    TemBreak 1 MCCBs 125 A 400 A Technical dataRatings charts, selection guides MCCBs and accessories

    Tembreak 1 Ratings charts selection guides 30 - 400 A 13 - 100 to 13 - 105

    XS125CS, XS125NS 16 - 125 A 13 - 106XS125CJ, XS125NJ 20 - 125 A 13 - 107XH125NJ 20 - 125 A 13 - 108XH125PJ 20 - 125 A 13 - 109XE225NC 125 - 225 A 13 - 110XH160PJ 160 A 13 - 111XS250NJ, XH250NJ 160 - 250 A 13 - 112XH250PJ, XH400PJ 160 - 400 A 13 - 113XS400CJ, XS400NJ 250 - 400 A 13 - 114XS400SE, XH400SE 250 - 400 A 13 - 115XH400PE 250 - 400 A 13 - 116

    TL30F, TL100F, TL100C 15 - 100 A 13 - 117TL100NJ 20 - 100 A 13 - 118TL250NJ 160 - 250 A 13 - 119TL400NE 400 A 13 - 120Switch disconnectors (non-auto MCCBs) 125 - 630 A 13 - 121Accessories for the above MCCBs (for 400 A refer section 5) 13 - 122 to 13 - 127NHP TemPlug accessory 13 - 128Selectivity and Cascade data MCB/MCCBs 13 - 129 to 13 - 131Type 1 and 2 Motor starter co-ordination tables 13 - 132 to 13 - 135

    Section 13

    13 - 99

    TemBreak1MC

    CBsnow

    availablewith

    superior

    TemBreak2IP

    65handles

    13

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    2/3813 - 100

    13

    Standard TemBreak circuit breakerSelection guide ratings

    Rated current (A).In NRC Nominal rated current

    ASR Adjustable setting range

    Rated current at 40C

    AC RATED INSULATION VOLTAGE (Ui)

    AC RATED BREAKING CAPACITY sym RMS [kA]

    IEC 60947-2 [Icu] IEC 60947-2 [Ics] 1100V

    AS/NZS 3947-2 [Icu] AS/NZS 3947-2[Ics] 1000V

    Note: Rated Impulse withstand voltage 690V

    Uimp (kV) is 8kV on all XS, XE and XH MCCBs 660V

    500V

    440V

    415V

    400V

    380V

    240V

    AS 2184 440V

    415V

    NEMA AB-1 600V

    480V

    without Inst. 240-690V

    DC RATED BREAKING 250V

    CAPACITY (kA) 125V

    RATED SHORT TIME CURRENT RMS [kA] [Icw]

    DIMENSIONS (mm)

    a

    b

    c

    d

    Weight (kg) marked standard typeCONNECTION AND MOUNTINGS

    front terminal screw

    connect (FC) a tt ached f la t bar

    solderless terminal (PWC)

    rear bolt stud

    connect (RC) flat bar s tud

    plug-in (PM) for sw itchboard

    for distribution board

    draw-out (DO)

    STANDARD FEATURES

    contact indicator

    trip button

    PROTECTIVE FUNCTIONS

    Electronic type

    Adjustable LTD, STD & INST

    Adjustable GFT or Adjustable PTA (option)

    Trip indicators (option) (contacts)

    Thermal-magnetic type

    thermal and fixed magnetic trips

    thermal and adjustable magnetic trips

    adjustable thermal and fixed magnetic trips

    adjustable thermal and magnetic trips

    ACCESSORIES (option) CODE

    Internally auxiliary s witch AUX

    mounted alarm switch ALT

    shunt trip SHT

    undervoltage trip UVT

    Externally motor operator MOT

    mounted external pane l mounte d ty pe XFE

    operating breaker mounted type TFJ

    handle variable depth type XFH

    IP 65 handle variable depth type TLK

    extension handle

    mechanical interlock front type

    mechanical interlock rear type

    mechanical interlock cable type

    key interlockhandle holder

    handle lock

    captive padlock attachment

    terminal cover front connect type

    terminal cover rear/plug-in type

    interpole barriers

    accessories lead terminals

    OCR sealing kit

    Type

    Ampere frame

    Number of poles

    Outside view

    Notes:1) 1 Pole breaker only, XS125CS and XS125NS respectively.2

    ) 2 pole breaker is a 3 pole breaker with the centre pole omitted. Supplied as standard. Optional standard.

    Yes or available. Not available

    Indent only

    XS125CS XS125CJ

    1P 1) 2P 2) 3P 4P

    125A

    1P 1) 2P 2) 3P 4P

    125A

    16

    20

    25

    32

    40

    690

    10/5

    14/7

    18/9

    18/9

    14/7

    14

    18

    10

    30

    155

    86

    104

    0.51

    50

    63

    80

    100

    125

    12.5

    20

    32

    40

    63

    80

    20

    32

    50

    63

    100

    125

    NRC

    20

    32

    50

    63

    100

    125

    NRC ASR

    min max

    XS125NS XS125NJ

    7.5/3.8

    10/5

    14/7

    18/9

    18/9

    25/13

    10

    10

    15

    90

    1.3

    120

    1.58

    16

    20

    25

    32

    40

    690

    22/11

    25/13

    25/13

    30/15

    25/13

    25

    30

    15

    30

    155

    86

    104

    0.51

    50

    63

    80

    100

    125

    12.5

    20

    32

    40

    63

    80

    20

    32

    50

    63

    100

    125

    NRC

    20

    32

    50

    63

    100

    125

    NRC ASR

    min max

    5/2.5

    5/2.5

    12/6

    22/11

    25/13

    25/13

    30/15

    25/13

    12

    22

    15

    20

    90

    1.3

    120

    1.58

    ii

    i

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    3/3813 - 101

    13

    Standard TemBreak circuit breakerSelection guide ratings

    3P 4P

    125A

    XH125NJ

    20

    32

    50

    63

    100

    125

    690

    8/4

    8/4

    25/13

    42/21

    50/25

    50/25

    50/25

    85/43

    50

    50

    25

    42

    40

    40

    90

    155

    86

    104

    1.3

    12.5

    20

    32

    40

    63

    80

    20

    32

    50

    63

    100

    125

    NRC ASR

    min max

    120

    1.58

    160

    250

    100

    160

    160

    250

    NRC ASR

    min max

    140

    2.4

    3P

    225A

    XE225NC

    125

    150

    175

    690

    10/5

    15/7.5

    15/7.5

    18/9

    18/9

    25/13

    15

    18

    15

    10

    15

    105

    165

    67

    82

    1.4

    (Bar)

    690

    8/4

    8/4

    22/11

    25/13

    25/13

    25/13

    35/18

    50/25

    30

    35

    22

    25

    40

    40

    105

    165

    86

    107

    1.85

    (Bar)

    200

    250

    NRC

    3P 4P

    250A

    XS250NJ

    160

    250

    100

    160

    160

    250

    NRC ASR

    min max

    140

    2.6

    690

    15/7.5

    15/7.5

    25/13

    42/21

    50/25

    50/25

    50/25

    85/43

    50

    50

    25

    42

    40

    40

    105

    165

    103

    124

    2.1

    (Bar)

    3P 4P

    250A

    XH250NJ

    250

    400

    160

    250

    250

    400

    NRC ASR

    min max

    185

    6.1

    690

    ICU/ICS

    16/8

    16/8

    22/11

    30/15

    30/15

    35/18

    35/18

    50/25

    36

    36

    22

    30

    40

    40

    140

    260

    103

    131

    4.7

    (Bar)

    3P 4P

    400A

    XS400CJ

    250

    400

    160

    250

    250

    400

    NRC ASR

    min max

    185

    6.1

    690

    ICU/ICS

    18/9

    18/9

    30/15

    42/12

    50/25

    50/25

    50/25

    85/43

    50

    50

    30

    42

    40

    40

    140

    260

    103

    131

    4.7

    (Bar)

    3P 4P

    400A

    XS400NJ

    i i

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    4/3813 - 102

    13

    Standard TemBreak circuit breakerSelection guide ratings

    Rated current (A).In NRC Nominal rated current

    Rated current at 40C

    AC RATED INSULATION VOLTAGE (Ui)

    AC RATED BREAKING CAPACITY sym RMS [kA] 1100V

    IEC 60947-2 [Icu] IEC 60947-2 [Ics] 1000V

    AS/NZS 3947-2 [Icu] AS/NZS 3947-2[Ics] 690V

    Note: Rated Impulse withstand voltage 660V

    Uimp (kV) is 8kV on all XS, XE and XH MCCBs 500V

    440V

    415V

    400V

    380V

    240V

    AS 2184 440V

    415V

    NEMA AB-1 600V

    480V

    without Inst. 240-690V

    DC RATED BREAKING 250V

    CAPACITY (kA) 125V

    RATED SHORT TIME CURRENT RMS [kA] [Icw]

    DIMENSIONS (mm)

    a

    b

    c

    d

    Weight (kg) marked standard typeCONNECTION AND MOUNTINGS

    front terminal screw

    connect (FC) a tt ached f la t bar

    solderless terminal (PWC)

    rear bolt stud

    connect (RC) flat bar s tud

    plug-in (PM) for sw itchboard

    for distribution board

    draw-out (DO)

    STANDARD FEATURES

    contact indicator

    trip button

    PROTECTIVE FUNCTIONS

    Electronic type

    Adjustable LTD, STD & INST

    Adjustable GFT or Adjustable PTA (option)

    Trip indicators (option) (contacts)

    Thermal-magnetic type

    thermal and fixed magnetic trips

    thermal and adjustable magnetic trips

    adjustable thermal and fixed magnetic trips

    adjustable thermal and magnetic trips

    ACCESSORIES (option) CODE

    Internally auxiliary s witch AUX

    mounted alarm switch ALT

    shunt trip SHT

    undervoltage trip UVT

    Externally motor operator MOT

    mounted external pane l mounte d ty pe XFE

    operating breaker mounted type TFJ

    handle variable depth type XFH

    IP 65 handle variable depth type TLK

    extension handle

    mechanical interlock front type

    mechanical interlock rear type

    mechanical interlock cable type

    key interlockhandle holder

    handle lock

    captive padlock attachment

    terminal cover front connect type

    terminal cover rear/plug-in type

    interpole barriers

    accessories lead terminals

    OCR sealing kit

    Type

    Ampere frame

    Number of poles

    Outside viewNotes:

    Supplied as standard. Optional standard.

    Yes or available. Not available

    Indent onlyi

    3P 4P

    30A

    TL30F

    15

    20

    30

    690

    25/13

    25/13

    42/31

    120/60

    120/60

    120/60

    120/60

    120/60

    120

    120

    25

    42

    40

    40

    90

    155

    86

    104

    1.3

    NRC

    120

    1.58

    i 3P 4P

    100A

    TL100F

    15

    20

    30

    40

    50

    690

    25/13

    25/13

    60/30

    120/60

    120/60

    120/60

    120/60

    120/60

    120

    120

    42

    75

    40

    40

    105

    165

    125

    143

    3.2

    NRC

    60

    75

    100

    140

    3.8

    i 3P

    125

    150

    175

    200

    225

    NRC

    TL225F

    690

    25/13

    25/13

    60/30

    120/60

    120/60

    120/60

    120/60

    120/60

    120

    120

    60

    75

    40

    40

    140

    260

    133

    167

    6

    (Bar)

    225A

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    5/3813 - 103

    13

    Non-automatic circuit breakerSelection guide ratings

    Type

    Ampere frame

    Number of poles

    Outside viewNotes:

    Supplied as standard. Optional standard.

