PROJECT INFORMATION · 2019. 10. 24. · 8. 3111.5.3.1 - total system weight shall not exceed 4.5...
Transcript of PROJECT INFORMATION · 2019. 10. 24. · 8. 3111.5.3.1 - total system weight shall not exceed 4.5...
88.50'
50.2
5'
77.00'
6.25'
58.7
5'
6.25'
6.50
'
7.5
0'
PV-1
SITE PLAN
(E) RESIDENCE
(E) PROPERTY LINE
(N) ARRAY #1
(E) DRIVEWAY
S
W
N
E
JUAN PEREZ RESIDENCE123 MAIN ST, ANY CITY, ST, ZIP971-240-7102
SINGLE FAMILYRESIDENTIAL
2014 OSSC & 2017 OESC
HYUNDAI HIS-S355RI SOLAR MODULES(17) X355W = 6.035 KWdc(1) SOLAREDGE SE5000H-US (240)
HYUNDAI HIS-S355RI(L) 77.17" X (W) 39.37" X (H) 1.57"WEIGHT = 50.5COMBINED WEIGHT OFMODULES AND RACKING: 3.64 PSF ≤ 4.5 PSF
DRAWING LIST
PV-1 SITE PLANPV-2 FRAMING PLANPV-3 ROOF PLANPV-4 SINGLE LINE DIAGRAMPV-5 LABELSAPPENDIX: DATA SHEETS
OWNER
BUILDING
DATA
APPLICABLE
CODES
SYSTEM
MODULE
SPECS
CONTRACTOR
ROOF SPECS
PROJECT INFORMATION
PROJECT NOTES
SITE DETAILS:
NO
RT
HW
ES
T P
RIM
INO
AV
E.
NOTES
1. CHECK WITH CITY/COUNTY OR LAND SURVEYORFOR ACCURATE PROPERTY LOCATE.
2. TSFR SUNEYE SHOT ON ROOF CORRESPONDS TOJUAN PEREZ RESIDENCE SHADE REPORT.
SITE PLANSCALE: 1/16" = 1'-0"
AVILA SOLARWWW.AVILASOLAR.COMPORTLAND, OR 97007CONTACT: DOUGLAS AVILAPHONE: 971-240-7102
ASPHALT SHINGLE 2X4 RAFTERS @ 24" O.C.,DOUGLAS FIR #2TILT: 42°AZIMUTH: 180° (S)AREA OF ROOF(PLAN VIEW)= 2862 SFAREA OF NEW ARRAY = 267 SF = 9% OF ROOFAREA (ARRAY < 25% OF ROOF AREA)
CLIMATE DATA SOURCE: PORTLANDINTERNATIONAL AP, 45.59N, 122.60WASHRAE EXTREME LOW: -6.4°CASHRAE 2% HIGH: 35°CASHRAE EXTREME HIGH: 41.9°CWIND SPEED: 110 MPH (ASCE7-10)RISK CATEGORY: IIWIND EXPOSURE CATEGORY: BGROUND SNOW LOAD: 20 PSF
CONTRACTOR
Contractor# Drawn by: Date:
Page:
Rev:
Ph:Ph:
System AC Size @ STC: System DC Size @ STC:
YOUR LOGO
The design reprented herein are for sample purposes only and requires review and adjustments for site specific application. These drawings are property of AVILA SOLAR and shall not be copied or used without written consent.
JUAN PEREZ RESIDENCEResidential Grid Interactive Solar Installation123 MAIN ST, ANY CITY, ST, ZIP
971-240-7102
DA PERMIT SET 6/14/2018
5 kW 6.035 kW
(17) HYUNDAI HIS-S355RI SOLAR MODULES & (17) SE P370 POWER OPTIMIZERS
(1) SOLAREDGE SE5000H-US (240)
WWW.AVILASOLAR.COMPORTLAND, OR 97007
971-240-7102
AVILA SOLAR
NUMBER OF ARRAYS PROPOSED: 2
ARRAY # 2 DETAILS # OF MODULES: 4 TILT: 42° AZIMUTH: 180°
ARRAY # 1 DETAILS # OF MODULES: 13 TILT: 42° AZIMUTH: 180°
(N) ARRAY #2
93
98
XX
1. PV SYSTEMS AND SUPPORTING STRUCTURE SHALL COMPLYWITH REQUIREMENTS OF 2017 OESC & 2014 OSSC.
2. 3111.3.2 - PV RACKING AND ATTACHMENTS SHALL BE UL 1703CERTIFIED.
