American Society of Heating Refrigerating,and Air Conditioning Engineers, Inc.1791 Tullie Circle, N.E.Atlanta, GA 30329-2305Telephone: (404) 636-8400Fax: (404) 321-5478

NFPA National Fire Protection AssociationBatterymarch ParkP.O. Box 9101Quincy, MA 02269-9901Telephone: (800) 344-3555Fax: (617) 984-7057

IGSHPA International Ground SourceHeat Pump Association490 Cordell SouthStillwater, OK 74078-8018

Page 4: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 4 of 27

QC SERIES WATER SOURCE GENERAL INFORMATIONQC MODEL NOMENCLATURE

QC 50 1 – A 10 X X X X X X

TABLE 1FACTORY BUILT-IN ELECTRIC HEAT TABLE

sledoM A-105CQ

1-V042 1-V802

WK HUTB HUTB

0.5 083,61 092,21

0.01 076,23 075,42

0.51 051,94 068,63

1Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.2Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code

(latest revision), article 310 for power conductor sizing.CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay

special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.

TABLE 2ELECTRICAL SPECIFICATIONS

tiucriCelgniS tiucriClauD

detaR&stloVsesahP

.oNdleiF

rewoPstiucriC

3

muminiMtiucriCyticapmA

1

mumixaMlanretxE

roesuFtiucriCrekaerB

2

dleiFrewoP

eriWeziS

2

dnuorGeriWeziS

3

muminiMtiucriCyticapmA

1mumixaMlanretxE

roesuFtiucriCrekaerB

2

dleiFrewoPeziSeriW

2

dnuorGeziSeriW

sledoMTKC

ATKC

BTKC

ATKC

BTKC

ATKC

BTKC

ATKC

B

Z0A-105CQ50A-01A-51A-

1-802/032

111

2ro1

7338538

51530609

41864

410101

8

–––05

–––33

–––05

–––04

–––8

–––8

–––01

–––01

Z0K-105CQ 1-511 1 01 51 41 41 – – – – – – – –

Ventilation OptionB - Blank Off Plate (no ventilation)X - Barometric Fresh Air Damper (no exhaust)V - Commercial Ventilator (w/Exhaust)P - Commercial Ventilator (w/Exhaust)

Motorized, Power ReturnR - Energy Recovery Ventilator (w/Exhaust) - 230/208-60-1 versions only

KW0Z - 0KW05 - 5 KW10 - 10KW15 - 15KW (Note 1)

