Psychrometry - Rajagiri School of Engineering & Technology

113
PSYCHROMETRY

Transcript of Psychrometry - Rajagiri School of Engineering & Technology

Page 1: Psychrometry - Rajagiri School of Engineering & Technology

PSYCHROMETRY

Page 2: Psychrometry - Rajagiri School of Engineering & Technology

AIR CONDITIONING Treating or conditioning of air to alter its

temperature and moisture content to suit

specific requirements.

William H Carrier – Father of Air

Conditioning.

Working substance – Atmospheric Air

Atmospheric Air – Dry Air + Water Vapor

Page 3: Psychrometry - Rajagiri School of Engineering & Technology

Composition of standard air

• International joint committee in 1949.

• The molecular weight of dry air is found tobe 28.966 and the gas constant R is287.035 J/kg.K.

• The mixture of dry air and water vapor iscalled as moist air.

Page 4: Psychrometry - Rajagiri School of Engineering & Technology

• At a given temperature and pressure the dryair can only hold a certain maximumamount of moisture.

• When the moisture content is maximum,then the air is known as saturated air.

• Any addition of moisture will drop out asfree water.

• The molecular weight of water vapour is18.015 and its gas constant is 461.52J/kg.K.

Page 5: Psychrometry - Rajagiri School of Engineering & Technology

Atmospheric air

Page 6: Psychrometry - Rajagiri School of Engineering & Technology

PSYCHROMETRY is the study of the properties ofmixtures of air and water vapor(Atmospheric Air).

Atmospheric air makes up the environment inalmost every type of air conditioning system.

Hence a thorough understanding of theproperties of atmospheric air and the ability toanalyze various processes involving air isfundamental to air conditioning design.

Psychrometry

Page 7: Psychrometry - Rajagiri School of Engineering & Technology

Psychrometric Properties• DRY BULB TEMPERATURE (DBT) - It is the

temperature of the moist air as measured by astandard thermometer or other temperaturemeasuring instruments.

• SATURATED VAPOUR PRESSURE (PSAT) - is thesaturated partial pressure of water vapour at thedry bulb temperature.

• WET BULB TEMPERATURE(WBT) - Temperatureof the moist air as measured by standardthermometer when its bulb is wound by a wet wick.

for dry air WBT < < DBT

for saturated air WBT = DBT

Page 8: Psychrometry - Rajagiri School of Engineering & Technology

DRY BULB AND WET BULB TEMPERATURES

Heat from atmospheric air

Heat from atmospheric air

Heat used for vaporization of water to atmospheric air

Note: If atmospheric air is saturated then vaporization won’t take place so whole of the heat will be transmitted to the wet bulb. So in case of saturated air DBT = WBT

Wet bulb depression

• For dry air WBD will be maximum

• For saturated air WBD will be 0

Dry bulb thermometer

Wet bulb thermometer

Page 9: Psychrometry - Rajagiri School of Engineering & Technology

Dry-Bulb Thermometer

Page 10: Psychrometry - Rajagiri School of Engineering & Technology

Wet-Bulb Thermometer

Page 11: Psychrometry - Rajagiri School of Engineering & Technology

DEW POINT TEMPERATURE(DPT)• If unsaturated moist air is cooled at constant pressure

the temperature at which moisture in the air begins tocondense is called DPT.

• The DPT is the saturation temperature corresponding tothe vapour pressure of water vapour. So it can beobtained from steam tables.

Page 12: Psychrometry - Rajagiri School of Engineering & Technology

Condensation Occurs At Dew Point

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 13: Psychrometry - Rajagiri School of Engineering & Technology

Fog Occurs When Air Is Saturated

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 14: Psychrometry - Rajagiri School of Engineering & Technology

Humidity Ratio(Specific Humidity)…compares water vapor to dry air, by weight

Page 15: Psychrometry - Rajagiri School of Engineering & Technology

Relative Humidity(Φ)…describes the degree of saturation

RelativeHumidity

Amount of moisture that a givenamount of air is holding at agiven temp.

=Amount of moisture that a givenamount of air can hold at sametemp.

• It is defined as the ratio of the mole fraction ofwater vapour in moist air to mole fraction ofwater vapour in saturated air at the sametemperature and pressure.

=

Page 16: Psychrometry - Rajagiri School of Engineering & Technology

50% 100%(saturated)

Relative Humidity…compares moisture content to saturation

Page 17: Psychrometry - Rajagiri School of Engineering & Technology

Relative Humidity

50% RH means that the air contains halfthe amount of water vapor it can hold atthat temp.