    Yes or available. Not available

    Indent only

    RATINGS AC

    RATED OPERATIONAL VOLTAGE (V) DC

    AS/NZS 3947-2 IEC 60947-2

    RATED SHORT CIRCUIT MAKING CAPACITY peak/kA

    RATED SHORT TIME CURRENT RMS [kA]

    DIMENSIONS (mm)

    a

    b

    c

    d

    Weight (kg) marked standard type

    CONNECTION AND MOUNTINGS

    front terminal screw

    connect (FC) a tt ached fl at bar

    solderless terminal (PWC)

    rear bolt stud

    connec t (RC) fla t bar stud

    plug-in (PM) for switchboar d

    for distribution board

    draw-out (DO)

    STANDARD FEATURES

    ON-OFF colour indicator

    trip button

    ACCESSORIES (option) CODE

    Internally auxiliary switch AUX

    mounted alarm switch ALT

    shunt trip SHT

    undervoltage trip 1) UVT

    Externally motor operator MOT

    mounted external panel mounted type XFEoperating breaker mounted type TFJ

    handle variable depth type XFH

    IP 65 handle variable depth type TLK

    extension handle

    mechanical interlock front type

    mechanical interlock rear type

    handle holder

    handle lock

    terminal cover front connect type

    terminal cover rear connect/plug-in type

    interpole barriers

    accessories lead terminal block 3)

    door flange

    IP 20 protection plug in type

    Maximum switching current AC

    DC

    Utilisation Category

    Endurance number of operations without current

    number of operations with current

    i

    3P 4P

    125A 250A

    XS125NN

    690

    250

    2.5

    1.8 (1 sec)

    90

    155

    86

    104

    1.1

    2)

    750

    313

    AC-23A

    7000

    1000

    120

    1.4

    690

    250

    5.5

    3 (1 sec)

    105

    160

    60

    83

    2.1

    2)

    1500

    625

    AC-23A

    7000

    1000

    690

    250

    6

    4 (1 sec)

    105

    165

    86

    107

    1.85

    2)

    1500

    625

    AC-23A

    7000

    1000

    140

    2.4

    690

    250

    9

    5 (0.3 secs)

    140

    260

    103

    131

    4.7

    2)

    2400

    1000

    AC-23A

    4000

    1000

    185

    6.1

    XE250NNC

    3P 4P

    250A

    XS250NN

    3P 4P

    400A

    XS400NN

    Notes:1) For AC UVT, a UVT Controller is mounted externally.2) Line side interpole barriers are supplied as standard.3) Draw-out leads, horizontally.4) Draw-out leads, vertically.

    i i i3P

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    6/3813 - 104

    13

    Rated current (A).In NRC Nominal rated current

    ASR Adjustable setting range

    Rated current at 40C

    AC RATED INSULATION VOLTAGE (Ui)

    AC RATED BREAKING CAPACITY sym RMS [kA]IEC 60947-2 [ Icu] IEC 60947-2[I cs] 1100V

    AS/NZS 3947-2 [Icu] AS/NZS 3947-2[Ics] 1000V

    Note: Rated Impulse withstand voltage 690V

    Uimp (kV) is 8kV on all XS, XE and XH MCCBs 500V

    440V

    415V

    400V

    240V

    without Inst. 240-690V

    DC RATED BREAKING 250V

    CAPACITY (kA) 125V

    RATED SHORT TIME CURRENT RMS [kA] [Icw]

    DIMENSIONS (mm)

    a

    b

    c

    d

    Weight (kg)

    marked standard typeCONNECTION AND MOUNTING

    front terminal screw

    connect (FC) a ttached fl at bar

    solderless terminal (PWC)

    rear bolt stud

    connect (RC) f la t bar s tud

    p lug- in (PM) for switchboard

    for distribution board

    draw-out (DO)

    STANDARD FEATURES

    contact indicator

    trip button

    PROTECTIVE FUNCTIONS

    Electronic type

    Adjustable LTD, STD & INST

    Adjustable GFT or Adjustable PTA (option)

    Trip indicators (option) (contacts)

    Thermal-magnetic type

    thermal and fixed magnetic tripsthermal and adjustable magnetic trips

    adjustable thermal and fixed magnetic trips

    adjustable thermal and magnetic trips

    ACCESSORIES (option) CODE

    Internally auxiliary s witch AUX

    mounted alarm switch ALT

    shunt trip SHT

    undervoltage trip UVT

    Externally motor operator MOT

    mounte d ope rating bre aker mounted type TFJ

    handle variable depth type XFH

    IP 65 handle variable depth type TLK

    extension handle

    mechanical interlock front type

    mechanical interlock rear type

    mechanical interlock cable type

    key interlock

    handle holder

    handle lock

    captive padlock attachment

    terminal cover front connect type

    terminal cover rear/plug-in type

    interpole barriers

    accessories lead terminals

    OCR sealing kit

    TypeAmpere frame

    Number of polesOutside view

    Notes:1) Adjustable ground fault available on indent,

    fitted externally.2) LED indicators only or LED contacts, please specify.

    Supplied as standard. Optional standard.

    Yes or available. Not available

    Available on indent onlyi

    3P 4P

    XH125PJ125A

    20

    32

    50

    63

    100

    125

    690

    8/4

    25/13

    42/21

    50/50

    50/50

    85/50

    40

    40

    90

    155

    86

    104

    1.3

    12.5

    20

    32

    40

    63

    80

    20

    32

    50

    63

    100

    125

    NRC ASR

    min max

    120

    1.6

    3P

    XH160PJ160A

    160

    690

    15/7.5

    23/13

    42/21

    50/50

    50/50

    85/50

    40

    40

    105

    165

    103

    124

    2.1

    (Bar)

    100 160

    NRC ASR

    min max

    140

    2.6

    3P

    XH250PJ250A

    250

    690

    18/9

    42/15

    42/21

    65/50

    65/50

    85/50

    40

    40

    140

    260

    103

    145

    4.7

    (Bar)

    160 250

    NRC ASR

    min max

    185

    6.1

    3P 4P

    XH400PJ400A

    250

    400

    690

    ICU/ICS

    18/9

    30/15

    42/21

    65/50

    65/50

    85/50

    5

    40

    40

    5 (0.3 sec)

    140

    260

    103

    145

    4.7

    (Bar)

    125

    250

    250

    400

    NRC ASR

    min max

    185

    6.1

    3P 4P

    XH630PJ630A

    400

    630

    690

    ICU/ICS

    45/23

    65/33

    85/43

    85/50

    100/50

    125/163

    40

    40

    210

    273

    103

    145

    9

    250

    400

    400

    630

    NRC ASR

    min max

    280

    11.5

    i

    TemBreak PlusSelection guide PowerBreaker Series Ics = 50 kA

    Ratings

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    7/3813 - 105

    13

    4P

    XH800PJ800A

    800

    690

    ICU/ICS

    45/23

    65/33

    85/43

    85/50

    100/50

    125/63

    40

    40

    210

    273

    103

    145

    9

    500 800

    NRC ASR

    min max

    280

    11.5

    3P 4P

    XH400PE400A

    250

    400

    690

    ICU/ICS

    20/10

    42/21

    65/50

    65/50

    65/50

    100/50

    5

    5 (0.3 sec)

    140

    260

    103

    14

    4.8

    (Bar)

    1)

    2)

    125

    200

    250

    400

    NRC ASR

    min max

    185

    6.2

    3P 4P

    XS400SE400A

    160

    250

    400

    690

    ICU/ICS

    18/9

    30/15

    42/21

    50/25

    50/25

    85/43

    5

    5 (0.3 sec)

    140

    260

    103

    131

    4.8

    (Bar)

    1)

    2)

    80

    125

    200

    160

    250

    400

    NRC ASR

    min max

    185

    6.2

    3P 4P

    XH400SE400A

    160

    250

    400

    690

    ICU/ICS

    20/10

    42/21

    65/33

    65/33

    65/33

    100/50

    5

    5 (0.3 sec)

    140

    260

    103

    131

    4.8

    (Bar)

    1)

    2)

    80

    125

    200

    160

    250

    400

    NRC ASR

    min max

    185

    6.2

    i i

    SelectivitySeries SE

    PowerBreakerSeries (contd)

    3P 4P

    TL100NJ100A

    20

    32

    50

    63

    100

    690

    85/85

    85/85

    85/85

    100/100

    40

    40

    90

    235

    86

    104

    2.2

    12.5

    20

    32

    40

    63

    20

    32

    50

    63

    100

    NRC ASR

    min max

    120

    2.7

    3P 4P

    TL250NJ250A

    160

    250

    690

    25/25

    70/70

    85/85

    85/85

    100/100

    130/130

    40

    40

    105

    360

    103

    145

    7.1

    (Bar)

    100

    160

    160

    250

    NRC ASR

    min max

    185

    9.1

    3P 4P

    TL400NE400A

    400

    690

    ICU/ICS

    25/25

    70/70

    85/85

    85/85

    100/100

    130/130

    140

    360

    103

    145

    7.1

    (Bar)

    200 400

    NRC ASR

    min max

    185

    9.1

    LimitorBreaker SeriesIcs = 65 - 85kA

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    8/3813 - 106

    13

    TemBreak MCCBsXS125 single pole series (CS / NS)

    XS125CS (14 kA)

    16

    20

    25

    3240

    50

    63

    80

    100

    125

    Ampererating

    XS125CS 16 1

    XS125CS 20 1

    XS125CS 25 1

    XS125CS 32 1XS125CS 40 1

    XS125CS 50 1

    XS125CS 63 1

    XS125CS 80 1

    XS125CS 100 1

    XS125CS 125 1

    1 poleCat. No.

    Notes: 1) An internal shunt trip may be mounted in anXS125CS/NS MCCB.Other accessories are external.

    Fixed thermal and magnetic trip.

    Current rating @ 45C 16 A - 125 A.

    Standards AS/NZS 3947-2.

    Breaking capacity at 250 V DC, 500 V AC.

    Dimensions (mm)

    30

    Height

    86

    Depth

    0.5

    kg

    XS125CS/NS 155

    Description Width

    Model I/C Voltage

    XS125CSXS125NS

    14 kA25 kA

    240 V 50 Hz240 V 50 Hz

    Short circuit capacity

    Base standards

    IEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2/Aust./NZ

    AS 2184-1990/Australia

    JIS C 8372/JAPAN

    JEC 160/JAPAN

    Approvals

    ASTA/UK, Aust. standards

    Marine

    NK/JAPAN

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

    Ampererating

    1 poleCat. No.