Volts & PhaseA - 230/208-60-1K - 115-60-1

RevisionCapacity50 - 4 ton

Model NumberQC - QTec™ Model

Filter OptionsX - 1 Inch Fiberglass

(Standard)F - 2 Inch FiberglassP - 2 Inch pleated

ColorV - Platinum w/SlateFront (vinyl)4 - Gray Paint

Climate ControlX - NoneD - Electronic/prog/man/auto

Internal ControlsX - None

Valve Options4 - 2-way valve5 - 3-way valve

NOTE 1: Electric heat available for -A models only

Page 5: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 5 of 27

TABLE 2ACOOLING PERFORMANCE CHART

MPG TWE MFC

)0001(yticapaCHUTB )0001(yticapaCHUTB lioCretaWporDerusserP1egatS 2dna1egatS

latoT elbisneS tnetaL latoT elbisneS tnetaL GISP .dH.tF

6

24 0001

1.51 5.01 6.4 5.83 3.52 2.31 9.1 4.4

8 4.61 1.11 3.5 5.14 8.62 7.41 3.3 5.7

01 4.71 7.11 7.5 2.34 4.72 8.51 9.4 3.11

6

44 0001

9.31 0.01 9.3 8.53 2.42 6.11 9.1 4.4

8 1.51 6.01 5.4 4.83 4.52 0.31 3.3 5.7

01 0.61 1.11 9.4 0.04 0.62 0.41 9.4 3.11

6

64 0001

8.21 6.9 2.3 0.33 0.32 0.01 9.1 4.4

8 9.31 1.01 8.3 3.53 0.42 3.11 3.3 5.7

01 7.41 6.01 1.4 9.63 6.42 3.21 9.4 3.11

6

84 0001

6.11 1.9 5.2 3.03 9.12 4.8 9.1 4.4

8 6.21 6.9 0.3 2.23 6.22 6.9 3.3 5.7

01 6.64 0.01 3.3 7.33 2.32 5.01 9.4 3.11

6

24 0021

9.51 5.11 4.4 1.24 0.92 1.31 9.1 4.4

8 4.71 2.21 2.5 0.64 6.03 4.51 3.3 5.7

01 8.81 8.21 0.6 3.94 9.13 4.71 9.4 3.11

6

44 0021

8.41 1.11 7.3 3.93 7.72 6.11 9.1 4.4

8 2.61 7.11 5.4 7.24 2.92 5.31 3.3 5.7

01 4.71 3.21 1.5 6.54 4.03 2.51 9.4 3.11

6

64 0021

6.31 7.01 9.2 4.63 5.62 9.9 9.1 4.4

8 9.41 3.11 6.3 5.93 9.72 6.11 3.3 5.7

01 1.61 7.11 1.1 0.24 0.92 0.31 9.4 3.11

6

84 0021

5.21 3.01 2.2 6.33 2.52 4.8 9.1 4.4

8 7.31 8.01 9.2 2.63 5.62 7.9 3.3 5.7

01 7.41 2.11 5.3 3.83 5.72 8.01 9.4 3.11

Page 6: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 6 of 27

FIG

UR

E 1

UN

IT D

IMEN

SIO

NS

Page 7: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 7 of 27

SHIPPING DAMAGEUpon receipt of equipment, the carton should bechecked for external signs of shipping damage. Theskid must remain attached to the unit until the unit isready for installation. If damage is found, the receivingparty must contact the last carrier immediately,preferably in writing, requesting inspection by thecarrier’s agent.

It is recommended that the unit not be removed fromthe skid with a fork lift.

The shipping brackets on each side of the unit must beremoved and discarded. See Figure 2-A on Page 7. Thereturn air grille panel can be removed to provide a placeto hold the unit. The unit can be slid forward on theskid until the front wheels hang over the edge of theskid. See Figure 2-B. The unit can be tipped forwardand slid down the edge of the skid until the frontwheels touch the ground. See Figure 2-C. The wheelswill not roll. They are shipped from the factory lockedso they will not roll. The back of the skid will have tobe held down to keep it from tipping up. The skid canbe slid out from under the unit. The unit can then beset upright. FIGURE 2

REMOVAL OF UNIT FROM SKID

HOLD SKID DOWN

A SHIPPING BRACKETS B FRONT WHEELS OVER EDGE C FRONT WHEELS ON FLOOR

MIS-1603

The unit will have to be turned sideways and removedfrom the skid to fit through a 36" doorway. If the doorheight allows, the unit can be slid sideways through thedoor.

If the unit can not be slid through the door, then the unitwill have to be put on a cart and tipped down to rollthrough the door. It is recommended that an appliancecart by used with a strap to hold the unit on the cart.The wheels of the unit must be locked. If the wheelswere allowed to roll, the unit could roll off the cart.The blade of the appliance cart should be slid under thewheels of the unit. See Figure 3. The strap of theappliance cart should be placed around the unit andstrapped tightly. Help will be required to tip the unitback onto the cart. The unit can be leaned far enoughback to be rolled through the door. Be careful whensetting the unit back up to keep from damaging the unit.

UNIT REMOVAL FROM SKID

HANDLING UNIT AFTER REMOVAL FROMSKID

WARNINGExercise extreme caution when pushing theunit on the rollers. Handle and push from thelower 1/3 of the unit. Insure that debris is noton the floor where the unit is to be moved onthe rollers. Failure to do so could result in theunit tipping over and causing bodily injuryand/or damage to the unit. WARNING

This unit is heavy and requires more than oneperson to handle and remove from the skid.Check unit wheels to ensure that wheels arelocked before removing from skid. Extremecaution must be taken to prevent injury topersonnel and damage to the unit.

Page 8: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 8 of 27

REMOVAL OF WALL BRACKET FROMSHIPPING LOCATIONThe wall brackets are attached to the back of the unit.Remove and retain the wall brackets for use whenattaching the unit to the wall. In those installationswhere a wall sleeve is required these two wall bracketsare to be discarded. A different style bracket is suppliedwith the sleeve assembly.

GENERALThe equipment covered in this manual is to be installedby trained, experienced service and installationtechnicians.

The unit is designed for use with or without duct work.For use without duct work, Plenum Box QPB** isrecommended.

These instructions explain the recommended method toinstall the water source self-contained unit and theelectrical wiring connections to the unit.

These instructions and any instructions packaged withany separate equipment required to make up the entireair conditioning system should be carefully read beforebeginning the installation. Note particularly “StartProcedure” and any tags and/or labels attached to theequipment.

While these instructions are intended as a generalrecommended guide, they do not supersede any nationaland/or local codes in any way. Authorities havingjurisdiction should be consulted before the installationis made. See Page 3 for information on codes andstandards.

