PROJECT TITLE - Ecuip Sustainability · location: point of interconnection, nec 705.12(d)(3)...

7
1234 COMPANY ADDRESS CITY STATE 12345 PH: 888-888-8888 WEB: WWW.COMPANY.COM 1234 PROJECT ADDRESS CITY STATE 12345 ENGINEER OF RECORD YOUR COMPANY CONTRACTOR | EC12345 CBC12345 PROJECT NAME PROJECT ID: XXXX-XXX-XXX DATE 00.00.00 BY DESCRIPTION INITIAL DESIGN M.D. T.01 SCALE: NTS' PAPER: ARCHB VER 01 VICINITY VIEW NTS 01 FNAME LNAME LIC NO. UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. SHEET INDEX COVER PAGE ROOF PLAN & PV LAYOUT ATTACHMENT DETAILS ELECTRICAL SLD LABELS DATASHEET (STRUCTURAL) DATASHEET (ELECTRICAL) T.01 S.01 S.02 E.01 L.01 D.01 D.02 PROJECT INFORMATION AUTHORITY HAVING JURISDICTION BUILDING: DESIGN SPECS WIND EXPOSURE: WIND SPEED: GOVERNING CODES BUILDING: ELECTRICAL: FIRE: SYSTEM SIZE (KWDC): # PANELS: PANEL: INVERTER: VOLTAGE: CITY OF XYZ B 140 MPH FBC 2017 NEC 2014 2015 NFPA 1 10.20KW 34 SM 300WATT SE10000 120/240V AERIAL MAP NTS 02 PROJECT TITLE PROJECT ADDRESS A B C D E F 1 2 3 4 5 6 7 8 9 LOGO EXAMPLE ONLY

Transcript of PROJECT TITLE - Ecuip Sustainability · location: point of interconnection, nec 705.12(d)(3)...

Page 1: PROJECT TITLE - Ecuip Sustainability · location: point of interconnection, nec 705.12(d)(3) warning: dual power sources. second source is pv system. general 1.1. labeling requirements

1234 COMPANY ADDRESS

CITY STATE 12345

PH: 888-888-8888

WEB: WWW.COMPANY.COM

1234 PROJECT ADDRESS

CITY STATE 12345

ENGINEER OF RECORD

YOUR COMPANY

CONTRACTOR | EC12345 CBC12345

PROJECT NAME

PROJECT ID: XXXX-XXX-XXX

DATE

00.00.00

BY DESCRIPTION

INITIAL DESIGNM.D.

T.01

SCALE:

NTS'

PAPER:

ARCHB

VER

01

VICINITY VIEW

NTS

01

FNAME LNAME

LIC NO.

UNAUTHORIZED USE OF THIS

DRAWING SET WITHOUT

WRITTEN PERMISSION FROM

CONTRACTOR IS IN VIOLATION

OF U.S. COPYRIGHT LAWS AND

WILL BE SUBJECT TO CIVIL

DAMAGES AND PROSECUTIONS.

SHEET INDEX

COVER PAGE

ROOF PLAN & PV LAYOUT

ATTACHMENT DETAILS

ELECTRICAL SLD

LABELS

DATASHEET (STRUCTURAL)

DATASHEET (ELECTRICAL)

T.01

S.01

S.02

E.01

L.01

D.01

D.02

PROJECT INFORMATION

AUTHORITY HAVING JURISDICTION

BUILDING:

DESIGN SPECS

WIND EXPOSURE:

WIND SPEED:

GOVERNING CODES

BUILDING:

ELECTRICAL:

FIRE:

SYSTEM

SIZE (KWDC):

# PANELS:

PANEL:

INVERTER:

VOLTAGE:

CITY OF XYZ

B

140 MPH

FBC 2017

NEC 2014

2015 NFPA 1

10.20KW

34

SM 300WATT

SE10000

120/240V

AERIAL MAP

NTS

02

PROJECT TITLE

PROJECT ADDRESS

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

LOGO

EXAMPLE ONLY

Page 2: PROJECT TITLE - Ecuip Sustainability · location: point of interconnection, nec 705.12(d)(3) warning: dual power sources. second source is pv system. general 1.1. labeling requirements

(34) SILFAB SLA-M 300 WP 60-CELL MODULES.