RH increases as the temp. decreases.

The maximum amount ofmoisture(saturation) that a given volumeof air can hold varies with temp.

The temp. at which RH becomes 100% iscalled DPT.

Page 18: Psychrometry - Rajagiri School of Engineering & Technology

Degree of saturation (μ)

Page 19: Psychrometry - Rajagiri School of Engineering & Technology

Enthalpy of Moist Air

Page 20: Psychrometry - Rajagiri School of Engineering & Technology

Humid specific heat

• It is the specific heat of humid(or moist) air per kg ofdry air.

• From the equation for enthalpy of moist air, thehumid specific heat of moist air can be written as:

• For all practical purposes the humid specific heat ofmoist air, cpm can be taken as 1.0216 kJ/kg dry air.K

Page 21: Psychrometry - Rajagiri School of Engineering & Technology

Specific volume • The specific volume is defined as the number of

cubic meters of moist air per kilogram of dry air.

• The empirical relations for the vapor pressure ofwater in moist air:

Page 22: Psychrometry - Rajagiri School of Engineering & Technology

Adiabatic saturation and Thermodynamic WBT

It is the temp at

which air can be

brought to saturation

state adiabatically by

evaporation of water

into the flowing air.

Page 23: Psychrometry - Rajagiri School of Engineering & Technology

• An adiabatic saturator is a device in which air flowsthrough an infinitely long duct containing water.

• The device is adiabatic as the walls of the chamber arethermally insulated.

• As the air comes in contact with water in the duct, therewill be heat and mass transfer between water and air.

• Air at the exit would be fully saturated and its temperatureis equal to that of water temperature.

• Make-up water to be provided to compensate for theamount of water evaporated into the air.

• After the adiabatic saturator has achieved asteady-state condition, the temperatureindicated by the thermometer immersed inthe water is the thermodynamic wet-bulbtemperature.

Page 24: Psychrometry - Rajagiri School of Engineering & Technology

Problem 1

On a particular day the weather forecaststates that the dry bulb temperature is 37oC,while the relative humidity is 50% and thebarometric pressure is 101.325 kPa. Find thehumidity ratio, dew point temperature andenthalpy of moist air on this day.

Page 25: Psychrometry - Rajagiri School of Engineering & Technology

Problem 2

Moist air at 1 atm. pressure has a dry bulbtemperature of 32oC and a wet bulbtemperature of 26oC. Calculate a) the partialpressure of water vapour, b) humidity ratio,c) relative humidity, d) dew pointtemperature, e) density of dry air in themixture, f) density of water vapour in themixture and g) enthalpy of moist air usingperfect gas law model and Psychrometricequations.

Page 26: Psychrometry - Rajagiri School of Engineering & Technology

The Psychrometric Chart

A Psychrometric chart graphically represents

the thermodynamic properties of moist air.

The chart is normally drawn for air at 1 atm.

Pressure.

Page 27: Psychrometry - Rajagiri School of Engineering & Technology

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 28: Psychrometry - Rajagiri School of Engineering & Technology

PSYCHROMERTIC PROPERTY CURVES

DBT= const

w = constDPT

• If we know any twoPsychrometric propertieswe can locate the statepoint of moist air inPsychrometric chart.

•And can easily identifyhow much energy (Δh) hasto be supplied or removedto bring the air to arequired state.

•From these data we candesign an AC system

Page 29: Psychrometry - Rajagiri School of Engineering & Technology

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

DRY BULB TEMPERATURE - °F

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

HU

MID

ITY

RA

TIO

- G

RA

INS

OF

MO

IST

UR

E P

ER

PO

UN

D O

F D

RY

AIR

PSYCHROMETRIC CHARTLexington, Kentucky USABAROMETRIC PRESSURE 28.874 inches of Mercury

Linric Company Psychrometric Chart, www.linric.com

Staturation Line

Saturation Line

Page 30: Psychrometry - Rajagiri School of Engineering & Technology

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

DRY BULB TEMPERATURE - °F

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

HU

MID

ITY

RA

TIO

- G

RA

INS

OF

MO

IST

UR

E P

ER

PO

UN

D O

F D

RY

AIR

PSYCHROMETRIC CHARTLexington, Kentucky USABAROMETRIC PRESSURE 28.874 inches of Mercury