3. 3111.3.4 - PV SYSTEM SHALL HAVE A FIRE CLASSIFICATION THATIS EQUAL TO OR GREATER THAN THE ROOF ASSEMBLYREQUIRED BY OSSC SECTION 1505.1.
4. 3111.4.3 - 3111.4.7- PV LAYOUT SHALL NOT RESTRICT EGRESS,LIGHT VENTILATION, OR ROOF DRAINAGE REQUIREMENTS.
5. 3111.4.8.1 - GENERAL PATHWAY REQUIREMENTS:
36" WIDE PATHWAY SHALL NOT BE REQUIRED ON STRUCTURESWITH A PV ARRAY AREA OF 1,000 SF OR LESS INSTALLED ON AROOF WITH A SLOPE THAT EXCEEDS 2:12 AND WITH ANINTERSECTING ADJACENT ROOF AND WHERE NO SECTION ISLARGER THAN 150 FEET MEASURED IN LENGTH OR WIDTH.
WHERE PV ARRAY DOES NOT EXCEED 25% AS MEASURED INPLAN VIEW OF TOTAL ROOF AREA OF A STRUCTURE, A MINIMUMOF 12" UNOBSTRUCTED PATHWAY SHALL BE MAINTAINED ALONGEACH SIDE OF ANY HORIZONTAL RIDGE.
WHERE THE SOLAR ARRAY EXCEEDS 25% AS MEASURED IN PLANVIEW OF TOTAL ROOF AREA OF THE STRUCTURE, A MINIMUM OFONE 36" UNOBSTRUCTED PATHWAY SHALL BE PROVIDED INADDITION TO A MINIMUM 12" UNOBSTRUCTED ALONG EA. SIDEOF ANY HORIZONTAL RIDGE.
6. ROOF STRUCTURE IS CONVENTIONAL LIGHT FRAMED WOODCONSTRUCTION WITH 2X4 MANUFACTURED TRUSSES @ 24" O.C.REFER TO ALLOWABLE SPAN REQUIREMENTS IN TABLE 305.4.1.
7. 3111.4.8.5.1 - DISCONNECTS, J-BOXES, COMBINER BOXES ORGUTTERS SHALL NOT BE PLACED IN ANY REQUIRED PATHWAYOR CUTOUT.
8. 3111.5.3.1 - TOTAL SYSTEM WEIGHT SHALL NOT EXCEED 4.5 PSF.PV MODULES AND RACKING SHALL BE DIRECTLY ATTACHED TOROOF FRAMING AS SHOWN IN PV-2. ATTACHMENT SPACING WILLBE 48" O.C. MAX, AND WHEN ATTACHMENT LOCATED WITHIN 3'OF ROOF EDGE, HIP, EAVE, RIDGE SHALL BE 24" O.C. MAX.
9. 3111.5.4 - MAX MODULE HEIGHT < 18" OFF ROOF SURFACE.
42°
FRAMING PLAN
FRAMING CROSS SECTIONSCALE: N.T.S.
PV-2
S
W
N
E
LEGEND:
MOUNTING DETAIL (SIDE)SCALE: N.T.S.
5/16"x3" LAGSCREWS WITH2 1/2" MIN.EMBEDMENT
COMP.SHINGLEROOFING
FRAMING PLANSCALE: 1/8" = 1'-0"
IRONRIDGE XR100 RAIL
SUNMODO EZR MOUNT
2X4 RAFTERS @ 24"O.C.
SUNMODO EZR MOUNTSPAN ~2FT. TO MEET
ASCE 7-10 WITH WIND
SPEED AT 110 MPH
SUNMODO EZR MOUNTSPAN ~4FT. TO MEET
ASCE 7-10 WITH WIND
SPEED AT 110 MPH
2X4 RAFTERS@ 24" O.C.
HYUNDAIHIS-S355RI
MODULE
HYUNDAI HIS-S355RIMODULE
SEE MOUNTING DETAILIRONRIDGE XR100 RAIL &
SUNMODO EZR MOUNT
2
1
42°
LOW PROFILE PROTUSION
CONTRACTOR
Contractor# Drawn by: Date:
Page:
Rev:
Ph:Ph:
System AC Size @ STC: System DC Size @ STC:
YOUR LOGO
The design reprented herein are for sample purposes only and requires review and adjustments for site specific application. These drawings are property of AVILA SOLAR and shall not be copied or used without written consent.
