TemBreak 1 MCCBs 125 A 400 A Technical dataRatings charts, selection guides MCCBs and accessories
Tembreak 1 Ratings charts selection guides 30 - 400 A 13 - 100 to 13 - 105
XS125CS, XS125NS 16 - 125 A 13 - 106XS125CJ, XS125NJ 20 - 125 A 13 - 107XH125NJ 20 - 125 A 13 - 108XH125PJ 20 - 125 A 13 - 109XE225NC 125 - 225 A 13 - 110XH160PJ 160 A 13 - 111XS250NJ, XH250NJ 160 - 250 A 13 - 112XH250PJ, XH400PJ 160 - 400 A 13 - 113XS400CJ, XS400NJ 250 - 400 A 13 - 114XS400SE, XH400SE 250 - 400 A 13 - 115XH400PE 250 - 400 A 13 - 116
TL30F, TL100F, TL100C 15 - 100 A 13 - 117TL100NJ 20 - 100 A 13 - 118TL250NJ 160 - 250 A 13 - 119TL400NE 400 A 13 - 120Switch disconnectors (non-auto MCCBs) 125 - 630 A 13 - 121Accessories for the above MCCBs (for 400 A refer section 5) 13 - 122 to 13 - 127NHP TemPlug accessory 13 - 128Selectivity and Cascade data MCB/MCCBs 13 - 129 to 13 - 131Type 1 and 2 Motor starter co-ordination tables 13 - 132 to 13 - 135
Section 13
13 - 99
TemBreak1MC
CBsnow
availablewith
superior
TemBreak2IP
65handles
13
-
7/24/2019 Pt c 2007 Sec 13b Lr
2/3813 - 100
13
Standard TemBreak circuit breakerSelection guide ratings
Rated current (A).In NRC Nominal rated current
ASR Adjustable setting range
Rated current at 40C
AC RATED INSULATION VOLTAGE (Ui)
AC RATED BREAKING CAPACITY sym RMS [kA]
IEC 60947-2 [Icu] IEC 60947-2 [Ics] 1100V
AS/NZS 3947-2 [Icu] AS/NZS 3947-2[Ics] 1000V
Note: Rated Impulse withstand voltage 690V
Uimp (kV) is 8kV on all XS, XE and XH MCCBs 660V
500V
440V
415V
400V
380V
240V
AS 2184 440V
415V
NEMA AB-1 600V
480V
without Inst. 240-690V
DC RATED BREAKING 250V
CAPACITY (kA) 125V
RATED SHORT TIME CURRENT RMS [kA] [Icw]
DIMENSIONS (mm)
a
b
c
d
Weight (kg) marked standard typeCONNECTION AND MOUNTINGS
front terminal screw
connect (FC) a tt ached f la t bar
solderless terminal (PWC)
rear bolt stud
connect (RC) flat bar s tud
plug-in (PM) for sw itchboard
for distribution board
draw-out (DO)
STANDARD FEATURES
contact indicator
trip button
PROTECTIVE FUNCTIONS
Electronic type
Adjustable LTD, STD & INST
Adjustable GFT or Adjustable PTA (option)
Trip indicators (option) (contacts)
Thermal-magnetic type
thermal and fixed magnetic trips
thermal and adjustable magnetic trips
adjustable thermal and fixed magnetic trips
adjustable thermal and magnetic trips
ACCESSORIES (option) CODE
Internally auxiliary s witch AUX
mounted alarm switch ALT
shunt trip SHT
undervoltage trip UVT
Externally motor operator MOT
mounted external pane l mounte d ty pe XFE
operating breaker mounted type TFJ
handle variable depth type XFH
IP 65 handle variable depth type TLK
extension handle
mechanical interlock front type
mechanical interlock rear type
mechanical interlock cable type
key interlockhandle holder
handle lock
captive padlock attachment
terminal cover front connect type
terminal cover rear/plug-in type
interpole barriers
accessories lead terminals
OCR sealing kit
Type
Ampere frame
Number of poles
Outside view
Notes:1) 1 Pole breaker only, XS125CS and XS125NS respectively.2
) 2 pole breaker is a 3 pole breaker with the centre pole omitted. Supplied as standard. Optional standard.
Yes or available. Not available
Indent only
XS125CS XS125CJ
1P 1) 2P 2) 3P 4P
125A
1P 1) 2P 2) 3P 4P
125A
16
20
25
32
40
690
10/5
14/7
18/9
18/9
14/7
14
18
10
30
155
86
104
0.51
50
63
80
100
125
12.5
20
32
40
63
80
20
32
50
63
100
125
NRC
20
32
50
63
100
125
NRC ASR
min max
XS125NS XS125NJ
7.5/3.8
10/5
14/7
18/9
18/9
25/13
10
10
15
90
1.3
120
1.58
16
20
25
32
40
690
22/11
25/13
25/13
30/15
25/13
25
30
15
30
155
86
104
0.51
50
63
80
100
125
12.5
20
32
40
63
80
20
32
50
63
100
125
NRC
20
32
50
63
100
125
NRC ASR
min max
5/2.5
5/2.5
12/6
22/11
25/13
25/13
30/15
25/13
12
22
15
20
90
1.3
120
1.58
ii
i
-
7/24/2019 Pt c 2007 Sec 13b Lr
3/3813 - 101
13
Standard TemBreak circuit breakerSelection guide ratings
3P 4P
125A
XH125NJ
20
32
50
63
100
125
690
8/4
8/4
25/13
42/21
50/25
50/25
50/25
85/43
50
50
25
42
40
40
90
155
86
104
1.3
12.5
20
32
40
63
80
20
32
50
63
100
125
NRC ASR
min max
120
1.58
160
250
100
160
160
250
NRC ASR
min max
140
2.4
3P
225A
XE225NC
125
150
175
690
10/5
15/7.5
15/7.5
18/9
18/9
25/13
15
18
15
10
15
105
165
67
82
1.4
(Bar)
690
8/4
8/4
22/11
25/13
25/13
25/13
35/18
50/25
30
35
22
25
40
40
105
165
86
107
1.85
(Bar)
200
250
NRC
3P 4P
250A
XS250NJ
160
250
100
160
160
250
NRC ASR
min max
140
2.6
690
15/7.5
15/7.5
25/13
42/21
50/25
50/25
50/25
85/43
50
50
25
42
40
40
105
165
103
124
2.1
(Bar)
3P 4P
250A
XH250NJ
250
400
160
250
250
400
NRC ASR
min max
185
6.1
690
ICU/ICS
16/8
16/8
22/11
30/15
30/15
35/18
35/18
50/25
36
36
22
30
40
40
140
260
103
131
4.7
(Bar)
3P 4P
400A
XS400CJ
250
400
160
250
250
400
NRC ASR
min max
185
6.1
690
ICU/ICS
18/9
18/9
30/15
42/12
50/25
50/25
50/25
85/43
50
50
30
42
40
40
140
260
103
131
4.7
(Bar)
3P 4P
400A
XS400NJ
i i
-
7/24/2019 Pt c 2007 Sec 13b Lr
4/3813 - 102
13
Standard TemBreak circuit breakerSelection guide ratings
Rated current (A).In NRC Nominal rated current
Rated current at 40C
AC RATED INSULATION VOLTAGE (Ui)
AC RATED BREAKING CAPACITY sym RMS [kA] 1100V
IEC 60947-2 [Icu] IEC 60947-2 [Ics] 1000V
AS/NZS 3947-2 [Icu] AS/NZS 3947-2[Ics] 690V
Note: Rated Impulse withstand voltage 660V
Uimp (kV) is 8kV on all XS, XE and XH MCCBs 500V
440V
415V
400V
380V
240V
AS 2184 440V
415V
NEMA AB-1 600V
480V
without Inst. 240-690V
DC RATED BREAKING 250V
CAPACITY (kA) 125V
RATED SHORT TIME CURRENT RMS [kA] [Icw]
DIMENSIONS (mm)
a
b
c
d
Weight (kg) marked standard typeCONNECTION AND MOUNTINGS
front terminal screw
connect (FC) a tt ached f la t bar
solderless terminal (PWC)
rear bolt stud
connect (RC) flat bar s tud
plug-in (PM) for sw itchboard
for distribution board
draw-out (DO)
STANDARD FEATURES
contact indicator
trip button
PROTECTIVE FUNCTIONS
Electronic type
Adjustable LTD, STD & INST
Adjustable GFT or Adjustable PTA (option)
Trip indicators (option) (contacts)
Thermal-magnetic type
thermal and fixed magnetic trips
thermal and adjustable magnetic trips
adjustable thermal and fixed magnetic trips
adjustable thermal and magnetic trips
ACCESSORIES (option) CODE
Internally auxiliary s witch AUX
mounted alarm switch ALT
shunt trip SHT
undervoltage trip UVT
Externally motor operator MOT
mounted external pane l mounte d ty pe XFE
operating breaker mounted type TFJ
handle variable depth type XFH
IP 65 handle variable depth type TLK
extension handle
mechanical interlock front type
mechanical interlock rear type
mechanical interlock cable type
key interlockhandle holder
handle lock
captive padlock attachment
terminal cover front connect type
terminal cover rear/plug-in type
interpole barriers
accessories lead terminals
OCR sealing kit
Type
Ampere frame
Number of poles
Outside viewNotes:
Supplied as standard. Optional standard.
Yes or available. Not available
Indent onlyi
3P 4P
30A
TL30F
15
20
30
690
25/13
25/13
42/31
120/60
120/60
120/60
120/60
120/60
120
120
25
42
40
40
90
155
86
104
1.3
NRC
120
1.58
i 3P 4P
100A
TL100F
15
20
30
40
50
690
25/13
25/13
60/30
120/60
120/60
120/60
120/60
120/60
120
120
42
75
40
40
105
165
125
143
3.2
NRC
60
75
100
140
3.8
i 3P
125
150
175
200
225
NRC
TL225F
690
25/13
25/13
60/30
120/60
120/60
120/60
120/60
120/60
120
120
60
75
40
40
140
260
133
167
6
(Bar)
225A
-
7/24/2019 Pt c 2007 Sec 13b Lr
5/3813 - 103
13
Non-automatic circuit breakerSelection guide ratings
Type
Ampere frame
Number of poles
Outside viewNotes:
Supplied as standard. Optional standard.