Linric Company Psychrometric Chart, www.linric.com

Constant Dry Bulb Temperature

Constant Dry Bulb Temperature

Page 31: Psychrometry - Rajagiri School of Engineering & Technology

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

DRY BULB TEMPERATURE - °F

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

HU

MID

ITY

RA

TIO

- G

RA

INS

OF

MO

IST

UR

E P

ER

PO

UN

D O

F D

RY

AIR

PSYCHROMETRIC CHARTLexington, Kentucky USABAROMETRIC PRESSURE 28.874 inches of Mercury

Linric Company Psychrometric Chart, www.linric.com

Constant Humidity Ratio

Constant Humidity Ratio & Pressure

Page 32: Psychrometry - Rajagiri School of Engineering & Technology

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

DRY BULB TEMPERATURE - °F

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

HU

MID

ITY

RA

TIO

- G

RA

INS

OF

MO

IST

UR

E P

ER

PO

UN

D O

F D

RY

AIR

PSYCHROMETRIC CHARTLexington, Kentucky USABAROMETRIC PRESSURE 28.874 inches of Mercury

Linric Company Psychrometric Chart, www.linric.com

Constant Humidity Ratio

Dew Point temp.

Page 33: Psychrometry - Rajagiri School of Engineering & Technology

30

Dry-Bulb Temperature (°F)

Gra

ins O

f M

ois

ture

Pe

r P

ou

nd

Of

Dry

Air

When S

atu

rate

d (

gra

ins/lb

of

dry

air)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

20

0

40

60

80

100

120

140

160

180

200

220

Constant Relative Humidity Curves

Relative Humidity

0%

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 34: Psychrometry - Rajagiri School of Engineering & Technology

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

DRY BULB TEMPERATURE - °F

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

0 5

510

1015

1520

2025

2530

3035

3540

4045

45 50

50 55

55 60

6065

65

70

70

75

75

80

80

85 WET BULB TEMPERATURE - °F

85

HU

MID

ITY

RA

TIO

- G

RA

INS

OF

MO

IST

UR

E P

ER

PO

UN

D O

F D

RY

AIR

PSYCHROMETRIC CHARTLexington, Kentucky USABAROMETRIC PRESSURE 28.874 inches of Mercury

Linric Company Psychrometric Chart, www.linric.com

Constant Web Bulb Temperature

Constant Wet Bulb Temperature

Page 35: Psychrometry - Rajagiri School of Engineering & Technology

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

DRY BULB TEMPERATURE - °F

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

HU

MID

ITY

RA

TIO

- G

RA

INS

OF

MO

IST

UR

E P

ER

PO

UN

D O

F D

RY

AIR

PSYCHROMETRIC CHARTLexington, Kentucky USABAROMETRIC PRESSURE 28.874 inches of Mercury

Linric Company Psychrometric Chart, www.linric.com

Constant Enthalpy

Constant Enthalpy

Page 36: Psychrometry - Rajagiri School of Engineering & Technology

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

DRY BULB TEMPERATURE - °F

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

0 5

510

1015

1520

2025

2530

3035

3540

4045

45 50

50 55

55 60

6065

65

70

70

75

75

80

80

85 WET BULB TEMPERATURE - °F

85

HU

MID

ITY

RA

TIO

- G

RA

INS

OF

MO

IST

UR

E P

ER

PO

UN

D O

F D

RY

AIR

PSYCHROMETRIC CHARTLexington, Kentucky USABAROMETRIC PRESSURE 28.874 inches of Mercury

Linric Company Psychrometric Chart, www.linric.com

Constant Enthalpy

and

Constant Web Bulb

Constant Enthalpy and Web Bulb

Page 37: Psychrometry - Rajagiri School of Engineering & Technology

30

Dry-Bulb Temperature (°F)

Gra

ins O

f M

ois

ture

Pe

r P

ou

nd

Of

Dry

Air

When S

atu

rate

d (

gra

ins/lb

of

dry

air)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

20

0

40

60

80

100

120

140

160

180

200

220

A Final Property…Specific Volume

Specific Volume Lines

(cubic feet / pound of dry air)

Page 38: Psychrometry - Rajagiri School of Engineering & Technology

“X Marks The Spot”…

95°F

78°F

72°F

Page 39: Psychrometry - Rajagiri School of Engineering & Technology

30

Dry-Bulb Temperature (°F)