    XS125NS (25 kA)

    16

    20

    25

    32

    40

    50

    63

    80

    100

    125

    XS125NS 16 1

    XS125NS 20 1

    XS125NS 25 1

    XS125NS 32 1

    XS125NS 40 1

    XS125NS 50 1

    XS125NS 63 1

    XS125NS 80 1

    XS125NS 100 1

    XS125NS 125 1

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    9/3813 - 107

    13

    XS125NJ 20 2

    XS125NJ 32 2

    XS125NJ 50 2

    XS125NJ 63 2

    XS125NJ 100 2XS125NJ 125 2

    TemBreak MCCBsXS125 series (CJ/NJ)

    155

    155155

    155

    Height

    90

    9090

    120

    Width

    XS125NJ (25 kA) 3 pole

    12.5

    20

    32

    40

    63

    80

    XS125NJ 20 3

    XS125NJ 32 3

    XS125NJ 50 3

    XS125NJ 63 3

    XS125NJ 100 3

    XS125NJ 125 3

    20

    32

    50

    63

    100

    125

    20

    32

    50

    63

    100

    125

    XS125NJ (25 kA) 4 pole

    12.5

    20

    32

    40

    63

    80

    XS125NJ 20 4

    XS125NJ 32 4

    XS125NJ 50 4

    XS125NJ 63 4

    XS125NJ 100 4

    XS125NJ 125 4

    20

    32

    50

    63

    100

    125

    20

    32

    50

    63

    100

    125

    Notes: 1) MCCBs only.2) Poles in series. Refer applications Section 13.3) 2 pole models use a 3 pole body with centre pole disabled.

    Special low instantaneous magnetic, generator protection MCCBs availableon request.

    Adjustment range 63 - 100% of nominal current rating.

    Standards AS/NZS 3947-2.

    Adjustable thermal and fixed magnetic trip.

    Dimensions (mm)

    86

    8686

    86

    Depth

    1.3

    1.31.3

    1.58

    kg

    XS125CJ 3 pole

    XS125NJ 2 poleXS125NJ 3 pole

    XS125NJ 4 pole

    Description

    Model I/C Voltage

    XS125CJ

    XS125NJ

    18 kA

    25 kA

    400 V 50 Hz

    400 V 50 Hz

    Short circuit capacity

    Base standards

    IEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2/Aust./NZ

    AS 2184-1990/Australia 1)

    JIS C 8372/JAPAN

    JEC 160/JAPAN

    Approvals

    ASTA/UK, Aust. standards

    Marine

    NK/JAPAN

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

    DNV NORWAY

    DC use I/C 2) Voltage

    XS125CJ

    XS125NJ

    10 kA

    15 kA

    250 V DC

    250 V DC

    XS125NJ (25 kA) 2 pole 3)

    12.5

    20

    32

    40

    6380

    20

    32

    50

    63

    100125

    20

    32

    50

    63

    100125

    XS125CJ (18 kA) 3 pole

    12.5

    20

    32

    40

    63

    80

    Non-auto (1.8 kA for 1s) Refer page 13 - 121

    Ampererating Min Max

    XS125CJ 20 3

    XS125CJ 32 3

    XS125CJ 50 3

    XS125CJ 63 3

    XS125CJ 100 3

    XS125CJ 125 3

    Cat. No.

    20

    32

    50

    63

    100

    125

    125

    20

    32

    50

    63

    100

    125

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    10/3813 - 108

    13

    TemBreak MCCBsXH125 series

    Adjustment range 63 - 100 % of nominal rating.

    Co-ordinated with Sprecher + Schuh contactors.

    Standards AS 2184/AS/NZS 3947-2.

    Adjustable thermal, fixed magnetic trip.

    XH125NJ (50 kA) 3 pole

    12.5

    20

    32

    40

    63

    80

    Ampererating Min Max

    XH125NJ 20 3

    XH125NJ 32 3

    XH125NJ 50 3

    XH125NJ 63 3

    XH125NJ 100 3

    XH125NJ 125 3

    Cat. No.

    20

    32

    50

    63

    100

    125

    20

    32

    50

    63

    100

    125

    XH125NJ (50 kA) 4 pole

    12.5

    20

    32

    40

    63

    80

    XH125NJ 20 4

    XH125NJ 32 4

    XH125NJ 50 4

    XH125NJ 63 4

    XH125NJ 100 4

    XH125NJ 125 4

    20

    32

    50

    63

    100

    125

    20

    32

    50

    63

    100

    125

    i

    i

    i

    i

    i

    Dimensions (mm)

    90

    120

    Height

    86

    86

    Depth

    1.3

    1.6

    kg

    XH125NJ 3 pole

    XH125NJ 4 pole

    155

    155

    Description Width

    Notes: 1) MCCBs only.2) Poles in series. Refer applications section 13.Special low instantaneous magnetic, generator protection MCCBs availableon request.

    Available on indent only.

    Model I/C Voltage

    XH125NJ 50 kA 400/415 V 50 Hz

    Short circuit capacity

    DC use I/C 2) Voltage

    XH125NJ 40 kA 250 V DC

    i

    Bolt-on earth leakage module ELB 125.Refer Section 11 for further details.

    Base standardsIEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2/Aust./NZ

    AS 2184-1990/Australia 1)

    JIS C 8372/JAPAN

    JEC 160/JAPAN

    ApprovalsASTA/UK, Aust. standards

    MarineNK/JAPAN

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

    DNV NORWAY

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    11/3813 - 109

    13

    TemBreak Plus MCCBsXH125PJ PowerBreaker seriesIcs = 50 kA Powerful interrupting capacities.

    Limitation of system damage.

    Unique contact structure. Icu = Ics = 50 kA.

    Adjustable thermal, fixed magnetic trip.

    Adjustment range 63 - 100 % of nominal current rating.

    Standards IEC 60947-2/AS/NZS 3947-2.

    XH125PJ (50 kA) 3 pole

    12.5

    20

    3240

    63

    80

    Ampererating Min Max

    XH125PJ 20 3

    XH125PJ 32 3

    XH125PJ 50 3XH125PJ 63 3

    XH125PJ 100 3

    XH125PJ 125 3

    Cat. No.

    20

    32

    5063

    100

    125

    20

    32

    5063

    100

    125

    XH125PJ (50 kA) 4 pole

    12.5

    20

    32

    40

    6380

    XH125PJ 20 4

    XH125PJ 32 4

    XH125PJ 50 4

    XH125PJ 63 4

    XH125PJ 100 4XH125PJ 125 4

    20

    32

    50

    63

    100125

    20

    32

    50

    63

    100125

    i

    i

    i

    i

    i

    Dimensions (mm)

    90

    120

    Height

    86

    86

    Depth

    1.3

    1.6

    kg

    XH125PJ 3 pole

    XH125PJ 4 pole

    155

    155

    Description Width

    Notes: 1) Poles in series. Refer applications section 13.Available on indent only.

    Model Icu Voltage

    XH125PJ 50 kA 400/415 V 50 Hz

    AC useShort circuit capacity

    DC use 1) Icu Voltage

    XH125PJ 40 kA

    Ics

    50 kA

    Ics

    250 V DC

    iBase standards

    IEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2 Aust./NZ

    Approvals

    ASTA/UK, Aust. standards

    Marine

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    12/3813 - 110

    13

    TemBreak MCCBsXE225NC economical series

    Standards AS/NZS 3947-2.

    Fixed thermal magnetic trip.

    XE250 Isolator

    Non-Auto (3 kA for 1sec) 1) 3) Refer page 13 - 121250

    Dimensions (mm)

    105

    Height

    67

    Depth

    1.85

    kg

    XE225N 3 pole 160

    Description Width

    Notes: 1) Load-break isolating switch only no protection.2) Chassis not available for XE225NC.3) Short time rating. Refer rating chart for complete technical data.4) MCCBs only.

    Special low instantaneous magnetic, generator protection MCCBs

    available on request.

    Model I/C Voltage

    XE225NC 18 kA 400 V 50 Hz

    Short circuit capacity

    DC use I/C Voltage

    XE225NC 10 kA 250 V DC

    XE225NC (18 kA) 3 pole

    125

    150

    175

    200

    225

    Ampere rating(fixed)

    XE225NC 125 3

    XE225NC 150 3

    XE225NC 175 3

    XE225NC 200 3

    XE225NC 225 3

    Cat. No. 1) 2)

    Base standards

    IEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2/Aust./NZ

    AS 2184-1990/Australia 4)

    JIS C 8372/JAPAN

    JEC 160/JAPAN

    Approvals

    ASTA/UK, Aust. standards

    Marine

    NK/JAPAN

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    13/3813 - 111

    13

    TemBreak Plus MCCBsXH160PJ PowerBreaker seriesIcs = 50 kA

    Powerful interrupting capacities.

    Limitation of system damage.

    Unique contact structure.

    Icu = Ics = 50 kA.

    Adjustable thermal, fixed magnetic trip.

    Adjustment range 63 - 100 % of nominal current rating.

    Standards IEC 60947-2/AS/NZS 3947-2.

    Notes: 1) Poles in series. Refer applications section 13.Available on indent only.

    XH160PJ (50 kA) 3 pole

    100

    Ampererating

    XH160PJ 160 3

    Cat. No.

    160 160

    Min Max

    XH160PJ (50 kA) 4 pole

    100 XH160PJ 160 4160 160

    Dimensions (mm)

    105

    140

    Height

    103

    103

    Depth

    2.1

    2.4

    kg

    XH160PJ 3 pole

    XH160PJ 4 pole

    165

    165

    Description Width

    Base standards

    IEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2 Australia/NZ

    Approvals

    ASTA/UK, Aust. standards

    Marine

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

    i

    i

    Model Icu Voltage

    XH160PJ 50 kA 400/415 V 50 Hz

    AC use

    Short circuit capacity

    DC use 1) Icu Voltage

    XH160PJ 40 kA

    Ics

    50 kA

    Ics

    250 V DC

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    14/3813 - 112

    13

    TemBreak MCCBsXS250 and XH250 NJ series

    Adjustment range 63 - 100 % of nominal current rating.

    Standards AS/NZS 3947-2.

    Adjustable thermal, fixed magnetic trip.

    XS250NJ (25 kA) 3 pole

    100

    160

    Non-Auto (4 kA for 1 sec) 1) 4)

    Ampererating

    XS250NJ 160 3

    XS250NJ 250 3

    Refer page 5 - 48

    Cat. No.

    160

    250

    250

    160

    250

    Min Max

    Notes: 1) Isolating switch only - no protection.2) MCCBs only.3) Poles in series. Refer applications Section 13.4) Short time rating. Refer rating chart for complete technical data.Special low instantaneous magnetic generator protection MCCBs available onrequest.

    XH250NJ (50 kA) 3 pole

    160

    250

    XH250NJ 160 3

    XH250NJ 250 3

    100

    160

    160

    250

    XH250NJ (50 kA) 4 pole160

    250

    XH250NJ 160 4

    XH250NJ 250 4

    100

    160

    160

    250

    XS250NJ (25 kA) 4 pole100

    160

    Non-Auto (4 kA for 1 sec) 1) 4)

    XS250NJ 160 4

    XS250NJ 250 4

    Refer page 5 - 48

    160

    250

    250

    160

    250

    Model I/C Voltage

    XS250NJ

    XH250NJ

    25 kA

    50 kA

    400 V 50 Hz

    400/415 V 50 Hz

    Short circuit capacity

    Dimensions (mm)

    105

    105

    140

    140

    Height

    86

    103

    86

    103

    Depth

    1.85

    2.1

    2.4

    2.6

    kg

    XS250NJ 3 pole

    XH250NJ 3 pole

    XS250NJ 4 pole

    XH250NJ 4 pole

    165

    165

    165

    165

    Description Width

    XS250NJ

    XH250NJ

    40 kA

    40 kA

    250 V DC

    250 V DC

    DC use I/C 3) Voltage

    Base standards

    IEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2/Aust./NZ

    AS 2184-1990/Australia 2)

    JIS C 8372/JAPAN

    JEC 160/JAPAN

    Approvals

    ASTA/UK, Aust. standards

    Marine

    NK/JAPAN

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

    DNV NORWAY

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    15/3813 - 113

    13

    TemBreak Plus MCCBsXH250PJ and XH400PJ PowerBreaker seriesIcs = 50 kA

    Powerful interrupting capacities.