Yes or available. Not available
Indent only
RATINGS AC
RATED OPERATIONAL VOLTAGE (V) DC
AS/NZS 3947-2 IEC 60947-2
RATED SHORT CIRCUIT MAKING CAPACITY peak/kA
RATED SHORT TIME CURRENT RMS [kA]
DIMENSIONS (mm)
a
b
c
d
Weight (kg) marked standard type
CONNECTION AND MOUNTINGS
front terminal screw
connect (FC) a tt ached fl at bar
solderless terminal (PWC)
rear bolt stud
connec t (RC) fla t bar stud
plug-in (PM) for switchboar d
for distribution board
draw-out (DO)
STANDARD FEATURES
ON-OFF colour indicator
trip button
ACCESSORIES (option) CODE
Internally auxiliary switch AUX
mounted alarm switch ALT
shunt trip SHT
undervoltage trip 1) UVT
Externally motor operator MOT
mounted external panel mounted type XFEoperating breaker mounted type TFJ
handle variable depth type XFH
IP 65 handle variable depth type TLK
extension handle
mechanical interlock front type
mechanical interlock rear type
handle holder
handle lock
terminal cover front connect type
terminal cover rear connect/plug-in type
interpole barriers
accessories lead terminal block 3)
door flange
IP 20 protection plug in type
Maximum switching current AC
DC
Utilisation Category
Endurance number of operations without current
number of operations with current
i
3P 4P
125A 250A
XS125NN
690
250
2.5
1.8 (1 sec)
90
155
86
104
1.1
2)
750
313
AC-23A
7000
1000
120
1.4
690
250
5.5
3 (1 sec)
105
160
60
83
2.1
2)
1500
625
AC-23A
7000
1000
690
250
6
4 (1 sec)
105
165
86
107
1.85
2)
1500
625
AC-23A
7000
1000
140
2.4
690
250
9
5 (0.3 secs)
140
260
103
131
4.7
2)
2400
1000
AC-23A
4000
1000
185
6.1
XE250NNC
3P 4P
250A
XS250NN
3P 4P
400A
XS400NN
Notes:1) For AC UVT, a UVT Controller is mounted externally.2) Line side interpole barriers are supplied as standard.3) Draw-out leads, horizontally.4) Draw-out leads, vertically.
i i i3P
-
7/24/2019 Pt c 2007 Sec 13b Lr
6/3813 - 104
13
Rated current (A).In NRC Nominal rated current
ASR Adjustable setting range
Rated current at 40C
AC RATED INSULATION VOLTAGE (Ui)
AC RATED BREAKING CAPACITY sym RMS [kA]IEC 60947-2 [ Icu] IEC 60947-2[I cs] 1100V
AS/NZS 3947-2 [Icu] AS/NZS 3947-2[Ics] 1000V
Note: Rated Impulse withstand voltage 690V
Uimp (kV) is 8kV on all XS, XE and XH MCCBs 500V
440V
415V
400V
240V
without Inst. 240-690V
DC RATED BREAKING 250V
CAPACITY (kA) 125V
RATED SHORT TIME CURRENT RMS [kA] [Icw]
DIMENSIONS (mm)
a
b
c
d
Weight (kg)
marked standard typeCONNECTION AND MOUNTING
front terminal screw
connect (FC) a ttached fl at bar
solderless terminal (PWC)
rear bolt stud
connect (RC) f la t bar s tud
p lug- in (PM) for switchboard
for distribution board
draw-out (DO)
STANDARD FEATURES
contact indicator
trip button
PROTECTIVE FUNCTIONS
Electronic type
Adjustable LTD, STD & INST
Adjustable GFT or Adjustable PTA (option)
Trip indicators (option) (contacts)
Thermal-magnetic type
thermal and fixed magnetic tripsthermal and adjustable magnetic trips
adjustable thermal and fixed magnetic trips
adjustable thermal and magnetic trips
ACCESSORIES (option) CODE
Internally auxiliary s witch AUX
mounted alarm switch ALT
shunt trip SHT
undervoltage trip UVT
Externally motor operator MOT
mounte d ope rating bre aker mounted type TFJ
handle variable depth type XFH
IP 65 handle variable depth type TLK
extension handle
mechanical interlock front type
mechanical interlock rear type
mechanical interlock cable type
key interlock
handle holder
handle lock
captive padlock attachment
terminal cover front connect type
terminal cover rear/plug-in type
interpole barriers
accessories lead terminals
OCR sealing kit
TypeAmpere frame
Number of polesOutside view
Notes:1) Adjustable ground fault available on indent,
fitted externally.2) LED indicators only or LED contacts, please specify.
Supplied as standard. Optional standard.
Yes or available. Not available
Available on indent onlyi
3P 4P
XH125PJ125A
20
32
50
63
100
125
690
8/4
25/13
42/21
50/50
50/50
85/50
40
40
90
155
86
104
1.3
12.5
20
32
40
63
80
20
32
50
63
100
125
NRC ASR
min max
120
1.6
3P
XH160PJ160A
160
690
15/7.5
23/13
42/21
50/50
50/50
85/50
40
40
105
165
103
124
2.1
(Bar)
100 160
NRC ASR
min max
140
2.6
3P
XH250PJ250A
250
690
18/9
42/15
42/21
65/50
65/50
85/50
40
40
140
260
103
145
4.7
(Bar)
160 250
NRC ASR
min max
185
6.1
3P 4P
XH400PJ400A
250
400
690
ICU/ICS
18/9
30/15
42/21
65/50
65/50
85/50
5
40
40
5 (0.3 sec)
140
260
103
145
4.7
(Bar)
125
250
250
400
NRC ASR
min max
185
6.1
3P 4P
XH630PJ630A
400
630
690
ICU/ICS
45/23
65/33
85/43
85/50
100/50
125/163
40
40
210
273
103
145
9
250
400
400
630
NRC ASR
min max
280
11.5
i
TemBreak PlusSelection guide PowerBreaker Series Ics = 50 kA
Ratings
-
7/24/2019 Pt c 2007 Sec 13b Lr
7/3813 - 105
13
4P
XH800PJ800A
800
690
ICU/ICS
45/23
65/33
85/43
85/50
100/50
125/63
40
40
210
273
103
145
9
500 800
NRC ASR
min max
280
11.5
3P 4P
XH400PE400A
250
400
690
ICU/ICS
20/10
42/21
65/50
65/50
65/50
100/50
5
5 (0.3 sec)
140
260
103
14
4.8
(Bar)
1)
2)
125
200
250
400
NRC ASR
min max
185
6.2
3P 4P
XS400SE400A
160
250
400
690
ICU/ICS
18/9
30/15
42/21
50/25
50/25
85/43
5
5 (0.3 sec)
140
260
103
131
4.8
(Bar)
1)
2)
80
125
200
160
250
400
NRC ASR
min max
185
6.2
3P 4P
XH400SE400A
160
250
400
690
ICU/ICS
20/10
42/21
65/33
65/33
65/33
100/50
5
5 (0.3 sec)
140
260
103
131
4.8
(Bar)
1)
2)
80
125
200
160
250
400
NRC ASR
min max
185
6.2
i i
SelectivitySeries SE
PowerBreakerSeries (contd)
3P 4P
TL100NJ100A
20
32
50
63
100
690
85/85
85/85
85/85
100/100
40
40
90
235
86
104
2.2
12.5
20
32
40
63
20
32
50
63
100
NRC ASR
min max
120
2.7
3P 4P
TL250NJ250A
160
250
690
25/25
70/70
85/85
85/85
100/100
130/130
40
40
105
360
103
145
7.1
(Bar)
100
160
160
250
NRC ASR
min max
185
9.1
3P 4P
TL400NE400A
400
690
ICU/ICS
25/25
70/70
85/85
85/85
100/100
130/130
140
360
103
145
7.1
(Bar)
200 400
NRC ASR
min max
185
9.1
LimitorBreaker SeriesIcs = 65 - 85kA
-
7/24/2019 Pt c 2007 Sec 13b Lr
8/3813 - 106
13
TemBreak MCCBsXS125 single pole series (CS / NS)
XS125CS (14 kA)
16
20
25
3240
50
63
80
100
125
Ampererating
XS125CS 16 1
XS125CS 20 1
XS125CS 25 1
XS125CS 32 1XS125CS 40 1
XS125CS 50 1
XS125CS 63 1
XS125CS 80 1
XS125CS 100 1
XS125CS 125 1
1 poleCat. No.
Notes: 1) An internal shunt trip may be mounted in anXS125CS/NS MCCB.Other accessories are external.
Fixed thermal and magnetic trip.
Current rating @ 45C 16 A - 125 A.
Standards AS/NZS 3947-2.
Breaking capacity at 250 V DC, 500 V AC.
Dimensions (mm)
30
Height
86
Depth
0.5
kg
XS125CS/NS 155
Description Width
Model I/C Voltage
XS125CSXS125NS
14 kA25 kA
240 V 50 Hz240 V 50 Hz
Short circuit capacity
Base standards
IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2/Aust./NZ
AS 2184-1990/Australia
JIS C 8372/JAPAN
JEC 160/JAPAN
Approvals
ASTA/UK, Aust. standards
Marine
NK/JAPAN
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
Ampererating
1 poleCat. No.
XS125NS (25 kA)
16
20
25
32
40
50
63
80
100
125
XS125NS 16 1
XS125NS 20 1
XS125NS 25 1
XS125NS 32 1
XS125NS 40 1
XS125NS 50 1
XS125NS 63 1
XS125NS 80 1
XS125NS 100 1
XS125NS 125 1
-
7/24/2019 Pt c 2007 Sec 13b Lr
9/3813 - 107
13
XS125NJ 20 2
XS125NJ 32 2
XS125NJ 50 2
XS125NJ 63 2
XS125NJ 100 2XS125NJ 125 2
TemBreak MCCBsXS125 series (CJ/NJ)
155
155155
155
Height
90
9090
120
Width
XS125NJ (25 kA) 3 pole
12.5
20
32
40
63
80
XS125NJ 20 3
XS125NJ 32 3
XS125NJ 50 3
XS125NJ 63 3
XS125NJ 100 3
XS125NJ 125 3
20
32
50
63
100
125
20
32
50
63
100
125
XS125NJ (25 kA) 4 pole
12.5
20
32
40
63
80
XS125NJ 20 4
XS125NJ 32 4
XS125NJ 50 4
XS125NJ 63 4
XS125NJ 100 4
XS125NJ 125 4
20
32
50
63
100
125
20
32
50
63
100
125
Notes: 1) MCCBs only.2) Poles in series. Refer applications Section 13.3) 2 pole models use a 3 pole body with centre pole disabled.