JUAN PEREZ RESIDENCEResidential Grid Interactive Solar Installation123 MAIN ST, ANY CITY, ST, ZIP
971-240-7102
DA PERMIT SET 6/14/2018
5 kW 6.035 kW
(17) HYUNDAI HIS-S355RI SOLAR MODULES & (17) SE P370 POWER OPTIMIZERS
(1) SOLAREDGE SE5000H-US (240)
WWW.AVILASOLAR.COMPORTLAND, OR 97007
971-240-7102
AVILA SOLAR
2X4 TRUSSES @ 24" O.C.
22'-0"
1
2
2
2
42°
9'-7
"
29'-11"
13'-3"
1'-9
"41'-9"
ROOF PLAN
PV-3
(N) SOLAREDGE SE5000H-US(240) (INTERIOR WALL)
S
W
N
E
AC DISCONNECT(EXTERIOR WALL)
SE P400 POWEROPTIMIZER
(E) METER(EXTERIOR WALL)
ROOF PLANSCALE: 1/8" = 1'-0"
HYUNDAI HIS-S355RIMODULE
12" SETBACK
NEMA 3RSOLADECK
STRING 1: 8 MODS
STRING 2: 9 MODS
(E) PANEL(INTERIOR WALL)
GARAGE
3/4" CONDUIT
CONTRACTOR
Contractor# Drawn by: Date:
Page:
Rev:
Ph:Ph:
System AC Size @ STC: System DC Size @ STC:
YOUR LOGO
The design reprented herein are for sample purposes only and requires review and adjustments for site specific application. These drawings are property of AVILA SOLAR and shall not be copied or used without written consent.
JUAN PEREZ RESIDENCEResidential Grid Interactive Solar Installation123 MAIN ST, ANY CITY, ST, ZIP
971-240-7102
DA PERMIT SET 6/14/2018
5 kW 6.035 kW
(17) HYUNDAI HIS-S355RI SOLAR MODULES & (17) SE P370 POWER OPTIMIZERS
(1) SOLAREDGE SE5000H-US (240)
WWW.AVILASOLAR.COMPORTLAND, OR 97007
971-240-7102
AVILA SOLAR
GENERAL NOTES:
1. CONDUIT IS DIAGRAMMATIC. FINAL ROUTING TO BEDETERMINED BY INSTALLER.
2. SUNEYE SHOT ON ROOF CORRESPONDS TO JUANPEREZ RESIDENCE SHADE REPORT.
XX
93
98
TO OWNER'S INTERNET
ROUTER/ CLOUD BASE
MONITORING PLATTFORM
3/4" EMT: CAT5 CABLE
(E) SERVICE:
120/240V, 1ф, 3W
M
(E) GROUNDING
ELECTRODE
(E) SERVICE PANEL
200A, 200A MCB,
120/240V, 1ф, 3W
(E) METER
(E) SERVICECONDUCTORS
(E) MAINBONDINGJUMPER
E
C
B
2P, 30A PVBACKFEEDBREAKER
N
G
O
UTILITY ACCESIBLEDISCONNECT WITHIN
10' OF UTILITY METER.30A, 240V, 2 POLES
0.75 EMT:(2) #10 AWG THWN-2 CONDUCTORS(1) #10 AWG THWN-2 NEUTRAL(1) #10 AWG THWN-2 GROUND
MP P1
D
L1L2
NEGC
A
J1
. . .
. . .PV POS (+)
INVERTER:SOLAREDGE SE5000H-US (240)99% CEC EFFICIENCY @ 240VAC5KW AC CONTINUOUS.MAX OUTPUT CURRENT 21AacMAX INPUT CURRENT 30dcGFCI PROTECTION PROVIDED PER NEC 690.35
SOLAREDGE SE5000H-US (240) AC/DC SAFETY SWITCH120/240V, 1ф, 3W, 21ac CONTINUOUS600 Vdc TO GND, OPENS ALL UNGROUNDEDCONDUCTORS PER NEC 690.35
PV NEG (-)
PV EGC
NEMA 3R SOLADECK TRANSITIONFROM PV WIRE TO THWN-2LOCATED ON ROOF.
3/4" EMT:4#10 THWN-21#10 THWN GROUND
FREE AIR:2#10 PV WIRE1#6 BARE COPPER GROUND
INTEGRATEDGROUNDING CLAMP, TYP
A
PV MODULES = HYUNDAI HIS-S355RISTRING SIZE: 8 MODULES8 MODULES = 2.84 STC
(8) SE P370 POWER OPTIMIZERRATED DC INPUT POWER - 370 WATTSMAXIMUM INPUT VOLTAGE - 60 VdcMPPT RANGE - 8-60 VdcMAXIMUM INPUT CURRENT - 13.75 AdcMAXIMUM OUTPUT CURRENT - 15 AdcRAPID SHUTDOWN COMPLIANT, TYP.