    Limitation of system damage.

    Unique contact structure.

    Adjustable thermal and magnetic trips.

    Thermal adjustment range 63 - 100 % of nominal current rating.

    Standards IEC 60947-2/AS/NZS 3947-2.

    Dimensions (mm)

    140185

    Height

    103103

    Depth

    4.76.1

    kg

    XH250/400PJ 3 poleXH250/400PJ 4 pole

    260260

    Description Width

    Base standards

    IEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2 Aust./NZ

    Approvals

    ASTA/UK, Aust. standards

    Marine

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

    Model Icu Voltage

    XH250/400PJ 65 kA 400/415 V 50 Hz

    AC use

    Short circuit capacity

    DC use 1) Icu Voltage

    XH250/400PJ 40 kA

    Ics

    50 kA

    Ics

    250 V DC

    Notes: 1) Poles in series. Refer applications section 13.Available on indent only.i

    XH250PJ and XH400PJ (65 kA) 3 pole

    100

    160

    250

    Ampererating Min Max

    XH250PJ 160 3

    XH250PJ 250 3

    XH400PJ 400 3

    Cat. No.

    160 (400AF)

    250 (400AF)

    400

    160

    250

    400

    XH250PJ and XH400PJ (65 kA) 4 pole

    100

    160

    250

    XH250PJ 160 4

    XH250PJ 250 4

    XH400PJ 400 4

    160 (400AF)

    250 (400AF)

    400

    160

    250

    400

    i

    i

    i

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    16/3813 - 114

    13

    TemBreak MCCBsXS400 series thermal magnetic type

    Notes: 1) Load-break isolating switch only no protection.2) MCCBs only.3) Poles in series. Refer applications Section 13.

    Dimensions (mm)

    140

    185

    Height

    103

    103

    Depth

    XS400CJ/NJ 3 pole

    4 pole

    260

    260

    Description Width

    4.7

    6.1

    kg

    Adjustment range 63 - 100 % of nominal current rating.

    Standards AS/NZS 3947-2.

    Adjustable thermal and magnetic trip.

    XS400CJ (35 kA) 3 pole

    160

    250

    Non-auto (5 kA for 0.3s) 1) Refer page 13 - 121

    Ampererating

    XS400CJ 250 3

    XS400CJ 400 3

    Cat. No.

    250

    400

    400

    250

    400

    Min Max

    XS400CJ (35 kA) 4 pole

    160

    250

    XS400CJ 250 4

    XS400CJ 400 4

    250

    400

    250

    400

    XS400NJ (50 kA) 3 pole

    160

    250

    XS400NJ 250 3

    XS400NJ 400 3

    250

    400

    250

    400

    XS400NJ (50 kA) 4 pole

    160

    250

    XS400NJ 250 4

    XS400NJ 400 4

    250

    400

    250

    400

    Model I/C Voltage

    XS400CJ

    XS400NJ

    35 kA

    50 kA

    400 V 50 Hz

    400/415 V 50 Hz

    Short circuit capacity

    Base standards

    IEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2/Aust./NZ

    AS 2184-1990/Australia 2)

    JIS C 8372/JAPAN

    JEC 160/JAPAN

    Approvals

    ASTA/UK, Aust. standards

    Marine

    NK/JAPAN

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

    DNV NORWAY

    DC use 3) I/C Voltage

    XS400CJ

    XS400NJ

    40 kA

    40 kA

    250 V DC

    250 V DC

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    17/3813 - 115

    13

    TemBreak Plus MCCBsXS400SE and XH400SE selectivity series electronic type

    SE Upstream Selectivity

    breakers. SE offers enhanced selectivity.

    3:1 ratio between upstream &

    downstream MCCBs.

    Ics rating is 50 % of Icu.

    I2t switch to assist in obtaining

    total selectivity.

    True RMS monitoring.

    Electronic trip unit with Long,Short and Instantaneous

    adjustments.

    Adjustment range 50 - 100 %

    of nominal current rating.

    Standards IEC 60947-2/

    AS/NZS 3947-2.

    Notes: Available on indent only.

    Dimensions (mm)

    140

    185

    Height

    103

    103

    Depth

    XS/XH400SE 3 pole

    XS/XH400SE 4 pole

    260

    260

    Description Width

    5

    6.2

    kg

    Description Code

    Pre-trip alarm

    Fault indicators

    Special LTD curves

    LSIP

    FI

    -

    OCR options (factory fitted)

    i

    Base standards

    IEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2 Aust./NZ

    Approvals

    ASTA/UK, Aust. standards

    Marine

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

    Model Icu Voltage

    XS400SE

    XH400SE

    50 kA

    65 kA

    400/415 V 50 Hz

    400/415 V 50 Hz

    AC useShort circuit capacity

    Ics

    25 kA

    33 kA

    XS400SE (50 kA) 3 pole

    125

    250

    Ampere

    ratingXS400SE 250 3

    XS400SE 400 3

    Cat. No.250

    400

    250

    400

    Min Max

    XH400SE (65 kA) 3 pole

    125

    250

    XH400SE 250 3

    XH400SE 400 3

    250

    400

    250

    400

    XS400SE (50 kA) 4 pole

    125

    250

    Ampererating

    XS400SE 250 4

    XS400SE 400 4

    Cat. No.

    250

    400

    250

    400

    Min Max

    XH400SE (65 kA) 4 pole

    125

    250

    XH400SE 250 4

    XH400SE 400 4

    250

    400

    250

    400

    i

    i

    i

    i

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    18/3813 - 116

    13

    TemBreak Plus MCCBsXH400PE PowerBreaker seriesIcs = 50 kA

    XH400PE (65 kA) 3 poleAmpererating Cat. No.Min Max

    Current limiting.

    True RMS monitoring. I2t switch to assist in obtaining total selectivity.

    Powerful interrupting capacities.

    Limitation of system damage.

    Unique contact structure.

    Electronic trip unit with Long, Short and Instantaneous adjustments.

    Adjustment range 50 - 100 % of nominal current rating.

    Standards IEC 60947-2/AS/NZS 3947-2.

    Notes: 1) Mounted externally.Available on indent only.

    Dimensions (mm)

    140

    185

    Height

    103

    103

    Depth

    XH400PE 3 pole

    XH400PE 4 pole

    260

    260

    Description Width

    5

    6.2

    kg

    125

    250

    XH400PE 250 3

    XH400PE 400 3

    250

    400

    250

    400

    XH400PE (65 kA) 4 pole

    125

    250

    XH400PE 250 4

    XH400PE 400 4

    250

    400

    250

    400

    Description Code

    Pre-trip alarm

    Fault indicators 1)

    Special LTD curves

    LSIP

    FI

    -

    OCR options (factory fitted)

    i

    Model Icu Voltage

    XH400PE 65 kA 400/415 V 50 Hz

    AC useShort circuit capacity

    Ics

    50 kA

    i

    i

    Base standards

    IEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2 Aust./NZS

    Approvals

    ASTA/UK, Aust. standards

    Marine

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    19/3813 - 117

    13

    TemBreak MCCBsHigh fault series thermal magnetic type

    Dimensions (mm)

    TL100C (180 kA) 3 pole

    15

    20

    30

    40

    50

    60

    75

    100

    TL100C 15 3P

    TL100C 20 3P

    TL100C 30 3P

    TL100C 40 3P

    TL100C 50 3P

    TL100C 60 3P

    TL100C 75 3P

    TL100C 100 3P

    TL100F (120 kA) 3 pole

    15

    20

    30

    40

    50

    60

    75

    100

    TL100F 15 3P

    TL100F 20 3P

    TL100F 30 3P

    TL100F 40 3P

    TL100F 50 3P

    TL100F 60 3P

    TL100F 75 3P

    TL100F 100 3P

    90

    105

    110

    Height

    86

    125

    133

    Depth

    TL30F

    TL100F

    TL100C

    155

    165

    230

    Description Width kg

    1.3

    3.2

    5.0

    Standards AS/NZS 3947-2.

    Interrupting capacity @ 415 V 120 kA.

    TL breakers are suitable for high fault high currentlimiting applications.

    Fixed thermal magnetic trip unit.

    TL30F (120 kA) 3 poleAmpererating

    TL30F 15 3P

    TL30F 20 3P

    TL30F 30 3P

    Cat. No.

    15

    20

    30

    Model I/C Voltage

    TL30F

    TL100F

    TL100C

    TL100F

    120 kA

    120 kA

    180 kA

    40 kA

    400/415 V 50 Hz

    400/415 V 50 Hz

    400/415 V 50 Hz

    250 V DC

    Short circuit capacity

    D/C use I/C I/C

    Base standards

    IEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2

    AS 2184-1990/Australia

    JIS C 8372/JAPAN

    JEC 160/JAPAN

    Approvals

    ASTA/UK, Aust. standards

    Marine

    NK/JAPAN

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    20/3813 - 118

    13

    TemBreak Plus MCCBsTL100NJ LimitorBreaker seriesIcs = 85 kA

    Dimensions (mm)

    90

    120

    Height

    86

    86

    Depth

    TL100NJ 3 pole

    TL100NJ 4 pole

    235

    235

    Description Width kg

    2.2

    2.7

    Standards IEC 60947-2/AS/NZS 3947-2.

    Two fast-break contacts per pole.

    Powerful interrupting capacities.

    Provides limitation of system damage during a fault.

    Icu = Ics = 85 kA.

    Variable thermal, fixed magnetic trip.

    Adjustment range 63 100 % of nominal current rating.

    Can be used for selectivity applications.

    3 or 4 pole types available.

    Notes: 1) Poles in series. Refer applications section 13.Available on indent only.

    Base standards

    IEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2

    Approvals

    ASTA/UK, Aust. standards

    Marine

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

    Model Icu Voltage

    TL100NJ 85 kA 400/415 V 50 Hz

    AC useShort circuit capacity

    DC use 1) Icu Voltage

    TL100NJ 40 kA

    Ics

    85 kA

    Ics

    250 V DC

    TL100NJ (85 kA) 3 pole

    12.5

    20

    32

    40

    63

    Ampererating Min Max

    TL100NJ 20 3

    TL100NJ 32 3

    TL100NJ 50 3

    TL100NJ 63 3

    TL100NJ 100 3

    Cat. No.

    20

    32

    50

    63

    100

    20

    32

    50

    63

    100

    TL100NJ (85 kA) 4 pole

    12.5

    20

    32

    40

    63

    TL100NJ 20 4TL100NJ 32 4

    TL100NJ 50 4

    TL100NJ 63 4

    TL100NJ 100 4

    20

    32

    50

    63

    100

    20

    32

    50

    63

    100

    i

    i

    i

    i

    i

    i

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    21/3813 - 119

    13

    TemBreak Plus MCCBsTL250NJ LimitorBreaker seriesIcs = 100 kA

    Base standards

    IEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2 Aust./NZ

    Approvals

    ASTA/UK, Aust. standards

    Marine

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

    Model Icu VoltageTL250NJ

    TL250NJ

    100 kA

    100 kA

    400 V AC 50 Hz

    400 V AC 50 Hz

    AC use

    Short circuit capacity

    DC use 1) Icu Voltage

    TL250NJ 40 kA

    Ics100 kA

    85 kA

    Ics

    250 V DC

    Dimensions (mm)

    140

    185

    Height

    103

    103

    Depth

    TL250NJ 3 pole

    TL250NJ 4 pole

    360

    360

    Description Width kg

    7.1

    9.1

    Standards IEC 60947-2/AS/NZS 3947-2.