Special low instantaneous magnetic, generator protection MCCBs availableon request.
Adjustment range 63 - 100% of nominal current rating.
Standards AS/NZS 3947-2.
Adjustable thermal and fixed magnetic trip.
Dimensions (mm)
86
8686
86
Depth
1.3
1.31.3
1.58
kg
XS125CJ 3 pole
XS125NJ 2 poleXS125NJ 3 pole
XS125NJ 4 pole
Description
Model I/C Voltage
XS125CJ
XS125NJ
18 kA
25 kA
400 V 50 Hz
400 V 50 Hz
Short circuit capacity
Base standards
IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2/Aust./NZ
AS 2184-1990/Australia 1)
JIS C 8372/JAPAN
JEC 160/JAPAN
Approvals
ASTA/UK, Aust. standards
Marine
NK/JAPAN
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
DNV NORWAY
DC use I/C 2) Voltage
XS125CJ
XS125NJ
10 kA
15 kA
250 V DC
250 V DC
XS125NJ (25 kA) 2 pole 3)
12.5
20
32
40
6380
20
32
50
63
100125
20
32
50
63
100125
XS125CJ (18 kA) 3 pole
12.5
20
32
40
63
80
Non-auto (1.8 kA for 1s) Refer page 13 - 121
Ampererating Min Max
XS125CJ 20 3
XS125CJ 32 3
XS125CJ 50 3
XS125CJ 63 3
XS125CJ 100 3
XS125CJ 125 3
Cat. No.
20
32
50
63
100
125
125
20
32
50
63
100
125
-
7/24/2019 Pt c 2007 Sec 13b Lr
10/3813 - 108
13
TemBreak MCCBsXH125 series
Adjustment range 63 - 100 % of nominal rating.
Co-ordinated with Sprecher + Schuh contactors.
Standards AS 2184/AS/NZS 3947-2.
Adjustable thermal, fixed magnetic trip.
XH125NJ (50 kA) 3 pole
12.5
20
32
40
63
80
Ampererating Min Max
XH125NJ 20 3
XH125NJ 32 3
XH125NJ 50 3
XH125NJ 63 3
XH125NJ 100 3
XH125NJ 125 3
Cat. No.
20
32
50
63
100
125
20
32
50
63
100
125
XH125NJ (50 kA) 4 pole
12.5
20
32
40
63
80
XH125NJ 20 4
XH125NJ 32 4
XH125NJ 50 4
XH125NJ 63 4
XH125NJ 100 4
XH125NJ 125 4
20
32
50
63
100
125
20
32
50
63
100
125
i
i
i
i
i
Dimensions (mm)
90
120
Height
86
86
Depth
1.3
1.6
kg
XH125NJ 3 pole
XH125NJ 4 pole
155
155
Description Width
Notes: 1) MCCBs only.2) Poles in series. Refer applications section 13.Special low instantaneous magnetic, generator protection MCCBs availableon request.
Available on indent only.
Model I/C Voltage
XH125NJ 50 kA 400/415 V 50 Hz
Short circuit capacity
DC use I/C 2) Voltage
XH125NJ 40 kA 250 V DC
i
Bolt-on earth leakage module ELB 125.Refer Section 11 for further details.
Base standardsIEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2/Aust./NZ
AS 2184-1990/Australia 1)
JIS C 8372/JAPAN
JEC 160/JAPAN
ApprovalsASTA/UK, Aust. standards
MarineNK/JAPAN
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
DNV NORWAY
-
7/24/2019 Pt c 2007 Sec 13b Lr
11/3813 - 109
13
TemBreak Plus MCCBsXH125PJ PowerBreaker seriesIcs = 50 kA Powerful interrupting capacities.
Limitation of system damage.
Unique contact structure. Icu = Ics = 50 kA.
Adjustable thermal, fixed magnetic trip.
Adjustment range 63 - 100 % of nominal current rating.
Standards IEC 60947-2/AS/NZS 3947-2.
XH125PJ (50 kA) 3 pole
12.5
20
3240
63
80
Ampererating Min Max
XH125PJ 20 3
XH125PJ 32 3
XH125PJ 50 3XH125PJ 63 3
XH125PJ 100 3
XH125PJ 125 3
Cat. No.
20
32
5063
100
125
20
32
5063
100
125
XH125PJ (50 kA) 4 pole
12.5
20
32
40
6380
XH125PJ 20 4
XH125PJ 32 4
XH125PJ 50 4
XH125PJ 63 4
XH125PJ 100 4XH125PJ 125 4
20
32
50
63
100125
20
32
50
63
100125
i
i
i
i
i
Dimensions (mm)
90
120
Height
86
86
Depth
1.3
1.6
kg
XH125PJ 3 pole
XH125PJ 4 pole
155
155
Description Width
Notes: 1) Poles in series. Refer applications section 13.Available on indent only.
Model Icu Voltage
XH125PJ 50 kA 400/415 V 50 Hz
AC useShort circuit capacity
DC use 1) Icu Voltage
XH125PJ 40 kA
Ics
50 kA
Ics
250 V DC
iBase standards
IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2 Aust./NZ
Approvals
ASTA/UK, Aust. standards
Marine
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
-
7/24/2019 Pt c 2007 Sec 13b Lr
12/3813 - 110
13
TemBreak MCCBsXE225NC economical series
Standards AS/NZS 3947-2.
Fixed thermal magnetic trip.
XE250 Isolator
Non-Auto (3 kA for 1sec) 1) 3) Refer page 13 - 121250
Dimensions (mm)
105
Height
67
Depth
1.85
kg
XE225N 3 pole 160
Description Width
Notes: 1) Load-break isolating switch only no protection.2) Chassis not available for XE225NC.3) Short time rating. Refer rating chart for complete technical data.4) MCCBs only.
Special low instantaneous magnetic, generator protection MCCBs
available on request.
Model I/C Voltage
XE225NC 18 kA 400 V 50 Hz
Short circuit capacity
DC use I/C Voltage
XE225NC 10 kA 250 V DC
XE225NC (18 kA) 3 pole
125
150
175
200
225
Ampere rating(fixed)
XE225NC 125 3
XE225NC 150 3
XE225NC 175 3
XE225NC 200 3
XE225NC 225 3
Cat. No. 1) 2)
Base standards
IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2/Aust./NZ
AS 2184-1990/Australia 4)
JIS C 8372/JAPAN
JEC 160/JAPAN
Approvals
ASTA/UK, Aust. standards
Marine
NK/JAPAN
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
-
7/24/2019 Pt c 2007 Sec 13b Lr
13/3813 - 111
13
TemBreak Plus MCCBsXH160PJ PowerBreaker seriesIcs = 50 kA
Powerful interrupting capacities.
Limitation of system damage.
Unique contact structure.
Icu = Ics = 50 kA.
Adjustable thermal, fixed magnetic trip.
Adjustment range 63 - 100 % of nominal current rating.
Standards IEC 60947-2/AS/NZS 3947-2.
Notes: 1) Poles in series. Refer applications section 13.Available on indent only.
XH160PJ (50 kA) 3 pole
100
Ampererating
XH160PJ 160 3
Cat. No.
160 160
Min Max
XH160PJ (50 kA) 4 pole
100 XH160PJ 160 4160 160
Dimensions (mm)
105
140
Height
103
103
Depth
2.1
2.4
kg
XH160PJ 3 pole
XH160PJ 4 pole
165
165
Description Width
Base standards
IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2 Australia/NZ
Approvals
ASTA/UK, Aust. standards
Marine
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
i
i
Model Icu Voltage
XH160PJ 50 kA 400/415 V 50 Hz
AC use
Short circuit capacity
DC use 1) Icu Voltage
XH160PJ 40 kA
Ics
50 kA
Ics
250 V DC
-
7/24/2019 Pt c 2007 Sec 13b Lr
14/3813 - 112
13
TemBreak MCCBsXS250 and XH250 NJ series
Adjustment range 63 - 100 % of nominal current rating.
Standards AS/NZS 3947-2.
Adjustable thermal, fixed magnetic trip.
XS250NJ (25 kA) 3 pole
100
160
Non-Auto (4 kA for 1 sec) 1) 4)
Ampererating
XS250NJ 160 3
XS250NJ 250 3
Refer page 5 - 48
Cat. No.
160
250
250
160
250
Min Max
Notes: 1) Isolating switch only - no protection.2) MCCBs only.3) Poles in series. Refer applications Section 13.4) Short time rating. Refer rating chart for complete technical data.Special low instantaneous magnetic generator protection MCCBs available onrequest.
XH250NJ (50 kA) 3 pole
160
250
XH250NJ 160 3
XH250NJ 250 3
100
160
160
250
XH250NJ (50 kA) 4 pole160
250
XH250NJ 160 4
XH250NJ 250 4
100
160
160
250
XS250NJ (25 kA) 4 pole100
160
Non-Auto (4 kA for 1 sec) 1) 4)
XS250NJ 160 4
XS250NJ 250 4
Refer page 5 - 48
160
250
250
160
250
Model I/C Voltage
XS250NJ
XH250NJ
25 kA
50 kA
400 V 50 Hz
400/415 V 50 Hz
Short circuit capacity
Dimensions (mm)
105
105
140
140
Height
86
103
86
103
Depth
1.85
2.1
2.4
2.6
kg
XS250NJ 3 pole
XH250NJ 3 pole
XS250NJ 4 pole
XH250NJ 4 pole
165
165
165
165
Description Width
XS250NJ
XH250NJ
40 kA
40 kA
250 V DC
250 V DC
DC use I/C 3) Voltage
Base standards
IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2/Aust./NZ
AS 2184-1990/Australia 2)
JIS C 8372/JAPAN
JEC 160/JAPAN
Approvals
ASTA/UK, Aust. standards
Marine
NK/JAPAN
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
DNV NORWAY
-
7/24/2019 Pt c 2007 Sec 13b Lr
15/3813 - 113
13
TemBreak Plus MCCBsXH250PJ and XH400PJ PowerBreaker seriesIcs = 50 kA
Powerful interrupting capacities.