Gra

ins O

f M

ois

ture

Pe

r P

ou

nd

Of

Dry

Air

When S

atu

rate

d (

gra

ins/lb

of

dry

air)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

20

0

40

60

80

100

120

140

160

180

200

220

relationship between…

Dry Bulb, Wet Bulb And Dew Point

60°F

Dew Point60°F

Wet Bulb

A B C DDry Bulb 60°F 62°F 75°F 90°F

Wet Bulb 60°F 60.8°F 65.2°F 70°F

Dew Point 60°F 60°F 60°F 60°F

Rel Humidity 100% 92% 60% 37%

DCB

A

Page 40: Psychrometry - Rajagiri School of Engineering & Technology

30

Dry-Bulb Temperature (°F)

Gra

ins O

f M

ois

ture

Pe

r P

ou

nd

Of

Dry

Air

When S

atu

rate

d (

gra

ins/lb

of

dry

air)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

20

0

40

60

80

100

120

140

160

180

200

220

Determining Wet-Bulb Lines

A

BICIDI

B C D

AI

Page 41: Psychrometry - Rajagiri School of Engineering & Technology

Knowing Two Properties…lets you determine the remaining three

Dry-bulb temperature

Wet-bulb temperature

Dew-point temperature

Relative humidity

Humidity ratio

Page 42: Psychrometry - Rajagiri School of Engineering & Technology

30

Dry-Bulb Temperature (°F)

Gra

ins O

f M

ois

ture

Pe

r P

ou

nd

Of

Dry

Air

When S

atu

rate

d (

gra

ins/lb

of

dry

air)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

20

0

40

60

80

100

120

140

160

180

200

220

intersection of two known air properties…

Determines The Remaining Three

Humidity Ratio

Dry BulbRelative Humidity

Wet Bulb

Dew Point

Page 43: Psychrometry - Rajagiri School of Engineering & Technology

PSYCHROMERTIC PROCESSES

DBT

wO AB

C

D

E

F

O-A SENSIBLE HEATINGO-B SENSIBLE COOLINGO-C HEATING + HUMIDIFICATIONO-D HEATING +DEHUMIDIFICATIONO-E COOLING + HUMIDIFICATIONO-F COOLING + DEHUMIDIFATION

WINTER AC

SUMMER AC

Page 44: Psychrometry - Rajagiri School of Engineering & Technology

PSYCHROMETRIC PROCESSES1. SENSIBLE HEATING – During this process moisture content of the airremains constant. But its temperature increases as it flows over a heatingcoil.

2. SENSIBLE COOLING – During this process moisture content of the airremains constant . But its temperature decreases as it flows over a coolingcoil. For the moisture to remain constant the surface of the cooling coilshould be dry and DBTin > Tsurface > DPTin to avoid condensation ofmoisture.

Heating coil Cooling coil (T > DPTin )

Cold air Cold airHot airHot air

SENSIBLE HEATING SENSIBLE COOLING

Page 45: Psychrometry - Rajagiri School of Engineering & Technology

Effect Of Adding Sensible Heat

Page 46: Psychrometry - Rajagiri School of Engineering & Technology

Effect Of Removing Sensible Heat

Page 47: Psychrometry - Rajagiri School of Engineering & Technology

30

Dry-Bulb Temperature (°F)

Gra

ins O

f M

ois

ture

Pe

r P

ou

nd

Of

Dry

Air

When S

atu

rate

d (

gra

ins/lb

of

dry

air)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

20

0

40

60

80

100

120

140

160

180

200

220

moisture content doesn’t change by…

Adding/removing Sensible Heat

100% Saturation

60°F

Dew Point60°F

Wet Bulb

Page 48: Psychrometry - Rajagiri School of Engineering & Technology

Effect Of Adding Moisture

Page 49: Psychrometry - Rajagiri School of Engineering & Technology

Effect Of Removing Moisture

Page 50: Psychrometry - Rajagiri School of Engineering & Technology

PSYCHROMETRIC PROCESSES

3. HEATING AND HUMIDIFICATION- in this process air is first sensiblyheated by a heating coil followed by spraying steam via steam nozzle.

4. HEATING AND DEHUMIDIFICATION - This process is achieved byusing hygroscopic materials. Absorption of moisture by hygroscopicmaterial(liquid/solid) is an exothermic reaction, as a result heat isreleased and temperature of air increases.

