    Saudi Cable Company

    Quality Control

    ITP-HV -02-12-12-10o

    Equipment/Material Description

    Saudi Cable Order Reference

    Purchase Order Reference

    Customer Name

    CU,XLPE,W-SCRN,ALFOIL, HOPE SHEATH 1X1200 mm2, 132 kV

    HVW 10239I&TP NUMBERREVISION

    REVISION DATE

    DATE OF ISSUE

    I/C

    12-Dec-10

    LKASXK3640SCOA

    1 Final Inspection 11-TMSS-02- Rev.OO

    1.1 Routine tests;

    a P ar ti al di sc har ge t es t @ 11 4 k V I EC- 60 84 0 C la us e 9 .2

    b Volta ge T est @ 1 90 kV f or 0 .5 h ou r I EC -6 08 40 C la use 9 .3

    c HV d .c t es t o n o ve r s hea th @ 25 k V I EC- 60 84 0 C la us e 9 .4

    1.2 Sample Tests IEC-60840 Clause 10

    a Conductor examination INo. of wi re s I EC -60 84 0 C la us e 1 0. 4

    b d.c resistance of conductor 0 /km @ 20 C IEC-60840 Clause 10.5

    c Approx d.c resistance of screen 0 /km @20 IEC-60840 Clause 10.5

    d T hickne ss o f con du ct or scree n_ mm I EC -6 08 40 C la use 1 0. 6

    e Thi ckness of i nsulation_mm IEC- 60840 Clause 10.6

    f T hickne ss o f insulat io n scree n_ mm I EC -6 08 40 C la use 1 0. 6

    g Hot set 1permanent set_% IEC-60840 Clause 10.9

    h Thickness of SC swellable tape_mm Technical Specification

    Cu wire screen cross-secti. area_mm2(Appro Technical Specification

    j Thickness of Outer Sheath_mm IEC-60840 Clause 10.6

    k Overall diameter of cable- approximate_mm IEC-60840 Clause 10.8

    I Measurement of capacitance_l.lf/km IEC-60840 Clause 10.10

    m Wat er e ne trat io n t est - j f a l icab le I EC -6 08 40 C la use 1 0. 2

    Notes: WC = Witness check (By SEC authorised representative)

    RC = Review of certificate(By SEC authorised representative)

    InspectionLimiting Values Ten. Date of

    Test Procedure S am pl in g T ype Location of Remarks

    MinimumNominal Maximum Tests Tests

    Using partial discharge detector 10% WC 5 SCC QC Asperschedule

    HV a.c transformer is used 10% WC No Break down SCCQC Asperschedule

    d .c v ol tag e is a pp li ed for 1 m inu te 1 0% WC No Break down SCCQC Asperschedule

    Visuallyexamined 10% WC SCCQC Asperschedule

    Usingautomatedresistancebridge 10% WC 0.0151 SCCQC Asperschedule

    Usingautomatedresistancebridge 10% WC 0.065 SCCQC Asperschedule

    Usingautomatedimage analyser 10% WC 0 .6 08 0 .7 6 SCCQC Asperschedule

    Usingautomatedimage analyser 10% WC 19.44 21.6 SCCQC Asperschedule

    Usingautomatedimage analyser 10% WC 1.4 1.75 SCCQC Asperschedule

    Dumbellsare placedinovenat 200C 10% WC 175/15 SCCQC Asperschedule

    UsingM icrometer 10% WC 0.12 SCCQC Asperschedule

    Micrometerand c alculation 10% WC 280 SCC QC Asperschedule

    Digitalcaliper/Profileprojectrisused 10% WC 4.5 5.0 SCCQC As perschedule

    Diametertape/digitalcaliper is used 10% WC 113.9 SCCQC As perschedule

    Capacitancemeteris used 10% WC 0.218 SCCQC Asperschedule

    Water penetrationtestapparatus EC-60 84 0 1 0. R C No water leak SCCQC Review

    S~~~~I;:~~;T~~~:~~YPrepared By : Sign

    Name:

    Sign

    Name'

    Checked/ApPVd.By :