    Two fast-break contacts per pole.

    Powerful interrupting capacities.

    Provides limitation of system damage during a fault.

    Icu = Ics = 85 kA at 415 V.

    Variable thermal and magnetic trip.

    Adjustment range 63 100 % of nominal current rating.

    Can be used for selectivity applications.

    3 or 4 pole types available.

    Notes: 1) Poles in series. Refer applications section 13.Available on indent only.i

    TL250NJ (100 kA) 3 pole

    100

    160

    Ampererating

    TL250NJ 160 3

    TL250NJ 250 3

    Cat. No.

    160

    250

    160

    250

    Min Max

    TL250NJ (65 kA) 4 pole

    100

    160

    TL250NJ 160 4

    TL250NJ 250 4

    160

    250

    160

    250

    i

    i

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    22/3813 - 120

    13

    TemBreak Plus MCCBsTL400NE LimitorBreaker series electronic type

    TL400NE (85 kA) 3 pole

    200

    Ampererating

    TL400NE 400 3

    Cat. No.

    400 400

    Min Max

    TL400NE (85 kA) 4 pole

    200 TL400NE 400 4400 400

    Notes: 1) Height excludes attached busbar.2) Factory fitted OCR controller specify voltage 240 V or 110 V AC.

    Available on indent only.

    Standards IEC 60947-2/AS/NZS 3947-2.

    Two fast-break contacts per pole.

    Powerful interrupting capacities.

    Provides limitation of system damage during a fault.

    Electronic trip unit with Long, Short & Instantaneous adjustments.

    Icu = Ics = 85 kA at 415 V.

    Adjustment range 50 100 % of nominal current rating.

    True RMS monitoring.

    I2t ramp switch to assist in obtaining total selectivity.

    3 or 4 pole types available.

    Description Code

    Pre-trip alarm 2)

    Fault indicators 2)

    Special LTD curves

    LSIP

    FI

    -

    OCR options (factory fitted)

    i

    i

    Base standards

    IEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2

    Approvals

    ASTA/UK, Aust. standards

    Marine

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

    Model Icu Voltage

    TL400NE

    TL400NE

    100 kA

    85 kA

    400 V AC 50 Hz

    415 V AC 50 Hz

    AC useShort circuit capacity

    Ics

    100 kA

    85 kA

    Dimensions (mm)

    140

    185

    Height 1)

    103

    103

    Depth

    TL400NE 3 pole

    TL400NE 4 pole

    360

    360

    Description Width kg

    7.1

    9.1

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    23/3813 - 121

    13

    TemBreak MCCBsMCCB isolating switches (non-auto MCCBs)

    Ampere

    rating (A)

    XS125NN3

    XE225NNC3

    XS250NN3

    XS400NN3

    XS630NN3

    3 pole

    Cat. No. 1)

    XS125NN4

    XE225NNC4

    XS250NN4

    XS400NN4

    XS630NN4

    4 pole

    Cat. No. 1)125

    250

    250

    400

    630

    Amprating (A)

    125

    225

    250

    400

    630

    Height 2)

    155

    160

    165

    260

    273

    Depth

    86

    67

    86

    103

    103

    Width

    3P 4P

    90

    105

    105

    140

    210

    120

    140

    185

    280

    Weight (kg)

    3P 4P

    1.3

    1.85

    1.85

    5

    9

    1.58

    2.4

    6.2

    12.2

    Short time

    rating (kA)1.8 kA for 1 sec

    3 kA for 1 sec

    4 kA for 1 sec

    5 kA for 0.3 sec

    9.6 kA for 0.3 sec

    Accepts MCCB accessories.

    Suitable for panelboards.

    Standards IEC 60947-2/AS/NZS 3947-2.

    Motor or motorised circuit isolation - no overcurrent protection.

    Notes: 1) Refer page 13 - 103 for additional technical details.2) Height excludes attached busbar.

    Dimensions (mm)

    Ordering details

    Base standards

    IEC 60947-2

    BS EN 60947 Part 2

    VDE 0660 Part 1

    AS/NZS 3947-2 Aust./NZ

    Approvals

    ASTA/UK, Aust. standards

    Marine

    Lloyds R/UK

    ABS/USA

    GL/GERMANY

    BV/FRANCE

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    24/3813 - 122

    13

    TemBreak MCCB accessoriesTemBreak standard combinations of internally mountedaccessories

    UVT rating

    A. Inst type

    AC 100 - 120 V

    AC 200 - 240 V

    AC 380 - 450 V

    DC 24 V

    DC 48 V

    DC 60 V

    DC 100 - 115 V

    DC 200 - 230 V

    B. Time delay type

    AC 100 - 120 V

    AC 200 - 240 V

    AC 380 - 450 V

    SHT rating

    AC 100 - 115 V

    AC 200 - 480 V

    AC 24 V

    AC 48 V

    DC 12 V

    DC 24 V

    DC 30 V

    DC 48 V

    DC 60 V

    DC 100 - 115 VDC 125 V

    DC 200 - 230 V

    AUX

    ALT

    SHT

    UVT

    Auxiliary switch

    Alarm switch

    Shunt trip

    Undervoltage trip

    Left pole

    Right polehandle

    i

    i

    i

    i

    Note: Available on indent only.i

    Internal accessories

    are NHP factory

    fit only

    XS 125PJXS-125CJXS-125NJXH-125NJ

    TL30F

    XH 160PJXS-250NJXH-250NJ

    XE-225NC

    XS400XH/XS400XS630XH/XS630XS800XH/XS800XS1250

    XS1600

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    25/3813 - 123

    13

    UXVC0001C

    2H1935BAC

    2H1935BBC

    2H1935BCC

    2H1935BDC

    2H1935BEC

    2H1936BAC

    2H1936BBC

    2H1936BDC

    2H1936BHC

    2H1947BAC

    2H1947BBC

    2H1947BCC

    2H1948BAC

    2H1948BBC

    UXUB0013B

    UXUB0014B

    UXUB0015B

    UXUB0016B

    UXUB0017B

    UXUB0018B

    UXUB0037B

    UXXB0019D

    UXXB0020D2H2383DAA

    2H2384DAA

    UXXB0026E

    UXXB0027E

    UXLB0001E

    2H2385DAA

    UXLB0027E

    UXLB0003E

    2H2387DAA

    UXLB0028E

    -

    TemBreak MCCB accessoriesAccessories to suit 125 AF, TL30F, TL100NJ 3)

    Undervoltage trip

    UVT controller

    Alarm switch

    Alarm & auxiliaryswitch

    Internal accessories (factory fit)

    Cat. No.

    Shunt trip

    (1 pole)

    Shunt trips

    (2, 3, 4 pole)

    Undervoltage

    trips

    Auxiliary

    switches

    Alarm

    switches

    Alarm &

    auxiliary switches

    Extra low

    or highmagnetic trip

    100-440 V AC / 48-250 V DC 1 P SHT

    110 V AC SHT (100-115 V)

    240 V AC SHT (200-480 V)

    24 V DC SHT

    48 V DC SHT

    110 V DC SHT (100-115 V)

    24 V AC SHT

    48 V AC SHT

    12 V DC SHT

    200 V DC SHT (200-230)

    AC coil 1)

    24 V DC coil 2)

    100-230 V DC coil 2)

    48 V DC coil 2)

    60 V DC coil 2)

    110 V AC instantaneous controller

    240 V AC instantaneous controller

    440 V AC instantaneous controller

    110 V AC time delay controller

    240 V AC time delay controller

    440 V AC time delay controller

    200-230 V DC controller

    AUX SW right hand 1 C / 3 P

    AUX SW right hand 2 C / 3 PAUX SW right hand 1 C / 4 P

    AUX SW right hand 2 C / 4 P

    AUX SW left hand 1 C

    AUX SW left hand 2 C

    ALT SW right hand / 3 P

    ALT SW right hand / 4 P

    ALT SW left hand

    ALT/AUX SW right hand 1 C / 3 P

    ALT/AUX SW right hand 1 C / 4 P

    ALT/AUX SW left hand 1 C

    Special selectivity, generator or marine applications

    Description

    Notes: 1) An AC UVT controller is required for 100-440 V AC.2) A DC UVT controller is needed for 200-230 V DC operation. None required for 24-110 V DC.3) AF = Ampere frame.

    XS125CS/20 Awith shunt trip fitted

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    26/3813 - 124

    13

    TRED0001

    TXED0005A

    TXED0006A

    UXRC0011A

    UXRC0012A

    UXMB0041C

    UXMB0057B

    UXMB0061C

    UXKB0017B

    UXKB0018B

    XFHA22T1HP12XR6BNA4

    TFJ22XU

    YASD22

    UXKB0013A

    -

    XKA2

    LOCTITE

    480 RESIN

    2H1407DAA

    2H1408DAA

    2A1785DAA

    2H1406DAA

    UXPD0031A

    UXPD0032A

    UXYD0007A

    UXYE0005A

    UXYC0013A

    TXED0010A

    XDM2-3

    UXYD0007A

    UXYE0005A

    UXYC0013A

    TXED0011A

    XDM2-4

    UPX3125UXQH0002B

    XS1250CRSK

    XAB2

    ELB125A

    TO400XS125

    TemBreak MCCB accessoriesAccessories to suit 125 AF, TL30F, TL100NJ 1)

    External accessories

    Cat. No.Attached

    busbar

    Tunnel Clamp

    terminals

    Rear connect

    studs

    Motor

    operators

    Mechanical

    interlocks

    Handleoperators

    Handle locks

    Terminal

    covers - front

    connect

    Terminal covers -

    rear connect

    Plug-in

    breaker parts

    3 pole 9)

    Plug-in

    breaker parts

    4 pole 8)

    TemPlugInterpole barrier

    OCR sealing kit

    Pole fillers

    Earth leakage

    block

    Adapter kit for TO400

    chassis

    3 P attached busbars (6 in kit)

    3 P solderless terminals (6 in kit) 2)

    4 P solderless terminals (8 in kit) 2)

    3 P rear connect studs (6 in kit)

    4 P rear connect studs (8 in kit)

    110 V AC motor

    240 V AC motor

    110 V DC motor

    3 P rear mech I/lock

    4 P rear mech I/lock

    Variable depth handle, door interlockingIP 65 rated variable depth handle, door interlocking

    IP 55 direct mount rotary handle 3)

    IP 65 metal variable depth handle

    Handle lock

    Key interlock (Fortress type) incl TFJ mechanism 4)

    Padlock attachment 5)

    Resin for XKA2

    3 P FC terminal cover

    4 P FC terminal cover

    IP 20 protection cover 6)

    Seal plate 7)

    3 P RC terminal cover

    4 P RC terminal cover

    Terminal and bolt

    Insulation plate

    AUX conn. block (MCCB side)

    3 P tulip blocks (6 in kit)

    3 P mounting base

    Terminal and bolt

    Insulation plate

    AUX Conn. block (MCCB side)

    4 P tulip blocks (8 in kit)

    4 P mounting base

    3 P TemPlugCat. No. for 1 only 9)

    OCR sealing kit

    For use with metal escutcheon covers

    Add-on earth leakage block with pre-trip alarm contacts

    Order one kit per breaker

    Description

    Notes: 1) AF = Ampere frame.2) Factory fit only.3) Flush plate included.4) Tech data Section 8.5

    ) Captive type. Resin fixing.6) 6 pieces required for 3 P / 8 pieces required for 4 P.7) Specify qty required (up to 2 pieces).8) Not suitable for TL100NJ types.9) A total of 4 individual barriers for 3 P, and 6 barriers required for 4 P.