Limitation of system damage.
Unique contact structure.
Adjustable thermal and magnetic trips.
Thermal adjustment range 63 - 100 % of nominal current rating.
Standards IEC 60947-2/AS/NZS 3947-2.
Dimensions (mm)
140185
Height
103103
Depth
4.76.1
kg
XH250/400PJ 3 poleXH250/400PJ 4 pole
260260
Description Width
Base standards
IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2 Aust./NZ
Approvals
ASTA/UK, Aust. standards
Marine
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
Model Icu Voltage
XH250/400PJ 65 kA 400/415 V 50 Hz
AC use
Short circuit capacity
DC use 1) Icu Voltage
XH250/400PJ 40 kA
Ics
50 kA
Ics
250 V DC
Notes: 1) Poles in series. Refer applications section 13.Available on indent only.i
XH250PJ and XH400PJ (65 kA) 3 pole
100
160
250
Ampererating Min Max
XH250PJ 160 3
XH250PJ 250 3
XH400PJ 400 3
Cat. No.
160 (400AF)
250 (400AF)
400
160
250
400
XH250PJ and XH400PJ (65 kA) 4 pole
100
160
250
XH250PJ 160 4
XH250PJ 250 4
XH400PJ 400 4
160 (400AF)
250 (400AF)
400
160
250
400
i
i
i
-
7/24/2019 Pt c 2007 Sec 13b Lr
16/3813 - 114
13
TemBreak MCCBsXS400 series thermal magnetic type
Notes: 1) Load-break isolating switch only no protection.2) MCCBs only.3) Poles in series. Refer applications Section 13.
Dimensions (mm)
140
185
Height
103
103
Depth
XS400CJ/NJ 3 pole
4 pole
260
260
Description Width
4.7
6.1
kg
Adjustment range 63 - 100 % of nominal current rating.
Standards AS/NZS 3947-2.
Adjustable thermal and magnetic trip.
XS400CJ (35 kA) 3 pole
160
250
Non-auto (5 kA for 0.3s) 1) Refer page 13 - 121
Ampererating
XS400CJ 250 3
XS400CJ 400 3
Cat. No.
250
400
400
250
400
Min Max
XS400CJ (35 kA) 4 pole
160
250
XS400CJ 250 4
XS400CJ 400 4
250
400
250
400
XS400NJ (50 kA) 3 pole
160
250
XS400NJ 250 3
XS400NJ 400 3
250
400
250
400
XS400NJ (50 kA) 4 pole
160
250
XS400NJ 250 4
XS400NJ 400 4
250
400
250
400
Model I/C Voltage
XS400CJ
XS400NJ
35 kA
50 kA
400 V 50 Hz
400/415 V 50 Hz
Short circuit capacity
Base standards
IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2/Aust./NZ
AS 2184-1990/Australia 2)
JIS C 8372/JAPAN
JEC 160/JAPAN
Approvals
ASTA/UK, Aust. standards
Marine
NK/JAPAN
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
DNV NORWAY
DC use 3) I/C Voltage
XS400CJ
XS400NJ
40 kA
40 kA
250 V DC
250 V DC
-
7/24/2019 Pt c 2007 Sec 13b Lr
17/3813 - 115
13
TemBreak Plus MCCBsXS400SE and XH400SE selectivity series electronic type
SE Upstream Selectivity
breakers. SE offers enhanced selectivity.
3:1 ratio between upstream &
downstream MCCBs.
Ics rating is 50 % of Icu.
I2t switch to assist in obtaining
total selectivity.
True RMS monitoring.
Electronic trip unit with Long,Short and Instantaneous
adjustments.
Adjustment range 50 - 100 %
of nominal current rating.
Standards IEC 60947-2/
AS/NZS 3947-2.
Notes: Available on indent only.
Dimensions (mm)
140
185
Height
103
103
Depth
XS/XH400SE 3 pole
XS/XH400SE 4 pole
260
260
Description Width
5
6.2
kg
Description Code
Pre-trip alarm
Fault indicators
Special LTD curves
LSIP
FI
-
OCR options (factory fitted)
i
Base standards
IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2 Aust./NZ
Approvals
ASTA/UK, Aust. standards
Marine
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
Model Icu Voltage
XS400SE
XH400SE
50 kA
65 kA
400/415 V 50 Hz
400/415 V 50 Hz
AC useShort circuit capacity
Ics
25 kA
33 kA
XS400SE (50 kA) 3 pole
125
250
Ampere
ratingXS400SE 250 3
XS400SE 400 3
Cat. No.250
400
250
400
Min Max
XH400SE (65 kA) 3 pole
125
250
XH400SE 250 3
XH400SE 400 3
250
400
250
400
XS400SE (50 kA) 4 pole
125
250
Ampererating
XS400SE 250 4
XS400SE 400 4
Cat. No.
250
400
250
400
Min Max
XH400SE (65 kA) 4 pole
125
250
XH400SE 250 4
XH400SE 400 4
250
400
250
400
i
i
i
i
-
7/24/2019 Pt c 2007 Sec 13b Lr
18/3813 - 116
13
TemBreak Plus MCCBsXH400PE PowerBreaker seriesIcs = 50 kA
XH400PE (65 kA) 3 poleAmpererating Cat. No.Min Max
Current limiting.
True RMS monitoring. I2t switch to assist in obtaining total selectivity.
Powerful interrupting capacities.
Limitation of system damage.
Unique contact structure.
Electronic trip unit with Long, Short and Instantaneous adjustments.
Adjustment range 50 - 100 % of nominal current rating.
Standards IEC 60947-2/AS/NZS 3947-2.
Notes: 1) Mounted externally.Available on indent only.
Dimensions (mm)
140
185
Height
103
103
Depth
XH400PE 3 pole
XH400PE 4 pole
260
260
Description Width
5
6.2
kg
125
250
XH400PE 250 3
XH400PE 400 3
250
400
250
400
XH400PE (65 kA) 4 pole
125
250
XH400PE 250 4
XH400PE 400 4
250
400
250
400
Description Code
Pre-trip alarm
Fault indicators 1)
Special LTD curves
LSIP
FI
-
OCR options (factory fitted)
i
Model Icu Voltage
XH400PE 65 kA 400/415 V 50 Hz
AC useShort circuit capacity
Ics
50 kA
i
i
Base standards
IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2 Aust./NZS
Approvals
ASTA/UK, Aust. standards
Marine
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
-
7/24/2019 Pt c 2007 Sec 13b Lr
19/3813 - 117
13
TemBreak MCCBsHigh fault series thermal magnetic type
Dimensions (mm)
TL100C (180 kA) 3 pole
15
20
30
40
50
60
75
100
TL100C 15 3P
TL100C 20 3P
TL100C 30 3P
TL100C 40 3P
TL100C 50 3P
TL100C 60 3P
TL100C 75 3P
TL100C 100 3P
TL100F (120 kA) 3 pole
15
20
30
40
50
60
75
100
TL100F 15 3P
TL100F 20 3P
TL100F 30 3P
TL100F 40 3P
TL100F 50 3P
TL100F 60 3P
TL100F 75 3P
TL100F 100 3P
90
105
110
Height
86
125
133
Depth
TL30F
TL100F
TL100C
155
165
230
Description Width kg
1.3
3.2
5.0
Standards AS/NZS 3947-2.
Interrupting capacity @ 415 V 120 kA.
TL breakers are suitable for high fault high currentlimiting applications.
Fixed thermal magnetic trip unit.
TL30F (120 kA) 3 poleAmpererating
TL30F 15 3P
TL30F 20 3P
TL30F 30 3P
Cat. No.
15
20
30
Model I/C Voltage
TL30F
TL100F
TL100C
TL100F
120 kA
120 kA
180 kA
40 kA
400/415 V 50 Hz
400/415 V 50 Hz
400/415 V 50 Hz
250 V DC
Short circuit capacity
D/C use I/C I/C
Base standards
IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2
AS 2184-1990/Australia
JIS C 8372/JAPAN
JEC 160/JAPAN
Approvals
ASTA/UK, Aust. standards
Marine
NK/JAPAN
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
-
7/24/2019 Pt c 2007 Sec 13b Lr
20/3813 - 118
13
TemBreak Plus MCCBsTL100NJ LimitorBreaker seriesIcs = 85 kA
Dimensions (mm)
90
120
Height
86
86
Depth
TL100NJ 3 pole
TL100NJ 4 pole
235
235
Description Width kg
2.2
2.7
Standards IEC 60947-2/AS/NZS 3947-2.
Two fast-break contacts per pole.
Powerful interrupting capacities.
Provides limitation of system damage during a fault.
Icu = Ics = 85 kA.
Variable thermal, fixed magnetic trip.
Adjustment range 63 100 % of nominal current rating.
Can be used for selectivity applications.
3 or 4 pole types available.
Notes: 1) Poles in series. Refer applications section 13.Available on indent only.
Base standards
IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2
Approvals
ASTA/UK, Aust. standards
Marine
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
Model Icu Voltage
TL100NJ 85 kA 400/415 V 50 Hz
AC useShort circuit capacity
DC use 1) Icu Voltage
TL100NJ 40 kA
Ics
85 kA
Ics
250 V DC
TL100NJ (85 kA) 3 pole
12.5
20
32
40
63
Ampererating Min Max
TL100NJ 20 3
TL100NJ 32 3
TL100NJ 50 3
TL100NJ 63 3
TL100NJ 100 3
Cat. No.