Size of unit for a proposed installation should be basedon heat loss calculation made according to methods ofAir Conditioning Contractors of America (ACCA). Theair duct should be installed in accordance with theStandards of the National Fire Protection Systems ofOther Than Residence Type, NFPA No. 90A, andResidence Type Warm Air Heating and AirConditioning Systems, NFPA No. 90B. Where localregulations are at a variance with instructions, installershould adhere to local codes.

MINIMUM INSTALLATION HEIGHTThe minimum installation height of the unit with a FreeBlow Plenum is 8 ft. 6 in. This provides enoughclearance for the plenum to be removed. See Figure 5.

The minimum installation height for ductedapplications is 8 ft. 4½ in. This provides enoughclearance to install the duct work. See Figure 6.

FIGURE 3PROPER HANDLING OF UNITAFTER REMOVAL FROM SKID

QTEC UNIT(RIGHT SIDE)

STRAP

APPLIANCECART

Page 9: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 9 of 27

FIGURE 4INSTALLATION OF UNIT THROUGH WALL WITH WALL SLEEVE

MIS-1564

Page 10: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 10 of 27

FIGURE 6DUCTED APPLICATION

MIS-1558

FIGURE 5INSTALLATION WITH FREE BLOW PLENUM

CEILING

FLOOR

DUCT FLANGE

DUCTFIXED CEILINGSUSPENDEDCEILING

FLOOR MIS-1559

20 IN.MINIMUM

Page 11: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 11 of 27

DUCT WORKAny heat pump is more critical of proper operatingcharge and an adequate duct system than a straight airconditioning unit. All duct work must be properly sizedfor the design air flow requirement of the equipment.Air Conditioning Contractors of America (ACCA) is anexcellent guide to proper sizing. All duct work orportions thereof not in the conditioned space should beproperly insulated in order to both conserve energy andprevent condensation or moisture damage. When ductruns through unheated spaces, it should be insulatedwith a minimum of one inch of insulation. Useinsulation with a vapor barrier on the outside of theinsulation. Flexible joints should be used to connect theduct work to the equipment in order to keep the noisetransmission to a minimum.

The QTEC series unit has provision to attach a supply airduct to the top of the unit. Duct connection size is 12inches x 20 inches. The duct work is field supplied andmust be attached in a manner to allow for ease ofremoval when it becomes necessary to slide the unit outfrom the wall for service. See Figure 7 for suggestedattachment method.

NOTE: Unit cabinet, supply air duct and free blowplenum are approved for “0” clearance tocombustible material.

The QTEC series units are designed for use with freereturn (non-ducted) and either free blow with the use ofQPB Plenum Box or a duct supply air system.

The QPB Plenum Box mounts on top of the unit and hasboth vertically and horizontally adjustable louvers onthe front discharge grille.

FIGURE 7SUPPLY DUCT CONNECTIONS

SUPPLY DUCTTO BE FIELDSUPPLIED

ATTACHMENTSCREWS TO BEFIELD SUPPLIED

DUCT FLANGEPROVIDED WITH UNIT

ROOM SIDEOF QC UNIT

MIS-978

When used with a ducted supply, a QCX CabinetExtension can be used to conceal the duct work abovethe unit to the ceiling. This extends 20" above the unitfor a total height above the floor of 10'-7/8". SeeOptional Accessories, Page 20 for the correct CabinetExtension model number. The unit is equipped with avariable speed indoor blower motor which increases inspeed with an increase in duct static pressure. The unitwill therefore deliver proper rated air flow up to theMaximum ESP shown in Table 5. However, for quietoperation of the air system, the duct static should bekept as low as practical, within the guidelines of goodduct design.

FILTERSTwo 1-inch throw away filters are supplied with eachunit. The filters fit into a fixed rack.

The filters are serviced from the inside of the building .To gain access to the filters release the latch on thecircuit breaker door and one 1/4 turn fastener near thebottom of the door. This door is hinged on the left so itwill swing open.

The internal filter brackets are adjustable toaccommodate 2-inch filters. The tabs for the 1-inchfilters must be bent down to allow the 2-inch filters toslide in place.

FIGURE 8FILTER LOCATION

RETURN AIRGRILLE

FILTERS

Page 12: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 12 of 27

CONDENSATE DRAINThe condensate drain hose is routed down from theevaporator drain pan on the right side of the unit into thecompressor compartment. There are three locations thatthe drain can exit the cabinet. For a stand pipe type ofdrain, the drain hose can exit the rear of the cabinet.There is adequate hose length to reach the floor on theright hand side of the unit.

If the drain is to be hard plumbed, there is a 3/4 inchpipe connection located on the right hand cabinet sidenear the rear and one on the cabinet rear panel. In theseinstallations the drain tube is to be slipped over the pipeconnection inside of the cabinet.