    Tunnel ClampTerminals (Solderlessterminals)

    Rear connect studs

    Plug-in tulip blocks

    Plug-in base

    Rear interlock

    Attached busbar

    UXMB motor operator

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    27/3813 - 125

    13

    TemBreak MCCB accessoriesAccessories to suit 225 AF (XE225NC) 1)

    TFJ handle

    Terminal cover

    TFH Handle operator

    Notes: 1) AF = Ampere frame.2) Flush plate included.3) Tech data Section 8.4

    ) 4 barriers required per breaker.

    Internal accessories (factory fit)

    Cat. No.Shunt trips

    (2, 3, 4 pole)

    Auxiliary switches

    Alarm switches

    Alarm & auxiliary

    switches

    110 V AC SHT (100 - 115 V)

    240 V AC SHT (200 - 480 V)

    24 V DC SHT

    48 V DC SHT

    110 V DC SHT (100 - 115 V)

    AUX SW right hand 1 C

    AUX SW right hand 2 C

    AUX SW left hand 1 C

    AUX SW left hand 2 C

    ALT SW right hand

    ALT/AUX SW right hand 1 C

    2H0153CAB

    2H0153CBB

    2H0153CDB

    2H0153CEB

    2H0153CCB

    2H0156CAB

    2H0156CBB

    2H1613BAA

    2H1613CBA

    2H0157CAB

    2H0157CBB

    External accessoriesAttached busbar

    Tunnel clamp

    (Solderless) terminals

    Rear connect studs

    Mechanical

    interlocks

    Handle operators

    Handle locks

    Terminal cover

    - front connect

    - rear connect

    Interpole barrier

    3 P attached busbars (6)

    3 P solderless terminals (6)

    3 P rear connect studs (6)

    3 P rear mech. I/lock

    Variable depth handle, door interlockingIP 55 direct mount rotary handle 2)

    Lock plate

    Handle lock

    Key interlock (Fortress Type) incl TFJ mechanism 3)

    3 P FC terminal cover

    3 P RC terminal cover

    Interpole barrier 4)

    7B3BA1B

    2A1818CAA

    2H1081CAA

    2H0158CAA

    TFH23CBTFJ23CU

    UXKE0030A

    KGH7123A

    -

    2H1080CAA

    2H1079CAA

    TQQ3CA

    Description

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    28/3813 - 126

    13

    TemBreak MCCB accessoriesAccessories to suit 160 AF / 250 AF 10)

    Internal accessories (factory fit)

    Cat. No.

    Shunt trips

    Undervoltage trips

    Auxiliary switches

    Alarm switchesAlarm & Auxiliary

    switches

    Extra low or high

    magnetic trip

    110 V AC (100 - 115 V)

    240 V AC (200 - 480 V)

    24 V DC

    48 V DC

    110 V DC (100 - 115 V)

    24 V AC

    48 V AC

    12 V DC

    200 V DC (200-230 V)

    AC coil 1)

    24 V DC coil 2)

    100-230 V DC coil 2)

    48 V DC coil 2)60 V DC coil 2)

    110 V AC instantaneous controller

    240 V AC instantaneous controller

    440 V AC instantaneous controller

    110 V AC time delay controller

    240 V AC time delay controller

    440 V AC time delay controller

    200-230 V DC controller

    AUX SW right hand 1 C

    AUX SW right hand 2 C

    AUX SW left hand 2 C

    ALT SW right handALT / AUX SW right hand 1 C

    Special selectivity, generator or marine applications

    2H1937BAA

    2H1937BBA

    2H1937BCA

    2H1937BDA

    2H1937BEA

    2H1938BAA

    2H1938BBA

    2H1938BDA

    2H1938BHA

    2H1949BAB

    2H1949BBB

    2H1949BCB

    2H1950BAB2H1950BBB

    UXUB0013B

    UXUB0014B

    UXUB0015B

    UXUB0016B

    UXUB0017B

    UXUB0018B

    UXUB0037B

    2H1951BAA

    2H1952BAA

    UXXB0028B

    2H1953BAA2H1954BAA

    -

    External accessories

    Attached busbars

    Tunnel clamp

    terminals

    (solderlessterminals)

    Crimp lugs

    3 P attached busbars (6)

    4 P attached busbars (8)

    3 P solderless term (6) / XS 9)

    4 P solderless term (8) / XS9

    )3 P solderless term (6) / XH 9)

    4 P solderless term (8) / XH 9)

    Compression term (80 mm2)

    Compression term (100 mm2)

    TXJD0050B

    TXJD0051B

    2H2008DAB

    2H2008DBB2H2734DAA

    2H2734DBA

    80-3BA

    100-3BA

    Description

    Cat. No.Description

    Tunnel clampterminals

    Undervoltage trip

    UVT controller

    Alarm switch

    Alarm & auxiliaryswitch

    Note: Refer following page for footnotes.

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    29/3813 - 127

    13

    TemBreak MCCB accessoriesAccessories to suit 160 AF / 250 AF 10)

    Interpole barriers

    OCR sealing kit

    External accessories

    Cat. No.

    Rear connection

    studs

    Motor operators

    Mechanical

    interlocks

    Handle operators

    Handle lock

    Terminal covers

    Plug-in breaker

    parts 3 pole

    Plug-in breaker

    parts 4 pole

    TemPlug

    Interpole barriers

    Pole fillers

    Earth leakage block

    OCR sealing kit

    3 P rear connect studs (6)

    4 P rear connect studs (8)

    110 V AC motor 3)

    220 V AC motor 3)

    240 V AC motor 3)

    110 V DC motor 3)

    3 P rear mech int. / XS

    4 P rear mech nt. / XS

    3 P rear mech int./ XH

    4 P rear mech int./ XH

    Variable depth handle, door interlocking 3)

    IP 65 rated variable depth handle, door interlocking 3)

    IP 55 direct mount rotary handle mechanism 4)

    IP 65 metal variable depth handle

    Handle lock

    Key interlock (Fortress Type) incl TFJ mechanism 11)

    Padlock attachment 5)

    Resin for XKA2

    3 P FC terminal cover / XS

    4 P FC terminal cover / XS

    3 P FC terminal cover / XH

    4 P FC terminal cover / XH

    IP 20 protective cover 6)

    3 P RC terminal cover / XS4 P RC terminal cover / XS

    3 P RC terminal cover / XH

    4 P RC terminal cover / XH

    Seal plate 7)

    AUX conn. block (MCCB side)

    AUX conn. block (panel side)

    3 P tulip block / XS

    3 P tulip block / XH

    3 P mounting base

    AUX conn. block (MCCB side)

    AUX conn. block (panel side)

    4 P tulip block / XS

    4 P tulip block / XH

    4 P mounting base

    3 P TemPlug / XH only

    Interpole barrier / XS 8)

    Interpole barrier / XH 8)

    For use with metal escutcheon covers

    Add-on earth leakage block with pre-trip alarm (XH250)

    Add-on earth leakage block with pre-trip alarm (XS250)

    OCR sealing kit

    2H2266DAA

    2H2266DBA

    UXMB0046D

    UXMB0047D

    UXMB0058B

    UXMB0062C

    UXKB0019B

    UXKB0020B

    UXKB0021B

    UXKB0022B

    XFHA23S

    T1HP25XR6BNA4

    TFJ23SUYASD23

    UXKB0014A

    -

    XKA2

    LOCTITE

    480 RESIN

    2H2135DAB

    2H1410DAB

    2H2136DAA

    2H1412DAA

    2A1786DAA

    UXPD0027BUXPD0028B

    UXPD0033B

    UXPD0034B

    2H1406DAA

    UXYC0010A

    UXYB0004A

    TXJD0054A

    TXJD0058A

    XDM3-3

    UXYC0010A

    UXYB0004A

    TXJD0055A

    TXJD0059A

    XDM3-4

    UPX3250

    UXQH0002B

    UXQH0003B

    XAB3

    ELB250AH

    ELB250A

    XS250OCRSK

    Description

    Notes: 1) An AC UVT controller is required for 100-440 V AC.2) A DC UVT controller is needed for 200-230 V DC operation. None required for 24-110 V DC.3) Add UXFD0016A when required for XH250NJ & XH160PJ.4) Flush plate included.5) Captive type. Resin fixing.6) 6 pieces required for 3 P / 8 pieces required for 4 P.7) Specify quantity required (up to 2 pieces).8) 4 pieces required for 3 P (6 pieces required for 4 P).9) Factory fit only.10) AF = Ampere frame.11) Tech data, Section 8.

    Rear interlock

    UXMB motor operator

    XFH Handle operator

    Note: 400 Aaccessories refer

    Section 5

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    30/3813 - 128

    13

    TemBreak MCCB accessoriesNHP TemPlug

    Available for MCCBs from 12-400 Ampere

    Easily fitted using supplied hardware

    Low resistance connection

    Moulding constructed from UL approved glass filled polyester

    Polycarbonate terminal cover supplied as standard

    Assembly bolts directly to module gear plate

    Lowest watts loss and temperature rise

    Silver plated contacts with domed face for increased

    contact pressure

    Currentrating (A)

    12

    100

    125

    250

    250

    400

    MCCB

    XM30PB

    TL100F

    XH125NJ

    XS250NJ

    XH250NJ

    XS400 / 400

    Vertical typeCat. No.

    UPX330PB

    UPX3100F

    UPX3125

    UPXS250

    UPXH250

    UPX3440

    Horizontally mounted versions are indent items, please refer to NHP.