Heating coilHYGROSCOPIC

MATERIAL

Colddry air

ColdHumid

air

Hot dry air

Hot humid air

HEATING AND HUMIDIFICATION HEATING AND DEHUMIDIFICATION

Steam Nozzle

Page 51: Psychrometry - Rajagiri School of Engineering & Technology

PSYCHROMETRIC PROCESSES

5. COOLING AND HUMIDIFICATION- In this process air is cooled by sprayingcold water into air stream.

6. COOLING AND DEHUMIDIFICATION - In this process air is cooled andmoisture is removed when it flows over a cooling coil

Cold water sprinkler

Hot dry air

Hot Humid

air

Cold dry air

Coldhumid air

COOLING AND HUMIDIFICATIONCOOLING AND DEHUMIDIFICATION

Cooling coil (

Page 52: Psychrometry - Rajagiri School of Engineering & Technology

effect of changing…

Sensible Heat And Moisture Content

Page 53: Psychrometry - Rajagiri School of Engineering & Technology

effect of changing…

Sensible Heat And Moisture Content

Page 54: Psychrometry - Rajagiri School of Engineering & Technology

PSYCHROMETER

• Any instrument capable of measuring thepsychrometric state of air is called apsychrometer.

• It comprises of two thermometers with thebulb of one covered by a moist wick.

• The two sensing bulbs are separated andshaded from each other so that the radiationheat transfer between them becomesnegligible

Page 55: Psychrometry - Rajagiri School of Engineering & Technology

Sling Psychrometer• Widely used for measurements where the

air velocity inside the room is small.

• Consists two thermometers mounted sideby side and fitted in a frame with a handlefor whirling the device through air.

• The required air circulation (≈ 3 to 5 m/s)over the sensing bulbs is obtained bywhirling the psychrometer (≈ 300 RPM).

• Readings are taken when both thethermometers show steady-state readings.

Page 56: Psychrometry - Rajagiri School of Engineering & Technology

Aspirated Psychrometer• The thermometers remain stationary, and a

small fan, blower or syringe moves the airacross the thermometer bulbs.

• The wicks made of cotton or cloth should bereplaced frequently, and only distilled watershould be used for wetting it.

Other types are:

1. Dunmore Electric Hygrometer

2. DPT meter

3. Hygrometer (Using horse’s or human hair)

Page 57: Psychrometry - Rajagiri School of Engineering & Technology

AIR WASHER

Page 58: Psychrometry - Rajagiri School of Engineering & Technology

• An air washer is a device for conditioningair.

• Air comes in direct contact with a spray ofwater - exchange of heat and mass (watervapour) between air and water.

• The outlet condition of air depends uponthe temperature of water sprayed.

• Hence, by controlling the water temperatureexternally, it is possible to control the outletconditions of air, which then can be used forair conditioning purposes.

Page 59: Psychrometry - Rajagiri School of Engineering & Technology

• The mean temperature of water droplets incontact with air decides the direction of heatand mass transfer. Examples are:-

• Cooling and dehumidification: tw < tDPT. Hereboth latent and sensible heat transfers are fromair to water. So water has to be externallycooled.

• Adiabatic saturation: tw = tWBT. Here the sensibleheat transfer from air to water is exactly equalto latent heat transfer from water to air. Hence,no external cooling or heating of water isrequired. This the process that takes place in aperfectly insulated evaporative cooler.

Page 60: Psychrometry - Rajagiri School of Engineering & Technology

• Cooling and humidification: tDPT < tw < tWBT.Here the sensible heat transfer is from air towater and latent heat transfer is from waterto air, but the total heat transfer is from airto water, hence, water has to be cooledexternally.

• Cooling and humidification: tWBT < tw < tDBT.Here the sensible heat transfer is from air towater and latent heat transfer is from waterto air, but the total heat transfer is fromwater to air, hence, water has to be heatedexternally. This is the process that takes placein a cooling tower.

Page 61: Psychrometry - Rajagiri School of Engineering & Technology

• Heating and humidification: tw > tDBT. Hereboth sensible and latent heat transfers arefrom water to air, hence, water has to beheated externally.

• An air washer works as a year-round airconditioning system.

• It is not commonly used for comfort airconditioning applications due to concernsabout health resulting from bacterial orfungal growth on the wetted surfaces.

• It can be used in industrial applications.