20
32
50
63
100
20
32
50
63
100
TL100NJ (85 kA) 4 pole
12.5
20
32
40
63
TL100NJ 20 4TL100NJ 32 4
TL100NJ 50 4
TL100NJ 63 4
TL100NJ 100 4
20
32
50
63
100
20
32
50
63
100
i
i
i
i
i
i
-
7/24/2019 Pt c 2007 Sec 13b Lr
21/3813 - 119
13
TemBreak Plus MCCBsTL250NJ LimitorBreaker seriesIcs = 100 kA
Base standards
IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2 Aust./NZ
Approvals
ASTA/UK, Aust. standards
Marine
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
Model Icu VoltageTL250NJ
TL250NJ
100 kA
100 kA
400 V AC 50 Hz
400 V AC 50 Hz
AC use
Short circuit capacity
DC use 1) Icu Voltage
TL250NJ 40 kA
Ics100 kA
85 kA
Ics
250 V DC
Dimensions (mm)
140
185
Height
103
103
Depth
TL250NJ 3 pole
TL250NJ 4 pole
360
360
Description Width kg
7.1
9.1
Standards IEC 60947-2/AS/NZS 3947-2.
Two fast-break contacts per pole.
Powerful interrupting capacities.
Provides limitation of system damage during a fault.
Icu = Ics = 85 kA at 415 V.
Variable thermal and magnetic trip.
Adjustment range 63 100 % of nominal current rating.
Can be used for selectivity applications.
3 or 4 pole types available.
Notes: 1) Poles in series. Refer applications section 13.Available on indent only.i
TL250NJ (100 kA) 3 pole
100
160
Ampererating
TL250NJ 160 3
TL250NJ 250 3
Cat. No.
160
250
160
250
Min Max
TL250NJ (65 kA) 4 pole
100
160
TL250NJ 160 4
TL250NJ 250 4
160
250
160
250
i
i
-
7/24/2019 Pt c 2007 Sec 13b Lr
22/3813 - 120
13
TemBreak Plus MCCBsTL400NE LimitorBreaker series electronic type
TL400NE (85 kA) 3 pole
200
Ampererating
TL400NE 400 3
Cat. No.
400 400
Min Max
TL400NE (85 kA) 4 pole
200 TL400NE 400 4400 400
Notes: 1) Height excludes attached busbar.2) Factory fitted OCR controller specify voltage 240 V or 110 V AC.
Available on indent only.
Standards IEC 60947-2/AS/NZS 3947-2.
Two fast-break contacts per pole.
Powerful interrupting capacities.
Provides limitation of system damage during a fault.
Electronic trip unit with Long, Short & Instantaneous adjustments.
Icu = Ics = 85 kA at 415 V.
Adjustment range 50 100 % of nominal current rating.
True RMS monitoring.
I2t ramp switch to assist in obtaining total selectivity.
3 or 4 pole types available.
Description Code
Pre-trip alarm 2)
Fault indicators 2)
Special LTD curves
LSIP
FI
-
OCR options (factory fitted)
i
i
Base standards
IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2
Approvals
ASTA/UK, Aust. standards
Marine
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
Model Icu Voltage
TL400NE
TL400NE
100 kA
85 kA
400 V AC 50 Hz
415 V AC 50 Hz
AC useShort circuit capacity
Ics
100 kA
85 kA
Dimensions (mm)
140
185
Height 1)
103
103
Depth
TL400NE 3 pole
TL400NE 4 pole
360
360
Description Width kg
7.1
9.1
-
7/24/2019 Pt c 2007 Sec 13b Lr
23/3813 - 121
13
TemBreak MCCBsMCCB isolating switches (non-auto MCCBs)
Ampere
rating (A)
XS125NN3
XE225NNC3
XS250NN3
XS400NN3
XS630NN3
3 pole
Cat. No. 1)
XS125NN4
XE225NNC4
XS250NN4
XS400NN4
XS630NN4
4 pole
Cat. No. 1)125
250
250
400
630
Amprating (A)
125
225
250
400
630
Height 2)
155
160
165
260
273
Depth
86
67
86
103
103
Width
3P 4P
90
105
105
140
210
120
140
185
280
Weight (kg)
3P 4P
1.3
1.85
1.85
5
9
1.58
2.4
6.2
12.2
Short time
rating (kA)1.8 kA for 1 sec
3 kA for 1 sec
4 kA for 1 sec
5 kA for 0.3 sec
9.6 kA for 0.3 sec
Accepts MCCB accessories.
Suitable for panelboards.
Standards IEC 60947-2/AS/NZS 3947-2.
Motor or motorised circuit isolation - no overcurrent protection.
Notes: 1) Refer page 13 - 103 for additional technical details.2) Height excludes attached busbar.
Dimensions (mm)
Ordering details
Base standards
IEC 60947-2
BS EN 60947 Part 2
VDE 0660 Part 1
AS/NZS 3947-2 Aust./NZ
Approvals
ASTA/UK, Aust. standards
Marine
Lloyds R/UK
ABS/USA
GL/GERMANY
BV/FRANCE
-
7/24/2019 Pt c 2007 Sec 13b Lr
24/3813 - 122
13
TemBreak MCCB accessoriesTemBreak standard combinations of internally mountedaccessories
UVT rating
A. Inst type
AC 100 - 120 V
AC 200 - 240 V
AC 380 - 450 V
DC 24 V
DC 48 V
DC 60 V
DC 100 - 115 V
DC 200 - 230 V
B. Time delay type
AC 100 - 120 V
AC 200 - 240 V
AC 380 - 450 V
SHT rating
AC 100 - 115 V
AC 200 - 480 V
AC 24 V
AC 48 V
DC 12 V
DC 24 V
DC 30 V
DC 48 V
DC 60 V
DC 100 - 115 VDC 125 V
DC 200 - 230 V
AUX
ALT
SHT
UVT
Auxiliary switch
Alarm switch
Shunt trip
Undervoltage trip
Left pole
Right polehandle
i
i
i
i
Note: Available on indent only.i
Internal accessories
are NHP factory
fit only
XS 125PJXS-125CJXS-125NJXH-125NJ
TL30F
XH 160PJXS-250NJXH-250NJ
XE-225NC
XS400XH/XS400XS630XH/XS630XS800XH/XS800XS1250
XS1600
-
7/24/2019 Pt c 2007 Sec 13b Lr
25/3813 - 123
13
UXVC0001C
2H1935BAC
2H1935BBC
2H1935BCC
2H1935BDC
2H1935BEC
2H1936BAC
2H1936BBC
2H1936BDC
2H1936BHC
2H1947BAC
2H1947BBC
2H1947BCC
2H1948BAC
2H1948BBC
UXUB0013B
UXUB0014B
UXUB0015B
UXUB0016B
UXUB0017B
UXUB0018B
UXUB0037B
UXXB0019D
UXXB0020D2H2383DAA
2H2384DAA
UXXB0026E
UXXB0027E
UXLB0001E
2H2385DAA
UXLB0027E
UXLB0003E
2H2387DAA
UXLB0028E
-
TemBreak MCCB accessoriesAccessories to suit 125 AF, TL30F, TL100NJ 3)
Undervoltage trip
UVT controller
Alarm switch
Alarm & auxiliaryswitch
Internal accessories (factory fit)
Cat. No.
Shunt trip
(1 pole)
Shunt trips
(2, 3, 4 pole)
Undervoltage
trips
Auxiliary
switches
Alarm
switches
Alarm &
auxiliary switches
Extra low
or highmagnetic trip
100-440 V AC / 48-250 V DC 1 P SHT
110 V AC SHT (100-115 V)
240 V AC SHT (200-480 V)
24 V DC SHT
48 V DC SHT
110 V DC SHT (100-115 V)
24 V AC SHT
48 V AC SHT
12 V DC SHT
200 V DC SHT (200-230)
AC coil 1)
24 V DC coil 2)
100-230 V DC coil 2)
48 V DC coil 2)
60 V DC coil 2)
110 V AC instantaneous controller
240 V AC instantaneous controller
440 V AC instantaneous controller
110 V AC time delay controller
240 V AC time delay controller
440 V AC time delay controller
200-230 V DC controller
AUX SW right hand 1 C / 3 P
AUX SW right hand 2 C / 3 PAUX SW right hand 1 C / 4 P
AUX SW right hand 2 C / 4 P
AUX SW left hand 1 C
AUX SW left hand 2 C
ALT SW right hand / 3 P
ALT SW right hand / 4 P
ALT SW left hand
ALT/AUX SW right hand 1 C / 3 P
ALT/AUX SW right hand 1 C / 4 P
ALT/AUX SW left hand 1 C
Special selectivity, generator or marine applications
Description
Notes: 1) An AC UVT controller is required for 100-440 V AC.2) A DC UVT controller is needed for 200-230 V DC operation. None required for 24-110 V DC.3) AF = Ampere frame.
XS125CS/20 Awith shunt trip fitted
-
7/24/2019 Pt c 2007 Sec 13b Lr
26/3813 - 124
13
TRED0001
TXED0005A
TXED0006A
UXRC0011A
UXRC0012A
UXMB0041C
UXMB0057B
UXMB0061C
UXKB0017B
UXKB0018B
XFHA22T1HP12XR6BNA4
TFJ22XU
YASD22
UXKB0013A
-
XKA2
LOCTITE
480 RESIN
2H1407DAA
2H1408DAA
2A1785DAA
2H1406DAA
UXPD0031A
UXPD0032A
UXYD0007A
UXYE0005A
UXYC0013A
TXED0010A
XDM2-3
UXYD0007A
UXYE0005A
UXYC0013A
TXED0011A
XDM2-4
UPX3125UXQH0002B
XS1250CRSK
XAB2
ELB125A
TO400XS125
TemBreak MCCB accessoriesAccessories to suit 125 AF, TL30F, TL100NJ 1)
External accessories
Cat. No.Attached
busbar
Tunnel Clamp
terminals
Rear connect
studs
Motor
operators
Mechanical
interlocks
Handleoperators
Handle locks
Terminal
covers - front
connect
Terminal covers -
rear connect
Plug-in
breaker parts
3 pole 9)
Plug-in
breaker parts
4 pole 8)
TemPlugInterpole barrier
OCR sealing kit
Pole fillers
Earth leakage
block
Adapter kit for TO400
chassis
3 P attached busbars (6 in kit)
3 P solderless terminals (6 in kit) 2)
4 P solderless terminals (8 in kit) 2)
3 P rear connect studs (6 in kit)
4 P rear connect studs (8 in kit)
110 V AC motor
240 V AC motor
110 V DC motor
3 P rear mech I/lock
4 P rear mech I/lock
Variable depth handle, door interlockingIP 65 rated variable depth handle, door interlocking
IP 55 direct mount rotary handle 3)
IP 65 metal variable depth handle
Handle lock
Key interlock (Fortress type) incl TFJ mechanism 4)
Padlock attachment 5)
Resin for XKA2
3 P FC terminal cover
4 P FC terminal cover
IP 20 protection cover 6)
Seal plate 7)
3 P RC terminal cover
4 P RC terminal cover
Terminal and bolt
Insulation plate
AUX conn. block (MCCB side)
3 P tulip blocks (6 in kit)
3 P mounting base
Terminal and bolt
Insulation plate
AUX Conn. block (MCCB side)
4 P tulip blocks (8 in kit)
4 P mounting base
3 P TemPlugCat. No. for 1 only 9)
OCR sealing kit
For use with metal escutcheon covers
Add-on earth leakage block with pre-trip alarm contacts
Order one kit per breaker
Description
Notes: 1) AF = Ampere frame.2) Factory fit only.3) Flush plate included.4) Tech data Section 8.5
) Captive type. Resin fixing.6) 6 pieces required for 3 P / 8 pieces required for 4 P.7) Specify qty required (up to 2 pieces).8) Not suitable for TL100NJ types.9) A total of 4 individual barriers for 3 P, and 6 barriers required for 4 P.