PLAN VIEW

NTS

ROOF ACCESS POINT

REFRENCE (NFPA 1) 11.12.2.2.1.3

ROOF ACCESS POINT

REFRENCE (NFPA 1) 11.12.2.2.1.3

slope

slope

"L" FEET SHALL BE INSTALLED PER MANUFACTURES

SPECIFICATIONS AND NOTES ON THIS DWG.

MAX CANTILEVER OF PANELS IS 2' FT IN ZONE ONE

"L" FOOT SPACING COULD BE NO MORE THAN 6' FT AND

MAX CANTILEVER OF PANELS IS 1.6' FT IN ZONE TWO

"L" FOOT SPACING COULD BE NO MORE THAN 5' FT AND

RIDGE STEBACK

REFRENCE (NFPA 1) 11.12.2.2.2.2

(34) MODULES

INVERTER AND SWITCH GEAR

IN GARAGE

PV AC DISCONNECT

CONTRACTOR WHILE FULLY ADHERING TO "NFPA 1".

FINAL PLACEMENT OF PANELS TO BE DETERMINED BY

ROOF LAYOUT IS HIP

ROOF TYPE IS SHINGLES

ROOF PITCH IS 27 DEGREES

1234 COMPANY ADDRESS

CITY STATE 12345

PH: 888-888-8888

WEB: WWW.COMPANY.COM

1234 PROJECT ADDRESS

CITY STATE 12345

ENGINEER OF RECORD

YOUR COMPANY

CONTRACTOR | EC12345 CBC12345

PROJECT NAME

PROJECT ID: XXXX-XXX-XXX

DATE

00.00.00

BY DESCRIPTION

INITIAL DESIGNM.D.

S.01

SCALE:

NTS

PAPER:

ARCHB

VER

01

FNAME LNAME

LIC NO.

UNAUTHORIZED USE OF THIS

DRAWING SET WITHOUT

WRITTEN PERMISSION FROM

CONTRACTOR IS IN VIOLATION

OF U.S. COPYRIGHT LAWS AND

WILL BE SUBJECT TO CIVIL

DAMAGES AND PROSECUTIONS.

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

LOGO

EXAMPLE ONLY

AutoCAD SHX Text
01
Page 3: PROJECT TITLE - Ecuip Sustainability · location: point of interconnection, nec 705.12(d)(3) warning: dual power sources. second source is pv system. general 1.1. labeling requirements

4. DUAL RACK LITE RAIL SHALL BE USED TO MOUNT THE

PV MODULES TO "L" BRACKETS AND ROOF SHEETING.

6. MODULES SHALL BE FASTENED USING MID-CLAMPS &

STANDARD END CLAMPS.

7. CONTRACTOR SHALL CHANGE/ADJUST THIS PLAN TO SATISFY

FBC, AHJ, JOBSITE CONSTRAINTS & OEM DOCUMENTATION.

1. DESIGN CONFORMS WITH 2017 FLORIDA

BUILDING CODE 6TH EDITION CRITERIA

FOR 140 MPH WIND FORCES PER

2. WIND EXPOSURE FACTOR 'B'

3. RISK CATEGORY II.

ASCE/SEI 7-10 MINIMUM DESIGN LOADS

FOR BUILDINGS & OTHER STRUCTURES.

8. "L" FOOT SPACING FOR LITE RAIL ATTACHMENT

SHALL BE NO MORE THAN 6' FT IN ZONE ONE AND 5' FT IN ZONE 2

5. LITE RAILS SHALL BE MOUNTED PERPENDICULAR AND

NOT CANTILEVER BEYOND OUTSIDE END OF ROOF ATTACHMENT

BY MORE THAN 2' FT IN ZONE ONE AND 1.6' FT IN ZONE TWO.