Page 62: Psychrometry - Rajagiri School of Engineering & Technology

Psychrometry

Air Mixtures

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 63: Psychrometry - Rajagiri School of Engineering & Technology

Air Conditioner

Supply Fan

Mixture OutdoorAir (OA)

Recirculated Air (RA)

A

C

B

Cooling Coil

Determining Entering Air Conditions

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 64: Psychrometry - Rajagiri School of Engineering & Technology

80°F95°F

Determining Entering Air Conditions

B

A

Outdoor

Air

Recirculated

Air

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 65: Psychrometry - Rajagiri School of Engineering & Technology

1,000 cfm4,000 cfm

= 0.25

OA

RA

Mixture

=

=

=

25%

75%

100%

A

C B4,000 cfmMixed Air

1,000 cfmOA

3,000 cfmRA

Determining Entering Air Conditions

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 66: Psychrometry - Rajagiri School of Engineering & Technology

95°F × 0.25 = 23.75°F

80°F × 0.75 = 60.00°F

Mixture = 83.75°F

Mixed Air Temperature

Determining Entering Air Conditions

Page 67: Psychrometry - Rajagiri School of Engineering & Technology

83.75°F

70°F

Determining Entering Air Conditions

B

80°F

95°F

C

A

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 68: Psychrometry - Rajagiri School of Engineering & Technology

Psychrometry

Sensible Heat Ratio

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 69: Psychrometry - Rajagiri School of Engineering & Technology

Effect Of Removing Sensible Heat

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 70: Psychrometry - Rajagiri School of Engineering & Technology

Effect Of Removing Latent Heat

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 71: Psychrometry - Rajagiri School of Engineering & Technology

effect of…

Removing Sensible And Latent Heat

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 72: Psychrometry - Rajagiri School of Engineering & Technology

SHRSensible Heat Gain

Sensible Heat Gain + Latent Heat Gain=

determining the…

Sensible Heat Ratio (SHR)

Page 73: Psychrometry - Rajagiri School of Engineering & Technology

78°F DB

65°F WB

Index Point

Sensible Heat Ratio Scale

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 74: Psychrometry - Rajagiri School of Engineering & Technology

Drawing An SHR Line

A

Index Point

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 75: Psychrometry - Rajagiri School of Engineering & Technology

Room SHR dictates…

Supply Air Conditions

A

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 76: Psychrometry - Rajagiri School of Engineering & Technology

C

DB

80°F

drawing an SHR line for…

Other Room Conditions

Index Point

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 77: Psychrometry - Rajagiri School of Engineering & Technology

Psychrometry

Air Quantity

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 78: Psychrometry - Rajagiri School of Engineering & Technology

80,000 kJ/hr sensible heat gain

20,000 kJ/hr latent heat gain

= 0.80

STEP 1: Calculate the sensible heat ratio (SHR)

80,000 kJ/hr

100,000 kJ/hrSHR =

Determining Supply Airflow

Page 79: Psychrometry - Rajagiri School of Engineering & Technology

Room — 78°F DB, 50% RH

OA — 95°F DB, 78°F WB

Ventilation — 25% OA

Determining Supply Airflow

Design Conditions:

Page 80: Psychrometry - Rajagiri School of Engineering & Technology

95°F × 0.25 = 23.75°F

78°F × 0.75 = 58.50°F

Mixture = 82.25°F

Determining Supply AirflowSTEP 2: Plot room, outdoor, and entering conditions

A

C

B

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 81: Psychrometry - Rajagiri School of Engineering & Technology

56.5°F 78°F

STEP 3: Identify supply air conditions

A

C

B

D

Determining Supply Airflow

Air Conditioning Clinic TRG-TRC001-EN© American Standard Inc. 1999

Page 82: Psychrometry - Rajagiri School of Engineering & Technology

Sensible Heat Gain0.02044 × (Room DBT – Supply

DBT)

SupplyAirflow in CMM

=

STEP 4: Solve the supply airflow equation

Determining Supply Airflow

CMM = Cubic meter/minute(m3/minute)

DBT in 0C

Sensible Heat gain in kJ/s

Page 83: Psychrometry - Rajagiri School of Engineering & Technology

DUCT DESIGN

Page 84: Psychrometry - Rajagiri School of Engineering & Technology

The chief requirements are:

• It should convey specified rates of air flowto prescribed locations

• It should be economical in combined initialcost, fan operating cost and cost of buildingspace

• It should not transmit or generateobjectionable noise

Page 85: Psychrometry - Rajagiri School of Engineering & Technology

Pre-requisites of duct design are:

• The required airflow rates from loadcalculations.

