PROJECT TITLE - Ecuip Sustainability · location: point of interconnection, nec 705.12(d)(3)...
Transcript of PROJECT TITLE - Ecuip Sustainability · location: point of interconnection, nec 705.12(d)(3)...
1234 COMPANY ADDRESS
CITY STATE 12345
PH: 888-888-8888
WEB: WWW.COMPANY.COM
1234 PROJECT ADDRESS
CITY STATE 12345
ENGINEER OF RECORD
YOUR COMPANY
CONTRACTOR | EC12345 CBC12345
PROJECT NAME
PROJECT ID: XXXX-XXX-XXX
DATE
00.00.00
BY DESCRIPTION
INITIAL DESIGNM.D.
T.01
SCALE:
NTS'
PAPER:
ARCHB
VER
01
VICINITY VIEW
NTS
01
FNAME LNAME
LIC NO.
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
SHEET INDEX
COVER PAGE
ROOF PLAN & PV LAYOUT
ATTACHMENT DETAILS
ELECTRICAL SLD
LABELS
DATASHEET (STRUCTURAL)
DATASHEET (ELECTRICAL)
T.01
S.01
S.02
E.01
L.01
D.01
D.02
PROJECT INFORMATION
AUTHORITY HAVING JURISDICTION
BUILDING:
DESIGN SPECS
WIND EXPOSURE:
WIND SPEED:
GOVERNING CODES
BUILDING:
ELECTRICAL:
FIRE:
SYSTEM
SIZE (KWDC):
# PANELS:
PANEL:
INVERTER:
VOLTAGE:
CITY OF XYZ
B
140 MPH
FBC 2017
NEC 2014
2015 NFPA 1
10.20KW
34
SM 300WATT
SE10000
120/240V
AERIAL MAP
NTS
02
PROJECT TITLE
PROJECT ADDRESS
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
LOGO
EXAMPLE ONLY
(34) SILFAB SLA-M 300 WP 60-CELL MODULES.
PLAN VIEW
NTS
ROOF ACCESS POINT
REFRENCE (NFPA 1) 11.12.2.2.1.3
ROOF ACCESS POINT
REFRENCE (NFPA 1) 11.12.2.2.1.3
slope
slope
"L" FEET SHALL BE INSTALLED PER MANUFACTURES
SPECIFICATIONS AND NOTES ON THIS DWG.
MAX CANTILEVER OF PANELS IS 2' FT IN ZONE ONE
"L" FOOT SPACING COULD BE NO MORE THAN 6' FT AND
MAX CANTILEVER OF PANELS IS 1.6' FT IN ZONE TWO
"L" FOOT SPACING COULD BE NO MORE THAN 5' FT AND
RIDGE STEBACK
REFRENCE (NFPA 1) 11.12.2.2.2.2
(34) MODULES
INVERTER AND SWITCH GEAR
IN GARAGE
PV AC DISCONNECT
CONTRACTOR WHILE FULLY ADHERING TO "NFPA 1".
FINAL PLACEMENT OF PANELS TO BE DETERMINED BY
ROOF LAYOUT IS HIP
ROOF TYPE IS SHINGLES
ROOF PITCH IS 27 DEGREES
1234 COMPANY ADDRESS
CITY STATE 12345
PH: 888-888-8888
WEB: WWW.COMPANY.COM
1234 PROJECT ADDRESS
CITY STATE 12345
ENGINEER OF RECORD
YOUR COMPANY
CONTRACTOR | EC12345 CBC12345
PROJECT NAME
PROJECT ID: XXXX-XXX-XXX
DATE
00.00.00
BY DESCRIPTION
INITIAL DESIGNM.D.
S.01
SCALE:
NTS
PAPER:
ARCHB
VER
01
FNAME LNAME
LIC NO.
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
LOGO
EXAMPLE ONLY
4. DUAL RACK LITE RAIL SHALL BE USED TO MOUNT THE
PV MODULES TO "L" BRACKETS AND ROOF SHEETING.