1. EACH MODULE SHALL HAVE A MIN. OF (4) CROSS RAIL CLAMPS EACH

2. EACH MODULE SHALL MOUNT TO DUAL RACK LITE RAILS

3. DUAL RACK LITE RAIL SHALL MOUNT TO ROOF PER ATTACHMENT DETAILS

4. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY CONDITION CHANGES

7. SYSTEM DEAD LOAD IS LESS THAN 3LBs PER SQ. FT.

5. ALL CONNECTION PLATES WITH L FOOT SHALL BE INSIDE ROOF EVE PERIMETER

6. MODULES SHALL NOT OVERHANG ANY RIDGE LINE.

LITE FLASH L KIT. 12" X 12", ALUMINUM

06

NTS

(34) SILFAB 300WP 60 CELL MODULES .

(8) DRAIN Øs

38MM

990MM

1650MM

01

NTS

L-FOOT , FRONT VIEW

07

NTS

L-FOOT , SIDE VIEW

08

NTS

L-FOOT, BOTTOM VIEW

09

NTS

MID CLAMP SIDE VIEW .

02

NTS

MID CLAMP TOP VIEW .

03

NTS

END CLAMP SIDE VIEW .

04

NTS

CHANNEL STRUT SIDE VIEW .

05

NTS

1234 COMPANY ADDRESS

CITY STATE 12345

PH: 888-888-8888

WEB: WWW.COMPANY.COM

1234 PROJECT ADDRESS

CITY STATE 12345

ENGINEER OF RECORD

YOUR COMPANY

CONTRACTOR | EC12345 CBC12345

PROJECT NAME

PROJECT ID: XXXX-XXX-XXX

DATE

00.00.00

BY DESCRIPTION

INITIAL DESIGNM.D.

S.02

SCALE:

NTS'

PAPER:

ARCHB

VER

01

FNAME LNAME

LIC NO.

UNAUTHORIZED USE OF THIS

DRAWING SET WITHOUT

WRITTEN PERMISSION FROM

CONTRACTOR IS IN VIOLATION

OF U.S. COPYRIGHT LAWS AND

WILL BE SUBJECT TO CIVIL

DAMAGES AND PROSECUTIONS.

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

LOGO

EXAMPLE ONLY

AutoCAD SHX Text
GENERAL NOTES:
AutoCAD SHX Text
MOUNTING NOTES:
AutoCAD SHX Text
+
AutoCAD SHX Text
_
Page 4: PROJECT TITLE - Ecuip Sustainability · location: point of interconnection, nec 705.12(d)(3) warning: dual power sources. second source is pv system. general 1.1. labeling requirements

CALCS BASED ON MAX CONDITIONS. CIRCUIT LENGTH BASED ON 1% VOLTAGE DROP. SEE NOTE 1.7 FOR RACEWAYS IN DIRECT SUNLIGHT. *CCC: CURRENT CARRYING CONDUCTORS

M

EXISTING 200A

120/240V

DISTRIBUTION

PANEL

EXISTING

GROUNDING

ELECTRODE

EGC BOND POINT

AT ROOF ARRAY RACKING

SYSTEM, NOTE #3.2.

C

JBOX

A: #10 PV WIRE,600V RATED

GENERAL NOTES

01

OPTIMIZER RATINGS

02

INVERTER RATINGS

03

SYSTEM

05

CONDUCTOR SCHEDULE

06

ELECTRICAL LINE DIAGRAM

07

GENERAL

1.1. CONTRACTOR IS RESPONSIBLE FOR COMPLYING WITH NEC 2014 AND FBC 2017 REQUIREMENTS AND EQUIPMENT INSTALLATION INSTRUCTIONS

NOT SPECIFIED IN THIS PLAN.

1.2. CONDUCTOR TYPES SHALL MEET THE REQUIREMENTS SET FOURTH IN NEC 310.10 BASED ON INSTALLATION LOCATION.

1.3. DIRECT-CURRENT PHOTOVOLTAIC SOURCE AND OUTPUT CIRCUITS INSIDE A BUILDING SHALL BE CONTAINED IN METAL RACEWAYS 690.31(E).

1.4. ALL EQUIPMENT SHALL BE LISTED PER NEC 690.4(D).

1.5. CONDUCTOR SIZING IS BASED ON RACEWAYS NOT EXPOSED TO DIRECT SUNLIGHT UNLESS STATED OTHERWISE. 10% OF CIRCUIT LENGTH CAN

BE EXPOSED DIRECT SUNLIGHT UP TO 10FT, NEC 310.15(A)(2).