FIGURE 9BOPTIONAL REAR DRAIN

See Figures 9A, 9B and 9C.

NOTE: Whichever type of drain connection is used a“P” trap must be formed.

The side drain requires a water trap for proper drainage.See Figure 8A. The drain can be routed through the flooror through the wall. If the drain is to be routed throughan unconditioned space, it must be protected fromfreezing. The drain line must be able to be removed fromthe unit if it is necessary to remove the unit from the wall.

MIS-974

FIGURE 9ASIDE DRAIN (SIDE VIEW)

QTEC UNIT

MIS-976

MIS-977

FIGURE 9CREAR DRAIN (TOP VIEW)

SLEEVE

WALLBRACKET

WALL(MAXIMUM 10"FOR REARDRAIN)

DRAIN LINE

COUPLINGS NOTSHOWN BUTRECOMMENDEDFOR EASE OFREMOVABILITYFOR SERVICE

WATERTRAP

UNIT

Page 13: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 13 of 27

BAROMETRIC FRESH AIR DAMPER (Optional)

Before start to remove make sure the power has beenturned off. The hinged return air grille panel must beopened. The fresh air damper assembly can be seen onthe back of the unit. Refer to Figure 10.

1. The fresh air damper is attached to the back of theunit with one screw on either side of the assembly.Both of the screws must be removed.

2. Once the mounting screws are removed, tilt theassembly down and lift it out.

The mist eliminator can be seen through the opening.The mist eliminator must be raised up and the bottomcan be pulled toward the front of the unit.

COMMERCIAL ROOM VENTILATOR OPTION

Before stating the removal make sure the power hasbeen turned off. The hinged return air grille must beopened. The commercial room ventilator (CRV) can beseen after the panel has been removed. The CRV mustbe removed to gain access to the mist eliminator.

1. The two mounting screws in the front of the CRVmust be removed.

2. The power connectors for the CRV (located on theright side of the unit) must be disconnected.Squeeze the tabs on the sides of the connector andpull straight out. Unplug both of the connectors.

3. Slide the CRV straight out of the unit.

The mist eliminator can be seen through the opening inthe back of the unit. The mist eliminator must be raisedup and the bottom can be pulled toward the front of theunit and removed.

The rear drain can be used with wall thickness of up to10 inches where a water trap can be installed betweenthe unit and the interior wall. See Figure 8B. The trapcannot extend beyond the edge of the unit or it willinterfere with the wall mounting bracket. The drain canbe routed through the floor or through the wall. If thedrain is routed through the wall, the drain line must bepositioned such that it will not interfere with the sleeveflange or the grille. See Figure 9C on Page 12. If thedrain is to be routed through an unconditioned space,it must be protected from freezing.

MIST ELIMINATOR SERVICE (Optional – only used with one of the vent options)A mist eliminator is supplied with the wall sleeve. Themist eliminator is constructed of aluminum frame andmesh. The mist eliminator is located in the top sectionof the wall sleeve and can be removed from the inside ofthe building without removing the unit from the wall.This requires that the ventilation package must beremoved.

The steps necessary to remove each of the vent optionsare listed following.

It is recommended that the mist eliminator be inspectedannually and serviced as required. The mist eliminatorcan be inspected from the outside of the building bylooking through the outdoor grille. The mist eliminatorcan be serviced from the outside. The outdoor grillemust be removed to do so.

The mist eliminator can be cleaned by washing withsoap and water. The excess water should be shaken offthe mist eliminator before it is reinstalled.

Page 14: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 14 of 27

FIGURE 10FRESH AIR DAMPER REMOVAL

MOUNTING SCREW

MIS-1627

Page 15: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 15 of 27

QTEC ENERGY RECOVERY VENTILATOROPTION

Before starting the removal make sure that the powerhas been turned off. The hinged return air grille panelmust be opened. The energy recovery ventilator(QERV) can be seen after the panel is opened. To gainaccess to the mist eliminator, the QERV must beremoved. Refer to Figure 11.

1. The front fill plate of the QERV must be removed.There is one screw on either side of the plate.Remove these screws and remove the plate.

2. On either side of the QERV there are mountingscrews that hold the QERV in place. Remove bothof these screws.

FIGURE 11REMOVAL OF THE QTEC ENERGY RECOVERY VENTILATOR

3. Underneath the heat recovery cassette there is apower connector for the lower blower assembly. Todisconnect this plug, the tabs on both sides of theplug must be squeezed to release the plug. Whilesqueezing the tabs, pull the plug out of the socket.