6. MODULES SHALL BE FASTENED USING MID-CLAMPS &
STANDARD END CLAMPS.
7. CONTRACTOR SHALL CHANGE/ADJUST THIS PLAN TO SATISFY
FBC, AHJ, JOBSITE CONSTRAINTS & OEM DOCUMENTATION.
1. DESIGN CONFORMS WITH 2017 FLORIDA
BUILDING CODE 6TH EDITION CRITERIA
FOR 140 MPH WIND FORCES PER
2. WIND EXPOSURE FACTOR 'B'
3. RISK CATEGORY II.
ASCE/SEI 7-10 MINIMUM DESIGN LOADS
FOR BUILDINGS & OTHER STRUCTURES.
8. "L" FOOT SPACING FOR LITE RAIL ATTACHMENT
SHALL BE NO MORE THAN 6' FT IN ZONE ONE AND 5' FT IN ZONE 2
5. LITE RAILS SHALL BE MOUNTED PERPENDICULAR AND
NOT CANTILEVER BEYOND OUTSIDE END OF ROOF ATTACHMENT
BY MORE THAN 2' FT IN ZONE ONE AND 1.6' FT IN ZONE TWO.
1. EACH MODULE SHALL HAVE A MIN. OF (4) CROSS RAIL CLAMPS EACH
2. EACH MODULE SHALL MOUNT TO DUAL RACK LITE RAILS
3. DUAL RACK LITE RAIL SHALL MOUNT TO ROOF PER ATTACHMENT DETAILS
4. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY CONDITION CHANGES
7. SYSTEM DEAD LOAD IS LESS THAN 3LBs PER SQ. FT.
5. ALL CONNECTION PLATES WITH L FOOT SHALL BE INSIDE ROOF EVE PERIMETER
6. MODULES SHALL NOT OVERHANG ANY RIDGE LINE.
LITE FLASH L KIT. 12" X 12", ALUMINUM
06
NTS
(34) SILFAB 300WP 60 CELL MODULES .
(8) DRAIN Øs
38MM
990MM
1650MM
01
NTS
L-FOOT , FRONT VIEW
07
NTS
L-FOOT , SIDE VIEW
08
NTS
L-FOOT, BOTTOM VIEW
09
NTS
MID CLAMP SIDE VIEW .
02
NTS
MID CLAMP TOP VIEW .
03
NTS
END CLAMP SIDE VIEW .
04
NTS
CHANNEL STRUT SIDE VIEW .
05
NTS
1234 COMPANY ADDRESS
CITY STATE 12345
PH: 888-888-8888
WEB: WWW.COMPANY.COM
1234 PROJECT ADDRESS
CITY STATE 12345
ENGINEER OF RECORD
YOUR COMPANY
CONTRACTOR | EC12345 CBC12345
PROJECT NAME
PROJECT ID: XXXX-XXX-XXX
DATE
00.00.00
BY DESCRIPTION
INITIAL DESIGNM.D.
S.02
SCALE:
NTS'
PAPER:
ARCHB
VER
01
FNAME LNAME
LIC NO.
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
LOGO
EXAMPLE ONLY
CALCS BASED ON MAX CONDITIONS. CIRCUIT LENGTH BASED ON 1% VOLTAGE DROP. SEE NOTE 1.7 FOR RACEWAYS IN DIRECT SUNLIGHT. *CCC: CURRENT CARRYING CONDUCTORS
M
EXISTING 200A
120/240V
DISTRIBUTION
PANEL
EXISTING
GROUNDING
ELECTRODE
EGC BOND POINT
AT ROOF ARRAY RACKING
SYSTEM, NOTE #3.2.