    (Horizontal type prefix is HBC3, for left or right mounting types)

    Cut-out for TemPlugs 125 to 400 AF

    TemPlug (125) / XM30PB TemPlug (250)

    Vertical mountedTemPlug/MCCB

    TemPlug (400)

    Ordering details

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    31/3813 - 129

    13

    Application dataSelectivity and Cascade tables at 400/415 VMCB to MCCB

    MCB to MCCB: thermal magnetic

    XS125NJ

    25

    XH125NJ

    XH125PJ

    TL100NJ

    50

    XH250NJ

    TL250NJ

    50

    XS400CJ

    35

    XH400SE

    65kA (RMS)

    XS125CJ

    18

    6

    6

    10

    10

    10

    1010

    10

    10

    6

    6

    2-20 A

    25-63 A

    0.5-32 A

    40-63 A

    0.5-32 A

    40 A80-125 A

    0.5-32 A

    40-63 A

    16-63 A

    16-20 A

    18/18

    18/18

    18/18

    18/18

    18/18

    18/184/18

    18/18

    18/18

    3/10

    3/10

    25/25

    20/25

    25/25

    20/25

    25/25

    20/254/25

    25/25

    20/25

    3/10

    3/10

    35/35

    20/25

    30/50

    25/25

    30/50

    25/254/25

    30/50

    25/25

    3/10

    3/10

    35/35

    30/30

    40/50

    30/30

    40/50

    30/3015/15

    40/50

    30/30

    -

    -

    XS250NJ

    25

    25/25

    25/25

    25/25

    25/25

    25/25

    25/2515/15

    25/25

    25/25

    -

    -

    -

    -

    35/35

    30/30

    35/35

    30/3010/10

    35/35

    30/30

    -

    -

    XS400SE

    XS400NJ

    50

    -

    -

    40/50

    30/30

    40/50

    30/3010/10

    40/50

    30/30

    -

    -

    -

    -

    40/50

    30/30

    40/50

    30/30-

    40/50

    30/30

    -

    -

    XX / YYGuide

    Selectivity Cascade

    DTCB6

    DTCB10

    DSRCBH & DSRCB

    DSRCBH & DSRCB

    DIN-T10H

    DTCB15

    SAFE-T

    SRCB

    Cascade

    The resultant cascade level with the XH630SE (65 kA) and XH250NJ (50 ka)MCCBs in series is 65 kA. This means that the XH630SE will back-up the

    XH250NJ MCCB to 65 kA, which is beyond its breaking capacity of 50 kA.

    Selectivity

    From the tables, the Selectivity level between the same two breakers,

    XH630SE and XH250NJ connected in series will be 50 kA. This means that

    for fault levels up to and including 50 kA the XH250NJ will trip before the

    XH630SE.

    Conclusion

    For short circuit currents up to and including 50 kA, the XH250NJ will trip

    before the XH630SE, therefore ensuring Selectivity. For fault levels above50 kA both breakers may trip, however, the XH630SE will back-up the

    XH250NJ to 65 kA.

    Range

    (A)

    Downstream

    MCB

    Upstream MCCB

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    32/3813 - 130

    13

    Application data TemBreak MCCBsSelectivity and Cascade tables at 400/415 V

    Upstream MCCB

    XS125CJ

    XS125NJ

    XH125NJ

    XH125PJ

    TL100NJ

    XH160PJ

    XE225NC

    XS250NJ

    XH250NJ

    XH250PJ

    TL250NJ

    XS400CJ

    XS400NJ

    XS400SE

    XH400PJ

    XH400SE

    XH400PE

    TL400NE

    XS630CJ

    XS630NJ

    XS630SE

    XH630PJ

    XH630SE

    XH630PE

    XS800NJ

    XS800SE

    XH800PJ

    XH800SE

    XH800PE

    XS1250SE

    XS1600SE

    kA(RMS)

    DownstreamMCCB

    XS400SE50

    TL400NEXH400SE

    65XS630SE

    50

    TL630NEXH630SE

    65XS800SE

    50

    TL800NEXH800SE

    65

    TL1250NEXS1250SE

    65

    18

    25

    50

    50

    85

    50

    18

    25

    50

    65

    85

    35

    50

    50

    65

    65

    65

    85

    42

    50

    50

    85

    65

    65

    50

    50

    85

    65

    65

    65

    85

    15/50

    25/50

    35/50

    35/50

    35/50

    25/50

    15/30

    15/50

    25/50

    -

    -

    -/50

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    15/50

    25/50

    35/65

    35/65

    35/65

    25/65

    15/30

    15/65

    25/65

    -

    -/65

    -/50

    -/65

    -/65

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    18/30

    25/30

    50/50

    50/50

    50/50

    50/50

    18/30

    25/50

    50/50

    10/50

    10/50

    10/50

    10/50

    10/50

    10/50

    10/50

    10/50

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    18/30

    25/30

    50/65

    50/65

    50/65

    50/65

    18/30

    25/65

    50/65

    10/65

    10/65

    10/65

    10/65

    10/65

    10/65

    10/65

    10/65

    -

    -/50

    -

    -/65

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    18/30

    25/30

    50/50

    50/50

    50/50

    50/50

    18/30

    25/50

    50/50

    25/50

    25/50

    25/50

    25/50

    25/50

    25/50

    25/50

    25/50

    25/50

    10/50

    10/50

    10/50

    10/50

    10/50

    10/50

    -

    -

    -

    -

    -

    -

    -

    18/30

    25/30

    50/65

    50/65

    50/65

    50/65

    18/30

    25/65

    50/65

    25/65

    25/65

    25/65

    25/65

    25/65

    25/65

    25/65

    25/65

    25/65

    10/50

    10/65

    10/65

    10/65

    10/65

    10/65

    -

    -/65

    -

    -

    -

    -

    -

    18/18

    25/30

    50/50

    50/50

    50/65

    50/50

    18/18

    25/35

    50/50

    50/65

    50/65

    35/42

    50/65

    50/65

    50/65

    50/65

    50/65

    65/65

    30/45

    30/65

    30/65

    30/65

    30/65

    30/65

    15/65

    15/65

    15/65

    15/65

    15/65

    -

    -

    XS1600SE85

    18/18

    25/30

    50/50

    50/50

    50/85

    50/50

    18/18

    25/35

    50/50

    50/65

    50/85

    35/42

    50/65

    50/65

    50/65

    50/65

    50/65

    85/85

    30/45

    30/85

    30/85

    30/85

    30/85

    30/85

    20/85

    20/85

    20/85

    20/85

    20/85

    20/65

    -

    XS2000NE100

    18/18

    25/30

    50/50

    50/50

    50/85

    50/50

    18/18

    25/35

    50/50

    50/65

    50/85

    35/42

    35/65

    50/65

    50/65

    50/65

    50/65

    50/85

    35/45

    35/85

    30/85

    30/85

    30/85

    30/85

    35/85

    20/85

    20/85

    20/85

    20/85

    35/65

    -

    XS2500NE100

    18/18

    25/30

    50/50

    50/50

    50/85

    50/50

    18/18

    25/35

    50/50

    50/65

    50/85

    35/42

    50/65

    50/65

    50/65

    50/65

    50/65

    50/85

    35/45

    35/85

    30/85

    30/85

    30/85

    30/85

    35/85

    20/85

    20/85

    20/85

    20/85

    35/65

    35/65

    XX / YY

    Guide

    Selectivity Cascade

    MCCB to MCCB: electronic and thermal magnetic

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    33/3813 - 131

    13

    Application data TemBreak MCCBsSelectivity and Cascade tables at 400/415 V

    Upstream MCCB

    XS125CJ

    XS125NJ

    XH125NJ/PJ

    XE225NC

    XS250NJ

    XH250NJ

    XS400CJ

    XS400NJ

    XS630CJ

    XS630NJ

    XS800NJ

    kA(RMS)

    DownstreamMCCB

    XH125NJ50

    XS250NJ25

    XH250NJ50

    XS400CJ35

    XS400NJ50

    XS800NJ50

    18

    25

    50

    18

    25

    50

    35

    50

    42

    50

    50

    -/50

    -/50

    -

    -

    -

    -

    -

    -

    -

    -

    -

    3/25

    3/25

    -

    -/25

    -

    -

    -

    -

    -

    -

    -

    3/50

    3/50

    -

    -/30

    -

    -

    -

    -

    -

    -

    -

    4/35

    4/35

    -

    -/30

    -

    -

    -

    -

    -

    -

    -

    4/50

    4/50

    -

    -/30

    4/50

    4/50

    -/50

    -

    -

    -

    -

    10/30

    10/30

    12/50

    8/30

    8/50

    10/50

    6/50

    6/50

    -

    -

    -

    XH800PJ85

    10/30

    10/30

    12/65

    8/30

    8/65

    10/65

    6/65

    6/65

    -/50

    -/85

    -/85

    XS630CJ42

    6/30

    6/30

    -

    6/25

    6/42

    -

    6/35

    -

    -

    -

    -

    XS630NJ50

    6/30

    6/30

    -

    6/30

    6/50

    -

    6/50

    -

    -

    -

    -

    XX / YY

    Guide

    Selectivity CascadeMCCB to MCCB: thermal magnetic

    Selectivity - Thermal magnetic MCCBs only.

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    34/3813 - 132

    13

    Type 1 short circuit co-ordinationMotor starter co-ordination tablefor DOL starting50 kA at 400-415 V to AS 3947-4-1

    Notes: 1) Use magnetic only breaker. Refer NHP for factory modification.2) Thermal or electronic overload relays may be used.3) Electronic overloads

    Fuses 65 kA. XH125NJ circuit breaker combinations limited to 50 kA, others 65 kA.

    Overloads may be changed to different types eg. thermal style to electronic.

    Some combinations also give Type 2 performance.

    0.37

    0.55

    0.75

    1.1

    1.5

    2.2

    3.0

    4.05.5

    7.5

    10

    11

    15

    18.5

    22

    30

    37

    4555

    75

    90

    110

    132

    150

    160

    185

    200

    250

    315

    1.1

    1.5

    1.8

    2.6

    3.4

    4.8

    6.5

    8.211

    14

    19

    21

    28

    34

    40

    55

    66

    80100

    130

    155

    200

    225

    250

    270

    310

    361

    425

    530

    XM30PB/1.4

    XM30PB/2

    XM30PB/2.6

    XM30PB/4.0

    XM30PB/5

    XM30PB/8

    XM30PB/8

    XM30PB/10XH125NJ/20

    XH125NJ/20

    XH125NJ/32

    XH125NJ/32

    XH125NJ/50

    XH125NJ/50

    XH125NJ/63

    XH125NJ/100

    XH125NJ/100

    XH125NJ/1251

    )XH125NJ/125 1)

    XH250NJ/250

    XH250NJ/250 1)

    XH250NJ/250 1)

    XS400SE/400

    XH400SE/400 2)

    XS400SE/400

    XH400SE/400 2)

    XS400SE/400

    XS630SE/630

    XS630SE/630

    CA 7-9

    CA 7-9

    CA 7-9

    CA 7-9

    CA 7-9

    CA 7-9

    CA 7-9

    CA 7-9CA 7-12

    CA 7-16

    CA 7-23

    CA 7-23

    CA 7-30

    CA 7-37

    CA 7-43

    CA 7-60

    CA 7-72

    CA 7-85CA 6-105-(El)

    CA 6-140-(El)

    CA 6-170-El

    CA 6-210-El

    CA 6-250-El

    CA 6-250-EI

    CA 6-300-El

    CA 6-300-EI

    CA 6-420-El/ CA 5-450

    CA 6-420-El/ CA 5-450CA 5-550

    CT 7-24

    CT 7-24

    CT 7-24

    CT 7-24

    CT 7-24

    CT 7-24

    CT 7-24

    CT 7-24CT 7-24

    CT 7-24

    CT 7-24

    CT 7-24

    CT 7-45

    CT 7-45

    CT 7-45

    CT 7-75

    CT 7-75

    CT 7-100CT 6-110

    CT 6-150

    CT 6-200

    CEF 1-41/42 3)

    CEF 1-41/42 3)

    CEF 1-41/41 3)

    CEF 1-41/42 3)

    CEF 1-41/42 3)

    CEF 1-41/42 3)

    CEF 1-52 3)

    CEF 1-52 3)

    1-1.6

    1-1.6

    2.4-4

    2.4-4

    2.4-4

    4-6

    6-10

    6-1010-16

    10-16

    16-24

    16-24

    18-30

    30-45

    30-45

    45-60

    60-75

    70-9085-110

    105-150

    140-200

    160-400

    160-400

    160-400

    160-400

    160-400

    160-400

    160-630

    160-630

    Approx.(amps)

    Motor size(kW)

    Terasaki circuitbreaker type

    Sprecher + Schuhcontactor type

    Sprecher + Schuhoverload type 2)

    Setting range(amps)

    TYPE 150 kA

    (Refer Part A section 1)

    Cat. No. CT 7-24Contactor CA 7-9 XM30PB

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    35/3813 - 133

    13

    Type 2 short circuit co-ordinationMotor starter co-ordination tablefor DOL starting50 kA at 400-415 V to AS 3947-4-1

    Notes: 1) Use magnetic only breaker or next higher circuit breaker/contactor combination. Refer NHP for factorymodification.