4. The QERV is plugged into the unit on the right sideof the unit. Both of these plugs must bedisconnected to remove the QERV. Squeeze thetabs on the sides of the connector and pull straightout.

5. Slide the QERV assembly straight out of the unitbeing careful not to let the cassette slide out of theQERV.

The mist eliminator can be seen through the opening inthe back of the unit. The mist eliminator must be raisedup and the bottom can be pulled toward the front of theunit and removed.

MIS-1605

FRONT FILL

MOUNTINGSCREWS

LOWER BLOWERASSEMBLY POWERCONNECTOR

POWERCONNECTORS

Page 16: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 16 of 27

INSTALLATION INSTRUCTIONS

MOUNTING THE UNITWhen installing a QC unit near an interior wall on theleft side, a minimum of 8 inches is required; 12 inchesis preferred.

When installing a QC unit near an interior wall on theright side, a minimum of 12 inches is required asadditional space is required to connect the drain.

This clearance is required to allow for the attachment ofthe unit to the wall mounting brackets and the side trimpieces to the wall.

This unit is to be secured to the wall with the wallmounting brackets provided. The unit itself, the supplyduct, and the free blow plenum are suitable for “0”clearance to combustible material.

NOTE: When a wall sleeve is to be used discard thebrackets shipped with the heat pump andattache the unit to the sleeve with bracketsupplied with the wall sleeve.

Following are the steps for mounting the QC units forreference see Figure 13.

1. Attach wall mounting bracket to the structure wallwith field supplied lag bolts. The fluid pipingconnections are to be within the confines of thisbracket. See Figure 1 for cabinet openings andlocation of fluid coil connection points.

2. Position the unit in front of the wall mountingbracket.

3. Remove the locking screws from the wheels. Referto Figure 11.

4. Roll the unit up to the wall mounting bracket. Theunit must be level from side to side. If anyadjustments are necessary, shim up under the rollerswith sheets of steel or any substance that is notaffected by moisture.

5. Secure the unit to the wall bracket with provided#10 hex head sheet metal screws. There areprepunched holes in the cabinet sides, and thebracket has slotted holes to allow for somemisalignment.

6. Position the bottom trim piece to the unit and attachwith provided screws (dark colored).

7. Position side trim pieces to the wall and attach withfield supplied screws. There are two long and twoshort pieces supplied. The long pieces are toenclose the gap behind the unit. The short piecesare to fill the gap behind the cabinet extension or thefree blow plenum box. They may be cut to suit theceiling height or overlap the unit side trim. There issufficient length to trim up to a 10'2" ceiling.

FIGURE 12REMOVING LOCKING SCREWS FROM WHEELS

MIS-1523REMOVE SCREWSFROM WHEELSBEFORE ROLLINGINTO PLACE

Page 17: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 17 of 27

FIGURE 13UNIT MOUNTING WITHOUT VENTILATION WALL SLEEVE

(REFER TO MOUNTING INSTRUCTIONS ON PAGE 13)

SIDE TRIM(2 PIECES)

SIDE TRIM (2PIECES)

WALL MOUNTINGBRACKET

BOTTOM TRIMEXTENSION

BOTTOM TRIM PIECE

MIS-1557

Page 18: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 18 of 27

FIGURE 14COMPONENT LOCATION

SIDE FIELDWIRE ENTRANCE

REMOTE THERMOSTATTERMINAL BLOCK

INDOOR BLOWER

CONTROL BOX/ CIRCUITBREAKER PANEL

MIS-1736

WIRING – MAIN POWERRefer to the unit rating plate and/or Table 2 for wiresizing information and maximum fuse or “HACRType” circuit breaker size. Each unit is marked with a“Minimum Circuit Ampacity”. This means that thefield wiring used must be sized to carry that amount ofcurrent. Depending on the installed KW of electricheat, there may be two field power circuits required. Ifthis is the case, the unit serial plate will so indicate. Allmodels are suitable only for connection with copperwire. Each unit and/or wiring diagram will be marked

“Use Copper Conductors Only”. These instructionsmust be adhered to. Refer to the National ElectricalCode (NEC) for complete current carrying capacity dataon the various insulation grades of wiring material. Allwiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75°Ccopper) for all models, including the most commonlyused heater sizes. Also shown are the number of fieldpower circuits required for the various models withheaters.

Page 19: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 19 of 27

The unit rating plate lists a “Maximum Time DelayRelay Fuse” or “HACR Type” circuit breaker that is tobe used with the equipment. The correct size must beused for proper circuit protection, and also to assure thatthere will be no nuisance tripping due to the momentaryhigh starting current of the compressor motor.