C
JBOX
A: #10 PV WIRE,600V RATED
GENERAL NOTES
01
OPTIMIZER RATINGS
02
INVERTER RATINGS
03
SYSTEM
05
CONDUCTOR SCHEDULE
06
ELECTRICAL LINE DIAGRAM
07
GENERAL
1.1. CONTRACTOR IS RESPONSIBLE FOR COMPLYING WITH NEC 2014 AND FBC 2017 REQUIREMENTS AND EQUIPMENT INSTALLATION INSTRUCTIONS
NOT SPECIFIED IN THIS PLAN.
1.2. CONDUCTOR TYPES SHALL MEET THE REQUIREMENTS SET FOURTH IN NEC 310.10 BASED ON INSTALLATION LOCATION.
1.3. DIRECT-CURRENT PHOTOVOLTAIC SOURCE AND OUTPUT CIRCUITS INSIDE A BUILDING SHALL BE CONTAINED IN METAL RACEWAYS 690.31(E).
1.4. ALL EQUIPMENT SHALL BE LISTED PER NEC 690.4(D).
1.5. CONDUCTOR SIZING IS BASED ON RACEWAYS NOT EXPOSED TO DIRECT SUNLIGHT UNLESS STATED OTHERWISE. 10% OF CIRCUIT LENGTH CAN
BE EXPOSED DIRECT SUNLIGHT UP TO 10FT, NEC 310.15(A)(2).
1.6. PV SOURCE AND OUTPUT CIRCUIT CONDUCTORS ARE SIZED BE EXPOSED TO DIRECT SUNLIGHT GREATER THAN 10% OF THEIR LENGTH WHEN
INSTALLED IN RACEWAYS ½” OR GREATER ABOVE ROOF. ADJUSTMENTS ARE BASED ON MAX STRING CURRENT OF 15A, 35C AMBIENT
TEMPERATURE, NEC 310.15(B)(2)(A) AND 310.15(B)(3)(C).
SYSTEM SPECIFIC
2.1. THE OUTPUT VOLTAGE OF THE OPTIMIZERS ARE REGULATED BY THE INVERTER AND ARE NOT IMPACTED BY THE NUMBER OF MODULES IN THE
STRING. THE CONTINUOUS CURRENT OF A SINGLE STRING IS EQUAL TO THE MAXIMUM OUTPUT CURRENT OF THE OPTIMIZER OF 15A.
2.2. THE INVERTER IS EQUIPPED WITH A RAPID SHUTDOWN FEATURE WHICH CONFORMS TO NEC 690.12 (2014).
2.3. THE INVERTER IS NON-ISOLATED AND UNGROUNDED. NEITHER THE NEGATIVE NOR POSITIVE CONDUCTOR IS GROUNDED AND HAS A COMMON
AC AND DC EQUIPMENT GROUNDING TERMINAL THEREFORE NO DC GEC IS REQUIRED.
2.4. UTILITY CONNECTION SHALL BE MADE AS SHOWN BY LINE-SIDE-TAP PER ARTICLE 705.12(A) USING INSULATED, PIERCING CONNECTORS UL
LISTED FOR THIS PURPOSE AND LOCATED WITHIN CODE COMPLIANT ENCLOSURE.
2.5. INTEGRATED DC DISCONNECT IS PROVIDED WITH INVERTER.
GROUNDING
3.1. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED PER THE REQUIREMENTS OF NEC ARTICLES 250 & 690.
3.2. PV MODULES SHALL BE GROUNDED TO MOUNTING RAILS USING MODULE LUGS OR RACKING INTEGRATED GROUNDING CLAMPS AS ALLOWED
BY LOCAL JURISDICTION. EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED IN ACCORDANCE WITH NEC 250.120(C).
3.3. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC ARTICLE 690.45, AND BE A MINIMUM OF #10 AWG WHEN NOT
EXPOSED TO DAMAGE, AND #6 AWG SHALL BE USED WHEN EXPOSED TO DAMAGE.