1.6. PV SOURCE AND OUTPUT CIRCUIT CONDUCTORS ARE SIZED BE EXPOSED TO DIRECT SUNLIGHT GREATER THAN 10% OF THEIR LENGTH WHEN

INSTALLED IN RACEWAYS ½” OR GREATER ABOVE ROOF. ADJUSTMENTS ARE BASED ON MAX STRING CURRENT OF 15A, 35C AMBIENT

TEMPERATURE, NEC 310.15(B)(2)(A) AND 310.15(B)(3)(C).

SYSTEM SPECIFIC

2.1. THE OUTPUT VOLTAGE OF THE OPTIMIZERS ARE REGULATED BY THE INVERTER AND ARE NOT IMPACTED BY THE NUMBER OF MODULES IN THE

STRING. THE CONTINUOUS CURRENT OF A SINGLE STRING IS EQUAL TO THE MAXIMUM OUTPUT CURRENT OF THE OPTIMIZER OF 15A.

2.2. THE INVERTER IS EQUIPPED WITH A RAPID SHUTDOWN FEATURE WHICH CONFORMS TO NEC 690.12 (2014).

2.3. THE INVERTER IS NON-ISOLATED AND UNGROUNDED. NEITHER THE NEGATIVE NOR POSITIVE CONDUCTOR IS GROUNDED AND HAS A COMMON

AC AND DC EQUIPMENT GROUNDING TERMINAL THEREFORE NO DC GEC IS REQUIRED.

2.4. UTILITY CONNECTION SHALL BE MADE AS SHOWN BY LINE-SIDE-TAP PER ARTICLE 705.12(A) USING INSULATED, PIERCING CONNECTORS UL

LISTED FOR THIS PURPOSE AND LOCATED WITHIN CODE COMPLIANT ENCLOSURE.

2.5. INTEGRATED DC DISCONNECT IS PROVIDED WITH INVERTER.

GROUNDING

3.1. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED PER THE REQUIREMENTS OF NEC ARTICLES 250 & 690.

3.2. PV MODULES SHALL BE GROUNDED TO MOUNTING RAILS USING MODULE LUGS OR RACKING INTEGRATED GROUNDING CLAMPS AS ALLOWED

BY LOCAL JURISDICTION. EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED IN ACCORDANCE WITH NEC 250.120(C).

3.3. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC ARTICLE 690.45, AND BE A MINIMUM OF #10 AWG WHEN NOT

EXPOSED TO DAMAGE, AND #6 AWG SHALL BE USED WHEN EXPOSED TO DAMAGE.

INVERTER 1

B

08 - 19 MODS

=

=

=

=

8 - 19

SE P320

01

=

=

08 - 19 MODS

MODULE RATINGS

04

MAKE SOLAREDGE

MODEL SE10000H-US

MAX INPUT POWER 15500 W

MAX INPUT VOLTAGE 480 V

NOM INPUT VOLTAGE 400 V

MAX INPUT CURRENT 27 A

NOM AC VOLTAGE 240 V

MAX AC CURRENT 42 A

NOM AC POWER 10000 W

MAKE SOLAREDGE

MODEL P320

INPUT POWER 320 W

MAX INPUT VOLTAGE 48 V

MAX INPUT CURRENT 13.75 A

MAX OUTPUT CURRENT 15 A

MAX STRING POWER 6000 W

MAKE SILFAB

MODEL SLA-300

RATED POWER 300 W

VMPP 32.8 V

IMPP 9.16 A

VOC 39.85 V

ISC 9.71 A

# MODS 34

# INVERTERS 1

# STRINGS/INV 2

MIN STRING SIZE 8 MOD

MAX STRING SIZE 19 MOD

STC DC RATING 10.2 KW

AC OUTPUT RATING 10 KW

DC/AC

102 %

MPP CURRENT

25.50 A

ID RUN

VOLTAGE (V) CURRENT (A) VD (%)

LENGTH CONDUCTOR SIZE Ω/KFT CONDUIT SIZE #CCC EGC OCPD

TERM (C)