    2) Use with separate mounting bracket.3) Thermal or electronic overload relays may be used.4) Electronic overloads.Combinations based on the thermal overload relay tripping before the circuit breaker at overloadcurrents up to the motor locked rotor current.

    0.37

    0.55

    0.75

    1.1

    1.5

    2.2

    3

    4

    5.5

    7.5

    11

    15

    18.5

    22

    30

    37

    45

    55

    75

    90

    110

    132

    150

    160

    200

    200

    250

    320

    1.1

    1.5

    1.8

    2.6

    3.4

    4.8

    6.5

    8.2

    11

    14

    21

    28

    34

    40

    55

    66

    80

    100

    130

    155

    200

    225

    250

    270

    361

    361

    425

    538

    XM30PB/1.4

    XM30PB/2

    XM30PB/2.6

    XM30PB/4.0

    XM30PB/5

    XM30PB/8

    XM30PB/10

    XM30PB/12

    XH125NJ/20

    XH125NJ/20

    XH125NJ/32

    XH125NJ/50

    XH125NJ/50

    XH125NJ/63

    XH125NJ/100

    XH125NJ/100

    XH125NJ/125

    XH125NJ/125 1)

    XH250NJ/250

    XH250NJ/250

    XH250NJ/250 1)

    XS400SE/400

    XS400SE/400

    XS400SE/400

    XS400SE/400

    XS400SE/400

    XS630SE/630

    XS630SE/630

    CA 7-9

    CA 7-9

    CA 7-9

    CA 7-16

    CA 7-16

    CA 7-16

    CA 7-30

    CA 7-30

    CA 7-30

    CA 7-30

    CA 7-30

    CA 7-43

    CA 7-43

    CA 7-43

    CA 7-85

    CA 7-85

    CA 6-105-(El)

    CA 6-105(El)

    CA 6-140-(El)

    CA 6-170-El

    CA 6-210-El

    CA 6-210-El

    CA 6-250-EI

    CA 6-300-El

    CA 6-420-El

    CA 5-450

    CA 5-700

    CA 5-700

    CT 7-24-1.6

    CT 7-24-1.6

    CT 7-24-2.4

    CT 7-24-4

    CT 7-24-4

    CT 7-24-6

    CT 7-24-10

    CT 7-24-10

    CT 7-24-16

    CT 7-24-16

    CT 7-24-24

    CT 7-45-30

    CT 7-45-45

    CT 7-45-45

    CT 7-75 2)

    CT 7-75 2)

    CT 6-90

    CT 6-110

    CT 6-150

    CT 6-200

    CEF 1-41/42 4)

    CEF 1-41/42 4)

    CEF 1-41/42 4)

    CEF 1-41/42 4)

    CEF 1-41/42 4)

    CEF 1- 22 2)

    CEF 1- 52 2)

    CEF 1- 52 2)

    1-1.6

    1-1.6

    1.6-2.4

    2.4-4

    2.4-4

    4-6

    6-10

    6-10

    10-16

    10-16

    16-24

    18-30

    30-45

    30-45

    45-60

    60-75

    70-90

    85-110

    105-150

    140-200

    160-400

    160-400

    160-400

    160-400

    160-400

    160-400

    160-630

    160-630

    Approx.(amps)

    Motor size(kW)

    Terasaki circuitbreaker type

    Sprecher + Schuhcontactor type

    Sprecher + Schuhoverload type 3)

    Setting range(amps)

    TYPE 250 kA

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    36/3813 - 134

    13

    Type 2 short circuit co-ordinationMotor starter co-ordination tablefor DOL starting65 kA, 400-415 V to AS 3947-4-1

    Notes: 1) Thermal or electronic overload relays may be used.2) Use with separate mounting bracket.3) Electronic overloads.Combinations based on the overload relay tripping before the circuit breaker at overloadcurrents up to the motor locked rotor current.

    0.37

    0.55

    0.75

    1.1

    1.5

    2.2

    3

    4

    5.5

    7.5

    11

    15

    18.5

    22

    30

    37

    45

    55

    75

    90

    110

    132

    150

    160

    200

    200

    250320

    1.1

    1.5

    1.8

    2.6

    3.4

    4.8

    6.5

    8.2

    11

    14

    21

    28

    34

    40

    55

    66

    80

    100

    130

    155

    200

    225

    250

    270

    361

    361

    425538

    XM30PB/1.4

    XM30PB/2

    XM30PB/2.6

    XM30PB/4.0

    XM30PB/5

    XM30PB/8

    XM30PB/8

    XM30PB/12

    TL30F/20A

    TL30F/30A

    TL30F/30A

    TL100NJ/50A

    TL100NJ/50A

    TL100NJ/63A

    TL100NJ/100A

    TL100NJ/100A

    TL100NJ/100A

    XH400SE/250

    XH400SE/250

    XH400SE/250

    XH400SE/250

    XH400SE/400

    XH400SE/400

    XH400SE/400

    XH400SE/400

    XH400SE/400

    XH630SE/630XH630SE/630

    CA 7-9

    CA 7-9

    CA 7-9

    CA 7-16

    CA 7-16

    CA 7-16

    CA 7-30

    CA 7-30

    CA 7-30

    CA 7-30

    CA 7-30

    CA 7-43

    CA 7-43

    CA 7-43

    CA 7-72

    CA 7-72

    CA 6-105-(El)

    CA 6-105-(El)

    CA 6-140-(El)

    CA 6-170-El

    CA 6-210-El

    CA 6-210-El

    CA 6-250-EI

    CA 6-300-El

    CA 6-420-El

    CA 5-450

    CA 5-700CA 5-700

    CEP 7

    CEP 7

    CEP 7

    CEP 7

    CEP 7

    CEP 7

    CEP 7

    CEP 7

    CEP 7

    CEP 7

    CEP 7

    CEP 7

    CEP 7

    CEP 7

    CEP 7

    CEP 7

    CT 6-90CT 6-110

    CT 6-150

    CT 6-200

    CEF 1-41/42 3)

    CEF 1-41/42 3)

    CEF 1-41/42 3)

    CEF 1-41/42 3)

    CEF 1-41/42 3)

    CEF 1- 22 2)

    CEF 1- 522

    )CEF 1- 52 2)

    1.0-2.9

    1.0-2.9

    1.0-2.9

    1.6-5

    1.6-5

    3.7-12

    3.7-12

    3.7-12

    3.7-12

    12-32

    12-32

    12-32

    12-37

    14-45

    26-85

    26-85

    70-90

    85-110

    105-150

    140-200

    160-400

    160-400

    160-400

    160-400

    160-400

    160-400

    160-630160-630

    Approx.(amps)

    Motor size(kW)

    Terasaki circuitbreaker type

    Sprecher + Schuhcontactor type

    Sprecher + Schuhoverload type 1)

    Setting range(amps)

    TYPE 265 kA

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    37/3813 - 135

    13

    Type 2 short circuit co-ordinationMotor starter co-ordination tablefor DOL starting85 kA, 400-415 V to AS 3947-4-1

    Notes: 1) Thermal or electronic overload relays may be used.Combinations based on the overload relay tripping before the circuit breaker at overload currents upto the motor locked rotor current.

    0.37

    0.55

    0.75

    1.1

    1.5

    2.2

    3

    4

    5.5

    7.5

    9

    10

    11

    15

    18.5

    22

    30

    37

    45

    55

    75

    90

    110

    132

    160

    200

    1.1

    1.5

    1.8

    2.6

    3.4

    4.8

    6.5

    8.2

    11

    14

    17

    19

    21

    28

    34

    40

    55

    66

    80

    100

    135

    160

    200

    230

    270

    361

    XM30PB/1.4

    XM30PB/2

    XM30PB/2.6

    XM30PB/4

    XM30PB/5

    XM30PB/8

    XM30PB/8

    XM30PB/10

    TL100NJ/20

    TL100NJ/20

    TL100NJ/32

    TL100NJ/32

    TL100NJ/32

    TL100NJ/50

    TL100NJ/50

    TL100NJ/63

    TL100NJ/100

    TL100NJ/100

    TL250NJ/160

    TL250NJ/160

    TL250NJ/250

    TL250NJ/250

    TL250NJ/250

    TL400NE/400

    TL400NE/400

    TL400NE/400

    CA 7-9

    CA 7-9

    CA 7-9

    CA 7-16

    CA 7-16

    CA 7-30

    CA 7-30

    CA 7-30

    CA 7-30

    CA 7-30

    CA 7-30

    CA 7-30

    CA 7-30

    CA 7-43

    CA 7-43

    CA 7-43

    CA 7-72

    CA 7-72

    CA 6-105

    CA 6-105

    CA 6-210-El

    CA 6-210-El

    CA 6-210-EI

    CA 6-210-El

    CA 6-300-El

    CA 6-420-El

    CEP 7-M32-2.9-10

    CEP 7-M32-2.9-10

    CEP 7-M32-2.9-10

    CEP 7-M32-2.9-10

    CEP 7-M32-5-10

    CEP 7-M32-12-10

    CEP 7-M32-12-10

    CEP 7-M32-12-10

    CEP 7-M32-12-10

    CEP 7-M32-32-10

    CEP 7-M32-32-10

    CEP 7-M32-32-10

    CEP 7-M32-32-10

    CEP 7-M32-32-10

    CEP 7-M37-37-10

    CEP 7-M45-45-10

    CEP 7-M85-85-10

    CEP 7-M85-85-10

    CEP 7-M85-85-10

    CEF 1-11/12

    CEF 1-11/12

    CEF 1-11/12

    CEF 1-41/42/52

    CEF 1-41/42/52

    CEF 1-41/42/52

    CEF 1-41/42/52

    1.0-2.9

    1.0-2.9

    1.0-2.9

    1.0-2.9

    1.6-5

    3.7-12

    3.7-12

    3.7-12

    3.7-12

    12-32

    12-32

    12-32

    12-32

    12-32

    12-37

    14-45

    26-8526-85

    26-85

    0.5-180

    0.5-180

    0.5-180

    160-630

    160-630

    160-630

    160-630

    Approx.FLC (A)at 415 V

    Motor size(kW)

    Terasaki circuitbreaker type

    Sprecher + Schuhcontactor type

    Sprecher + Schuhoverload type 1)

    Setting range(amps)

    TYPE 285 kA

  • 7/24/2019 Pt c 2007 Sec 13b Lr

    38/38

    Nowf

    its

    MCCB

    sto

    800A