INVERTER 1
B
08 - 19 MODS
=
=
=
=
8 - 19
SE P320
01
=
=
08 - 19 MODS
MODULE RATINGS
04
MAKE SOLAREDGE
MODEL SE10000H-US
MAX INPUT POWER 15500 W
MAX INPUT VOLTAGE 480 V
NOM INPUT VOLTAGE 400 V
MAX INPUT CURRENT 27 A
NOM AC VOLTAGE 240 V
MAX AC CURRENT 42 A
NOM AC POWER 10000 W
MAKE SOLAREDGE
MODEL P320
INPUT POWER 320 W
MAX INPUT VOLTAGE 48 V
MAX INPUT CURRENT 13.75 A
MAX OUTPUT CURRENT 15 A
MAX STRING POWER 6000 W
MAKE SILFAB
MODEL SLA-300
RATED POWER 300 W
VMPP 32.8 V
IMPP 9.16 A
VOC 39.85 V
ISC 9.71 A
# MODS 34
# INVERTERS 1
# STRINGS/INV 2
MIN STRING SIZE 8 MOD
MAX STRING SIZE 19 MOD
STC DC RATING 10.2 KW
AC OUTPUT RATING 10 KW
DC/AC
102 %
MPP CURRENT
25.50 A
ID RUN
VOLTAGE (V) CURRENT (A) VD (%)
LENGTH CONDUCTOR SIZE Ω/KFT CONDUIT SIZE #CCC EGC OCPD
TERM (C)
TEMP ADJ FILL ADJ BASE AMP DERATED AMP
A STR - JBOX 400 15 1 108 PV WIRE #10 1.24 FREE AIR NA 4 #10 NA 75 0.96 1 35 35
B JBOX - INV 400 15 1 108
THHN/THWN-2 | PV WIRE
#10 1.24 PVC/EMT/FMC 3/4" 4 #10 NA 75 0.96 0.8 35 30.72
C INV - DISC 240 42 1 58 THHN/THWN-2 #6 0.491 PVC/EMT/FMC 3/4" 3 #10 60 75 0.96 1 65 65
D DISC - PCC 240 42 1 58 THHN/THWN-2 #6 0.491 PVC/EMT/FMC 3/4" 3 #10 60 75 0.96 1 65 65
RE: NOTE 2.4
D
1 PH LOCKABLE FUSED AC
DISCONNECT, MIN 60A,
120/240V, W/ 60A FUSES
ENGINEER OF RECORD
PROJECT ID: XXXX-XXX-XXX
DATE BY DESCRIPTION
INITIAL DESIGNM.D.
E.01
SCALE:
NTS
PAPER:
ARCHB
VER
01
FNAME LNAME
LIC NO.
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
PROJECT NAME
1234 PROJECT ADDRESSCITY STATE 12345
YOUR COMPANY1234 COMPANY ADDRESSCITY STATE 12345888-888-8888WWW.COMPANY.COM
CONTRACTOR | EC12345 CBC1234500.00.00
LOGO
EXAMPLE ONLY
ELECTRIC SHOCK HAZARD IF A GROUND FAULT IS INDICATED,
NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND
ENERGIZED
LOCATION: EACH INVERTER & BATTERY, NEC 690.5(C)
LABELS
01
! WARNING !
ELECTRIC SHOCK HAZARD. DO NOT TOUCH TERMINALS.
TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE
ENERGIZED IN THE OPEN POSITION
LOCATION: DC DISCONNECT, NEC 690.17
! WARNING !
ELECTRICAL SHOCK HAZARD.
THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE
UNGROUNDED AND MAY BE ENERGIZED
LOCATION: JBOX, COMBINER BOX, DC DISCONNECT, NEC 690.35(F)
! WARNING !
LOCATION: EACH DISCONNECT, NEC 690.13(B),NFPA 11.12
PHOTOVOLTAIC
DISCONNECT
LOC: MARKINGS SHALL COMPLY WITH NEC 690.31(E)(3), 690.31(E)(4)
AND NFPA 11.12 AND SHALL BE PLACED ON ALL INTERIOR AND
EXTERIOR DC CONDUIT, RACEWAYS, ENCLOSURES, AND CABLE
ASSEMBLIES AT LEAST EVERY 10 FEET; AT TURNS AND
ABOVE/BELOW PENETRATIONS AND ALL JUNCTION BOXES.