• The location of fans and air outlets arefixed initially.

• The duct layout is then made takinginto account the space available andease of construction.

Page 86: Psychrometry - Rajagiri School of Engineering & Technology

General rules for duct design

• Air should be conveyed as directly aspossible to save space, power andmaterial.

• Sudden changes in directions should beavoided. When not possible to avoidsudden changes, turning vanes shouldbe used to reduce pressure loss.

• Diverging sections should be gradual.Angle of divergence ≤ 20o

Page 87: Psychrometry - Rajagiri School of Engineering & Technology

• Aspect ratio should be as close to1.0 as possible. Normally, it shouldnot exceed 4.

• Air velocities should be withinpermissible limits to reduce noiseand vibration.

• Duct material should be as smoothas possible to reduce frictionallosses.

Page 88: Psychrometry - Rajagiri School of Engineering & Technology

Classification

• Low pressure systems: Velocity ≤10 m/s, static pressure ≤ 5 cm H2O

• Medium pressure systems: Velocity≤ 10 m/s, static pressure ≤ 15 cmH2 O

• High pressure systems: Velocity >10 m/s, static pressure 15<p ≤ 25cm H2O

Page 89: Psychrometry - Rajagiri School of Engineering & Technology

High velocities in the ducts resultsin:

• Smaller ducts and hence, lowerinitial cost and lower spacerequirement

• Higher pressure drop and hencelarger fan power consumption

• Increased noise and hence a needfor noise attenuation

Page 90: Psychrometry - Rajagiri School of Engineering & Technology

Typical recommended velocities are:

• Residences: 3 m/s to 5 m/s

• Theatres: 4 to 6.5 m/s

• Restaurants: 7.5 m/s to 10 m/s

If nothing is specified, then a velocity of 5 to 8m/s is used for main ducts and a velocity of 4to 6 m/s is used for the branches.

The allowable air velocities can be as high as30 m/s in ships and aircrafts to reduce thespace requirement.

Page 91: Psychrometry - Rajagiri School of Engineering & Technology

Duct Design Methods • The run with the highest

pressure drop is called asthe index run.

• From load andPsychrometric calculationsthe required supply airflowrates are known.

• From the building layoutand the location of thesupply fan, the length ofeach duct run is known.

Page 92: Psychrometry - Rajagiri School of Engineering & Technology

• The purpose of the duct design is to selectsuitable dimensions of duct for each runand then to select a fan, which can providethe required supply airflow rate to eachconditioned zone.

• Most commonly used methods are:

1. Velocity method

2. Equal Friction (Constant pressure loss) Method

3. Static Regain method

Page 93: Psychrometry - Rajagiri School of Engineering & Technology

Velocity method• Here the velocity decreases as the flow

proceeds.

The various steps involved are:

Select suitable velocities in the main andbranch ducts

Find the diameters of main and branchducts from airflow rates and velocities forcircular ducts. For rectangular ducts, findthe cross-sectional area from flow rate andvelocity, and then by fixing the aspect ratio,find the two sides of the rectangular duct.

Page 94: Psychrometry - Rajagiri School of Engineering & Technology

From the velocities and ductdimensions obtained, find thefrictional pressure drop for main andbranch ducts.

From the duct layout, dimensions andairflow rates, find the dynamicpressure losses for all the bends andfittings.

Select a fan that can provide sufficientairflow for the index run.

Page 95: Psychrometry - Rajagiri School of Engineering & Technology

• Balancing dampers have to be installedin each run.

• The damper in the index run is leftcompletely open, while the otherdampers are throttled to reduce theflow rate to the required design values.

• The application of this method requiresselection of suitable velocities indifferent duct runs, which requiresexperience.

Page 96: Psychrometry - Rajagiri School of Engineering & Technology

• Wrong selection of velocities can lead tovery large ducts, which, occupy largebuilding space and increases the cost, orvery small ducts which lead to largepressure drop and hence necessitates theselection of a large fan leading to higher fancost and running cost.

• The method is not very efficient as itrequires partial closing of all the dampersexcept the one in the index run, so that thetotal pressure drop in each run will be same.

Page 97: Psychrometry - Rajagiri School of Engineering & Technology

Equal friction method• Here the frictional pressure drop per unit

length in the main and branch ducts (Δpf/L)are kept same, i.e.,

The stepwise procedure are as follows:

Select a suitable frictional pressure drop perunit length (Δpf/L) so that the combinedinitial and running costs are minimized.