TEMP ADJ FILL ADJ BASE AMP DERATED AMP

A STR - JBOX 400 15 1 108 PV WIRE #10 1.24 FREE AIR NA 4 #10 NA 75 0.96 1 35 35

B JBOX - INV 400 15 1 108

THHN/THWN-2 | PV WIRE

#10 1.24 PVC/EMT/FMC 3/4" 4 #10 NA 75 0.96 0.8 35 30.72

C INV - DISC 240 42 1 58 THHN/THWN-2 #6 0.491 PVC/EMT/FMC 3/4" 3 #10 60 75 0.96 1 65 65

D DISC - PCC 240 42 1 58 THHN/THWN-2 #6 0.491 PVC/EMT/FMC 3/4" 3 #10 60 75 0.96 1 65 65

RE: NOTE 2.4

D

1 PH LOCKABLE FUSED AC

DISCONNECT, MIN 60A,

120/240V, W/ 60A FUSES

ENGINEER OF RECORD

PROJECT ID: XXXX-XXX-XXX

DATE BY DESCRIPTION

INITIAL DESIGNM.D.

E.01

SCALE:

NTS

PAPER:

ARCHB

VER

01

FNAME LNAME

LIC NO.

UNAUTHORIZED USE OF THIS

DRAWING SET WITHOUT

WRITTEN PERMISSION FROM

CONTRACTOR IS IN VIOLATION

OF U.S. COPYRIGHT LAWS AND

WILL BE SUBJECT TO CIVIL

DAMAGES AND PROSECUTIONS.

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

PROJECT NAME

1234 PROJECT ADDRESSCITY STATE 12345

YOUR COMPANY1234 COMPANY ADDRESSCITY STATE 12345888-888-8888WWW.COMPANY.COM

CONTRACTOR | EC12345 CBC1234500.00.00

LOGO

EXAMPLE ONLY

AutoCAD SHX Text
=
AutoCAD SHX Text
-
AutoCAD SHX Text
+
AutoCAD SHX Text
-
AutoCAD SHX Text
+
AutoCAD SHX Text
-
AutoCAD SHX Text
+
Page 5: PROJECT TITLE - Ecuip Sustainability · location: point of interconnection, nec 705.12(d)(3) warning: dual power sources. second source is pv system. general 1.1. labeling requirements

ELECTRIC SHOCK HAZARD IF A GROUND FAULT IS INDICATED,

NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND

ENERGIZED

LOCATION: EACH INVERTER & BATTERY, NEC 690.5(C)

LABELS

01

! WARNING !

ELECTRIC SHOCK HAZARD. DO NOT TOUCH TERMINALS.

TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE

ENERGIZED IN THE OPEN POSITION

LOCATION: DC DISCONNECT, NEC 690.17

! WARNING !

ELECTRICAL SHOCK HAZARD.

THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE

UNGROUNDED AND MAY BE ENERGIZED

LOCATION: JBOX, COMBINER BOX, DC DISCONNECT, NEC 690.35(F)

! WARNING !

LOCATION: EACH DISCONNECT, NEC 690.13(B),NFPA 11.12

PHOTOVOLTAIC

DISCONNECT

LOC: MARKINGS SHALL COMPLY WITH NEC 690.31(E)(3), 690.31(E)(4)

AND NFPA 11.12 AND SHALL BE PLACED ON ALL INTERIOR AND

EXTERIOR DC CONDUIT, RACEWAYS, ENCLOSURES, AND CABLE

ASSEMBLIES AT LEAST EVERY 10 FEET; AT TURNS AND

ABOVE/BELOW PENETRATIONS AND ALL JUNCTION BOXES.

WARNING: PHOTOVOLTAIC

POWER SOURCE

LOCATION: RAPID SHUTDOWN SWITCH, NEC 690.56(C)

SOLAR PV SYSTEM EQUIPPED

WITH RAPID SHUTDOWN

LOCATION: MAIN SERVICE DISCONNECT, NFPA 11.12

WARNING: PHOTOVOLTAIC

POWER SOURCE

LOCATION: POINT OF INTERCONNECTION, NEC 705.12(D)(3)

WARNING: DUAL POWER

SOURCES. SECOND SOURCE

IS PV SYSTEM

GENERAL

1.1. LABELING REQUIREMENTS BASED ON NEC 2014 & NFPA 2015.

1.2. MATERIALS USED ARE SUBJECT TO THE REQUIREMENTS OF THE AUTHORITY

HAVING JURISDICTION.