Tunnel ClampTerminals (Solderlessterminals)
Rear connect studs
Plug-in tulip blocks
Plug-in base
Rear interlock
Attached busbar
UXMB motor operator
-
7/24/2019 Pt c 2007 Sec 13b Lr
27/3813 - 125
13
TemBreak MCCB accessoriesAccessories to suit 225 AF (XE225NC) 1)
TFJ handle
Terminal cover
TFH Handle operator
Notes: 1) AF = Ampere frame.2) Flush plate included.3) Tech data Section 8.4
) 4 barriers required per breaker.
Internal accessories (factory fit)
Cat. No.Shunt trips
(2, 3, 4 pole)
Auxiliary switches
Alarm switches
Alarm & auxiliary
switches
110 V AC SHT (100 - 115 V)
240 V AC SHT (200 - 480 V)
24 V DC SHT
48 V DC SHT
110 V DC SHT (100 - 115 V)
AUX SW right hand 1 C
AUX SW right hand 2 C
AUX SW left hand 1 C
AUX SW left hand 2 C
ALT SW right hand
ALT/AUX SW right hand 1 C
2H0153CAB
2H0153CBB
2H0153CDB
2H0153CEB
2H0153CCB
2H0156CAB
2H0156CBB
2H1613BAA
2H1613CBA
2H0157CAB
2H0157CBB
External accessoriesAttached busbar
Tunnel clamp
(Solderless) terminals
Rear connect studs
Mechanical
interlocks
Handle operators
Handle locks
Terminal cover
- front connect
- rear connect
Interpole barrier
3 P attached busbars (6)
3 P solderless terminals (6)
3 P rear connect studs (6)
3 P rear mech. I/lock
Variable depth handle, door interlockingIP 55 direct mount rotary handle 2)
Lock plate
Handle lock
Key interlock (Fortress Type) incl TFJ mechanism 3)
3 P FC terminal cover
3 P RC terminal cover
Interpole barrier 4)
7B3BA1B
2A1818CAA
2H1081CAA
2H0158CAA
TFH23CBTFJ23CU
UXKE0030A
KGH7123A
-
2H1080CAA
2H1079CAA
TQQ3CA
Description
-
7/24/2019 Pt c 2007 Sec 13b Lr
28/3813 - 126
13
TemBreak MCCB accessoriesAccessories to suit 160 AF / 250 AF 10)
Internal accessories (factory fit)
Cat. No.
Shunt trips
Undervoltage trips
Auxiliary switches
Alarm switchesAlarm & Auxiliary
switches
Extra low or high
magnetic trip
110 V AC (100 - 115 V)
240 V AC (200 - 480 V)
24 V DC
48 V DC
110 V DC (100 - 115 V)
24 V AC
48 V AC
12 V DC
200 V DC (200-230 V)
AC coil 1)
24 V DC coil 2)
100-230 V DC coil 2)
48 V DC coil 2)60 V DC coil 2)
110 V AC instantaneous controller
240 V AC instantaneous controller
440 V AC instantaneous controller
110 V AC time delay controller
240 V AC time delay controller
440 V AC time delay controller
200-230 V DC controller
AUX SW right hand 1 C
AUX SW right hand 2 C
AUX SW left hand 2 C
ALT SW right handALT / AUX SW right hand 1 C
Special selectivity, generator or marine applications
2H1937BAA
2H1937BBA
2H1937BCA
2H1937BDA
2H1937BEA
2H1938BAA
2H1938BBA
2H1938BDA
2H1938BHA
2H1949BAB
2H1949BBB
2H1949BCB
2H1950BAB2H1950BBB
UXUB0013B
UXUB0014B
UXUB0015B
UXUB0016B
UXUB0017B
UXUB0018B
UXUB0037B
2H1951BAA
2H1952BAA
UXXB0028B
2H1953BAA2H1954BAA
-
External accessories
Attached busbars
Tunnel clamp
terminals
(solderlessterminals)
Crimp lugs
3 P attached busbars (6)
4 P attached busbars (8)
3 P solderless term (6) / XS 9)
4 P solderless term (8) / XS9
)3 P solderless term (6) / XH 9)
4 P solderless term (8) / XH 9)
Compression term (80 mm2)
Compression term (100 mm2)
TXJD0050B
TXJD0051B
2H2008DAB
2H2008DBB2H2734DAA
2H2734DBA
80-3BA
100-3BA
Description
Cat. No.Description
Tunnel clampterminals
Undervoltage trip
UVT controller
Alarm switch
Alarm & auxiliaryswitch
Note: Refer following page for footnotes.
-
7/24/2019 Pt c 2007 Sec 13b Lr
29/3813 - 127
13
TemBreak MCCB accessoriesAccessories to suit 160 AF / 250 AF 10)
Interpole barriers
OCR sealing kit
External accessories
Cat. No.
Rear connection
studs
Motor operators
Mechanical
interlocks
Handle operators
Handle lock
Terminal covers
Plug-in breaker
parts 3 pole
Plug-in breaker
parts 4 pole
TemPlug
Interpole barriers
Pole fillers
Earth leakage block
OCR sealing kit
3 P rear connect studs (6)
4 P rear connect studs (8)
110 V AC motor 3)
220 V AC motor 3)
240 V AC motor 3)
110 V DC motor 3)
3 P rear mech int. / XS
4 P rear mech nt. / XS
3 P rear mech int./ XH
4 P rear mech int./ XH
Variable depth handle, door interlocking 3)
IP 65 rated variable depth handle, door interlocking 3)
IP 55 direct mount rotary handle mechanism 4)
IP 65 metal variable depth handle
Handle lock
Key interlock (Fortress Type) incl TFJ mechanism 11)
Padlock attachment 5)
Resin for XKA2
3 P FC terminal cover / XS
4 P FC terminal cover / XS
3 P FC terminal cover / XH
4 P FC terminal cover / XH
IP 20 protective cover 6)
3 P RC terminal cover / XS4 P RC terminal cover / XS
3 P RC terminal cover / XH
4 P RC terminal cover / XH
Seal plate 7)
AUX conn. block (MCCB side)
AUX conn. block (panel side)
3 P tulip block / XS
3 P tulip block / XH
3 P mounting base
AUX conn. block (MCCB side)
AUX conn. block (panel side)
4 P tulip block / XS
4 P tulip block / XH
4 P mounting base
3 P TemPlug / XH only
Interpole barrier / XS 8)
Interpole barrier / XH 8)
For use with metal escutcheon covers
Add-on earth leakage block with pre-trip alarm (XH250)
Add-on earth leakage block with pre-trip alarm (XS250)
OCR sealing kit
2H2266DAA
2H2266DBA
UXMB0046D
UXMB0047D
UXMB0058B
UXMB0062C
UXKB0019B
UXKB0020B
UXKB0021B
UXKB0022B
XFHA23S
T1HP25XR6BNA4
TFJ23SUYASD23
UXKB0014A
-
XKA2
LOCTITE
480 RESIN
2H2135DAB
2H1410DAB
2H2136DAA
2H1412DAA
2A1786DAA
UXPD0027BUXPD0028B
UXPD0033B
UXPD0034B
2H1406DAA
UXYC0010A
UXYB0004A
TXJD0054A
TXJD0058A
XDM3-3
UXYC0010A
UXYB0004A
TXJD0055A
TXJD0059A
XDM3-4
UPX3250
UXQH0002B
UXQH0003B
XAB3
ELB250AH
ELB250A
XS250OCRSK
Description
Notes: 1) An AC UVT controller is required for 100-440 V AC.2) A DC UVT controller is needed for 200-230 V DC operation. None required for 24-110 V DC.3) Add UXFD0016A when required for XH250NJ & XH160PJ.4) Flush plate included.5) Captive type. Resin fixing.6) 6 pieces required for 3 P / 8 pieces required for 4 P.7) Specify quantity required (up to 2 pieces).8) 4 pieces required for 3 P (6 pieces required for 4 P).9) Factory fit only.10) AF = Ampere frame.11) Tech data, Section 8.
Rear interlock
UXMB motor operator
XFH Handle operator
Note: 400 Aaccessories refer
Section 5
-
7/24/2019 Pt c 2007 Sec 13b Lr
30/3813 - 128
13
TemBreak MCCB accessoriesNHP TemPlug
Available for MCCBs from 12-400 Ampere
Easily fitted using supplied hardware
Low resistance connection
Moulding constructed from UL approved glass filled polyester
Polycarbonate terminal cover supplied as standard
Assembly bolts directly to module gear plate
Lowest watts loss and temperature rise
Silver plated contacts with domed face for increased
contact pressure
Currentrating (A)
12
100
125
250
250
400
MCCB
XM30PB
TL100F
XH125NJ
XS250NJ
XH250NJ
XS400 / 400
Vertical typeCat. No.
UPX330PB
UPX3100F
UPX3125
UPXS250
UPXH250
UPX3440
Horizontally mounted versions are indent items, please refer to NHP.