The disconnect access door on this unit may be lockedto prevent unauthorized access to the disconnect.

The field wiring connections are located behind the toppanel in the circuit breaker panel. The return air panelmust be removed first. This panel is equipped with adoor switch which shuts the unit down when it isremoved. The filter rack must be removed next.

WIRING – LOW VOLTAGE WIRING230/208V, 1 PHASE AND 3 PHASE EQUIPMENTDUAL PRIMARY VOLTAGE TRANSFORMERSAll equipment leaves the factory wired on 240V tap.For 208V operation, reconnect from 240V to 208V tap.The acceptable operating voltage range for the 240 and208V taps are as noted in Table 3.

The Climate Control Option D is an electronic,programmable thermostat. The subbase of thethermostat is factory wired to the front panel of the unit.Compatible for use with Energy Recovery Ventilator orEconomizer.

GENERALThis unit is equipped with a variable speed ECM motor.The motor is designed to maintain rated airflow up tothe maximum static allowed. It is important that theblower motor plugs are not plugged in or unpluggedwhile the power is on. Failure to remove power priorto unplugging or plugging in the motor could result inmotor failure.

NOTE: The voltage should be measured at the fieldpower connection point in the unit and whilethe unit is operating at full load (maximumamperage operating condition).

TABLE 3OPERATING VOLTAGE RANGE

PAT EGNAR

V042 612-352

V802 781-022

TABLE 4WALL THERMOSTATS AND SUBBASE COMBINATIONS

tatsomrehT esabbuS serutaeFtnanimoderP

940-3048)083-39FI( A/N looC/taeH/otuA/launaM

cinortcelEelbammargorP

CAUTIONDo not plug in or unplug blower motor connec-tors while the power is on. Failure to do somay result in motor failure.

FLUID CONNECTIONSSee Figure 1 for location of fluid connection.Connection size is 1" FPT.

If the free blow plenum box is to be used, there areknock outs in the top of the box that can be removed toallow passage of the fluid piping.

All plumbing to and from the unit is to be installed inaccordance with local plumbing codes. The use ofplastic pipe where permissible is recommended toprevent electrolytic corrosion of the fluid pipes.

It is strongly recommended that the fluid piping to theunit be insulated to prevent water droplets fromcondensing on the pipe surface.

The standard Climate Control Option X is a remotethermostat connection terminal block. See Figure 17for wiring diagram. Compatible thermostats are listedin Table 4.

Page 20: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 20 of 27

LOW VOLTAGE CONNECTIONS

These units use a grounded 24 volt AC low voltagecircuit.

The “R” terminal is the hot terminal and the “C”terminal is grounded.

“G” terminal or pins 6 and 1 of P2 are the fan inputs.Both must be energized for proper fan operation. Thisis done automatically in the factory installed climatecontrol options. If the climate control option isabandoned and connections are made directly to P2both pins 6 and 1 of P2 must be energized for properoperation.

“Y” terminal or pin 7 of P2 is the first stage coolinginput.

“B” terminal or pin 8 of P2 is the first stage heatinginput.

“R” terminal or pin 10 of P2 is 24 VAC hot.

“C” terminal or pin 11 of P2 is 24 VAC grounded.

“L” terminal or pin 12 of P2 is the second stagecooling input.

“W2” terminal or pin 9 of P2 is second stage heatingoutput.

“O1” terminal of pin 5 of P2 is the ventilation input.This terminal energizes any factory installed ventilationoption.

Fan Only Energize G

1st Cooling Mode Energize Y, G

2nd Cooling Mode Energize Y, L, G

1st Stage Heating Energize G, B

2nd Stage Heating Energize G, B, W2

Ventilation Energize G, O1

LOW VOLTAGE CONNECTIONS FORDDC CONTROL

FIGURE 15BLOWER MOTOR LOW VOLTAGE

WIRE HARNESS PLUG

MIS-1285

VIEWED FROM PIN ENDVIEWED FROM PIN END

Page 21: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 21 of 27

FIGURE 16REMOTE THERMOSTAT WIRING DIAGRAM

“X” OPTION

MIS-1734

IF93-380

Page 22: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 22 of 27

4102-028

IF93-380

FIGURE 17REMOTE THERMOSTAT WIRING DIAGRAM

“D” THERMOSTAT OPTION

Page 23: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 23 of 27

1 Maximum ESP (inches WC) shown is with 1" thick disposable filter (reduced by .2 for 2" filter).2 Rated CFM for ducted applications – required for maximum performance rating. To obtain full CFM locate low

voltage terminal strip in the circuit breaker box.There is a pink jumper wire with both ends attached to terminalmarked “G2”. Move one end of the jumper to terminal “Y”.