A
. . .
. . .
FREE AIR:2#10 PV WIRE1#6 BARE COPPER GROUND
PV MODULES = HYUNDAI HIS-S355RISTRING SIZE: 9 MODULES9 MODULES = 3.195 STC
(9) SE P370PV POS (+)PV NEG (-)
PV EGC
CONTRACTOR
Contractor# Drawn by: Date:
Page:
Rev:
Ph:Ph:
System AC Size @ STC: System DC Size @ STC:
YOUR LOGO
The design reprented herein are for sample purposes only and requires review and adjustments for site specific application. These drawings are property of AVILA SOLAR and shall not be copied or used without written consent.
JUAN PEREZ RESIDENCEResidential Grid Interactive Solar Installation123 MAIN ST, ANY CITY, ST, ZIP
971-240-7102
DA PERMIT SET 6/14/2018
5 kW 6.035 kW
(17) HYUNDAI HIS-S355RI SOLAR MODULES & (17) SE P370 POWER OPTIMIZERS
(1) SOLAREDGE SE5000H-US (240)
WWW.AVILASOLAR.COMPORTLAND, OR 97007
971-240-7102
AVILA SOLARSINGLE LINE DIAGRAM
PV-4
MODULE SPECIFICATIONS
MAKE AND MODEL HYUNDAI
POWER STC 355W
Imp 9.1A
Vmp 38.9V
Voc 47.3V
Isc 9.7A
ELECTRICAL NOTES:
1. THE OUTPUT VOLTAGE OF THE POWER OPTIMIZERS ARE REGULATED BY THE INVERTER.THEY ARE NOT IMPACTED BY THE NUMBER OF MODULES IN THE STRING. THECONTINUOUS CURRENT OF A SINGLE STRING IS EQUAL TO THE MAXIMUM OUTPUTCURRENT OF THE OPTIMIZER.
2. THE SOLAR EDGE INVERTER IS EQUIPPED WITH A RAPID SHUTDOWN FEATURE WHICHCONFORMS TO NEC 690.12 (2017), WHICH REQUIRES THAT A RAPID SHUTDOWN FEATUREEXISTS TO DE-ENERGIZE PV SOURCE CIRCUITS FROM ALL SOURCES TO LESS THAN 30VOLTS WITHIN 30 SECONDS.
3. UNGROUNDED SYSTEM DC CONDUCTORS SHALL BE COLOR-CODED AS FOLLOWS. DCPOSITIVE SHALL BE RED (OR MARKED RED) AND DC NEGATIVE SHALL BE BLACK (ORMARKED BLACK)
4. DC VOLTAGE RANGE OF THE ARRAY IS REGULATED BY INVERTER AND WILL BECONSTANT AT 380V. MAX DC VOLTAGE OF THE PV MODULE IS EXPECTED TO BE 52.15VAT -6.4°C (-6.4°C - 25°C) X -0.33%V/C + 47.3V = 52.15V ) WHICH IS LESS THAN SE P370POWER OPTIMIZER MAX INPUT VOLTAGE OF 60V.
5. INTEGRATED DC DISCONNECT IS PROVIDED WITH INVERTER. DISCONNECT IS LISTEDFOR USE WITH SOLAR EDGE UL 1741 LISTED STRING INVERTERS.
6. PER MANUFACTURERS RECOMMENDATIONS FOR SINGLE-PHASE 3-7.6KW INVERTERS,USE ONLY COPPER CONDUCTORS RATED FOR A MINIMUM OF 75°C/ 167°F.
MAX. DC + AC VOLTAGE DROP: 1.18%
*MAX OPTIMER OUTPUT CURRENT LIMITED TO: 15 AMPS
CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS
CIRCUIT TYPICAL CONDUCTOR CONDUIT
CURRENT-CARRYING
CONDUCTORS IN
CONDUIT
OCPD EGCTEMP. CORR.
FACTOR
CONDUIT FILL
FACTOR
CONT.
CURRENT
MAX. CURRENT
(125%)BASE
AMP.
DERATED
AMP.
TERM. TEMP.