(Horizontal type prefix is HBC3, for left or right mounting types)
Cut-out for TemPlugs 125 to 400 AF
TemPlug (125) / XM30PB TemPlug (250)
Vertical mountedTemPlug/MCCB
TemPlug (400)
Ordering details
-
7/24/2019 Pt c 2007 Sec 13b Lr
31/3813 - 129
13
Application dataSelectivity and Cascade tables at 400/415 VMCB to MCCB
MCB to MCCB: thermal magnetic
XS125NJ
25
XH125NJ
XH125PJ
TL100NJ
50
XH250NJ
TL250NJ
50
XS400CJ
35
XH400SE
65kA (RMS)
XS125CJ
18
6
6
10
10
10
1010
10
10
6
6
2-20 A
25-63 A
0.5-32 A
40-63 A
0.5-32 A
40 A80-125 A
0.5-32 A
40-63 A
16-63 A
16-20 A
18/18
18/18
18/18
18/18
18/18
18/184/18
18/18
18/18
3/10
3/10
25/25
20/25
25/25
20/25
25/25
20/254/25
25/25
20/25
3/10
3/10
35/35
20/25
30/50
25/25
30/50
25/254/25
30/50
25/25
3/10
3/10
35/35
30/30
40/50
30/30
40/50
30/3015/15
40/50
30/30
-
-
XS250NJ
25
25/25
25/25
25/25
25/25
25/25
25/2515/15
25/25
25/25
-
-
-
-
35/35
30/30
35/35
30/3010/10
35/35
30/30
-
-
XS400SE
XS400NJ
50
-
-
40/50
30/30
40/50
30/3010/10
40/50
30/30
-
-
-
-
40/50
30/30
40/50
30/30-
40/50
30/30
-
-
XX / YYGuide
Selectivity Cascade
DTCB6
DTCB10
DSRCBH & DSRCB
DSRCBH & DSRCB
DIN-T10H
DTCB15
SAFE-T
SRCB
Cascade
The resultant cascade level with the XH630SE (65 kA) and XH250NJ (50 ka)MCCBs in series is 65 kA. This means that the XH630SE will back-up the
XH250NJ MCCB to 65 kA, which is beyond its breaking capacity of 50 kA.
Selectivity
From the tables, the Selectivity level between the same two breakers,
XH630SE and XH250NJ connected in series will be 50 kA. This means that
for fault levels up to and including 50 kA the XH250NJ will trip before the
XH630SE.
Conclusion
For short circuit currents up to and including 50 kA, the XH250NJ will trip
before the XH630SE, therefore ensuring Selectivity. For fault levels above50 kA both breakers may trip, however, the XH630SE will back-up the
XH250NJ to 65 kA.
Range
(A)
Downstream
MCB
Upstream MCCB
-
7/24/2019 Pt c 2007 Sec 13b Lr
32/3813 - 130
13
Application data TemBreak MCCBsSelectivity and Cascade tables at 400/415 V
Upstream MCCB
XS125CJ
XS125NJ
XH125NJ
XH125PJ
TL100NJ
XH160PJ
XE225NC
XS250NJ
XH250NJ
XH250PJ
TL250NJ
XS400CJ
XS400NJ
XS400SE
XH400PJ
XH400SE
XH400PE
TL400NE
XS630CJ
XS630NJ
XS630SE
XH630PJ
XH630SE
XH630PE
XS800NJ
XS800SE
XH800PJ
XH800SE
XH800PE
XS1250SE
XS1600SE
kA(RMS)
DownstreamMCCB
XS400SE50
TL400NEXH400SE
65XS630SE
50
TL630NEXH630SE
65XS800SE
50
TL800NEXH800SE
65
TL1250NEXS1250SE
65
18
25
50
50
85
50
18
25
50
65
85
35
50
50
65
65
65
85
42
50
50
85
65
65
50
50
85
65
65
65
85
15/50
25/50
35/50
35/50
35/50
25/50
15/30
15/50
25/50
-
-
-/50
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
15/50
25/50
35/65
35/65
35/65
25/65
15/30
15/65
25/65
-
-/65
-/50
-/65
-/65
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
18/30
25/30
50/50
50/50
50/50
50/50
18/30
25/50
50/50
10/50
10/50
10/50
10/50
10/50
10/50
10/50
10/50
-
-
-
-
-
-
-
-
-
-
-
-
-
-
18/30
25/30
50/65
50/65
50/65
50/65
18/30
25/65
50/65
10/65
10/65
10/65
10/65
10/65
10/65
10/65
10/65
-
-/50
-
-/65
-
-
-
-
-
-
-
-
-
-
18/30
25/30
50/50
50/50
50/50
50/50
18/30
25/50
50/50
25/50
25/50
25/50
25/50
25/50
25/50
25/50
25/50
25/50
10/50
10/50
10/50
10/50
10/50
10/50
-
-
-
-
-
-
-
18/30
25/30
50/65
50/65
50/65
50/65
18/30
25/65
50/65
25/65
25/65
25/65
25/65
25/65
25/65
25/65
25/65
25/65
10/50
10/65
10/65
10/65
10/65
10/65
-
-/65
-
-
-
-
-
18/18
25/30
50/50
50/50
50/65
50/50
18/18
25/35
50/50
50/65
50/65
35/42
50/65
50/65
50/65
50/65
50/65
65/65
30/45
30/65
30/65
30/65
30/65
30/65
15/65
15/65
15/65
15/65
15/65
-
-
XS1600SE85
18/18
25/30
50/50
50/50
50/85
50/50
18/18
25/35
50/50
50/65
50/85
35/42
50/65
50/65
50/65
50/65
50/65
85/85
30/45
30/85
30/85
30/85
30/85
30/85
20/85
20/85
20/85
20/85
20/85
20/65
-
XS2000NE100
18/18
25/30
50/50
50/50
50/85
50/50
18/18
25/35
50/50
50/65
50/85
35/42
35/65
50/65
50/65
50/65
50/65
50/85
35/45
35/85
30/85
30/85
30/85
30/85
35/85
20/85
20/85
20/85
20/85
35/65
-
XS2500NE100
18/18
25/30
50/50
50/50
50/85
50/50
18/18
25/35
50/50
50/65
50/85
35/42
50/65
50/65
50/65
50/65
50/65
50/85
35/45
35/85
30/85
30/85
30/85
30/85
35/85
20/85
20/85
20/85
20/85
35/65
35/65
XX / YY
Guide
Selectivity Cascade
MCCB to MCCB: electronic and thermal magnetic
-
7/24/2019 Pt c 2007 Sec 13b Lr
33/3813 - 131
13
Application data TemBreak MCCBsSelectivity and Cascade tables at 400/415 V
Upstream MCCB
XS125CJ
XS125NJ
XH125NJ/PJ
XE225NC
XS250NJ
XH250NJ
XS400CJ
XS400NJ
XS630CJ
XS630NJ
XS800NJ
kA(RMS)
DownstreamMCCB
XH125NJ50
XS250NJ25
XH250NJ50
XS400CJ35
XS400NJ50
XS800NJ50
18
25
50
18
25
50
35
50
42
50
50
-/50
-/50
-
-
-
-
-
-
-
-
-
3/25
3/25
-
-/25
-
-
-
-
-
-
-
3/50
3/50
-
-/30
-
-
-
-
-
-
-
4/35
4/35
-
-/30
-
-
-
-
-
-
-
4/50
4/50
-
-/30
4/50
4/50
-/50
-
-
-
-
10/30
10/30
12/50
8/30
8/50
10/50
6/50
6/50
-
-
-
XH800PJ85
10/30
10/30
12/65
8/30
8/65
10/65
6/65
6/65
-/50
-/85
-/85
XS630CJ42
6/30
6/30
-
6/25
6/42
-
6/35
-
-
-
-
XS630NJ50
6/30
6/30
-
6/30
6/50
-
6/50
-
-
-
-
XX / YY
Guide
Selectivity CascadeMCCB to MCCB: thermal magnetic
Selectivity - Thermal magnetic MCCBs only.
-
7/24/2019 Pt c 2007 Sec 13b Lr
34/3813 - 132
13
Type 1 short circuit co-ordinationMotor starter co-ordination tablefor DOL starting50 kA at 400-415 V to AS 3947-4-1
Notes: 1) Use magnetic only breaker. Refer NHP for factory modification.2) Thermal or electronic overload relays may be used.3) Electronic overloads
Fuses 65 kA. XH125NJ circuit breaker combinations limited to 50 kA, others 65 kA.
Overloads may be changed to different types eg. thermal style to electronic.
Some combinations also give Type 2 performance.
0.37
0.55
0.75
1.1
1.5
2.2
3.0
4.05.5
7.5
10
11
15
18.5
22
30
37
4555
75
90
110
132
150
160
185
200
250
315
1.1
1.5
1.8
2.6
3.4
4.8
6.5
8.211
14
19
21
28
34
40
55
66
80100
130
155
200
225
250
270
310
361
425
530
XM30PB/1.4
XM30PB/2
XM30PB/2.6
XM30PB/4.0
XM30PB/5
XM30PB/8
XM30PB/8
XM30PB/10XH125NJ/20
XH125NJ/20
XH125NJ/32
XH125NJ/32
XH125NJ/50
XH125NJ/50
XH125NJ/63
XH125NJ/100
XH125NJ/100
XH125NJ/1251
)XH125NJ/125 1)
XH250NJ/250
XH250NJ/250 1)
XH250NJ/250 1)
XS400SE/400
XH400SE/400 2)
XS400SE/400
XH400SE/400 2)
XS400SE/400
XS630SE/630
XS630SE/630
CA 7-9
CA 7-9
CA 7-9
CA 7-9
CA 7-9
CA 7-9
CA 7-9
CA 7-9CA 7-12
CA 7-16
CA 7-23
CA 7-23
CA 7-30
CA 7-37
CA 7-43
CA 7-60
CA 7-72
CA 7-85CA 6-105-(El)
CA 6-140-(El)
CA 6-170-El
CA 6-210-El
CA 6-250-El
CA 6-250-EI
CA 6-300-El
CA 6-300-EI
CA 6-420-El/ CA 5-450
CA 6-420-El/ CA 5-450CA 5-550
CT 7-24
CT 7-24
CT 7-24
CT 7-24
CT 7-24
CT 7-24
CT 7-24
CT 7-24CT 7-24
CT 7-24
CT 7-24
CT 7-24
CT 7-45
CT 7-45
CT 7-45
CT 7-75
CT 7-75
CT 7-100CT 6-110
CT 6-150
CT 6-200
CEF 1-41/42 3)
CEF 1-41/42 3)
CEF 1-41/41 3)
CEF 1-41/42 3)
CEF 1-41/42 3)
CEF 1-41/42 3)
CEF 1-52 3)
CEF 1-52 3)
1-1.6
1-1.6
2.4-4
2.4-4
2.4-4
4-6
6-10
6-1010-16
10-16
16-24
16-24
18-30
30-45
30-45
45-60
60-75
70-9085-110
105-150
140-200
160-400
160-400
160-400
160-400
160-400
160-400
160-630
160-630
Approx.(amps)
Motor size(kW)
Terasaki circuitbreaker type
Sprecher + Schuhcontactor type
Sprecher + Schuhoverload type 2)
Setting range(amps)
TYPE 150 kA
(Refer Part A section 1)
Cat. No. CT 7-24Contactor CA 7-9 XM30PB
-
7/24/2019 Pt c 2007 Sec 13b Lr
35/3813 - 133
13
Type 2 short circuit co-ordinationMotor starter co-ordination tablefor DOL starting50 kA at 400-415 V to AS 3947-4-1
Notes: 1) Use magnetic only breaker or next higher circuit breaker/contactor combination. Refer NHP for factorymodification.