3 Optional CFM – the unit is shipped from the factory set to operate at the optional CFM level shown.This provides lower operating sound levels for non-ducted, free discharge applications. This reducessystem capacity performance by approximately 2% at the same energy efficiency.

4 Continuous fan CFM is the total air being circulated during continuous fan mode.

OPTIONAL CFMThese units are shipped from the factory set to operateat the optional CFM level shown in Table 4. Thisprovides lower operating sound levels for non-ducted,free discharge applications. This CFM level will reducethe system capacity performance by approximately 2%at the same energy efficiency.Rated CFM is required for ducted applications formaximum performance rating. To obtain full CFM onthese models, connect jumper wire as follows:

1. Disconnect all power to the unit. Failure to do somay result in damage to the motor.

2. Open hinged return air grille panel

3. Open control panel cover.

4. Add pink jumper wire (provided) to terminal5 and 6 on the terminal board.

5. Reverse steps to reassemble.

IMPORTANT INSTALLER NOTEFor improved start up performance, wash the indoorcoil with dishwashing detergent.

SERVICE HINTS 1. Caution user to maintain clean air filters at all times.

Also, not to needlessly close off supply air registers.This may reduce air flow through the system whichshortens equipment service life as well as increasingoperating costs and noise levels.

2. The wall thermostat perform multiple functions. Besure that all function switches are correctly set forthe desired operating mode before trying todiagnose any reported service problems.

SEQUENCE OF OPERATIONFIRST STAGE COOLING – Circuit R-Y makes thethermostat open the first stage cooling water valve.

SECOND STAGE COOLING – Circuit R-Y2 makethe thermostat open the second stage cooling watervalve. The G (indoor motor) circuit is automaticallycompleted on any call for cooling operation, or can beenergized by manual fan switch on subbase for constantair circulation.

Caution: Second stage cooling must always beenergized in conjunction with first stage. Ifthe second state were energized alone, thecondensate from the upper part of the coilcould be blow off or re-evaporated as itpasses down over the dry portion of thecoil.

HEATING – A thermostat demand for heating makesR-W1 circuit as well as R-G circuit. This starts theindoor blower as well as turns on the electric heater.

SECOND STAGE HEATING (15 KW only) – CircuitR-W2 energizes the second contactor and brings on thelast 5 KW of heat.

START UP

TABLE 5INDOOR BLOWER PERFORMANCE

NOTE: These units are equipped with a variable speed (ECM) indoor motor that automaticallyadjusts itself to maintain approximately the same rate of indoor air flow in both heatingand cooling, dry and wet coil conditions, and at both 230/208 or 460 volts.

LEDOMDETAR

PSE

1

PSE.XAM

2

MFCDETAR

3LANOITPO

MFC

4SUOUNITNOC

MFCMFC @ .XAM

PSE

105CQ 0.0 8.0 0021 0001 0001 5711

Page 24: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 24 of 27

MOTPMYS ERUDECORP/ESUAC.gnitratsnehwylthgilsskcorrotoM MCIrofpu-tratslamronsisihT

tratst'nowrotoM

tnemevomoN rotomtarewopkcehC

rotomta)CotRCAV42(egatlovwolkcehC

rotomta)C,R,W,Y,G(snoitcennocegatlovwolkcehC

ssenrahrotomnosrotcennocnisnipdetaesnurofkcehC

G-RneewtebrepmujyraropmetahtiwtseT

tfahsthgitrofrotomkcehC

nuR kcehCerutisoM

tratst'nowtub,skcorrotoM tnuomrotomtnailpmocroesoolrofkcehC

tfahsnothgitsileehwrewolberusekaM

gniebelihwnwoddnapusetallicsorotoMrewolbfoffodetset .tfahsnodaolonhtiwetallicsootrotomroflamronsitI