RATINGLENGTH
VOLTAGE
DROP
PV STRING TO SOLADECK 1 10 AWG PV WIRE, CU FREE AIR 2 N/A 6 AWG BARE, COPPER 0.87 (41.9°C) 1 12.13A 15.16A 35A 30.45A 75°C 70FT 0.58%
SOLADECK TO INVERTER 1 10 AWG PV WIRE, CU0.75" DIA. PVC
404 15A 10 AWG THWN-2, CU 0.87 (41.9°C) 0.8 12.13A 15.16A 35A 24.36A 75°C 50FT 0.41%
INVERTER TO INTERCONNECTION 1 10 AWG THWN-2, CU 0.75" DIA. EMT 3 30A 10 AWG THWN-2, CU 0.96 (35°C) 1 21A 26A 35A 33.6A 75°C 10FT 0.20%
WARNING - PHOTOVOLTAIC
POWER SOURCE
LABEL EVERY 10'
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
RATED MPP CURRENT 14ARATED MPP VOLTAGE 380VMAXIMUM SYSTEM VOLTAGE 480VSHORT CIRCUIT CURRENT 30A
LOCATION: DC DISCONNECT REQUIREDBY NEC 690.53
PHOTOVOLTAIC SYSTEMDC DISCONNECT
LOCATION: MAIN AC DISCONNECTREQUIRED BY NEC 690.54
PHOTOVOLTAIC SYSTEMAC DISCONNECT
OPERATING AMPS 21AOPERATING VOLTAGE 240V
LOCATION: BUILDING MAIN SERVICE PANEL
CAUTION
POWER TO THIS BUILDING IS SUPPLIED FROM THEFOLLOWING SOURCES WITH DISCONNECTS LOCATED ASSHOWN:
ELECTRIC SHOCK HAZARDWARNING
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN
THE OPEN POSITION
O
N
A
B
C
DO NOT RELOCATETHIS OVERCURRENT
DEVICE
PV SOLAR BREAKER
LOCATION: NEXT TOSOLAR BREAKERINSIDE PANEL
DUAL POWER SUPPLY
SOURCES: UTILITY GRID ANDSOLAR PHOTOVOLTAIC SYSTEM
WARNING
REQUIRED BY: NEC 705.12(D)(3)
PLACEMENT: MAIN SERVICE PANEL
SOLAR ELECTRIC SYSTEM
DISCONNECT LOCATED IN MAIN
SERVICE PANEL
LOCATION: NEAR UTILITY METER, ON UTILITY
METER OR SOLAR PRODUCTION METER.
NOMINAL OPERATING AC VOLTAGE:NOMINAL OPERATING AC FREQUENCY:MAXIMUM AC POWER:MAXIMUM AC CURRENT:MAXIMUM OVERCURRENT PROTECTIVEDEVICE FOR AC MODULE PROTECTION:
240V60HZ5KW21A
30A
LOCATION AT POINT OF INTERCONNECTION CODE SECTION: NEC 690.53
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWNSWITCH TO THE "OFF"
POSITION TO SHUT DOWNCONDUCTORS OUTSIDE
THE ARRAY. CONDUCTORSWITHIN THE ARRAY
REMAIN ENERGIZED INSUNLIGHT.
LABEL FOR PV SYSTEMS THAT SHUT DOWN THECONDUCTORS LEAVING THE ARRAY ONLY.
SOLAR ELECTRICPV PANELS
NEC 2017 690.12, 690.56(C)(1)(b)
P1
P
M
DE
J1
88.50'
50.2
5'
77.00'
6.25'
58.7
5'
6.25'
6.50
'
7.5
0'
LABELS AND IDENTIFICATION
PV-5
PV SYSTEM ACDISCONNECT
SOLAR ARRAYS
CONTRACTOR
Contractor# Drawn by: Date:
Page:
Rev:
Ph:Ph:
System AC Size @ STC: System DC Size @ STC:
YOUR LOGO
The design reprented herein are for sample purposes only and requires review and adjustments for site specific application. These drawings are property of AVILA SOLAR and shall not be copied or used without written consent.
JUAN PEREZ RESIDENCEResidential Grid Interactive Solar Installation123 MAIN ST, ANY CITY, ST, ZIP
971-240-7102
DA PERMIT SET 6/14/2018
5 kW 6.035 kW
(17) HYUNDAI HIS-S355RI SOLAR MODULES & (17) SE P370 POWER OPTIMIZERS
(1) SOLAREDGE SE5000H-US (240)
WWW.AVILASOLAR.COMPORTLAND, OR 97007
971-240-7102
AVILA SOLAR