  • 8/11/2019 QAS3-00-UZT-EFH-SCC-001-REV+1-INSP+&+TEST+PLN+FOR+132KV+CBL - 9

    3/3

    Saudi Cable Company

    Quality Control

    INSPECTION AND TEST PLAN (1&TP}

    Equipment/Material DescriptionSaudi Cable Order Reference

    Purchase Order Reference

    Customer Name

    CU,XLPE,W-SCRN,ALFOIL, HDPE SHEATH 1X2000 mm2 , 132 kVHVW10239

    I&TPNUMBERREVISION

    REVISION DATE

    DATE OF ISSUE

    IIC

    ITP-HV -01-12-12-10o

    12-Dec-10

    LKASXK4040SE2A

    InspectionLimiting Values Ten. Date of

    Si# Test/Inspection Item Applicable Standards Test Procedure Sampling Type Location ofTests

    Remarks

    Minimum Nominal Maximum Tests

    1 Final Inspection 11-TMSS-02- Rev.OO

    1.1 Routine tests;

    a P ar ti al di sch ar ge t est @ 11 4 kV I EC -60 84 0 C lau se 9. 2 Us ing p ar ti al di sch ar ge d et ect or 10% WC 5 SCCQC As per schedule

    b V ol ta ge T es t @ 1 90 k V fo r 0 .5 h ou r I EC -6 08 40 C la us e 9. 3 H V a .c t ra ns fo rm er is u se d 10% WC No Break down SCCQC A s per schedule

    C HV d.C test on over sheath @25 kV IEC-60840 Clause 9.4 d.c voltage is applied for 1 minute 10% WC No Break down SCCQC As per schedule

    1.2 Sample Tests IEC-60840 Clause 10

    a Conductor examination INo. of wires IEC-60840 Clause 10.4 Visually examined 10% WC - - - SCCQC As perschedule

    b d.c resistance of conductor O/km @ 20C IEC-60840 Clause 10.5 Using automated resistance br idge 10% WC - - 0.009 SCCQC As perschedule

    c Approx d.c resistance of screen O/km @ 2 0 I EC -6 08 40 C la us e 10 .5 U si ng a ut om at ed r es is ta nc e b ri dg e 1 0% WC 0.065 SCCQC As perschedule

    d T hi ckn es s of con du ct or scr een _m m I EC -6 08 40 Cl ause 10 .6 Us ing au tom at ed i mag e a nal yse r 1 0% WC 0 .6 08 0 .7 6 SCCQC As perschedule

    e T hi ckn es s of i nsu lat ion _m m I EC -6 08 40 Cl ause 10 .6 Us ing au tom at ed i mag e a nal yse r 10% WC 19.44 21.6 SCCQC As per schedule

    f Thickness of insulation screen_mm IEC-60840 Clause 10.6 Using automated image analyser 10% WC 1.4 1.75 SCCQC As per schedule

    g Hot set 1permanent seC% IEC-60840 Clause 10.9 Dumbells are placed in oven at 200C 10% WC 175/15 SCCQC As per schedule

    h T hi ck ne ss o f S C s we ll ab le t ap e_ mm T ec hn ic al S pe ci fi ca ti on U si ng M ic ro me te r 10% WC 0.12 SCCQC As per schedule

    i Cu wire screen cross-secti. area_mm2(Appro Technical Specification Micrometer and calculation 10% WC 280 SCCQC As perschedule

    j Thi ckn ess of Ou ter S hea th _m m I EC -6 08 40 C la use 10 .6 Digital caliper/Profileprojectr is used 10% WC 4.5 5.0 SCCQC As perschedule

    k Overall diameter of cable- approximate_mm IEC-60840 Clause 10.8 Diameter tape/digital caliper is used 10% WC 126.1 SCCQC As perschedule

    I M easu re me nt o f ca pa ci ta nc e_ lJf /km I EC- 608 40 C la us e 1 0. 10 C apa ci tanc e me ter i s use d 10 % WC - 0.259 SCCQC As perschedule

    m W at er p en et ra ti on t es t - i f a pp li ca bl e I EC -6 08 40 C la us e 10 .2 W at er p en et ra ti on t es t a pp ar at us E C- 60 84 0 10 . RC No water leak SCCQC Review

    Notes: WC = Witness check (By SEC authorised representative)