tenibacforewolbysioN .cte,slenap,gnisuohrewolbesoolrofkcehC

?deepsrewolbhgihgnitaerccitatshgiH– ,stcudnismaeshguorhtgniltsihwriarofkcehC

.slenaprostenibac– noitamrofedtcud/tenibacrofkcehC

)deeps(MFChgihta"sffup"ro"stnuH" ?"gniffup"ecuderretlifrolenapgnivomerseoD

– noitcitserecudeR

– wolfriamumixamecudeR

erutsioMfoecnedivEdnaderuccosahnoitcnuflamfoeruliafrotoM

tneserpsierutsiommrofrepdnarotomecalpeR kcehCerutsioM

revomriaedisnitneserperutsiomfoecnedivE kcehCerutsioMmrofreP

OD T'NODsnoitcennocdnagniriw,slortnoc,rotomtuokcehC

rotomgnicalpererofebylhguorohtdabsirotomehtemussayllacitamotuA

;nitegt'nacretawosnwodsrotcennoctneirO"spoolpird"llatsni

snoitsopksolc'o4dna7evobasrotcennocetacoL

srebmunledomlortnocdnarotomdezirohtuaesUtnemecalperrof

rehtonahtiwrebmunledomlortnocforotomenoecalpeR)tnemecalperdezirohtuanasselnu(

:muminimaoterusserpcitatspeeK H"2/1evahemoS.sretlifporderusserphgihesU 2 !pordO

– sretlifcitatswol,ycneiciffehgihdnemmoceR snruterdetcirtseresU

– naelcsretlifgnipeekdnemmoceR– ,citatsmuminimrofkrowtcudngiseD

trofmocmumixam– krowtcuddnemmocerdnarofkooL

.tnemecalperni,yrassecenerehw,tnemevorpmi

Moisture Check

TROUBLESHOOTING ECM BLOWER MOTORS

CAUTIONDisconnect power from unit before removing or replacing connectors, or servicing motor.Wait at least 5 minutes after disconnection power before opening motor.

Page 25: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 25 of 27

MOTPMYS ERUDECORP/ESUACyllacitarresnurtubstratsrotoM

tnettimretnironwoddnapuseiraV "gas"ronoitairavrofegatlovenilkcehC;rotomta)C,R,W,Y,G(snoitcennocegatlovwolkcehC

srotcennocssenrahrotomnisnipdetaesnudeepselbairavni(dnammocMFCcitarrerof"kB"kcehC

snoitacilppa?tatsomreht-slortnocmetsystuokcehC

mrofreP kcehCerutsioM

)deeps(MFChgihta"sffupro"stnuH" ?"gniffup"ecuderretlifrolenapgnivomerseoD– noitcirtserecudeR– wolfriamumixamecudeR

roloocrofllacmetssysetipsedMFCwoltasyatSMFCtaeh

snoitcennocdnaseriw)tatsomreht(egatlovwolkcehC

siyaledlitnutiaw-edomyaladnitonsinafyfireVetelpmoc

rotomtadetcennocton/gnissim"R"kcehctnemecalperlortnoc/rotommrofreP

MFChgihtasyatS rotomtadetcennocton/gnissim"R"etelpmocemityaledlitnutiaw-?edomyaladninafsI

ffotuhst'nowrewolB ?WroY,GotnislortnocmorfegakaeltnerruC– etatsdilosrotatsomrehtdehctiwscairTrofkcehC

yaler

NOTPMYS ERUDECORP/ESUACesionevissecxE .esionrotomrotcud,tenibac,esionriasitifienimreteD

.yrssecenfiremotsucweivretnI

esioNriA ?deepsrewolbhgihgnitaerccitatshgiH– ?ylreporpteswolfriasI– ?nwodwolsotrewolbesuacretlifgnivomerseoD

retlifecalper/kcehC– retlifporderusserpwolesU– snoitcritsertcudtcerroc/kcehC

OD T'NODylesiwtnempuqeehteziS wolfriawolhtiwetasnepmocnehtmetsysezisrevO

rotomgnitresnierofebnoitatneirokcehCsrotcennoc

sdrawkcabrotcennocrewopnigulP

sgulpecroF

ERUDECORPKCEHCERUTSIOM ERUDECORPKCEHCTROFMOC"nwod"detneiroerasrotcennoC sgnitteswolfriareporpkcehC

rotomrednu"poolpird"htiwsessenrahegnarrA esiontsewolroferusserpcitatswoL?deggulpniardetsnednoC MFCnafsuounitnocwolteS

)yticapactnetalhcumoot(wolfriawolrofkcehC stinugniloocdeeps-2dnatatsidimuhesUnoitidnocdegrahcrednurofkcehC MFCetalugertahtMCIrofdengisedslortnocgninozesU

tenibacdnastcudnrtuerniskaelgulpdnakcehC ?noitacoldabnitatsomrehT

Page 26: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 26 of 27

FIGURE 18INTERNAL 2-WAY VALVE PIPING

Water Valves

Valve Location

"NC" side of valve

"NO" side of valve

"COM" side of valve

Valve Detail

MIS-1899

Page 27: QC SERIES INSTALLATION CHILLED WATER UNIT INSTRUCTIONS ...

Manual 2100-416DPage 27 of 27

FIGURE 19INTERNAL 3-WAY VALVE PIPING

Water Valves

Valve Location

"NC" side of valve

"COM" side of valve

"NO" side of valve

Valve Detail

MIS-1900