2) Use with separate mounting bracket.3) Thermal or electronic overload relays may be used.4) Electronic overloads.Combinations based on the thermal overload relay tripping before the circuit breaker at overloadcurrents up to the motor locked rotor current.
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
150
160
200
200
250
320
1.1
1.5
1.8
2.6
3.4
4.8
6.5
8.2
11
14
21
28
34
40
55
66
80
100
130
155
200
225
250
270
361
361
425
538
XM30PB/1.4
XM30PB/2
XM30PB/2.6
XM30PB/4.0
XM30PB/5
XM30PB/8
XM30PB/10
XM30PB/12
XH125NJ/20
XH125NJ/20
XH125NJ/32
XH125NJ/50
XH125NJ/50
XH125NJ/63
XH125NJ/100
XH125NJ/100
XH125NJ/125
XH125NJ/125 1)
XH250NJ/250
XH250NJ/250
XH250NJ/250 1)
XS400SE/400
XS400SE/400
XS400SE/400
XS400SE/400
XS400SE/400
XS630SE/630
XS630SE/630
CA 7-9
CA 7-9
CA 7-9
CA 7-16
CA 7-16
CA 7-16
CA 7-30
CA 7-30
CA 7-30
CA 7-30
CA 7-30
CA 7-43
CA 7-43
CA 7-43
CA 7-85
CA 7-85
CA 6-105-(El)
CA 6-105(El)
CA 6-140-(El)
CA 6-170-El
CA 6-210-El
CA 6-210-El
CA 6-250-EI
CA 6-300-El
CA 6-420-El
CA 5-450
CA 5-700
CA 5-700
CT 7-24-1.6
CT 7-24-1.6
CT 7-24-2.4
CT 7-24-4
CT 7-24-4
CT 7-24-6
CT 7-24-10
CT 7-24-10
CT 7-24-16
CT 7-24-16
CT 7-24-24
CT 7-45-30
CT 7-45-45
CT 7-45-45
CT 7-75 2)
CT 7-75 2)
CT 6-90
CT 6-110
CT 6-150
CT 6-200
CEF 1-41/42 4)
CEF 1-41/42 4)
CEF 1-41/42 4)
CEF 1-41/42 4)
CEF 1-41/42 4)
CEF 1- 22 2)
CEF 1- 52 2)
CEF 1- 52 2)
1-1.6
1-1.6
1.6-2.4
2.4-4
2.4-4
4-6
6-10
6-10
10-16
10-16
16-24
18-30
30-45
30-45
45-60
60-75
70-90
85-110
105-150
140-200
160-400
160-400
160-400
160-400
160-400
160-400
160-630
160-630
Approx.(amps)
Motor size(kW)
Terasaki circuitbreaker type
Sprecher + Schuhcontactor type
Sprecher + Schuhoverload type 3)
Setting range(amps)
TYPE 250 kA
-
7/24/2019 Pt c 2007 Sec 13b Lr
36/3813 - 134
13
Type 2 short circuit co-ordinationMotor starter co-ordination tablefor DOL starting65 kA, 400-415 V to AS 3947-4-1
Notes: 1) Thermal or electronic overload relays may be used.2) Use with separate mounting bracket.3) Electronic overloads.Combinations based on the overload relay tripping before the circuit breaker at overloadcurrents up to the motor locked rotor current.
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
150
160
200
200
250320
1.1
1.5
1.8
2.6
3.4
4.8
6.5
8.2
11
14
21
28
34
40
55
66
80
100
130
155
200
225
250
270
361
361
425538
XM30PB/1.4
XM30PB/2
XM30PB/2.6
XM30PB/4.0
XM30PB/5
XM30PB/8
XM30PB/8
XM30PB/12
TL30F/20A
TL30F/30A
TL30F/30A
TL100NJ/50A
TL100NJ/50A
TL100NJ/63A
TL100NJ/100A
TL100NJ/100A
TL100NJ/100A
XH400SE/250
XH400SE/250
XH400SE/250
XH400SE/250
XH400SE/400
XH400SE/400
XH400SE/400
XH400SE/400
XH400SE/400
XH630SE/630XH630SE/630
CA 7-9
CA 7-9
CA 7-9
CA 7-16
CA 7-16
CA 7-16
CA 7-30
CA 7-30
CA 7-30
CA 7-30
CA 7-30
CA 7-43
CA 7-43
CA 7-43
CA 7-72
CA 7-72
CA 6-105-(El)
CA 6-105-(El)
CA 6-140-(El)
CA 6-170-El
CA 6-210-El
CA 6-210-El
CA 6-250-EI
CA 6-300-El
CA 6-420-El
CA 5-450
CA 5-700CA 5-700
CEP 7
CEP 7
CEP 7
CEP 7
CEP 7
CEP 7
CEP 7
CEP 7
CEP 7
CEP 7
CEP 7
CEP 7
CEP 7
CEP 7
CEP 7
CEP 7
CT 6-90CT 6-110
CT 6-150
CT 6-200
CEF 1-41/42 3)
CEF 1-41/42 3)
CEF 1-41/42 3)
CEF 1-41/42 3)
CEF 1-41/42 3)
CEF 1- 22 2)
CEF 1- 522
)CEF 1- 52 2)
1.0-2.9
1.0-2.9
1.0-2.9
1.6-5
1.6-5
3.7-12
3.7-12
3.7-12
3.7-12
12-32
12-32
12-32
12-37
14-45
26-85
26-85
70-90
85-110
105-150
140-200
160-400
160-400
160-400
160-400
160-400
160-400
160-630160-630
Approx.(amps)
Motor size(kW)
Terasaki circuitbreaker type
Sprecher + Schuhcontactor type
Sprecher + Schuhoverload type 1)
Setting range(amps)
TYPE 265 kA
-
7/24/2019 Pt c 2007 Sec 13b Lr
37/3813 - 135
13
Type 2 short circuit co-ordinationMotor starter co-ordination tablefor DOL starting85 kA, 400-415 V to AS 3947-4-1
Notes: 1) Thermal or electronic overload relays may be used.Combinations based on the overload relay tripping before the circuit breaker at overload currents upto the motor locked rotor current.
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
9
10
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
1.1
1.5
1.8
2.6
3.4
4.8
6.5
8.2
11
14
17
19
21
28
34
40
55
66
80
100
135
160
200
230
270
361
XM30PB/1.4
XM30PB/2
XM30PB/2.6
XM30PB/4
XM30PB/5
XM30PB/8
XM30PB/8
XM30PB/10
TL100NJ/20
TL100NJ/20
TL100NJ/32
TL100NJ/32
TL100NJ/32
TL100NJ/50
TL100NJ/50
TL100NJ/63
TL100NJ/100
TL100NJ/100
TL250NJ/160
TL250NJ/160
TL250NJ/250
TL250NJ/250
TL250NJ/250
TL400NE/400
TL400NE/400
TL400NE/400
CA 7-9
CA 7-9
CA 7-9
CA 7-16
CA 7-16
CA 7-30
CA 7-30
CA 7-30
CA 7-30
CA 7-30
CA 7-30
CA 7-30
CA 7-30
CA 7-43
CA 7-43
CA 7-43
CA 7-72
CA 7-72
CA 6-105
CA 6-105
CA 6-210-El
CA 6-210-El
CA 6-210-EI
CA 6-210-El
CA 6-300-El
CA 6-420-El
CEP 7-M32-2.9-10
CEP 7-M32-2.9-10
CEP 7-M32-2.9-10
CEP 7-M32-2.9-10
CEP 7-M32-5-10
CEP 7-M32-12-10
CEP 7-M32-12-10
CEP 7-M32-12-10
CEP 7-M32-12-10
CEP 7-M32-32-10
CEP 7-M32-32-10
CEP 7-M32-32-10
CEP 7-M32-32-10
CEP 7-M32-32-10
CEP 7-M37-37-10
CEP 7-M45-45-10
CEP 7-M85-85-10
CEP 7-M85-85-10
CEP 7-M85-85-10
CEF 1-11/12
CEF 1-11/12
CEF 1-11/12
CEF 1-41/42/52
CEF 1-41/42/52
CEF 1-41/42/52
CEF 1-41/42/52
1.0-2.9
1.0-2.9
1.0-2.9
1.0-2.9
1.6-5
3.7-12
3.7-12
3.7-12
3.7-12
12-32
12-32
12-32
12-32
12-32
12-37
14-45
26-8526-85
26-85
0.5-180
0.5-180
0.5-180
160-630
160-630
160-630
160-630
Approx.FLC (A)at 415 V
Motor size(kW)
Terasaki circuitbreaker type
Sprecher + Schuhcontactor type
Sprecher + Schuhoverload type 1)
Setting range(amps)
TYPE 285 kA
-
7/24/2019 Pt c 2007 Sec 13b Lr
38/38
Nowf
its
MCCB
sto
800A