WARNING: PHOTOVOLTAIC
POWER SOURCE
LOCATION: RAPID SHUTDOWN SWITCH, NEC 690.56(C)
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
LOCATION: MAIN SERVICE DISCONNECT, NFPA 11.12
WARNING: PHOTOVOLTAIC
POWER SOURCE
LOCATION: POINT OF INTERCONNECTION, NEC 705.12(D)(3)
WARNING: DUAL POWER
SOURCES. SECOND SOURCE
IS PV SYSTEM
GENERAL
1.1. LABELING REQUIREMENTS BASED ON NEC 2014 & NFPA 2015.
1.2. MATERIALS USED ARE SUBJECT TO THE REQUIREMENTS OF THE AUTHORITY
HAVING JURISDICTION.
1.3. LABEL MATERIALS SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE
ENVIRONMENT.
1.4. LABELS SHALL BE A MINIMUM LETTER HEIGHT OF 3/8" AND PERMANENTLY AFFIXED.
PHOTOVOLTAIC AC DISCONNECT
AC OUTPUT VOLTAGE 240 V
AC OUTPUT CURRENT 42 A
LOCATION: AC DISCONNECT, NEC 690.54
MPP CURRENT 25.50 A
MPP VOLTAGE 400 V
MAX VOLTAGE 480 V
MAX CURRENT 30 A
LOCATION: DC DISCONNECT, NEC 690.53
SOLAR SYSTEM POWERED BY
YOUR COMPANY
888-888-8888
WWW.COMPANY.COM
LOCATION: ADJACENT TO MAIN SERVICE DISC, NFPA 11.12
ENGINEER OF RECORD
PROJECT ID: XXXX-XXX-XXX
DATE BY DESCRIPTION
INITIAL DESIGNM.D.
L.01
SCALE:
NTS
PAPER:
ARCHB
VER
01
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
FNAME LNAME
LIC NO.
PROJECT NAME YOUR COMPANY1234 COMPANY ADDRESSCITY STATE 12345888-888-8888WWW.COMPANY.COM
1234 PROJECT ADDRESSCITY STATE 12345
00.00.00
CONTRACTOR | EC12345 CBC12345
LOGO
EXAMPLE ONLY
1234 COMPANY ADDRESS
CITY STATE 12345
PH: 888-888-8888
WEB: WWW.COMPANY.COM
1234 PROJECT ADDRESS
CITY STATE 12345
ENGINEER OF RECORD
YOUR COMPANY
CONTRACTOR | EC12345 CBC12345
PROJECT NAME
PROJECT ID: XXXX-XXX-XXX
DATE
00.00.00
BY DESCRIPTION
INITIAL DESIGNM.D.
D.01
SCALE:
NTS
PAPER:
ARCHB
VER
01
FNAME LNAME
LIC NO.
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
LOGO
EXAMPLE ONLY
INVERTER
01
MODULE
02
OPTIMIZER
03
ENGINEER OF RECORD
PROJECT ID: XXXX-XXX-XXX
DATE BY DESCRIPTION
INITIAL DESIGNM.D.
D.02
SCALE:
NTS
PAPER:
ARCHB
VER
01
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT
WRITTEN PERMISSION FROM
CONTRACTOR IS IN VIOLATION
OF U.S. COPYRIGHT LAWS AND
WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
FNAME LNAME
LIC NO.
PROJECT NAME CONTRACTOR | EC12345 CBC12345YOUR COMPANY1234 COMPANY ADDRESSCITY STATE 12345888-888-8888WWW.COMPANY.COM
1234 PROJECT ADDRESSCITY STATE 12345
00.00.00
LOGO
EXAMPLE ONLY