1.3. LABEL MATERIALS SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE

ENVIRONMENT.

1.4. LABELS SHALL BE A MINIMUM LETTER HEIGHT OF 3/8" AND PERMANENTLY AFFIXED.

PHOTOVOLTAIC AC DISCONNECT

AC OUTPUT VOLTAGE 240 V

AC OUTPUT CURRENT 42 A

LOCATION: AC DISCONNECT, NEC 690.54

MPP CURRENT 25.50 A

MPP VOLTAGE 400 V

MAX VOLTAGE 480 V

MAX CURRENT 30 A

LOCATION: DC DISCONNECT, NEC 690.53

SOLAR SYSTEM POWERED BY

YOUR COMPANY

888-888-8888

WWW.COMPANY.COM

LOCATION: ADJACENT TO MAIN SERVICE DISC, NFPA 11.12

ENGINEER OF RECORD

PROJECT ID: XXXX-XXX-XXX

DATE BY DESCRIPTION

INITIAL DESIGNM.D.

L.01

SCALE:

NTS

PAPER:

ARCHB

VER

01

UNAUTHORIZED USE OF THIS

DRAWING SET WITHOUT

WRITTEN PERMISSION FROM

CONTRACTOR IS IN VIOLATION

OF U.S. COPYRIGHT LAWS AND

WILL BE SUBJECT TO CIVIL

DAMAGES AND PROSECUTIONS.

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

FNAME LNAME

LIC NO.

PROJECT NAME YOUR COMPANY1234 COMPANY ADDRESSCITY STATE 12345888-888-8888WWW.COMPANY.COM

1234 PROJECT ADDRESSCITY STATE 12345

00.00.00

CONTRACTOR | EC12345 CBC12345

LOGO

EXAMPLE ONLY

Page 6: PROJECT TITLE - Ecuip Sustainability · location: point of interconnection, nec 705.12(d)(3) warning: dual power sources. second source is pv system. general 1.1. labeling requirements

1234 COMPANY ADDRESS

CITY STATE 12345

PH: 888-888-8888

WEB: WWW.COMPANY.COM

1234 PROJECT ADDRESS

CITY STATE 12345

ENGINEER OF RECORD

YOUR COMPANY

CONTRACTOR | EC12345 CBC12345

PROJECT NAME

PROJECT ID: XXXX-XXX-XXX

DATE

00.00.00

BY DESCRIPTION

INITIAL DESIGNM.D.

D.01

SCALE:

NTS

PAPER:

ARCHB

VER

01

FNAME LNAME

LIC NO.

UNAUTHORIZED USE OF THIS

DRAWING SET WITHOUT

WRITTEN PERMISSION FROM

CONTRACTOR IS IN VIOLATION

OF U.S. COPYRIGHT LAWS AND

WILL BE SUBJECT TO CIVIL

DAMAGES AND PROSECUTIONS.

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

LOGO

EXAMPLE ONLY

Page 7: PROJECT TITLE - Ecuip Sustainability · location: point of interconnection, nec 705.12(d)(3) warning: dual power sources. second source is pv system. general 1.1. labeling requirements

INVERTER

01

MODULE

02

OPTIMIZER

03

ENGINEER OF RECORD

PROJECT ID: XXXX-XXX-XXX

DATE BY DESCRIPTION

INITIAL DESIGNM.D.

D.02

SCALE:

NTS

PAPER:

ARCHB

VER

01

UNAUTHORIZED USE OF THIS

DRAWING SET WITHOUT

WRITTEN PERMISSION FROM

CONTRACTOR IS IN VIOLATION

OF U.S. COPYRIGHT LAWS AND

WILL BE SUBJECT TO CIVIL

DAMAGES AND PROSECUTIONS.

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

FNAME LNAME

LIC NO.

PROJECT NAME CONTRACTOR | EC12345 CBC12345YOUR COMPANY1234 COMPANY ADDRESSCITY STATE 12345888-888-8888WWW.COMPANY.COM

1234 PROJECT ADDRESSCITY STATE 12345

00.00.00

LOGO

EXAMPLE ONLY