Page 98: Psychrometry - Rajagiri School of Engineering & Technology

Then the equivalent diameter of the mainduct (A) is obtained from the selected valueof (Δpf/L) and the airflow rate.

• Airflow rate in the main duct is equal to thesum total of airflow rates to all theconditioned zones.

• From the airflow rate and (Δpf/L) theequivalent diameter of the main duct (Deq.)can be obtained either from the friction chartor using the frictional pressure drop equation:

Page 99: Psychrometry - Rajagiri School of Engineering & Technology

Since the frictional pressure drop per unitlength is same for all the duct runs, theequivalent diameters of the other duct runs,are obtained from the equation:

The velocity of air through each duct isobtained from the volumetric flow rate and thecross-sectional area.

Next from the dimensions of the ducts in eachrun, the total frictional pressure drop of thatrun is obtained by multiplying the frictionalpressure drop per unit length and the length

Page 100: Psychrometry - Rajagiri School of Engineering & Technology

Next the dynamic pressure losses in eachduct run are obtained based on the typeof bends or fittings used in that run.

Next the total pressure drop in each ductrun is obtained by summing up thefrictional and dynamic losses of that run

Next the fan is selected to suit the indexrun with the highest pressure loss.Dampers are installed in all the duct runsto balance the total pressure loss.

Page 101: Psychrometry - Rajagiri School of Engineering & Technology

• This method usually yields a better design asmost of the available pressure drop isdissipated as friction in the duct runs, ratherthan in the balancing dampers.

• Generally suitable when the ducts are not toolong, and it can be used for both supply andreturn ducts.

• However, it requires partial closure of dampersin all but the index run, which may generatenoise.

• If the ducts are too long then the total pressuredrop will be high and due to dampering, ductsnear the fan get over-pressurized.

Page 102: Psychrometry - Rajagiri School of Engineering & Technology

Static Regain Method• Commonly used for high velocity systems

with long duct runs, especially in largesystems.

• The static pressure is maintained samebefore each terminal or branch.

The procedure followed is as given below:

Velocity in the main duct leaving the fan isselected first.

Page 103: Psychrometry - Rajagiri School of Engineering & Technology

Velocities in each successive runs arereduced such that the gain in static pressuredue to reduction in velocity pressure equalsthe frictional pressure drop in the next ductsection. Thus the static pressure before eachterminal or branch is maintained constant.

Page 104: Psychrometry - Rajagiri School of Engineering & Technology

If section 1 is the outlet of the fan, then itsdimensions are known from the flow rateand velocity (initially selected).

Since both the dimensions and velocity atsection 2 are not known, a trial-and-errormethod has to be followed to get requireddimensions of the section at 2.

The procedure is followed in the direction ofairflow, and the dimensions of thedownstream ducts are obtained.

The total pressure drop is obtained from thepressure drop in the longest run and a fan isaccordingly selected.

Page 105: Psychrometry - Rajagiri School of Engineering & Technology

• Static Regain method yields a morebalanced system and does not call forunnecessary dampering.

• However, as velocity reduces in thedirection of airflow, the duct size mayincrease in the airflow direction.

• Also the velocity at the exit of thelonger duct runs may become too smallfor proper air distribution in theconditioned space.

Page 106: Psychrometry - Rajagiri School of Engineering & Technology

AIR DISTRIBUTION SYSTEMS

Page 107: Psychrometry - Rajagiri School of Engineering & Technology

Definitions

Page 108: Psychrometry - Rajagiri School of Engineering & Technology
Page 109: Psychrometry - Rajagiri School of Engineering & Technology

Principles of air distribution

Page 110: Psychrometry - Rajagiri School of Engineering & Technology

Location of return duct opening

Page 111: Psychrometry - Rajagiri School of Engineering & Technology

Air-handling SystemThe air handling system consists:

Figure shows schematic air-flow diagram foran air-conditioning system. It may be seenthat in circulation of air a closed loop isformed. In this loop the point is room itselfwhich can be considered at atmosphericpressure.

Page 112: Psychrometry - Rajagiri School of Engineering & Technology

Through the inlets the air enters and it continues todrop in pressure until it reaches the fan. The fanraises the pressure, and this pressure thereafterstarts dropping again until the air enters the space.Therefore, the pressure on the discharge side of thefan is positive and on suction side negative.

Page 113: Psychrometry - Rajagiri School of Engineering & Technology